f gfr3300 heated safety station with eyewash, ieee ... · compliant with ieee standard 515-2011....

3
Freeze-Resistant Units Guardian Equipment 312 447 8100 TELEPHONE 1140 N North Branch St 312 447 8101 FACSIMILE Chicago, IL 60642 gesafety.com Listed 8116. Units have been tested to and comply with ANSI Z358.1-2014 and the Uniform Plumbing Code. Application: IEEE compliant heat-traced station includes control panel with single point connection for electrical components. Thermostat regulated units are heated by self-limiting heat-tracing cable wrapped around internal pipe. Units prevent freezing in extreme conditions down to -40º F. See ‘Tempering Valves’ section to ensure tepid water compliance with ANSI Z358.1-2014. Compliant with IEEE standard 515-2011. Control Panel: Single point connection for electrical components. Includes power indicator light, heat trace indicator light and high/ low temperature warning lights. Panel includes dry contacts to signal power failure or high/low temperature warning. Panel also includes dry contacts to signal an event when alarm options are installed. UL listed NEMA 4X approved for Class I, Division 2, Groups B, C, and D. Heating Cable: Self-regulated with external termination guards. Heating cable activates when internal piping temperature falls below 75°F. FM, UL, and CSA approved for Class I, Division 2, Groups B, C, and D. Electrical System: Unit is fully wired at factory. Junction box and components rated for Class I, Division 2, Groups B, C, and D. Requires 120 VAC single phase power supply. Jacket/Insulation: UV-resistant orange ABS plastic with polyethylene foam insulation. Jacket sections secured with removable stainless steel screws for easy maintenance. Shower Head: 10” diameter orange ABS plastic with 20 GPM flow control. Shower Valve: 1” IPS brass stay-open ball valve. US-made with brass ball and PTFE seals. Includes stainless steel actuating arm and 29” stainless steel pull rod. Spray Head Assembly: Freeze-resistant with float-off dust covers and internal flow control. Eyewash Valve: 1/2” IPS brass three-way self-draining stay-open ball valve. US-made with brass ball and PTFE seals. Includes 1/2” NPT female port to drain water from spray heads after use. Pipe and Fittings: Schedule 40 galvanized steel. Supply: 1-1/4” NPT female top inlet. Sign: ANSI-compliant identification sign. Quality Assurance: Factory tested prior to shipment. Ships fully assembled and crated. Alarm Options Specify desired alarm using fourth digit of model number, as follows: 0 No alarm 1 Single pole, double throw flow switch for remote sensing capability 3 Alarm horn and remote sensing capability 5 Light and remote sensing capability 7 Alarm horn, light and remote sensing capability Power Cable Heat Tracing High Temperature Warning Low Temperature Warning LISTED THERMOSTAT FOR USE IN HAZARDOUS LOCATIONS E358614 Control Panel with power indicator, trace indicator and high/low temperature warning lights. Model GFR3307 shown. F GFR3300 Heated Safety Station with Eyewash, IEEE Compliant, Top Inlet, Rated for Class I, Division 2 Environment Available Options F SSH Stainless steel shower head F GRN Green ABS plastic shower head and shell F HV 240 volt heat-tracing F SP Scald protection valve F FP Freeze protection valve F ALC Clear Area Light (ships separately from unit) F G3800LF Thermostatic mixing valve. Note: Must be installed in a non-freezing environment.

Upload: others

Post on 21-Apr-2020

5 views

Category:

Documents


0 download

TRANSCRIPT

Freeze-Resistant Units

Guardian Equipment 312 447 8100 TELEPHONE 1140 N North Branch St 312 447 8101 FACSIMILE Chicago, IL 60642 gesafety.com

Listed 8116. Units have been tested to and comply with

ANSI Z358.1-2014 and the Uniform Plumbing Code.

Application: IEEE compliant heat-traced station includes control panel with single point connection for electrical components. Thermostat regulated units are heated by self-limiting heat-tracing cable wrapped around internal pipe. Units prevent freezing in extreme conditions down to -40º F. See ‘Tempering Valves’ section to ensure tepid water compliance with ANSI Z358.1-2014. Compliant with IEEE standard 515-2011.

Control Panel: Single point connection for electrical components. Includes power indicator light, heat trace indicator light and high/low temperature warning lights. Panel includes dry contacts to signal power failure or high/low temperature warning. Panel also includes dry contacts to signal an event when alarm options are installed. UL listed NEMA 4X approved for Class I, Division 2, Groups B, C, and D.

Heating Cable: Self-regulated with external termination guards. Heating cable activates when internal piping temperature falls below 75°F. FM, UL, and CSA approved for Class I, Division 2, Groups B, C, and D.

Electrical System: Unit is fully wired at factory. Junction box and components rated for Class I, Division 2, Groups B, C, and D. Requires 120 VAC single phase power supply.

Jacket/Insulation: UV-resistant orange ABS plastic with polyethylene foam insulation. Jacket sections secured with removable stainless steel screws for easy maintenance.

Shower Head: 10” diameter orange ABS plastic with 20 GPM flow control.

Shower Valve: 1” IPS brass stay-open ball valve. US-made with brass ball and PTFE seals. Includes stainless steel actuating arm and 29” stainless steel pull rod.

Spray Head Assembly: Freeze-resistant with float-off dust covers and internal flow control.

Eyewash Valve: 1/2” IPS brass three-way self-draining stay-open ball valve. US-made with brass ball and PTFE seals. Includes 1/2” NPT female port to drain water from spray heads after use.

Pipe and Fittings: Schedule 40 galvanized steel.

Supply: 1-1/4” NPT female top inlet.

Sign: ANSI-compliant identification sign.

Quality Assurance: Factory tested prior to shipment. Ships fully assembled and crated.

Alarm OptionsSpecify desired alarm using fourth digit of model number, as follows:

0 No alarm1 Single pole, double throw flow switch for remote sensing

capability3 Alarm horn and remote sensing capability5 Light and remote sensing capability7 Alarm horn, light and remote sensing capability

Power

Cable Heat Tracing

High Temperature Warning

Low Temperature WarningLISTED

THERMOSTAT FOR USE INHAZARDOUS LOCATIONS

E358614

Control Panel with power indicator, trace indicator and high/low temperature warning lights.

Model GFR3307 shown.

F GFR3300 Heated Safety Station with Eyewash, IEEE Compliant, Top Inlet, Rated for Class I, Division 2 Environment

Available Options F SSH Stainless steel shower head

F GRN Green ABS plastic shower head and shell

F HV 240 volt heat-tracing

F SP Scald protection valve

F FP Freeze protection valve

F ALC Clear Area Light (ships separately from unit)

F G3800LF Thermostatic mixing valve. Note: Must be installed in a non-freezing environment.

Sign IncludedEmergencyShower/Eyewash

THIS SPACE FOR ARCHITECT/ENGINEER APPROVAL

Due to continuing product improvement, the information contained in this document is subject to change without notice. All dimensions are ± 1/4" (6mm).

Freeze-Resistant Units

Guardian Equipment 312 447 8100 TELEPHONE 1140 N North Branch St 312 447 8101 FACSIMILE Chicago, IL 60642 gesafety.com

Listed 8116. Units have been tested to and comply with

ANSI Z358.1-2014 and the Uniform Plumbing Code.

NOTES:

1. FREEZE RESISTANT SPRAY HEAD ASSEMBLY WITH INTERNAL 3.2 GPM FLOW CONTROL AND FLOAT OFF DUST COVERS.2. DESIGNED FOR USE IN A CLASS I, DIVISION 2, GROUPS B, C, & D ENVIRONMENT.3. IN ORDER TO MEET CLASS I, DIVISION 2 REQUIREMENTS, APPROVED CONDUIT AND FITTINGS MUST BE USED. ALL

THREADED ELECTRICAL CONNECTIONS MUST HAVE HAZARDOUS LOCATION RATED SEALANT APPLIED TO THREADS.4. SEE PAGE 2 FOR WIRING SCHEMATIC.

Ø7/16" MOUNTING SLOTSON 7-5/8" BOLT CIRCLE

UNIVERSAL FLOOR FLANGEDETAIL "A"

91 3/4"(2330mm)

32 5/8"(829mm)

ABS PLASTICSHOWER HEAD

1/2" NPTMALE DRAIN

CONNECTION

1 1/4" NPTFEMALE

UNION INLET

POWDER COATEDCAST ALUMINUMFLOOR FLANGE(SEE DETAIL "A")

6 1/2"(165mm)

STAINLESS STEELFLAG HANDLE

FREEZE RESISTANTSPRAY HEADS WITHDUST COVERS

STAINLESS STEELPULL ROD

40"(1016mm)

29"(737mm)

9"(229mm)

28 5/8"(727mm)

9 1/4"(235mm)

1" BRASS BALL VALVEWITH IN-LINE 20 GPM

FLOW CONTROL

UNIVERSAL SIGN(2 PLCS.)

1/2" 3-WAYBRASS BALL VALVE

23 1/2"(597mm)

SINGLE POINT CONNECTION BOX FOR HEAT TRACE CABLE, HEAT TRACE INDICATOR LIGHT, AND

TEMPERATURE WARNING LIGHTS

82 7/8"(2105mm)

rev. 110419

F GFR3300 Heated Safety Station with Eyewash, IEEE Compliant, Top Inlet, Rated for Class I, Division 2 Environment

Sign IncludedEmergencyShower/Eyewash

THIS SPACE FOR ARCHITECT/ENGINEER APPROVAL

Due to continuing product improvement, the information contained in this document is subject to change without notice. All dimensions are ± 1/4" (6mm).

Guardian Equipment 312 447 8100 TELEPHONE 1140 N North Branch St 312 447 8101 FACSIMILE Chicago, IL 60642 gesafety.com

Listed 8116. Units have been tested to and comply with

ANSI Z358.1-2014 and the Uniform Plumbing Code.

Freeze-Resistant Units

*** EVENT AND DRY ALARM CONTACT SWITCHES MAYNOT WORK FOR ALL APPLICATIONS. IN SOMESITUATIONS, AN EXTERNALSOLID STATE RELAY MAY BE NECESSARY BECAUSE OF VOLTAGE LEAKAGE THROUGH EVENT AND DRY CONTACT SWITCH.

IN THIS CASE, SOLID STATE RELAYS WILL NEED TO BE INSTALLED ACCORDING TO THE WIRING DIAGRAMSHOWN BELOW.RELAYS MUST BE INSTALLED IN A NONHAZARDOUS ENVIRONMENT AND RATED FOR THE CORRECT VOLTAGE.

*** ***

NOTES:

1. RELAYS MUST BE INSTALLED IN A NONHAZARDOUS LOCATION.

2. POWER SUPPLYING RELAYS PROVIDED BY OTHERS, 120 OR 24 VAC REQUIRED. A MAXIMUM LOAD OF 10 A ON SWITCHING CURRENT.

3. EVENT RELAY 1 WILL CLOSE UPON ACTIVATION OF EITHER THE SHOWER OR THE EYEWASH. RELAY 1 NORMALLY OPEN CONTACTS POSTION 4 AND 3.

4. DRY ALARM RELAY 2 WILL OPEN UPON POWER FAILURE, HIGH TEMPERATURE OR LOW TEMPERATURE. RELAY 2 NORMALLY CLOSED CONTACTS POSITION 2 AND 4.

5. CONTACTS SHOWN IN UNENERGIZED STATE.

1

5 4 3

N.O.

RELAY 1

1

5 2 4

N.C.

RELAY 2

DRY ALARM

L2 (NEUTRAL)

65 87

L1

EVENT

EVENTDRY

ALARM

GFR3300 CONTROL PANEL

HAZARDOUSLOCATION

SOLID STATE RELAY WIRING SCHEMATIC

(NOT SUPPLIED WITH UNIT)

NONHAZARDOUSLOCATION

NOTES:

1. ALL THROUGH HOLE PENETRATIONS IN THE CONTROL PANEL SHOULD BE LOCATED EITHER IN THE SIDE OR BOTTOM. NO HOLE PENETRATIONS SHOULD BE LOCATED AT THE TOP OF THE CONTROL PANEL.

2. PEAK HEAT TRACE POWER CONSUMPTION IS 75 WATTS.

ALARM(HIGH)

ALARM(LOW)

SET POINT

75

100

60

60 100°F

90 120°F

30 60°F

GROUNDBLOCK

1 2

L1 L2

3 4 5 6 7 8

9 10HT

CABLE2A

AREALIGHT

1A

HORN

1A

ALARMLIGHT

1A

1 2 3 4 5 6 7 8

RED

RED

WHT

EVENT1A

DRY ALARM

1A

FLOW/PROX RTDFLOW/

PROX

HEAT TRACECABLE

CONTROL BOX WIRING SCHEMATIC

(N.O.) (N.C.)

120 VAC, 1Ø, 60HZ

L1

L2 (NEUTRAL)

rev. 110419

F GFR3300 Heated Safety Station with Eyewash, IEEE Compliant, Top Inlet, Rated for Class I, Division 2 Environment