The Emergency Voice Communications System (EVCS) is for use as a Fire Telephone system, Disabled Refuge Call system or as a combined system when both Fire Telephones and Disabled Refuge Points are required. Compact 5 System The EVCS Compact 5 and Compact 9 systems provide fixed, secure, bi-directional, full-duplex voice communication system, to assist fire fighters within high rise buildings or large sites where radio communication may not be possible. Where both a fire telephone and disabled refuge system are fitted to a building BS 5839 Part 9 specifies these should form a single system. The EVCS Compact 5 is designed to comply with BS5839 Part 9 2003. The system comprises of a master EVCS Compact handset, and up to five outstations (Type A, Type B, or Emergency Assist Alarms) and is ideal for small buildings that are required to install an Emergency Voice Communication System but only need two or three outstations, leaving room for expansion. Features Analogue addressable communications Monitored handset Fully monitored supply and charger Up to five outstations per system Duplex two way communication No programming required BS5839 part 9 2003 compliant Compact 9 System The EVCS Compact 9 system comprises of the 9 Line Master Exchange Unit and up to 9 Outstations (Type A, Type B, or Emergency Assist Alarms). Using the 10 line Slave Exchange Unit this system can be easily expanded to 19 lines. The Compact 9 Emergency Voice Communication System (EVCS) is designed to fully comply with BS 5839-9 -2011 for use as a Fire Telephone System, Disabled Refuge Call System or as a combined system when both Fire Telephones and Disabled Refuge points are required. The Compact 9 is modular in design and the controller manages all functions for the first 9 zones. There is no need for additional equipment such as power supplies. Features Analogue addressable communications Full duplex communications Simple menu programming Contact outputs to interface with Fire Detection or Voice Alarm Systems. Up to 19 Outstations - using 10 Line Slave Exchange unit and the 9 Line Master Exchange In addition to Type A and Type B Outstation can also monitor Emergency Assist Alarms (using a 2 core radial) EVCS Compact 5 & Compact 9 Data Sheet This document is not intended to be used for installation purposes. Every care has been taken in the preparation of this document but no liability can be accepted for the use of the information therein. Design features may be changed or amended without prior notice. For more information, contact: NOTIFIER. Charles Avenue, Burgess Hill, West Sussex, RH15 9UF. United Kingdom Phone: +44 (0) 1444 230 300 Fax: +44 (0) 1444 230 888 ISO9001 Design, Manufacture and Supply to Quality Manage- ment Systems Certified to ISO9001:1994 Page 1 of 10 - 990-142_0213 www.notifierfiresystems.co.uk

Upload: others

Post on 28-Feb-2021

4 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: EVCS Compact 5 & Compact 9...• Product Family: BS 5839-9 & BS 9999 & EN 60118-4 Mounting The Unit The Handset should be mounted at a height of either 1200mm from the fioor, or on

The Emergency Voice Communications System (EVCS) is for use as a Fire Telephone system, Disabled Refuge Call system or as a combined system when both Fire Telephones and Disabled Refuge Points are required.

Compact 5 SystemThe EVCS Compact 5 and Compact 9 systems provide fixed, secure, bi-directional, full-duplex voice communication system, to assist fire fighters within high rise buildings or large sites where radio communication may not be possible. Where both a fire telephone and disabled refuge system are fitted to a building BS 5839 Part 9 specifies these should form a single system.

The EVCS Compact 5 is designed to comply with BS5839 Part 9 2003. The system comprises of a master EVCS Compact handset, and up to five outstations (Type A, Type B, or Emergency Assist Alarms) and is ideal for small buildings that are required to install an Emergency Voice Communication System but only need two or three outstations, leaving room for expansion.

Features• Analogue addressable communications

• Monitored handset

• Fully monitored supply and charger

• Up to five outstations per system

• Duplex two way communication

• No programming required

• BS5839 part 9 2003 compliant

Compact 9 SystemThe EVCS Compact 9 system comprises of the 9 Line Master Exchange Unit and up to 9 Outstations (Type A, Type B, or Emergency Assist Alarms). Using the 10 line Slave Exchange Unit this system can be easily expanded to 19 lines.

The Compact 9 Emergency Voice Communication System (EVCS) is designed to fully comply with BS 5839-9 -2011 for use as a Fire Telephone System, Disabled Refuge Call System or as a combined system when both Fire Telephones and Disabled Refuge points are required.

The Compact 9 is modular in design and the controller manages all functions for the first 9 zones. There is no need for additional equipment such as power supplies.

Features• Analogue addressable communications

• Full duplex communications

• Simple menu programming

• Contact outputs to interface with Fire Detection or Voice Alarm Systems.

• Up to 19 Outstations - using 10 Line Slave Exchange unit and the 9 Line Master Exchange

• In addition to Type A and Type B Outstation can also monitor

Emergency Assist Alarms (using a 2 core radial)

EVCS Compact 5 & Compact 9Data Sheet

This document is not intended to be used for installation purposes. Every care has been taken in the preparation of this document but no liability can be accepted for the use of the information therein. Design features may be changed or amended without prior notice. For more information, contact: NOTIFIER. Charles Avenue, Burgess Hill, West Sussex, RH15 9UF. United KingdomPhone: +44 (0) 1444 230 300 Fax: +44 (0) 1444 230 888

ISO9001Design, Manufacture and

Supply to Quality Manage-ment Systems Certified to

ISO9001:1994

Page 1 of 10 - 990-142_0213 www.notifierfiresystems.co.uk

Page 2: EVCS Compact 5 & Compact 9...• Product Family: BS 5839-9 & BS 9999 & EN 60118-4 Mounting The Unit The Handset should be mounted at a height of either 1200mm from the fioor, or on

SpecificationsEVCS Compact 5Mechanical Specification

• Dimensions: Height: 330 mm Width: 350 mm Depth: 103 mm • Weight: 6.5Kg

Inputs• Number of Lines 5• Remote Enable Short to Use• End of Line 10K

Outputs• Number 2, Fault & In Use• Type Volt Free Relay• Contact 30V DC 1A

Controls• Buttons 6, 5 Lines, 1 Fault acknowledgement• Zone LEDs 5 Status, 5 Fault Status• Fault LEDs 3, AC, DC, General

Electrical Specification • AC Input 230V AC +/- 10% 50/60Hz

• Internal Power Supply 14V DC

• Supply & Battery Monitored, Open, Short, Fuses

• Protection Deep discharge, Short, Thermal

• Temperature Compensation Yes

• Battery Size and Type 1 x 12V 4.2AHr

• Mains Fuse 240V 2A HRC

• Battery Fuse 1A PTC

• Max Charge Current 250mA

Outstation Cables• Type Enhanced• Cores 2 Core 1mm or 1.5mm• Distance 500m

Standards• EMC EN 55103-1 & EN 55103-2• Product Family BS 5839-9 & BS 9999

EVCS Compact 5 - EVCS-CMPTThe Emergency Voice Communications System (EVCS) is for use as a Fire Telephone system, Disabled Refuge Call system or as a combined system when both Fire Telephones and Disabled Refuge Points are required.

The EVCS Compact 5 is a self contained enclosure housing a master handset, five line exchange, power supply, battery charger and can be surface or semi-flush mounted as standard. The enclosure is made from powder coated Zintec and is fitted with 20mm cable knockouts for all cables needed. It also provides space for the system backup 12V SLA battery.

The unit is processor controlled, but requires no programming on site, the panel is fitted with end of lines which are replaced with field wiring when an outstation is connected.

Page 2 of 10 - 990-142_0213 www.notifierfiresystems.co.uk

Page 3: EVCS Compact 5 & Compact 9...• Product Family: BS 5839-9 & BS 9999 & EN 60118-4 Mounting The Unit The Handset should be mounted at a height of either 1200mm from the fioor, or on

SpecificationsEVCS Compact 9Mechanical Specification

• Dimensions: Height 330 mm Width 350mm Depth 103mm• Weight 6.5kg

Inputs • Number of Lines 9 or 19 • Remote Enabler Short To Use

Outputs• Number 2 (fault & in-use)• Type Volt Free Relay• Contact 30V dc 1A

Controls• Buttons 4 navigation keys• Zone LEDs 3 (in-use, healthy, energised)• Fault LEDs 3 (Line, PSU And General)

Electrical Specification• AC Input 230V AC +/- 10% 50/60Hz• Internal Power Supply 14V DC• Supply And Battery Monitored, Open, Short, Fuses• Protection Deep Discharge, Short Thermal, Impedence• Battery Type 1 x 12V VRSLA (5AH Required)• Mains Fuse 240V 1A HRC• Battery Fuse 250MA PTC• Charge Current 250MA

Outstation Cables• Cores 2 core (1mm or 1.5mm)• Distance 500m

Standards• EMC EN 55103-1 & EN 55103-2• Product Family BS 5839-9 & BS 9999

EVCS Compact 9 - EVCS-CMPT9The EVCS Compact 9 is a combined Line Exchange Unit and Master Handset which connects to up to 9 Disabled Refuge or Fire Emergency Telephones. Capable of being extended to 19 outstations it is the ideal solution for EVCS in small and medium buildings.

Fully compliant with BS5839 part 9 (2011) each Compact 9 unit is supplied complete with power supply requiring no further equipment and minimum commissioning effort.

Complies to BS5839 Part 9 :2011VCC S10 SlaveEN54-4:A2 :2006

VoCALLEVCSCompact

General

Supply

CFVCCM9

CFVCCS10

4 core fire rated enhanced cable

��

*

Making a Call:

Press * for the directory and use thenavigation to select the extension name to call press � to call.

Receiving a Call:

Use the navigation keys to select the caller, press � to connect, press � again to place on HOLD

VoCALLEVCSCompact

Call

Healthy Line

PSU

General

Supply

VoCALL Compact VCCM9

System Healthy20|01|11 10:20:01

330mm

350mm 103mm

Page 3 of 10 - 990-142_0213 www.notifierfiresystems.co.uk

Page 4: EVCS Compact 5 & Compact 9...• Product Family: BS 5839-9 & BS 9999 & EN 60118-4 Mounting The Unit The Handset should be mounted at a height of either 1200mm from the fioor, or on

Page 4 of 10 - 990-142_0213 www.notifierfiresystems.co.uk

SpecificationsEVCS Type A OutstationMechanical Specification - EVCS-HSP (Surface Mounting)

• Dimensions: Height: 320 mm Width: 152 mm Depth: 85 mm • Weight: 1.4 Kg (no batteries)

Mechanical Specification - EVCS-HFP (Flush Mounting)• Dimensions (with bezel): Height: 334 mm Width: 191 mm Depth: 85 mm • Dimensions (backbox hole): Height: 320 mm Width: 152 mm Depth: 85 mm • Weight: 1.4 Kg (no batteries)

Features• Telephone type handset• Automatic dialling to Compact Handset when ‘off hook’• Telecoil for hearing impaired users• Magnetic push catch door

Electrical Specification • Fully monitored connections. DC open, DC Short and Earth Fault

Status LED• Flashing when ringing• Dimly lit to indicate surveillance

Standards• EMC: EN 55103-1 & EN 55103-2• LVD: EN 60950• Product Family: BS 5839-9 & BS 9999 & EN 60118-4

Surface mounting enclosure

Flush mounting enclosure

Type A Outstation - EVCS-HSP & EVCS-HFP The EVCS Type A outstation is designed to fully comply with BS5839-Part 9:2003 for use as a Fire Telephone system, Disabled Refuge Call system or as a combined system when both Fire Telephones and Disabled Refuge Points are required.

The Type A outstation is a monitored phone handset providing full duplex speech capability. The unit is available as a surface mounting or flush mounting unit cased in a metal wall mounting enclosure.

The EVCS type A Outstation is a slick compact unit which offers easy access via a magnetic push catch door and a unique front levelling system allowing the back box to be mounted at a slight angle whilst still retaining a true front face and door.

Compatible with all EVC systems for use as a standard Fire Telephone or Disabled Refuge call point.

334mm

191mm 85mm

320mm

152mm 85mm

EVCS-HFPSS Flush Mount

EVCS-HSPSS Surface Mount

Page 5: EVCS Compact 5 & Compact 9...• Product Family: BS 5839-9 & BS 9999 & EN 60118-4 Mounting The Unit The Handset should be mounted at a height of either 1200mm from the fioor, or on

Page 5 of 10 - 990-142_0213 www.notifierfiresystems.co.uk

SpecificationsEVCS Type A Outstation Stainless SteelMechanical Specification - EVCS-HSPSS (Surface Mounting)

• Dimensions: Height: 320 mm Width: 152 mm Depth: 85 mm • Weight: 1.4 Kg (no batteries)

Mechanical Specification - EVCS-HFPSS (Flush Mounting)• Dimensions (with bezel): Height: 334 mm Width: 191 mm Depth: 85 mm • Dimensions (backbox hole): Height: 320 mm Width: 152 mm Depth: 85 mm • Weight: 1.4 Kg (no batteries)

Features• Telephone type handset• Automatic dialling to Compact Handset when ‘off hook’• Telecoil for hearing impaired users• Magnetic push catch door

Electrical Specification • Fully monitored connections. DC open, DC Short and Earth Fault

Status LED• Flashing when ringing• Dimly lit to indicate surveillance

Standards• EMC: EN 55103-1 & EN 55103-2• LVD: EN 60950• Product Family: BS 5839-9 & BS 9999 & EN 60118-4

Type A Outstation Stainless Steel - EVCS-HFPSS & EVCS-HSPSS The EVCS Type A outstation is designed to fully comply with BS5839-Part 9:2003 for use as a Fire Telephone system, Disabled Refuge Call system or as a combined system when both Fire Telephones and Disabled Refuge Points are required.

The Type A outstation is a monitored phone handset providing full duplex speech capability. The unit is available as a surface mounting or flush mounting unit cased in a metal wall mounting enclosure.

The EVCS type A Outstation is a slick compact unit which offers easy access via a magnetic push catch door and a unique front levelling system allowing the back box to be mounted at a slight angle whilst still retaining a true front face and door.

Compatible with all EVC systems for use as a standard Fire Telephone or Disabled Refuge call point.

334mm

191mm 85mm

320mm

152mm 85mm

EVCS-HFPSS Flush Mount

EVCS-HSPSS Surface Mount

Page 6: EVCS Compact 5 & Compact 9...• Product Family: BS 5839-9 & BS 9999 & EN 60118-4 Mounting The Unit The Handset should be mounted at a height of either 1200mm from the fioor, or on

Page 6 of 10 - 990-142_0213 www.notifierfiresystems.co.uk

SpecificationsType A Outstation IP65 Lockable Surface MountMechanical Specification - EVCS-HFW

• Dimensions: Height: 300 mm Width: 200 mm Depth: 120 mm • Weight: 2.5 Kg• Material Zintec, Powder coated

• Colour RAL7035 Grey

Outstation Cables• Type Enhanced• Cores 2 core 1mm or 1.5mm• Distance 500m

Features• Telephone type handset• Automatic dialling to Compact Handset when ‘off hook’• Telecoil for hearing impaired users• Fitted with a standard firemans key lock to prevent unauthorised use

Electrical Specification • Fully monitored connections. DC open, DC Short and Earth Fault

Status LED• Flashing when ringing• Dimly lit to indicate surveillance

Standards• EMC EN55103-1, EN55103-2• LVD EN60950• Product Family: BS 5839-9 & BS 9999 & EN 60118-4

Mounting The UnitThe Handset should be mounted at a height of either 1200mm from the fioor, or on a 1400mm centre line to comply with the requirements of Building Regulations Document M (Access for the Disabled). The back box has four indented feet to allow mounting on uneven walls.If the unit is to be used as a refuge point suitable space must be allowed to the side of the unit to allow a wheelchair to be parked for using the system.

Type A Outstation IP65 Lockable Surface Mount - EVCS-HFW The EVCS Type A outstation is designed to fully comply with BS5839-Part 9:2003 for use as a Fire Telephone system, Disabled Refuge Call system or as a combined system when both Fire Telephones and Disabled Refuge Points are required.

The Type A outstation is a monitored phone handset providing full duplex speech capability.

The EVCS-HFW is a type A EVCS outstation compatible with the Notifier Compact and Network systems. It is supplied in an IP65 case fitted with a standard firemans key lock to prevent unauthorised use.

300m

m

200mm 120mm

Page 7: EVCS Compact 5 & Compact 9...• Product Family: BS 5839-9 & BS 9999 & EN 60118-4 Mounting The Unit The Handset should be mounted at a height of either 1200mm from the fioor, or on

SpecificationsType B OutstationMechanical Specification

• Dimensions: Height: 133 mm Width: 133 mm Depth: 45 mm • Weight: 1.1Kg • Construction Zintec powder coated • Colour Green, Red or Stainless Steel

Electrical Specification • Fully monitored connections. DC open, DC Short and Earth Fault

Outstation Cables• Cores 2 core 1mm or 1.5mm• Distance 500m

Indications & Controls• Status LEDs 2 off red -flashes location, lights solid in use• Call Press to call button• Cancel Press to cancel button

Hands Free Communications• Push button dialling to EVCS Master Handset• Echo cancellation• Noise reduction• Induction loop output for hearing impaired users• Push button cancel• Braille Signage

Standards• EMC: EN55103-1 & EN55103-2 • LVD: EN60950• Product Family: BS5839 Pt9 & BS9999

Mounting The UnitAll Type B Outstations should be mounted at a height of either 1200mm from the floor, or on a 1400mm centre line to comply with the requirements of Building Regulations Document M (access for the disabled).The back box has 4 indented feet to allow mounting on uneven walls.Type B Outstations can be flush mounted by cutting a hole 133mm x 133mm and 45mm deep, and using the stainless steel bezel to finish the surround.

Type B Outstation - EVCS-HSBG, EVCS-HSB, EVCS-HSFSSThe EVCS Type B outstation is designed to fully comply with BS5839-Part 9:2003 for use as a Fire Telephone system, Disabled Refuge Call system or as a combined system when both Fire Telephones and Disabled Refuge Points are required.

The Type B outstation is a fixed, monitored and maintained, bi-directional, full duplex voice communication system to assist the orderly evacuation of disabled or mobility impaired people and enhance fire fighters communication during emergencies.

Please note: When choosing the outstation type for use with an EVCS we recommend reading Section 11 of BS5839-9:2003 which deals with outstation types. Type B outstations can only be used where the background noise is below 40dBA (therefore there can be no sounder or voice alarm coverage in the area).

Page 7 of 10 - 990-142_0213 www.notifierfiresystems.co.uk

Page 8: EVCS Compact 5 & Compact 9...• Product Family: BS 5839-9 & BS 9999 & EN 60118-4 Mounting The Unit The Handset should be mounted at a height of either 1200mm from the fioor, or on

SpecificationsJack Plate Mechanical Specification

• Dimensions: Height: 86 mm Width: 86 mm Depth: 25 mm • Weight: 140g • Construction Brushed stainless steel

Outstation Cables• Cores 2 core 1mm or 1.5mm • Distance 500m• End of Line 10K 1/4 W

Electrical Specification • Fully monitored connections. DC open, DC Short and Earth Fault

Roaming Handset Mechanical Specification

• Dimensions: Height: 210 mm Width: 66 mm Depth: 45 mm • Weight: 700g • Construction ABS UL90V1• Connection 1/4” mono neutrik heavy duty jack

Standards Compliance• EMC EN55103-1,EN55103-2• LVD EN60950

Controls

• Call Automatic off hook dialing

Roaming Handset and Jack PlateThe Roaming Handset and Jack plate are designed to provide a cost effective solution for Fire Telephones in high rise buildings. Notifier’s range of EVCS systems cover a wide range of building sizes providing high quality full duplex Emergency Voice Communication.

The Roaming Handset is used along with the Jack Plate for Emergency Voice Communication System installations in countries whose fire codes allow for Roaming Handsets*. When used together, the Roaming Handset and Jack Plate form a Type A Outstation which is compatible with all EVCS systems.

Low noise high quality telephone jack with Telecoil for hearing impaired users.

Stainless steel jack plate can be surface or flush mounted

*These units are not suitable for installation in the UK to BS5839 Pt9

Page 8 of 10 - 990-142_0213 www.notifierfiresystems.co.uk

Page 9: EVCS Compact 5 & Compact 9...• Product Family: BS 5839-9 & BS 9999 & EN 60118-4 Mounting The Unit The Handset should be mounted at a height of either 1200mm from the fioor, or on

SpecificationsEmergency Assist Alarm Kit EVCS-TA

Features• Monitored to BS 5839-9

• Remote powered from EVCS exchange

• Dual loop pull cord

• High contrast labels

• Braille on cancel plate

• Blue indication

Benefits• No PSU is required remote powered by

EVCS system

• All calls from disabled toilets and refuge points monitored from one location

• Tactile braille signage to assist partially sighted people

Page 9 of 10 - 990-142_0213 www.notifierfiresystems.co.uk

Over door indicator

Dimensions: Width:Height:Depth:

87 mm87 mm31.5 mm

Electrical Specification: Operating voltage: 12V dc (nominal)

Physical: Construction: PC

Cancel button

Dimensions: Width:Height:Depth:

87 mm87 mm25 mm

Electrical Specification: Operating voltage: 12V dc (nominal)

Physical: Construction: PC

Pull cord unit

Dimensions: Width:Height:Depth:

87 mm87 mm30.5 mm

Electrical Specification: Operating voltage: 12V dc (nominal)

Physical: Construction: PC

Wiring Guide Using 2 Core Cable

+-

+-

Power Supply

12V +-

+-

+-+

-

Over DoorIndicator

CancelUnit

Pull Cord Unit

IN

IN

OUT

OUT

OUT INEVCS Exchange Over Door IndicatorOver Door Indicator Cancel UnitCancel Unit Pull Cord Unit

Emergency Assist Alarm Kit - EVCS-TAThe Emergency assist alarm kit has been specifically designed to integrate disabled call functions into the EVCS Network or EVCS Compact ranges providing the perfect solution for conformity with the Building regulations Document M and Equality Act 2010.

The Emergency Assist Alarm Kit solution is fully monitored and battery backed by the EVCS system, saving local power supplies and giving confidence in the system integrity.

The Emergency Assist Alarm Kit shows up as a call on the EVCS system, but has no speech path so a conversation cannot be had with the occupant, use of the Type B Outstations would allow this.

www.notifierfiresystems.co.uk

Page 10: EVCS Compact 5 & Compact 9...• Product Family: BS 5839-9 & BS 9999 & EN 60118-4 Mounting The Unit The Handset should be mounted at a height of either 1200mm from the fioor, or on

Charles AvenueBurgess HillW. SussexRH15 9UF

T: +44 (0) 116 246 2255F: +44 (0) 116 246 2210E: [email protected]

Page 10 of 10 - 990-142_0213

Product Range at a Glance

Part Number

EVCS Compact Master Handset-Wall Mount EVCS-CMPT

Compact 9 line master exchange unit EVCS-CMPT9

10 line slave exchange unit EVCS-XC10

Flush Outstation Push Door. Type A EVCS-HFP

Flush Outstation Type A, Push Door, Stainless Steel EVCS-HFPSS

Surface Outstation. Push Door. Type A EVCS-HSP

Surface Outstation Type A, Push Door, Stainless Steel EVCS-HSPSS

Weatherproof Type A Outstation EVCS-HFW

Surface Outstation, Type B, Green EVCS-HSBG

Surface Outstation, Type B, Red EVCS-HSB

Surface Outstation, Type B Stainless Steel EVCS-HSFSS

Wall Jack Outlet Point EVCS-WJP

Loose Handset with Jack Lead EVCS-HLJ

Emergency Assist Alarm Kit (without PSU) EVCS-TA

EVCS-HSB Stainless Steel flush mounting bezel EVCS-VCFHB

EVCS-MS Rackmount Kit 6U. EVCS-RM