608 State St. South Kirkland, WA 98033 www.faira.com [email protected] +1.800.571.FAIR FAIRA TRANSPARENCY REPORTS 5583 Vista San Simeon, San Diego, CA 92154 September 7, 2017 Thank you for your interest in this Faira Certified home. We have coordinated the efforts of certified and licensed inspection and title professionals to create the Faira Transparency Reports for this home. The Faira Transparency Reports are a detailed portfolio of information that is prepared on behalf of buyers in preparation for making an informed offer on the property. You may view more detailed information for this home and can make an offer at http://www.faira.com/listings/11163 All of the information in the Faira Transparency Reports was gathered and compiled without any bias or influence from the seller(s). In fact, these reports are materially identical had you as the buyer(s) ordered the same professionals to perform the evaluations on the same date. Nevertheless, Faira takes no obligation of the reports being complete or accurate. The buyers are recommended to conduct their own due-diligence to their satisfaction. Please contact us if you have any questions or would like more information. We’re happy you’ve chosen a Faira Certified home and look forward to the opportunity of working with you! The Faira Team

Upload: others

Post on 04-Jul-2020

4 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: FAIRA TRANSPARENCY REPORTS 5583 Vista San Simeon, San Diego… · 2017-09-07 · 5583 Vista San Simeon, San Diego, CA 92154 . September 7, 2017 . ... 10 Heating / Central Air Conditioning

608 State St. South Kirkland, WA 98033

www.faira.com

[email protected] +1.800.571.FAIR

FAIRA TRANSPARENCY REPORTS

5583 Vista San Simeon, San Diego, CA 92154

September 7, 2017 Thank you for your interest in this Faira Certified home. We have coordinated the efforts of certified and licensed inspection and title professionals to create the Faira Transparency Reports for this home. The Faira Transparency Reports are a detailed portfolio of information that is prepared on behalf of buyers in preparation for making an informed offer on the property.

You may view more detailed information for this home and can make an offer at

http://www.faira.com/listings/11163 All of the information in the Faira Transparency Reports was gathered and compiled without any bias or influence from the seller(s). In fact, these reports are materially identical had you as the buyer(s) ordered the same professionals to perform the evaluations on the same date. Nevertheless, Faira takes no obligation of the reports being complete or accurate. The buyers are recommended to conduct their own due-diligence to their satisfaction. Please contact us if you have any questions or would like more information. We’re happy you’ve chosen a Faira Certified home and look forward to the opportunity of working with you! The Faira Team

Page 2: FAIRA TRANSPARENCY REPORTS 5583 Vista San Simeon, San Diego… · 2017-09-07 · 5583 Vista San Simeon, San Diego, CA 92154 . September 7, 2017 . ... 10 Heating / Central Air Conditioning

Inspection Report

Christopher Ellis

Property Address:5583 Vista San SimeonSan Diego CA 92154

John Robinson's Inspection Group

Dallas Compton5291 Mount Burnham Dr. San Diego, CA 92111

(619)684-1444 - [email protected]

Page 3: FAIRA TRANSPARENCY REPORTS 5583 Vista San Simeon, San Diego… · 2017-09-07 · 5583 Vista San Simeon, San Diego, CA 92154 . September 7, 2017 . ... 10 Heating / Central Air Conditioning

John Robinson's Inspection Group Ellis

5583 Vista San Simeon Page 2 of 58

Page 4: FAIRA TRANSPARENCY REPORTS 5583 Vista San Simeon, San Diego… · 2017-09-07 · 5583 Vista San Simeon, San Diego, CA 92154 . September 7, 2017 . ... 10 Heating / Central Air Conditioning

Table of Contents

Cover Page ................................................1

Table of Contents........................................3

Intro Page .................................................4

1 Built-In Kitchen Appliances........................7

2 Plumbing System.....................................9

3 Interiors ............................................... 16

4 Electrical System ................................... 22

5 Garage ................................................. 28

6 Insulation and Ventilation ....................... 29

7 Roofing ................................................ 30

8 Exterior ................................................ 32

9 Structural Components ........................... 36

10 Heating / Central Air Conditioning .......... 38

11 General Pictures................................... 43

General Summary .................................... 49

Invoice.................................................... 55

Agreement .............................................. 56

John Robinson's Inspection Group Ellis

5583 Vista San Simeon Page 3 of 58

Page 5: FAIRA TRANSPARENCY REPORTS 5583 Vista San Simeon, San Diego… · 2017-09-07 · 5583 Vista San Simeon, San Diego, CA 92154 . September 7, 2017 . ... 10 Heating / Central Air Conditioning

Date: 9/6/2017 Time: 01:00:00 PM Report ID: 090617DC2Property:5583 Vista San SimeonSan Diego CA 92154

Customer:Christopher Ellis

Real Estate Professional:Christopher EllisFaira.com Corp

PLEASE BE ADVISED:This inspection report is the exclusive and sole property of John Robinson's Inspection Group and the Clients

who's name appears in the area above labeled Customer.

Unauthorized reproduction and/or distribution of this report is strictly prohibited.

Subsequent buyers, real estate agents and/or sellers assume full responsibility for giving this inspection reportto anyone who does not have a signed contract or written agreement with John Robinson's Inspection Group.Due to the natural aging process of the materials used in constructing a home, and the normal wear and tearon the mechanical items in the home, THIS REPORT CAN ONLY REFLECT OBSERVATIONS MADE ON THEDAY OF THE INSPECTION. Subsequent buyers should have a new inspection performed to protect theirinterests.

Inspectors working for John Robinson's Inspection Group inspect properties in accordance with the Standardsof Practice of the International Association of Certified Home Inspectors and our inspection agreement whichare listed on our website at the following link: Inspection Agreement. Items that are excluded (not inspected)are indicated in the contract and/or disclaimed in the aforementioned Standards of Practice. The observationsand opinions expressed within the report take precedence over any verbal comments. It should be understoodthat the inspector is only on-site for a few hours and will not comment on insignificant deficiencies, but rather,confine the observations to truly significant defects or deficiencies that significantly affect the value,desirability, habitability or safety of the structure. The Client should consider all defects identified in thisinspection report as significant.

The inspection shall be limited to those specific systems, structures and components that are present andaccessible. Components and systems shall be operated with normal user controls, and not forced or modifiedto work. Those components or systems that are found not to work at time of inspection will be reported, andthose items should be inspected and repaired or replaced by a qualified specialist in that field. You must obtainestimates for any items noted in the report that require further evaluation or repair. The inspector cannot knowwhat expense would be considered significant by client, as everyone's budget is different. It is thereforeclient's responsibility to obtain quotations prior to the end of the contingency period. . This is very important,as once you pass the contingency period, or purchase the house, repairs become your sole responsibility. Ifyou have questions about the significance of a repair item, call a licensed professional immediately.

The recommendations that the inspector makes in this report for specialist evaluations should be completedwithin the contingency period by licensed professionals, who may well identify additional defects orrecommend some upgrades or replacements that could affect your evaluation of the property. We caution youto be wary of anyone who has a vested interest, and particularly those who attempt to alarm you or denigrateothers.

We feel that everything in this inspection report is significant. Especially the items marked "Repair or Replace"(RR). We cannot assume liability for an item, system, or component the client did not feel was significant attime of inspection, but later feels is. For this reason, we are informing you now that when as little as one (1)"Repair or Replace" (RR) item is indicated in any portion of the inspection report, you must have that entiresystem further evaluated by a licensed specialist in that field before the end of your contingency period. Theselicensed specialist may well identify additional defects or recommend some upgrades or replacements thatcould affect your evaluation of the property. Paying John Robinson's Inspection Group for this general homeinspection and written inspection report constitutes your understanding and agreeing to what has beenoutlined in this paragraph.

John Robinson's Inspection Group Ellis

5583 Vista San Simeon Page 4 of 58

Page 6: FAIRA TRANSPARENCY REPORTS 5583 Vista San Simeon, San Diego… · 2017-09-07 · 5583 Vista San Simeon, San Diego, CA 92154 . September 7, 2017 . ... 10 Heating / Central Air Conditioning

SCOPE OF WORKYou have contracted for us, John Robinson's Inspection Group, to perform a general inspection. We performedthis inspection in accordance with standards of practice established by the International Association of CertifiedHome Inspectors (Inter-NACHI). A copy of these standards can be obtained by visiting Standards of Practice.It is distinct from a specialist inspection, which can be costly, take several days to complete, involve the use of

specialized instruments, the dismantling of equipment, video-scanning, destructive testing, and laboratoryanalysis. By contrast, the general inspection is completed on-site, at a fraction of the cost and within a few

hours. Consequently, the general inspection and its report will not be as comprehensive as that generated byspecialists and it is not intended to be. The purpose of this inspection is to identify systems that should befurther evaluated by licensed contractors who through their evaluations may identify additional material

defects or adverse conditions that could result in injury or lead to costs that would significantly affect yourevaluation of the property. We strongly urge you to follow our further evaluation recommendations as statedin the inspection report prior to the end of your contingency period to prevent issues from arising after the

close of escrow.

We evaluate conditions, systems, or components, and report on their condition, which does not mean that theyare ideal but that they are either functional or met a reasonable standard at a given point in time. We do takeinto consideration when a house was built and allow for the predictable deterioration that would occur throughtime, such as the cracks that appear in concrete and in the plaster around windows and doors, scuffed walls orwoodwork, worn or squeaky floors, stiff or stuck windows, and cabinetry that does not function as it did whennew. Therefore, we tend to ignore insignificant and predictable defects, and do not annotate them, andparticularly those that would be apparent to the average person or to someone without any constructionexperience. We are not authorized, or have the expertise, to test for environmental contaminants, or commenton termite, dry rot, fungus or mold, but may alert you to its presence. Similarly, we do not test the quality ofthe air within a residence. However, clean air is essential to good health, and we categorically recommend airsampling and the cleaning of supply ducts as a wise investment in environmental hygiene. Therefore, youshould schedule any such specialized inspections with the appropriate specialist before the close of escrow.

A house and its components are complicated, and because of this and the limitations of an on-site report, weoffer unlimited consultation and encourage you to ask questions. In fact, we encourage candid and forthrightcommunication between all parties, because we believe that it is the only way to avoid stressful disputes andcostly litigation. Remember, we only summarized the report on-site and it is essential that you read all of it,and that any recommendations that we make for service or evaluation by specialists should be completed anddocumented well before the close of escrow, because additional defects could be revealed by specialists, orsome upgrades recommended that could affect your evaluation of the property, and our service does notinclude any form of warranty or guarantee.

If you or a family member has health problems, or you are concerned about mold, it is YOURresponsibility to get an air quality or mold inspection regardless of the findings in this report. JohnRobinson's Inspection Group is not a mold inspection company and is not qualified/licensed toinspect for nor identify mold.

Definitions of CommentsThe following definitions of comment descriptions represent this inspection report. All comments by theinspector should be considered before purchasing this home. Any recommendations by the inspector to repairor replace suggests a second opinion or further inspection by a qualified contractor. That professional shouldinspect the entire system or component, as problems at one area could indicate problems at other areas of thesystem. All costs associated with further inspection fees and repair or replacement of item, component or unitshould be considered before you purchase the property.

Inspected (IN) = I visually observed the item, component or unit and if no other comments were made thenit appeared to be functioning as intended allowing for normal wear and tear.

John Robinson's Inspection Group Ellis

5583 Vista San Simeon Page 5 of 58

Page 7: FAIRA TRANSPARENCY REPORTS 5583 Vista San Simeon, San Diego… · 2017-09-07 · 5583 Vista San Simeon, San Diego, CA 92154 . September 7, 2017 . ... 10 Heating / Central Air Conditioning

Informational (INF)= This unit or component appeared to be functional at the time of the inspection.However, it may be showing signs of age, use, wear and/or approaching the end of its life. This unit orcomponent may need to be cleaned, serviced or repaired by a qualified technician and to determine its liferemaining.

Not Inspected (NI)= I did not inspect this item, component or unit and made no representations of whetheror not it was functioning as intended and will state a reason for not inspecting.

Not Present (NP) = This item, component or unit is not in this home or building.

Repair or Replace (RR) = The item is not functioning as intended and/or its entire system needs to befurther evaluated or inspected by a licensed contractor in that field (Plumbing = Plumber, Electrical =Electrician, etc.). Note: Damage or additional items in need of repair may exist that are not identified in thisinspection report and/or are beyond the scope of this home inspection, may be discovered by the licensedcontractor. This is why we strongly recommend that you seek further inspections and evaluations BEFORE THEEND OF YOUR CONTENGICY PERIOD. We cannot and will not be responsible for your failure to follow ourrecommendations listed in this inspection report.

Safety Concern (SC)=This system or component current state poses a potential safety hazard to theoccupants or structure. This item should be immediately further evaluated and repaired by a qualifiedtechnician/contractor to ensure safety.

A home inspection and it's report are only describing the condition of the systems and components of thishouse on the day of inspection. A home inspection is not a home warranty or guarantee of any kind. Systemsand components of this home may and probably will fail anytime after the inspection. We HIGHLYrecommend that you purchase and maintain a comprehensive home warranty, including coverage for yourroofing, heating and air conditioning, plumbing, and electrical systems and renew it each year you own thishouse.

Homes more than 13 years old may have areas that are not current in code requirements. This is not a newhome and this home cannot be expected to meet current code standards. While this inspection makes everyeffort to point out safety issues, it does not inspect for code. It is common that homes of any age will have hadrepairs performed and some repairs may not be in a workmanlike manner. Some areas may appear less thanstandard. This inspection looks for items that are not functioning as intended. It does not grade the repair. It issometimes common to see old plumbing or mixed materials. Sometimes water signs in crawlspaces orbasements could be years old from a problem that no longer exists. Or, it may still need further attention andrepair. Determining this can be difficult in a lived in home. Sometimes homes have signs of damage to woodfrom wood eating insects. Having this is typical and fairly common. If the home inspection reveals signs ofdamage you should have a pest control company inspect further for activity and possible hidden damage. Thehome inspection does not look for possible manufacturer re-calls on components that could be in this home.Always consider hiring the appropriate expert for any repairs or further inspection.

Due to personal items such as clothing, furniture, window coverings, towels, hygiene and/or cleaning products,a full evaluation of the cabinets, closet, and walls could not be made. I recommend you carefully inspect thecabinets prior to close of escrow.

Style of Home:Single family detached

Year home was built:2004

Parties present:Seller

Weather:Clear

Temperature:80 to 85 degrees

Rain in last 3 days:No

Number of levels:2

Occupied:Yes*

House Square Footage:2,328 Sq. Ft.

John Robinson's Inspection Group Ellis

5583 Vista San Simeon Page 6 of 58

Page 8: FAIRA TRANSPARENCY REPORTS 5583 Vista San Simeon, San Diego… · 2017-09-07 · 5583 Vista San Simeon, San Diego, CA 92154 . September 7, 2017 . ... 10 Heating / Central Air Conditioning

1. Built-In Kitchen Appliances

The home inspector shall observe and operate the basic functions of the following kitchen appliances: Permanentlyinstalled dishwasher, through its normal cycle; Range, cook top, and permanently installed oven; Trash compactor;Garbage disposal; Ventilation equipment or range hood; and Permanently installed microwave oven. The homeinspector is not required to observe: Clocks, timers, self-cleaning oven function, or thermostats for calibration orautomatic operation; Non built-in appliances; or Refrigeration units. The home inspector is not required to operate:Appliances in use; or Any appliance that is shut down or otherwise inoperable.

Styles & MaterialsRange:-Gas-LG

Dishwasher:General Electric

Disposer:Unknown

Exhaust/Range Hood:-Vented-Built into MicrowaveGeneral Electric

Buit-in Microwave:General Electric

Wall Oven:-Gas-

Items1.0 DISHWASHER

Repair or ReplaceWater draining at air gap observed during the draining cycle of the dish washer. This is possible indicationof a clogged/obscured dishwasher drain. Recommend repair/replace by a qualified/licensed professional.

1.1 RANGES AND COOKTOPSRepair or Replace, Safety Concern(1) Infrared picture of range/cooktop in operation. This unit appeared operational.

1.1 Item 1(Picture)

(2) No anti-tip bracket was installed at the range. This bracket prevents the range from tipping forward,which could cause the range to fall over and/or spill hot food from pots and pans. The anti-tip bracket is asimple metal plate that holds the rear foot of the range to the floor. Recommend installation by a qualifiedperson to prevent injury.

1.2 EXHAUST FAN/RANGE HOOD/DOWNDRAFTRepair or ReplaceFlexible vent observed at exhaust fan/range hood. Recommend correcting and installing a ridged vent bya qualified/licensed professional.

John Robinson's Inspection Group Ellis

5583 Vista San Simeon Page 7 of 58

Page 9: FAIRA TRANSPARENCY REPORTS 5583 Vista San Simeon, San Diego… · 2017-09-07 · 5583 Vista San Simeon, San Diego, CA 92154 . September 7, 2017 . ... 10 Heating / Central Air Conditioning

1.3 GARBAGE DISPOSERInspected

1.4 BUILT-IN MICROWAVEInformationalThe operation of the microwave was tested using a microwave tester. This unit appeared functional at thetime of inspection.

1.4 Item 1(Picture)

1.5 WALL OVENInformationalInfrared picture of oven in operation. This unit appeared operational.

1.5 Item 1(Picture)

1.6 REFRIGERATORNot InspectedRefrigerators are not inspected because they are outside the scope of a standard home inspection.

1.7 WASHER/DRYERNot InspectedClothes washer and dryer were not tested nor inspected. Testing these units is outside the scope of astandard home inspection.

The built-in appliances of the home were inspected and reported on with the above information. While the inspector makes everyeffort to find all areas of concern, some areas can go unnoticed. Please be aware that the inspector has your best interest in mind.Any repair items mentioned in this report should be considered before purchase. It is recommended that qualified contractors beused in your further inspection or repair issues as it relates to the comments in this inspection report.

John Robinson's Inspection Group Ellis

5583 Vista San Simeon Page 8 of 58

Page 10: FAIRA TRANSPARENCY REPORTS 5583 Vista San Simeon, San Diego… · 2017-09-07 · 5583 Vista San Simeon, San Diego, CA 92154 . September 7, 2017 . ... 10 Heating / Central Air Conditioning

2. Plumbing System

The home inspector shall observe: Interior water supply and distribution system, including: piping materials, supports,and insulation; fixtures and faucets; functional flow; leaks; and cross connections; Interior drain, waste, and ventsystem, including: traps; drain, waste, and vent piping; piping supports and pipe insulation; leaks; and functionaldrainage; Hot water systems including: water heating equipment; normal operating controls; automatic safety controls;and chimneys, flues, and vents; Fuel storage and distribution systems including: interior fuel storage equipment, supplypiping, venting, and supports; leaks; and Sump pumps. The home inspector shall describe: Water supply anddistribution piping materials; Drain, waste, and vent piping materials; Water heating equipment; and Location of mainwater supply shutoff device. The home inspector shall operate all plumbing fixtures, including their faucets and allexterior faucets attached to the house, except where the flow end of the faucet is connected to an appliance. The homeinspector is not required to: State the effectiveness of anti-siphon devices; Determine whether water supply and wastedisposal systems are public or private; Operate automatic safety controls; Operate any valve except water closet flushvalves, fixture faucets, and hose faucets; Observe: Water conditioning systems; Fire and lawn sprinkler systems; On-site water supply quantity and quality; On-site waste disposal systems; Foundation irrigation systems; Spas, except asto functional flow and functional drainage; Swimming pools; Solar water heating equipment; or Observe the system forproper sizing, design, or use of proper materials. Please refer to our Standards of Practice for a detailed list of what isinspected and what is not inspected.

We evaluate plumbing systems and their components in accordance with state or industry standards, which includetesting for pressure and functional flow. Plumbing systems have common components but they are not uniform. Inaddition to fixtures, components typically consist of gas pipes, potable water pipes, drain and vent pipes, shut-offvalves, which we do not test, pressure regulators, pressure relief valves, and water-heating devices. The best and mostdependable water pipes are copper, because they are not subject to the build-up of minerals that bond to the inside ofgalvanized pipes and gradually reduce their inner diameter and restrict the volume of water. A water softener willremove most of these minerals, but not once they are bonded within the pipes, for which there would be no remedyother than a re-pipe.

The water pressure within pipes is commonly confused with water volume, but whereas high water volume is good highwater pressure is not. In fact, whenever the street pressure exceeds eighty pounds per square inch a regulator isrecommended, which typically comes factory preset between forty-five and sixty-five pounds per square inch. However,regardless of the pressure, leaks will occur in any system, and particularly in one with older galvanized pipes, andcommonly when the regulator fails and high pressure begins to stress the washers and diaphragms within the variouscomponents.

Waste pipes are equally varied and are comprised of older ones, such as those made of clay, or others that are made ofa material like cardboard coated with tar, and modern plastic ones referred to as ABS. Typically, the condition of thesepipes is directly related to their age. ABS pipes, for instance, are virtually impervious to deterioration. However, someABS pipes are alleged to have manufacturing defects. Regardless, inasmuch as most drainpipes are concealed, we canonly infer their condition by observing the draw at drains. Nonetheless, blockages will occur at some point in the life ofany system, but blockages in the waste lines, and particularly in a main sewer line, can be costly, and it would beprudent to have the main sewer line video scanned. This would also confirm that the house is connected to the publicsewer system, which is important because such systems should be evaluated by a specialist before the close of escrow.

Styles & MaterialsWater Source:Public

Plumbing Supply:Copper

Plumbing Distribution:CopperPEX*

Washer Drain Size:2" Diameter

Plumbing Waste:ABS

Water Heater Fuel Source:Natural Gas

Water Heater Flue Pipe Material:Double Wall MetalFlexible Metal

Capacity:50 GALLONS

Year Water Heater Was Made:OLDER THAN 10 YEARS2005

Manufacturer:RHEEM

Water Pressure:65-70 psi

Gas Distribution Piping:Rigid Iron Pipe

John Robinson's Inspection Group Ellis

5583 Vista San Simeon Page 9 of 58

Page 11: FAIRA TRANSPARENCY REPORTS 5583 Vista San Simeon, San Diego… · 2017-09-07 · 5583 Vista San Simeon, San Diego, CA 92154 . September 7, 2017 . ... 10 Heating / Central Air Conditioning

Items2.0 PLUMBING GENERAL

InformationalA majority of the plumbing supply, distribution, drain, waste, and vent systems were concealed behind theflooring, buried in the slab, routed through the attic below the insulation insulation or in inaccessiblesections of the attic or crawlspace and were not visible at the time of the inspection. Our inspection ofthe plumbing system is non-intrusive and non-destructive and only included the visibly accessiblecomponents of the plumbing system. Please be advised: THIS INSPECTION OF THE PLUMBING SYSTEMIS NOT A WARRANTY OR GUARANTEE THAT LEAKS OR BLOCKAGES WILL NOT OCCUR ANYWHERE IN THEPLUMBING SYSTEM AT ANY POINT IN TIME AFTER THIS HOME INSPECTION HAS BEEN COMPLETED. Weare informing you now that you should purchase a homeowner insurance policy and home warrantee thatcovers the plumbing system in the event problems develop in this system. John Robinson's InspectionGroup is not and will not be responsible for concealed defects and will be held harmless should anydevelop in this home.

2.1 MAIN WATER SHUT-OFF DEVICE (Describe location)InformationalThe main water shut off valve is located in the garage.

2.1 Item 1(Picture)

2.2 PRESSURE REGULATORInspected

2.3 PLUMBING WATER SUPPLY AND DISTRUBUTION SYSTEMInformational(1) Please note: due to wall coverings, insulation, HVAC ductwork, buried lines or other obstructions, itwas not possible to observe the entire water supply and distribution system throughout this entire home.Damage to the piping can be present in a non-visible location. You may wish to have the water supplyand distribution system further explored by a licensed plumber contractor before the end of yourcontingency period to determine if any latent defects exist.(2) AQUAPEX non-metallic water supply lines have been installed in this house. Our inspection is limitedto the visible connectors and pipes. If client concerned about information regarding guarantees orwarranties of this product, we advise contacting Wirsbo Aquapex at 1-800-321-4739. For moreinformation about PEX, please visit the PPFA (Plastic Pipe and Fittings Association) athttp://www.ppfahome.org/pex/faqpex.htm

2.4 FIXTURES AND CONNECTED DEVICESInspected

John Robinson's Inspection Group Ellis

5583 Vista San Simeon Page 10 of 58

Page 12: FAIRA TRANSPARENCY REPORTS 5583 Vista San Simeon, San Diego… · 2017-09-07 · 5583 Vista San Simeon, San Diego, CA 92154 . September 7, 2017 . ... 10 Heating / Central Air Conditioning

(1) One or more sink faucet is loose to the countertop/sink. Advise further evaluation and repair by alicensed plumber or qualified professional.

2.4 Item 1(Picture) Kitchen

(2) One or more sink stopper did not function or is missing properly at the time of the inspection in one ormore areas. We advise necessary corrections.

2.4 Item 2(Picture) Master bathroom 2.4 Item 3(Picture) Hall bathroom

2.5 CORRECT PLUMBING AT FAUCETS (hot left, cold right)Inspected

2.6 TUB/SHOWER FIXTURESInformationalThe drain overflow cover appeared to be installed properly at the bathtub(s). However, determining if thedrain line is properly connected behind these covers is beyond the scope of this inspection. Recommendfurther evaluation by a licensed plumber.

2.7 PLUMBING DRAIN, WASTE AND VENT SYSTEMSRepair or Replace

John Robinson's Inspection Group Ellis

5583 Vista San Simeon Page 11 of 58

Page 13: FAIRA TRANSPARENCY REPORTS 5583 Vista San Simeon, San Diego… · 2017-09-07 · 5583 Vista San Simeon, San Diego, CA 92154 . September 7, 2017 . ... 10 Heating / Central Air Conditioning

(1) Unconventional plumbing materials were noted in use below one or more sink(s). These flexible drainlines are more prone to blockages due to their design and are typically not used by licensed plumbingcontractors. I recommend replacing this drain line with an approved drain line by a licensed plumber.

2.7 Item 1(Picture) Master bathroom

(2) The main sewer cleanout was noted at the garage. This is for your information.

2.7 Item 2(Picture)

(3) We attempt to evaluate drain pipes by flushing every drain that has an active fixture while observingits draw and watching for blockages or slow drains, but this is not a conclusive test and only a video-scanof the main line would confirm its actual condition. However, you can be sure that blockages will occur,usually relative in severity to the age of the system, and will range from minor ones in the branch lines, orat the traps beneath sinks, tubs, and showers, to major blockages in the main line. The minor ones areeasily cleared, either by chemical means or by removing and cleaning the traps. However, if tree rootsgrow into the main drain that connects the house to the public sewer, repairs could become expensive andmight include replacing the entire main line. For these reasons, we recommend that you ask the sellers ifthey have ever experienced any drainage problems, or you may wish to have the main waste line video-scanned before the close of escrow. Failing this, you should obtain an insurance policy that coversblockages and damage to the main line. However, most policies only cover plumbing repairs within thehouse, or the cost of rooter service, most of which are relatively inexpensive.

2.8 WATER HEATERS, CONTROLS, CHIMNEYS, FLUES AND VENTSRepair or Replace

John Robinson's Inspection Group Ellis

5583 Vista San Simeon Page 12 of 58

Page 14: FAIRA TRANSPARENCY REPORTS 5583 Vista San Simeon, San Diego… · 2017-09-07 · 5583 Vista San Simeon, San Diego, CA 92154 . September 7, 2017 . ... 10 Heating / Central Air Conditioning

(1) The water heater was functioning at the time of inspection. However, it appears to be an older unit (10years+), and repairs or even failure can be expected. You should consider replacing this water heater asa preventive measure.

2.8 Item 1(Picture) 2.8 Item 2(Picture)

(2) Leaking observed in a number of areas at the water heater water lines and TPR valve. Recommendcorrecting and advise repair and further review by a licensed plumbing contractor.

2.8 Item 3(Picture)

John Robinson's Inspection Group Ellis

5583 Vista San Simeon Page 13 of 58

Page 15: FAIRA TRANSPARENCY REPORTS 5583 Vista San Simeon, San Diego… · 2017-09-07 · 5583 Vista San Simeon, San Diego, CA 92154 . September 7, 2017 . ... 10 Heating / Central Air Conditioning

(3) The gas line for the water heater is missing a drip leg or sediment trap. Advise installation by alicensed plumber.

2.8 Item 4(Picture)

2.8 Item 5(Picture)

(4) Missing drip pan and drain line observed under the water heater. We advise installation by a qualified/licensed plumber.

2.8 Item 6(Picture)

(5) An expansion tank is not installed at the water heater. Most water heater manufactures recommend anexpansion tank be installed, whenever the water system is a "closed" system, such as this home. Advisefurther evaluation by a licensed plumber.

2.9 TEMPERATURE AND PRESSURE (T&P) RELIEF VALVEInspected

2.10 WATER HEATER STRAPPING AND BRACINGInspected

2.11 MAIN GAS SHUT OFF VALVE (describe location)Informational

John Robinson's Inspection Group Ellis

5583 Vista San Simeon Page 14 of 58

Page 16: FAIRA TRANSPARENCY REPORTS 5583 Vista San Simeon, San Diego… · 2017-09-07 · 5583 Vista San Simeon, San Diego, CA 92154 . September 7, 2017 . ... 10 Heating / Central Air Conditioning

The main gas shut off valve is located at the gas meter at the left side of the house (facing front).

2.11 Item 1(Picture)

2.12 GAS STORAGE AND DISTRIBUTION SYSTEMS (Interior fuel storage, piping, venting, supports,leaks)Inspected

2.13 WATER FILTER/SOFTENERNot InspectedWe do not inspect water filtration units. Recommend contacting the installer for information on lifeexpectancy or condition.

The plumbing in the home was inspected and reported on with the above information. While the inspector makes every effort tofind all areas of concern, some areas can go unnoticed. Washing machine drain line for example cannot be checked for leaks or theability to handle the volume during drain cycle. Older homes with galvanized supply lines or cast iron drain lines can be obstructedand barely working during an inspection but then fails under heavy use. If the water is turned off or not used for periods of time(like a vacant home waiting for closing) rust or deposits within the pipes can further clog the piping system. Please be aware thatthe inspector has your best interest in mind. Any repair items mentioned in this report should be considered before purchase. It isrecommended that qualified contractors be used in your further inspection or repair issues as it relates to the comments in thisinspection report.

John Robinson's Inspection Group Ellis

5583 Vista San Simeon Page 15 of 58

Page 17: FAIRA TRANSPARENCY REPORTS 5583 Vista San Simeon, San Diego… · 2017-09-07 · 5583 Vista San Simeon, San Diego, CA 92154 . September 7, 2017 . ... 10 Heating / Central Air Conditioning

3. Interiors

The home inspector shall observe the visually accessible areas of the: walls, ceiling, and floors; steps, stairways,balconies, and railings; counters and a representative number of installed cabinets; and a representative number ofdoors and windows. The home inspector shall: operate a representative number of windows and interior doors; andreport signs of abnormal or harmful water penetration into the building or signs of abnormal or harmful condensationon building components.

The home inspector is not required to observe: Paint, wallpaper, and other finish treatments on the interior walls,ceilings, and floors; Carpeting; or Draperies, blinds, or other window treatments.

Styles & MaterialsCeiling Materials:Sheetrock

Wall Materials:Sheetrock

Floor Covering(s):Engineered HardwoodTile

Interior Doors:Hollow Core

Cabinetry:Wood

Kitchen Countertop:Granite

Windows:Aluminum

Items3.0 INTERIOR GENERAL

InformationalLimited review of the interior due to restrictive clearances and a number of personal items. Please note:Determining if damage, the presence of organic growths, moisture or wood rot behind wall, floor andceiling coverings is beyond the scope of this inspection. If you are concerned or believe that theseconditions may exist in a nonvisible or concealed area, I recommend that you have this home furtherexamined by a qualified contractor or environmental hygienist.

3.1 CEILINGSInspected

3.2 WALLSInformationalEvidence of repairs noted on the wall below one or more sink. This is indicative of past plumbing repairs.Recommend asking the sellers about this. Please note: determining if damage exist behind the walls ofany surface is beyond the scope of this inspection.

3.2 Item 1(Picture) Hall bathroom

John Robinson's Inspection Group Ellis

5583 Vista San Simeon Page 16 of 58

Page 18: FAIRA TRANSPARENCY REPORTS 5583 Vista San Simeon, San Diego… · 2017-09-07 · 5583 Vista San Simeon, San Diego, CA 92154 . September 7, 2017 . ... 10 Heating / Central Air Conditioning

3.3 DOORS (REPRESENTATIVE NUMBER)Repair or ReplaceDoor(s) dose not latch properly in one or more areas. Advise correcting and maintenance as needed.

3.3 Item 1(Picture) Master bathroom closet

3.4 WINDOWS (REPRESENTATIVE NUMBER)Repair or Replace(1) Slipped/damaged sash balance spring noted at master bathroom single hung window(s). This effectsthe operation of the window and/or the window will not remain open. Advise further evaluation and repairby a licensed window contractor or qualified professional.

3.4 Item 1(Picture)

John Robinson's Inspection Group Ellis

5583 Vista San Simeon Page 17 of 58

Page 19: FAIRA TRANSPARENCY REPORTS 5583 Vista San Simeon, San Diego… · 2017-09-07 · 5583 Vista San Simeon, San Diego, CA 92154 . September 7, 2017 . ... 10 Heating / Central Air Conditioning

(2) Window lock(s) are not functioning properly or are inoperable in one or more areas. Recommendcorrecting and advise repair by a qualified/licensed window contractor.

3.4 Item 2(Picture) 3rd bedroom

(3) The window tracks and hardware need to be cleaned and/or serviced to function properly and/orsmoothly. Recommend further evaluation by a licensed window contractor.

3.4 Item 3(Picture) 3.4 Item 4(Picture)

(4) One or more window screen is damaged, bent or missing. Advise repair or replacement as needed.(5) Please be advised: Failed seals in insulated glass (double-pane) windows are not always detectable. Insome instances inspector may not be able to disclose the exact condition of every window, depending onthe ambient conditions (weather) or if the windows are dirty at time of inspection. Moisture betweenpanes of glass in a double-pane window with a failed seal may or may not be observable depending onvariations in ambient conditions such as temperature and humidity. Windows are reported as they areobserved at the time of the inspection only. If you have present or future concerns regarding the integrityof thermal pane seals, it is strongly suggested that you consult with a licensed window contractor forfurther evaluation. This inspection is not a warranty or guarantee of any kind regarding the integrity ofthe windows.

3.5 FLOORS COVERINGSInspected

3.6 STEPS, STAIRWAYS, BALCONIES AND RAILINGSRepair or Replace, Safety Concern

John Robinson's Inspection Group Ellis

5583 Vista San Simeon Page 18 of 58

Page 20: FAIRA TRANSPARENCY REPORTS 5583 Vista San Simeon, San Diego… · 2017-09-07 · 5583 Vista San Simeon, San Diego, CA 92154 . September 7, 2017 . ... 10 Heating / Central Air Conditioning

Improper sloping observed at the stairway steps in one or more areas. This is a potential fall hazard.Recommend correcting and advise further review by a licensed general contactor for any necessaryrepairs.

3.6 Item 1(Picture)

3.7 COUNTERS AND A REPRESENTATIVE NUMBER OF CABINETSRepair or Replace(1) Back-splash is missing at the bathroom sink wall in one or more areas. Recommend correcting andadvise repair by a licensed professional.

3.7 Item 1(Picture) 1/2 bathroom

John Robinson's Inspection Group Ellis

5583 Vista San Simeon Page 19 of 58

Page 21: FAIRA TRANSPARENCY REPORTS 5583 Vista San Simeon, San Diego… · 2017-09-07 · 5583 Vista San Simeon, San Diego, CA 92154 . September 7, 2017 . ... 10 Heating / Central Air Conditioning

(2) Cracked/missing grout observed at counter/back-splash in one or more areas. Recommend correctingand advise repair by a qualified professional.

3.7 Item 2(Picture) Master bathroom

(3) Advise caulking around the sinks/countertops. Where sealant is aged and or failing. Recommendcorrecting and advise repair by a licensed professional.

3.7 Item 3(Picture) Kitchen

(4) Moisture stains noted at the underside of the kitchen counter top. This area appeared dry at the timeof the inspection. Recommend further evaluation by a licensed termite inspector.

3.7 Item 4(Picture) Kitchen

John Robinson's Inspection Group Ellis

5583 Vista San Simeon Page 20 of 58

Page 22: FAIRA TRANSPARENCY REPORTS 5583 Vista San Simeon, San Diego… · 2017-09-07 · 5583 Vista San Simeon, San Diego, CA 92154 . September 7, 2017 . ... 10 Heating / Central Air Conditioning

3.8 TUB/SHOWER ENCLOSURERepair or ReplaceGaps noted in one or more areas at the master bathroom shower glass door. Recommend correcting andadvise repair by a licensed professional.

3.8 Item 1(Picture) 3.8 Item 2(Picture)

3.9 ATTICInformationalDue to the structure of the roof/framing and forced air handling components, some areas of the atticcould not be inspected.

3.10 ROOM ADDITIONS/MODIFICATIONSInformationalThis home has undergone major renovation, remodeling, and additions to the original structure. As it isbeyond the scope of our inspection to verify the existence of permits, we advise obtaining this prior tothe close of escrow.

The interior of the home was inspected and reported on with the above information. While the inspector makes every effort to findall areas of concern, some areas can go unnoticed. The inspection did not involve moving furniture and inspecting behind furniture,area rugs or areas obstructed from view. Please be aware that the inspector has your best interest in mind. Any repair itemsmentioned in this report should be considered before purchase. It is recommended that qualified contractors be used in yourfurther inspection or repair issues as it relates to the comments in this inspection report.

John Robinson's Inspection Group Ellis

5583 Vista San Simeon Page 21 of 58

Page 23: FAIRA TRANSPARENCY REPORTS 5583 Vista San Simeon, San Diego… · 2017-09-07 · 5583 Vista San Simeon, San Diego, CA 92154 . September 7, 2017 . ... 10 Heating / Central Air Conditioning

4. Electrical System

The home inspector shall observe: Service entrance conductors; Service equipment, grounding equipment, main overcurrent device, and main and distribution panels; Amperage and voltage ratings of the service; Branch circuitconductors, their over current devices, and the compatibility of their ampacities and voltages; The operation of arepresentative number of installed ceiling fans, lighting fixtures, switches and receptacles located inside the house,garage, and on the dwelling's exterior walls; The polarity and grounding of all receptacles within six feet of interiorplumbing fixtures, and all receptacles in the garage or carport, and on the exterior of inspected structures; Theoperation of ground fault circuit interrupters; and Smoke detectors. The home inspector shall describe: Serviceamperage and voltage; Service entry conductor materials; Service type as being overhead or underground; andLocation of main and distribution panels. The home inspector shall report any observed aluminum branch circuit wiring.The home inspector shall report on presence or absence of smoke detectors, and operate their test function, ifaccessible, except when detectors are part of a central system.

The home inspector is not required to: Insert any tool, probe, or testing device inside the panels; Test or operate anyover current device except ground fault circuit interrupters; Dismantle any electrical device or control other than toremove the covers of the main and auxiliary distribution panels; or Observe: Low voltage systems; Security systemdevices, heat detectors, or carbon monoxide detectors; Telephone, security, cable TV, intercoms, or other ancillarywiring that is not a part of the primary electrical distribution system; or Built-in vacuum equipment.

Common national safety standards require electrical panels to be weatherproof, readily accessible, and have a minimumof thirty-six inches of clear space in front of them for service. Also, they should have a main disconnect, and eachcircuit within the panel should be clearly labeled. Industry standards only require us to test a representative number ofaccessible switches, receptacles, and light fixtures. However, we attempt to test every one that is unobstructed, but if aresidence is furnished we will obviously not be able to test each one.

Styles & MaterialsElectrical Service Conductors:Below Ground

Panel Type:Circuit Breakers

Panel Capacity:125 AMP

Electric Panel Manufacturer:CUTLER HAMMER

Branch Wire 15 and 20 Amp:Copper

Wiring Methods:Romex

Exterior Lighting Control:Standard switched

Items4.0 LOCATION OF MAIN AND DISTRIBUTION PANELS

InformationalMain panel is located at left corner of house (facing front).

4.0 Item 1(Picture) 4.0 Item 2(Picture)

John Robinson's Inspection Group Ellis

5583 Vista San Simeon Page 22 of 58

Page 24: FAIRA TRANSPARENCY REPORTS 5583 Vista San Simeon, San Diego… · 2017-09-07 · 5583 Vista San Simeon, San Diego, CA 92154 . September 7, 2017 . ... 10 Heating / Central Air Conditioning

4.1 MAIN AND DISTRIBUTION PANELSRepair or Replace(1) The electrical panel appears to be mostly full. Space may not be available for the addition of morebreakers (if any). Advise consulting a licensed electrician for any future upgrades and/or any furtherinformation regarding the electrical panel/system.

4.1 Item 1(Picture)

(2) Some labels are present, but illegible or confusing. Recommend correcting for safety reasons.

4.1 Item 2(Picture)

4.2 SYSTEM GROUNDING AND GROUNDING EQUIPMENTInspected

4.3 OVERCURRENT DEVICES (Circuit Breakers, Fuses) AND COMPATIBILITY OF THEIR AMPERAGEAND VOLTAGERepair or Replace

John Robinson's Inspection Group Ellis

5583 Vista San Simeon Page 23 of 58

Page 25: FAIRA TRANSPARENCY REPORTS 5583 Vista San Simeon, San Diego… · 2017-09-07 · 5583 Vista San Simeon, San Diego, CA 92154 . September 7, 2017 . ... 10 Heating / Central Air Conditioning

Unconventional wiring observed at the main panel breaker in one or more areas. Conductive paste wasnoted missing at breaker multi strand wiring. Recommend correcting and further review by a qualified/licensed electrician.

4.3 Item 1(Picture)

4.4 BRANCH CIRCUIT CONDUCTORSInformationalPlease note: due to wall coverings, insulation, HVAC ductwork or other obstructions, it was not possible toobserve the branch circuit wiring throughout this entire home. Damage to the insulation or wiring itselfcan be present in a non-visible location. You may wish to have the branch circuit wiring further exploredby a licensed electrical contractor before the end of your contingency period to determine if any latentdefects exist.

4.5 POLARITY AND GROUNDING OF RECEPTACLESInspected

4.6 CONNECTED DEVICES AND FIXTURES (Observed from a representative number operation ofceiling fans, lighting fixtures, switches and receptacles located inside the house, garage, andon the dwelling's exterior walls)Repair or Replace, Safety Concern(1) Improper location of electrical outlet noted in the bathroom (installed next to tub/shower) at one ormore areas. This is a possible safety concern. Recommend relocating and advise repair by a qualifiedelectrician, prior to the close of escrow.

4.6 Item 1(Picture) Master bathroom

John Robinson's Inspection Group Ellis

5583 Vista San Simeon Page 24 of 58

Page 26: FAIRA TRANSPARENCY REPORTS 5583 Vista San Simeon, San Diego… · 2017-09-07 · 5583 Vista San Simeon, San Diego, CA 92154 . September 7, 2017 . ... 10 Heating / Central Air Conditioning

(2) One or more light(s) is/are inoperable; possibly due to bulb. Advise replacing bulbs and checking theoperation of these fixtures. If light fails to work, further evaluation by a licensed electrician isrecommended.

4.6 Item 2(Picture) Kitchen 4.6 Item 3(Picture) Hall bathroom

4.7 EXTERIOR LIGHTING (Patio lights, motion sensors)Repair or Replace(1) I was unable to verify operation of one or more exterior light. Recommend asking the seller todemonstrate operation of the exterior lighting and have further evaluated by a licensed electricalcontractor to determine if corrections are needed at this time.

4.7 Item 1(Picture) 4.7 Item 2(Picture)

John Robinson's Inspection Group Ellis

5583 Vista San Simeon Page 25 of 58

Page 27: FAIRA TRANSPARENCY REPORTS 5583 Vista San Simeon, San Diego… · 2017-09-07 · 5583 Vista San Simeon, San Diego, CA 92154 . September 7, 2017 . ... 10 Heating / Central Air Conditioning

(2) Sensor lights were not tested. Recommend verifying operation and have further evaluation asnecessary.

4.7 Item 3(Picture)

4.8 OPERATION OF GFCI (GROUND FAULT CIRCUIT INTERRUPTERS)Inspected

4.9 OPERATION OF AFCI (ARC FAULT CIRCUIT INTERRUPTERS)Not Present

4.10 SMOKE DETECTORSInformationalWe recommend replacing all smoke detectors upon moving into the home. Smoke detectors that are 10years old or older may have a failure rate as high as 30%, and smoke detectors that are 15 years old orolder may have a failure rate as high as 50% according to the National FIre Protection Associationwww.nfpa.org. We also recommend that a smoke alarm be installed in each bedroom, and at least oneon each level outside of bedrooms.

4.11 CARBON MONOXIDE DETECTOR(S) (Describe number and location)InformationalCO detectors are installed on each level of the home as required.

4.11 Item 1(Picture) 4.11 Item 2(Picture)

4.12 CABLE AND TELEPHONE ENTRANCENot Inspected

John Robinson's Inspection Group Ellis

5583 Vista San Simeon Page 26 of 58

Page 28: FAIRA TRANSPARENCY REPORTS 5583 Vista San Simeon, San Diego… · 2017-09-07 · 5583 Vista San Simeon, San Diego, CA 92154 . September 7, 2017 . ... 10 Heating / Central Air Conditioning

The electrical system of the home was inspected and reported on with the above information. While the inspector makes everyeffort to find all areas of concern, some areas can go unnoticed. Outlets were not removed and the inspection was only visual. Anyoutlet not accessible (behind the refrigerator for example) was not inspected or accessible. Please be aware that the inspector hasyour best interest in mind. Any repair items mentioned in this report should be considered before purchase. It is recommendedthat qualified contractors be used in your further inspection or repair issues as it relates to the comments in this inspection report.

John Robinson's Inspection Group Ellis

5583 Vista San Simeon Page 27 of 58

Page 29: FAIRA TRANSPARENCY REPORTS 5583 Vista San Simeon, San Diego… · 2017-09-07 · 5583 Vista San Simeon, San Diego, CA 92154 . September 7, 2017 . ... 10 Heating / Central Air Conditioning

5. Garage

Styles & MaterialsGarage Door Type:One automatic

Garage Door Material:Metal

Auto-opener Manufacturer:LIFT-MASTER

Items5.0 GARAGE GENERAL

InformationalDue to occupants personal items, not all areas were visible. Advise a careful evaluation during final walk-through.

5.1 GARAGE CEILINGS/ROOF FRAMINGInspected

5.2 GARAGE WALLS (INCLUDING FIREWALL SEPARATION)Inspected

5.3 GARAGE FLOORInspected

5.4 GARAGE DOOR (S)Inspected

5.5 GARAGE DOOR OPERATORS (Report whether or not doors will reverse when met withresistance)Inspected

5.6 OCCUPANT DOOR FROM GARAGE TO INSIDE HOMERepair or Replace, Safety ConcernThe occupant door from the garage is not equipped with a self-closing device. For fire safety it isrecommended this door be self-closing/latching. Advise installing a self closing device.

5.6 Item 1(Picture)

5.7 GARAGE VENTSInspected

John Robinson's Inspection Group Ellis

5583 Vista San Simeon Page 28 of 58

Page 30: FAIRA TRANSPARENCY REPORTS 5583 Vista San Simeon, San Diego… · 2017-09-07 · 5583 Vista San Simeon, San Diego, CA 92154 . September 7, 2017 . ... 10 Heating / Central Air Conditioning

6. Insulation and Ventilation

The home inspector shall observe: Insulation and vapor retarders in unfinished spaces; Ventilation of attics andfoundation areas; Kitchen, bathroom, and laundry venting systems; and the operation of any readily accessible atticventilation fan, and, when temperature permits, the operation of any readily accessible thermostatic control. The homeinspector shall describe: Insulation in unfinished spaces; and Absence of insulation in unfinished space at conditionedsurfaces. The home inspector shall: Move insulation where readily visible evidence indicates the need to do so; andMove insulation where chimneys penetrate roofs, where plumbing drain/waste pipes penetrate floors, adjacent to earthfilled stoops or porches, and at exterior doors. The home inspector is not required to report on: Concealed insulationand vapor retarders; or Venting equipment that is integral with household appliances.

Styles & MaterialsAttic Insulation:BattFiberglass

Ventilation:Roof vents

Exhaust Fans:FanWindow

Dryer Power Source:Gas Connection

Dryer Vent:Flexible Metal

Items6.0 INSULATION IN ATTIC

Inspected

6.1 VENTILATION OF ATTIC AND FOUNDATION AREASInspected

6.2 VENTING SYSTEMS (Kitchens, baths and laundry)Inspected

6.3 VENTILATION FANS AND THERMOSTATIC CONTROLSNot Present

The insulation and ventilation of the home was inspected and reported on with the above information. While the inspector makesevery effort to find all areas of concern, some areas can go unnoticed. Venting of exhaust fans or clothes dryer cannot be fullyinspected and bends or obstructions can occur without being accessible or visible (behind wall and ceiling coverings). Onlyinsulation that is visible was inspected. Please be aware that the inspector has your best interest in mind. Any repair itemsmentioned in this report should be considered before purchase. It is recommended that qualified contractors be used in yourfurther inspection or repair issues as it relates to the comments in this inspection report.

John Robinson's Inspection Group Ellis

5583 Vista San Simeon Page 29 of 58

Page 31: FAIRA TRANSPARENCY REPORTS 5583 Vista San Simeon, San Diego… · 2017-09-07 · 5583 Vista San Simeon, San Diego, CA 92154 . September 7, 2017 . ... 10 Heating / Central Air Conditioning

7. Roofing

The home inspector shall observe: Roof covering; Roof drainage systems; Flashings; Skylights, chimneys, and roofpenetrations; and Signs of' leaks or abnormal condensation on building components. The home inspector shall:Describe the type of roof covering materials; and Report the methods used to observe the roofing. The home inspectoris not required to: Walk on the roofing; or Observe attached accessories including but not limited to solar systems,antennae, and lightning arrestors.

If this home is identified as having a Tile roof covering, it was inspected from the ground and attic to avoid damagingthe roof covering, and possibly voiding the warranty. This is in accordance with the CREIA and ASHI standards ofpractice. The entire roof was not visible and I cannot guarantee that all of the tiles are in good condition. I recommendthat you have the roof inspected by a licensed roof contractor if you are concerned that there may be tiles that arebroken or have slipped out of position.

We recommend that you include "roof" coverage on a home warranty. To guarantee this roof will not leak, you wouldneed to have a roofing company perform a water test and issue a roof certification, which is beyond the scope of ahome inspection. However, the sellers or the occupants will generally have the most intimate knowledge of the roof, andyou should ask them about its history and then schedule a regular maintenance service.

Please note that a home inspection is neither a guarantee of any kind against leaking, nor a warranty of the longevity ofthe roof. It is a visual evaluation of the roof and the attic below. We strongly recommend that you purchase andmaintain a roof rider with your home warranty.

Styles & MaterialsRoof Covering:ConcreteTile

Viewed roof covering from:Pole Camera

Chimney (exterior):Stucco

Items7.0 ROOF COVERINGS

Repair or ReplaceTile roof covering was inspected from the ground and attic to avoid damaging the roof covering, andpossibly voiding the warranty. This is in accordance with the CalNACHI standards of practice. The entireroof was not visible. I cannot guarantee that all of the tiles, flashings, and roof penetrations are in goodcondition. I recommend that you have the roof inspected by a licensed roof contractor if you areconcerned that there may be tiles that are broken or have slipped out of position.

7.0 Item 1(Picture) 7.0 Item 2(Picture)

John Robinson's Inspection Group Ellis

5583 Vista San Simeon Page 30 of 58

Page 32: FAIRA TRANSPARENCY REPORTS 5583 Vista San Simeon, San Diego… · 2017-09-07 · 5583 Vista San Simeon, San Diego, CA 92154 . September 7, 2017 . ... 10 Heating / Central Air Conditioning

7.0 Item 3(Picture)

7.1 FLASHINGS, SKYLIGHTS, CHIMNEYS AND ROOF PENETRATIONSInformationalMy inspection of the roof penetrations was limited to what could be seen from our vantage points. Icannot guarantee that all the roof penetrations are in good condition. You may wish to contact a alicensed roof contractor for further evaluation.

7.2 ROOF SHEATHING (As observable from attic)Inspected

7.3 ROOF DRAINAGE SYSTEMSInformationalMy inspection of the roof drainage system was limited to what could be seen from our vantage points. Icannot guarantee that all the roof drainage system(s) are in good condition. You may wish to contact a alicensed gutter/roof drainage contractor for further evaluation.

The roof of the home was inspected and reported on with the above information. While the inspector makes every effort to find allareas of concern, some areas can go unnoticed. Roof coverings and skylights can appear to be leak proof during inspection andweather conditions. Our inspection makes an attempt to find a leak but sometimes cannot. Please be aware that the inspector hasyour best interest in mind. Any repair items mentioned in this report should be considered before purchase. It is recommendedthat qualified contractors be used in your further inspection or repair issues as it relates to the comments in this inspection report.

John Robinson's Inspection Group Ellis

5583 Vista San Simeon Page 31 of 58

Page 33: FAIRA TRANSPARENCY REPORTS 5583 Vista San Simeon, San Diego… · 2017-09-07 · 5583 Vista San Simeon, San Diego, CA 92154 . September 7, 2017 . ... 10 Heating / Central Air Conditioning

8. Exterior

The home inspector shall observe: Wall cladding, flashings, and trim; Entryway doors and a representative number ofwindows; Garage door operators; Decks, balconies, stoops, steps, areaways, porches and applicable railings; Eaves,soffits, and fascias; and Vegetation, grading, drainage, driveways, patios, walkways, and retaining walls with respect totheir effect on the condition of the building. The home inspector shall: Describe wall cladding materials; Operate allentryway doors and a representative number of windows; Operate garage doors manually or by using permanentlyinstalled controls for any garage door operator; Report whether or not any garage door operator will automaticallyreverse or stop when meeting reasonable resistance during closing; and Probe exterior wood components wheredeterioration is suspected. The home inspector is not required to observe: Storm windows, storm doors, screening,shutters, awnings, and similar seasonal accessories; Fences; Presence of safety glazing in doors and windows; Garagedoor operator remote control transmitters; Geological conditions; Soil conditions; Recreational facilities (including spas,saunas, steam baths, swimming pools, tennis courts, playground equipment, and other exercise, entertainment, orathletic facilities); Detached buildings or structures; or Presence or condition of buried fuel storage tanks. The homeinspector is not required to: Move personal items, panels, furniture, equipment, plant life, soil, snow, ice or debris thatobstructs access or visibility.

Styles & MaterialsSIDING MATERIAL:STUCCO

EXTERIOR ENTRY DOORS:WOODGLASS

APPURTENANCE:BALCONY

DRIVEWAY:CONCRETE

Items8.0 EXTERIOR GENERAL INFORMATION

InformationalThis home has undergone major renovation, remodeling, and additions to the original structure. As it isbeyond the scope of our inspection to verify the existence of permits, we advise obtaining this prior to theclose of escrow.

8.0 Item 1(Picture)

8.1 WALL CLADDING FLASHING AND TRIMRepair or Replace(1) The sprinklers appear to be spraying the stucco in various areas of the exterior. This condition canlead to damaged stucco, rusted weep screed and lead to moisture intrusion. Recommend adjusting thesprinkler heads to spray away from the building to prevent further damage. You may also wish to havethe stucco further evaluated by a licensed stucco contractor to determine if any repairs are needed at this

John Robinson's Inspection Group Ellis

5583 Vista San Simeon Page 32 of 58

Page 34: FAIRA TRANSPARENCY REPORTS 5583 Vista San Simeon, San Diego… · 2017-09-07 · 5583 Vista San Simeon, San Diego, CA 92154 . September 7, 2017 . ... 10 Heating / Central Air Conditioning

time. Please note: Determining if damage exist behind the walls of the siding is outside the scope of thisinspection.

8.1 Item 1(Picture)

(2) Moisture damaged stucco noted in areas. Recommend further evaluation and repair by a licensedstucco contractor.

8.1 Item 2(Picture)

(3) Stucco cracks and deterioration noted in areas. These cracks may be prone to moisture intrusionissues. You may wish to view them for yourself and have repaired by a licensed contractor.

8.2 DOORS (Exterior)Repair or Replace, Safety Concern

John Robinson's Inspection Group Ellis

5583 Vista San Simeon Page 33 of 58

Page 35: FAIRA TRANSPARENCY REPORTS 5583 Vista San Simeon, San Diego… · 2017-09-07 · 5583 Vista San Simeon, San Diego, CA 92154 . September 7, 2017 . ... 10 Heating / Central Air Conditioning

A double keyed dead bolt was noted present at one or more exterior door. This condition poses a potentialemergency egress concern. Advise replacement with a standard thumb latch dead bolt by a qualifiedprofessional.

8.2 Item 1(Picture) Front entry door

8.3 WINDOWSInspected

8.4 TEMPERED GLASS PRESENT AT DOORS AND WINDOWSInspected

8.5 EAVES, SOFFITS AND FASCIASInspected

8.6 FENCING AND GATESInspected

8.7 VEGETATION, GRADING, DRAINAGE, DRIVEWAYS, PATIO FLOOR, WALKWAYS AND RETAININGWALLS (With respect to their effect on the condition of the building)Repair or Replace(1) Low/neutral areas were observed at the grading which will cause water to pond during rain orextended irrigation. Standing water can be detrimental to the integrity of the foundation of the house. Itis important to prevent or minimize standing water around the house. This can be accomplished byproperly sloping the ground away from the house, or adding yard drains to carry water away from the lowlying areas. Rain gutters should also be installed and drained away from the house. Advise monitoringduring times of rain and making corrections as needed.(2) Typical settlement cracks noted in areas of the hardscape. Advise monitoring and repair whenneeded.(3) Sub surface drainage observed throughout the exterior in one or more areas. Unable to determinecondition and drainage qualified. Advise verifying condition with a qualified/licensed processional, prior tothe close of escrow.

8.8 DECKS, BALCONIES, STOOPS, STEPS, AREAWAYS, PORCHES, PATIO/ COVER AND APPLICABLERAILINGSRepair or Replace, Safety Concern

John Robinson's Inspection Group Ellis

5583 Vista San Simeon Page 34 of 58

Page 36: FAIRA TRANSPARENCY REPORTS 5583 Vista San Simeon, San Diego… · 2017-09-07 · 5583 Vista San Simeon, San Diego, CA 92154 . September 7, 2017 . ... 10 Heating / Central Air Conditioning

Loose railing observed at the master bedroom balcony in one or more areas. This is a possible safetyconcern. Recommend correcting and advise repair by a licensed professional.

8.8 Item 1(Picture)

8.9 IRRIGATION SYSTEMSNot InspectedIrrigation systems are not inspected as part of a home inspection.

The exterior of the home was inspected and reported on with the above information. While the inspector makes every effort to findall areas of concern, some areas can go unnoticed. Please be aware that the inspector has your best interest in mind. Any repairitems mentioned in this report should be considered before purchase. It is recommended that qualified contractors be used in yourfurther inspection or repair issues as it relates to the comments in this inspection report.

John Robinson's Inspection Group Ellis

5583 Vista San Simeon Page 35 of 58

Page 37: FAIRA TRANSPARENCY REPORTS 5583 Vista San Simeon, San Diego… · 2017-09-07 · 5583 Vista San Simeon, San Diego, CA 92154 . September 7, 2017 . ... 10 Heating / Central Air Conditioning

9. Structural Components

The Home Inspector shall observe structural components including foundations, floors, walls, columns or piers, ceilingsand roof. The home inspector shall describe the type of Foundation, floor structure, wall structure, columns or piers,ceiling structure, roof structure. The home inspector shall: Probe structural components where deterioration issuspected; Enter under floor crawl spaces, basements, and attic spaces except when access is obstructed, when entrycould damage the property, or when dangerous or adverse situations are suspected; Report the methods used toobserve under floor crawl spaces and attics; and Report signs of abnormal or harmful water penetration into thebuilding or signs of abnormal or harmful condensation on building components. The home inspector is not required to:Enter any area or perform any procedure that may damage the property or its components or be dangerous to oradversely effect the health of the home inspector or other persons.

Styles & MaterialsFoundation:Poured concrete

Wall Structure:Wood

Floor Structure:Not visible

Ceiling Structure:4" or better

Roof Structure:Engineered wood trusses

Roof-Type:Gable

Method used to observe attic:Limited access

Items9.0 WALLS (Structural)

Inspected

9.1 FOUNDATIONS, BASEMENTS AND CRAWLSPACES (Report signs of abnormal or harmful waterpenetration into the building or signs of abnormal or harmful condensation on buildingcomponents.)InformationalDue to floor coverings, vegetation, siding or other obstructions, not all areas of the foundation wherevisible. Our review of the home's foundation is limited. You may wish to have this further explored by alicensed foundation contactor and/or a licensed structural engineer to determine if any latent defectsexist.

9.2 CEILINGS (structural)Inspected

9.3 FLOORS (Structural)InformationalDue to floor coverings, vegetation, siding or other obstructions, not all areas of the foundation wherevisible. Our review of the home's foundation is limited. You may wish to have this further explored by alicensed foundation contactor and/or a licensed structural engineer to determine if any latent defectsexist.

9.4 ROOF STRUCTURE AND ATTICRepair or Replace

John Robinson's Inspection Group Ellis

5583 Vista San Simeon Page 36 of 58

Page 38: FAIRA TRANSPARENCY REPORTS 5583 Vista San Simeon, San Diego… · 2017-09-07 · 5583 Vista San Simeon, San Diego, CA 92154 . September 7, 2017 . ... 10 Heating / Central Air Conditioning

Engineered wood truss structure has been cracked/damaged in one or more areas. This roofing structureis engineered for this home. Further evaluation and repair is recommended by a licensed/qualifiedstructural contractor, prior to the close of escrow.

9.4 Item 1(Picture)

9.5 PRESENCE OF FOUNDATION BOLTSInformationalThe home is likely bolted to the foundation. However, drywall was in place at the time of the inspection.Bolts could not be seen because of this.

The structure of the home was inspected and reported on with the above information. While the inspector makes every effort tofind all areas of concern, some areas can go unnoticed. Please be aware that the inspector has your best interest in mind. Anyrepair items mentioned in this report should be considered before purchase. It is recommended that qualified contractors be usedin your further inspection or repair issues as it relates to the comments in this inspection report.

John Robinson's Inspection Group Ellis

5583 Vista San Simeon Page 37 of 58

Page 39: FAIRA TRANSPARENCY REPORTS 5583 Vista San Simeon, San Diego… · 2017-09-07 · 5583 Vista San Simeon, San Diego, CA 92154 . September 7, 2017 . ... 10 Heating / Central Air Conditioning

10. Heating / Central Air Conditioning

The home inspector shall observe permanently installed heating and cooling systems including: Heating equipment;Cooling Equipment that is central to home; Normal operating controls; Automatic safety controls; Chimneys, flues, andvents, where readily visible; Solid fuel heating devices; Heat distribution systems including fans, pumps, ducts andpiping, with supports, insulation, air filters, registers, radiators, fan coil units, convectors; and the presence of aninstalled heat source in each room. The home inspector shall describe: Energy source; and Heating equipment anddistribution type. The home inspector shall operate the systems using normal operating controls. The home inspectorshall open readily openable access panels provided by the manufacturer or installer for routine homeownermaintenance. The home inspector is not required to: Operate heating systems when weather conditions or othercircumstances may cause equipment damage; Operate automatic safety controls; Ignite or extinguish solid fuel fires; orObserve: The interior of flues; Fireplace insert flue connections; Humidifiers; Electronic air filters; or The uniformity oradequacy of heat supply to the various rooms.

Styles & MaterialsHeat Type:Forced AirReplaced

Energy Source:Gas

Number of Heat Systems (excludingwood):One

Heat SystemManufacturer:AMANA

Ductwork:Insulated

Filter Type:Washable

Cooling EquipmentType:Air conditioner unitReplaced

Cooling Equipment EnergySource:Electricity

Number of AC Only Units:One

Central AirManufacturer:AMANA

Types of Fireplaces:Gas logPrefabricated

Items10.0 HEATING EQUIPMENT

Repair or Replace

John Robinson's Inspection Group Ellis

5583 Vista San Simeon Page 38 of 58

Page 40: FAIRA TRANSPARENCY REPORTS 5583 Vista San Simeon, San Diego… · 2017-09-07 · 5583 Vista San Simeon, San Diego, CA 92154 . September 7, 2017 . ... 10 Heating / Central Air Conditioning

(1) The furnace installed in this home is not original. The furnace appeared functional at the time ofinspection. However, we recommend asking the sellers for documentation showing that this unit wasinstalled by a licensed HVAC contractor per the manufactures installation requirements. Ifdocumentation cannot be produced, I recommend this unit be further explored by a licensed HVACcontractor for safety.

10.0 Item 1(Picture) 10.0 Item 2(Picture)

(2) The furnace gas piping is not equipped with a sediment trap or drip leg. Advise installation by alicensed plumber or qualified professional.

10.0 Item 3(Picture)

10.0 Item 4(Picture)

10.1 NORMAL OPERATING CONTROLSInspected

10.2 AUTOMATIC SAFETY CONTROLSInspected

10.3 PRESENCE OF INSTALLED HEAT SOURCE IN EACH ROOMInspected

10.4 FLUE(S) FOR HEATING EQUIPMENTInspected

10.5 DISTRIBUTION SYSTEMS (including fans, pumps, ducts and piping, with supports, insulation,air filters, registers, radiators, fan coil units and convectors)Repair or Replace

John Robinson's Inspection Group Ellis

5583 Vista San Simeon Page 39 of 58

Page 41: FAIRA TRANSPARENCY REPORTS 5583 Vista San Simeon, San Diego… · 2017-09-07 · 5583 Vista San Simeon, San Diego, CA 92154 . September 7, 2017 . ... 10 Heating / Central Air Conditioning

(1) The filter is dirty and needs to be cleaned and/or replaced.

10.5 Item 1(Picture) Second level

(2) Please note: due to wall or floor coverings, insulation, roof framing or other obstructions, it was notpossible to observe the entire HVAC distribution system throughout this entire home. Damage to theducting can be present in a non-visible location. You may wish to have the HVAC distribution systemfurther explored by a licensed HVAC contractor before the end of your contingency period to determine ifany latent defects exist.

10.6 CHIMNEYS AND FLUES (for fireplaces)Repair or Replace(1) The fireplace is not equipped with a damper clamp as required by today's safety standards. They arerequired whenever gas is supplied to a fireplace to prevent the damper from closing completely. Irecommend installing a damper clamp as a safety upgrade.

10.6 Item 1(Picture)

(2) The liner was not fully inspected inspected by our company. It is recommended to have a qualifiedchimney sweep clean and inspect for safety.(3) The fireplace installed at one or more location appears to be a prefabricated system. We do notinspect the system for proper drafting and installation beyond what is visible from the firebox.Recommend having a safety check performed by a licensed fireplace contractor to ensure the fireplace isinstalled in accordance with the manufacturers specifications and is safe for continued operation.

10.7 GAS/LP FIRELOGS AND FIREPLACESRepair or Replace, Safety Concern

John Robinson's Inspection Group Ellis

5583 Vista San Simeon Page 40 of 58

Page 42: FAIRA TRANSPARENCY REPORTS 5583 Vista San Simeon, San Diego… · 2017-09-07 · 5583 Vista San Simeon, San Diego, CA 92154 . September 7, 2017 . ... 10 Heating / Central Air Conditioning

The gas pipe to the gas fireplace(s) is an aluminum type at one or more areas. This style connector wascommon at the time of installation but are now considered unsafe. Advise replacement by a qualifiedprofessional.

10.7 Item 1(Picture)

10.8 COOLING AND AIR HANDLER EQUIPMENTRepair or Replace(1) The A/C installed in this home is not original. Recommend asking the sellers for documentationshowing that this unit was installed by a licensed HVAC contractor per the manufactures installationrequirements. If documentation cannot be produced, I recommend this unit be further explored by alicensed HVAC contractor for safety.

10.8 Item 1(Picture) 10.8 Item 2(Picture)

John Robinson's Inspection Group Ellis

5583 Vista San Simeon Page 41 of 58

Page 43: FAIRA TRANSPARENCY REPORTS 5583 Vista San Simeon, San Diego… · 2017-09-07 · 5583 Vista San Simeon, San Diego, CA 92154 . September 7, 2017 . ... 10 Heating / Central Air Conditioning

(2) Condenser is not properly secured in one or more areas. Advise correcting and strapping by aqualified person.

10.8 Item 3(Picture)

(3) The AC primary condensation drain appeared to determinate at the master bathroom. I was unableto verify the condition of the entire span of the drain line due to wall cladding and other finishes. Youmay wish to have this further evaluated by a licensed HVAC contractor to determine if maintenance isneeded at this time.

10.8 Item 4(Picture)

10.9 NORMAL OPERATING CONTROLSInspected

10.10 PRESENCE OF INSTALLED COOLING SOURCE IN EACH ROOMInspected

The heating and cooling system of this home was inspected and reported on with the above information. While the inspector makesevery effort to find all areas of concern, some areas can go unnoticed. The inspection is not meant to be technically exhaustive.The inspection does not involve removal and inspection behind service door or dismantling that would otherwise reveal somethingonly a licensed heat contractor would discover. Please be aware that the inspector has your best interest in mind. Any repair itemsmentioned in this report should be considered before purchase. It is recommended that qualified contractors be used in yourfurther inspection or repair issues as it relates to the comments in this inspection report.

John Robinson's Inspection Group Ellis

5583 Vista San Simeon Page 42 of 58

Page 44: FAIRA TRANSPARENCY REPORTS 5583 Vista San Simeon, San Diego… · 2017-09-07 · 5583 Vista San Simeon, San Diego, CA 92154 . September 7, 2017 . ... 10 Heating / Central Air Conditioning

11. General Pictures

Items11.0 KITCHEN

InformationalKitchen

11.0 Item 1(Picture)

11.1 MASTER BATHROOMInformationalMaster Bathroom.

11.1 Item 1(Picture)

11.2 MASTER BEDROOMInformational

John Robinson's Inspection Group Ellis

5583 Vista San Simeon Page 43 of 58

Page 45: FAIRA TRANSPARENCY REPORTS 5583 Vista San Simeon, San Diego… · 2017-09-07 · 5583 Vista San Simeon, San Diego, CA 92154 . September 7, 2017 . ... 10 Heating / Central Air Conditioning

Master Bedroom.

11.2 Item 1(Picture)

11.3 HALL BATHROOMInformationalHall bathroom.

11.3 Item 1(Picture)

11.4 2ND BEDROOMInformational

John Robinson's Inspection Group Ellis

5583 Vista San Simeon Page 44 of 58

Page 46: FAIRA TRANSPARENCY REPORTS 5583 Vista San Simeon, San Diego… · 2017-09-07 · 5583 Vista San Simeon, San Diego, CA 92154 . September 7, 2017 . ... 10 Heating / Central Air Conditioning

2nd bedroom.

11.4 Item 1(Picture)

11.5 1/2 BATHROOMInformational1/2 bathroom.

11.5 Item 1(Picture)

11.6 3RD BEDROOMInformational

John Robinson's Inspection Group Ellis

5583 Vista San Simeon Page 45 of 58

Page 47: FAIRA TRANSPARENCY REPORTS 5583 Vista San Simeon, San Diego… · 2017-09-07 · 5583 Vista San Simeon, San Diego, CA 92154 . September 7, 2017 . ... 10 Heating / Central Air Conditioning

3rd bedroom.

11.6 Item 1(Picture)

11.7 LIVING ROOMInformationalLiving room.

11.7 Item 1(Picture)

11.8 DINING AREAInformational

John Robinson's Inspection Group Ellis

5583 Vista San Simeon Page 46 of 58

Page 48: FAIRA TRANSPARENCY REPORTS 5583 Vista San Simeon, San Diego… · 2017-09-07 · 5583 Vista San Simeon, San Diego, CA 92154 . September 7, 2017 . ... 10 Heating / Central Air Conditioning

Dining Area.

11.8 Item 1(Picture)

11.9 REAR YARDInformationalRear yard.

11.9 Item 1(Picture)

11.10 LAUNDRY ROOM/AREAInformational

John Robinson's Inspection Group Ellis

5583 Vista San Simeon Page 47 of 58

Page 49: FAIRA TRANSPARENCY REPORTS 5583 Vista San Simeon, San Diego… · 2017-09-07 · 5583 Vista San Simeon, San Diego, CA 92154 . September 7, 2017 . ... 10 Heating / Central Air Conditioning

Laundry room.

11.10 Item 1(Picture)

11.11 GARAGEInformationalGarage.

11.11 Item 1(Picture)

John Robinson's Inspection Group Ellis

5583 Vista San Simeon Page 48 of 58

Page 50: FAIRA TRANSPARENCY REPORTS 5583 Vista San Simeon, San Diego… · 2017-09-07 · 5583 Vista San Simeon, San Diego, CA 92154 . September 7, 2017 . ... 10 Heating / Central Air Conditioning

General Summary

John Robinson's Inspection Group

5291 Mount Burnham Dr. San Diego, CA 92111(619)684-1444 - www.jrinspections.com

[email protected]

CustomerChristopher Ellis

Address5583 Vista San SimeonSan Diego CA 92154

The following items or discoveries indicate that these systems or components do not function as intended or adversely affectsthe habitability of the dwelling; or warrants further investigation by a specialist, or requires subsequent observation.This summary shall not contain recommendations for routine upkeep of a system or component to keep it in proper functioningcondition or recommendations to upgrade or enhance the function or efficiency of the home. This Summary is not the entire report.The complete report may include additional information of concern to the customer. It is recommended that the customer read thecomplete report.

1. Built-In Kitchen Appliances

1.0 DISHWASHER

Repair or ReplaceWater draining at air gap observed during the draining cycle of the dish washer. This is possibleindication of a clogged/obscured dishwasher drain. Recommend repair/replace by a qualified/licensedprofessional.

1.1 RANGES AND COOKTOPS

Repair or Replace, Safety Concern(2) No anti-tip bracket was installed at the range. This bracket prevents the range from tippingforward, which could cause the range to fall over and/or spill hot food from pots and pans. The anti-tipbracket is a simple metal plate that holds the rear foot of the range to the floor. Recommendinstallation by a qualified person to prevent injury.

1.2 EXHAUST FAN/RANGE HOOD/DOWNDRAFT

Repair or ReplaceFlexible vent observed at exhaust fan/range hood. Recommend correcting and installing a ridged ventby a qualified/licensed professional.

John Robinson's Inspection Group Ellis

5583 Vista San Simeon Page 49 of 58

Page 51: FAIRA TRANSPARENCY REPORTS 5583 Vista San Simeon, San Diego… · 2017-09-07 · 5583 Vista San Simeon, San Diego, CA 92154 . September 7, 2017 . ... 10 Heating / Central Air Conditioning

2. Plumbing System

2.7 PLUMBING DRAIN, WASTE AND VENT SYSTEMS

Repair or Replace(1) Unconventional plumbing materials were noted in use below one or more sink(s). These flexibledrain lines are more prone to blockages due to their design and are typically not used by licensedplumbing contractors. I recommend replacing this drain line with an approved drain line by a licensedplumber.

2.8 WATER HEATERS, CONTROLS, CHIMNEYS, FLUES AND VENTS

Repair or Replace(1) The water heater was functioning at the time of inspection. However, it appears to be an older unit(10 years+), and repairs or even failure can be expected. You should consider replacing this waterheater as a preventive measure.(2) Leaking observed in a number of areas at the water heater water lines and TPR valve. Recommendcorrecting and advise repair and further review by a licensed plumbing contractor.(3) The gas line for the water heater is missing a drip leg or sediment trap. Advise installation by alicensed plumber.(4) Missing drip pan and drain line observed under the water heater. We advise installation by aqualified/licensed plumber.(5) An expansion tank is not installed at the water heater. Most water heater manufactures recommendan expansion tank be installed, whenever the water system is a "closed" system, such as this home.Advise further evaluation by a licensed plumber.

3. Interiors

3.0 INTERIOR GENERAL

InformationalLimited review of the interior due to restrictive clearances and a number of personal items. Pleasenote: Determining if damage, the presence of organic growths, moisture or wood rot behind wall, floorand ceiling coverings is beyond the scope of this inspection. If you are concerned or believe that theseconditions may exist in a nonvisible or concealed area, I recommend that you have this home furtherexamined by a qualified contractor or environmental hygienist.

3.3 DOORS (REPRESENTATIVE NUMBER)

Repair or ReplaceDoor(s) dose not latch properly in one or more areas. Advise correcting and maintenance as needed.

3.4 WINDOWS (REPRESENTATIVE NUMBER)

Repair or Replace(1) Slipped/damaged sash balance spring noted at master bathroom single hung window(s). Thiseffects the operation of the window and/or the window will not remain open. Advise further evaluationand repair by a licensed window contractor or qualified professional.(2) Window lock(s) are not functioning properly or are inoperable in one or more areas. Recommendcorrecting and advise repair by a qualified/licensed window contractor.(3) The window tracks and hardware need to be cleaned and/or serviced to function properly and/orsmoothly. Recommend further evaluation by a licensed window contractor.(4) One or more window screen is damaged, bent or missing. Advise repair or replacement as needed.

3.6 STEPS, STAIRWAYS, BALCONIES AND RAILINGS

Repair or Replace, Safety ConcernImproper sloping observed at the stairway steps in one or more areas. This is a potential fall hazard.Recommend correcting and advise further review by a licensed general contactor for any necessaryrepairs.

John Robinson's Inspection Group Ellis

5583 Vista San Simeon Page 50 of 58

Page 52: FAIRA TRANSPARENCY REPORTS 5583 Vista San Simeon, San Diego… · 2017-09-07 · 5583 Vista San Simeon, San Diego, CA 92154 . September 7, 2017 . ... 10 Heating / Central Air Conditioning

3.7 COUNTERS AND A REPRESENTATIVE NUMBER OF CABINETS

Repair or Replace(1) Back-splash is missing at the bathroom sink wall in one or more areas. Recommend correcting andadvise repair by a licensed professional.(2) Cracked/missing grout observed at counter/back-splash in one or more areas. Recommendcorrecting and advise repair by a qualified professional.(3) Advise caulking around the sinks/countertops. Where sealant is aged and or failing. Recommendcorrecting and advise repair by a licensed professional.(4) Moisture stains noted at the underside of the kitchen counter top. This area appeared dry at thetime of the inspection. Recommend further evaluation by a licensed termite inspector.

3.8 TUB/SHOWER ENCLOSURE

Repair or ReplaceGaps noted in one or more areas at the master bathroom shower glass door. Recommend correctingand advise repair by a licensed professional.

3.10 ROOM ADDITIONS/MODIFICATIONS

InformationalThis home has undergone major renovation, remodeling, and additions to the original structure. As itis beyond the scope of our inspection to verify the existence of permits, we advise obtaining this priorto the close of escrow.

4. Electrical System

4.1 MAIN AND DISTRIBUTION PANELS

Repair or Replace(1) The electrical panel appears to be mostly full. Space may not be available for the addition of morebreakers (if any). Advise consulting a licensed electrician for any future upgrades and/or any furtherinformation regarding the electrical panel/system.(2) Some labels are present, but illegible or confusing. Recommend correcting for safety reasons.

4.3 OVERCURRENT DEVICES (Circuit Breakers, Fuses) AND COMPATIBILITY OF THEIRAMPERAGE AND VOLTAGE

Repair or ReplaceUnconventional wiring observed at the main panel breaker in one or more areas. Conductive paste wasnoted missing at breaker multi strand wiring. Recommend correcting and further review by a qualified/licensed electrician.

4.6 CONNECTED DEVICES AND FIXTURES (Observed from a representative number operation ofceiling fans, lighting fixtures, switches and receptacles located inside the house, garage,and on the dwelling's exterior walls)

Repair or Replace, Safety Concern(1) Improper location of electrical outlet noted in the bathroom (installed next to tub/shower) at one ormore areas. This is a possible safety concern. Recommend relocating and advise repair by a qualifiedelectrician, prior to the close of escrow.(2) One or more light(s) is/are inoperable; possibly due to bulb. Advise replacing bulbs and checkingthe operation of these fixtures. If light fails to work, further evaluation by a licensed electrician isrecommended.

4.7 EXTERIOR LIGHTING (Patio lights, motion sensors)

Repair or Replace(1) I was unable to verify operation of one or more exterior light. Recommend asking the seller todemonstrate operation of the exterior lighting and have further evaluated by a licensed electricalcontractor to determine if corrections are needed at this time.

John Robinson's Inspection Group Ellis

5583 Vista San Simeon Page 51 of 58

Page 53: FAIRA TRANSPARENCY REPORTS 5583 Vista San Simeon, San Diego… · 2017-09-07 · 5583 Vista San Simeon, San Diego, CA 92154 . September 7, 2017 . ... 10 Heating / Central Air Conditioning

(2) Sensor lights were not tested. Recommend verifying operation and have further evaluation asnecessary.

5. Garage

5.6 OCCUPANT DOOR FROM GARAGE TO INSIDE HOME

Repair or Replace, Safety ConcernThe occupant door from the garage is not equipped with a self-closing device. For fire safety it isrecommended this door be self-closing/latching. Advise installing a self closing device.

7. Roofing

7.0 ROOF COVERINGS

Repair or ReplaceTile roof covering was inspected from the ground and attic to avoid damaging the roof covering, andpossibly voiding the warranty. This is in accordance with the CalNACHI standards of practice. The entireroof was not visible. I cannot guarantee that all of the tiles, flashings, and roof penetrations are in goodcondition. I recommend that you have the roof inspected by a licensed roof contractor if you areconcerned that there may be tiles that are broken or have slipped out of position.

8. Exterior

8.0 EXTERIOR GENERAL INFORMATION

InformationalThis home has undergone major renovation, remodeling, and additions to the original structure. As itis beyond the scope of our inspection to verify the existence of permits, we advise obtaining this priorto the close of escrow.

8.1 WALL CLADDING FLASHING AND TRIM

Repair or Replace(1) The sprinklers appear to be spraying the stucco in various areas of the exterior. This condition canlead to damaged stucco, rusted weep screed and lead to moisture intrusion. Recommend adjusting thesprinkler heads to spray away from the building to prevent further damage. You may also wish to havethe stucco further evaluated by a licensed stucco contractor to determine if any repairs are needed atthis time. Please note: Determining if damage exist behind the walls of the siding is outside the scopeof this inspection.(2) Moisture damaged stucco noted in areas. Recommend further evaluation and repair by a licensedstucco contractor.(3) Stucco cracks and deterioration noted in areas. These cracks may be prone to moisture intrusionissues. You may wish to view them for yourself and have repaired by a licensed contractor.

8.2 DOORS (Exterior)

Repair or Replace, Safety ConcernA double keyed dead bolt was noted present at one or more exterior door. This condition poses apotential emergency egress concern. Advise replacement with a standard thumb latch dead bolt by aqualified professional.

8.7 VEGETATION, GRADING, DRAINAGE, DRIVEWAYS, PATIO FLOOR, WALKWAYS ANDRETAINING WALLS (With respect to their effect on the condition of the building)

Repair or Replace(1) Low/neutral areas were observed at the grading which will cause water to pond during rain orextended irrigation. Standing water can be detrimental to the integrity of the foundation of the house.

John Robinson's Inspection Group Ellis

5583 Vista San Simeon Page 52 of 58

Page 54: FAIRA TRANSPARENCY REPORTS 5583 Vista San Simeon, San Diego… · 2017-09-07 · 5583 Vista San Simeon, San Diego, CA 92154 . September 7, 2017 . ... 10 Heating / Central Air Conditioning

It is important to prevent or minimize standing water around the house. This can be accomplished byproperly sloping the ground away from the house, or adding yard drains to carry water away from thelow lying areas. Rain gutters should also be installed and drained away from the house. Advisemonitoring during times of rain and making corrections as needed.(2) Typical settlement cracks noted in areas of the hardscape. Advise monitoring and repair whenneeded.

8.8 DECKS, BALCONIES, STOOPS, STEPS, AREAWAYS, PORCHES, PATIO/ COVER ANDAPPLICABLE RAILINGS

Repair or Replace, Safety ConcernLoose railing observed at the master bedroom balcony in one or more areas. This is a possible safetyconcern. Recommend correcting and advise repair by a licensed professional.

9. Structural Components

9.4 ROOF STRUCTURE AND ATTIC

Repair or ReplaceEngineered wood truss structure has been cracked/damaged in one or more areas. This roofingstructure is engineered for this home. Further evaluation and repair is recommended by a licensed/qualified structural contractor, prior to the close of escrow.

10. Heating / Central Air Conditioning

10.0 HEATING EQUIPMENT

Repair or Replace(2) The furnace gas piping is not equipped with a sediment trap or drip leg. Advise installation by alicensed plumber or qualified professional.

10.5 DISTRIBUTION SYSTEMS (including fans, pumps, ducts and piping, with supports,insulation, air filters, registers, radiators, fan coil units and convectors)

Repair or Replace(1) The filter is dirty and needs to be cleaned and/or replaced.

10.6 CHIMNEYS AND FLUES (for fireplaces)

Repair or Replace(1) The fireplace is not equipped with a damper clamp as required by today's safety standards. Theyare required whenever gas is supplied to a fireplace to prevent the damper from closing completely. Irecommend installing a damper clamp as a safety upgrade.(2) The liner was not fully inspected inspected by our company. It is recommended to have a qualifiedchimney sweep clean and inspect for safety.

10.7 GAS/LP FIRELOGS AND FIREPLACES

Repair or Replace, Safety ConcernThe gas pipe to the gas fireplace(s) is an aluminum type at one or more areas. This style connectorwas common at the time of installation but are now considered unsafe. Advise replacement by aqualified professional.

10.8 COOLING AND AIR HANDLER EQUIPMENT

Repair or Replace(2) Condenser is not properly secured in one or more areas. Advise correcting and strapping by aqualified person.

John Robinson's Inspection Group Ellis

5583 Vista San Simeon Page 53 of 58

Page 55: FAIRA TRANSPARENCY REPORTS 5583 Vista San Simeon, San Diego… · 2017-09-07 · 5583 Vista San Simeon, San Diego, CA 92154 . September 7, 2017 . ... 10 Heating / Central Air Conditioning

Home inspectors are not required to report on the following: Life expectancy of any component or system; The causes of the needfor a repair; The methods, materials, and costs of corrections; The suitability of the property for any specialized use; Complianceor non-compliance with codes, ordinances, statutes, regulatory requirements or restrictions; The market value of the property orits marketability; The advisability or inadvisability of purchase of the property; Any component or system that was not observed;The presence or absence of pests such as wood damaging organisms, rodents, or insects; or Cosmetic items, underground items,or items not permanently installed. Home inspectors are not required to: Offer warranties or guarantees of any kind; Calculate thestrength, adequacy, or efficiency of any system or component; Enter any area or perform any procedure that may damage theproperty or its components or be dangerous to the home inspector or other persons; Operate any system or component that isshut down or otherwise inoperable; Operate any system or component that does not respond to normal operating controls; Disturbinsulation, move personal items, panels, furniture, equipment, plant life, soil, snow, ice, or debris that obstructs access or visibility;Determine the presence or absence of any suspected adverse environmental condition or hazardous substance, including but notlimited to mold, toxins, carcinogens, noise, contaminants in the building or in soil, water, and air; Determine the effectiveness ofany system installed to control or remove suspected hazardous substances; Predict future condition, including but not limited tofailure of components; Since this report is provided for the specific benefit of the customer(s), secondary readers of thisinformation should hire a licensed inspector to perform an inspection to meet their specific needs and to obtain current informationconcerning this property.

Prepared Using HomeGauge http://www.HomeGauge.com : Licensed To Dallas Compton

John Robinson's Inspection Group Ellis

5583 Vista San Simeon Page 54 of 58

Page 56: FAIRA TRANSPARENCY REPORTS 5583 Vista San Simeon, San Diego… · 2017-09-07 · 5583 Vista San Simeon, San Diego, CA 92154 . September 7, 2017 . ... 10 Heating / Central Air Conditioning

INVOICE

John Robinson's Inspection Group5291 Mount Burnham Dr. San Diego, CA92111(619)684-1444 - [email protected] By: Dallas Compton

Inspection Date: 9/6/2017Report ID: 090617DC2

Customer Info: Inspection Property:

Christopher Ellis608 State Street South100CKirkland WA 98033

Customer's Real Estate Professional:Christopher EllisFaira.com Corp

5583 Vista San SimeonSan Diego CA 92154

Inspection Fee:Service Price Amount Sub-TotalInspection Fee 500.00 1 500.00

Tax $0.00Total Price $500.00

Payment Method:Payment Status:Note:

John Robinson's Inspection Group Ellis

5583 Vista San Simeon Page 55 of 58

Page 57: FAIRA TRANSPARENCY REPORTS 5583 Vista San Simeon, San Diego… · 2017-09-07 · 5583 Vista San Simeon, San Diego, CA 92154 . September 7, 2017 . ... 10 Heating / Central Air Conditioning

The address of the property is: 5583 Vista San Simeon San Diego CA 92154Fee for the home inspection is $500.00.

THIS IS A LEGALLY BINDING CONTRACT. PLEASE READ IT.

I/We (Client) hereby request a limited, visual, non-intrusive, non-destructive, non-technically exhaustive generalist inspection of thestructure at noted address to be conducted by John Robinson’s Inspection Group, (Company), for my/our sole use and benefit for the agreedupon fee of $500.00. I/We warrant that I/We will read the following agreement carefully. I/We understand that I/We are bound by all theterms of this contract. I/We further warrant that I/We will read the entire inspection report when I receive it and promptly call the inspectorwith any questions I/We may have.

SCOPE OF THE INSPECTION: The real estate inspection to be performed for Client is a limited, visual, non-invasive, non-destructive, non-technically exhaustive evaluation, performed for the fee set forth on the attached invoice, designed to identify material defects in thesystems, structures, and components of the above-referenced primary building and its associated primary parking structure as they existat the time of the inspection. A material defect is a condition that significantly affects the value, desirability, habitability or safety of thebuilding. Style or aesthetics shall not be considered in determining whether a specific system, structure, or component is defective. Theinspection shall be limited to those specific systems, structures, and components that are present and VISUALLY ACCESSIBLE at the dateand time of the inspection. Components and systems shall be operated with normal user controls only and as conditions permit. NO RETURNTRIPS ARE INCLUDED. RETURN TRIPS WILL BE BILLED AS A NEW INSPECTION.

The inspection will be performed in accordance with the Standards Practice setforth by the International Association of Certified HomeInspectors, available at our website (www.jrinspections.com) in effect at the time of this inspection. Inspector shall prepare a writteninspection report for the sole use and benefit of Client. The inspection report shall describe and identify the inspected systems, structures,and components of the building and identify material defects in those systems, structures, and components observable during theinspection, with the limitations defined below.

THIS INSPECTION IS A LIMITED, VISUAL, NON-DESTRUCTIVE, NON-INTRUSIVE, NON-TECHNICALLY EXHAUSTIVE EVALUATION OF THEABOVE-REFERENCED PRIMARY BUILDING AND ITS ASSOCIATED PRIMARY PARKING STRUCTURE. DEFECTS THAT ARE CONCEALED ARESPECIFICALLY DISCLAIMED. THIS INCLUDES DEFECTS THAT ARE CONCEALED IN THE WALLS, BEHIND WALL COVERINGS, UNDERFLOOR COVERINGS, CONCEALED WITH FRESH PAINT, SOIL, VEGETATION, OR OTHER LANDSCAPING. CLIENT UNDERSTANDS THATINSPECTOR WILL USE ALL TOOLS AT HIS DISPOSAL WITH CLIENT'S BEST INTEREST IN MIND, BUT THAT SOME CONCEALED DEFECTSMAY GO UNDETECTED. CLIENT AGREES TO HOLD JOHN ROBINSON'S INSPECTION GROUP AND IT'S REPRESENTATIVES HARMLESS IFCLIENT DISCOVERS CONCEALED DEFECTS THAT WERE UNDETECTED DURING THIS VISUAL, NON-DESTRUCTVE, NON-INTRUSIVE, NON-TECHNICALLY EXHAUSTIVE INSPECTION.

I have read and agree to the Scope of the Inspection: (Initial Here) ______/______

**Client agrees to read the entire inspection report when it is received and shall promptly call the inspector with any questions or concernsclient may have regarding the real estate inspection or the inspection report. **LIMITATIONS, EXCEPTIONS AND EXCLUSIONS: Excluded from this real estate inspection is any system, structure, or component of thebuilding which is inaccessible, concealed from view, or cannot be inspected due to circumstances beyond the control of Inspector, or whichClient has agreed is not to be inspected. In addition to concealed defects, the following are excluded from the scope of this real estateinspection unless specifically agreed to in writing:• Determining compliance with each manufacturers' specifications, researching building codes for the year built or modified, ordinances,regulations, covenants, or other restrictions (such as HOA rules), including local interpretations thereof.• Obtaining or reviewing information from any third-parties including, but not limited to: government agencies (such as permits), componentor system manufacturers (including product defects, recalls or similar notices, unless agreed to in writing), square footage, contractors,managers, sellers, occupants, neighbors, consultants, homeowner or similar associations, attorneys, agents or brokers. John Robinson'sInspection Group does not endores nor inspect unpermitted structures or additions and exclusively disclaims them from our inspection andinspection report.

John Robinson's Inspection Group Ellis

5583 Vista San Simeon Page 56 of 58

Page 58: FAIRA TRANSPARENCY REPORTS 5583 Vista San Simeon, San Diego… · 2017-09-07 · 5583 Vista San Simeon, San Diego, CA 92154 . September 7, 2017 . ... 10 Heating / Central Air Conditioning

• Geotechnical, engineering, structural, architectural, geological, hydrological, land surveying or soils-related examinations.• Examination of conditions related to animals, rodents, insects, wood-destroying insects, organisms, mold, and mildew or the damagecaused thereby. Mold determination is not part of this inspection. If evidence of unidentified stains is noted, a specialist should be consultedto determine type. Mold has been known to cause health risks.• Certain factors relating to any systems, structures, or components of the building, including, but not limited to: Recalls, adequacy,efficiency, durability or remaining useful life, costs to repair, replace or operate, fair market value, marketability, quality, or advisability ofpurchase.• Environmental hazards or conditions, including, but not limited to, toxic, reactive, combustible, corrosive contaminants, wildfire, geologicor flood.• Dismantling of any system, structure, or component, or perform any intrusive or destructive examination, test or analysis. Home Inspectoris limited to evaluating components from standard service or access covers.• Examining or evaluating fire-resistive qualities of any system, structure or component of the building.• Systems, structures, or components of the building, which are not permanently installed (such as refrigerators, window AC, etc).• Systems, structures, or components that are not part of the main house, unless specifically identified in the written inspection report.• Common areas, or systems, structures, or components thereof, including, but not limited to, those of a common interest (HOA).• Examining or evaluating the acoustical or other nuisance characteristics of any system, structure, or component of a building, complex,adjoining properties, or neighborhood.• Operating or evaluating low voltage electrical, antennas, security systems, cable or satellite television, telephone, remote controls, radiocontrols, timers, intercoms, computers, computer networks, photo-electric, motion sensing, or other such similar non-primary electricalpower devices, components, or systems.• Evaluation of any pool, spa, barn, fence, irrigation system, or structures other than the main building unless agreed to in writing.• Examining or operating any sewage disposal system or component including, but not limited to: septic tanks and/or any undergroundsystem or portion thereof, or ejector pumps for rain or waste.• Environmental evaluation and inspection. The building inspection is not intended to determine the presence of lead, radon, mold, PCB’s,mildew, urea- formaldehyde, asbestos, sulfur, contaminated drywall, Chinese drywall, or other toxins in the building, ground, water or air.Services for inspecting or evaluating the excluded items listed above may be available from Company for an additional fee or from 3rd partyspecialists qualified to inspect or evaluate a particular category or item.Inspector is a home inspection generalist and is not acting as an expert in any craft or trade. The inspection report may containrecommendations for further evaluation by an individual other than Inspector herein who is qualified as an expert or specialist. If Inspectorrecommends contacting other specialized experts, Client agrees to do so at their own expense before the end of his/her contingecy period.Inspector is not responsible and will be held harmless for Client's failure to follow further evaluation recommendations.

I have read and agree to the Exceptions and Exclusions: (Initial Here) ______/_____

It is Client's duty and obligation to exercise reasonable care to protect him or herself regarding the condition of the subject property,including those facts which are known to or within the diligent attention and observation of Client. Client agrees to act on therecommendations of the inspector.CONFIDENTIAL REPORT: The inspection report to be prepared for Client is solely and exclusively for Client's own information and may notbe relied upon by any other person. Client agrees to maintain the confidentiality of the inspection report and agrees not to disclose anypart of it to any other person. Client may distribute copies of the inspection report to the seller and the real estate agents directly involvedin this transaction, but Client and Company do not in any way intend to benefit said seller or the real estate agents directly or indirectlythrough this Agreement or the inspection report. CLIENT AGREES TO INDEMNIFY, DEFEND AND HOLD INSPECTOR HARMLESS FROM ANYTHIRD PARTY CLAIMS ARISING OUT OF CLIENT'S UNAUTHORIZED DISTRIBUTION OF THE INSPECTION REPORT.SEVERABILITY: Should any provision of this contract be held by a court of competent jurisdiction to be either invalid or unenforceable, theremaining provisions of this contract shall remain in full force and effect, unimpaired by the court’s holding.ARBITRATION: Any dispute concerning the interpretation of this Agreement or arising from this inspection and report, except one forpayment of inspection fee, shall be resolved between the parties by BINDING ARBITRATION conducted in accordance with the rules of theAmerican Arbitration Association except that the parties shall select an arbitrator who is familiar with the Home Inspection industry andstandards of practice. The parties hereto shall be entitled to all discovery rights and legal motions as provided in the California Code of CivilProcedure. The arbitrator shall apply the substantive and procedural laws of the State of California to all issues submitted in the arbitrationproceeding. The award of the arbitrator shall be final, and a judgment may be entered on it by any court having jurisdiction.GENERAL PROVISIONS: This inspection contract, the real estate inspection, and the inspection report do not constitute a home warranty,guarantee, or insurance policy of any kind whatsoever. The real estate inspection and inspection report are not a substitute disclosurefor real estate transactions, which may be required by law. No legal action or proceeding of any kind, including those sounding in tort orcontract, can be commenced against Inspector/Inspection Company, or its officers, agents or employees more than one year after the dateof the subject inspection. Time is expressly of the essence herein. THIS TIME PERIOD IS SHORTER THAN OTHERWISE PROVIDED BY LAW.LIABILITY LIMITS: Client agrees that Company's liability arising from any and all disputes, claims of negligence or non-performance underthe obligations defined in this contract, shall be limited to no more than THREE times the inspection fee paid by client for the inspectionservice.In the event Client discovers a material defect or other deficiency that was not identified and reported by Inspector, Client shall immediatelynotify Inspection Company in writing and allow Company and/or Company's designated representative to re-inspect and document thecondition(s) of the material defect or deficiency prior to making any repair, alteration or replacement to said material defect or deficiency.Client agrees to hold Company harmless if client fails to inform the Inspection Company prior to performing repairs.The written report to be prepared by Inspector shall be considered the final and exclusive findings of the Inspector regarding the inspectionof the property. Client shall not rely on any oral statements made by the Inspector prior to issuance of the written report. This Agreementshall be binding upon and inure to the benefit of the parties hereto and their heirs, successors and assigns.This agreement constitutes the entire integrated agreement between the parties hereto pertaining to the subject matter hereof, and maybe modified only by a written agreement signed by all of the parties hereto. No oral agreements, understandings, or representations shallchange, modify, or amend any part of this agreement.Each party signing this Agreement warrants and represents that he/she has the full capacity and authority to execute this Agreementon behalf of the named party. If this Agreement is executed on behalf of Client by any third party, the person executing this Agreementexpressly represents to Company that he/she has the full and complete authority to execute this Agreement on Client's behalf and to fully

John Robinson's Inspection Group Ellis

5583 Vista San Simeon Page 57 of 58

Page 59: FAIRA TRANSPARENCY REPORTS 5583 Vista San Simeon, San Diego… · 2017-09-07 · 5583 Vista San Simeon, San Diego, CA 92154 . September 7, 2017 . ... 10 Heating / Central Air Conditioning

and completely bind Client to all of the terms, conditions, limitations, exceptions and exclusions of this Agreement. A 24-hour cancellationnotice is requested. Inspections cancelled within 24 hours will be charge a $150 cancellation fee. Inspections terminated onsite due toabsence of utility service will be billed the entire inspection fee.I have read this entire agreement, and I understand and agree to be bound by the terms of this contract. THIS AGREEMENT CONTAINSA BINDING ARBITRATION PROVISION WHICH MAY BE ENFORCED BY EITHER PARTY. I am aware that this is a limitation of liability and acontract between me and John Robinson’s Inspection Group. In the event of refund of the fees charged, such refund shall be accepted by theundersigned as full and final settlement of all claims and causes of action against Company and/or inspector as agreed herein. Acceptanceof this report constitutes acceptance of all contractual terms herein.

Client Signature________________________________________________Date_____________

Print Client's First and Last Name___________________________________________________

2nd Client Signature_____________________________________________Date_____________

Print 2nd Client's First and Last Name________________________________________________

Inspector Signature______________________________________________Date____________

Report ID: 090617DC2

John Robinson's Inspection Group Ellis

5583 Vista San Simeon Page 58 of 58