faira transparency reports 11721 se mcgillivray blvd ... · 11721 se mcgillivray blvd, vancouver,...
TRANSCRIPT
608 State St. South Kirkland, WA 98033
www.faira.com
[email protected] +1.800.571.FAIR
FAIRA TRANSPARENCY REPORTS
11721 SE McGillivray Blvd, Vancouver, WA 98683
April 28th, 2017 Thank you for your interest in this Faira Certified home. We have coordinated the efforts of certified and licensed inspection and title professionals to create the Faira Transparency Reports for this home. The Faira Transparency Reports are a detailed portfolio of information that is prepared on behalf of buyers in preparation for making an informed offer on the property.
You may view more detailed information for this home and can make an offer at
http://www.faira.com/listings/11065 All of the information in the Faira Transparency Reports was gathered and compiled without any bias or influence from the seller(s). In fact, these reports are materially identical had you as the buyer(s) ordered the same professionals to perform the evaluations on the same date. Nevertheless, Faira takes no obligation of the reports being complete or accurate. The buyers are recommended to conduct their own due-diligence to their satisfaction. Please contact us if you have any questions or would like more information. We’re happy you’ve chosen a Faira Certified home and look forward to the opportunity of working with you! The Faira Team
Inspection No. 43204-27722Date: 15-May-2017
Visual Property Inspection
11721 SE McGillivray BlvdVancouver, WA 98683
Prepared for :
Will Donohue
Inspected by :
Brian Gustafson7644 NE Hazel Dell Ave
Vancouver, Washington 98665Phone: (360) 546-2190 Email: [email protected]
Page 1 of 50 43204-27722
This summary is not the entire report. The complete report may include additional information of concern to theclient. It is recommended that the client read the entire report.
Brian Gustafson
Licensed Home Inspector #237
11721 SE McGillivray Blvd, Vancouver, WA 98683
Report Commentary
Date: 15-May-2017
Property and Site1.0
Inspection Information1.1
THIS REPORT IS INTENDED ONLY FOR THE EXCLUSIVE USE OF THE PERSON(S) PURCHASINGTHE HOME INSPECTION SERVICES. NO OTHER PERSON OR PARTY MAY RELY UPON ANYREPRESENTATION MADE IN THIS REPORT AND ARE HEREBY NOTIFIED THAT DISSEMINATING,DISTRIBUTING OR COPYING THIS REPORT WITHOUT THE PERMISSION OF PILLAR TO POSTINSPECTION IS PROHIBITED.
Exterior2.0
Exterior Wall Surface2.1
The siding has been replaced with cement composite lap type siding. The condition of the walls and orstructure concealed behind the siding can not be determined in this inspection. Advise consulting withthe owners and obtaining all permits, invoices and warranty information with respect to the sidinginstallation contractor.
Windows2.2
The windows have been replaced with vinyl windows. Concealed issues regarding the installation cannotbe determined in this inspection. All related contractor invoice and warranties should be obtained fromthe seller of the home.
Some of the windows are the original aluminum windows and are past the end of their typical service life.Replacement should be considered.
Page 2 of 50 43204-27722
This summary is not the entire report. The complete report may include additional information of concern to theclient. It is recommended that the client read the entire report.
Brian Gustafson
Licensed Home Inspector #237
11721 SE McGillivray Blvd, Vancouver, WA 98683
Report Commentary
Date: 15-May-2017
Exterior2.0
Foundation Vents2.3
East: The vent screens are missing or damaged on the crawlspace vent openings. Advise repair toprevent vermin / animal entry into the crawlspace.
Improve the drainage at the crawl vent openings to help keep storm and irrigation water from entering thecrawlspace. Vent openings at or below grade level must have vent wells installed to keep water fromentering the crawlspace.
Page 3 of 50 43204-27722
This summary is not the entire report. The complete report may include additional information of concern to theclient. It is recommended that the client read the entire report.
Brian Gustafson
Licensed Home Inspector #237
11721 SE McGillivray Blvd, Vancouver, WA 98683
Report Commentary
Date: 15-May-2017
Exterior2.0
Exterior Electrical Wiring2.4
There are modifications / additions of electrical wiring visible on the exterior of the home. East light waswired with a cord cover instead of conduit. The wiring appears to be poorly / non-professionally installed.Advise correction by an electrician.
There is exposed electrical wiring visible on the exterior of the home at the conduit at the East side of thehome . All exposed wires should be installed within protective conduits. Advise correction by anelectrician.
There are modifications / additions of electrical wiring visible on the exterior of the home. The wiringappears to be poorly / non-professionally installed. Advise correction by an electrician.
Page 4 of 50 43204-27722
This summary is not the entire report. The complete report may include additional information of concern to theclient. It is recommended that the client read the entire report.
Brian Gustafson
Licensed Home Inspector #237
11721 SE McGillivray Blvd, Vancouver, WA 98683
Report Commentary
Date: 15-May-2017
Exterior2.0
Miscellaneous 2.5
Unknown drain line was noted leaving the East crawl space area ,advise further investigation with thecurrent home owner as to the use of this drain
Garage3.0
Main Garage Door3.1
The garage door operated , door is weathered
Page 5 of 50 43204-27722
This summary is not the entire report. The complete report may include additional information of concern to theclient. It is recommended that the client read the entire report.
Brian Gustafson
Licensed Home Inspector #237
11721 SE McGillivray Blvd, Vancouver, WA 98683
Report Commentary
Date: 15-May-2017
Garage3.0
Floor3.2
Due to very Heavy storage in the garage - unable to inspect garage floor and or the walls thoroughly.
Ceiling3.3
The attic pull-down stairs located in the garage, should have a fire rated drywall cover added to thebottom of the access panel to ensure proper fire-wall integrity. Advise correction.
Lights / Receptacles3.4
We recommend installation of GFCI receptacles to reduce risk of electrical shock.
Page 6 of 50 43204-27722
This summary is not the entire report. The complete report may include additional information of concern to theclient. It is recommended that the client read the entire report.
Brian Gustafson
Licensed Home Inspector #237
11721 SE McGillivray Blvd, Vancouver, WA 98683
Report Commentary
Date: 15-May-2017
Roof Structure4.0
Fascia / Soffit / Eaves4.1
There are water stains visible on the underside of the eaves indicating past or current leaks. Furtherinvestigation is advised
There is rot apparent in the fascia / eaves. There may be additional concealed damage, a more thoroughexamination is required to determine the full extent of damage. Advise replacement of all damagedstructure.
Page 7 of 50 43204-27722
This summary is not the entire report. The complete report may include additional information of concern to theclient. It is recommended that the client read the entire report.
Brian Gustafson
Licensed Home Inspector #237
11721 SE McGillivray Blvd, Vancouver, WA 98683
Report Commentary
Date: 15-May-2017
Roof Structure4.0
Roof Covering4.2
The home has an upgraded composition roof covering. This type of roof covering has an approximatelife of 25 to 30 years. The actual service life will vary with different shingle brands and specificapplications.
Attic5.0
Sheathing5.1
There are moisture stains on the underside of the roof sheathing. This indicates past or present roof leakissues. There was no visible moisture present during this inspection. Advise further investigation andcorrection as necessary.
Page 8 of 50 43204-27722
This summary is not the entire report. The complete report may include additional information of concern to theclient. It is recommended that the client read the entire report.
Brian Gustafson
Licensed Home Inspector #237
11721 SE McGillivray Blvd, Vancouver, WA 98683
Report Commentary
Date: 15-May-2017
Attic5.0
Electrical5.2
There are indications of electrical additions and / or modifications visible in the attic. All related permitsand invoices should be obtained from the homeowner. In the absence of documentation an electricianshould inspect and make corrections as necessary.
Page 9 of 50 43204-27722
This summary is not the entire report. The complete report may include additional information of concern to theclient. It is recommended that the client read the entire report.
Brian Gustafson
Licensed Home Inspector #237
11721 SE McGillivray Blvd, Vancouver, WA 98683
Report Commentary
Date: 15-May-2017
Crawlspace6.0
Crawlspace Conditions 6.1
Batts of insulation been torn down throughout the crawl space under the home . Down / hanginginsulation limits view of the crawl space in many areas . Advise removal of and replacement of anydamaged insulation as needed
There is visible evidence of past plumbing leaks below the bathrooms and the kitchen (dry stains on theground). No current leaks visible.
Page 10 of 50 43204-27722
This summary is not the entire report. The complete report may include additional information of concern to theclient. It is recommended that the client read the entire report.
Brian Gustafson
Licensed Home Inspector #237
11721 SE McGillivray Blvd, Vancouver, WA 98683
Report Commentary
Date: 15-May-2017
Crawlspace6.0
Crawlspace Ducts/Pipes6.2
Main Hall : The drain line or related component is leaking below the bathroom. Advise proper repairs by aplumbing contractor.
Page 11 of 50 43204-27722
This summary is not the entire report. The complete report may include additional information of concern to theclient. It is recommended that the client read the entire report.
Brian Gustafson
Licensed Home Inspector #237
11721 SE McGillivray Blvd, Vancouver, WA 98683
Report Commentary
Date: 15-May-2017
Crawlspace6.0
Electrical Service7.0
Distribution Panel(s)7.1
There are visible non-professional modifications in the main service panel. Wiring has been installed without the use of grommets to secure the wiring in to the panel . Advise inspection and correction by anelectrical contractor.
Page 12 of 50 43204-27722
This summary is not the entire report. The complete report may include additional information of concern to theclient. It is recommended that the client read the entire report.
Brian Gustafson
Licensed Home Inspector #237
11721 SE McGillivray Blvd, Vancouver, WA 98683
Report Commentary
Date: 15-May-2017
Electrical Service7.0
Circuit Wire7.2
The home has solid conductor aluminum branch circuit wiring visible in the service panel. In accordancewith Washington inspection standards, this type of wiring is considered a potential hazard and should beevaluated by a licensed electrician.
Auxiliary Service Panel7.3
The ground and neutral wires are not properly isolated in the sub-panel. This is an improper wiringcondition. Advise correction by an electrician.
Page 13 of 50 43204-27722
This summary is not the entire report. The complete report may include additional information of concern to theclient. It is recommended that the client read the entire report.
Brian Gustafson
Licensed Home Inspector #237
11721 SE McGillivray Blvd, Vancouver, WA 98683
Report Commentary
Date: 15-May-2017
Electrical Service7.0
Heating & Cooling8.0
CO Alarms8.1
Washington State requires the installation of CO alarms(s) in all homes sold after April 1, 2012.Installation of CO detectors on each level of the home is advised.
Heating Distribution8.2
The home has individual wall mounted heaters in each living area. The units should be cleaned regularlyfor safe / proper operation.
Plumbing Components9.0
Distribution Piping9.2
The water pipes are older and of galvanized steel construction. Typically water pressure will be reduceddue to corrosion build up.
Exterior East: There are visible plumbing modifications noted. Advise obtaining all related permits andcontractor invoices or further evaluation by a plumber.
Page 14 of 50 43204-27722
This summary is not the entire report. The complete report may include additional information of concern to theclient. It is recommended that the client read the entire report.
Brian Gustafson
Licensed Home Inspector #237
11721 SE McGillivray Blvd, Vancouver, WA 98683
Report Commentary
Date: 15-May-2017
Plumbing Components9.0
Waste Drainage9.3
The home has old cast iron sewer lines. These are subject to corrosion and failure over time. The waterflow test conducted during this inspection can not simulate living conditions. Advise further investigationof the sewer drain condition with a drainage contractor.
Water Heater9.4
Although the water heater was not acceded for inspection. ,the water heater has been replaced. Adviseobtaining the permits and contractor invoices from the homeowner.
Page 15 of 50 43204-27722
This summary is not the entire report. The complete report may include additional information of concern to theclient. It is recommended that the client read the entire report.
Brian Gustafson
Licensed Home Inspector #237
11721 SE McGillivray Blvd, Vancouver, WA 98683
Report Commentary
Date: 15-May-2017
Plumbing Components9.0
Bathrooms10.0
Lighting / Receptacles10.1
Recommend installation of GFCI receptacles to reduce risk of electrical shock.
Faucet / Trap / Drain10.2
Both Bathrooms : The drain has a non-approved drain connection (flex pipe). Advise replacement by aplumber.
Toilet10.3
Page 16 of 50 43204-27722
This summary is not the entire report. The complete report may include additional information of concern to theclient. It is recommended that the client read the entire report.
Brian Gustafson
Licensed Home Inspector #237
11721 SE McGillivray Blvd, Vancouver, WA 98683
Report Commentary
Date: 15-May-2017
Bathrooms10.0Master : The toilet base is loose on the floor. Advise removing the toilet and re-setting with a new waxseal. Leaking toilet seals will damage the wood floor structure if not corrected. The concealed floorstructure should be examined when the base has been removed. Any damaged structure should bereplaced.
Tub Faucet / Shower Head and Drain10.4
Main Hall : The Hot water at the highest setting is only warm at the shower tub enclosure . Advisecorrection by a plumbing contractor
Shower Enclosure10.5
Master: There is visible chips / damage on the surface of the shower enclosure . Advise professionalrepair.
Heat Source10.6
Main Hall : The ceiling heater has been removed There is no visible heat source in this room. Advisecorrection.
Kitchen11.0
Windows11.1
Failed seal between double panes of glass. Window has fogged.
Receptacles / Lights / Fans11.2
Recommend installation of GFCI receptacles to reduce risk of electrical shock.
Range Hood11.3
Kitchen exhaust fan inoperative at time of inspection.
Interior Living Areas12.0
Windows12.1
Living Room : Window pain is missing from the sliding windows left . Advise replace
Page 17 of 50 43204-27722
This summary is not the entire report. The complete report may include additional information of concern to theclient. It is recommended that the client read the entire report.
Brian Gustafson
Licensed Home Inspector #237
11721 SE McGillivray Blvd, Vancouver, WA 98683
Report Commentary
Date: 15-May-2017
Interior Living Areas12.0
Additional Comments13.0
General Photos13.1
General Roof Photos13.2
Page 18 of 50 43204-27722
This summary is not the entire report. The complete report may include additional information of concern to theclient. It is recommended that the client read the entire report.
Brian Gustafson
Licensed Home Inspector #237
11721 SE McGillivray Blvd, Vancouver, WA 98683
Report Commentary
Date: 15-May-2017
Additional Comments13.0
General Attic Photos13.3
Page 19 of 50 43204-27722
This summary is not the entire report. The complete report may include additional information of concern to theclient. It is recommended that the client read the entire report.
Brian Gustafson
Licensed Home Inspector #237
11721 SE McGillivray Blvd, Vancouver, WA 98683
Report Commentary
Date: 15-May-2017
Additional Comments13.0
General Crawlspace Photos13.4
Page 20 of 50 43204-27722
This summary is not the entire report. The complete report may include additional information of concern to theclient. It is recommended that the client read the entire report.
Brian Gustafson
Licensed Home Inspector #237
11721 SE McGillivray Blvd, Vancouver, WA 98683
Report Commentary
Date: 15-May-2017
Additional Comments13.0
Page 21 of 50 43204-27722
Unless noted otherwise, all exterior components are inspected from the ground. These observations arevisual, limited to what can be seen from that perspective and not exhaustive in scope.
This inspection does not include cosmetic or workmanship issues such as minor typical drywall cracking,uneven trim, unevenness in walls & floors that are typical of using wood for a building material, paint touch-ups etc. Typical wear and tear that is proportional to the age of the home/ structure / system or component,is not documented in this inspection report.
If the house is currently occupied by the owner or tenant and their belongings, storage throughout thehouse, under sinks, in closets, etc will limit inspection of those areas / systems / components or items.Some issues may not become evident until after belongings are removed. UNDER NO CIRCUMSTANCESARE PERSONAL BELONGINGS DISTURBED BY THE INSPECTOR. For a more completeunderstanding of the scope of this inspection refer to the included Washington State Inspection Standards.
11721 SE McGillivray Blvd, Vancouver, WA 98683
Licensed Home Inspector #237
Brian Gustafson
Date: 15-May-2017
Property and Site
Inspection Information
The scope and method of this home inspection is conducted in accordance with the standards andpractices set forth by the Washington State Department of Licensing for home inspections performed inWashington - Chapter 308-408C WAC
It is strongly advised that all repairs advised or recommended, be corrected prior to closing, by aprofessional, licensed in the specific expertise. It is common that additional (related and unrelated) damage,improper materials &/or workmanship are discovered in the course of making those repairs, which were notvisible during this inspection.
Housing built before 1978 may contain lead-based paint. Lead from paint, paint chips and dust can posehealth hazards if not managed properly. Lead exposure is especially harmful to young children andpregnant women. This inspection does not identify nor test for lead based paint. We advise the purchasershave a lead paint assessment performed prior to purchase of this property if constructed prior to 1978.
This report is a full home inspection, not a wood destroying insect inspection. When noted in this report,the discovery of evidence of past or current wood destroying insect activity, we advise having the homeevaluated by a Pest Control Professional. There may be concealed damage related to insect activity thatwill not be reported in this inspection, and that cannot be discovered without further investigation.
The presence of asbestos containing building materials is not within the scope of this inspection, and isspecifically excluded from this report. Older homes may contain asbestos in many building productsincluding insulation, exterior siding, drywall, plaster, heating equipment, etc. If this is a concern, it is yourresponsibility to arrange further testing to determine the presence of asbestos in the home.
THIS REPORT IS INTENDED ONLY FOR THE EXCLUSIVE USE OF THE PERSON(S) PURCHASINGTHE HOME INSPECTION SERVICES. NO OTHER PERSON OR PARTY MAY RELY UPON ANYREPRESENTATION MADE IN THIS REPORT AND ARE HEREBY NOTIFIED THAT DISSEMINATING,DISTRIBUTING OR COPYING THIS REPORT WITHOUT THE PERMISSION OF PILLAR TO POSTINSPECTION IS PROHIBITED.
Structure Faces: NorthApproximate Year of Construction: 1969
BasementOtherRural
Hi-RiseDuplexRanchSplit-LevelTown HouseCondo
Building Type
Heavy StorageAll Utilities Of
WinterizedVacantOccupiedVegetation IceSnow
Limitations
Page 22 of 50 43204-27722
Unless specificity noted as inspected, detached structures are not included in the Washington State homeinspection.
The swimming pool and all related components are not included in this inspection. Electrical componentsand wiring are prone to corrosion over time and should be inspected by an electrician prior to purchase.
11721 SE McGillivray Blvd, Vancouver, WA 98683
Licensed Home Inspector #237
Brian Gustafson
Date: 15-May-2017
Property and Site
Unless noted otherwise, all exterior components are inspected from the ground. These observations arevisual, limited to what can be seen from that perspective and not exhaustive in scope.
This inspection does not include cosmetic or workmanship issues such as minor typical drywall cracking,uneven trim, unevenness in walls & floors that are typical of using wood for a building material, paint touch-ups etc. Typical wear and tear that is proportional to the age of the home/ structure / system or component,is not documented in this inspection report.
If the house is currently occupied by the owner or tenant and their belongings, storage throughout thehouse, under sinks, in closets, etc will limit inspection of those areas / systems / components or items.Some issues may not become evident until after belongings are removed. UNDER NO CIRCUMSTANCESARE PERSONAL BELONGINGS DISTURBED BY THE INSPECTOR. For a more completeunderstanding of the scope of this inspection refer to the included Washington State Inspection Standards.
SnowRainCloudyClear
Weather Conditions
FrozenSaturatedWetDampDry
Ground Conditions
ErosionEarth to Wood
RavineTreeVegetationFlower BedSlopes to House
Landscaping
If applicable, exterior surface / landscaping drains are not tested during the inspection nor is it determinedwhere underground drains are connected (pipes, drain fields, etc). It is recommend that you contact theseller regarding the adequacy of all exterior drains or have the drains tested, or scoped, by a qualifiedcontractor if concerned.
CrackSettlementSlopes to House
BrickConcreteGravelPaving StoneAsphalt
Driveway
Earth to WoodSettlementDeterioration
RotUnsecuredCrackStoneConcretePatio Block
Paving StoneTileWoodStoneCompositeBrick
Porches / Walkways / Railings
Earth to WoodSettlementDeteriorationMold/Mildew
RotUnsecuredCrackStoneConcretePatio Block
Paving StoneTileWoodStoneCompositeBrick
Decks and Patios
In accordance with Washington State Inspection standards, the underside portion of exterior decks withless than 5 (five) feet of clearance from joist to ground, may not be inspected. In addition, due to wet-climate conditions, areas of non-structural wood rot on deck boards or railings may not be noted in thisreport.
RotNone
IncompletePlasticCompositeWoodMetalUnsecured
Damaged: NoDeck Railings and Covers
Non-permanent covers such as retractable awnings, etc., are not included in this inspection.
Misc.
Page 23 of 50 43204-27722
11721 SE McGillivray Blvd, Vancouver, WA 98683
Licensed Home Inspector #237
Brian Gustafson
Date: 15-May-2017
Property and SiteUnless specificity noted as inspected, detached structures are not included in the Washington State homeinspection.
The swimming pool and all related components are not included in this inspection. Electrical componentsand wiring are prone to corrosion over time and should be inspected by an electrician prior to purchase.
Recorded Property and Site Inspection Times: 5/15/2017 7:57:41 AM - 5/15/2017 7:57:41 AM
Exterior
Restricted
SnowVegetationDebrisSeasonal Storm WindowsClearance
Limitations
Obstructions such as vegetation, storage, dog runs, sheds, etc., may limit complete inspection of theexterior areas of the home
SettlementFoundation PargedNot VisibleDeterioration
CrackPost and PierConcreteBrickConcrete BlockStone
Foundation Wall
Cracks that could be seen in the foundation at the time of the inspection appeared to be typical.Recommend monitoring for signs of future movement/expansion.
WornStucco
Composite OSB / Wood FiberBrick / StoneMetal / VinylRecaulk / Repaint
Earth to SidingBlister/PeelWoodCrack / SplitCement Composite
Exterior Wall Surface
A piece-by-piece inspection of the siding was not performed and is beyond the scope of this inspection.The exterior of the home is inspected from ground level.
The siding has been replaced with cement composite lap type siding. The condition of the walls and orstructure concealed behind the siding can not be determined in this inspection. Advise consulting with theowners and obtaining all permits, invoices and warranty information with respect to the siding installationcontractor.
Mold/MildewRecaulkRepaintBlister/PeelNo Visible Flashing
Windows
Note- If applicable, upper floor windows are inspected from ground level.
The condition the thermal seals in each window cannot be determined in this inspection and is specificallyexcluded from this report.
The windows have been replaced with vinyl windows. Concealed issues regarding the installation cannotbe determined in this inspection. All related contractor invoice and warranties should be obtained from theseller of the home.
Some of the windows are the original aluminum windows and are past the end of their typical service life.Replacement should be considered.
Page 24 of 50 43204-27722
11721 SE McGillivray Blvd, Vancouver, WA 98683
Licensed Home Inspector #237
Brian Gustafson
Date: 15-May-2017
Exterior
Covered
Foundation Vents
East: The vent screens are missing or damaged on the crawlspace vent openings. Advise repair to preventvermin / animal entry into the crawlspace.
Improve the drainage at the crawl vent openings to help keep storm and irrigation water from entering thecrawlspace. Vent openings at or below grade level must have vent wells installed to keep water fromentering the crawlspace.
WeatheredRecaulkBinds
Doors
Exterior Lighting
Open GroundReverse PolarityGFCI Tested and ResetNo Cover
Exterior Outlets
Exterior Electrical Wiring
There are modifications / additions of electrical wiring visible on the exterior of the home. East light waswired with a cord cover instead of conduit. The wiring appears to be poorly / non-professionally installed.Advise correction by an electrician.
There is exposed electrical wiring visible on the exterior of the home at the conduit at the East side of thehome . All exposed wires should be installed within protective conduits. Advise correction by anelectrician.
There are modifications / additions of electrical wiring visible on the exterior of the home. The wiringappears to be poorly / non-professionally installed. Advise correction by an electrician.
Miscellaneous
Unknown drain line was noted leaving the East crawl space area ,advise further investigation with thecurrent home owner as to the use of this drain
Recorded Exterior Inspection Times: 5/15/2017 7:57:41 AM - 5/15/2017 2:57:49 PM
Garage
Two CarDetachedBuilt-InAttached
Type
WeatheredDentedCorrosionStaining
RotMetalWoodSectionalAutomaticBinds
Main Garage Door
The garage door operated , door is weathered
Page 25 of 50 43204-27722
The evaluation of the roof provided by this inspection is a general guideline only and does not constitute aformal roof certification. Some deficiencies such as leaks may not be visible on the day of the inspection.Accordingly this inspection does not include any guarantees against current or future leaking nor the needfor roof repairs or replacement. If a precise estimate of the current condition and remaining usefulness ofthe roof is desired, contact a licensed roofer for a full technical evaluation. Upper story roofs on two-storyhomes may not be walked on due to Washington State safety regulations.
11721 SE McGillivray Blvd, Vancouver, WA 98683
Licensed Home Inspector #237
Brian Gustafson
Date: 15-May-2017
Garage
Noisey
Garage Door Opener
Carpeting / Concealed SettlementCrack
Floor
Due to very Heavy storage in the garage - unable to inspect garage floor and or the walls thoroughly.
CrackStainPatchedUnfinished
Wall
CrackStainPatchedAttic AccessUnfinished
Ceiling
The attic pull-down stairs located in the garage, should have a fire rated drywall cover added to the bottomof the access panel to ensure proper fire-wall integrity. Advise correction.
Windows
GFCI Tested and Reset
Open GroundNo GroundReverse PolarityInstall GFCI
Lights / Receptacles
We recommend installation of GFCI receptacles to reduce risk of electrical shock.
BindsCorrosion
Access Door
Miscellaneous
Garage shelving and / or cabinets are not included in this inspection.
Recorded Garage Inspection Times: 5/15/2017 7:57:41 AM - 5/15/2017 1:46:05 PM
Roof Structure
Walk OnRoof EdgeBinocular
Method of Inspection
Slick SurfaceIce / SnowRainFragile Roofing Steep SlopeHeight
Limitations
Page 26 of 50 43204-27722
11721 SE McGillivray Blvd, Vancouver, WA 98683
Licensed Home Inspector #237
Brian Gustafson
Date: 15-May-2017
Roof Structure
The evaluation of the roof provided by this inspection is a general guideline only and does not constitute aformal roof certification. Some deficiencies such as leaks may not be visible on the day of the inspection.Accordingly this inspection does not include any guarantees against current or future leaking nor the needfor roof repairs or replacement. If a precise estimate of the current condition and remaining usefulness ofthe roof is desired, contact a licensed roofer for a full technical evaluation. Upper story roofs on two-storyhomes may not be walked on due to Washington State safety regulations.
Estimated Slope: 6/12Estimated Age: 1 -3 years
ShedHipValleyGableFlat
Main Roof Type
DentsNeed To Clean
LeakImproper SlopeRust / CorrosionIncompleteNot Secured
Gutters and Downspouts
Monitor gutters and downspouts on a continuing basis during periods of rain. Seal any leaking joints andclean any clogs in the gutters, downspouts and drains as needed to reduce the chance of moisture damageto the surrounding structure.
Downspouts that drain into underground drain systems are not tested for functionality / water flow.
Not Vented
WornUnpaintedPaint PeelingStainMildew/MoldLoose
Fascia / Soffit / Eaves
There are water stains visible on the underside of the eaves indicating past or current leaks. Furtherinvestigation is advised
There is rot apparent in the fascia / eaves. There may be additional concealed damage, a more thoroughexamination is required to determine the full extent of damage. Advise replacement of all damagedstructure.
Estimated # of Layers 1
Upgraded Composition3-Tab AsphaltExcessive Wear
Advise Further EvaluationImproper InstallationWornMoss
PatchedCrackBrokenMissing ShinglesLoose
Rolled RoofingMetalTarWood ShakeWood ShingleTile
Roof Covering
The home has an upgraded composition roof covering. This type of roof covering has an approximate lifeof 25 to 30 years. The actual service life will vary with different shingle brands and specific applications.
Dish
AntennaSkylightElectrical MastPlumbing StackAttic VentsNot Secured
Accessories
ConcealedImproperResealTarred
CorrosionDeteriorationGapMetalRoll RoofingValley
StackRoof to WallSkylightFlat RoofDrip EdgeChimney
Flashing
Page 27 of 50 43204-27722
11721 SE McGillivray Blvd, Vancouver, WA 98683
Licensed Home Inspector #237
Brian Gustafson
Date: 15-May-2017
Roof Structure
Gas Appliance VentMossNo CapAbandoned
LooseCorrosionDeteriorationCrackFireplace / Wood Stove
Chimney / Flue
Recorded Roof Structure Inspection Times: 5/15/2017 7:57:41 AM - 5/15/2017 1:47:47 PM
Attic
InsulatedEntered
Looked In OnlyStorage ObstructionsSealedNo Visible Access
Limitations
Due to limited access and insulation covering the structure, some areas of the attic can not be viewed forinspection. The attic inspection is limited to only the areas that can be viewed from reasonable points ofaccess. It is not possible to view all areas or identify all potential issues in the attic.
Pull Down LadderDoorHatch
Attic Access
Warped / SagRafterTruss
Structure
Visible StainingRe-SheathedBoardOSB / Plywood
Sheathing
There are moisture stains on the underside of the roof sheathing. This indicates past or present roof leakissues. There was no visible moisture present during this inspection. Advise further investigation andcorrection as necessary.
Estimated Depth 14''
Batt TypeVermiculite
FoamBlown / Loose FillCelluloseFiberglass / Mineral Wool
Insulation
Some older homes may have insulation material containing vermiculite. The insulation may be concealedand not identified in this report. Some vermiculite may contain asbestos and may represent a hazard ifdisturbed. Hazardous materials may not be identified in this inspection, if you have concerns, further testingshould be performed.
Only visible portions of the insulation are inspected. Insulation material is not disturbed in this inspection.
Obstructed Mechanical FanGable EndSoffitRoof / Ridge
Ventilation
The performance of the attic vents / ventilation cannot be determined in this inspection.
Flex TypeMetalInto The AtticConcealed
Exhaust Ducts
Page 28 of 50 43204-27722
11721 SE McGillivray Blvd, Vancouver, WA 98683
Licensed Home Inspector #237
Brian Gustafson
Date: 15-May-2017
Attic
Open Wire Splices
Knob & Tube VisiblAbandoned WiringConcealed
Electrical
There are indications of electrical additions and / or modifications visible in the attic. All related permits andinvoices should be obtained from the homeowner. In the absence of documentation an electrician shouldinspect and make corrections as necessary.
Recorded Attic Inspection Times: 5/15/2017 7:57:41 AM - 5/15/2017 3:07:01 PM
Crawlspace
Inadequate ClearancesStanding WaterNo AccessInsulated
Crawlspace Limitations
Inspection of the crawlspace is limited due to ducting, plumbing, insulation, etc. Crawlspace inspectionsare limited and all areas cannot be viewed or inspected. It is not possible or assured that all defects can beidentified in the crawlspace. Areas that have been excluded may have unreported damage to structures orcomponents.
ExteriorInteriorBinds
Crawlspace Door
WoodMetalStainConcealed
Floor Joists
The overhead floor is insulated, covering the sides of the joists and the underside of the floor. The floorstructure is concealed and was not inspected.
Concealed
Sill Plate
The sill plate is concealed by insulation and not visible for inspection.
MetalWoodConcealed
Beam
BlockWoodBrick
Posts
Concealed
Foundation Wall
Standing Water
DampMoisture StainingInsulatedVapor Barrier
Crawlspace Conditions
Page 29 of 50 43204-27722
11721 SE McGillivray Blvd, Vancouver, WA 98683
Licensed Home Inspector #237
Brian Gustafson
Date: 15-May-2017
Crawlspace
Batts of insulation been torn down throughout the crawl space under the home . Down / hanging insulationlimits view of the crawl space in many areas . Advise removal of and replacement of any damagedinsulation as needed
There is visible evidence of past plumbing leaks below the bathrooms and the kitchen (dry stains on theground). No current leaks visible.
Animal ActivitInsectsRodent Activity
Animal / Rodent / Insect Activity
InsulatedVisible LeaksNot Secured
Crawlspace Ducts/Pipes
Main Hall : The drain line or related component is leaking below the bathroom. Advise proper repairs by aplumbing contractor.
NoneInadequateObstructed Mechanical
Crawlspace Ventilation
We recommend keeping all foundation vents unblocked year round, except during freezing weather, toprovide adequate ventilation especially in the winter months when it is the most damp outside.
Recorded Crawlspace Inspection Times: 5/15/2017 7:57:41 AM - 5/15/2017 2:53:46 PM
Electrical Service
Not Secured120/240 VoltOverheadUnderground
Service Entrance
Electrical systems are inspected only in a very limited and general manner. We do not inspect the functionof low voltage wiring or 220-volt outlets and/or systems. This is not an electrical code complianceinspection.
While testing outlets within the home, personal items will not be moved or unplugged. In addition,accessible receptacles and switches will be checked for function but not load capacity. Only exteriorreceptacles that are attached to the house will be tested or inspected. No ancillary or low voltage wiring istested or inspected. 3-prong type receptacles are checked for polarity and grounding, 2-prong receptaclesfor polarity and function. Meters are not used to determine specific line voltage.
CopperAluminumConcealed
Entrance Cable
Circuit BreakerSwitch / Cartridge Fuse / Other
Main Disconnect
Page 30 of 50 43204-27722
11721 SE McGillivray Blvd, Vancouver, WA 98683
Licensed Home Inspector #237
Brian Gustafson
Date: 15-May-2017
Electrical Service
Rated Amperage Of Disconnect 200
No Main Shut-Off At The Pane
Disconnect Rating
Panel Location Laundry
Multiple Service PanelsObsolete Panel
Rust / CorrosionObstructedNon Standard InstallationNot Opened
Distribution Panel(s)
There are visible non-professional modifications in the main service panel. Wiring has been installed without the use of grommets to secure the wiring in to the panel . Advise inspection and correction by anelectrical contractor.
Amps 200
Distribution Panel Amperage Rating
Over-FusedAFCI BreakerGFCI Breaker
Circuit Breakers
Determining if the circuits in electrical panels are labeled accurately is beyond the scope of this inspection.
ScorchedCorrosionCopperBraided AluminumSolid Aluminum
Circuit Wire
The home has solid conductor aluminum branch circuit wiring visible in the service panel. In accordancewith Washington inspection standards, this type of wiring is considered a potential hazard and should beevaluated by a licensed electrician.
Water MainGround RodConcealed
Service Grounding Conductor
Electrical bonding is concealed and cannot be affirmed in this inspection.
Location garage
Obsolete
CorrosionUnsecuredNot OpenedNon Standard InstallationConcealed
Auxiliary Service Panel
The ground and neutral wires are not properly isolated in the sub-panel. This is an improper wiringcondition. Advise correction by an electrician.
Amps 50 amp
Auxiliary Disconnect Rating
Amps 50
Room For Expansion
Auxiliary Panel Rating
Page 31 of 50 43204-27722
11721 SE McGillivray Blvd, Vancouver, WA 98683
Licensed Home Inspector #237
Brian Gustafson
Date: 15-May-2017
Electrical Service
ScorchedOver Fused
BlownGFCI BreakerTime DelayCartridgeGlassBreaker
Auxiliary Fuse/Breakers
Recorded Electrical Service Inspection Times: 5/15/2017 7:57:41 AM - 5/15/2017 1:43:47 PM
Heating & Cooling
Other3rd Floor2nd Floor1st FloorBasement
Smoke Alarms
Testing of smoke and CO alarms / detectors is excluded from the Washington state home inspection. Werecommend testing regularly according to manufacturer's instructions. Consult your local fire departmentregarding any questions on concerns. We advise installation of smoke detectors on each level of the homeand in each bedroom. Batteries should be replaced in existing units.
Smoke alarms have a limited life span. Alarms that are ten years old or older should be replaced (Look forthe date stamp on the smoke alarm.) Test smoke alarms monthly and vacuum to remove dust andcobwebs.
Washington State requires the installation of CO detector(s) in all homes sold after April 1, 2012.Installation of CO detectors is advised.
Installed Lower FloorInstalled Upper FloorInstalled Main Floor
CO Alarms
Washington State requires the installation of CO alarms(s) in all homes sold after April 1, 2012. Installationof CO detectors on each level of the home is advised.
Ductless SystemRadiatorsForced AirConvectors
Heating Distribution
On forced air type systems, not all air registers can be viewed or inspected in an occupied home. Air flowis not measured at the registers.
The home has individual wall mounted heaters in each living area. The units should be cleaned regularlyfor safe / proper operation.
Recorded Heating & Cooling Inspection Times: 5/15/2017 7:57:41 AM - 5/15/2017 7:57:41 AM
Page 32 of 50 43204-27722
The home has old cast iron sewer lines. These are subject to corrosion and failure over time. The waterflow test conducted during this inspection can not simulate living conditions. Advise further investigation ofthe sewer drain condition with a drainage contractor.
11721 SE McGillivray Blvd, Vancouver, WA 98683
Licensed Home Inspector #237
Brian Gustafson
Date: 15-May-2017
Plumbing Components
OtherWater is Shut OffPrivate SystemFinished Basement
Limitation
The purpose of the plumbing system inspection is to determine if the household plumbing is currentlyfunctional for typical / normal usage. A technical evaluation to determine the adequacy or ongoingusefulness of the plumbing pipes, fixtures, etc is not included (this service can be performed by a licensedplumber if desired). Drain lines from the house to the street, particularly in older homes, may fail over timeand require repair or replacement. This inspection does not include sprinkler or irrigation systems or anyrelated component. Fire-suppression sprinkler systems are excluded and any related components.
At Meter
Main Gas Utility Shut Off
Interior of The Home
In CrawlspaceIn BasementIn GarageAt MeterNot Visible
Main Water Line Shut Off Location
Main water shut off valves are not tested during the inspection.
TypicalLow
Observed Water Flow
Covered / Not VisibleAnti-SiphonFrost Free
Hose Bibb
Non-frost proof hose valves are required to be shut off and drained in freezing temperatures. Non-attachedwater valves are not tested or inspected in this inspection.
InsulatedConcealedCopperPlasticGalvanized
Distribution Piping
The plumbing system is mostly concealed within the walls, floors and ceilings of the home, and not fullyvisible for inspection. Piping observed at this inspection include only the areas with exposed pipingaccessible for inspection within the home interior, basement areas or crawlspace. All other areas ofconcealed piping are excluded from this inspection report.
The water pipes are older and of galvanized steel construction. Typically water pressure will be reduceddue to corrosion build up.
Exterior East: There are visible plumbing modifications noted. Advise obtaining all related permits andcontractor invoices or further evaluation by a plumber.
Advise System be ScopedConcealed
CorrosionNot SecuredCopperPlasticCast IronGalvanized
Waste Drainage
Page 33 of 50 43204-27722
11721 SE McGillivray Blvd, Vancouver, WA 98683
Licensed Home Inspector #237
Brian Gustafson
Date: 15-May-2017
Plumbing Components
Buried &/or concealed sewer drain lines are outside the scope of this inspection. Sewer lines can often bepartially obstructed, cracked, crushed, disconnected or in some other way damaged in a way that would notbe detected in this inspection. The water flow test conducted during this inspection can not simulate livingconditions.
The inspection of the sewer and drain line components is limited to what is visible within the home interiorand the crawlspace / basement areas (if present). ALL systems and components OUTSIDE of the homeincluding but not limited to, sewer pumps, tank alarms, septic and step systems, are excluded from thisinspection.
The bathtub and sink drain overflows are not tested in this inspection.
The home has old cast iron sewer lines. These are subject to corrosion and failure over time. The waterflow test conducted during this inspection can not simulate living conditions. Advise further investigation ofthe sewer drain condition with a drainage contractor.
ConcealedPlasticCast IronGalvanized
Vent Stack Piping
Location was not located
Damaged CoverImproper PlugConcealed
Main Sewage Cleanout
Approximate Year of Manufacture: unkown
CorrosionGasElectricTankless Unit
Water Heater
The generally accepted maximum safe water temperature is one hundred twenty degrees Fahrenheit (120).The water temperature was not tested during this inspection.
NOTE- Lowering the water temperature to safe levels increases the risk of bacterial growth and necessaryprecautions should be taken.
Although the water heater was not acceded for inspection. ,the water heater has been replaced. Adviseobtaining the permits and contractor invoices from the homeowner.
Recorded Plumbing Components Inspection Times: 5/15/2017 7:57:41 AM - 5/15/2017 2:17:49 PM
Laundry
WornTornStainCrack
Floor / Wall / Ceiling
DamagedBindsMissing
Door
Unsecure
Lighting / Receptacles
Drain Pan RecommendedNot Tested
Washer
Page 34 of 50 43204-27722
11721 SE McGillivray Blvd, Vancouver, WA 98683
Licensed Home Inspector #237
Brian Gustafson
Date: 15-May-2017
Laundry
Installed washer and dryers conceal some areas of the floor and walls.
The washer drain function was not tested.
Not Tested
Dryer
The 220 volt dryer receptacle is not tested. The internal condition of the dryer exhaust vent/ducting cannotbe viewed or inspected. Cleaning on a regular schedule is recommended.
Recorded Laundry Inspection Times: 5/15/2017 7:57:41 AM - 5/15/2017 2:18:14 PM
Living Room Family RoomFireplace
Non-Vented Gas
MasonrySealed GasZero-ClearanceWood InsertGas InsertFree Standing
Fireplace Description
Cracked
Hearth / Doors / Firebox
CreosoteCorrosionNot-SecuredBindsMissingNone
Damper
Advise Inspection/CleaningUnsecureSootNot Checked
Chimney Flue
On wood burning fireplaces, the fireplace flue cannot be fully viewed or inspected.To ensure safe operation, cleaning and inspection of flue and fireplace/firebox/chimney/flue advised by alicensed qualified chimney contractor prior to use.
Recorded Living Room Family Room FireplaceInspection Times:
5/15/2017 7:57:41 AM - 5/15/2017 2:37:46 PM
Bathrooms
Four + BathsThree Bath
Two BathOne Bath3rd Floor2nd Floor1st FloorBasement
Bathroom Info
LowSuspectNormal
Water Flow
WornTornCrackStain
Floor
Page 35 of 50 43204-27722
11721 SE McGillivray Blvd, Vancouver, WA 98683
Licensed Home Inspector #237
Brian Gustafson
Date: 15-May-2017
Bathrooms
StainCrackPatched
Wall
StainPatchedCrack
Ceiling
DamagedNot Tested
FoggedBindsStainMold/MildewSkylightStationary
Windows
DamagedBindsMissing
Door
GFCI Tested and ResetOpen Ground2 Pronged
Reverse PolarityInstall GFCIUnsecuredNo CoverDamaged
Lighting / Receptacles
Recommend installation of GFCI receptacles to reduce risk of electrical shock.
Advise InstallationDamagedNoisyCover Missing
Exhaust Fan
WornLeakCorrosionUnsecuredCrackChip
Sink
Non-Standard Vent Device
Flex PipeLeakCorrosionSlow DrainImproper TrapUnsecured
Faucet / Trap / Drain
Both Bathrooms : The drain has a non-approved drain connection (flex pipe). Advise replacement by aplumber.
Not SecuredWornDamaged / Loose HardwareMold/Mildew
Vanity / Counter Top
LeakCrackNot SecuredTank LooseNo Shut-Off
Toilet
Master : The toilet base is loose on the floor. Advise removing the toilet and re-setting with a new wax seal.Leaking toilet seals will damage the wood floor structure if not corrected. The concealed floor structureshould be examined when the base has been removed. Any damaged structure should be replaced.
Worn
ChipCrackMold/MildewRecaulk/RegroutNot Secured
Tub and Enclosure
Page 36 of 50 43204-27722
Failed seal between double panes of glass. Window has fogged.
11721 SE McGillivray Blvd, Vancouver, WA 98683
Licensed Home Inspector #237
Brian Gustafson
Date: 15-May-2017
Bathrooms
The condition of the wall / structure behind the enclosure cannot be viewed or inspected.
Worn
LeakCorrosionUnsecuredCloggedSticksNot Tested
Tub Faucet / Shower Head and Drain
Main Hall : The Hot water at the highest setting is only warm at the shower tub enclosure . Advisecorrection by a plumbing contractor
Worn
ChipCrackMold/MildewRecaulk/RegroutNot Secured
Shower Enclosure
The condition of the wall / structure behind the enclosure cannot be viewed or inspected.
Master: There is visible chips / damage on the surface of the shower enclosure . Advise professionalrepair.
WornLeak
MisingCorrosionNot SecuredCloggedSticksNot Tested
Shower Faucet / Head and Drain
None
Heat LampAir RegisterConvectorRadiant Floor / CeilingBaseboard
Heat Source
Main Hall : The ceiling heater has been removed There is no visible heat source in this room. Advisecorrection.
Recorded Bathrooms Inspection Times: 5/15/2017 7:57:41 AM - 5/15/2017 2:35:18 PM
Kitchen
WornTornStainCrack
Floor
StainCrackPatched
Wall
StainPatchedCrack
Ceiling
DamagedNot Tested
FoggedBindsStainedMold/MildewSkylightStationary
Windows
Page 37 of 50 43204-27722
11721 SE McGillivray Blvd, Vancouver, WA 98683
Licensed Home Inspector #237
Brian Gustafson
Date: 15-May-2017
KitchenFailed seal between double panes of glass. Window has fogged.
GFCI Tested and ResetOpen Ground2 Pronged
Reverse PolarityInstall GFCIUnsecuredNo CoverDamaged
Receptacles / Lights / Fans
Recommend installation of GFCI receptacles to reduce risk of electrical shock.
WornCorrosionCrackChip
Sink(s) and Faucets
Non-Standard Vent Device
Flex PipeLeakCorrosionSlow DrainImproper TrapNot Secured
Trap/Drain
UnsecuredWornRegroutRecaulk
Cabinets / Counters
NoisyNo LightNo ExhaustCooktop Exhaust
Range Hood
Kitchen exhaust fan inoperative at time of inspection.
ConcealedNot SecuredDuctless
Exhaust Vent / Filter
Did Not Test All FunctionsTested ON/OFF only.
Major Appliances (Built-in)
The appliance testing performed in this inspection is a basic functional test of each built-in appliance. Notevery function or cycle can be tested and the accuracy of temperature control cannot be determined.Intermittent problems may not be detected in this inspection. Older appliances may be unreliable. Werecommend you invest in a home warranty designed for repair or replacement of mechanical item failures inthe homes. No warranties concerning satisfactory operation are given.
Appliances are not moved during the inspection.
DamagedNot SecuredLeakTested ON/OFF Only
Dishwasher
Exposed WiringNoisyTested ON/OFF only
Garbage Disposal
DamagedInterior cold to the touch
Refrigerator
Page 38 of 50 43204-27722
Testing of smoke alarms is not part of the Washington State Home inspection. Recommend testingregularly according to manufacturer's instructions. Consult your local fire department regarding anyquestions on concerns.
Smoke alarms have a limited life span. Alarms that are ten years old or older need to be replaced becausethe sensor wears out. (Look for the date stamp on the smoke alarm.) Test smoke alarms monthly. Vacuumyour alarms monthly to remove dust and cobwebs.
We advise installation of smoke detectors on each level of the home and in each bedroom. Batteriesshould be replaced in existing units.
11721 SE McGillivray Blvd, Vancouver, WA 98683
Licensed Home Inspector #237
Brian Gustafson
Date: 15-May-2017
Kitchen
DamagedNot SecuredBurners/Elements Function
Stove/Oven/Range
NoneAir RegisterRadiant Floor / CeilingBaseboard / Wall Heater
Heat Source
Recorded Kitchen Inspection Times: 5/15/2017 7:57:41 AM - 5/15/2017 1:53:29 PM
Interior Living Areas
WornTornStainCrack
Floors / Walls / Ceilings
Damaged
Not TestedBindsStainMold/MildewSkylightFixed
Windows
Living Room : Window pain is missing from the sliding windows left . Advise replace
Open J BoxOpen Ground
2 ProngedReverse PolaritySwitchedNo CoverDamaged
Receptacles / Lighting / Fans
Mold/MildewDamagedBinds
Closets and Doors
Trip HazardWornNot Secured
Stairway and Railings
Loose HingesBindsWeather Seal Damaged
Exterior Doors
NoneFloor / Ceiling RadiantAir RegistersBaseboard / Wall Heater
Heating Source
Advise InstalltionNone VisibleInstalled
Smoke Detectors
Page 39 of 50 43204-27722
11721 SE McGillivray Blvd, Vancouver, WA 98683
Licensed Home Inspector #237
Brian Gustafson
Date: 15-May-2017
Interior Living Areas
Testing of smoke alarms is not part of the Washington State Home inspection. Recommend testingregularly according to manufacturer's instructions. Consult your local fire department regarding anyquestions on concerns.
Smoke alarms have a limited life span. Alarms that are ten years old or older need to be replaced becausethe sensor wears out. (Look for the date stamp on the smoke alarm.) Test smoke alarms monthly. Vacuumyour alarms monthly to remove dust and cobwebs.
We advise installation of smoke detectors on each level of the home and in each bedroom. Batteriesshould be replaced in existing units.
Recorded Interior Living Areas Inspection Times: 5/15/2017 7:57:41 AM - 5/15/2017 1:53:53 PM
Bedrooms
Four+ BedroomsThree Bedroom
Two BedroomOne BedroomStudioUpper FloorMain FloorBasement
Bedroom Information
WornTornStainCrack
Floors / Walls / Ceilings
DamagedNot Tested
FoggedBindsStainMold/MildewSkylightStationary
Windows
DamagedBindsMissing
Door
Missing / RemovedMold/MildewDamagedBinds
Closets
Open J BoxOpen Ground2-Pronged Type
Reversed PolaritySwitchedNot SecuredMissing CoversDamaged
Receptacles / Lighting / Fans
NoneAir RegisterRadiant Floor / CeilingBaseboard / Wall Heater
Heat Source
Advise InstallationNone VisibleInstalled
Smoke Detectors
Testing of smoke alarms is not part of the Washington State Home inspection. Recommend testingregularly according to manufacturer's instructions. Consult your local fire department regarding anyquestions on concerns.
Smoke alarms have a limited life span. Alarms that are ten years old or older need to be replaced becausethe sensor wears out. (Look for the date stamp on the smoke alarm.) Test smoke alarms monthly. Vacuumyour alarms monthly to remove dust and cobwebs.
We advise installation of smoke detectors on each level of the home and in each bedroom. Batteriesshould be replaced in existing units.
Recorded Bedrooms Inspection Times: 5/15/2017 7:57:41 AM - 5/15/2017 1:53:41 PM
Page 40 of 50 43204-27722
Pilla
r To
Post
®Aluminum Branch-circuit Wiring
Information Series©2007 Pillar To Post Inc.
If you ask three electricians about the uses and safety of aluminum wiring, you will likely get at least three different answers. Furthermore, opinion varies again depending on where you live in North America. The more you research into aluminum wiring, the more frustrated you may become. We hope this article will clear up any confusion and end the frustration.
What’s the Problem with Aluminum Wiring?From the mid ’60s to the late ’70s, aluminum wire often replaced copper as a less expensive alternative. Aluminum, however, is not a direct replacement for copper since each type of wire has different physical properties. Aluminum’s properties proved problematic for reasons no one had anticipated. What you need to know is the following: with aluminum wiring it is possible that, over time, a high resistance connection and/or arcing could develop somewhere in the electrical system, resulting in a connection that gets very hot and increases risk of fire.
Fortunately, the problems associated with aluminum wiring are now well understood, thus shifting the focus to rendering existing installations safe. A knowledgeable electrician with aluminum wiring experience can check for safety and fix what needs fixing.
SolutionsRe-wire the HomeIf you are renovating, or the configuration of your home is such that stringing new wiring is relatively easy, re-wiring your home may be a good idea. In most cases, however, re-wiring is an expensive and disruptive undertaking.
COPALUM® Crimp ConnectionCOPALUM® is a proprietary system that involves crimping a copper wire to existing aluminum wire using a special crimp connection tool that exerts extremely high pressure on the joint. This kind of connection is called “cold welding.” The copper wire is then connected to fixtures and outlets, etc. Once you “convert” the aluminum to copper with the cold-weld method, the repair is considered permanent. This solution, however, is expensive and requires an electrician certified in this system.
Page 41 of 50 43204-27722
Pillar To Post®, the home of home inspectionWe welcome your comments and suggestions for future Information Series topics
[email protected] 1-800-294-5591 www.pillartopost.com
Pigtail RepairSimilar to the COPALUM connection described above, the pigtail repair method involves attaching copper wire to the existing aluminum. Pigtailing uses special twist connectors compatible with both aluminum and copper. While the pigtailing parts are inexpensive and readily available, the pigtailing technique requires specialized knowledge and experience. Furthermore, although pigtailing is cheaper than the COPALUM system, its success depends entirely on how well the electrician executes the repair. It is difficult to get a good connection that will not oxidize, making long term safety an issue. Some believe that a poorly executed pigtail is worse than doing nothing. In some geographical areas, pigtailing is not considered an acceptable solution.
Retrofit all Connections with Aluminum Compatible DevicesStandard electrical outlets and light switches are not compatible with aluminum wiring. Fortunately, tested and approved replacement devices and connectors are available from electrical supply shops. Some devices, however, such as ceiling-mounted light fixtures not rated for aluminum wire, still require an electrician who knows the pigtailing technique.
A Few More PointsIn 1972, a new aluminum alloy, and aluminum-compatible devices, entered the market. Homes wired with aluminum after 1972 are more likely to have this new aluminum. This new aluminum solved many of the problems associated with the original aluminum wiring. These homes, however, still require an experienced electrician for a wiring retrofit.
Also, generally speaking, the problems associated with aluminum wiring have to do with branch-circuit wiring smaller than 8 gauge. Anything 8 gauge and higher, such as wiring for a dryer or stove, does not present a problem.
Most important to remember: if you have aluminum wiring, a licensed and experienced electrician should perform all electrical work.
The Best Course of ActionSince even amongst electricians misinformation and confusion persist, an electrician with specific knowledge and experience should evaluate each home on a case-by-case basis.
The good news is, aluminum wiring can be made safe, but seek the advice of an expert.
Page 42 of 50 43204-27722
Pilla
r To
Post
®Ground Fault Circuit Interrupter
Information Series©2007 Pillar To Post Inc.
A ground fault circuit interrupter, or GFCI, is an inexpensive electrical safety device that can protect you and your family members from a serious electric shock.
Have you ever had an electric shock? While it is an unpleasant experience, it is not usually fatal. However, given the right conditions, the same shock could be fatal! If your body makes a solid connection to the ground, the shock could easily kill you. Here are two examples of a solid ground connection: If you are physically standing or
touching the ground outsideIf you touch something conductive, such as any part of the plumbing system in your
house, that is also touching the ground outside
In other words, if you decide to operate your hedge trimmer in your bare feet and you get a shock, you may not survive it.
How Can a GFCI Help?A GFCI is a special electrical outlet that prevents electric shocks in situations such as the ones described above. The GFCI monitors the electrical current leaving from and returning to the outlet. The current leaving the outlet should be the same amount as the returning current. If the current returning is less than that which leaves, the missing current could be passing through somebody’s body to the ground. The GFCI detects the mismatch and shuts off the electrical outlet in a split second.
Where Should GFCI Outlets Be Located?GFCI outlets should be installed in any area that presents a risk of an electric shock withg a direct path to the ground. In other words, anywhere you might directly touch the ground outside or anywhere where you might touch a part of the plumbing system. Some smart GFCIs locations are: Exterior outletsKitchen counter outlets (not common in Canada)Bathroom outletsGarage outletsOutlets in unfinished basements
Page 43 of 50 43204-27722
Pillar To Post®, the home of home inspectionWe welcome your comments and suggestions for future Information Series topics
[email protected] 1-800-294-5591 www.pillartopost.com
This is not a complete list. Areas near swimming pools, hot tubs, and so on should also include this type of outlet.
GFCIs are not perfect, however, and have been known to “nuisance trip” when connected to certain types of electrical equipment. For this reason, exceptions to the suggested (or required) locations for GFCIs exist. For example, a regular outlet would be a better choice for a freezer in your garage since the potential for nuisance tripping of the GCFI is high and might go undetected for days, leading to spoiled food in the shut-off freezer.
Remote GFCISeveral electrical outlets usually connect to a single circuit in an average home. A single GFCI outlet will protect all of the outlets in the circuit, even if the other outlets are not GFCIs. But the GFCI outlet must be the first outlet in the string in order for it to properly protect the other outlets, and, of course the connections have to be properly made.
Remote GFCIs sometimes cause confusion for home owners in the following ways:A home owner thinks the bathroom does not have a GFCI because the outlet looks like a standard one.
The standard outlet under the protection of a remote GFCI should have a sticker indicating its GFCI protection. The problem is, the sticker does not stick forever. A Pillar To Post® inspector can test this for you.
A standard outlet that does not appear to work in a bathroom or kitchen may actually be attached to a remote GFCI outlet that has nuisance tripped. Before calling an electrician, check the GFCI outlets in other bathrooms and in other locations around the house.
TestingGFCIs are easy to test and should be tested every month. Simply press the test button on the outlet. You should hear a pop as the reset button pops out a little. To reset, just press the reset button. If the GFCI fails to trip, or if you are unable to reset it, it is time for an electrician to replace it.
Special breakers also provide GFCI protection to the entire circuit. These breakers can be installed instead of GFCI outlets. The GFCI breaker should also be tested monthly. You will recognize this breaker from the test and reset button.
GFCIs can help prevent injury and death from electric shock. It is a small device worth having to ensure the safety of your family members.
Page 44 of 50 43204-27722
Pilla
r To
Post
®Fireplaces & Wood Stoves
Information Series©2007 Pillar To Post Inc.
There is nothing like the ambiance of a wood burning fireplace. But like any heating system, wood burning fireplaces require maintenance to ensure safe and efficient operation. They should be inspected and cleaned every year. This process is not a do-it-yourself job.
Most chimney flues are not readily visible when you look up the chimney. Often, you cannot properly inspect the flue until it has been cleaned. It is important to get your chimney and flue cleaned and inspected every year for a number of reasons, but the two main reasons involve safety. Simply put, get the flue cleaned to avoid a chimney fire. A chimney fire occurs when the combustible deposits in the chimney (creosote) ignite. A chimney fire involves flames shooting out the chimney top, and air roaring up the chimney to feed the fire. It is as loud as it is dangerous! A chimney sweep can remove the creosote deposits that potentially cause fires. Second, have the flue inspected. A flue liner in good condition will help protect your home if you do have a chimney fire. An inspection of the chimney flue is not part of a home inspection. Call a trained technician to clean and inspect your chimney flue.
Old Unlined ChimneysFireplaces in old homes may not have clay flue liners. It is particularly important to seek the advice of an expert for these old chimneys. Unlined brick chimneys come in two varieties: single thickness (four inches of brick), and double thickness (eight inches of brick). There is little debate that a four inch thick, unlined chimney is not acceptable. This chimney should either have a liner added, or the fireplace decommissioned. For chimneys with eight inch brick, conflicting opinions abound. Some believe these are safe as long as the brick and mortar are in good condition, and the flue is cleaned regularly. Others believe
Page 45 of 50 43204-27722
Pillar To Post®, the home of home inspectionWe welcome your comments and suggestions for future Information Series topics
[email protected] 1-800-294-5591 www.pillartopost.com
that double brick flues should also have a liner added. Consider hiring an expert who does not offer a chimney lining service. This will give you an unbiased expert opinion on whether a liner is needed.
Glass DoorsSome fireplaces have glass doors across their opening. The glass doors reduce heat loss when the fireplace is not running. Most glass door systems added to an existing fireplace are not designed to be closed when the fire is lit. On the other hand, some high efficiency zero-clearance fireplaces are designed for operation with the doors closed. If you are not sure, ask the technician who cleans and inspects your fireplace and flue.
Wood StoveA wood stove is more efficient than a fireplace. Modern wood stoves burn wood cleanly and efficiently. Like fireplaces, the wood stove must be cleaned and inspected annually. An expert will check the flue, the hearth and the clearance to combustibles. The clearance to combustibles information is listed on the data tag on the wood stove.
Zero-ClearanceToday, a fireplace can be added to almost any home. A zero-clearance fireplace can be installed directly against an existing wall and supported by the existing floor (a foundation is not required). A good installer is a must for this job.
Tips for All Wood Burning FireplacesDo not burn trash.Do not burn pressure-treated
or painted wood.Burn seasoned hardwood.
Softwood will cause creosote to build up more quickly.
Load the logs near the back of the fireplace.
Use the spark screen.Make sure smoke and CO
detectors are functioning.Have the chimney and
fireplace or wood stove inspected and cleaned annually.
Page 46 of 50 43204-27722
Pilla
r To
Post
®Smoke Alarms
Information Series©2007 Pillar To Post Inc.
Smoke alarms are an incredible success story. Once the concept took hold in the 1970s, it wasn’t long before the fire death rate was cut in half! Now, more than three decades later, most homes have at least one smoke alarm but we still have a problem – the smoke alarms aren’t working! In one quarter of the homes with smoke alarms, the smoke alarms don’t work. The cause is missing, dead or disconnected batteries (National Fire Protection Association). Pillar To Post® would like to encourage you to pay more attention to your smoke alarms.
The two key goals of smoke alarms are –To wake you up. You can’t sense smoke and flame when you are asleep.Early warning. The sooner you know about a fire the better the possible outcome
Placement of Smoke AlarmsWhile you should consult the instructions provided with the smoke alarm, here are some general guidelines. We do not address local bylaws and codes here.There should be at least one smoke alarm per floor including the basement.Smoke alarms should be placed outside every separate sleeping area. Many authorities
suggest an alarm inside each bedroom as well.The alarm can be placed on the ceiling or high up on the wall. If the alarm is on the
ceiling, it should be at least four inches away from any walls. If the alarm is on the wall, it should be at least four inches but not more than twelve inches from the ceiling.
Peaked ceilings have stagnant air at the top. The smoke alarm should be three feet from the highest point.
Do not place the smoke alarm where it could be affected by drafts such as next to a window or air vent.
Page 47 of 50 43204-27722
Pillar To Post®, the home of home inspectionWe welcome your comments and suggestions for future Information Series topics
[email protected] 1-800-294-5591 www.pillartopost.com
MaintainingTest the smoke alarm once per month by pressing the test button until the alarm sounds then release the button. If the smoke alarm is battery operated, replace the battery every year. If you hear a chirping sound from the smoke alarm, change the batteries. Dust or vacuum the surface periodically. Replace the entire unit if it is older than 10 years or if you are not sure how old it is. Print the installation date inside the cover.
False AlarmsNuisance tripping of your smoke alarm is bound to happen occasionally. Unfortunately, many people remove the battery to silence the alarm with the good intention of replacing it after the smoke clears. Here are some better ways to deal with nuisance tripping: Use an alarm with a ‘hush button’. Move the smoke alarm a little further from the kitchen area. Try a different type of alarm. Some experts say that a photoelectric smoke alarm is a little less sensitive to common causes of false alarms.
Hard Wired AlarmsMany homes today have smoke alarms wired right into the household electrical system. In addition, some homes have interconnected smoke alarms. This means if one alarm in the home sounds then the others sound as well.
Escape PlanSmoke and flame can spread quickly so you need to react quickly. It is vital that you and your family know what to do on hearing a smoke alarm. You should plan an escape route from every area of the home and identify a safe area to meet outside the home. You should rehearse the escape plan with your family. Walk through and identify obstacles that may slow you down such as windows that are jammed or exits that are crowded with storage etc.
Page 48 of 50 43204-27722
Pilla
r To
Post
®Carbon Monoxide
Information Series©2007 Pillar To Post Inc.
Carbon monoxide, or CO, a byproduct of incomplete combustion of fossil fuels, is a colorless, odorless gas. Breathing CO reduces the blood’s ability to carry oxygen. In severe cases, CO can cause death.
Defective or malfunctioning fossil fuel appliances, or inappropriate use of appliances that burn fossil fuel close to or inside the home can pose a serious health hazard. Here are a few examples of dangerous operations:
• Runninganautomobileor gas lawn mower inside the garage
• Operatingabarbequeinside the home
• Agasoroilburningfurnacewithablockageinthechimney• Kerosenespaceheaters• Operatingageneratorinthehomeduringapowerfailure
Symptoms of Carbon Monoxide PoisoningSymptoms of carbon monoxide poisoning include headache, dizziness, nausea, vomiting, weakness,chestpain,confusion,andlossofconsciousness.Carbonmonoxidepoisoningcanleadtodeath.Lowlevelpoisoningmaygounnoticedbecauseitmaybemistakenforthe flu.
Carbon Monoxide DetectorYou should have at least one carbon monoxide detector in your home. In some geographic areas,aCOdetectorisrequiredbylaw.TheCOdetectorshouldbeplacedwhereyoucanhearitifitgoesoffwhenyouareasleep.ACOdetectordoesnothavetobeplacedontheceiling,sinceunlikesmoke,COhasapproximatelythesameweightasairsoitmixes
Page 49 of 50 43204-27722
Pillar To Post®, the home of home inspectionWe welcome your comments and suggestions for future Information Series topics
[email protected] 1-800-294-5591 www.pillartopost.com
uniformlythroughouttheroomratherthanfloatinguptotheceiling.Toavoidfalsealarms,donotinstallthedetectornexttoheatingandcookingappliances,vents,flues,orchimneys.Makesureyoureadandfollow the operating, placement, and testing instructions that come with the detector.
Ifthecarbonmonoxidedetectoralarms,takeitseriously.
Avoiding CO Poisoning• Haveyourheatingsystemsservicedeveryyearbyaqualifiedtechnician.• Haveyourfireplacechimneycleanedandinspectedeveryyear.• InstallatleastoneCOdetectorinyourhomeandreplacethebatteriestwiceperyear.• Openthegaragedoorpriortostartingyourcar;drivethecaroutpromptly.Donotleaveitidlinginthe
garage. Do not use a remote car starter when the car is in the garage.• Donotuseacharcoalorpropanebarbequeinthehome.
Page 50 of 50 43204-27722