Product Overview The Pertronic F220 is a modular, expandable, networkable, intelligent fire alarm control panel which fully complies with the ISO based AS 7240.2 Australian fire alarm standard. The F220 exceeds the minimum requirements of this standard by displaying the exact location of the alarm activation as well as the mandated zone location information. The F220 uses a 7 inch (180 mm) 800 x 480 pixel colour display to unmistakably identify the panel status. The alarm mode is clearly identified by the use of red status bars, and by using large easy to read text descriptors. Fault information, device disablement information, pre-alarm conditions, walk test, supervisory and system information all have their own unique coloured display screens to provide comprehensive easy to use information for all users including fire brigade personnel, building managers, and service technicians. The F220 also has multiple event logs to provide all users with powerful diagnostic information. A full range of LCD and LED mimic panels provide remote display, control and monitoring capabilities. The F220 is fully compatible with Pertronic FireMap™ PC Graphics. Standard Features » Seven-inch 800 x 480 pixel TFT LCD colour display » Easily readable 5 mm text height on Alarm screen » Monitors and controls up to 3,180 sensors, and 1,980 input / output modules, manual call points, or addressable warning devices » Automatically identifies the exact location of an alarm » Colour-coded status and event display » Numeric keypad for rapid information access » Multiple panels may be connected in a fault-tolerant Pertronic Net2 network system » EWIS or BOWS system interface » Virtual detection makes better use of information from intelligent sensors to combine maximum alarm sensitivity and excellent nuisance alarm immunity » High-speed upload/download of configuration files (less than thirty seconds) via USB memory stick » PC interface programming and interrogation with the user-friendly Pertronic FireUtils® application » Serial buses (RS-485) for interfacing to LCD and LED mimic panels and ancillary peripheral devices » Specialised history logs retain critical information even after large numbers of minor events » User can disable individual sensors, loop devices, zones, local MCP, local buzzer, alarm routing, timers, logic blocks, and network inputs » Compatible with a full range of peripherals including sounders, strobes, audio-visual signs, amplifiers, speakers, audible warning and evacuation systems, and Ethernet and SMS (text-messaging) interfaces » Large range of cabinet sizes, including weatherproof » Customised assembly options » Complies with Australian Standards AS 7240-2, AS 7240-4, AS 4428-3, & AS 1668 F220 Fire Alarm Control Panel F220 Analogue Addressable Fire Alarm Control Panel The large-text colour display automati- cally identifies the exact location of an alarm Instant fire alarm location ̶ Easily readable large-text colour display Power and Flexilility ̶ User-friendly operation Rapid configuration ̶ Economical, intuitive installation Page 1

Upload: nguyentuyen

Post on 10-Jun-2018

302 views

Category:

Documents


14 download

TRANSCRIPT

Product Overview

The Pertronic F220 is a modular, expandable, networkable, intelligent fire alarm control panel which fully complies with the ISO based AS 7240.2 Australian fire alarm standard. The F220 exceeds the minimum requirements of this standard by displaying the exact location of the alarm activation as well as the mandated zone location information.

The F220 uses a 7 inch (180 mm) 800 x 480 pixel colour display to unmistakably identify the panel status. The alarm mode is clearly identified by the use of red status bars, and by using large easy to read text descriptors. Fault information, device disablement information, pre-alarm conditions, walk test, supervisory and system information all have their own unique

coloured display screens to provide comprehensive easy to use information for all users including fire brigade personnel, building managers, and service technicians.

The F220 also has multiple event logs to provide all users with powerful diagnostic information.

A full range of LCD and LED mimic panels provide remote display, control and monitoring capabilities. The F220 is fully compatible with Pertronic FireMap™ PC Graphics.

Standard Features

» Seven-inch 800 x 480 pixel TFT LCD colour display » Easily readable 5 mm text height on Alarm screen » Monitors and controls up to 3,180 sensors, and

1,980 input / output modules, manual call points, or addressable warning devices

» Automatically identifies the exact location of an alarm

» Colour-coded status and event display » Numeric keypad for rapid information access » Multiple panels may be connected in a fault-tolerant

Pertronic Net2 network system » EWIS or BOWS system interface » Virtual detection makes better use of information

from intelligent sensors to combine maximum alarm sensitivity and excellent nuisance alarm immunity

» High-speed upload/download of configuration files (less than thirty seconds) via USB memory stick

» PC interface programming and interrogation with the user-friendly Pertronic FireUtils® application

» Serial buses (RS-485) for interfacing to LCD and LED mimic panels and ancillary peripheral devices

» Specialised history logs retain critical information even after large numbers of minor events

» User can disable individual sensors, loop devices, zones, local MCP, local buzzer, alarm routing, timers, logic blocks, and network inputs

» Compatible with a full range of peripherals including sounders, strobes, audio-visual signs, amplifiers, speakers, audible warning and evacuation systems, and Ethernet and SMS (text-messaging) interfaces

» Large range of cabinet sizes, including weatherproof » Customised assembly options » Complies with Australian Standards AS 7240-2,

AS 7240-4, AS 4428-3, & AS 1668

F220 Fire Alarm Control Panel

F220 Analogue Addressable Fire Alarm Control Panel

The large-text colour display automati-cally identifies the exact location of an alarm

Instant fire alarm location Easily readable large-text colour display Power and Flexilility User-friendly operation

Rapid configuration Economical, intuitive installation

Page 1

F220 Peripherals

Analogue Addressable Loop Devices

Aspirating Smoke Detectors

Smoke Detectors Multi-Criteria Detectors Heat Detectors

FAAST XTFAAST XSFAAST LT

PhotoelectricLaser

Acclimate: Smoke + HeatPTIR: Smoke, Thermal + Infra-RedCOPTIR: Carbon Monoxide, Smoke, Thermal + IR

Static Temperature or Rate of Temperature RiseIndoor and Weatherproof Options

Duct Smoke Detector Beam Smoke Detector Alarm Acknowledge Module

Manual Call Points

Indoor and Watertight Options

For use with Alarm Acknowledge Facility

Indoor and IP 67 Weatherproof

Loop Responder Module Loop Relay Module Input/Output Control ModulesInterface up to 8 conventional detection zones or switch contacts to analogue addressable loop

4 relay outputs, individually configurable supervised or non-supervised

Single InputDual InputDual Input, Single OutputDual Input, Dual OutputTen InputSingle OutputSingle Output 240V SwitchingSix OutputConventional Zone Interface

Warning System Devices

DC Operated Addressable Sounders Addressable Strobes Add. Sounder-StrobesStrobe LightSounder-StrobeSounder

Indoor and Weatherproof

Indoor synchronised, with or without integral detector base

Indoor (synchronised) and Weatherproof options

Indoor (synchronised, with or without integral detector base) and Weatherproof options

Audio Distribution Modules Ceiling Speakers Horn Speakers2-Way4-Way

3 W to 15 W Ratings100 mm to 200 mmDiameter

10 W Power RatingIP66, OutdoorIP66, Marine Grade

For more information please refer to the product datasheets, available from www.pertronic.com.au, or contact your nearest Pertronic office.

F220 Options

Internal Options

Pertronic Industries supply an extensive range of options for the F220 Fire Alarm Control Panel. The number and type of internal options required for a specific project will affect the choice of cabinet size, power supply current rating, and battery capacity.*

Accessories

A full range of accessories is available for the F220, including the range of F220 Mimics and AS 7240 Power Supplies. Please refer to the Pertronic website or contact Pertronic for more information.

The following list outlines the popular internal options:

Two-Loop Driver (F120P2LMB-A) Provides two analogue addressable loops.AA Multi-Function Loop Responder (AALR-MFA) Provides eight conventional detection zone or switch input circuits with one relay configurable as Form C clean contact or supervised 100 Volt Line output.Addressable Loop Relay (AALREL) Provides four outputs, individually configurable as supervised or voltage-free relay contacts. Also provides an input for supervising the fault signal from an external power supply.AA Isolator Board (8SAAIB) Provides eight isolated analogue addressable loop spurs. Allows conventional fire alarm zones to be converted to analogue addressable spurs using the existing cable, when upgrading from a conventional to an intelligent fire alarm control panel.Evacuation Amplifiers Complete with evacuation tone generator and a single supervised 100 Volt Line output for speakers:

• 20 Watt (EVAC20W24V-T3),• 50 Watt (EVAC50W24V-A),• 120 Watt (EVAC120W24V).

(Note that the 120 Watt amplifier requires the evacuation tone generator)Audio Distribution Module (ADM-2, ADM-4) Provides multiple audio channels from a single 100 Volt line. All channels are continuously supervised for line faults. A line fault on any channel does not prevent operation on other channels. An F220 may be fitted with multiple Audio Distribution Modules.

Evacuation Tone Generator (EVACGEN-EA) Provides inputs for local and remote microphones, evacuation tones, standard or custom evacuation messages, and supervision of audio amplifiers.Emergency Warning and Information System (EWIS) Audible voice warning and emergency intercom system.Fan Control Plate A 3U rack-mounted front plate that accepts any combination of control units and AFI displays. Each Fan Control Plate accepts 10 standard units or five AFI displays.

AS1668 Fan Control Unit Occupies one space on the Fan Control Plate.AFI Display Alarm, fault, and isolate indicators for 8 zones. Occupies two spaces on the Fan Control Plate.

Fan Control Plate with AFI Display (left), Fan Control Reset Unit (centre) & Fan Control Switch Unit (right)

Special Purpose Control Units• Building Occupant Warning

System Controls• 8 Way Solenoid Test Control• 8 Way Zone Isolate Switch

Special Purpose DisplaysA range of special purpose LED displays is available for the F220. The displays are designed to satisfy specific project requirements.

Please contact Pertronic Industries for more information about special purpose control units and displays.

Hand-Held Microphone and cradle, mounted on front panel.Bell Monitor Board (ZMB24V)Provides additional supervised outputs for warning devices such as strobes, sounders (bells), and audio-visual signs.Network Card (NET2CARD)Interface with a Pertronic Net2 Network System.Ethernet Gateway (NET2GATE)Interface with any Ethernet network including a virtual private network (VPN), or the Internet. The Ethernet Gateway provides an interface for Pertronic FireMap™ PC Graphics.Ancillary Peripherals

• 48-way Open Collector Board• 8 Way Relay Mimic• 8 Way Common Relay Board• Auxiliary Panel Relay (2-pole

4-amp 24 Vdc form C contact)General Purpose InterfacesBACNet, Modbus, Nurse Call Pager, Printer.Fibre Optic Interface Adaptors available for RS-232, RS-485, or Ethernet.Brigade Transmitter Interface Highly adaptable interface system designed to work with a wide range of Alarm Signalling Equipment. The F220 Auxiliary Relay Board, and the 8 Way Common Relay Board, may be used to provide additional connections if necessary.DC-DC Converter Isolated supply to increase noise immunity of one pair of analogue addressable loops.24 Vdc Door Holder Power Supply2 amp, 5 amp, 10 amp

Page 2 Page 3

* The fire alarm panel’s maximum total current consumption, including any auxiliary power outputs, must not exceed the power supply’s load capacity. Most optional components draw their maximum current when the system is in Alarm mode. The Pertronic website (www.pertronic.com.au) provides a calculator for computing supply current and battery capacity.

Horn Speaker

Input / output Control Module Smoke Detector Duct Smoke DetectorMCP

Aspirating Smoke Detector Addressable Sounder

Alarm Acknowledge Module

Addressable Strobe Light

Beam Smoke Detector

Enhanced Mini Mimic

Full Function Mimic

Alarm Mini Mimic

Base Station Pager

Printer

Monitored 100V Audio Line

Loop Relay Module

Sounder

Sounder Strobe Analogue Addressa

ble LoopBell C

ircuit

Analogue Addressable Loop

Door HolderHeat Detector

Relay output

F220F220

Manual Call Point

Ceiling Speaker

ConventionalDetection Zone

External High SpeedRS-485 Bus

External Low SpeedRS-485 Bus

Multi-Criteria Detector

Loop Responder Module

F220 System Diagram

A simplified Pertronic F220 system illustrating connections between the panel and popular external devices

F220 Cabinet Dimensions

Height mm

Width mm

Depth mm

Protrusion mm

600mm Cabinet, with window & MCP 600 450 155 30 (MCP)10U Cabinet, with window & MCP 530 550 185 30 (MCP)

13U Cabinet, with window & MCP 645 550 185 30 (MCP)16U Cabinet, with window & MCP 800 550 185 30 (MCP)28U Slim Cabinet, with window & MCP 1330 575 290 30 (MCP)28U Deep Cabinet, with window & MCP 1330 575 385 30 (MCP)40U Deep Cabinet, with window 1865 575 385 016U Weatherproof Cabinet, IP55, with window 800 600 260 30 (Handle)28U Weatherproof Cabinet, IP55, with window 1330 600 260 30 (Handle)16U Weatherproof Cabinet, IP65 (no window) 800 600 260 30 (Handle)28U Weatherproof Cabinet, IP65 (no window) 1330 600 260 30 (Handle)• Document holder is standard on 16U Cabinet, and optional on other cabinets (except 16U weatherproof.• Manual call point optional on 40U Deep Cabinet.• Other cabinet sizes and styles available for special orders.• Refer to the Weatherproof Cabinets datasheet for more information about weatherproof cabinets.• Specified depth is measured to front face. Some fittings protrude forward of the front face.• This datasheet specifies nominal physical dimensions. Actual dimensions may vary slightly.

Weatherproof Cabinets 16U & 28U

Configuring the F220 with FireUtils®

Pertronic FireUtils® is a computer application that makes it easy to configure a Pertronic F220 system. For a stand-alone panel, FireUtils® uploads the configuration file to a USB stick, or direct to the panel via RS-232.

For a network, FireUtils® uploads all configuration files for panels, NCUs, displays, and network cards via Ethernet to any individual Net2 Card on the system. From there, the configuration files are automatically transferred to their destination devices.

FireUtils® provides diagnostic, debugging, and event log management tools, and runs on Microsoft Windows 7, 8 and 10. For more information, refer to the FireUtils® datasheet.

Networking the Pertronic F220

The Pertronic Net 2 Network connects multiple F220 fire alarm control panels, Net 2 Network Control Units and Net 2 displays into a single fault-tolerant system, in which:

» All connected panels can be controlled and monitored from any Net 2 Network Control Unit

» Information from any connected panel can be viewed on any Net 2 Network Control Unit or Net 2 display

» Events anywhere on the network can trigger or influence events at any connected panel

» System time in all connected panels, control units and mimic displays is automatically synchronised

Please refer to Pertronic Net 2 Network System datasheet for more information about the Net 2 Network System.

F220 Compliance and Approvals

» Independent laboratory tested to AS 7240-2, AS 7240-4, & AS 4428-3

» Air handling controls (if fitted) comply with AS 1668 » ActivFire listing: afp – 3054

F220 Colour Specification

Item Colour Dulux CodeCabinets and Doors Off White Ripple 288-97072Front (Rack) Plates Arctic White 915-58861

Front Plates (optional) Apo Grey 915-32786Weatherproof cabinets also available in Brushed Stainless Steel

FireUtils® workstation in use

The Pertronic Net2 Network System connects multiple F220 panels in a fault-tolerant bi-direc-tional ring circuit

F220 Specifications

Display 7 inch 800 x 480 pixel colour TFT-LCD

Power Supplies Total Charge Current Current

• 28 Vdc 5 Amp PSU 5 A 2.1 A• 28 Vdc 11 Amp PSU 11 A 2.1 A

Maximum Battery Size• 16 U Cabinet 33 Ah• 28 U Slim Cabinet 40 Ah• 28 U Deep Cabinet, 40 U Deep Cabinet 55 Ah

Relay Contact Ratings (Resistive Load)• Fire, Fault, Battery Fault, Disable,

General Purpose, GP ASE 2 A @ 30 Vdc• Door Holder 5 A @ 30 Vdc

Supervised Outputs• Ancillary Control Function (ACF), O/P 1, O/P 2

2 A @ 28 Vdc• Warning System, External Bell 5 A @ 28 Vdc

Communication Ports• External High-Speed RS-485 (data) 115.2 kbit/s

(power) 1.4 Amp• External Low-Speed RS-485 (data) 9,600 bit/s

(power) 1.4 Amp• RS-232 (auto-adapting) 9.6 or 115.2 kbit/s• USB USB 2

Analogue Addressable (AA) Loop• Number of Loops 2 to 20, in 2-loop increments• Sensors Up to 159 per loop• Input/output modules,

addressable warningdevices, or MCPs Up to 99 per loop

• Loop Current Maximum 350 mA• Loop Resistance Maximum 50 Ω• Length Up to 2500 metres end to end,

with appropriate configuration. Loop configuration must be verified using the loop calculator at http://www.pertronic.com.au/

Operating Temperature -10 °C to +50 °CHumidity ≤ 95 % RH, non-condensing

28U 40U

Page 6 Page 7

F220 Ordering Information

Product Code* DescriptionF220-A0.6/5A F220, 600mm Cabinet with 2 Loops and 5 Amp PSU

F220-A10U/5A F220, 10U Cabinet with 2 Loops and 5 Amp PSU

F220-A13U/5A F220, 13U Cabinet with 2 Loops and 5 Amp PSU

F220-A13U/11A F220, 13U Cabinet with 2 Loops and 11 Amp PSU

F220-A13UEA50/5A F220, 13U Cabinet with 2 Loops and 50W Amplifier + Mic, 5 Amp PSU

F220-A13UEA50/11A F220, 13U Cabinet with 2 Loops and 50W Amplifier + Mic, 11 Amp PSU

F220-A16U/5A F220, 16U with 2 Loops, 5 Amp PSU

F220-A16U/11A F220, 16U with 2 Loops, 11 Amp PSU

F220-A16UEA50/5A F220, 16U with 2 Loops, 50W Amplifier + Mic, 5 Amp PSU

F220-A16UEA50/11A F220, 16U with 2 Loops, 50W Amplifier + Mic, 11 Amp PSU

F220-A16UEA120/11A F220, 16U with 2 Loops, 120W Amplifier + Mic, 11 Amp PSU

F220-A28U/5A F220, 28U with 2 Loops, 5 Amp PSU

F220-A28U/11A F220, 28U with 2 Loops, 11 Amp PSU

F220-A28UEA50/5A F220, 28U with 2 Loops, 50W Amplifier + Mic, 5 Amp PSU

F220-A28UEA50/11A F220, 28U with 2 Loops, 50W Amplifier + Mic, 11 Amp PSU

F220-A28UEA120/11A F220, 28U with 2 Loops, 120W Amplifier + Mic, 11 Amp PSU

F220-A28UEA250/11A F220, 28U with 2 Loops, 250W Amplifier + Mic, 11 Amp PSU

F220-A28US/5A F220, 28U Slim with 2 Loops and 5 Amp PSU

F220-A28US/11A F220, 28U Slim with 2 Loops and 11 Amp PSU

F220-A28USEA50/5A F220, 28U Slim with 2 Loops, 50W Amplifier + Mic, 5 Amp PSU

F220-A28USEA50/11A F220, 28U Slim with 2 Loops, 50W Amplifier + Mic, 11 Amp PSU

F220-A28USEA120/11A F220, 28U Slim with 2 Loops, 120W Amplifier + Mic, 11 Amp PSU

F220-A28USEA250/11A F220, 28U Slim with 2 Loops, 250W Amplifier + Mic, 11 Amp PSU

F220-A40U/5A F220, 40U with 2 Loops, 5 Amp PSU

F220-A40U/11A F220, 40U with 2 Loops, 11 Amp PSU

F220-A40UEA50/5A F220, 40U with 2 Loops, 50W Amplifier + Mic, 5 Amp PSU

F220-A40UEA50/11A F220, 40U with 2 Loops, 50W Amplifier + Mic, 11 Amp PSU

F220-A40UEA120/11A F220, 40U with 2 Loops, 120W Amplifier + Mic, 11 Amp PSU

F220-A40UEA250/11A F220, 40U with 2 Loops, 250W Amplifier + Mic, 11 Amp PSU

* These product codes specify white front plates. To specify grey front plates, add a suffix “-G” to the product code. For example: F220-A28U/5A-G.

16U

FireMap™

Pertronic FireMap™ is an economical fire system management tool that adds advanced features to any fire system. A FireMap system remotely monitors one or more fire indicating panels via Ethernet connections. Whenever a monitored fire indicating panel originates an alarm:

» FireMap sounds an audible warning and automatically displays a map of the zone that triggered the alarm, with the active zone outlined in red,

» FireMap’s status window displays the word “Alarm” and details of the location,

» Fire panels with active alarms are highlighted in red on the FireMap display.

» In Pertronic F220 systems, FireMap’s smart icons map the active detectors in red.

FireMap’s information storage and retrieval capabilities provide quick and easy access to additional information, including contact information for key personnel, response procedures, and photographs. In Pertronic F220 systems, authorised FireMap users are able to acknowledge alarms, reset devices from alarm mode, and disable or enable devices or zones directly from any FireMap workstation.

F220 Software Features

» Configurable from front panel, USB stick or Personal Computer

» Numeric keypad for rapid information retrieval and efficient front panel configuration

» User definable text descriptors for: sensors, loop devices (modules), zones, logic blocks, AAF/ADF units

» AS 1670.1: 2015-compliant nuisance alarm management facilities: Alarm Acknowledgement (AAF), Alarm Delay (ADF), and Alarm Verification (AVF)

» Multiple configurable action levels per sensor (with appropriate sensor types)

» Sensor Pre-Alarm and Maintenance warnings » Individual sensor dual sensitivity for configurable automatic

Day / Night operation » Versatile easy-to-programme Cause and Effect features

with highly adaptable logic blocks, timers, and AS 1668 fan control blocks

» Auto-Learn function for fast loop configuration » Automatic clock adjustment for daylight saving » Automatic system test of charger, batteries and sensors.

The test may be configured to occur at any one time of the day, on any day(s) of the week

» Fire alarm control panel door interlock switch » Memory Lock switch to write-protect configuration data

» Intelligent Sensors 3,180 (max.) » Intelligent Modules 1,980 (max.) » Zones 999 » Cause-Effect Logic Blocks 999 » Timers 50 » AAF/ADF Units 1,200 » AS1668 Controls 400 » Groups 200 » Network Inputs 999 » Multiple Unique Panel History Logs

» Main All Event Log 10,000 events » Alarm Log 2,000 events » Pre-Alarm Log 500 events » Fault Log 500 events » Supervisory Log 500 events » Disablement Log 500 events » Disablement Activity Log 500 events » Active Event Log 500 events » System Event Log 500 events » Power Supply Log 5,000 entries

(Each power supply log entry includes: System voltage; Charge voltage & current; Battery voltage; and Temperature.)

Note: In total the panel history logs can store up to 20,500 entries. Logs may be saved to a USB stick or imported to a PC running FireUtils®

0060 F220 Panel Issue 3.3 20180201

Pertronic Industries Pty Ltd www.pertronic.com.auPage 8