events incident 05-11-2014- du départ 30kv fechkeur 6h14
DESCRIPTION
LOCATORTRANSCRIPT
Disturbance Report
Recording file: F630_H05_DR44_20141105061430Date: 05/11/2014 06:14:30Station/Bay: ALGERIE/DEPART MT_0_REF630_1
1 (10)
Template: C:\PCMDataBases\DRTool\templates\default.xml
General data
Station name ALGERIE
Object name DEPART MT
IED name REF630
Line length Not applicable
System Frequency 50.0 Hz
Recording number 44
Trigger signal name GENERAL TRIP
Trig date and time 05/11/2014 06:14:30.576
Pre-trig recording time 500 ms
Post trig recording time 1000 ms
Total recording time 1655 ms
Max. recording time 5000 ms
Recording in Test mode No
Type of time synchronization SNTP
IED type REF630 1.1.01
IED version 1.1.0
Sampling frequency 1.0 kHz
Disturbance recorder Installed
Event recorder Installed
Fault locator Not Installed
Active setting group during recording 1
Disturbance Report
Recording file: F630_H05_DR44_20141105061430Date: 05/11/2014 06:14:30Station/Bay: ALGERIE/DEPART MT_0_REF630_1
2 (10)
Template: C:\PCMDataBases\DRTool\templates\default.xml
Fault location
Fault loop type Not applicable
Fault location Not applicable
Status of fault calculation Not applicable
Fault Direction Not applicable
Disturbance Report
Recording file: F630_H05_DR44_20141105061430Date: 05/11/2014 06:14:30Station/Bay: ALGERIE/DEPART MT_0_REF630_1
3 (10)
Template: C:\PCMDataBases\DRTool\templates\default.xml
Analog channels
1 IL1 0.1 kA 0.0° 0.2 kA -0.2°
2 IL2 0.0 kA -97.4° 0.0 kA -95.3°
3 IL3 0.0 kA 146.3° 0.0 kA 150.5°
5 U1 10.5 kV -148.4° 9.5 kV -142.5°
6 U2 20.0 kV 53.0° 20.5 kV 50.5°
7 U3 24.7 kV -33.0° 25.9 kV -31.4°
8 Uo 8.0 kV -7.2° 9.3 kV -7.2°
Disturbance Report
Recording file: F630_H05_DR44_20141105061430Date: 05/11/2014 06:14:30Station/Bay: ALGERIE/DEPART MT_0_REF630_1
4 (10)
Template: C:\PCMDataBases\DRTool\templates\default.xml
Digital channels
1 GENERAL TRIP 1 1 1 1
2 GENERAL START 0 1 0 0
3 3I> TRIP 0 1 0 0
4 3I>> TRIP 0 1 0 0
5 I0> TRIP 0 1 0 0
6 ISG1 TRIP 0 1 0 0
7 ISG2 TRIP 0 1 0 0
8 ISG3 TRIP 0 1 0 0
9 CB OPEN 0 1 0 0
10 CB CLOSED 0 1 1 0
11 DELESTAGE 0 1 0 0
12 SF6 Q0 0 1 0 0
13 SF6 JDB 0 1 0 0
14 DISJ TT 0 1 0 0
15 DISJ FM 0 1 0 0
16 DISJ AC 0 1 0 0
17 DISJ C OUVERT 0 1 0 0
18 MANIVELLE-N-I 0 1 1 0
19 DISJ-CTRL-Q0 0 1 0 0
20 Q0 DEBROCHE 0 1 0 0
21 Q0 EMBROCHE 0 1 1 0
22 Q8 FERME 0 1 0 0
23 Q8 OUVERT 0 1 1 0
24 REGIME NORMAL 0 1 1 0
25 REGIME A 0 1 0 0
26 REGIME B 0 1 0 0
27 RESSORT_DESAR 0 1 0 0
28 AR_IN_PROGRES 0 1 1 0
29 AR_LOCKOUT 0 1 0 0
30 AR_READY 0 1 0 0
31 CDE DECL Q1/8 0 1 0 0
32 DISJ-Q1/8 OUV 0 1 0 0
33 DEF-INTERN 0 1 0 0
34 DEF-SNTP 0 1 0 0
35 FER-N-EXEC 0 1 0 0
36 OUV-N-EXEC 0 1 0 0
37 DEFHPDEF_OPER 0 1 0 0
Disturbance Report
Recording file: F630_H05_DR44_20141105061430Date: 05/11/2014 06:14:30Station/Bay: ALGERIE/DEPART MT_0_REF630_1
5 (10)
Template: C:\PCMDataBases\DRTool\templates\default.xml
kV
-30
-20
-10
0
10
20
30
kV
-30
-20
-10
0
10
20
30
kV
-30
-20
-10
0
10
20
30
kV
-30
-20
-10
0
10
20
30
kA
-0.15
-0.075
0
0.075
0.15
kA
-0.15
-0.075
0
0.075
0.15
kA
-0.15
-0.075
0
0.075
0.15
Total recordingTrigger time: 05/11/2014 06:14:30.576
-500 -250 0 250 500 750 1000 1154ms
U1 (5)
U2 (6)
U3 (7)
Uo (8)
IL1 (1)
IL2 (2)
IL3 (3)
Disturbance Report
Recording file: F630_H05_DR44_20141105061430Date: 05/11/2014 06:14:30Station/Bay: ALGERIE/DEPART MT_0_REF630_1
6 (10)
Template: C:\PCMDataBases\DRTool\templates\default.xml
Total recordingTrigger time: 05/11/2014 06:14:30.576
-500 -250 0 250 500 750 1000 1154ms
GENERAL TRIP (1)
GENERAL START (2)
3I> TRIP (3)
3I>> TRIP (4)
I0> TRIP (5)
ISG1 TRIP (6)
ISG2 TRIP (7)
ISG3 TRIP (8)
CB OPEN (9)
CB CLOSED (10)
DELESTAGE (11)
SF6 Q0 (12)
SF6 JDB (13)
DISJ TT (14)
DISJ FM (15)
DISJ AC (16)
DISJ C OUVERT (17)
MANIVELLE-N-I (18)
DISJ-CTRL-Q0 (19)
Q0 DEBROCHE (20)
Q0 EMBROCHE (21)
Q8 FERME (22)
Q8 OUVERT (23)
REGIME NORMAL (24)
REGIME A (25)
REGIME B (26)
RESSORT_DESAR (27)
AR_IN_PROGRES (28)
AR_LOCKOUT (29)
AR_READY (30)
CDE DECL Q1/8 (31)
DISJ-Q1/8 OUV (32)
DEF-INTERN (33)
DEF-SNTP (34)
FER-N-EXEC (35)
OUV-N-EXEC (36)
DEFHPDEF_OPER (37)
Disturbance Report
Recording file: F630_H05_DR44_20141105061430Date: 05/11/2014 06:14:30Station/Bay: ALGERIE/DEPART MT_0_REF630_1
7 (10)
Template: C:\PCMDataBases\DRTool\templates\default.xml
kV
-20-10
01020
kV
-20-10
01020
kV
-20-10
01020
kV
-20-10
01020
kA
-0.15
-0.075
0
0.075
0.15
kA
-0.15
-0.075
0
0.075
0.15
kA
-0.15
-0.075
0
0.075
0.15
Disturbance 1Trigger time: 05/11/2014 06:14:30.576
-50 -25 0 25 50 75 100 125 150 175186ms
U1 (5)
U2 (6)
U3 (7)
Uo (8)
IL1 (1)
IL2 (2)
IL3 (3)
GENERAL TRIP (1)
GENERAL START (2)
I0> TRIP (5)
CB OPEN (9)
CB CLOSED (10)
MANIVELLE-N-I (18)
AR_IN_PROGRES (28)
AR_READY (30)
Disturbance Report
Recording file: F630_H05_DR44_20141105061430Date: 05/11/2014 06:14:30Station/Bay: ALGERIE/DEPART MT_0_REF630_1
8 (10)
Template: C:\PCMDataBases\DRTool\templates\default.xml
Disturbance 1 (Voltages)
1
2
3
4
Calculation interval: -13 to 5 ms
Number ID RMS (kV) Angle
1 U1 9.5 -142.5°
2 U2 20.5 50.5°
3 U3 25.9 -31.4°
4 Uo 9.3 -7.2°
Disturbance Report
Recording file: F630_H05_DR44_20141105061430Date: 05/11/2014 06:14:30Station/Bay: ALGERIE/DEPART MT_0_REF630_1
9 (10)
Template: C:\PCMDataBases\DRTool\templates\default.xml
Disturbance Report
Recording file: F630_H05_DR44_20141105061430Date: 05/11/2014 06:14:30Station/Bay: ALGERIE/DEPART MT_0_REF630_1
10 (10)
Template: C:\PCMDataBases\DRTool\templates\default.xml
Event list
5 I0> TRIP On 05/11/2014 06:14:30.563
28 AR_IN_PROGRES On 05/11/2014 06:14:30.563
30 AR_READY Off 05/11/2014 06:14:30.563
5 I0> TRIP Off 05/11/2014 06:14:30.573
1 GENERAL TRIP On 05/11/2014 06:14:30.576
2 GENERAL START Off 05/11/2014 06:14:30.606
10 CB CLOSED Off 05/11/2014 06:14:30.626
9 CB OPEN On 05/11/2014 06:14:30.636
18 MANIVELLE-N-I Off 05/11/2014 06:14:30.645
1 GENERAL TRIP Off 05/11/2014 06:14:30.731
18 MANIVELLE-N-I On 05/11/2014 06:14:30.744
28 AR_IN_PROGRES Off 05/11/2014 06:14:30.883
9 CB OPEN Off 05/11/2014 06:14:30.946
10 CB CLOSED On 05/11/2014 06:14:30.951