evans elementary school kitchen remodel · evans elementary school kitchen remodel falcon sd 49...
TRANSCRIPT
PVC POLYVINYL CHLORIDE
PAINT, PAINTEDPT
PUSH BUTTONPB
PERPENDICULARPERP
FIRE ALARM ANNUNCIATOR PANELFAAPFIRE ALARM CONTROL PANELFACP
FIRE EXTINGUISHER BRACKETFEB
CARD READERCR
CONCRETE MASONRY UNITCMU
CARD ACTUATEDCA
AUTOMATICALLY ACTUATEDAA
WOODWATER CLOSETWITHOUTWITHWIDE/WIDTH
VENDOR FURNISHED VENDOR INSTALLEDVENDOR FURNISHED OWNER INSTALLEDVENDOR FURNISHED CONTRACTOR INSTALLEDVESTIBULEVERTICALVINYL COMPOSITE TILE
UNLESS NOTED OTHERWISEUNDER CONTRACT
TYPICALTUBE STEELTOP OFTHROUGHTHICK(NESS)
TO BE DETERMINEDTACKBOARD
SUSPENDEDSTRUCTURALSTONE
STAINLESS STEEL
SQUARESPECIFICATION(S)
SIMILARSHEETSQUARE FEETSTORM DRAINSCHEDULESEALED CONCRETE
ROUGH OPENINGROOMROOM FINISH SCHEDULEREINFORCED(ING)
REVISIONREFERENCEROOF DRAIN
POLYISOCYANURATE
PLYWOODPLASTIC LAMINATEPROPERTY LINEPLATE
PARTICLE BOARDPARAPET
OPPOSITEOPENINGOVERHEADOPPOSITE HANDOWNER FURNISHED VENDOR INSTALLEDOWNER FURNISHED OWNER INSTALLEDOWNER FURNISHED CONTRACTOR INSTALLED
OUTSIDE DIAMETER (or) OVERFLOWDRAINON CENTER
NOMINALNUMBERNOT IN CONTRACT
METALMETAL STUDSMASONRY OPENINGMINIMUM
MANUFACTURE(R)
MECHANICALMEDIUM DENSITY FIBERMARKERBOARDMAXIMUMMASONRY
LONG/LENGTH
KNEE SPACEKEYBOARD
JOINT
INTERIORINSULATION, INSULATINGINCHESINSIDE DIAMETER
HEIGHTHAND RAILHORIZONTALHOLD OPENHOLLOW METAL (CUSTOM STEEL)HOSE BIBHIGH/HEIGHT
GYPSUMGYPSUM WALL BOARDGRADE, GRADINGGENERAL CONTRACTORGALVANIZEDGAUGE
FIELD VERIFYFOOTINGFEETFLOOR SINKFIBERGLASS REINFORCED PLASTICFLOORFINISHFIRE HOSE CABINETFINISH FLOORFIRE EXTINGUISHER CABINET
FIRE EXTINGUISHERFIRE DEPARTMENT CONNECTIONFLOOR DRAIN
EXTERIOREXPANSIONEXISTINGELECTRIC WATER COOLEREQUAL
ELEVATION/ELEVATOR
ELECTRIC(AL)
EXPANSION JOINT
ELECTRIC CABINET UNIT HEATER
DRAWINGDETAILDOWNSPOUTDIAMETERDOOR AND FRAME SCHEDULEDRINKING FOUNTAINDEEP/DEPTH
CARPETCONTINUOUS, CONTINUECONCRETECOLUMN
CEILINGCENTER LINECONTROL JOINTCAST IN PLACE
CORNER GUARDCONTRACTOR FURNISHED CONTRACTOR INSTALLEDCORK FLOORING
BOTTOM OFBLOCKBUILDINGBOARD
ARCHITECT(URAL)
ALUMINUMALTERNATE
ABOVE FINISHED FLOORABOVE COUNTERANCHOR BOLT
WDWCW/OW/W
VFVIVFOIVFCIVESTVERTVCT
UNOUC
TYPTSTOTHRUTHK
TBDTB
SUSPSTRUCTSTN
SSTL
SQSPEC
SIMSHTSFSDSCHSC
RORMRFSREINF
REVRERD
PIC
PLWDPLAMPLPL
PBPAR
OPPOPNGOHOHOFVIOFOIOFCIODOC
NOMNONIC
MTLMSMOMIN
MFR
MECHMDFMBMAXMAS
L
KSKB
JT
INTINSULINID
HTHRHORZHOHMHBH
GYPGWBGRGCGALVGA
FVFTGFTFSFRPFLRFINFHCFFFEC
FEFDCFD
EXTEXPEXISTEWCEQ
ELEV
ELEC
EJEIFSECUH
DWGDTLDSDIADFSDFD
CPTCONTCONCCOL
CLGCLCJCIP
CGCFCICF
BOBLKBLDGBD
ARCH
ALUMALT
AFFACAB
EXTERIOR INSUL. FINISH SYSTEM
CH CONDUCTOR HEAD
MAGNETIC HOLD OPENMHO
EACHEA
EDGE OF SLABEOS
WRITABLE SURFACEWOOD BASE
WSWDB
WALL TALKERWT
STEELSPECIAL TREATMENTST
STL
SOLID SURFACESS
SUSPENDED ACOUS. TILESAT
REFLECTED CEILING PLANRCPRUBBER BASERB
POLISHED CONCRETEPC
LINOLEUMLIN
CUSTOM STEEL (HOLLOW METAL)CSCORK / RUBBER FLOORINGCRF
CERAMIC TILECT
CHALKBOARDCB
ACRYLIC GLAZINGAG
CLOSED CIRCUIT TELEVISIONCCTV
EXISTING(E)
SECTION DETAIL
BUILDING ANDWALL SECTION
PLAN DETAIL
0
0
N 1
R @ 7 1/2"20
1 View Name1/8" = 1'-0"A101
A2S
?
H1
A101
1SIM
3/32" HIGH ARIAL TEXT
1i1'-0"
No.12"12"
NEW COLUMNCENTER LINE
EXISTINGCOLUMNCENTER LINE
PARTITION TYPE
DIMENSION STYLE
STANDARDNOTE TEXT
ELEVATION LEVEL
KEYNOTE
WINDOW TAGS
101A
DOOR DESIGNATION
REVISION TAG
STAIR TAG
ROOM NAME
100
150 SF
ROOM DESIGNATION
WF
BF
FF
PLAN / DETAIL TAG
2
CEILING TAG
NORTH ARROW
FINISH TAG CASEWORK TAG
Detail Number
Sheet Number
Detail Number
Sheet Number
Detail Number
Sheet Number
Room Name
Room Number
Room SF IF SHOWN
Room Number
HOLLOW
METAL
Revision Number
View Number
Sheet Number
View Name
SPOT ELEVATION .100'-0"
SPOT COORDINATE
N - 200'-0"E - 400'-0"100'-0"
A101EXTERIOR ELEVATION
Detail Number
Sheet Number
1
A101INTERIOR ELEVATION
Detail Number
Sheet Number
A
C
D B
0' 4' 8' 16' 32'
SCALE: 1/8" = 1'-0"
BASED ON PRODUCT #
WIDTH
DEPTH
N
GRAPHIC SCALE
CURTAIN
WALL
STOREFRONT
C1 S1
WALL FINISH
BASE FINISH
FLOOR FINISH
?Toilet Accessory Tag GB2
1i
GLAZING
PANEL
ASSEMBLY TAGA1
A101
1SIM
A101
1SIM
NORTH
PO
WE
RS
BLV
D
PALMER PARK BLVD
PE
TR
SO
N R
OA
D
WIN
NE
BA
GO
RD
PROJECT SITE1675 WINNEBAGO ROADCOLORADO SPRINGS, CO
VICINITY MAP
1. VERIFY ROUGH-IN DIMENSIONS OF ALL EQUIPMENT WITH MANUFACTURES OR OWNER IF REUSED.
2. ANY DISCREPANCIES IN THE DOCUMENTS OR BETWEEN THE SITE CONDITIONS AND THE DOCUMENTS SHALL BE BROUGHT TO THE IMMEDIATE ATTENTION OF THE ARCHITECT/ ENGINEER.
3. IT IS THE INTENT OF THE CONTRACT DOCUMENTS THAT ALL SYSTEMS (WALL ASSEMBLIES, DOORS, HARDWARE, FINISHES, PLUMBING SYSTEMS, MECHANICAL SYSTEMS, ELECTRICAL SYSTEMS, ETC.) BE COMPLETE TO PROVIDE A REASONABLE EXPECTEDPERFORMANCE AND USE. THE CONTRACTOR AND THE SUBCONTRACTORS SHALL PROVIDE ALLINCIDENTAL ITEMS AND PARTS NECESSARY TO ACHIEVE THIS INTENDED REQUIREMENT WHETHERSHOWN IN THE CONSTRUCTION DOCUMENTS OR NOT.
4. THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE PROPER DISPOSAL AND REMOVAL OF ALL TRASH, DEBRIS AND SURPLUS MATERIAL GENERATED AS A RESULT OF THEWORK.
5. CONTRACTOR SHALL COORDINATE ANY AND ALL UTILITY INTERRUPTIONS WITH OWNER PRIOR TO SHUT DOWN OF ELECTRICAL, WATER, TELEPHONE, FIRE PROTECTION, FIRE DETECTION, ETC.
6. DO NOT SCALE THE DRAWINGS. FIELD VERIFY ALL EXISTING CONDITIONS PRIOR TO STARTING THE WORK.
7. PROVIDE ADEQUATE DUST, SIGHT AND SAFETY BARRIERS BETWEEN THE WORK ANDOTHER AREAS
8. COORDINATE ANY CONSTRUCTION ACTIVITIES IN ADJACENT OCCUPIED SPACES WITH THEOWNER PRIOR TO COMMENCEMENT OF WORK.
9. THE CONTRACTOR SHALL MAINTAIN ALL EXISTING EXIT WAYS AND SHALL NOT BLOCK EXIT PATHS. IF AN EXIT PATH MUST BE BLOCKED, AN ALTERNATE MEANS OFEGRESS SHALL BE PROVIDED AS APPROVED BY THE OWNER AND LOCAL AUTHORITIES HAVING JURISDICTION OVER THE PROJECT.
10. DRAWINGS AND SPECIFICATIONS ARE COMLEMENTARY AND OF EQUAL WEIGHT. REFER TOOUTLINE SPECIFICATIONS WITHIN EACH DISCIPLINE DRAWING PAGES, IN ADDITION TODRAWINGS FOR FULL SCOPE OF WORK AND CONTRACT REQIIREMENTS. NOTIFY ARCHITECTARCHITECT OF ANY DISCREPENCIES PRIOR TO COMMENCEMENT ANY OF WORK.
11. LOCATE ALL EXISTING UNDERGROUND UTILITIES, INTERIOR AND EXTERIOR, PRIOR TOCOMMENCING WORK.
SCALE:
PROJECT NUMBER: 1601
DATE:
REVISION:
ISSUED FOR: CONSTRUCTION
EV
AN
S E
LE
ME
NT
AR
Y S
CH
OO
L
KIT
CH
EN
RE
MO
DE
L
FALCON SD 49 10850 EAST WOODMEN ROAD FALCON, CO 80831
GALLETTA ARCHITECTURE
2012 NORTH TEJON STREETCOLORADO SPRINGS, CO 80907P: 719.632.7675.E: [email protected]
As indicated
3/2
5/2
016 1
0:0
9:2
9 A
M
1-A0.1
TITLE SHEET
01-MARCH-2016
EVANS ELEMENTARY SCHOOL KITCHEN REMODEL
FALCON SCHOOL DISTRICT 49
CONSTRUCTION : MARCH 1, 2016
Sheet List
SheetNumber Sheet Name
1-A0.1 TITLE SHEET
1-A0.2 CODE ANALYSIS
1-A0.3 SPECIFICATIONS
1-A0.4 SPECIFICATIONS
1-A1.1 KITCHEN DEMOLITION PLANS
1-A2.1 KITCHEN PLANS
2-M1.0 GENERAL INFORMATION
2-M2.0 SPECIFICATIONS
2-M3.0 MECHANICAL PLANS
2-P1.0 GENERAL INFORMATION
2-P2.0 PLUMBING SPECIFICATIONS
2-P3.0 PLUMBING PLANS
3-E1.0 GENERAL INFORMATION
3-E2.0 SPECIFICATIONS
3-E3.0 ELECTRICAL SCHEDULES
3-E4.0 POWER PLANS
3-E5.0 LIGHTING PLANS
4-FS01 KITCHEN EQUIPMENT & PLUMBING PLANS
4-FS02 KITCHEN ELECTRICAL & BUILDING COND.
4-FS03 KITCHEN EXHAUST HOOD
12" = 1'-0"
VICINITY MAP
ARCHITECTURAL ABBREVIATIONS
ARCHITECTURAL DRAWING SYMBOLS
GENERAL NOTES
03-21-16
1
1
WH
CODE REVIEW
PROJECT SUMMARY:
EXISTING KITCHEN EQUIPMENT REPLACEMENT/RECONFIGURATION, INCLUDING EXHAUST AND CONDENSATEHOODS. NEW RESINOUS FLOOR SYSTEM. ALTERNATE TOREPLACE EXISTING LIGHT FIXTURES TO LED.NO CHANGES TO EXISTING PARTITION WALLS, DOORS OREGRESS PATTERN, NO INCREASE IN OCCUPANCY LOAD.
GOVERNING CODES
2015 International Building Code2015 International Energy Conservation Code2015 Mechanical Code2015 Plumbing Code2014 National Electric Code2015 Fire Code
OCCUPANCY
EDUCATIONAL GROUP E, PRIMARY WITHASSEMBLY GROUP A AND BUSINESS GROUP B
CONSTRUCTION TYPE
TYPE IIB (ASSUMED)
GENERAL BUILDING HEIGHTS AND AREAS
Allowable Building Height/ Stories: 55 feet/ 2 storiesActual Building Height: 27 feet @ 2 story addition
Allowable Area Factor:E Occupancy: 14,500 GSF per floorA Occupancy: 9,500 GSF per floorB Occupancy: 23,000 GSF per floor
Actual Area:
Main Level: 45,382 GSFLower Level: 6,272 GSFTotal Area: 51,654 GSF
FIRE RESISTANCE RATINGS - BUILDING ELEMENTS
Structural frame 0 hoursExterior bearing walls 0 hoursInterior bearing walls 0 hoursExterior non-bearing walls 0 hoursNon-bearing walls 0 hoursShafts 0 hoursFloors/ceiling 0 hoursRoofs/ceiling 0 hours
FIRE PROTECTION SYSTEM
BUILDING IN NON-SPRINKLERED THROUGHOUT
MEANS OF EGRESS
Exit Requirements4 per floor (more than 1000 occupants)Exits Provided:Main Level: 7Lower Level: 1
OCCUPANCY COUNT
First Level: 1,760Lower Level: 156Total Occupants: 1,916
1
ST-1 ST-2
CLASSROOM WINGOCCUPANCY: EDUCATIONAL (E)OCCUPANT LOAD: 375
CAFETERIAA= 2643 SFOCCUPANCY: ASSEMBLY (A-2)OCCUPANCY LOAD: 177
GYM ADDITIONA= 3,586 SFOCCUPANCY: ASSEMBLY (A-3)OCCUPANCY LOAD: 242
2- STORY CLASSROOM ADDITIONOCCUPANCY: EDUCATIONAL (E)OCCUPANT LOAD: 192
EXISTING KITCHENA= 744 SFPROJECT WORK AREA
FIRE AREAA= 8,449 SF
FIRE AREAA= 10,850 SF
FIRE AREAA= 13,913 SF
FIRE AREAA= 6,272 SF
CLASSROOM WINGOCCUPANCY: EDUCATIONAL (E)OCCUPANT LOAD: 532
A= 744 SFOCCUPANCY: BUSINESS (B)OCCUPANT LOAD: 15
CLASSROOM/ ADMIN. WINGOCCUPANCY: EDUCATIONAL (E),BUSINESS (B)OCCUPANCY LOAD: 227
FIRE AREAA= 5,866 SF
SCALE:
PROJECT NUMBER: 1601
DATE:
REVISION:
ISSUED FOR: CONSTRUCTION
EV
AN
S E
LE
ME
NT
AR
Y S
CH
OO
L
KIT
CH
EN
RE
MO
DE
L
FALCON SD 49 10850 EAST WOODMEN ROAD FALCON, CO 80831
GALLETTA ARCHITECTURE
2012 NORTH TEJON STREETCOLORADO SPRINGS, CO 80907P: 719.632.7675.E: [email protected]
As indicated
3/2
5/2
016 1
0:0
9:2
9 A
M
1-A0.2
CODE ANALYSIS
01-MARCH-2016
1" = 30'-0"1-A0.2
1 CODE PLAN
ASSUMED 2-HOUR FIRE BARRIER
POINT OF EGRESS
03-21-161
WH
SD
F
ELECTPANEL
FEC
HOTHOLDING
OVEN/GRILL
CONVECTIONOVEN
WORKTABLE
OFFICE
05
TLT
04
DISHWASH
02
WALK-IN
07
WALK-IN
08
CAFETERIA
06
STOR.
03
RACK
RACK RACK
B/I SHELVING
MILKCOOLER
POS CART
KITCHEN
01
FA
FA
STOR
MW
1.02
1.01
X
X
X
XX
X
X
X
X
X X X
1.02
1.051.06 1.02
1.09
EXISTING GAS METER
EXISTING STORMWATER INLET
EXISTINGBOLLARDS, TY.P OF 3
EXISTINGGREASE TRAPACCESS
EXISTINGCHAIN-LINKFENCE
1.12
1.13
EXISTINGDOWN SPOUT
1.10
1.14
1.03
1.04
1.07
1.11
1.01
1.01
1.01
1.01
EXISTINGGAS LINE, VIF
1.02
1.07
MIXER
DW
SOLID DISHTABLE
CLEAN DISHTABLE
GARBAGEDISPOSAL
EXISTINGFLOOR DRAIN
EXISTINGFLOOR DRAIN
SLICER
3- COMPARTMENT SINK
1.14
1.14
1.14
1.14
1.14
1.02
1.14
1.021.02
EXISTING GWB &MTL STUD WALL,FV
1
CUH
EXHAUSTHOOD
CONDENSATEHOOD
HOOD CONTROLS
1.08
1.08
WALL MOUNTEDSTROBE (E)
CABINET UNITHEATER (E)
S
1.03
1.04
1.15
1.15
1. THE DRAWINGS ARE DIAGRAMATIC AND MAY NOT SHOW ALLDEMOLITION THAT IS REQUIRED. THE CONTRACTOR MUST VISIT THE SITE TODOCUMENT ALL SITE CONDITIONS AND DETERMINE THE EXTENT OFDEMOLITION THAT WILL BE REQUIRED TO CONSTRUCT THE PROJECT AS IT ISDOCUMENTED. ALL FIXTURES THAT CAN BE REUSED AND ARE NOT REQUIREDFOR THE PROJECT SHALL BE RENDERED TO THE OWNER.
2. DISCONNECT EXISTING EQUIPMENT WHICH IS TO BE REMOVED.PROTECT EXISTING EQUIPMENT WHICH IS TO REMAIN IN PLACE. INCLUDE FORREMOVEAL AND REINSTALLATION ALL EXISING FLOOR MOUNTED EQUIPMENTAND OTHER EQUIPMENT AS IDENTIFIED. THE OWNER MAY ELECT TO HAVE THEEXISTING FLOOR MOUNTED EQUIPMENT REMOVED AND REINSTALLED BY THETHE ABATEMENT CONTRACTOR. COORDINATE DIRECTLY WITH OWNER.
3. REFER TO MECHANICAL, ELECTRICAL AND PLUMBING DRAWINGS FORADDITIONAL DEMOLITION INFORMATION. THE CONTRACTOR IS RESPONSIBLEFOR THE REMOVAL OF ALL SUPPORTS, ACCESSORIES AND CONVEYANCESRELATED TO EQUIPMENT AND FIXTURES SHOWN TO BE REMOVED.
4. THE ARCHITECT ASSUMES NO RESPONSIBILITY FOR THE DETECTIONOR REMOVAL OF ANY HAZARDOUS MATERIAL, INCLUDING BUT NOT LIMITED TOASBESTOS. PARTIES RESPONSIBLE FOR DEMOLITION SHALL NOTIFY THEOWNER IMMEDIATELY OF ANY SUSPECTED MATERIALS.
DEMOLITION NOTES
SCALE:
PROJECT NUMBER: 1601
DATE:
REVISION:
ISSUED FOR: CONSTRUCTION
EV
AN
S E
LE
ME
NT
AR
Y S
CH
OO
L
KIT
CH
EN
RE
MO
DE
L
FALCON SD 49 10850 EAST WOODMEN ROAD FALCON, CO 80831
GALLETTA ARCHITECTURE
2012 NORTH TEJON STREETCOLORADO SPRINGS, CO 80907P: 719.632.7675.E: [email protected]
As indicated
3/2
5/2
016 1
0:0
9:2
9 A
M
1-A1.1
KITCHENDEMOLITION
PLANS
01-MARCH-2016
1/4" = 1'-0"1-A1.1
1 DEMOLITION PLAN 1/4" = 1'-0"1-A1.1
2 DEMOLITION REFLECTED CEILING PLAN
KEYNOTE LEGEND
KEYVALUE KEYNOTE TEXT
1.01 EXISTING VCT AND BASE REMOVAL BY OTHERS, TYP.
1.02 REMOVE/ REINSTALL EXISTING KITCHEN EQUIPMENT
1.03 REMOVE EXISTING EXHAUST HOOD
1.04 REMOVE EXISTING CONDENSATE HOOD
1.05 REMOVE/ REINSTALL EXISTING HOT WATER HEATER
1.06 REMOVE/ REINSTALL EXISTING TOILET
1.07 REMOVE PORTION OF CONCRETE SLAB FOR NEW DRAINLINE
1.08 REMOVE/REINSTALL PORTION OF EXISTING CEILING TILEAND GRID
1.09 REMOVE EXISTING FRP, FULL HEIGHT
1.10 REMOVE BOTTOM 4 INCHES OF FRP PANEL FOR NEWCOVE BASE.TRIM EDGE
1.11 REMOVE EXISTING SCREEN DOOR
1.12 REMOVE PORTION OF EXISTING ASPHALT PAVEMENT FORNEW DRAIN LINE
1.13 REMOVE PORTION OF EXISTING CONCRETE PAVEMENT
1.14 REMOVE EXISTING EQUIPMENT. RETURN TO OWNER ORDISCARD
1.15 REMOVE/ REINSTALL EXISTING LIGHT FIXTURES. RE:ALTERNATE NO. 1
2.01 NEW KITCHEN EQUIPMENT INSTALLATION BY KEC.COORDINATE HOOK-UP
2.02 RESINOUS FLOOR FINISH SYSTEM
2.03 NEW CONCRETE SLAB MATCH/FLUSH WITH EXISTING
2.04 NEW FLOOR SINK. ROUTE DRAIN LINE TO GREASE TRAP
2.05 EXISTING/ REINSTALLED KITCHEN EQUIPMENT BYGENERAL CONTRACTOR.
2.06 NEW WALL MOUNTED SINK. CONNECT TO EXISTINGSANITARY LINE
2.07 NEW FRP WALL PANEL TOP OF BASE TO CEILING
2.08 NEW WALL MOUNTED SHELVING BY KEC. PROVIDEBLOCKING AS REQUIRED
2.09 NEW CONCRETE PAVEMENT.SLOPE TO STORM INLET
2.10 NEW ASHPHALT PAVEMENT PATCH
2.11 VERIFY DEPTH OF FOUNDATION WALL. CORE DRILL 6INCH DIAMETER HOLE
2.12 SEAL DRAIN LINE PENETRATION WITH EXPANDING FOAMINSULATION, BACKERROD AND SEALANT.
2.13 STAINLESS STEEL WALL FLASHING AND CORNERGURARDS BY KEC.
3.01 NEW EXHAUST HOOD TO REPLACE EXISING
3.02 NEW CONDENSATE HOOD TO REPLACE EXISTING
3.03 REUSE EXISTING CEILING TILE AND TRACK
3.04 REINSTALL EXISTING LIGHT FIXTURE IN SAME LOCATION
3.05 REINSTALL EXISTING SMOKE ALARM IN SAME LOCATION
3.06 NEW EXIT LIGHT TO REPLACE EXISTING
3.07 RELOCATE EXISTING LIGHT FIXTURE IN GRID
3.08 ALTERNATE #1: REPLACE LIGHT FIXTURES
03-21-161
SCALE:
PROJECT NUMBER: 1601
DATE:
Sheet Name
01 MARCH, 2016
AS NOTED
REVISION:
ISSUED FOR: CONSTRUCTION
EV
AN
S E
LE
ME
NT
AR
Y S
CH
OO
L
KIT
CH
EN
RE
MO
DE
L
GALLETTA ARCHITECTURE
2012 NORTH TEJON STREETCOLORADO SPRINGS, CO 80907P: 719.632.7675.E: [email protected]
3/21/16
ARVADA OFFICE COLORADO SPRINGS OFFICE
10807 NEW ALLEGIANCE DRIVE
SUITE 400
COLORADO SPRINGS, CO 80921
719.533.1112
5420 WARD ROAD
SUITE 200
ARVADA, CO 80002
303.422.7400
CONTACT LIST
PROJECT ENGINEER
GREG [email protected]
PROJECT MANAGER
PAUL [email protected]
PROJECT NARRATIVE
M1
GENERALINFORMATION
EXISTING
4"
BEVELED TAP OFF OF TOP
H
T
VCP
TYP
(E)
(R)
(N)
DIA, D
C
EL.
CI
CL
AFF
AP
FIRE DEPARTMENT CONNECTION
MANUAL VOLUME DAMPER
MOTORIZED DAMPER
MVD
MD
MIXED AIR
INVERT ELEVATION
MA
I.E.
FDC
EA OUTSIDE AIR
SUPPLY AIR
RETURN AIR
NIC
RA
SA
NORMALLY OPEN
NOT IN CONTRACT
NORMALLY CLOSED
OA
NC
NO
ROUND DUCT UP (1.5D ELBOW)
AIR FLOW - SUPPLY
AIR FLOW DIRECTION
RELOCATED
VITRIFIED CLAY PIPE
NEW
EXISTING
TYPICAL
UNIT MOUNTED THERMOSTAT
HUMIDISTAT
TRANSFER DUCT & GRILLES
M
BD
T
VANED ELBOW
LINEAR SLOT DIFFUSER
VANED ELBOW
RADIUS ELBOW; 1 DIAMETER
DOUBLE VANED ELBOW
WALL MOUNTED THERMOSTATN - INDICATES NIGHTS - INDICATES SENSOR
FLEXIBLE DUCT CONNECTION
MOTORIZED DAMPER MOTOR
MANUAL VOLUME DAMPER
FLEXIBLE DUCT
DOOR UNDERCUT
ACCESS PANEL
BACK DRAFT DAMPER
SUPPLY AIR DIFFUSER
RADIUS ELBOW
F
TCOAD
TCEAD
VENT THROUGH ROOFVTR
S
FS
RETURN DUCT UP
SUPPLY DUCT UP
EXHAUST DUCT UP
F
AIR FLOW DIRECTION ARROW
FLOW SWITCH
FLOW TRANSMITTER
FS
FT
H HUMIDITY SENSOR
PDT
PI
PDS
PRESSURE DIFFERENTIALTRANSMITTER
POSITION INDICATOR
PRESSUREDIFFERENTIAL SWITCH
PSL PRESSURE SWITCH LOW
PSH PRESSURE SWITCH HIGH
TSH
TSL TEMPERATURE SWITCH LOW
TEMPERATURE SWITCH HIGH
T TEMPERATURE SENSOR
MANUAL SWITCH
P PRESSURE SENSOR
S
SP STATIC PRESSURE SENSOR
SENSOR
CO CARBON MONOXIDE
N
AQUASTAT
PRESSURE SWITCH
PRESSURE INDICATOR
PS
INDICATOR LIGHT
(F) FUTURE
ROUND DUCT DOWN (1.5D ELBOW)
RETURN DUCT DOWN(MITERED ELBOW)
EXHAUST DUCT DOWN(MITERED ELBOW)
SUPPLY DUCT DOWN(MITERED ELBOW)
BOD
BOP
UNO UNLESS NOTED OTHERWISE
UNIT HEATER
EXHAUST FAN ON ROOF
BASEBOARD HEATER
SOUND ATTENUATOR
ABOVE FINISHED FLOOR
ACCESS PANEL
BOTTOM OF DUCT
BOTTOM OF PIPE
COMMON
CAST IRON
CENTER LINE ELEVATION
DIAMETER
EXHAUST AIR
ROUND 90° CONICAL TAKE OFFFROM RECTANGLE TRUNK
RECTANGULAR 90° TAKEOFFFROM RECTANGULAR TRUNK
RECTANGULAR 90° TAKEOFFON END OF MAIN W/MIN. 12"AIR CUSHION DOWNSTREAM ROUND 90° CONICAL TAKEOFF
FROM RECTANGULAR TRUNK W/MANUAL VOLUME DAMPER
ROUND 90° SPIN-IN TAKEOFFFROM RECTANGULAR TRUNKW/MANUAL VOLUME DAMPER
DUCT TRANSITION CONCENTRIC
DUCT TRANSITION ECCENTRIC
SIDE TAKEOFF ATREGISTER OR GRILLE
BOTTOM TAKEOFF ATDIFFUSER. PROVIDE TYPICALPROJECT BALANCING
SIDE TAKEOFF AT DIFFUSER
RECTANGULAR 90° TAKEOFFWITH BEVELED TAP
ROUND DUCT DROP/RISE IN PLAN
RECTANGLE DUCTDROP/RISE IN PLAN
DIRECTION OF VIEW
DRAWN ON THIS SHEET
BOX ##__
A PICTURE DESIGNATION
NEW
LIGHT LINE WEIGHT FOREQUIPMENT, PIPING, SYMBOLS,TEXT, ETC. INDICATESEXISTING CONDITIONS WITHNEW WORK SHOWN AS DARK
HEATING COIL
CONTROL/COILACCESS
INDICATESSUPPLYAND RETURNPIPING TO UNIT
EQUIPMENTTERMINALOR VAV BOX
CFM
GPM
TB-103
650
1.2
POINT OFCONNECTION NEWTO EXISTING
DUCT SMOKE DETECTORS
OPPOSED BLADE DAMPER
PARALLEL BLADE DAMPER
VFD
MS MOTOR STARTER
VARIABLE FREQUENCY DRIVE
DM DAMPER ACTUATOR
H HUMIDIFIER
CS CURRENT SENSOR
HORNH
FLOW SWITCHFS
DIRECTION OF CUT
SECTION DESIGNATION
TCRAD
RETURN OREXHAUSTREGISTER/GRILLE
UNSHADED AREAS INDICATEDIRECTION OF AIR FLOW (IF NOSHADING, 4-WAY ORADJUSTABLE)
ROUND DUCT TAKE OFFFROM TOP OF DUCT
BURIED,UNDERFLOOR ORUNDER DUCT
AIR FLOW -RETURNOR EXHAUST
TEMPERATURE CONTROLEXHAUST AIR DAMPER
TEMPERATURE CONTROLOUTSIDE AIR DAMPER
TEMPERATURE CONTROLRETURN AIR DAMPER
EQUIPMENT TYPE
FLOOR #__IF MULTIPLE
TRANSITIONTOSIZE ON PLANS
CONTROLENCLOSURE
FIRE/SMOKE DAMPER(# REFERS TO SCHEDULE)
FIRE DAMPER
SMOKE DAMPER
CEILING AIR DEVICEWITH FIRE DAMPER
R
DR
D
CO CARBON DIOXIDE
ALL SYMBOLS IN LEGEND MAY NOT NECESSARILY BE USED ON THIS PROJECT
4"
ABBREVIATIONS AND DESCRIPTIONS
ALL SYMBOLS IN LEGEND MAY NOT NECESSARILY BE USED ON THIS PROJECT
SHEET METAL FITTINGS AND EQUIPMENT
MECHANICAL GENERAL NOTES (CONT.)MECHANICAL GENERAL NOTES
MECHANICAL DRAWING LIST
Sheet Number Sheet Title
M1 GENERAL INFORMATION
M2 MECHANICAL SPECIFICATION
M3 MECHANICAL PLANS
MECHANICAL LEGEND
CONTROLS DEVICES
SCREENING INDICATESEXISTING TO BE REMOVED
EXISTING TO BE REMOVED
SCALE:
PROJECT NUMBER: 1601
DATE:
Sheet Name
01 MARCH, 2016
AS NOTED
REVISION:
ISSUED FOR: CONSTRUCTION
EV
AN
S E
LE
ME
NT
AR
Y S
CH
OO
L
KIT
CH
EN
RE
MO
DE
L
GALLETTA ARCHITECTURE
2012 NORTH TEJON STREETCOLORADO SPRINGS, CO 80907P: 719.632.7675.E: [email protected]
3/21/16
M2
MECHANICALSPECIFICATION
OFFICE
05
TLT
04
DISHWASH
02
WALK-IN
-
WALK-IN
-
CAFTE
06
PE STORAGE
-
FIELD STORAGE
-
STOR.
03
KITCHEN
01
OFFICE
05
TLT
04
DISHWASH
02
WALK-IN
-
WALK-IN
-
CAFTER
06
PE STORAGE
-
FIELD STORAGE
-
STOR.
03
KITCHEN
01
SCALE:
PROJECT NUMBER: 1601
DATE:
Sheet Name
01 MARCH, 2016
AS NOTED
REVISION:
ISSUED FOR: CONSTRUCTION
EV
AN
S E
LE
ME
NT
AR
Y S
CH
OO
L
KIT
CH
EN
RE
MO
DE
L
GALLETTA ARCHITECTURE
2012 NORTH TEJON STREETCOLORADO SPRINGS, CO 80907P: 719.632.7675.E: [email protected]
3/21/16
M3
MECHANICALPLANS
SCALE:
PROJECT NUMBER: 1601
DATE:
Sheet Name
01 MARCH, 2016
AS NOTED
REVISION:
ISSUED FOR: CONSTRUCTION
EV
AN
S E
LE
ME
NT
AR
Y S
CH
OO
L
KIT
CH
EN
RE
MO
DE
L
GALLETTA ARCHITECTURE
2012 NORTH TEJON STREETCOLORADO SPRINGS, CO 80907P: 719.632.7675.E: [email protected]
3/21/16
P1
GENERALINFORMATION
ARVADA OFFICE COLORADO SPRINGS OFFICE
10807 NEW ALLEGIANCE DRIVE
SUITE 400
COLORADO SPRINGS, CO 80921
719.533.1112
5420 WARD ROAD
SUITE 200
ARVADA, CO 80002
303.422.7400
CONTACT LIST
PROJECT ENGINEER
GREG [email protected]
PROJECT MANAGER
PAUL [email protected]
PROJECT NARRATIVE
PLUMBING GENERAL NOTES
EXISTING
4"
GW
IW
OD
GREASE WASTE
INDIRECT WASTE
SD
OD
SD
HOT WATER CIRCULATING
SANITARY VENT (V)
ABOVE GRADE OR FLOOR
SANITARY WASTE
HOT WATER (HW)
COLD WATER (CW)
NATURAL GAS
LP
EQUIPMENT DRAIN
PUMPED CONDENSATEPC
D
PUMP DISCHARGE
COMPRESSED AIR
LIQUIFIED PETROLEUM GAS
PD
CA
G
BDSANITARY (BUILDING DRAIN)
BELOW GRADE
NON-POTABLE WATERNP(HWC)
TEMPERED WATERTW
S/O
W
SHW SOFT HOT WATER
SCW SOFT COLD WATER
SOLAR COLLECTOR SUPPLYSCS
SOLAR COLLECTOR RETURNSCR
FSP
DFSP
ASD
TAMPER SWITCH
OUTSIDE LIGHT AND HORN
T
T
WATER FLOW SWITCH
DRY PIPE VALVE
PRESSURE SWITCH
T
POST INDICATOR VALVE
T
FIRE HOSE RACK SIDEWALL SPRINKLER HEAD
EXISTING SPRINKLER HEAD
NEW SPRINKLER HEAD
E
FIRE SPRINKLER
FIRE STANDPIPE
DRY FIRE STANDPIPE
SP
F FIRE
PUBLIC WATER MAINW
FLOOR DRAIN
ROOF DRAIN
OVERFLOW ROOF DRAIN
DOWNSPOUT NOZZLE
CLEANOUT, WALL (WCO)
CLEANOUT PLUG (LCO)
TEMPERATURE GAUGE
METER (GAS OR WATER)
TEE DOWN
ELBOW DOWN
TEE UP
BRANCH-BOTTOM CONNECTION
GATE VALVE IN VERTICAL
BRANCH-TOP CONNECTION
RISE OR DROP
ELBOW UP
UNION
P-TRAP
PIPE CAP OR PLUG
SHOWER HEAD
PIPE ALIGNMENT GUIDE
PIPE ANCHOR
STRAINER
FLEXIBLE CONNECTION
STRAINER W/BLOWOFF VALVE
EXPANSION JOINT
BACKFLOW PREVENTER
WATER HAMMERARRESTER W/ BALL VALVE
BFP
VALVE IN YARD BOX
VACUUM BREAKER
AQUASTAT
PRESSURE SWITCH
PRESSURE INDICATOR
WELL
FLOW SWITCH
GAUGE COCK
PRESSURE REDUCING VALVE
PRESSURE/TEMPERATURE TAP
GAS PRESSURE REGULATOR
AUTOMATIC AIR VENT
PRESSURE GAUGE
GLOBE VALVE
CHECK VALVE
GAS COCK
BUTTERFLY VALVE
CIRCUIT SETTER
BALL VALVE
PLUG VALVE
GATE VALVE
SOLENOID VALVE
CALIBRATED BALANCE VALVE
MANUAL AIR VENT
DIA, D DIAMETER
EL.
C
LC
CI
AP
AFF
CENTER LINE ELEVATION
ABOVE FINISHED FLOOR
ACCESS PANEL
COMMON
CAST IRON
INVERT ELEVATIONI.E.
NC
NO
NIC
VITRIFIED CLAY PIPE
NORMALLY CLOSED
NOT IN CONTRACT
NORMALLY OPEN
TYPICALTYP
VCP
VENT THROUGH ROOFVTR
THERMOSTATIC MIXING VALVE
(E)
(R)
(N)
RELOCATED
NEW
EXISTING
(F) FUTURE
DIRECTION OF VIEW
PICTURE DESIGNATION
NEW
LIGHT LINE WEIGHT FOREQUIPMENT, PIPING, SYMBOLS,TEXT, ETC. INDICATESEXISTING CONDITIONS WITHNEW WORK SHOWN AS DARK
POINT OF CONNECTIONNEW TO EXISTING
DASHED INDICATESEXISTING TO BE REMOVED
STORM/RAINWATER DRAINABOVE FLOOR OR GRADE
STORM/RAINWATER DRAINBELOW FLOOR OR GRADE
OVERFLOW DRAIN ABOVEFLOOR OR GRADE
OVERFLOW DRAIN BELOWFLOOR OR GRADE
PIPING TO SAND/OILINTERCEPTOR BELOWFLOOR OR GRADE
OUTSIDE SCREW & YOKEVALVE (RISING STEM)
FREE STANDING FIREDEPARTMENT CONNECTION
ALARM CHECK VALVE(HORIZONTAL OR VERTICAL)
NON-INDICATING VALVE(NON-RISING STEM)
FIRE DEPARTMENTCONNECTION
ANGLE VALVE (FIREHOSE VALVE)
ANGLE DRAIN VALVEAND SIGHT GLASS
BUTTERFLY VALVEW/ TAMPER SWITCH
SUCTION MAIN ORFIRE LINE LEAD-IN
AUTOMATIC FIRESPRINKLER SYSTEM DRAIN
FIRE HOSE VALVE CABINET(SURFACE MOUNTED)
FIRE HOSE VALVECABINET (RECESSED)
FIRE STANDPIPEDESIGNATION
FIRE SPRINKLER RISERDESIGNATION
DELUGE VALVE ORPREACTION VALVE
HOSE END BALL VALVEWITH VACUUM BREAKER
TEMPERATURE/PRESSURERELIEF VALVE
STEAM TRAP(INDICATE TYPE)
CLEANOUT, FLOOR (FCO)OR GRADE (GCO)
FLOOR SINK; (1/2"GRATE SHOWN)
WALL HYDRANT WITHVACUUM BREAKER
HOSE BIBB WITHVACUUM BREAKER
4"
DRAWN ON THIS SHEET
DIRECTION OF CUT
SECTION DESIGNATION
A
XX
F
XX
SP
ABBREVIATIONS AND DESCRIPTIONS
ALL SYMBOLS IN LEGEND MAY NOT NECESSARILY BE USED ON THIS PROJECT
VALVES AND FITTINGS
FIRE PROTECTION
PS
PLUMBING DRAWING LIST
Sheet Number Sheet Title
P1 GENERAL INFORMATION
P2 PLUMBING SPECIFICATION
P3 PLUMBING PLANS
PLUMBING LEGEND
SCALE:
PROJECT NUMBER: 1601
DATE:
Sheet Name
01 MARCH, 2016
AS NOTED
REVISION:
ISSUED FOR: CONSTRUCTION
EV
AN
S E
LE
ME
NT
AR
Y S
CH
OO
L
KIT
CH
EN
RE
MO
DE
L
GALLETTA ARCHITECTURE
2012 NORTH TEJON STREETCOLORADO SPRINGS, CO 80907P: 719.632.7675.E: [email protected]
3/21/16
P2
PLUMBINGSPECIFICATION
OFFICE
05
TLT
04
DISHWASH
02
WALK-IN
-
WALK-IN
-
CAFTERIA
06
PE STORAGE
-
FIELD STORAGE
-
STOR.
03
KITCHEN
01
OFFICE
05
TLT
04
DISHWASH
02
WALK-IN
-
WALK-IN
-
CAFTERIA
06
PE STORAGE
-
FIELD STORAGE
-
STOR.
03
KITCHEN
01
SCALE:
PROJECT NUMBER: 1601
DATE:
Sheet Name
01 MARCH, 2016
AS NOTED
REVISION:
ISSUED FOR: CONSTRUCTION
EV
AN
S E
LE
ME
NT
AR
Y S
CH
OO
L
KIT
CH
EN
RE
MO
DE
L
GALLETTA ARCHITECTURE
2012 NORTH TEJON STREETCOLORADO SPRINGS, CO 80907P: 719.632.7675.E: [email protected]
3/21/16
P3
PLUMBINGPLANS
GENERAL CONTRACTOR NOTES
NOTE: ROUGH-IN INFORMATION SHOWN IS
FOR NEW OR FUTURE EQUIPMENT ONLY,
EXISTING EQUIPMENT NEEDS TO BE
VERIFIED WITH SIGHT CONDITIONS AND
OWNER. USE EXISTING UTILITIES WEAR
POSSIBLE.
13
12
11
10
9
24
23
20
19
17
4
22
3
8
EQUIPMENT SCHEDULE
16
14
28
37
31
3632
31
41
42
3638
PLUMBING NOTES
PLUMBING SCHEDULE
KITCHEN PLUMBING PLAN
22
NOTE:
ALL VACUUM BREAKERS AND
OR BACK FLOW PREVENTERS
TO BE SUPPLIED AND
INSTALLED BY PLUMBING
CONTRACTOR.
EXISTING
DISH DROP
ADD UNDER
SHELF
NEW
CONDENSATE
HOOD,
DUCT TO
MATCH
EXISTING
EXISTING
WALK-IN
EXISTING
WALK-IN1
1
2
2
5
18
29
31
15
15
7
21
WH
EL
EC
T
PA
NE
L
FE
C
OF
FIC
E
05
TL
T
04
WA
LK
-IN
-
WA
LK
-IN
-
GY
M
06
PE
S
TO
RA
GE
-
FIE
LD
S
TO
RA
GE
-
ST
OR
.
03
FA
FA
FL
OO
R
SIN
K
FL
OO
R
SIN
K
2
WH
EL
EC
T
PA
NE
L
FE
C
OF
FIC
E
05
TL
T
04
WA
LK
-IN
-
WA
LK
-IN
-
GY
M
06
PE
S
TO
RA
GE
-
FIE
LD
S
TO
RA
GE
-
ST
OR
.
03
FA
FA
1'-1"
2'-2 1/2"
2'-1"
4'-6 1/2"
1'-11"
3'-0 1/2"
11"
2'-0 1/2"
2'-3 1/2"
5'-9 1/2"
1'-5 1/2"
24
21
10
10a
4a
3a
3
4
1'-1"
21a
6"
8 1/2"
FS-01
SCALE:
PROJECT NUMBER: 1601
DATE:
Kitchen
Equipment &
Plumbing Plan
21 MARCH 2016
1/4" = 1'-0"
REVISION:
ISSUED FOR:
EV
AN
S E
LE
ME
NT
AR
Y S
CH
OO
LK
ITC
HE
N R
EM
OD
EL
GALLETTA ARCHITECTURE
2012 NORTH TEJON STREET
COLORADO SPRINGS, CO 80907
P: 719.632.7675.
KITCHEN EQUIPMENT PLAN
Food Service Consultant
United Restaurant Supply,
LLC
725 Clark Place
Colorado Springs, CO
80915
303.838.5990
3
8 1/2"
3a
3
W/ SIDE
SPLASH
NOTE: PRE
RINSE TO
HAVE
SHORT
RISER.
21b
7'-10"
ADDENDUM #3
NOTE:
HOOD
CONTROL
PANEL
REV 1
NOTE: ROUGH-IN INFORMATION SHOWN IS
FOR NEW OR FUTURE EQUIPMENT ONLY,
EXISTING EQUIPMENT NEEDS TO BE
VERIFIED WITH SIGHT CONDITIONS AND
OWNER. USE EXISTING UTILITIES WEAR
POSSIBLE.
ALL WALL BACKING
TO BE 2" x 12" FIRE
RATED WOOD, MOLD
AND INSECT PROOF.
SEE PLAN VIEW &
SCHEDULE FOR
EXACT SIZE AND
PLACEMENT
BUILDING CONDITIONS/VENTILATION NOTES
1'-6"
7'-6 1/4"
6'-0"
10'-0"
ELECTRICAL NOTES
C
ELECTRICAL SCHEDULE
C
2'-0"
WH
EL
EC
T
PA
NE
L
FE
C
OF
FIC
E
05
TL
T
04
WA
LK
-IN
-
WA
LK
-IN
-
GY
M
06
PE
S
TO
RA
GE
-
FIE
LD
S
TO
RA
GE
-
ST
OR
.
03
FA
FA
WH
EL
EC
T
PA
NE
L
FE
C
OF
FIC
E
05
TL
T
04
WA
LK
-IN
-
WA
LK
-IN
-
GY
M
06
PE
S
TO
RA
GE
-
FIE
LD
S
TO
RA
GE
-
ST
OR
.
03
FA
FA
KITCHEN BUILDING COND
NOTE: MATCH DUCT COLLAR
TO EXISTING DUCT . 400 CFM
NOTE; IF WALL BACKING IS
NOT POSSIBLE KEC TO USE
150 lb WALL ANCHORS .
4'-0"
1"
2 1/2"
3 1/2"
3'-0"
7'-0"
3'-9"
8'-1 1/2"
NOTE:
WALL BACKING NOT NEEDED IF
WALLS ARE BLOCK OR
CONCRETE
BACKING TO BE WOOD, 2"x12"
S/S WALL FLASHING BY KECS/S WALL FLASHING BY KEC
S/S CORNER GUARDS BY KEC
CLOSURE PANELS ABOVE
HOOD AS
REQ. BY KEC
MISC S/S TRIM
1'-10"1'-6 1/2"
4"
2'-4" 3'-5 1/2"
3'-1"
1'-6"
3'-11"
5"
3'-10"
4 1/2"
10"
3'-1 1/2"
NOTE: ELECTRICAL CONTRACTOR (EC) AND MECHANICAL CONTRACTOR
(MC)
EC TO MAKE ALL CONNECTIONS FOR EXHAUST HOODS INCLUDING,
LIGHTS, FANS, TEMPERATURE PROBES, HOOD CONTROLS, ANSUL SYSTEM
AND REMOTE SENSING AND OR MONITORING DEVICES. EC TO PROVIDE
WALL MOUNT SWITCH FOR EXHAUST HOOD LIGHTS AND FANS IF NO
SWITCH / CONTROL PANEL IS PROVIDED. MC TO PERFORM ALL START UP
FUNCTIONS AND BALANCING AS REQUIRED.
24a
C
33
4142C
17
C 24
23
21
7"
29
SCALE:
PROJECT NUMBER: 1601
DATE:
21 MARCH 2016
1/4" = 1'-0"
REVISION:
ISSUED FOR:
EV
AN
S E
LE
ME
NT
AR
Y S
CH
OO
LK
ITC
HE
N R
EM
OD
EL
GALLETTA ARCHITECTURE
2012 NORTH TEJON STREET
COLORADO SPRINGS, CO 80907
P: 719.632.7675.
KITCHEN ELECTRICAL PLAN
Food Service Consultant
United Restaurant Supply,
LLC
725 Clark Place
Colorado Springs, CO
80915
303.838.5990
FS-02
Kitchen
Electrical &
Building Cond.
7'-10"
ADDENDUM #3
NOTE: SEE HOOD
DRAWING FS-03 FOR
COMPLETE INFORMATION
REGARDING HOOD
5'-1"
11"
EXHAUST DUCT - 10"
x 16" - 2000 CFM @
.S75 SP
REV 1
SCALE:
PROJECT NUMBER: 1601
21 MARCH 2016
1/4" = 1'-0"
ISSUED FOR:
EV
AN
S E
LE
ME
NT
AR
Y S
CH
OO
LK
ITC
HE
N R
EM
OD
EL
GALLETTA ARCHITECTURE
2012 NORTH TEJON STREET
COLORADO SPRINGS, CO 80907
P: 719.632.7675.
Food Service Consultant
United Restaurant Supply,
LLC
725 Clark Place
Colorado Springs, CO
80915
303.838.5990
FS-03
Kitchen
Exhaust
Hood
ADDENDUM #3
REV 1
DATE:
REVISION:
EXHAUST ONLY DOUBLE SHELL FRONT DETAIL
HOOD FRONT SECTION VIEW
AVAILABLE ON EXHAUST ONLY RECTANGULAR HOOD MODELS ONLY
INTERIOR SHELL
PERFORMANCE ENHANCING LIP (PEL)
TECHNOLOGY W/ BURR FREE CLOSED
HEM CONSTRUCTION
HOOD FRONT PANEL
INSULATION
HOOD TOP
1" INSULATION
MOUNTED TO
BACK OF HOOD
ZERO CLEARANCE TO BACK OF HOOD
NOTES:
TO BE UL LISTED THERE MUST BE
BACKSPLASH PANELS MOUNTED THE FULL
LENGTH OF THE HOOD AGAINST THE
COMBUSTIBLE WALL
ZERO CLEARANCE TO END OF HOOD
NOTES:
TO BE UL LISTED THERE MUST BE
SIDESPLASH PANELS MOUNTED THE FULL
WIDTH OF THE HOOD AGAINST THE
COMBUSTIBLE WALL
1" INSULATION
FULL WALL
END FILLER PANEL
PARTIAL WALL
END FILLER PANEL
1" INSULATION
VERIFICATION OF HOOD HANGING HEIGHT ABOVE FINISHED FLOOR (A.F.F.)
IS REQUIRED FOR CORRECT PLACEMENT OF FIRE SYSTEM NOZZLES.
HOOD HANGING HEIGHT FOR FIRE SYSTEMS
RECOMMENDED HANGING HEIGHT = 80" FROM
FINISHED FLOOR TO LOWER FRONT EDGE OF HOOD.
OTHER HANGING HEIGHT = __________" FROM
FINISHED FLOOR TO LOWER EDGE OF HOOD.
TYPICAL
HANGER
BRACKET
ON HOODS OVER 120"
HOOD HANGER BRACKET DETAIL
NOT TO SCALE
REFERENCE SCALED DRAWING FOR ACTUAL LOCATIONS
THREADED
ROD (1/2")
WASHER
HANGER
BRACKET
1/2" NUT
ZERO CLEARANCE TO HOOD TOP
INSULATION MOUNTED TO
HOOD TOP BETWEEN
STANDING SEAMS
MODEL
LENGTH WIDTH HEIGHT
HOOD DIMENSIONS (IN.)
MARK
WIDTH LENGTH DIA. CFM S.P.
COLLAR(S)
EXHAUST
HOOD
NO.
HOOD
TEMP
RATING
HOOD
CONSTR.
MUA
CFM
AC
CFM
TOTAL
WEIGHT
LBS.
SECTION
LOCATION
TOTAL
CFM
SUPPLY
12 16 0.375
2000
2000
440
600
DEG F
430 SS
WHERE
EXPOSED
LIGHTING DETAILS
QTY
L
GREASE FILTRATION DETAILS
QTY
H
LOCATION
UTILITY CABINET(S)
CONTROLS
HOOD INFORMATION
MARK
FIXTURE TYPE
BULB / LAMP INFO
FOOT
CANDLES
TYPE / MODEL
MATERIAL
SIZE (IN.)
HOOD
NO.
FIRE SYSTEM
MODELTYPE SIZE INTERFACE
41.35
6
20
0
20
16INCANDESCENT (GLOBE)
100W A19 (BULBS NOT INCL.)
BAFFLE
STAINLESS STEEL
3
HOOD OPTIONS
IT
EM
17
EV
AN
S IN
TE
RN
AT
IO
NA
L E
SA
CC
UR
EX
- C
O, W
Y
JASON AGIN
CO
WY
@A
CC
UR
EX
.C
OM
(3
03
)6
53
-6
05
7
PR
OJE
CT
MA
RK
3/2
3/2
01
6
REAR INTEGRAL AIR SPACE
AGENT
TANK
AMEREX
MECHANICAL
RELEASE
MODULE
TEMPERATURE SENSORS
FIELD WIRING TO CONTROLS REQUIRED
INSULATED DOUBLE
SHELL FRONT
REMOVABLE GREASE CUP W/
CONCEALED GREASE TROUGH
UL LISTED
STANDARD BAFFLE FILTERS
UL LISTED LIGHT FIXTURE
ZERO CLEARANCE INTEGRAL AIRSPACE
TEMPERATURE
SENSORS
122.0
2.125
HOOD
HEIGHT
0.750
HOOD LENGTH
3.63.6
4.0
2.6
8.0
6.0
6.0 8.0
16.0
12.0
8.0
60.0 60.0
120.0
1.0
AIR SPACE
1.0
AIR SPACE
3.0
54.0
4.0
80.0
ABOVE
FINISHED
FLOOR
24.0
104.0
S1
S1H
FAN SWITCH 1
FAN SWITCH
ON CONTROL PACKAGE
ORANGE
RED
208/3 15 AMPS
MARK: KEF-1
1 HP
TYPICAL
EXHAUST
FAN
OL1
T1L1 T1
T2L2 T2
T3L3 T3
L1
L2
L3
ST1
MARK: MAU-1
1 HP
TYPICAL
SUPPLY FAN
208/3
NOTE: POWER FOR FAN FEEDS
DIRECTLY FROM BREAKER PANEL TO
FAN (REFER TO MAKE UP AIR DETAIL)
Electrical - Field Wiring Schematic
H1
N1
POWER WIRING FOR XFCC CONTROL SYSTEM
BUILDING BREAKER PANEL
CONTROL
NON-SHUNTED
SHUNT TRIP COIL
120V OUTPUT DURING
FIRE
CONTROL WIRING FOR XFCC CONTROL SYSTEM
T1-A
T1-B
120/1 15 AMPS
INPUT OUTPUT
INPUT OUTPUT
SHUNT TRIP BREAKER IN BUILDING
PANEL (PROVIDED BY OTHERS)
1. All wiring to be done by certified and qualified persons and
must be wired to all local & national codes.
2. Exhaust and supply fan(s) shown as typical for
representation of the fan. For exhaust or supply fan detail
see fan submittals.
3. Exhaust and/or supply fans may be shown more than once
for purpose of separating power versus control wiring.
Capture Tank
NOTE: ALL SENSORS TO
BE WIRED
INDEPENDENTLY
Duct Collar
Shipped
Loose for Field
Installation
4. Power wiring is the responsibility of the electrician. Control wiring
is the responsibility of controls contractor. If there is no controls
contractor, both power and control wiring is the responsibility of the
electrician.
5. All ground wiring not shown on above diagram for clarity.
6. For further instructions please see the XFCC Installation and
Operations Manual that was shipped with panel, or contact
ACCUREX's Kitchen Ventilation team at 1-800-371-6858
Possible Sensor Locations:
Note(s):
HOOD TEMPERATURE
SENSOR 1
USE 18 AWG, STRANDED
PLENUM RATED WIRE
Kitchen Fan Control Center (XFCC)
Evans International ES
USE 18 AWG,
SHIELDED WIRE
C1
NO1
FIRE SYSTEM MICROSWITCH
NC1
FIRE SYSTEM
MICROSWITCH
COM
NO
NC
C3
NO3
NC3
C4
NO4
NC4
SPARE, DRY CONTACTS
ON/OFF WITH FIRE
COMMON
NORMALLY OPEN
NORMALLY CLOSED
COMMON
NORMALLY OPEN
NORMALLY CLOSED
SPARE, DRY CONTACTS
ON/OFF WITH FIRE
*
*
* DRY CONTACTS ARE
RATED UP TO 250VAC
AND 8 AMPS
STN
STH
NOTE: ALL SENSORS TO
BE WIRED
INDEPENDENTLY
NOTE: REMOVE JUMPER BETWEEN C1,
NC1 ONCE MICROSWITCH IS CONNECTED
B2
H2
LIGHT SWITCH 1
LIGHT SWITCH
ON CONTROL PACKAGE
BLACK
BLACK
H2
N2
120/1 15 AMPS
HOOD LIGHTS 1
INPUT POWER
HOOD LIGHTS 1
120V OUTPUT TO
LIGHTS
B2
W2
TYPICAL HOOD
WIRE TO ALL HOOD LIGHTS TO
OPERATE WITH LIGHT CIRCUIT 1 (1400W
MAX)
R
G
MUA UNIT
CONTROL
CENTER
R
G SUPPLY
COMMON
24VAC
MARK: MAU-1
MUA
CONTROL WIRING
NOTE: ENSURE THAT THE JUMPER BETWEEN R AND G IS
REMOVED FROM MUA TERMINALS WHEN THE WIRING IS
CONNECTED
Item 17 Section 1 CAPTURE TANK1
HOOD MARK QTY LOCATION
SENSOR
CONTROL PANEL
Installation Location:
Ship Loose
"FAN" SWITCH
"LIGHTS" SWITCH
NOTES:
DRAWING SHOWN DE-ENERGIZED AT L1 (TERM. #H1),
W/ FIRE SYSTEM ARMED (NON-FIRE MODE). (NORMAL
OPERATION, R1 & R2 ARE ENERGIZED) IF WALL
MOUNTED PREWIRE, OR FIELD INSTALLED FIRE
SYSTEM, THE FIRE SYSTEM MICROSWITCHES MUST
BE FIELD WIRED.
TORQUE: FIELD WIRING:
UL LISTED
LABEL DESCRIPTION
Electrical Prewire Package
Kitchen Fan Control Center (XFCC)
Evans International ES
110-2BLM-311 2-2.2
CP-1
TEMPERATURE INTERLOCK CALIBRATION
1. PRESS THE SET BUTTON TO SEE THE FIRST SET POINT. (PRESS THE SET
BUTTON TWICE, SLOWLY TO SEE THE SECOND SET POINT)
2. PRESS THE UP/DOWN ARROW BUTTON TO CHANGE THE SET POINT.
3. PRESS THE SET BUTTON TO VIEW THE CURRENT TEMPERATURE.
4. CHECK SYSTEM OPERATION BEFORE MAKING ADDITIONAL ADJUSTMENTS
LIGHT INPUT: 120VAC,
15AMPS FROM BREAKER
Switches Mounting - On Control Package
Exh
FAN 1
CONNECTIONS TO
TEMPERED MUA FAN
TYP. THRU ALL
EXHAUST STARTERS
CONTROL INPUT: 120VAC, 15AMPS FROM BREAKER
T1-A T1-B
TS1
1513
TC1
1411
R1
YW
OR
D3 D1 D2
CP
-1
EV
AN
S IN
TE
RN
AT
IO
NA
L E
SA
CC
UR
EX
- C
O, W
Y
JASO
N AG
INC
OW
Y@
AC
CU
RE
X.C
OM
(3
03
)6
53
-6
05
7
PR
OJE
CT
MA
RK
3/2
3/2
01
6
MARK
CONTROL INFORMATION
FANS CONTROLLED
TYPE HPVOLT PHASEMARKMODEL LOCATION
USER INTERFACE
LOCATION
ELECTRICAL CONTROL PACKAGE
TYPE
SWITCHES ON CONTROL PACKAGEXFCC SHIP LOOSECP-1
1
1
CONTROL FEATURES
20.0
6.0
12.0