     New Site External alarm implementation guide

    For new site External we have two scenario:

    1.  ZTE ODU External Alarm Configuration (With Sceco)2.  ZTE ODU EXTERNAL ALARM CONFIGURATION TEST (With Genset)

    ZTE ODU External Alarm Configuration (With Sceco)

    Alarm

    No.Designation

    DDF

    SLOTRemarks Connection

    1 Door Cabinet Open(WHITE /

    BLUE) 

    1 Connected directly to

    BBU SA Card

    Sensor - DDF 1 - BBU SA

    2 High Temperature(WHITE /

    ORANGE) 

    2 Connected directly to

    BBU SA Card

    Sensor - DDF 2 - BBU SA

    3 Tower Light Failure

     Alarm(WHITE / GREEN)

    3 Connected directly to

    BBU SA Card

    Sensor - DDF 3 - BBU SA

    4 Rectifier Alarm (WHITE /

    BROWN)

    4 From B201 SIB Board

    (Power Unit) - X15 port

    X15 - DDF 4 - BBU SA

    5 AC Power Fail(WHITE / GRAY)  5 From B201 SIB Board

    (Power Unit) - X16 port

    X16 - DDF 5 - BBU SA

    6 Environmental Over

    Humidity(RED / BLUE)

    6 From B201 SIB Board

    (Power Unit) - X16 port

    X16 - DDF 6 - BBU SA

    7 DC Low Voltage alarm(RED /

    ORANGE) 

    7 From B201 SIB Board

    (Power Unit) - X17 port

    X17 - DDF 7 - BBU SA

    8 SMOKE Alarm(RED / Green)  8 From B201 SIB Board

    (Power Unit) - X17 port

    X17 - DDF 8 - BBU SA

  • 8/18/2019 External alarm implementation

    2/15

     

    内部公开 Internal Use Only▲ 

     

    All Rights reserved, No Spreading abroad without Permission of ZTE 

    第 2页 

    SA card

    (BS8800)

    D

    D

    F

    Medium light alarm cable

    Door open alarm

    DDF Port 1

    Rectifier alarm

    DDF Port 4

    Tower Light Failre Alarm

    DDF Port 3

    High tep. Alarm

    DDF Port 2

    Door 1 sensor 

    AC1(1500W) alarm cable

    Smoke alarm

    DDF Port 8

    DC Low voltage alarm

    DDF Port 7

    Environmental over humidity alarm

    DDF Port 6

    AC power fail alarm

    DDF Port 5

    ODU Cabinet

    Door 2 sensor 

    AC2(1500W) alarm cable

    AC3(500W) alarm cable

    Smoke sensor 

    B201 X15 Port(NC/COM)

    B201 X16 Port(NC/COM)

    B201 X16 Port(NC/COM)

    B201 X17 Port(NC/COM)

    B201 Module

    Tower 

    ZTE ODU External Alarm Drawing With Sceco)

    Low light alarm cable

    Low light alarm cable

    Junction

     box

    Control

     box

    B201 X17

    Port(NC/COM)

    Actual

    virtual

    B201 X24

    Port

     

     NodeB(BS8800) part:

    SA card

    (BS8800)

    D

    D

    F

     

    For New site External alarm we through BS8800 SA card report to EMS/OMC.all external alarm sensor

    should be connect to SA card through DDF terminal.before connect sensor,please make loop back test

    from DDF to OMC,make sure 8channel no any cross.it very important for test external alarm.

    External alarm connection :

    SA card-------SA cable(B3 connector)---------SA E1 Cable----------DDF-------each sensor

    1.  SA cable :material code: 052740402435 DS-91228-001|Digital Signal Cable

  • 8/18/2019 External alarm implementation

    3/15

     

    内部公开 Internal Use Only▲ 

     

    All Rights reserved, No Spreading abroad without Permission of ZTE 

    第 3页 

    2.SA E1 Cable: material code: 052740402185 DS-91223-002|Digital Signal Cable

    We used core color(new)

  • 8/18/2019 External alarm implementation

    4/15

     

    内部公开 Internal Use Only▲ 

     

    All Rights reserved, No Spreading abroad without Permission of ZTE 

    第 4页 

    3.connection picture:

  • 8/18/2019 External alarm implementation

    5/15

     

    内部公开 Internal Use Only▲ 

     

    All Rights reserved, No Spreading abroad without Permission of ZTE 

    第 5页 

     No1. Door Cabinet Open(WHITE / BLUE)(in DOU cabinet) 

    SA card

    (BS8800)

    D

    D

    F

    Door open alarm

    DDF Port 1

    Door 1 sensor ODU Cabinet

    Door 2 sensor 

    Door1 and Door2 Sensor cable need parallel connect to DDF port1

    Door 1 Sensor :

    Door2 Sensor

    Door 1&Door 2 Sensor cable :

  • 8/18/2019 External alarm implementation

    6/15

     

    内部公开 Internal Use Only▲ 

     

    All Rights reserved, No Spreading abroad without Permission of ZTE 

    第 6页 

     No 2.High Temperature(WHITE / ORANGE) (in DOU cabinet) 

    SA card

    (BS8800)

    D

    D

    F

    High tep. Alarm

    DDF Port 2

    AC1(1500W) alarm cable

    ODU Cabinet

    AC2(1500W) alarm cable

    AC3(500W) alarm cable

     

    AC1&AC2&AC3 Alarm cable need parallel connect to DDF port2

    1.AC1(1500W)alarm cable:(Location:in Door1 up area Port:NC/COM)

  • 8/18/2019 External alarm implementation

    7/15

     

    内部公开 Internal Use Only▲ 

     

    All Rights reserved, No Spreading abroad without Permission of ZTE 

    第 7页 

    2.AC2(1500W)alarm cable:(Location:in Door2 up area Port:NC/COM)

    3.AC3(500W)alarm cable:(Location:in Door2 down area Port:NC/COM)

    4.alarm cable in ODU location

  • 8/18/2019 External alarm implementation

    8/15

     

    内部公开 Internal Use Only▲ 

     

    All Rights reserved, No Spreading abroad without Permission of ZTE 

    第 8页 

     No 3.Tower Light Failure Alarm(WHITE / GREEN)-on tower

    SA card

    (BS8800)

    D

    D

    F

    Medium light alarm cable

    Tower Light Failre Alarm

    DDF Port 3

    Tower 

    Low light alarm cable

    Low light alarm cable

    Junction

     box

    Control

     box

     

    Tower lignht Alarm cable(alarm output in control box) need connect to DDF port3

    Medium light(1pcs) /low light(2pcs) cable (Brow/blue) connect to Junction box alarm input terminal,

    From Junction box connect to Control box alarm input terminal, From Control box alarm outputconnect to DDF port3 terminal. For detail connection please reference installation and operation

    manual in the box.

  • 8/18/2019 External alarm implementation

    9/15

     

    内部公开 Internal Use Only▲ 

     

    All Rights reserved, No Spreading abroad without Permission of ZTE 

    第 9页 

     No 4. Rectifier Alarm (WHITE / BROWN)

     No 5. AC Power Fail(WHITE / GRAY)

     No 6.Environmental Over Humidity(RED / BLUE)

     No 7.DC Low Voltage alarm(RED / ORANGE) 

    SA card

    (BS8800)

    D

    D

    F

    Rectifier alarm

    DDF Port 4

    DC Low voltage alarm

    DDF Port 7

    Environmental over humidity alarm

    DDF Port 6

    AC power fail alarm

    DDF Port 5

    B201 X15 Port(NC/COM)

    B201 X16 Port(NC/COM)

    B201 X16 Port(NC/COM)

    B201 X17 Port(NC/COM)

     

    Rectifier Alarm From X15 NC/COM connect to DDF port4 AC Power Fail From X16 NC/COM connect to DDF port5

    Environmental Over Humidity From X16 NC/COM connect to DDF port6

    DC Low Voltage alarm From X17 NC/COM connect to DDF port7

    Below description detail how to setting external alarm in ZXDU68 B201 system.

    About the relay alarm of the ZXDU68B201 power supply system

    The boards of the zxdu68 B201system is integrated in the signal transfer box. Figure as below:

    shown the board layout.

  • 8/18/2019 External alarm implementation

    10/15

     

    内部公开 Internal Use Only▲ 

     

    All Rights reserved, No Spreading abroad without Permission of ZTE 

    第 10页 

    1.   Network interface board(IP/SNMP);

    2.  Modem power board(MPB);

    3.  Signal interface board(SIB)

    And the signal interface board provides external communication interfaces and monitoring

    unit signal interfaces. The signal board is shown in figure as below. Refer to table for the

    signal board interfaces description.

    Figure signal board:

    Table signal interface name

    Interface Interface name Interface Interface name

    X4 Battery 1 temperature X21 RS485 interface

    X5 Battery 2 temperature X22 Rs232 interface

    X12 Temperature control X23 Flood alarm

    X14 Input relays 1,2,3,4 X24 Smoke alarm

    X15 Out relays 1,2 X25 Ambient temperature

    X16 Out relays 3,4 X26 Intrusion alarm

    X17 Out relays 5,6

    Then the relays alarm function need to three interface: X15 X16 X17.

    So the relays alarm function of the signal interface definition as belowTable-1:

    Interface Pin Signal

    definition

    Signal description Relay alarm definition

    (monitor parameters)

    X15

    Output relays1,2

    1 2NO Relay output 2-NO(normally open) A3

    2 2COM Relay output 2-Common end A33 2NC Relay output 2-NC(normally closed) A3

  • 8/18/2019 External alarm implementation

    11/15

     

    内部公开 Internal Use Only▲ 

     

    All Rights reserved, No Spreading abroad without Permission of ZTE 

    第 11页 

    4 1NO Relay output 1-NO --

    5 1COM Relay output 1-Common end --

    6 1NC Relay output 1-NC --

    X16

    Outputrelays3,4

    1 4NO Relay output 4-NO A5

    2 4COM Relay output 4-Common end A53 4NC Relay output 4-NC A5

    4 3NO Relay output 3-NO A2

    5 3COM Relay output 3-Common end A2

    6 3NC Relay output 3-NC A2

    X17

    Output relays

    5,6

    1 6NO Relay output 6-NO A4

    2 6COM Relay output 6-Common end A4

    3 6NC Relay output 6-NC A4

    4 5NO Relay output 5-NO A5

    5 5COM Relay output 5-Common end A5

    6 5NC Relay output 5-NC A5

    The relays alarm function has two options on the signal board, one relay output-NO(normal open)

    and one relay output-NC(normal close). So need to know the BTS interface alarm definition

    which it is NO or NC.

    If it is ‘ NO’, and connect relay alarm cables step:

    1、 One group relay out need two signal cables , and one terminal connect with relay out  – ON and

    relay output  – common end on the signal board interface, another terminal connect with the

    BTS interface.

    DDF

    NO

     O ON

     

    2、 Other relays alarm as above the connection step, until it finished.

    After finished to connect the signal cables , and set parameters in the monitor.

    Step:

    1、check the monitor screen, find the CTRL menu.

  • 8/18/2019 External alarm implementation

    12/15

     

    内部公开 Internal Use Only▲ 

     

    All Rights reserved, No Spreading abroad without Permission of ZTE 

    第 12页 

    2、 press the button ENTER of the monitor.

    3、 Entering the password: 0000.

    4、 Enter the setup parameter system: 1. Setup Para, press the Enter button.

    5、 Find the Alarm Para in the Setup Para.

    6、 Enter the Alarm Para menu, find the 1.Set Relay to Enter

    7、 And find the relays alarm parameter. According to the relays alarm requirements, set the relay

  • 8/18/2019 External alarm implementation

    13/15

     

    内部公开 Internal Use Only▲ 

     

    All Rights reserved, No Spreading abroad without Permission of ZTE 

    第 13页 

    alarm.

    Setup procedures: 

    If the relay alarm connected the X15(1,2) of the signal board, it mean what it is SMR Alarm.

    So the relay alarm parameter set A2.

    Refer to above the Table-1.

    Figure (set parameter:

     No 8. SMOKE Alarm(RED / Green) 

    SA card

    (BS8800)

    D

    D

    F

    Smoke alarm

    DDF Port 8

    ODU Cabinet

    Smoke sensor B201 X17

    Port(NC/COM)

    B201 X24

    Port

     

    Smoke alarm From Smoke sensor first connect to X24,then X17 NC/COM connect to DDF port8

  • 8/18/2019 External alarm implementation

    14/15

     

    内部公开 Internal Use Only▲ 

     

    All Rights reserved, No Spreading abroad without Permission of ZTE 

    第 14页 

    ZTE ODU EXTERNAL ALARM CONFIGURATION TEST (With Genset)

    Alarm

    No.Designation

    DDF

    SLOT

    DRY Contact Alarm

    ConnectionConnection

    1 Door Cabinet Open(WHITE / BLUE)  1Connected directly to BBU SA

    CardSensor - DDF 1 - BBU SA

    2 High Temperature(WHITE / ORANGE)  2Connected directly to BBU SA

    CardSensor - DDF 2 - BBU SA

    3 Rectifier Alarm (WHITE / GREEN) 3From B201 SIB Board

    (Power Unit) - X15 port X15 - DDF 3 - BBU SA

    4 AC Power Fail(WHITE / BROWN)  4From B201 SIB Board

    (Power Unit) - X16 portX16 - DDF 4 - BBU SA

    5

    Environmental Over Humidity(WHITE /

    GRAY) 5

    From B201 SIB Board

    (Power Unit) - X16 port X16 - DDF 5 - BBU SA

    6 DC Low Voltage alarm(RED / BLUE)  6From B201 SIB Board

    (Power Unit) - X17 portX17 - DDF 6 - BBU SA

    7 Generator Fault(RED / ORANGE)  7From Generator Control Port

    connected directly to SA CardGenerator Control - DDF 7 - BBU SA

    8 Generator Low Fuel(RED / GREEN)  8From the Storage Tank

    Connected directly to SA CardStorage Tank Sensor - DDF 8 - BBU SA

    SA card

    (BS8800)

    D

    D

    F

    Generator

    Door open alarm

    DDF Port 1

    Rectifier alarm

    DDF Port 3

    Generator Fault

    DDF Port 7

    High tep. Alarm

    DDF Port 2

    Door 1 sensor 

    AC1(1500W) alarm cable

    DC Low voltage alarm

    DDF Port 6

    Environmental over humidity alarm

    DDF Port 5

    AC power fail alarm

    DDF Port 4

    ODU Cabinet

    Door 2 sensor 

    AC2(1500W) alarm cable

    AC3(500W) alarm cable

    B201 X15 Port(NC/COM)

    B201 X16 Port(NC/COM)

    B201 X16 Port(NC/COM)

    B201 X17 Port(NC/COM)

    B201 Module

    Generator 

    ZTE ODU External Alarm Drawing With Genset)

    Genterator tank 

    Actual

    virtual

    Generator Low Fuel

    DDF Port 8

     

  • 8/18/2019 External alarm implementation

    15/15

     

    内部公开 Internal Use Only▲ 

     

    All Rights reserved, No Spreading abroad without Permission of ZTE 

    第 15页 

    For alarm No.1 —  No.6,please refer ZTE ODU EXTERNAL ALARM CONFIGURATION TEST

    (With Sceco) installation.

     No7. Generator Fault(RED / ORANGE)

     No8 Generator Low Fuel(RED / GREEN) 

    SA card

    (BS8800)

    D

    D

    F

    GeneratorGenerator Fault

    DDF Port 7

    Generator 

    Genterator tank Generator Low Fuel

    DDF Port 8