Steam Systems Basics, Challenges and

Troubleshooting

John Cilyo

Senior Account Executive Spirax Sarco Inc.

For Steve Jalowiec, PE, CHFM

Page 2: Fall2011 jalowiec

Steam Systems & Chaos Theory

In mathematics, chaos theory describes the behavior of certain dynamic systems – that is, systems whose states evolve with time – that may exhibit dynamics that are highly sensitive to initial conditions (popularly referred to as the butterfly effect). As a result of this sensitivity, which manifests itself as an exponential growth of perturbations in the initial conditions, the behavior of chaotic systems appears to be random. This happens even though these systems are deterministic, meaning that their future dynamics are fully defined by their initial conditions with no random elements involved. This behavior is known as deterministic chaos, or simply chaos.

Page 3: Fall2011 jalowiec

Steam Systems & the 2nd Law

Second Law of Thermodynamics• The entropy of an isolated system not in equilibrium

will tend to increase over time, approaching a maximum value at equilibrium.

• In a simple manner, the second law states "energy systems have a tendency to increase their entropy rather than decrease it." This can also be stated as "heat can spontaneously flow from a higher-temperature region to a lower-temperature region, but not the other way around." (Heat can flow from cold to hot, but not spontaneously—- for example, when a refrigerator expends electrical power.)

• A way of thinking about the second law for non-scientists is to consider entropy as a measure of disorder. So, for example, a broken cup has less order (more entropy) than an intact one, and it is more difficult to repair a broken cup (reducing its entropy) than to break an intact one (increasing its entropy). Likewise, solid crystals, the most organized form of matter, have very low entropy values; and gases, which are very disorganized, have high entropy values.

Page 4: Fall2011 jalowiec

Basic Steam System

Page 5: Fall2011 jalowiec

Another view of a Steam System

BOILER

Steam Header

Condensate ReturnPiping

LoadsRadiators, SterilizersHeat Exchangers, etc

Condensate Return Tank

Deaerator

(Treated) Make up water

Steam Traps

Page 6: Fall2011 jalowiec

Steam System Basics• Boiler Design

• Water Tube, smaller steam space, need to be run closer to design pressure

• Fire Tube, large steam chest, can be run a lower than design pressure.

• Definitions• "Carryover" means that you have a problem with the TDS (total

dissolved solids). You need to properly define the PPM values needed. Fire tube boilers have a normal TDS of 3000 ppm, while water tube designs need 2000 ppm. Everyone uses the 3000 ppm value regardless of boiler type and that is their first mistake.

• "Priming" is a mechanical condition caused by too great of a takeoff velocity (50 to 100fpm).This is corrected mechanically.

• Testing• With the boiler running, take a condensate sample from a drip pocket on

the main header. If you see a high TDS value (say 2000 PPM), you have a carryover issue. If your value is 5 ppm or is immeasurable, you have priming. Remember, steam has no TDS!

Page 7: Fall2011 jalowiec

Steam systems have many end uses in hospitals; radiators, heat exchangers,

humidification but probably none as critical as Steam Sterilizers

Page 8: Fall2011 jalowiec

Your Objectives(Challenges)

•Deliver good quality steam to heating, humidification and process equipment.

•Operate the system safely.

•Get maximum efficiency from heating equipment - energy $$$

•Maintain the system at a reasonable cost.

Page 9: Fall2011 jalowiec

Steam Has Another Objective In Mind!

(Challenges)•Condenses anywhere and everywhere

it can.

•Happily fills the system with air, in the worst possible locations.

•Carries entrained water, gases, chemicals and dirt into every nook and cranny.

•Will slow down and stop flowing as soon as differential pressure is lost.

Page 10: Fall2011 jalowiec

Your Mission Is To Stay Ahead of Potential Problems

(Challenges)

• Test/maintain steam traps routinely.• Clean strainers!• Clean and maintain regulators/control valves• Routine maintenance of condensate pumps.• Keep an ear open for excess pipe-line water-

hammer & correct the root-cause.• Watch for repeat instances of valve wire-draw

& correct root-cause (wet steam, valve sizing)• Recognize that water hammer in heat

exchangers and heating coils is correctable.

Page 11: Fall2011 jalowiec

No problem – right?All it takes is money and

manpower!Anyone here have enough of both?

But there is help:•Boiler Water Treatment Company

•Steam Specialty Companies

•Steam Consultants

•Some of these can help for free, some will cost.

Challenges

Page 12: Fall2011 jalowiec

Steam System Challenges• Remember Steam Systems are dynamic systems

• Never Steady State• Loads coming on and off

• Sterilizers

• Heating coils

• Steam Absorption Chillers

• Manual Building Heat (Old fashion radiators)

• System Sizing• Sized for steady state or instantaneous loads

(sterilizers)

Page 13: Fall2011 jalowiec

Steam System Troubleshooting

Myths• My boilers never carry over, prime, etc.• The water level is always steady in the gauge

glass.• I don’t need trap maintenance, failed traps

will become apparent on their own. (The water hammer will tell me about a bad trap.)

• Boiler water treatment is a scam.• Boiler blow-down wastes energy and water.

Page 14: Fall2011 jalowiec

Steam System TroubleshootingSteam System Chemistry

• Feed Water Quality•Softener•Deaerator

– Dissolved O2 and non-condensable gases

•Chemical Treatment• Totaled Dissolved Solids (TDS)

•Blow down• Continuous Surface• Bottom Blow Down

Page 15: Fall2011 jalowiec

Test TypicalLimitsLow/Hi

Softener Feedwater Boiler Condensate Return

Deaerator

pH See chart > 8.5 8.3 – 9.4

Sulfite % So2(Higher in lay-up)

30/60 XX XX

Alkalinity P 200/400 XX

Alkalinity M 250/500

Silica Monitor trends

< 150 mg/L

XX XX

Conductivity 3000/3500 XX XX XX

Calcium < 0.3/FW XX XX XX

Iron < 0.1/FW XX XX

Copper < 0.05/FW XX XX

PrimaryTreatment Chem.

Permfg

XX

Dissolved O2 7 ppb XX

Typical Steam System Chemistry

(May vary with chemical supplier and boiler manufacturer)

Page 16: Fall2011 jalowiec

Status Polytreat

TL-200

Sulfite

as SO3

Alkalinity

P M

pH

Silica Conductivity Calcium Iron Copper

Boiler 2 Lead 18.5 110 370 510 - 77.6 2886(N) -

Boiler 3 Open - - - - - - - -

Softener 2 6.0 129 0.17

Pwr. Plnt. cond. 8.60 45 0.05 0.03 0.03

MR1 cond. - - - - -

Kitchen Dish.

condensate

- - -

Sub base. large - - -

Feedwater 3.6 8.35 2.2 72 0.26 0.10 0.03

Recommended Low/ High Limits

__10__

20

_30_

60

_200

_ 400

_250

_ 500

_8.0_

8.5

Record

__3000__

3500

_< .3_

FW

_< .1_

FW

_< .05_

FW

Courtesy of Barclay Water Management, Inc.

Typical Boiler Water Treatment Test Report (partial)

Page 17: Fall2011 jalowiec

Steam System Troubleshooting• Water Level Control

• Sight glass levels are not reliable• Variable feed versus on/off

• Steam Flow Metering & Data• Data is invaluable for system troubleshooting

You cannot manage what you cannot measure”

Lord Kelvin

Page 18: Fall2011 jalowiec

Why is proper condensate drainage important?

Page 19: Fall2011 jalowiec

Water hammer!

Result of a drip trap being removed, that was draining a 100 psig line, before a valve

Page 20: Fall2011 jalowiec

Steam System Troubleshooting•Steam Traps

•Properly located

•Drip Legs properly sized

•Trap Selection and sizing

•Steam Trap Testing & Maintenance

Page 21: Fall2011 jalowiec

Steam System Troubleshooting• Steam Traps

• Main Header Main header drip legs are full size

• Other drip legs are properly sized• Drips located 300’ or less and any change of

elevation• Drip stations located ahead of automatic

valves• Steam traps are properly sized• Steam traps are working and maintained• Missing insulation

• heat goes to cold• another consequence of the 2nd law thermodynamics!

Page 22: Fall2011 jalowiec
Page 23: Fall2011 jalowiec

Ineffective vs Proper Drain Ineffective vs Proper Drain PointsPoints

Condensate

Steam Trap SetFull

Diameter Pocket

Cross Section

Cross Section

Steam Trap Set

Steam Flow

Steam Flow

CorrectCorrect

IncorrectIncorrect

Page 24: Fall2011 jalowiec

Steam System Troubleshooting

Steam Trap Testing• Visual *

• Temperature **

• Ultrasonic ***

• Continuous monitoring systems ****• conductivity

Page 25: Fall2011 jalowiec

Steam System Troubleshooting•Belts & suspenders

• Steam separators & filters

Wet Steam

Dry Steam

Condensate Outlet

Page 26: Fall2011 jalowiec

Example: Process requires 4,645,000 Btu’s / hr

Available: 30 psig steam @ 274oF

@ 100% Dry (saturated) steam supplies 929 Btu / lb. process requires 5,000 lb/hr.

@ 90% Dryness Fraction, steam supplies 836 Btu/lb. process now requires 5556 lb /hr. A 11% Increase

@ 80% Dryness Fraction, steam supplies 743 Btu/lb process now requires 6251 lb /hr. A 25% increase

Steam Conditioning Dry Steam saves energy

Page 27: Fall2011 jalowiec

Steam System Troubleshooting

•Condensate equipment operating properly• Pumps• Flash tanks

•Loads• Varying loads• Instantaneous loads - Sterilizers

Page 28: Fall2011 jalowiec

Steam System Troubleshooting Now what do I do

If you suddenly have problems• What has changed?• Go back to basics

•Start at the boiler plant and work your way out into the system

•Left Hand Analysis

Page 29: Fall2011 jalowiec

Courtesy of Walt Graham Thermo Diagnostics, Co, LLC

Page 30: Fall2011 jalowiec

Now what do I do

• Steam Trap Repairs• Steam Trap Survey & Assessment• Steam Trap Maintenance Program• Boiler Water Treatment Modification• Steam Conditioning Equipment

• Separators• Filters

• Repair damaged insulation• Steam Metering (for troubleshooting)