608 State St. South Kirkland, WA 98033 www.faira.com [email protected] +1.800.571.FAIR FAIRA TRANSPARENCY REPORTS 12222 Greenwood Ave N, Unit C, Seattle, WA 98133 September 30, 2016 Thank you for your interest in this Faira Certified home. We have coordinated the efforts of certified and licensed inspection and title professionals to create the Faira Transparency Reports for this home. The Faira Transparency Reports are a detailed portfolio of information that is prepared on behalf of buyers in preparation for making an informed offer on the property. You may view more detailed information for this home and can make an offer at http://www.faira.com/listings/10748 All of the information in the Faira Transparency Reports was gathered and compiled without any bias or influence from the seller(s). In fact, these reports are materially identical had you as the buyer(s) ordered the same professionals to perform the evaluations on the same date. Nevertheless, Faira takes no obligation of the reports being complete or accurate. The buyers are recommended to conduct their own due-diligence to their satisfaction. Please contact us if you have any questions or would like more information. We’re happy you’ve chosen a Faira Certified home and look forward to the opportunity of working with you! The Faira Team

Upload: hoanghanh

Post on 11-Jun-2018

215 views

Category:

Documents


0 download

TRANSCRIPT

608 State St. South Kirkland, WA 98033

www.faira.com

[email protected] +1.800.571.FAIR

FAIRA TRANSPARENCY REPORTS

12222 Greenwood Ave N, Unit C, Seattle, WA 98133

September 30, 2016 Thank you for your interest in this Faira Certified home. We have coordinated the efforts of certified and licensed inspection and title professionals to create the Faira Transparency Reports for this home. The Faira Transparency Reports are a detailed portfolio of information that is prepared on behalf of buyers in preparation for making an informed offer on the property.

You may view more detailed information for this home and can make an offer at

http://www.faira.com/listings/10748 All of the information in the Faira Transparency Reports was gathered and compiled without any bias or influence from the seller(s). In fact, these reports are materially identical had you as the buyer(s) ordered the same professionals to perform the evaluations on the same date. Nevertheless, Faira takes no obligation of the reports being complete or accurate. The buyers are recommended to conduct their own due-diligence to their satisfaction. Please contact us if you have any questions or would like more information. We’re happy you’ve chosen a Faira Certified home and look forward to the opportunity of working with you! The Faira Team

Inspection Report12222 Greenwood Ave N, Unit C, Seattle, WA 98133

ICN : 10506AQ001

Prepared By

Lasswell Home Inspection LLC

Lasswell Home Inspection, LLC206-793-0118

Page 2

REPORT LIMITATIONS

ALL INSPECTIONS ARE PERFORMED IN ACCORDANCE WITH THEWASHINGTON STATE STANDARDS OF PRACTICE FOR HOME INSPECTORS

Inspector: John Lasswell - Washington Home Inspector License #341 - WSDA License #68317.

This report is intended only as a general guide to help the client make his own evaluation of the overall condition of the home, and isnot intended to reflect the value of the premises, nor make any representation as to the advisability of purchase. The report expressesthe personal opinions of the inspector, based upon his visual impressions of the conditions that existed at the time of the inspectiononly. The inspection and report are not intended to be technically exhaustive, or to imply that every component was inspected, or thatevery possible defect was discovered. No disassembly of equipment, opening of walls, moving of furniture, appliances or storeditems, or excavation was performed. All components and conditions which by the nature of their location are concealed, camouflagedor difficult to inspect are excluded from the report.

Systems and conditions which are not within the scope of the building inspection include, but are not limited to: formaldehyde, leadpaint, asbestos, toxic or flammable materials, and other environmental hazards; pest infestation, playground equipment, efficiencymeasurement of insulation or heating and cooling equipment, internal or underground drainage or plumbing, any systems which areshut down or otherwise secured; water wells (water quality and quantity) zoning ordinances; intercoms; security systems; heatsensors; cosmetics or building code conformity. Any general comments about these systems and conditions are informational onlyand do not represent an inspection.

The inspection report should not be construed as a compliance inspection of any governmental or non governmental codes orregulations. The report is not intended to be a warranty or guarantee of the present or future adequacy or performance of thestructure, its systems, or their component parts. This report does not constitute any express or implied warranty of merchantability orfitness for use regarding the condition of the property and it should not be relied upon as such. Any opinions expressed regardingadequacy, capacity, or expected life of components are general estimates based on information about similar components andoccasional wide variations are to be expected between such estimates and actual experience.

We certify that our inspectors have no interest, present or contemplated, in this property or its improvement and no involvement withtradespeople or benefits derived from any sales or improvements. To the best of our knowledge and belief, all statements andinformation in this report are true and correct.

Should any disagreement or dispute arise as a result of this inspection or report, it shall be decided by arbitration and shall besubmitted for binding, non-appealable arbitration to the American Arbitration Association in accordance with its ConstructionIndustry Arbitration Rules then obtaining, unless the parties mutually agree otherwise. In the event of a claim, the Client will allowthe Inspection Company to inspect the claim prior to any repairs or waive the right to make the claim. Client agrees not to disturb orrepair or have repaired anything which may constitute evidence relating to the complaint, except in the case of an emergency.

Lasswell Home Inspection, LLC206-793-0118

Page 3

INSPECTION CONDITIONS

CLIENT & SITE INFORMATIONInspection Date: 09/07/2016.

Inspection Time: 2:30 PM.

Client Name: FAIRA.

Inspection Address: 12222 Greenwood Ave N, Unit C.

City, State, Zip: Seattle, WA 98133.

CLIMATIC CONDITIONSWeather: Overcast.

Soil Condition: Damp.

Outside Temp. in F: 60-70.

BUILDING CHARACTERISTICSYear Built: 2008.

Building Type: Townhouse.

Stories: 3

Space Below Grade: Ground floor living area.

Orientation: The home faces West.

UTILITY SERVICESWater Source: Public.

Sewage Disposal: Public.

Underground sewer lines are not inspected as part of a home inspection. If you would like the sewer linesinspected or "scoped" you should contact a firm that specializes in sewer line inspections. Thesecompanies will run a video camera down the line to check for crushed or broken pipes and infiltration bytree roots.

Utilities Status: All utilities on.

OTHER INFORMATIONHouse Occupied? Yes.

WSDA InspectionControl Number

10506AQ001.

Lasswell Home Inspection, LLC206-793-0118

Page 4

Comments: Because the home was occupied there is a chance there are problems that were not visible due to furnitureand other possessions of the current resident.

PAYMENT INFORMATIONTotal Fee: $275.

Lasswell Home Inspection, LLC206-793-0118

Page 5

ROOF SYSTEM

The foregoing is an opinion of the general quality and condition of the roofing material. The inspector cannot and does not offer anopinion or warranty as to whether the roof leaks or may be subject to future leakage. This report is issued in consideration of theforegoing disclaimer. The only way to determine whether a roof is absolutely water tight is to observe it during a prolonged rainfall. Many times, this situation is not present during the inspection.

ROOFStyle: Gable.

Covering Type: Composition shingles.

Roof Access: I was not able to access the roof due to the height of the building.

GUTTERS & DOWNSPOUTType & Condition: Metal, No visible defects.

The downspouts are connected to a subterranean drain system. This was not tested during the inspectionand very little of it is visible for inspection.

ATTIC AND INSULATIONAccessibility &Conditions:

There is no accessible attic space over the home.

Lasswell Home Inspection, LLC206-793-0118

Page 6

EXTERIOR - FOUNDATION - BASEMENT

An inspection of the exterior includes the visible wall coverings, trim, protective coatings and sealants, windows and doors, attachedporches, decks, steps, balconies, handrails, guardrails, carports, eaves, soffits, fascias and visible exterior portions of chimneys.

The following items are outside the scope of a home inspection. Buildings, decks, patios, fences, retaining walls, and other structuresdetached from the dwelling. Safety type glass or the integrity of thermal window seals. Verifying the presence of flue liners orcondition of the flue beyond what can be safely and readily seen from the roof or the firebox of a stove or fireplace. Testing orevaluation of the operation of security locks, devices or systems. .Areas beneath decks with less than five feet of clearance from theunderside of joists to grade. Evaluation of the function or condition of shutters, awnings, storm doors, storm windows, screens, andsimilar accessories. Area obscured vegetation or personal property of the current resident.

WALLSMaterial: Fiber Cement.

Condition

In general the siding is in good condition.

There is insufficient clearance between the finished grade and bottom edge of the siding. With this type ofsiding there should be two inches of clearance from hard surfaces such as driveways and 6 inches ofclearance from soil or gravel. Insufficient clearance can lead to premature failure along the bottom edge ofthe siding.

TRIMMaterial: Wood, Metal.

Condition: In general the trim is in good condition and no major defects were found.

SLAB ON GRADECondition: The floor slab is not visible due to carpet and/or floor covering. No readily visible problem were found.

Lasswell Home Inspection, LLC206-793-0118

Page 7

KITCHEN - APPLIANCES

Inspection of stand alone freezers and built-in ice makers are outside the scope of the inspection. No opinion is offered as to theadequacy of dishwasher operation. Ovens, self or continuous cleaning operations, cooking functions, clocks, timing devices, lightsand thermostat accuracy are not tested during this inspection. Appliances are not moved during the inspection. Portable dishwashersare not inspected, as they require connection to facilitate testing.

KITCHENSink Stainless Steel, Appears serviceable, Faucet appears to operate correctly. Hand sprayer is operational.

Range/Cooktop &Oven

Electric, Appears to operate correctly.

Ventilation External, Fan/Hood operational.

Refrigerator The refrigerator was inspected and appears operational.

Dishwasher The dishwasher was inspected appears to operate properly.

Garbage Disposal Appears to operate correctly, no visible defects were found.

Microwave: Appears to operated correctly, no visible defects were found.

Counters & Cabinets: Counters are tile, No visible defects were found.

All cabinet drawers and doors were opened and no visible defects were found

Switches, Fixtures &Outlets:

Operation appears normal, no visible defects were found.

Lasswell Home Inspection, LLC206-793-0118

Page 8

LAUNDRY

Laundry appliances are not moved during the inspection and the condition of any walls or flooring hidden by them cannot be judged. Drain lines and water supply valves serving washing machines are not operated. Water supply valves may be subject to leaking ifturned.

LAUNDRYLocation: 3rd Floor.

Condition: Plumbing appears serviceable, Electrical outlet is grounded, 240 Volt outlet is present. Dryer venting isprovided.

There are no opening to allow make up air for the dryer. When a dryer is installed in a closet louvereddoors or other ventilation must be installed to provide sufficient airflow for proper operation. Insufficientairflow will cause the dryer to overheat and may lead to a fire. I recommend reviewing the dryersinstallation instructions to determine the ventilation requirements.

Washing Machine: Appears to operate correctly, no visible defects were found.

Dryer: Electric, Appears to operate correctly, no visible defects were found.

Lasswell Home Inspection, LLC206-793-0118

Page 9

INTERIOR

The condition of walls behind wall coverings, paneling and furnishings cannot be judged. Only the general condition of visibleportions of floors is included in this inspection. As a general rule, cosmetic deficiencies are considered normal wear and tear and arenot reported. Determining the source of odors or like conditions is not a part of this inspection. Floor covering damage or stains maybe hidden by furniture. The condition of floors underlying floor coverings is not inspected. Determining the condition of insulatedglass windows is not always possible due to temperature, weather and lighting conditions. Check with owners for further information.

All fireplaces should be cleaned and inspected on a regular basis to make sure that no cracks have developed. Large fires in thefirebox can overheat the firebox and flue liners, sometimes resulting in internal damage.

INTERIORMain Entry Door: No visible defects.

Other ExteriorDoors:

All exterior doors were inspected and no visible defects were found.

Interior Doors: All interior doors were inspected and the following problem(s) were found:

The guides are broken or missing at the bottom of the following closet doors: ground floor bedroom.

Windows: Vinyl clad, double pane construction. No visible defects were found with the windows.

Interior Walls: Drywall, General condition appears good.

Ceilings: Drywall, General condition appears good.

Floors:

Carpet, Vinyl, Wood.

The carpet in the ground floor bedroom has visible staining and will need professional cleaning.

Lasswell Home Inspection, LLC206-793-0118

Page 10

The finish on the base shoe trim is damaged in the living room.

Stairs & Handrails: Interior stairs serviceable, Stair handrail serviceable.

Smoke/Fire & CODetectors:

Smoke alarms were present in all locations required by current safety standards. Smoke alarms are nottested during the course of a home inspection.

Carbon monoxide alarms were present on every floor of the home.

Lasswell Home Inspection, LLC206-793-0118

Page 11

BATHROOMS

SECOND FLOOR BATHROOMCondition of Sink:

The bolts that attach the pedestal sink to the wall are missing. Pedestal sinks are heavy and should bebolted to the wall to prevent them from tipping over.

Condition of Toilet: Operation appears normal, no visible defects were found.

Bath Ventilation Appears adequate.

THIRD FLOOR BATHROOMCondition of Sink: No visible defects were found. Counters/cabinets appear serviceable.

Condition of Toilet: Operation appears normal, no visible defects were found.

Lasswell Home Inspection, LLC206-793-0118

Page 12

Tub, Shower,Plumbing Fixtures:

I recommend sealing where the tub spout meets the wall with caulking. This will prevent water leakinginto the wall through opening around the supply plumbing.

Tub, Shower &Walls:

No visible defects found in tub or shower enclosure.

Bath Ventilation Appears adequate.

Lasswell Home Inspection, LLC206-793-0118

Page 13

HEATING - AIR CONDITIONING

The inspector is not equipped to inspect furnace heat exchangers for evidence of cracks or holes, as this can only be done bydismantling the unit. This is beyond the scope of this inspection. Some furnaces are designed in such a way that inspection is almostimpossible. The inspector can not light pilot lights. Safety devices are not tested by the inspector.NOTE: Asbestos materials have been commonly used in heating systems.Determining the presence of asbestos can ONLY be preformed by laboratory testing and is beyond the scope of this inspection. Thermostats are not checked for calibration or timed functions. Adequacy, efficiency or the even distribution of air throughout abuilding cannot be addressed by a visual inspection. Electronic air cleaners, humidifiers and de-humidifiers are beyond the scope ofthis inspection. Have these systems evaluated by a qualified individual. The inspector does not perform pressure tests on coolantsystems, therefore no representation is made regarding coolant charge or line integrity. Subjective judgment of system capacity is nota part of the inspection. Normal service and maintenance is recommended on a yearly basis. Determining the condition of oil tanks,whether exposed or buried, is beyond the scope of this inspection. Leaking oil tanks represent an environmental hazard which issometimes costly to remedy.

HEATING SYSTEM DESCRIPTIONSystem Type: Forced air wall heaters.

Fuel Type & Notes: Electric.

HEATING SYSTEM CONDITIONPrimary Unit: All wall heaters were tested and were working at the time of the inspection.

Normal Controls: Operation appears normal.

Electric wall heater require very little maintenance, however annually your should remove the front grill andvacuum any dust or debris from the inside of the heaters. This is important and should not be overlooked. Abuildup of dust and debris within the heater could lead to a fire. Before removing the front grill be sure to shutoff the power to the heaters at the breaker panel.

It is important to never place anything in front of the heaters that will block the flow of air. This could cause theheater to overheat and catch fire. You should maintain a minimum of three feet of clearance in front of theheaters. Combustible materials should never be placed in front of the heaters.

Lasswell Home Inspection, LLC206-793-0118

Page 14

ELECTRICAL SYSTEM

Any electrical repairs attempted by anyone other than a licensed electrician should be approached with caution. The power to theentire house should be turned off prior to beginning any repair efforts, no matter how trivial the repair may seen. Aluminum wiringrequires periodic inspection and maintenance by a licensed electrician. Operation of time clock motors is not verified. Inoperativelight fixtures often lack bulbs or have dead bulbs installed. Light bulbs are not changed during the inspection, due to time constraints.Smoke Alarms should be installed within 15 feet of all bedroom doors, and tested regularly.

SERVICEType & Condition: Underground service, 125 Amps, 120/240 Volt, Circuit breakers.

ELECTRICAL PANELSMain Panel Location

Garage.

Inspector Notes:

Circuit and wire sizing correct so far as visible.

Grounding system is present.

Grounding Foundation ground is present.

Sub panel Notes: +

CONDUCTORSEntrance Cables: Aluminum- OK.

Branch Wiring: Copper, Appears serviceable.

Lasswell Home Inspection, LLC206-793-0118

Page 15

SWITCHES, OUTLETS & FIXTURESCondition: All accessible switches and outlets were tested and no visible problems were found.

Lasswell Home Inspection, LLC206-793-0118

Page 16

PLUMBING

Water quality or hazardous materials (lead) testing is available from local testing labs. All underground piping related to watersupply, waste, or sprinkler use are excluded from this inspection. Leakage or corrosion in underground piping cannot be detected bya visual inspection. The temperature pressure relief valve, at the upper portion of the water heater, is a required safety valve whichshould be connected to a drain line of proper size terminating just above floor elevation. If no drain is located in the floor a catch panshould be installed with a drain extending to a safe location. The steam caused by a blow-off can cause scalding. Improperinstallations should be corrected.

MAIN LINEMaterial: +

Plastic.

Condition:

No visible defects.

The main shut off is located in the garage. The main shut off was tested and appears to operate properly.

SUPPLY LINESMaterial: Plastic, (PEX)

Condition: Most of the supply plumbing is not visible because of the ceiling and wall finish. No visible defects couldbe found.

Water Pressure The water pressure was tested at 55 psi. Normal household water pressure should be between 40 and 80psi.

Lasswell Home Inspection, LLC206-793-0118

Page 17

WASTE LINESMaterial: Plastic.

Condition: Most of the waste plumbing is not visible because of the ceiling and wall finish. No visible defects couldbe found.

HOSE FAUCETSCondition:

Sample operated, operation appears normal.

WATER HEATERType: Electric.

Size: 50 Gallons.

Location: Garage.

Condition

The water heater was manufactured in 2008. Water heaters typically have a life expectancy of 10-15 years.

A temperature and pressure relief valve is present at the water heater.

Since the thermal expansion tank is mounted on copper pipe, it should have strapping to hold it in placepreventing it from breaking the pipe during an earthquake.

Lasswell Home Inspection, LLC206-793-0118

Page 18

GARAGE - CARPORT

Notice: Determining the heat resistance rating of firewalls is beyond the scope of this inspection. Flammable materials should not bestored within closed garage areas.

TYPELocation: Under main house roof, One car.

FLOORCondition:

Typical cracks noted.

The garage floor was not fully inspected because storage and/or vehicles of the current resident blockedaccess to part or all of the floor.

FIRE WALLCondition: Appears serviceable.

GARAGE DOOR(S)Condition: Operation appears normal. Automatic door opener(s)- operational

The garage door failed to reverse when it hit a 2x4 block at the bottom of its travel. This simulates a bodypart being trapped under the door. The automatic opener should be adjusted.

Lasswell Home Inspection, LLC206-793-0118

Page 19

GROUNDS

This inspection is not intended to address or include any geological conditions or site stability information. For informationconcerning these conditions, a geologist or soils engineer should be consulted. Any reference to grade is limited to only areas aroundthe exterior of the exposed areas of foundation or exterior walls. This inspection is visual in nature and does not attempt to determinedrainage performance of the site or the condition of any underground piping, including municipal water and sewer service piping orseptic systems. Decks and porches are often built close to the ground, where no viewing or access is possible. These areas as well asothers too low to enter, or in some other manner not accessible, are excluded from the inspection and are not addressed in the report. We routinely recommend that inquiry be made with the seller about knowledge of any prior foundation or structural repairs.

DRIVEWAYCondition: Asphalt, No visible defects were found.

SIDEWALKSType: Paver/Tile.

Condition: No visible defects were found.

LANDSCAPINGCondition: Landscaping appears to be well maintained.

GRADINGSite: Flat site.

PORCHType: Concrete.

Condition: No visible defects were found.

PATIOType: Paver/Tile.

Condition: No visible defects were found.

DECKType: Composite.

Condition: No visible defects were found.

FENCES & GATESType: Wood.

Condition: No visible defects were found.

Lasswell Home Inspection, LLC206-793-0118

Page 20

WASHINGTON WOOD DESTROYING ORGANISMINSPECTION REPORT

This report is prepared from an inspection conducted by a Washington State Department of Agriculture licensed Structural PestInspector in accordance with Washington Administrative Code. Opinions contained herein are based on conditions visible andevident at the time of the inspection. This report does not warrant, represent, or guarantee that the structure reported on is free fromevidence of WDOs (Wood destroying organisms), their damage or conditions conductive to WDOs, nor does it represent or guaranteethat the total damage, infestation or infection is limited to that disclosed in this report.

INSPECTION PROCEEDURES

A thorough visual inspection will be made using accepted methods and practices, of the subject structure to render and opinion on thepresence of or damage from WDOs as well as the conditions conductive to WDOs.

Areas inspected include: structural exterior (accessible visually and physically to an inspector at ground level); accessible interior;accessible crawlspace(s); garages, carports and decks which are attached to the structure. Deck inspections include railings, woodensteps and accessible wooden surface materials, as well as, deck framing which is accessible (minimum 5' soil to joist clearance orthose that can be reached using a 6' step ladder).Wood destroying organisms include subterranean termites, dampwood termites, carpenter ants, moisture ants, wood boring beetles,and damp wood decay fungus (rot). The inspector will not assume any responsibility for WDOs that were not detected during theirdormant season. Conductive conditions include but not to be limited to inadequate clearance or structural members, earth wood contact, conductivedebris in the crawlspace or basement, inadequate ventilation, excessive moisture, vegetation contact with the structure, bare ground inthe crawlspace, existing or seasonal standing water in the crawlspace, failed caulking or grout in water splash areas, and/or inadequateor non-functioning gutter system.

LIMITATIONS OF INSPECTION

Inaccessible areas: Certain areas of a structure, which are inaccessible by their nature, may be subject to infestation by WDOs yetcannot be inspected without excavation, removal of finished surfaces or unless physical obstructions are removed. Examples of theseareas are wall voids, spaces between floors, substructures concealed by sub-floor insulation or those with inadequate clearance, floorsbeneath coverings, sleeper floors, areas concealed by furniture, appliances or personal possessions, and deck substructures with lessthan 5' clearance.Sheds and outbuildings: Sheds garages, carports or other structures, which are not attached to the main structure by roof system orfoundation, are excluded from this report unless specifically requested and noted. The inspector reserves the right to chargeadditionally to inspect any unattached structures.Climatic Conditions: In certain geographical areas of Washington State where wet climate is common and due to their constructionand materials, structures may be subject to conditions from normal weathering. Such conditions as cracking, checking, and/orwarping of doors, window casings, siding, and non-structural wooden members shall not be reported on the inspection report exceptat the discretion of the inspector. Inspectors are not required to report on any WDOs or other conditions that might be subject toseasonal constraints or environmental conditions if evidence of those constraints or conditions is not visible a the time of theinspections.Mold: Molds, mildews and other fungal growth (except wood rot) shall be reported on only to the extent that they indicate anexcessive moisture condition which may be conductive to WDOs. Structural Assesment: While it may be possible for the inspector to note damaged materials, neither the inspector nor the inspectionfirm is liable or responsible in any way to determine the structural integrity of any building materials. If a more qualified opinion isdesired, the services of a licensed, qualified contractor or structural engineer should be obtained.

Lasswell Home Inspection, LLC206-793-0118

Page 21

EVIDENCE OF ACTIVE WOOD DESTROYING INSECTSType of Insect: No evidence of wood destroying insects were found.

EVIDENCE OF ACTIVE WOOD DECAY FUNGILocation &Description:

No evidence of wood decay was found.

EVIDENCE OF PRIOR INSECT INFESTATIONType of Insect: No damage from wood destroying organisms was found.

CONDITIONS CONDUCTIVE TO WOOD DESTROYING ORGANISMSLocation &Description:

No conductive conditions were found.

OTHER INFORMATIONInaccessible areas There were no inaccessible areas.