experimental investigation of ultimate capacity of wired mesh-reinforced cementitious slabs
TRANSCRIPT
-
8/13/2019 Experimental Investigation of Ultimate Capacity of Wired Mesh-reinforced Cementitious Slabs
1/9
Experimental investigation of ultimate capacity of wired mesh-reinforced
cementitious slabs
Hassan Mohamed Ibrahim*
Concrete Structures, Civil Engineering Dept., Faculty of Engineering, Suez Canal University, Port-Said 42523, Egypt
a r t i c l e i n f o
Article history:Received 10 March 2010
Received in revised form 19 June 2010
Accepted 19 June 2010
Keywords:
Ferrocement
Slabs
Square
Punching
Patch
Wire mesh
a b s t r a c t
Experimental tests conducted on 27 square cementitious slabs of 490
490 mm simply supported onfour edges and subjected to patch load are presented. The slabs had a clear span of 400 400 mm and
provided with a 445 445 mm closed frame of 8 mm diameter steel bar to hold the reinforcement in
place and to act as a line support. The test variables were the wire mesh volume fraction: four expanded
and two square types; slab thickness: 40, 45, 50 and 60 mm; and the patch load pattern: square and rect-
angular. The test results showed that as the volume fraction increased the punching strength of the slabs
was also increased. Adding a wire mesh to ordinary reinforcement increases significantly the punching
resistance at column stub. Moreover, as the loaded area size increases both ductility and stiffness
increases and the bridging effect due to the difference in the reinforcement ratio in orthogonal directions
was clearly noticed. More research was needed to identify the volume fraction ratio at which the mode of
failure alter from flexure to punching.
2010 Elsevier Ltd. All rights reserved.
1. Introduction
Ferrocement is suitable for low-cost roofing, pre-cast units,
man-hole covers, etc. It can be used for the construction of domes,
vaults, shells, grid surfaces and folded plates. It is a good substitute
for timber. It can be used for making furniture, doors and window
frames, shutters and partitions. It can also be used for making
water tanks, boats and silos. Ferrocement is the best alternative
to concrete and steel. The most significant contribution of ferroce-
ment is that most of the structures made of traditional materials
can also be constructed in ferrocement[1,2].
Ferrocement has been used effectively for affordable roofing
applications around the world hence at first glance it seems a via-
ble solution for rural areas in Egypt. However, it is still not replac-
ing steel and concrete to a large extent in spite of its major
advantage over reinforced concrete because many engineers are
not convinced about this material yet. Moreover, there are also
some professionals who, without a proper study, have said that fer-
rocement is not a good material. The main reason is that they com-
pare ferrocement to reinforced concrete. To adopt this material in
actual Egyptian practice and to enrichment the information and
understanding of its behavior, an experimental investigation was
performed on cementitious slabs of thickness greater than the
common thickness of ferrocement (range 1025 mm) and rein-
forced with low cost local steel wire mesh to cover some of itsbehavioral aspects under patch loading. Since punching shear fail-
ure in reinforced concrete slabs subjected to concentrated load is
brittle, evaluation of punching shear resistance of cementitious
slabs reinforced with wire mesh should also be highlighted. Punch-
ing shear has been the object of an intense experimental effort
since the 1950s. Punching failure of slabs based on experimental
results was addressed by various authors, among others: Menetrey
[3], Mansur et al. [4], Naaman et al. [5], and Aurelio Muttoni[6]
whereas experimental study of flexural behavior of ferrocement
and cementitious composite two way slabs were reported by many
investigator among them: El Debs and Naaman[7] and Shannag
et al.[8].
Since the punching capacity of cementitious slabs reinforced
with wire mesh is the main objective of this study, an experimental
investigation on 27 simply supported slabs is reported too. The
slabs were tested to failure to investigate the deformation and
strength characteristics under patch loading. The slab reinforce-
ment is either expanded steel mesh or a square mesh. Four types
of expanded steel mesh (diamond) and two types of square mesh
were used. The slabs were square of side length of 490 mm and
clear span of 400 mm. The specimens were provided with 8 mm
diameter skeletal steel bar as a square closed frame with inner side
dimension of 445 mm that should provide line support. Primary
variables investigated include also the volume fraction of rein-
forcement, the slab thickness: 40, 45, 50 and 60 mm; and the cen-
tric load pattern: square area of 80 80 mm or rectangular area of
55 360 mm.
0950-0618/$ - see front matter 2010 Elsevier Ltd. All rights reserved.doi:10.1016/j.conbuildmat.2010.06.032
* Tel.: +20 105110316; fax: +20 119187871.
E-mail address:[email protected]
Construction and Building Materials 25 (2011) 251259
Contents lists available at ScienceDirect
Construction and Building Materials
j o u r n a l h o m e p a g e : w w w . e l s e v i e r . c o m / l o c a t e / c o n b u i l d m a t
http://dx.doi.org/10.1016/j.conbuildmat.2010.06.032mailto:[email protected]://dx.doi.org/10.1016/j.conbuildmat.2010.06.032http://www.sciencedirect.com/science/journal/09500618http://www.elsevier.com/locate/conbuildmathttp://www.elsevier.com/locate/conbuildmathttp://www.sciencedirect.com/science/journal/09500618http://dx.doi.org/10.1016/j.conbuildmat.2010.06.032mailto:[email protected]://dx.doi.org/10.1016/j.conbuildmat.2010.06.032 -
8/13/2019 Experimental Investigation of Ultimate Capacity of Wired Mesh-reinforced Cementitious Slabs
2/9
2. Experimental program
The experimental program consists of 27 cementitious slabs. Two of these slabs
were the control specimens and made of plain mortar. For the sake of comparison
with traditional steel, two cementitious slab specimens reinforced with 6 mm
steel bars arranged in two orthogonal directions and spaced 100 mm apart were
cast. To evaluate the effect of combining traditional steel with wire mesh reinforce-
ment on the punching shear capacity, a diamond wire mesh of diameter 1.5 mm
was added to one of those slabs. All slab specimens were tested using a universal
testing machine under monotonic loading up to failure. The slabs were square witha side length of 490 mm and thickness of 4060 mm and were reinforced with a
single layer of wire mesh placed at 10 mm from the tension side. They are identified
using three abbreviated terms: the first term represents the wire mesh reinforce-
ment type (D for diamond and S for square mesh); the second term represents
the type of loading pattern (P for square patch loaded area of 80 80 mm with disk
height of 20 mm and L for rectangular loaded area of 55 360 mm with maximum
semi cylinder disk height of 70 mm at center area and, the last term represents the
thickness of wire mesh (3.0, or 0.63 mm for square mesh, and 2.0, or 1.50, or 0.7, or
0.30 mm for diamond mesh).
2.1. Materials and mixing proportions
The mortar matrix consisted of ordinary Portland cement complying with ESS
373[9]and ECCS 203[10]and sand passing through a No. 7 sieve (2.36 mm), free
from any deleterious substances. Grading of the sand was controlled in such a way
Table 1
Sieve analysis results for the sand.
Sieve size (mm) 2.36 1.18 0.600 0.300 0.150 0.075
% Passing by weight 100 86.54 61.63 24.77 3.69 0.88
Sand grading[2] 80 0 100 50 8 5 2 5 60 1 0 30 2 1 0 N/ A
Table 2
Types of mesh reinforcement.
Mesh type Long-way
(mm)
Transverse
(mm)
% Volume fraction
(h= 40 mm)
Diamond 0.3 mm 17.5 7.5 0.12
Diamond 0.7 mm 22.5 12.5 0.18
Diamond 1.5 mm 37.5 17.5 0.60
Diamond 2.0 mm 22.5 57.5 0.60
Galvanized square
0.63 mm
10 10 0.18
Square 3.0 mm 50 50 0.70
Square 6.0 mm 100 100 1.41
400mm
490 mm
Loadingarea360x55mm
400 mm
Loading disk 360x55 mm Loading disk 80x80 mm
480mm
400mm
490 mm
Loading plate
80 x 80 x 20 mm
Fig. 1. Set-up for panel test under patch and line loads.
Types of wire mesh
480mm
360mm
40 mm lab splice
445 mm
8 mm
diameter
steel bar490 mm
Wire Mesh
Steel bars 6 mm mesh
Fig. 2. Alternatives reinforcement details of the cementitious slabs.
252 H.M. Ibrahim / Construction and Building Materials 25 (2011) 251259
-
8/13/2019 Experimental Investigation of Ultimate Capacity of Wired Mesh-reinforced Cementitious Slabs
3/9
that it would confirm with the ACI 549-1R 93[2],ESS 1108[11]and ECCS 203[10].
Table 1shows the sieve analysis results of the sand. The sand and water to cement
ratios by weight were chosen to be 2 and 0.5 respectively to achieve a normal
strength with good workability.
At the time of casting, six companion cube specimens of size 70.6 70.6
70.6 mm were also cast to determine the ultimate compressive strength of ferroce-
ment mortar. Three prisms of 40 40 160 mm were cast to determine the flex-
ural tensile and compressive strengths[10]. All specimens were cured under wet
condition for 28 days and tested for compressive and flexural tensile strengths.
The average compressive cube strength was 32 MPa where prism flexural tensile
strength was 5.6 MPa.
Steel wire mesh fabrics locally produced in the form of rolls of 1 m wide and of
yield strength around 300 MPa were used. The wire mesh was tied to a framework
made from mild steel bar with a diameter of 8 mm. The reinforcement framework
was first fabricated and the wire mesh was tied to it, making a relatively strong
cage. The skeletal steel frame is not considered a structural reinforcement but to
serve as a spacer to the mesh reinforcements. The different types of wire mesh rein-
forcement used in the present work are listed in Table 2.As can be seen fromFig. 1, the tested specimens were simply supported on four
edges on a rigid steel frame. Either centric square or rectangular patch load was ap-
plied to a contact area of 80 80 mm or 55 360 mm respectively.Fig. 2shows the
details of reinforcement of the slab specimens and the different configurations of
reinforcing wire mesh.
2.2. Test procedure and instrumentation
Tested slabs were placed on a rigid steel frame as shown inFig. 3and a dial
gauge was centrally placed at the bottom face to record deflections at different
stages of loading. An opening along one of the steel frame sides was made to pro-
vide accessibility to the placement of dial gauge and to investigate cracking pro-
gress at the bottom face during testing. Either steel square plate of 20 mm thick
or cylindrical sector of projected rectangular area and maximum height of 75 mm
and was used to transfer the load from the machine to the top face of the slab.
After testing, the slab specimens were removed from the test setup and both topand bottom sides were examined to investigate the sustained damage, such as
yielding of reinforcement, punching shear failure surface and cracking pattern at
the bottom face.Fig. 3. Testing of specimens under central square patch loading.
Table 3
Test results for ultimate load, ultimate deflection and failure mode.
I.D. h
(mm)
Pu (kN) Du (mm) Failure description
Specimens without reinforcement
Slab-I 40 8.0 0.30 Two-way flexure failure (diagonal cracks)
Slab-II 40 8.4 0.25
Specimens reinforced with diamond mesh 0.30 mm volume fraction 0.12
DP-0.3 4 0 9 .1 1 .1 4 Flex ural failure in t wo way action four t riangles rup ture of mesh
DL-0.3 40 12.4 1.62 Two-way flexure failure (2 triangles and 2 trapezoidal) rupture of mesh
Specimens reinforced with square mesh 0.63 mm volume fraction 0.18
SL-0.63 50 21.4/22.4 1.7/4.93 Flexural failure in two way action (bridging effect)
SL-0.63 40 19.2 1.25 Sudden failure trapezoidal and triangular cracks at top neoprene bad
SP-0.63 4 5 1 4.6 0.79 Sudd en failure rup ture of reinforcement t wo way 4 tr iangle
SP-0.63 40 11.2 1.5 Flexural failure (diagonal cracks)
Specimens reinforced with diamond mesh 0.70 mm volume fraction 0.18
DP-0.7 4 0 1 3.4 1 .7 3 Flex ural failure in t wo way action four t riangles rup ture of mesh
DP-0.7 40 13.8 2.47
DL-0.7 40 19.8 4.66 Two-way flexure failure (2 triangles and 2 trapezoidal) rupture of mesh
Specimens reinforced with diamond mesh 1.50 mm volume fraction 0.60
DP-1 .5 5 0 2 3.8 2 .7 9 Flex ural failure rupt ure of mesh along b ot h diagonals
DP-1.5 50 22.4 2.07 Flexural failure fracture of mesh reinforcement
DP-1.5 40 22.3 3.77 Flexural failure Rupture of mesh
DL-1.5 40 38.5 2.49 Flexural failure nearly one way action
Specimens reinforced with diamond mesh 2.0 mm volume fraction 0.60DP-2.0 40 19.6 6.29 Flexural bond failure two way action
DP-2.0 40 20.5 3.97
DP-2.0 60 29.5 3.78 Flexural failure in two way action
DP-2.0 50 25.0 4.49 Punching failure no mesh rupture mesh yield
DP-2.0 50 23.8 8.2 Flexural punching failure diagonal cracks at bottom face at top face cracks around loaded area and extend
diagonally from the corner of the loaded area to the corners of the slab
DL-2.0 50 35.6 20.91 Punching failure neoprene bad used at bottom triangle and trapezoidal cracks crack lines along line load
boundary half circle cracks around load edges at top face
Specimens reinforced with square mesh 3.0 mm volume fraction 0.70
SL-3.0 40 68.4 4.35 Punching failure different shape of crack
SP-3.0 40 31.0 7.46 Punching failure rupture of mesh
SP-3.0 40 25.6 6.70 Punching failure rupture of mesh
SP-3.0 50 36.0 5.32 Punching failure yield of mesh
Specimens reinforced with 6 @ 100 mm both ways volume fraction 1.41
6 mm 50 34.5 6.19 Punching failure steel yielded
6 mm+DP-
1.5
50 45.8 4.77 Flexural punching failure cracks at slab corners
H.M. Ibrahim / Construction and Building Materials 25 (2011) 251259 253
-
8/13/2019 Experimental Investigation of Ultimate Capacity of Wired Mesh-reinforced Cementitious Slabs
4/9
3. Test results and discussion
In the present work the load versus central deflection curves for
the tested slabs were used to classify the failure type. Flexural fail-
ure is considered to take place in slabs in which most of the rein-
forcement yields before punching occurs and consequently the
slabs exhibits large deflection prior to failure. The flexural failure
is characterized by a smooth decrease of the carrying load withincreasing displacement. Shear failure was defined when a sudden
decrease of the load carrying capacity after the peak load has been
reached (nearly vertical branch of the load deflection curve).
On the other hand, the cracking and failure pattern were also
used to classify the failure type. Slabs were considered to fail in
flexure in the case of observing diagonal cracks extending from
the center of the patch area. Flexural punching failure occurred
as tangential crack at the outlines of patch area, followed by diag-
onal cracks extending from that area and a nearly flat plateau of
resistance was reached. The failure progressed with the rupture
of bottom reinforcement. Punching failure was monitored in some
of the tests as the load fell suddenly and was released completely.
Table 3summarizes the peak load, displacement at peak load, and
failure mode for all test specimens.
The reference slabs I and II were tested to define the ultimateload carrying capacity of plain mortar specimens, include a skeletal
frame, in flexure under monotonic patch load. Comparing the
ultimate load and deflection at ultimate load (Figs. 4 and 5), it
was found that adding diamond mesh of volume fraction of 0.12,
slab DP-0.30 and DL-0.30, increases the ultimate load under patch
and line loads by 11% and 48% respectively, whereas the deflection
0
1
2
3
4
5
6
7
8
9
10
0.0 0.1 0.2 0.3 0.4
Deflection (mm)
Load(kN)
Rreference Slab - I - h = 40 mm
Reference Slab - II - h = 40 mm
Fig. 4. Load versus deflection at center of plain mortar slabs under patch load.
0
2
4
6
8
10
12
14
0.0 1.0 2.0 3.0 4.0 5.0 6.0
Deflection (mm)
Load(kN)
DP-0.3 mm - h = 40 mm
DL-0.3 mm - h = 40 mm
Fig. 5. Comparison of load versus deflection response at center of slabs reinforcedwith 0.3 mm diamond mesh under patch and line loads.
Fig. 6. Failure pattern of slab DL-0.30 mm under linear loads.
Fig. 7. Specimen, DP-0.70 mm typical failure pattern under patch loads.
0
5
10
15
20
25
0.0 1.0 2.0 3.0 4.0 5.0 6.0
Deflection (mm)
Load(kN)
DP-0.7 mm - h = 40 mm
DL-0.7 mm - h = 40 mm
DP-0.7 mm - h = 40 mm
Fig. 8. Comparison of load versus deflection response at center of slabs reinforcedwith 0.7 mm diamond mesh under patch and line loads.
254 H.M. Ibrahim / Construction and Building Materials 25 (2011) 251259
-
8/13/2019 Experimental Investigation of Ultimate Capacity of Wired Mesh-reinforced Cementitious Slabs
5/9
at ultimate load was increased by 418% and 589% respectively. It is
obvious that the effect of using wire mesh significantly increases
ductility. In both cases, flexural failure was observed as shown in
Fig. 6. Similarly, for slab DP-0.7 subjected to patch load, flexural
failure mode was also obtained as presented inFig. 7. Comparing
the results of ultimate load and deflection for 40 mm slab thickness
under square patch load for the slabs DP-0.30 (Vf = 0.12) and DP-
0.7 (Vf = 0.18) shown inFigs. 5 and 8, it was found that the ulti-mate load was increased by nearly 50% whereas the ultimate
deflection was increased by 84%. For 40 mm slab thickness under
line load, the results of ultimate load and deflection of slabs DL-
0.30 and DL-0.7 shown inFigs. 5 and 8, it was found that the ulti-
mate load and deflection were increased by nearly 60% and 288%
respectively. It is worth mention that the slabs of diamond mesh
0.7 fail in flexural pattern.
For slabs reinforced with single layer of square mesh and of the
same thickness SP-0.63 (Vf= 0.18) illustrated inFig. 9and Table 3
which tested under square patch load, the ultimate load and
deflection were decreased than those of DP-0.7 (Vf= 0.18) by 21%
and 40% respectively. Under rectangular line load the percentage
decrease was 3% and 372% respectively. The ductile nature of dia-
mond mesh over square mesh was obvious from these results. The
results of slabs reinforced with square mesh show increase in the
stiffness and reduction in ductility by increasing the slab thickness
in both loading patterns adopted in this work.
Since flexural failure mode is dominant in slabs with small per-
centage of reinforcement, increasing thickness did not alter the
failure mode as illustrated in slabs SP-0.63 of 40 and 45 mm thick-
ness. In such cases, higher slab thickness led to stiffness increase
and consequently decrease in ductility. For slabs of moderate vol-
ume fraction as slabs DP-2.0, failure mode may change from flex-
ure failure (40 mm) to flexural punching or even pure punching
failure (50 mm). The failure mode may change again to flexure fail-
ure as the thickness increase (60 mm). Therefore, changing slab
thickness is an attempt aimed to define the slab thickness that con-
trols the failure mode. Increasing volume fraction (main Steel per-
centage, i.e., dowel action) is not effective as the depth increase tochange the failure mode.
Comparing the results of ultimate load and deflection for
50 mm slab thickness under square patch load for DP-1.5
(Vf= 0.60) and DP-2.0 (Vf= 0.60) of Figs. 10 and 11, it was found
that the average ultimate load was almost the same whereas the
ultimate deflection of slab DP-2.0 was greater by almost two and
half times. For slabs of 40 mm, the difference of results between
the two meshes did not vary significantly. For line loads, the con-
clusion is similar to that of square patch load case.It was observed that slabs DP-1.5 failed in flexural mode under
square patch load whereas a punching failure mode was noticed
under rectangular line loading as shown inFigs. 12 and 13. The fail-
ure pattern of slabs DP-2.0 was flexural punching for slab thickness
50 mm under both cases of loading as shown inFigs. 14 and 15. For
slabs of 40 mm and 60 mm it was found that, the failure mode was
0
5
10
15
20
25
0.0 2.0 4.0 6.0 8.0 10.0 12.0
Deflection (mm)
Load(k
N)
SP-0.63 mm - h = 40 mm
SL-0.63 mm - h = 40 mm
SP-0.63 mm - h = 45 mm
SL-0.63 mm - h = 50 mm
Fig. 9. Comparison of load versus deflection response at center of slabs reinforcedwith 0.63 mm square mesh under patch and line loads.
0
5
10
15
20
25
30
35
40
0.0 2.0 4.0 6.0 8.0 10.0 12.0
Deflection (mm)
Load(kN)
DP-1.5 mm - h = 50 mm
DP-1.5 mm - h = 50 mm
DL-1.5 mm - h = 40 mm
DP-1.5 mm - h = 40 mm
Fig. 10. Comparison of load versus deflection response at center of slabs reinforced
with 1.5 mm diamond mesh under patch and line loads.
0
4
8
12
16
20
24
28
32
36
0.0 3.0 6.0 9.0 12.0 15.0 18.0
Deflection (mm)
Load(kN)
DP-2.0 mm - h = 40 DP-2.0 mm - h = 50
DP-2.0 mm - h = 60 DP-2.0 mm - h = 50
DP-2.0 mm - h = 40 DL-2.0 mm - h = 50
Fig. 11. Comparison of load versus deflection response at center of slabs reinforcedwith 2.0 mm diamond mesh under patch and line loads.
H.M. Ibrahim / Construction and Building Materials 25 (2011) 251259 255
-
8/13/2019 Experimental Investigation of Ultimate Capacity of Wired Mesh-reinforced Cementitious Slabs
6/9
flexure as shown in Fig. 16. The failure pattern of slab SP-3.0
(Vf= 0.70) was punching for all slab thickness tested in this work
and under both cases of loading as shown inFigs. 17 and 18.
Since flexural failure mode is dominant in slabs with small per-
centage of reinforcement, increasing thickness did not alter the
failure mode as illustrated in slabs SP-0.63 of 40 and 45 mm thick-
ness. In such cases, higher slab thickness led to stiffness increase
and consequently decrease in ductility. For slabs of moderate vol-
ume fraction as slabs DP-2.0, failure mode may change from flex-
ure failure (40 mm) to flexural punching or even pure punching
failure (50 mm). The failure mode may change again to flexure fail-
ure as the thickness increase (60 mm). Therefore, changing slab
thickness is an attempt aimed to define the slab thickness that con-
trols the failure mode. Increasing volume fraction (main Steel per-
(b) bottom face(a) top face
Fig. 12. Specimen, DP-1.5 mm, after failure.
(b) bottom face(a) top face
Fig. 13. Specimen, DL-1.5 mm, after failure.
(a) top face (b) under loading disk (c) bottom face
Fig. 14. Specimen, DP-2.0 mm h = 50 mm, after punching failure.
(a) top face (b) bottom face
Fig. 15. Specimen, DL-2.0 mm, after punching failure.
256 H.M. Ibrahim / Construction and Building Materials 25 (2011) 251259
-
8/13/2019 Experimental Investigation of Ultimate Capacity of Wired Mesh-reinforced Cementitious Slabs
7/9
centage, i.e., dowel action) is not effective as the depth increase to
change the failure mode.
An attempt was made to evaluate the effect of combining wire
mesh of diamond shape to ordinary reinforcing steel as a reinforce-
ment of cementitious slabs. Two slabs were reinforced with steel
bars of diameter 6 mm and spaced 100 mm in the two orthogonal
directions of the slabs. One of them was additionally reinforced
with a diamond wire mesh of volume fraction of 0.18. The results
of load versus deflection and the failure patterns of these slabs are
shown inFigs. 1921. Punching failure patterns were observed for
both slabs. The contribution of diamond mesh was noticed through
an increase of the ultimate load by 32% and a decrease in deflection
at ultimate load by 30% as shown in Table 4. The recognized in-
crease in the ultimate punching capacity was referred to the dowel
action contribution of the wire mesh. Since the two orthogonal
directions of the mesh have different geometries and structure,
their bridging effects were also different as clearly shown in load
deflection curves of slabs loaded with rectangular area, where both
the mesh directions and the loaded area were different.
(a) top face (b) bottom face (c) enlarged part showsmesh rupture
Fig. 17. Specimen, SP-3.0 mm h = 40 mm, after punching failure.
Fig. 16. Specimen, DP-2.0 mm h = 60 mm, after flexural failure.
0
10
20
30
40
50
60
70
0.0 2.0 4.0 6.0 8.0 10.0 12.0 14.0 16.0 18.0
Deflection (mm)
Load(kN)
SP- 3.0 - h = 40
SP-3.0 - h = 40
SL-3.0 - h = 40
SP-3.0 - h = 50
Fig. 18. Comparison of load versus deflection response at center of slabs reinforcedwith 3.0 mm square mesh under patch and line loads.
0
5
10
15
20
25
30
35
40
45
50
0.0 5.0 10.0 15.0 20.0 25.0
Deflection (mm)
Load(k
N)
D 6mm@100 mm-h=50
DP-1.5mm+D 6mm@100mm -h=50
Fig. 19. Effect of adding 1.5 mm diamond mesh to slabs reinforced with ordinary
reinforcing steel bars of6 mm @ 100 mm both ways on the load-deflectionresponse at center of the slab.
H.M. Ibrahim / Construction and Building Materials 25 (2011) 251259 257
-
8/13/2019 Experimental Investigation of Ultimate Capacity of Wired Mesh-reinforced Cementitious Slabs
8/9
On the other hand, a comparison between the slab reinforced
with steel bars of diameter 6 mm and other specimens of the same
thickness 50 mm was made and presented inTable 4. For diamond
meshes of the same volume fraction of 0.6%, an average ultimate
capacity of 70% was obtained. However, the ductility of wider spac-
ing mesh is nearly twice times greater than that of the narrow one.
For square mesh of volume fraction of 0.6%, the ultimate capacity
obtained by 6 mm diameter ordinary steel mesh was attained with
a loss of ductility of 14%.
4. Conclusion
The following observations and conclusions were drawn for
similar slabs to those tested in the present work:
1. Using single layer of diamond wire mesh of low volume fraction
of 0.12% leads to numerous increase of plain cementitious slabs
ductility by more than four times. On the other hand, the ulti-
mate capacity was slightly increased by more than 10% for
the cases of loading considered in the present study. Hence,
the key influence of low volume fraction diamond mesh is ded-
icated to ductility improvement. Moreover, increasing the vol-
ume fraction of diamond mesh by 50% consequently increases
the ultimate load and accompanied deflection by 50% and 84%respectively.
2. Under line rectangular loading, the ultimate load and accompa-
nied deflection for slabs reinforced with diamond mesh were
increased significantly than those tested under square patch
load by nearly 60% and 288% respectively. In some cases the
failure mode may alter from punching to a flexural pattern.
3. For specimens of similar thickness and volume fraction, slabsreinforced with square meshes exhibit a reduction of ultimate
load and deflection than those of slabs reinforced with diamond
mesh by 21% and 40% respectively. The ductile nature of dia-
mond mesh over square mesh was obvious from these results.
4. For slabs reinforced with diamond mesh of similar volume frac-
tion, the mesh of wider openings configuration, DP-2.0,
revealed a ductility increase to nearly two and half times than
that of closer openings, DP-1.5, while the ultimate load is nearly
kept equal. However, the failure mode may alter between flex-
ure and punching according to the opening size of the mesh and
the loading pattern. Contrary, slabs reinforced with square
mesh, SP-3.0, examined a punching failure for all slab thickness
and under both cases of loading.
5. Adding a diamond mesh to traditionally reinforced cementi-tious slabs did not amend its punching failure mode. Neverthe-
less, it increases the ultimate load capacity due to the dowel
action contribution of the wire mesh accompanied with a
reduction of the deflection at ultimate load. A volume fraction
of 0.18% increases the ultimate load capacity by nearly 30%
associated with a reduction of the deflection at ultimate load
by almost the same percentage.
6. Since, the two orthogonal directions of the diamond mesh have
different geometries and structures; the bridging effect is
expected to arise. This is clearly recognized from the load
deflection diagram of slabs loaded with rectangular line load,
where both mesh and loaded area were different in the two
orthogonal directions.
7. More research study is needed to identify the volume fractionratio at which the mode of failure alter between flexure and
(a) top face (b) bottom face
Fig. 20. Punching failure of slab reinforced with bars 6 mm @ 100 mm.
(a) top face (b) bottom face
Fig. 21. Failure of slab with bars 6 mm @ 100 mm and 1.5 mm diamond mesh.
Table 4
Wired mesh versus 6 mm ordinary steel specimens (50 mm).
Specimen designation Volume fraction Pu/Pu(6) Du/Du(6)
DP-1.5 0.60 0.69 0.45
DP-1.5 0.60 0.65 0.33
DP-2.0 0.60 0.72 0.73DP-2.0 0.60 0.69 1.32
SP-3.0 0.60 1.04 0.86
6 mm + DP-1.5 2.01 1.33 0.77
258 H.M. Ibrahim / Construction and Building Materials 25 (2011) 251259
-
8/13/2019 Experimental Investigation of Ultimate Capacity of Wired Mesh-reinforced Cementitious Slabs
9/9
punching with particular attention to the opening size of the
mesh and loading configuration.
References
[1] ACI Committee 549. State-of-the-art report on ferrocement. ACI 549-R97manual of concrete practice, Detroit; 1997.
[2] ACI Committee 549-1R-88. Guide for design construction and repair offerrocement. ACI 549-1R-88 and 1R-93 manual of concrete practice, Detroit;1993.
[3] Menetrey Ph. Synthesis of punching failure in reinforced concrete. Cem ConcrCompos 2002;24:497507.
[4] Mansur MA, Ahmad I, Paramasivam P. Punching shear strength of simplysupported ferrocement slabs. J Mater Civil Eng 2001;6(13):41826.
[5] Naaman AE, Likhitruangsilp V, Gustavo PM. Punching shear response of highperformance fiber reinforced cementitious composite slabs. ACI Struct J2007;104(2):1709.
[6] Muttoni A. Punching shear strength of reinforced concrete slabs withouttransverse reinforcement. ACI Struct J 2008;105(4):44050.
[7] El Debs MK, Naaman AE. Bending behavior of mortar reinforced with steelmeshes and polymeric fibers. Cem Concr Compos 1995;17(4):32738.
[8] Shannag MJ, Tareq BZ. Flexural response of ferrocement with fibrouscementitious matrices. Construct Build Mater 2007;21:1198205.
[9] ESS No. 373. Portland cement, ordinary, and rapid hardening. Egyptian
Standard Specifications Ministry of Industry Cairo; 1991.[10] ECCS 203-2009. Egyptian code of practice for design and construction of
reinforced concrete structures. 2nd ed.; 2004.[11] ESS No. 1108. Sand for masonry mortars. Egyptian Standard Specification
Ministry of Industry Cairo; 1971.
H.M. Ibrahim / Construction and Building Materials 25 (2011) 251259 259