EXHIBIT 1
SOUTH CARGO EAST SIDE DOOR REPLACEMENT July 2016
2
CE26 CE25 CE24
SUITE 1
3
SUITE 2
CE23 CE22 CE21
CE20 CE19 CE18
CE17
4
SUITE 3
CE16 CE15 CE14 CE13
Partition Wall
5
SUITE 4
CE12
Partition Wall
SUITE 5
CE11 CE10 CE9
6
There is no door CE8.
SUITE 6 SUITE 7
CE7 CE6 CE5 CE4 CE3 CE2 CE1
7
Suite 1 - CE26P Currently RH Manual Chain Operator Change to LH Operator 208V 3P. Mount to left of conduit and extend spring shaft (from center of door to end of extended shaft approximately 7’ 7”) GSP to provide power to operator disconnect
8
Suite 1 - CE26P Note: Do not mount operator to RH wall, there is no lintel where block was cut out for store front.
9
Suite 1 - CE25 Currently LH Electric – 208V 3P Go back with LH 208V 3P – Use existing disconnect.
10
Suite 1 – CE24 Currently RH Manual Chain Operator Change to LH Electric 208V 3P GSP to provide power to disconnect
11
Suite 2 – CE23 Currently no operator Change to LH electric 208V 3P GSP to re-route receptacle conduit
12
Suite 2 – CE22 Currently RH 230V 1P operating on 208V 1P Change to RH 208V 3P GSP to provide power to operator disconnect
13
Suite 2 – CE21P Currently RH 208V 1P Change to LH 208V 3P GSP to re-route 2 conduits GSP to provide power to new 3P operator disconnect
14
Suite 2 – CE20 Currently RH Manual Chain Operator Change to RH electric 208V 3P GSP to provide power to operator disconnect
15
Suite 2 – CE19 Currently RH Manual Chain Operator Change to RH electric 208V 3P GSP to provide power to operator disconnect
16
Suite 2 – CE18 Currently RH Manual Chain Operator Change to RH electric 208V 3P GSP to provide power to operator disconnect
17
Suite 2 – CE17 Currently RH Manual Chain Operator Change to RH electric 208V 3P GSP to provide power to operator disconnect
18
Suite 3 - CE16P Currently RH Manual Chain Operator Go back with RH Manual Chain Operator
19
Suite 3 - CE16P Note: Door not usable for loading/unloading with lift truck
20
Suite 3 – CE15 Currently RH Electric 480V 3P Direct Coupled Gear Reducer Go back with RH 480V 3P operator Use existing disconnect
21
Suite 3 – CE14 Currently RH Manual Chain Operator Change to LH Electric 480V 3P GSP to provide power to operator disconnect
22
Suite 3 – CE13 Currently RH Manual Chain Operator Go back with RH Manual Chain Operator GSP to remove section of partition wall; Delta to move air compressor
23
Suite 4 – CE12 Currently RH Manual Chain Operator Change to LH 480V 3P Operator GSP to provide power to operator disconnect (get power from Suite 3 – same breaker as CE12 & CE10)
24
Suite 4 – CE11 Currently RH Manual Chain Operator Change to RH Electric 480V 3P Operator GSP to provide power to operator disconnect (get power from Suite 3 – same breaker as CE12 & CE10)
25
Suite 4 – CE10 Currently RH Manual Chain Operator Change to RH 480V 3P Operator GSP to provide power to operator disconnect (get power from Suite 3 – Same breaker as CE11 & CE12)
26
Suite 5 – CE9 Currently RH Manual Chain Operator Change to LH 208V 3P GSP to provide power to operator disconnect (tie onto circuit with CW5)
27
There is no Door CE8
Suite 6 – CE7 Currently RH Manual Chain Operator Go back with RH Manual Chain Operator
28
Suite 6 – CE7 Door not usable for loading/unloading with lift truck
29
Suite 6 – CE6 (American) Currently RH Electric Operator – Chain driven Remove existing photo eye(s) (Change to constant contact) RE-USE EXISTING OPERATOR – REPLACE ALL OTHER COMPONENTS
30
Suite 7 – CE5P Currently RH Manual Chain Operator Change to LH 208V 3P GSP to provide power to operator disconnect (put on same circuit as CE1)
31
Suite 7 – CE4 Currently LH Electric 208V 3P Go back with LH Electric – 208V 3P Use existing disconnect
32
Suite7 – CE3 Currently RH Electric 208V 3P Go back with RH Electric 208V 3P Use existing disconnect
33
Suite 7 – CE2P Currently RH Electric – 208V 3P Go back with RH Electric - 208V 3P Use existing disconnect
34
Suite 7 – CE1 Currently RH Electric – 120V 1P Go back with RH Electric – 208V 3P GSP to provide power to 3P operator disconnect (use breaker currently used for air compressor)