fam 10 fam 10/15 - hydac.com · fam 10 fam 10/15. fluidaqua mobil operating and maintenance...

68
FAM 10 FAM 10/15 FluidAqua Mobil Operating and maintenance instructions, part 1/2 English (translation of original instructions) Keep for future reference. Document No.: 4170099 (Valid for FAM-xx-x-x-x-xx-x-C-x-x)

Upload: vuliem

Post on 23-Jan-2019

234 views

Category:

Documents


1 download

TRANSCRIPT

Page 1: FAM 10 FAM 10/15 - hydac.com · FAM 10 FAM 10/15. FluidAqua Mobil Operating and maintenance instructions, ... HRB 1 7216 Executive director: Mathias Dieter, Dipl.Kfm. Wolfgang Haering

FAM 10 FAM 10/15

FluidAqua Mobil Operating and maintenance instructions,

part 1/2 English (translation of original instructions)

Keep for future reference.

Document No.: 4170099 (Valid for FAM-xx-x-x-x-xx-x-C-x-x)

Page 2: FAM 10 FAM 10/15 - hydac.com · FAM 10 FAM 10/15. FluidAqua Mobil Operating and maintenance instructions, ... HRB 1 7216 Executive director: Mathias Dieter, Dipl.Kfm. Wolfgang Haering

Imprint

Imprint

Publisher and responsible for the content: HYDAC FILTER SYSTEMS GMBH Postfach 1251 66273 Sulzbach / Saarland Germany Phone: +49 6897 509 01 Fax: +49 6897 509 846 E-mail: [email protected] Homepage: www.hydac.com Court of Registration: Saarbrücken, HRB 17216 Executive director: Mathias Dieter, Dipl.Kfm. Wolfgang

Haering

Documentation Representative

Mr. Günter Harge c/o HYDAC International GmbH, Industriegebiet, 66280 Sulzbach / Saar Phone: +49 6897 509 1511 Fax: +49 6897 509 1394 E-mail: [email protected]

© HYDAC FILTER SYSTEMS GMBH

All rights reserved. No part of this work may be reproduced in any form (print, photocopy or by other means) or processed, duplicated or distributed using electronic systems without the written consent of the publisher. These documents have been created and inspected with the greatest care. However, errors cannot be ruled out completely. All details are subject to technical modifications. The content of this manual is subject to change without notice.

FAM 10, Instructions, part 1/2 en(us) Page 2 / 68

BEWA FAM10-15 1-2 4170099 en-us 2016-10-18.doc 2016-10-18

Page 3: FAM 10 FAM 10/15 - hydac.com · FAM 10 FAM 10/15. FluidAqua Mobil Operating and maintenance instructions, ... HRB 1 7216 Executive director: Mathias Dieter, Dipl.Kfm. Wolfgang Haering

Content

Content

Imprint ............................................................................................................ 2

Documentation Representative ................................................................... 2

Content .......................................................................................................... 3

Preface ........................................................................................................... 6

Technical Support ........................................................................................ 6

Product modification .................................................................................... 6

Warranty ...................................................................................................... 6

Using the documentation ............................................................................. 7

Safety information ........................................................................................ 8

Hazard symbols ........................................................................................... 8

Signal words and their meaning in the safety information and instructions .................................................................................................. 9

Structure of the safety information and instructions ................................... 10

Observe regulatory information ................................................................. 10

Proper/Designated Use ............................................................................. 11

Improper Use or Use Deviating from Intended Use ................................... 12

Qualifications of personnel / target group .................................................. 13

Wear suitable clothing ............................................................................... 15

Stoppage in an emergency (EMERGENCY STOP) ................................... 15

Unpacking the unit ...................................................................................... 15

Transporting the unit .................................................................................. 16

Transporting with the fork lift truck ............................................................. 16

Transporting with the crane ....................................................................... 17

Transporting by train / truck ....................................................................... 17

Checking the scope of delivery ................................................................. 18

Description of unit ...................................................................................... 19

Unit versions .............................................................................................. 19

Technical specifications ............................................................................. 20

Function description .................................................................................. 21

Cleaning in Bypass Flow ........................................................................... 23

Purifying and transferring by pumping ....................................................... 23

Unit system components ........................................................................... 24

FAM 10, Instructions, part 1/2 en(us) Page 3 / 68

BEWA FAM10-15 1-2 4170099 en-us 2016-10-18.doc 2016-10-18

Page 4: FAM 10 FAM 10/15 - hydac.com · FAM 10 FAM 10/15. FluidAqua Mobil Operating and maintenance instructions, ... HRB 1 7216 Executive director: Mathias Dieter, Dipl.Kfm. Wolfgang Haering

Content

Unit dimensions .......................................................................................... 26

Stationary version ...................................................................................... 26

Mobile version ........................................................................................... 27

Hydraulic circuit .......................................................................................... 28

Unit setup and connection ......................................................................... 30

Setting up the unit ...................................................................................... 30

Connection overview ................................................................................. 31

Notes on pipes and hoses ......................................................................... 32

Connecting the inlet (IN) ......................................................................... 34

Connect outlet (OUT) ............................................................................. 34

Preparing the Vacuum Pump ..................................................................... 35

Filling up the rotary vane vacuum pump ............................................. 36

Electrical connection of the FAM ............................................................... 37

Checking the direction of rotation of the electric motors ......................... 38

Operating elements on the FAM ................................................................ 39

Switching on / switching off / commissioning and error messages ...... 40

Performing maintenance ............................................................................ 41

Function testing of the fault indicator lamp ................................................ 43

Change Air filter ......................................................................................... 43

Checking the AquaSensor ......................................................................... 43

Clean the suction screen ........................................................................... 45

Rotary vane vacuum pump components ................................................... 46

Performing an oil change ....................................................................... 47

Replacing the Air De-oiling Element ....................................................... 48

Replacing the filter element on the fluid filter ............................................. 49

Testing the Float Switch in the Oil Pan ...................................................... 54

Check the safety thermostat on the heater ................................................ 55

Reset safety thermostat on the heater ....................................................... 56

Checking the settings on the heater (optional) .......................................... 56

Spare parts .................................................................................................. 57

FAM 10 ...................................................................................................... 57

Fluid filter (OLF 5) ...................................................................................... 57

Rotary vane vacuum pump ........................................................................ 58

Taking the unit out of operation ................................................................ 58

Disposing of the unit .................................................................................. 58

FAM 10, Instructions, part 1/2 en(us) Page 4 / 68

BEWA FAM10-15 1-2 4170099 en-us 2016-10-18.doc 2016-10-18

Page 5: FAM 10 FAM 10/15 - hydac.com · FAM 10 FAM 10/15. FluidAqua Mobil Operating and maintenance instructions, ... HRB 1 7216 Executive director: Mathias Dieter, Dipl.Kfm. Wolfgang Haering

Content

Technical Data............................................................................................. 59

Attachment .................................................................................................. 61

Contact Customer Service / Service .......................................................... 61

Model Code ............................................................................................... 62

Explanation of terms and abbreviations ..................................................... 63

Index .......................................................................................................... 66

FAM 10, Instructions, part 1/2 en(us) Page 5 / 68

BEWA FAM10-15 1-2 4170099 en-us 2016-10-18.doc 2016-10-18

Page 6: FAM 10 FAM 10/15 - hydac.com · FAM 10 FAM 10/15. FluidAqua Mobil Operating and maintenance instructions, ... HRB 1 7216 Executive director: Mathias Dieter, Dipl.Kfm. Wolfgang Haering

Preface

Preface

These operation and maintenance instructions were made to the best of our knowledge. Nevertheless and despite the greatest care, it cannot be excluded that mistakes could have crept in. Therefore please understand that, in the absence of any provisions to the contrary hereinafter, our warranty and liability – for any legal reasons whatsoever – are excluded in respect of the information in these operating instructions. In particular, we shall not be liable for lost profit or other financial loss. This exclusion of liability does not apply in cases of intent and gross negligence. Moreover, it does not apply to defects which have been deceitfully concealed or whose absence has been guaranteed, nor in cases of culpable harm to life, physical injury and damage to health. If we negligently breach any material contractual obligation, our liability shall be limited to foreseeable damage. Claims due to Product Liability shall remain unaffected.

Technical Support Contact our technical sales department if you have any questions on our product. When contacting us, please always include the model code, serial no. and part no. of the product: Fax: +49 6897 509 9046 E-mail: [email protected]

Product modification We would like to point out that changes to the product (e.g. purchasing options, etc.) may result in the information in the operating instructions no longer being completely accurate or sufficient. After modification or repair work that affects the safety of the product has been carried out on components, the product may not be returned to operation until it has been checked and released by a HYDAC technician. Please notify us immediately of any modifications made to the product whether by you or a third party.

Warranty For the warranty provided by us, please refer to the General Terms of Sale and Delivery of HYDAC FILTER SYSTEMS GMBH. You will find these under www.hydac.com -> General terms and conditions.

FAM 10, Instructions, part 1/2 en(us) Page 6 / 68

BEWA FAM10-15 1-2 4170099 en-us 2016-10-18.doc 2016-10-18

Page 7: FAM 10 FAM 10/15 - hydac.com · FAM 10 FAM 10/15. FluidAqua Mobil Operating and maintenance instructions, ... HRB 1 7216 Executive director: Mathias Dieter, Dipl.Kfm. Wolfgang Haering

Preface

Using the documentation

Note that the method described for locating specific information does not release you from your responsibility of carefully reading all these instructions prior to starting the unit up for the first time and at regular intervals in the future.

What do I want to know? I determine which topic I am looking for. WHERE can I find the information I’m looking for? The documentation has a table of contents at the beginning. There, I select the chapter I'm looking for and the corresponding page number.

deHYDAC Filtertechnik GmbHBeWa 123456a de

Seite x

Produkt / Kapitel

200x-xx-xx

The documentation number with its index enables you to order another copy of the operating and maintenance instructions. The index is incremented every time the manual is revised or changed.

Chapter description

Page number Edition date

Document language

Documentation No. with Index /

File name

FAM 10, Instructions, part 1/2 en(us) Page 7 / 68

BEWA FAM10-15 1-2 4170099 en-us 2016-10-18.doc 2016-10-18

Page 8: FAM 10 FAM 10/15 - hydac.com · FAM 10 FAM 10/15. FluidAqua Mobil Operating and maintenance instructions, ... HRB 1 7216 Executive director: Mathias Dieter, Dipl.Kfm. Wolfgang Haering

Safety information

Safety information

The unit was built according to the statutory provisions valid at the time of delivery and satisfies current safety requirements. Any residual hazards are indicated by safety information and instructions and are described in the operating instructions. Observe all safety and warning instructions attached to the unit. They must always be complete and legible. Do not operate the unit unless all the safety devices are present. Secure the hazardous areas which may arise between the unit and other equipment. Maintain the unit inspection intervals prescribed by law. Document the results in an inspection certificate and keep it until the next inspection.

Hazard symbols These symbols are listed for all safety information and instructions in these operating instructions which indicate particular hazards to persons, property or the environment. Observe these instructions and act with particular caution in such cases. Pass all safety information and instructions on to other users.

General hazard

Danger due to electrical voltage / current

Exposed electrical components Danger of electrical shock

Danger due to operating pressure

FAM 10, Instructions, part 1/2 en(us) Page 8 / 68

BEWA FAM10-15 1-2 4170099 en-us 2016-10-18.doc 2016-10-18

Page 9: FAM 10 FAM 10/15 - hydac.com · FAM 10 FAM 10/15. FluidAqua Mobil Operating and maintenance instructions, ... HRB 1 7216 Executive director: Mathias Dieter, Dipl.Kfm. Wolfgang Haering

Safety information

Risk of burns due to hot surfaces

Substances that are health hazards or irritants

Signal words and their meaning in the safety information and instructions

In these instructions you will find the following signal words:

DANGER DANGER – The signal word indicates a hazardous situation with a high level of risk, which, if not avoided, will result lethal or serious injury.

WARNING WARNING – The signal word indicates a hazardous situation with a medium level of risk, which, if not avoided, can result lethal or serious injury.

CAUTION CAUTION – The signal word indicates a hazardous situation with a low level of risk, which, if not avoided, can result in minor or moderate injury.

NOTICE NOTICE – The signal word indicates a hazardous situation with a high level of risk, which, if not avoided, will result in damage to property.

FAM 10, Instructions, part 1/2 en(us) Page 9 / 68

BEWA FAM10-15 1-2 4170099 en-us 2016-10-18.doc 2016-10-18

Page 10: FAM 10 FAM 10/15 - hydac.com · FAM 10 FAM 10/15. FluidAqua Mobil Operating and maintenance instructions, ... HRB 1 7216 Executive director: Mathias Dieter, Dipl.Kfm. Wolfgang Haering

Safety information

Structure of the safety information and instructions All warning instructions in this manual are highlighted with pictograms and signal words. The pictogram and the signal word indicate the severity of the danger. Warning instructions listed before an activity are laid out as follows:

HAZARD SYMBOL

SIGNAL WORD Type and source of danger

Consequence of the danger

► Measures to avert danger

Observe regulatory information Observe the following regulatory information and guidelines:

• Legal and local regulations for accident prevention.

• Legal and local regulations for environmental protection.

• Country-specific regulations, organization-specific regulations.

FAM 10, Instructions, part 1/2 en(us) Page 10 / 68

BEWA FAM10-15 1-2 4170099 en-us 2016-10-18.doc 2016-10-18

Page 11: FAM 10 FAM 10/15 - hydac.com · FAM 10 FAM 10/15. FluidAqua Mobil Operating and maintenance instructions, ... HRB 1 7216 Executive director: Mathias Dieter, Dipl.Kfm. Wolfgang Haering

Safety information

Proper/Designated Use Use the unit only for the application described in the following. The FAM is for dewatering, filtering and degassing hydraulic and lubricating oils. In addition, it removes free water, emulsified water and a large percentage of the water found in solution. Proper or designated use of the product extends to the following:

• Observing all instructions contained in the instruction manual.

• performing inspection and maintenance work. Depending on the version (see model code), the FAM may only be used for the following media (see model code): FAM-xx-M-… FAM-xx-I-…

Mineral oils acc. to DIN 50524 Gear oils acc. to DIN 51517, 51524 Other hydraulic and lubrication oils which require or are compatible with NBR seals

FAM-xx-B-… Synthetic esters (HEES) DIN 51524/2 Vegetable oils (HETG, HTG) Hydraulic and lubrication oils which require or are compatible with Viton seals.

FAM-xx-X-… HFD fluids (not for pure phosphate esters which require EPDM seals).

FAM 10, Instructions, part 1/2 en(us) Page 11 / 68

BEWA FAM10-15 1-2 4170099 en-us 2016-10-18.doc 2016-10-18

Page 12: FAM 10 FAM 10/15 - hydac.com · FAM 10 FAM 10/15. FluidAqua Mobil Operating and maintenance instructions, ... HRB 1 7216 Executive director: Mathias Dieter, Dipl.Kfm. Wolfgang Haering

Safety information

Improper Use or Use Deviating from Intended Use

DANGER Danger due to unanticipated use of the unit

Bodily injury and damage to property will result when operated improperly.

► Never operate the unit in potentially explosive atmospheres.

► The unit is only to be used with permissible media.

NOTICE

Impermissible operating conditions

The unit will be damaged

► The unit is only to be used with permissible media.

Any use extending beyond this or deviating therefrom shall not be considered intended use. HYDAC Filter Systems GmbH will assume no liability for any damage resulting from such use. This risk is borne solely by the owner. Improper use or use deviating from intended may result in hazards and/or will damage the unit. Examples of improper use:

• Operation in potentially explosive atmospheres.

• Operation with a non-approved medium.

• Operation under non-approved operational conditions.

• Operation when the safety devices are defective.

• Modifications to the power unit made by the user or purchaser.

• Inadequate monitoring of parts that are subject to wear and tear

• Improperly performed repair work.

FAM 10, Instructions, part 1/2 en(us) Page 12 / 68

BEWA FAM10-15 1-2 4170099 en-us 2016-10-18.doc 2016-10-18

Page 13: FAM 10 FAM 10/15 - hydac.com · FAM 10 FAM 10/15. FluidAqua Mobil Operating and maintenance instructions, ... HRB 1 7216 Executive director: Mathias Dieter, Dipl.Kfm. Wolfgang Haering

Safety information

Qualifications of personnel / target group Persons who work on the power unit must be aware of the associated hazards when using the power unit. Operating and specialist personnel must have read and understood the operating instructions, in particular the safety information and instructions, and applicable regulations before beginning work. The operating instructions and applicable regulations are to kept so they are accessible for operating and specialist personnel. These operating instructions are intended for: Operating personnel: such persons have been instructed in power unit operation and are aware of potential hazards due to improper use. Specialist personnel: such persons with corresponding specialist training and several years work experience. They are able to assess and perform the work assigned to them, they are also able to recognize potential hazards.

FAM 10, Instructions, part 1/2 en(us) Page 13 / 68

BEWA FAM10-15 1-2 4170099 en-us 2016-10-18.doc 2016-10-18

Page 14: FAM 10 FAM 10/15 - hydac.com · FAM 10 FAM 10/15. FluidAqua Mobil Operating and maintenance instructions, ... HRB 1 7216 Executive director: Mathias Dieter, Dipl.Kfm. Wolfgang Haering

Safety information

Activity Person Knowledge

Transport / storage Forwarding agent Specialist personnel

• Proof of knowledge of cargo securing instructions

• Safe handling/operation of hoisting and lifting equipment

Hydraulic / electrical installation, first commissioning, maintenance, troubleshooting, repair, decommissioning, Disassembly

Specialist personnel

• Safe handling/use of tools

• Fitting and connection of hydraulic lines and connections

• Fitting and connection of electrical lines, electrical machinery, sockets, etc.

• Checking the phase sequence

• Product-specific knowledge

Operation Operations control

Specialist personnel

• Product-specific knowledge

• Knowledge about how to handle operating media.

• Knowledge about contamination due to solids and water

Disposal Specialist personnel

• Proper and environmentally-friendly disposal of materials and substances

• Decontamination of contaminants

• Knowledge about reuse

FAM 10, Instructions, part 1/2 en(us) Page 14 / 68

BEWA FAM10-15 1-2 4170099 en-us 2016-10-18.doc 2016-10-18

Page 15: FAM 10 FAM 10/15 - hydac.com · FAM 10 FAM 10/15. FluidAqua Mobil Operating and maintenance instructions, ... HRB 1 7216 Executive director: Mathias Dieter, Dipl.Kfm. Wolfgang Haering

Unpacking the unit

Wear suitable clothing Loosely worn clothing increases the danger of getting caught or wound up in rotating parts and the danger of getting snagged on projecting parts. You can be severely injured or killed.

• Wear close-fitting clothing.

• Do not wear any rings, chains or any other jewelry.

• Wear work safety shoes.

Stoppage in an emergency (EMERGENCY STOP) In the event of an emergency, turn the main switch by 90° in a counter-clockwise direction to shut down the entire unit. The entire unit downstream of this switch is voltage-free and depressurized.

Normal pressure is restored to the vacuum column after ≈ 1 minute.

Unpacking the unit

Before delivery, the FAM is inspected for leaks and proper functioning at the factory, then carefully packed for shipment. When receiving and unpacking the unit, check it for damage in transit. Dispose of the packaging material in an environmentally friendly manner.

FAM 10, Instructions, part 1/2 en(us) Page 15 / 68

BEWA FAM10-15 1-2 4170099 en-us 2016-10-18.doc 2016-10-18

Page 16: FAM 10 FAM 10/15 - hydac.com · FAM 10 FAM 10/15. FluidAqua Mobil Operating and maintenance instructions, ... HRB 1 7216 Executive director: Mathias Dieter, Dipl.Kfm. Wolfgang Haering

Transporting the unit

Transporting the unit

CAUTION High empty weight (> 300 kg depending on version)

Danger of bodily injury

► Use at least 2 persons to shift the mobile unit.

NOTICE

Using components for pushing/pulling

The unit will be damaged.

► Never use the components to push or pull the unit.

► Use only the grips provided for shifting.

Drain the unit completely before transport. Seal off the inlets and/or outlets. Move the FAM manually using the rollers. When doing so, use only the grips provided on the FAM frame for pushing. Before shifting the unit, make sure to release the hand brake on the steering rollers. Once the FAM is in its new position, actuate the hand brake on the steering rollers.

Transporting with the fork lift truck Use the lift eyes when transporting the unit with a forklift.

FAM 10, Instructions, part 1/2 en(us) Page 16 / 68

BEWA FAM10-15 1-2 4170099 en-us 2016-10-18.doc 2016-10-18

Page 17: FAM 10 FAM 10/15 - hydac.com · FAM 10 FAM 10/15. FluidAqua Mobil Operating and maintenance instructions, ... HRB 1 7216 Executive director: Mathias Dieter, Dipl.Kfm. Wolfgang Haering

Transporting the unit

Transporting with the crane The unit has four eyelets on the frame for fastening lifting accessories.

NOTICE

Unsuitable lifting accessories

The unit will be damaged / Components will be damaged / destroyed

► Use only suitable lifting accessories to raise or lash the unit.

► Take care to ensure that the lifting accessories do not cause any pressures to be brought to bear against the components on the unit.

Transporting by train / truck For transport by rail or truck, supports must be placed under the mobile unit so that the rollers are subjected to no load pressure. The unit is to be secured with suitable belts.

FAM 10, Instructions, part 1/2 en(us) Page 17 / 68

BEWA FAM10-15 1-2 4170099 en-us 2016-10-18.doc 2016-10-18

Page 18: FAM 10 FAM 10/15 - hydac.com · FAM 10 FAM 10/15. FluidAqua Mobil Operating and maintenance instructions, ... HRB 1 7216 Executive director: Mathias Dieter, Dipl.Kfm. Wolfgang Haering

Checking the scope of delivery

Checking the scope of delivery

Upon receiving the FAM check it for any damage in transit. The FAM may not be set up and installed unless it is in perfect order. Any damage in transit is to be reported to the forwarding agent or the department in charge immediately; the unit may not be commissioned until this damage is properly remedied. The following items are supplied:

Qty Description

1 FluidAqua Mobil, ready for connection with suction and pressure hose

1

Technical documentation comprising: - Operation and Maintenance Instructions, part 1/2 - Operation and Maintenance Instructions, part 2/2 - Electrical wiring diagram - Additional documents - Report / certificate

1 Vacuum pump oil, 1 liter

1 Four-sided hollow socket key, 6 mm

FAM 10, Instructions, part 1/2 en(us) Page 18 / 68

BEWA FAM10-15 1-2 4170099 en-us 2016-10-18.doc 2016-10-18

Page 19: FAM 10 FAM 10/15 - hydac.com · FAM 10 FAM 10/15. FluidAqua Mobil Operating and maintenance instructions, ... HRB 1 7216 Executive director: Mathias Dieter, Dipl.Kfm. Wolfgang Haering

Description of unit

Description of unit

The FluidAqua Mobil was developed for the dewatering, filtration and degassing of hydraulic and lubricating oils. It removes free water, emulsified water and a large percentage of the water to be found in solution. The Fluidfilter that is installed provides efficient particulate separation. The drying and degassing of the medium is achieved by the neg. pressure in the vacuum column.

Unit versions

Stationary (FAM-xx-x-1-…) Mobile (FAM-xx-x-2-…)

In comparison to the stationary version, the mobile version of the FAM has: - 2 casters, 2 fixed casters

- Suction hose, length 5 m

- Return hose, length = 5 m

- Connection cable, electric, length 10 m

FAM 10, Instructions, part 1/2 en(us) Page 19 / 68

BEWA FAM10-15 1-2 4170099 en-us 2016-10-18.doc 2016-10-18

Page 20: FAM 10 FAM 10/15 - hydac.com · FAM 10 FAM 10/15. FluidAqua Mobil Operating and maintenance instructions, ... HRB 1 7216 Executive director: Mathias Dieter, Dipl.Kfm. Wolfgang Haering

Description of unit

Technical specifications The FluidAqua Mobil is able to dewater authorized fluids down to a water content of less than 100 ppm and transformer oils down to less than 10 ppm. As an approximate guideline, the dimensioning of the FluidAqua Mobil can be defined in accordance with the tank volume. Tank volume in liters Filter Size

< 1,500 FAM 5

1,000 – 7,000 FAM10/15

7,000 – 15,000 FAM 25

15,000 – 25,000 FAM 45

25,000 – 35,000 FAM 60

35,000 – 45,000 FAM 75

> 45,000 FAM95 Generally speaking, however, it must be taken into account that the design depends on the application, the fluid and the ambient temperature, the fluid amount and the water input into the system. These exercise a great influence over the dewatering performance. It is for that reason that the specifications can serve only as a starting point. The dewatering performance is dependent upon: Dewatering

performance

Water content

Fluid temperature

Detergent additives

Volumetric flow of the FAM

FAM 10, Instructions, part 1/2 en(us) Page 20 / 68

BEWA FAM10-15 1-2 4170099 en-us 2016-10-18.doc 2016-10-18

Page 21: FAM 10 FAM 10/15 - hydac.com · FAM 10 FAM 10/15. FluidAqua Mobil Operating and maintenance instructions, ... HRB 1 7216 Executive director: Mathias Dieter, Dipl.Kfm. Wolfgang Haering

Function description

Function description

AS

M

M

M

CS

M

OUT IN

1629

2827*

6*

5

13

14

15

25

7

24

26

3

2

1

20*

21*

23*

22*

* Option

Option Contamination Sensor

9

4

8 30

19

19

19

10

11

Connect up the power unit in bypass flow with the tank that is to be cleaned. After the unit is switched on, the filling pump (3) begins to convey the fluid from the tank through the suction filter (1) into the vacuum column (5). The vacuum pump (16) sets up the negative pressure in the vacuum column (5) required for dewatering and degassing. The negative pressure is regulated by the negative pressure setting (14), continuously measured at the negative pressure sensor (15) and displayed on the operating panel in the control cabinet. The fluid percolates downwards in the vacuum column over a special tower packing and collects in the lower area. The evacuations pump (7) switches on once the MAX level [02] in the vacuum column is reached. As a result of the greater volume flow of the evacuation pump, the filling level in the vacuum column drops down to the Min level [01]. Once this is reached, the return valve (2/2-way solenoid valve) (26) opens and a partial volume flow is returned into the vacuum column. The return valve (2/2-way solenoid valve) (26) closes once again after the Max level [02] has been reached. Air is drawn in through the air filter (13) as a result of the negative pressure in the vacuum column (5). In the counter flow, this air absorbs the moisture of the fluid and is then drawn off by the vacuum pump (16) through an oil mist separator (17).

FAM 10, Instructions, part 1/2 en(us) Page 21 / 68

BEWA FAM10-15 1-2 4170099 en-us 2016-10-18.doc 2016-10-18

Page 22: FAM 10 FAM 10/15 - hydac.com · FAM 10 FAM 10/15. FluidAqua Mobil Operating and maintenance instructions, ... HRB 1 7216 Executive director: Mathias Dieter, Dipl.Kfm. Wolfgang Haering

Function description

The saturation level of the aspirated fluid is measured via the installed AquaSensor (2) and displayed on the control panel. The saturation level indicates what percent of maximum possible water is dissolved in the oil. A value of 0% would indicate water-free oil and 100% would mean oil that is completely saturated with water. It is possible to use the saturation level to control the power unit. All of the functions on the control panel can be selected, except for the regulation of the vacuum pressure. The electrical control of the Siemens S7 series monitors the functioning of the unit. Malfunction and error messages are displayed in plain text in the correspondingly available national language. All E-STOP messages will lead to a direct switch-off of the unit. After the FluidAqua Mobil is shut down using the control panel, the filling pump and the rotary vane vacuum pump - together with its charge pump when a ContaminationSensor is present - are also switched off. Exception: If the heater is switched on, then a cooling phase of 60 seconds will intervene during which the heater is first shut off. Afterwards, all of the pumps will be switched off, except for the evacuation pump. The evacuation pump runs until the "Min" fill level in the vacuum column is reached. The run-down phase status is shown in the display. If the fill level "Min" in the vacuum column is reached, the power unit will be switched off. The water that is absorbed is expelled as water vapor from the rotary vane vacuum pump.

FAM 10, Instructions, part 1/2 en(us) Page 22 / 68

BEWA FAM10-15 1-2 4170099 en-us 2016-10-18.doc 2016-10-18

Page 23: FAM 10 FAM 10/15 - hydac.com · FAM 10 FAM 10/15. FluidAqua Mobil Operating and maintenance instructions, ... HRB 1 7216 Executive director: Mathias Dieter, Dipl.Kfm. Wolfgang Haering

Function description

Cleaning in Bypass Flow The FAM is connected with suction and pressure lines to the tank and cleans the medium to be found there in continuous operation.

Purifying and transferring by pumping The FAM is connected to the contaminated oil tank with the suction hose and pumps the fluid into the tank for the purified oil while cleaning it at the same time.

(A) = Waste oil tank

(B) = Pure oil tank The fill level of the clean-oil tank is to be monitored constantly during this process to prevent overfilling. You achieve permanently better levels of purity by operating the system continuously in bypass flow.

FAM 10, Instructions, part 1/2 en(us) Page 23 / 68

BEWA FAM10-15 1-2 4170099 en-us 2016-10-18.doc 2016-10-18

Page 24: FAM 10 FAM 10/15 - hydac.com · FAM 10 FAM 10/15. FluidAqua Mobil Operating and maintenance instructions, ... HRB 1 7216 Executive director: Mathias Dieter, Dipl.Kfm. Wolfgang Haering

Function description

Unit system components

FAM 10, Instructions, part 1/2 en(us) Page 24 / 68

BEWA FAM10-15 1-2 4170099 en-us 2016-10-18.doc 2016-10-18

Page 25: FAM 10 FAM 10/15 - hydac.com · FAM 10 FAM 10/15. FluidAqua Mobil Operating and maintenance instructions, ... HRB 1 7216 Executive director: Mathias Dieter, Dipl.Kfm. Wolfgang Haering

Function description

Item Description 1 Suction strainer 2 AquaSensor AS1000 3 filling pump 4 Non-return valve 5 Vacuum column 6 Heater (Option) 7 Evacuation pump 8 Check valve at the outlet 9 Fluid filter for separating solid particles 11 Fluid filter drainage 13 Air filter and dryer 14 Needle valve for vacuum setting 15 Pressure sensor for vacuum measurement 16 Vacuum pump 19 Vacuum column level sensor 24 Float switch, oil pan 25 Vacuum column drainage 27 Temperature sensor (optional for heater) 28 Vacuum pump drainage 29 Level sensor for vacuum pump 30 Ball valve at the inlet (IN) 40 Switch cabinet 41 Main switch / E-STOP 42 Fault indicator lamp 43 Control panel, SIEMENS 44 SensorMonitoring Unit SMU1200 (optional) 45 Cable holder 46 Hose retainer 51 Caster with immobilization brake 52 Rigid caster 55 Sliding grip

FAM 10, Instructions, part 1/2 en(us) Page 25 / 68

BEWA FAM10-15 1-2 4170099 en-us 2016-10-18.doc 2016-10-18

Page 26: FAM 10 FAM 10/15 - hydac.com · FAM 10 FAM 10/15. FluidAqua Mobil Operating and maintenance instructions, ... HRB 1 7216 Executive director: Mathias Dieter, Dipl.Kfm. Wolfgang Haering

Unit dimensions

Unit dimensions

The different versions of the FAM series have the following illustrated dimensions.

Stationary version

FAM 10, Instructions, part 1/2 en(us) Page 26 / 68

BEWA FAM10-15 1-2 4170099 en-us 2016-10-18.doc 2016-10-18

Page 27: FAM 10 FAM 10/15 - hydac.com · FAM 10 FAM 10/15. FluidAqua Mobil Operating and maintenance instructions, ... HRB 1 7216 Executive director: Mathias Dieter, Dipl.Kfm. Wolfgang Haering

Unit dimensions

Mobile version

FAM 10, Instructions, part 1/2 en(us) Page 27 / 68

BEWA FAM10-15 1-2 4170099 en-us 2016-10-18.doc 2016-10-18

Page 28: FAM 10 FAM 10/15 - hydac.com · FAM 10 FAM 10/15. FluidAqua Mobil Operating and maintenance instructions, ... HRB 1 7216 Executive director: Mathias Dieter, Dipl.Kfm. Wolfgang Haering

Hydraulic circuit

Hydraulic circuit

FAM 10, Instructions, part 1/2 en(us) Page 28 / 68

BEWA FAM10-15 1-2 4170099 en-us 2016-10-18.doc 2016-10-18

Page 29: FAM 10 FAM 10/15 - hydac.com · FAM 10 FAM 10/15. FluidAqua Mobil Operating and maintenance instructions, ... HRB 1 7216 Executive director: Mathias Dieter, Dipl.Kfm. Wolfgang Haering

Hydraulic circuit

Item Description 1 Suction strainer 2 AquaSensor AS1000 3 filling pump 4 Non-return valve 5 Vacuum column 6 Heater (Option) 7 Evacuation pump 8 Check valve at the outlet 9 Fluid filter for separating solid particles 10 Differential pressure switch for filter monitoring 11 Fluid filter drainage 13 Air filter and dryer 14 Needle valve for vacuum setting 15 Pressure sensor for vacuum measurement 16 Vacuum pump 19 Vacuum column level sensor 20 Pump to the ContaminationSensor CS1000 (optional) 21 ContaminationSensor CS1000 (Optional) 22 Pressure relief valve CS1000 (optional) 23 Pressure relief valve CS1000 (optional) 24 Float switch, oil pan 25 Vacuum column drainage 26 Return valve 27 Temperature sensor (optional for heater) 28 Vacuum pump drainage 29 Level sensor for vacuum pump 30 Ball valve at the inlet (IN)

FAM 10, Instructions, part 1/2 en(us) Page 29 / 68

BEWA FAM10-15 1-2 4170099 en-us 2016-10-18.doc 2016-10-18

Page 30: FAM 10 FAM 10/15 - hydac.com · FAM 10 FAM 10/15. FluidAqua Mobil Operating and maintenance instructions, ... HRB 1 7216 Executive director: Mathias Dieter, Dipl.Kfm. Wolfgang Haering

Unit setup and connection

Unit setup and connection

CAUTION Outlet air of the rotary vane vacuum pump

Hazardous to health

► Always make sure there is sufficient ventilation in the surrounding area of the unit.

Air coming out of the rotary vane vacuum pump can contain particles of vacuum pump oil and/or the fluid. Depending on the composition of the oil and the composition of the gas, there is a danger of damage to health if the emergent gas is inhaled over an extended period of time.

Setting up the unit Observe the following points when setting up the unit:

• Set up the unit horizontally on a level surface. Special mounting is not required.

• Lock the immobilization brakes on the wheels to avoid unintended movement of the unit.

• Set up the unit directly beside the tank that is to be cleaned. Observe the maximum permitted suction pressure.

• Make sure to note the ambient temperature on the type label of the unit.

• Ensure that the main switch is freely accessible at all times.

• Keep an area of at least 0.8 m around the unit free for maintenance purposes.

• Make sure that the control panel is always freely accessible and that the control cabinet can be opened fully.

FAM 10, Instructions, part 1/2 en(us) Page 30 / 68

BEWA FAM10-15 1-2 4170099 en-us 2016-10-18.doc 2016-10-18

Page 31: FAM 10 FAM 10/15 - hydac.com · FAM 10 FAM 10/15. FluidAqua Mobil Operating and maintenance instructions, ... HRB 1 7216 Executive director: Mathias Dieter, Dipl.Kfm. Wolfgang Haering

Unit setup and connection

Connection overview The stationary and mobile FAM versions have different scopes of delivery. The stationary FAM has positions 1-4, while the mobile FAM has positions 5-8.

Item

1 FAM inlet connector 28L / M36x2 (external thread)*

2 Adapter Adapter G1 A (external thread)**

3 FAM outlet connector

18L / M26x1.5 (external thread)*

4 Adapter Adapter G1/2 A (external thread)**

5 Suction hose connection

28L / M36x2 (internal thread)***

6 Adapter Adapter G1 A (external thread)**

7 Pressure hose connection

18L / M26x1.5 (female thread)***

8 Adapter Adapter G1/2 A (external thread)**

*) Output drive type D to ISO 8434-1 Series L (corresponds to ISO 12151, Form S, Series L)

**) Stud end to ISO 1179-2 (Form E)

***) Output drive type N to ISO 8434-4 Series L (corresponding to ISO 12151, Form SWS, Series L)

FAM 10, Instructions, part 1/2 en(us) Page 31 / 68

BEWA FAM10-15 1-2 4170099 en-us 2016-10-18.doc 2016-10-18

Page 32: FAM 10 FAM 10/15 - hydac.com · FAM 10 FAM 10/15. FluidAqua Mobil Operating and maintenance instructions, ... HRB 1 7216 Executive director: Mathias Dieter, Dipl.Kfm. Wolfgang Haering

Unit setup and connection

Notes on pipes and hoses

NOTICE

Non-permitted pressure at the inlet IN/outlet OUT

Failure malfunction

► Determine the pressure to be anticipated at the inlet/outlet with the prescribed values.

Note that the cross-section of the connected hoses/piping must be at least as large as the cross-section of the inlet/outlet port sizes. In order to keep the pressure loss as low as possible, use as few threaded connections as possible. Connect all connectors to the unit without initial stress. The pressure at the inlet (IN) / outlet (OUT) depends on the height differential between the FAM fluid surface in the tank port (suction height ∆P(height)) and the line losses (∆P(line)). If the FAM is above the fluid surface in the tank, estimate the pressure as follows: P(IN) = - ∆P(height) - ∆P(line) P(OUT) = - ∆P(height) + ∆P(line) If the FAM is below the fluid surface in the tank, estimate the pressure as follows: P(IN) = + ∆P(height) - ∆P(line) P(OUT) = + ∆P(height) + ∆P(line) Estimate the pressure loss ∆P(height) as follows: ∆P(height)[bar] = h/10. h stands here for the distance between the inlet (IN) / outlet (OUT) on the FAM and the fluid surface in the tank The pressure differential in a hydraulic line (∆P(line)) depends on the following:

• flow rate

• kinematic viscosity

• Pipe dimensions

• Fluid density

FAM 10, Instructions, part 1/2 en(us) Page 32 / 68

BEWA FAM10-15 1-2 4170099 en-us 2016-10-18.doc 2016-10-18

Page 33: FAM 10 FAM 10/15 - hydac.com · FAM 10 FAM 10/15. FluidAqua Mobil Operating and maintenance instructions, ... HRB 1 7216 Executive director: Mathias Dieter, Dipl.Kfm. Wolfgang Haering

Unit setup and connection

The pressure loss in straight pipes (∆P(line)) can be calculated as follows:

Δp ≈ 6.8 * L / d4 * Q * V * D Δp = Pressure differential in [bar]

L = pipe length [m]

d = internal pipe diameter [mm]

Q = Flow rate [l/min]

V = Kinematic viscosity [mm²/s]

D = Density [kg/dm³] Mineral oil-based hydraulic fluid has a density of ≈ 0.9 kg/dm³.

The density (D) is: Mineral hydraulic oil HLP 0.85 … 0.90 kg / dm³

Phosphate ester HFDR 1.00 … 1.10 kg / dm³

Insulation oil 0.90 … 1.00 kg / dm³

Lubricating oil 0.90 … 0.95 kg / dm³ Find the flow rate in chapter "Technical Data" on page 59. Additional threaded connections and pipe bends increase the pressure differential and must be taken into account. Keep the height difference between the pump and the oil level in the tank as low as possible. Avoid constrictions in the connected hoses. They compromise output and increase the risk of cavitation. Make sure that no tension or vibrations are carried over to the pump or filter housing when the pipes are connected. Use hoses or expansion joints if necessary.

FAM 10, Instructions, part 1/2 en(us) Page 33 / 68

BEWA FAM10-15 1-2 4170099 en-us 2016-10-18.doc 2016-10-18

Page 34: FAM 10 FAM 10/15 - hydac.com · FAM 10 FAM 10/15. FluidAqua Mobil Operating and maintenance instructions, ... HRB 1 7216 Executive director: Mathias Dieter, Dipl.Kfm. Wolfgang Haering

Unit setup and connection

Connecting the inlet (IN) The suction pressure at the FAM inlet must be -0.2 bar. Use a negative pressure-resistant, flexible hose or a pipe for the suction-side connection. Note that the cross-section of the connected hoses/piping must be at least as large as the cross-section of the inlet/outlet port sizes. The shape of the tank connection should be set up in such a way that it will always be lower than the level of the oil.

NOTICE

Contamination too high

The unit will be damaged

► Do not prime directly at the bottom of the tank

► Do not prime in the sump

► Never prime without a built-in suction screen

The greatest contamination is found on the bottom of the tank. All impurities and other particles are deposited on the bottom of the tank. All impurities and other particles are deposited on the bottom of the tank.

Connect outlet (OUT)

Take care to ensure that the maximum pressure of 3 bar is not exceeded at the outlet.

NOTICE

OUT connection closed off

The unit will be destroyed

► Check to be sure that all of the locking fixtures at the inlet/outlet are in "open" position each time before start-up.

To prevent air from entering the medium, make sure that the pressure hose with lance is always below the oil level in operation.

FAM 10, Instructions, part 1/2 en(us) Page 34 / 68

BEWA FAM10-15 1-2 4170099 en-us 2016-10-18.doc 2016-10-18

Page 35: FAM 10 FAM 10/15 - hydac.com · FAM 10 FAM 10/15. FluidAqua Mobil Operating and maintenance instructions, ... HRB 1 7216 Executive director: Mathias Dieter, Dipl.Kfm. Wolfgang Haering

Unit setup and connection

Preparing the Vacuum Pump The rotary vane vacuum pump is not filled with oil at the time the FAM is delivered. A sufficient amount of vacuum pump oil for the initial filling is included in the scope of delivery.

NOTICE

Operation without vacuum pump oil

The rotary vane vacuum pump will be destroyed

► The rotary vane vacuum pump requires oil as its operating medium.

► Check the oil level before star-up, topping up with vacuum pump oil VE101 if necessary.

The maximum filling amount for vacuum pump oil VE101 is 0.3 liters. The water level is monitored automatically by the integrated float switch while the FAM is in operation. A message will appear on the control panel when the MIN MAX filling level has been reached. Synthetic vacuum pump oil in accordance with DIN 51506, Group VDL, ISO VG100 must be used for topping up. You can find the HYDAC vacuum pump oil in chapter "Fehler! Verweisquelle konnte nicht gefunden werden." on page Fehler! Textmarke nicht definiert..

FAM 10, Instructions, part 1/2 en(us) Page 35 / 68

BEWA FAM10-15 1-2 4170099 en-us 2016-10-18.doc 2016-10-18

Page 36: FAM 10 FAM 10/15 - hydac.com · FAM 10 FAM 10/15. FluidAqua Mobil Operating and maintenance instructions, ... HRB 1 7216 Executive director: Mathias Dieter, Dipl.Kfm. Wolfgang Haering

Unit setup and connection

Filling up the rotary vane vacuum pump Remove the safety screw for the plug at the level switch (1). Remove the plug (2) for the level switch. Unscrew the level switch (3) from the vacuum pump. Fill up with vacuum pump oil VE101 through the filling nozzle (4). Check the oil level through the inspection glass (5). Fill up the vacuum pump oil no higher than the MAX marking. We recommend filling up to a level between the MIN and MAX markings. The suction strainer is re-mounted in reverse order.

12

34

5

FAM 10, Instructions, part 1/2 en(us) Page 36 / 68

BEWA FAM10-15 1-2 4170099 en-us 2016-10-18.doc 2016-10-18

Page 37: FAM 10 FAM 10/15 - hydac.com · FAM 10 FAM 10/15. FluidAqua Mobil Operating and maintenance instructions, ... HRB 1 7216 Executive director: Mathias Dieter, Dipl.Kfm. Wolfgang Haering

Unit setup and connection

Electrical connection of the FAM

DANGER Exposed electrical components in the switch cabinet

Danger of fatal injury due to electric shock

► Any work involving the electrical system may only be done by a properly trained, certified electrician.

The electrical connection of units without connection plugs to the power supply module may only be performed by a technician with corresponding knowledge and skills. Make sure that the voltage and frequency specifications on the FAM type label correspond to the existing mains voltage. If a plug is present on the FAM or if a plug is mounted, then the FAM is to be operated from a correspondingly fused socket.

FAM 10, Instructions, part 1/2 en(us) Page 37 / 68

BEWA FAM10-15 1-2 4170099 en-us 2016-10-18.doc 2016-10-18

Page 38: FAM 10 FAM 10/15 - hydac.com · FAM 10 FAM 10/15. FluidAqua Mobil Operating and maintenance instructions, ... HRB 1 7216 Executive director: Mathias Dieter, Dipl.Kfm. Wolfgang Haering

Unit setup and connection

Checking the direction of rotation of the electric motors Check the direction of rotation of the electric motor by switching it on briefly (jog mode). An arrow on the fan cover shows the correct direction of rotation for the unit. The FAM requires a clockwise rotating field at the connecting socket.

NOTICE

Incorrect phase sequence/direction of rotation of the motor

The pumps will be destroyed.

► In jog mode, check the direction of rotation of the electric motors.

► A rotation direction arrow on the fan cover of the electric motor identifies the correct direction of rotation.

Make sure there is a clockwise rotating field. If this is not the case, then the phases can be rotated in the 16A/32 A connection plug with the aid of the phase changing switch in the plug. For the 63A version, the two phases must be switched on the terminal block S0 (e.g. L1 and L2).

A phase sequence relay checks the correct phase sequence after switch-on. In the event of an incorrect phase sequence, error message no. 29 is shown on the control panel.

FAM 10, Instructions, part 1/2 en(us) Page 38 / 68

BEWA FAM10-15 1-2 4170099 en-us 2016-10-18.doc 2016-10-18

Page 39: FAM 10 FAM 10/15 - hydac.com · FAM 10 FAM 10/15. FluidAqua Mobil Operating and maintenance instructions, ... HRB 1 7216 Executive director: Mathias Dieter, Dipl.Kfm. Wolfgang Haering

Operating elements on the FAM

Operating elements on the FAM

The following operating elements are to be found on the FAM:

Item Description

a Main switch with E-STOP function

B Alarm signal lamp (yellow)

C Operate the control panel and error messages / troubleshooting see Operation and maintenance instructions, part 2/2

D Needle valve to set the pressure in the vacuum column

E SensorMonitoring Unit SMU1200 (for details see the corresponding operating instructions)

FAM 10, Instructions, part 1/2 en(us) Page 39 / 68

BEWA FAM10-15 1-2 4170099 en-us 2016-10-18.doc 2016-10-18

Page 40: FAM 10 FAM 10/15 - hydac.com · FAM 10 FAM 10/15. FluidAqua Mobil Operating and maintenance instructions, ... HRB 1 7216 Executive director: Mathias Dieter, Dipl.Kfm. Wolfgang Haering

Switching on / switching off / commissioning and error messages

Switching on / switching off / commissioning and error messages

Details on switching on/off, commissioning and error messages/troubleshooting can be found in the Operation and Maintenance Instructions, part 2/2.

FAM 10, Instructions, part 1/2 en(us) Page 40 / 68

BEWA FAM10-15 1-2 4170099 en-us 2016-10-18.doc 2016-10-18

Page 41: FAM 10 FAM 10/15 - hydac.com · FAM 10 FAM 10/15. FluidAqua Mobil Operating and maintenance instructions, ... HRB 1 7216 Executive director: Mathias Dieter, Dipl.Kfm. Wolfgang Haering

Performing maintenance

Performing maintenance

Before performing any maintenance work, pull out the plug on the FAM and wind up the power cord to prevent the unit from being switched on again. The Unit is to be disconnected from the power supply and protected against being inadvertently switched back on when performing any maintenance, servicing, inspection or repair work. Once maintenance work is complete, check that the safety devices are still working properly. Any screwed fittings which have been undone/removed are to be checked to see that they have been properly resecured.

See

pag

e

24 h

ours

/ da

ily

500

hour

s /

mon

thly

3000

hou

rs /

ever

y si

x m

onth

s

6000

hou

rs /

annu

ally

General

Check the FAM for any leaks (visual check). - X

Check the screwed fittings to see that they have been properly resecured.

- X

Inspection of the measurement technics / Pressure sensor in the vacuum column / Differential pressure manometer at the fluid filter / AquaSensor at the IN port / ETS at the vacuum column (optional)

- X

Check the fault indicator lamps / perform a lamp test 43 X

Change Air filter 43 X

Clean the suction strainer. 45 X

Rotary vane vacuum pump

Checking the oil level - X

FAM 10, Instructions, part 1/2 en(us) Page 41 / 68

BEWA FAM10-15 1-2 4170099 en-us 2016-10-18.doc 2016-10-18

Page 42: FAM 10 FAM 10/15 - hydac.com · FAM 10 FAM 10/15. FluidAqua Mobil Operating and maintenance instructions, ... HRB 1 7216 Executive director: Mathias Dieter, Dipl.Kfm. Wolfgang Haering

Performing maintenance

See

pag

e

24 h

ours

/ da

ily

500

hour

s /

mon

thly

3000

hou

rs /

ever

y si

x m

onth

s

6000

hou

rs /

annu

ally

Changing oil 47 X

Replacing the Air De-oiling Element 48 X

Check and clean the ventilator hood - X

Emptying / filling pump

Check and clean the ventilator hood - X

Fluid filter OLF

Changing the filter element 49 X

Emptying and cleaning the filter housing - X

Electric System

Check cable conduits for damage, replacing as necessary - X

Measure the engine power consumption of all engines and compare the values with the type label

- X

Checking the AquaSensor X

Perform electrical safety inspection in accordance with DIN VDE 0702 and/or corresponding national regulation.

- X

Measure power consumption of the heater and compare values with type label (applies only to versions with integrated heater)

- X

Function Test

FAM 10, Instructions, part 1/2 en(us) Page 42 / 68

BEWA FAM10-15 1-2 4170099 en-us 2016-10-18.doc 2016-10-18

Page 43: FAM 10 FAM 10/15 - hydac.com · FAM 10 FAM 10/15. FluidAqua Mobil Operating and maintenance instructions, ... HRB 1 7216 Executive director: Mathias Dieter, Dipl.Kfm. Wolfgang Haering

Performing maintenance

See

pag

e

24 h

ours

/ da

ily

500

hour

s /

mon

thly

3000

hou

rs /

ever

y si

x m

onth

s

6000

hou

rs /

annu

ally

Testing the oil pan float switch 54 X

Completely replace all of the hoses after 5 years. The pictures and illustrations in the descriptions are examples. They do not represent all of the different product variants.

Function testing of the fault indicator lamp To perform the function test of the fault indicator lamp, follow these steps: 1. Switch on the unit at the main switch (A).

2. An automatic lamp test is conducted after the unit has been switched on. The fault indicator lamp (B) lights up briefly during this test.

3. The function test of the fault indicator lamp has been completed.

Change Air filter Replace the air filter (1) every six months. If you are operating the unit in a very dusty/damp environment, the replacement interval is accordingly shorter. 1. Manually unscrew the air filter (1).

2. Dispose of the air filter in an environmentally friendly manner.

3. Manually screw on the new air filter (1) and tighten this manually until secure.

4. The air filter replacement has been completed.

Checking the AquaSensor Check the AquaSensor annually with the calibration and adjustment set (HYDAC p/no. 3122629).

FAM 10, Instructions, part 1/2 en(us) Page 43 / 68

BEWA FAM10-15 1-2 4170099 en-us 2016-10-18.doc 2016-10-18

Page 44: FAM 10 FAM 10/15 - hydac.com · FAM 10 FAM 10/15. FluidAqua Mobil Operating and maintenance instructions, ... HRB 1 7216 Executive director: Mathias Dieter, Dipl.Kfm. Wolfgang Haering

Performing maintenance

Replace the AquaSensor if it exhibits great deviations. The part no. can be found in the spare parts list.

FAM 10, Instructions, part 1/2 en(us) Page 44 / 68

BEWA FAM10-15 1-2 4170099 en-us 2016-10-18.doc 2016-10-18

Page 45: FAM 10 FAM 10/15 - hydac.com · FAM 10 FAM 10/15. FluidAqua Mobil Operating and maintenance instructions, ... HRB 1 7216 Executive director: Mathias Dieter, Dipl.Kfm. Wolfgang Haering

Clean the suction screen

Clean the suction screen

NOTICE

Operation without a suction strainer

The pump will be destroyed

► The unit may not be operated without the suction strainer.

► Clean the suction screen regularly.

To protect the pump from coarse contamination particles and other foreign bodies, a dirt trap with a strainer insert is fitted at the pump inlet. Clean the suction strainer at regular intervals. To install / dismount the suction screen, proceed as follows: 1. Unscrew the screw plug (1)

counterclockwise with an open-jaw wrench.

123

2. Remove strainer insert (3) and clean it.

3. To clean the suction screen, wash it out with solvent and then dry it using compressed air.

3. Check strainer insert (3) and the seal ring (2) on the screw plug for damage and replace if necessary.

4. Install the new strainer insert (3).

5. Turn the screw plug (1) clockwise manually. Firmly screw in the screw plug (1) with the open-jaw wrench.

6. After commissioning, check the suction strainer fittings for leaks.

FAM 10, Instructions, part 1/2 en(us) Page 45 / 68

BEWA FAM10-15 1-2 4170099 en-us 2016-10-18.doc 2016-10-18

Page 46: FAM 10 FAM 10/15 - hydac.com · FAM 10 FAM 10/15. FluidAqua Mobil Operating and maintenance instructions, ... HRB 1 7216 Executive director: Mathias Dieter, Dipl.Kfm. Wolfgang Haering

Clean the suction screen

Rotary vane vacuum pump components

l

ma i

g

h

d

c

k

Item Designation

a Oil filler neck

c Oil drain

d Oil sight glass

g Oil separator

h Suction port connection

i Gas outlet

k Safety screw on the plug

l Plug for the level sensor

m Level switch in the vacuum pump The following descriptions are in reference to these positions.

FAM 10, Instructions, part 1/2 en(us) Page 46 / 68

BEWA FAM10-15 1-2 4170099 en-us 2016-10-18.doc 2016-10-18

Page 47: FAM 10 FAM 10/15 - hydac.com · FAM 10 FAM 10/15. FluidAqua Mobil Operating and maintenance instructions, ... HRB 1 7216 Executive director: Mathias Dieter, Dipl.Kfm. Wolfgang Haering

Clean the suction screen

Performing an oil change The first oil change must take place after 100 operating hours. Afterwards, the interval increases to ≈ 3000 hours or twice per year. The vacuum pump must be at operating state temperature when the oil is changed: Put the FAM into operation for 10 minutes. Switch off the FAM at the main switch. Wait until the pressure in the vacuum column has reached atmospheric pressure (approx. 1000 mbar abs). To perform these tasks, you will need the following tools and equipment:

• Compressor oil VE101 (for part-no., see replacement parts list)

• Maintenance set, comprising oil filter, air deoiling element, ventilation cover seal (for part-no., see replacement parts list)

• Fork wrenches SW 27 / SW 32 To change the oil, proceed as follows:

1. Put a suitable container in place to catch the used oil.

2. Open the oil drain (c) and allow the used oil to drain into the container. Dispose of the used oil properly.

3. Close the screw plug when the flow of oil diminishes. Let the pump run again briefly for a few seconds,

4. Open the plug screw once again and drain off the remaining oil.

5. Screw in the plug screw and tighten it firmly.

6. Remove the oil filter and dispose of it properly.

7. Install the new oil filter.

8. Fill in new oil through the oil filling screw plug (a) until the MAX marking (d) has been reached.

FAM 10, Instructions, part 1/2 en(us) Page 47 / 68

BEWA FAM10-15 1-2 4170099 en-us 2016-10-18.doc 2016-10-18

Page 48: FAM 10 FAM 10/15 - hydac.com · FAM 10 FAM 10/15. FluidAqua Mobil Operating and maintenance instructions, ... HRB 1 7216 Executive director: Mathias Dieter, Dipl.Kfm. Wolfgang Haering

Clean the suction screen

Replacing the Air De-oiling Element Oil mist or increased electricity consumption by the drive engine (response of the engine protection switch) are signs of a soiled air de-oiling element. To replace the air de-oiling element, proceed as follows: 1. Remove the ventilation cover (i) from the oil separator (g). 2. Undo the screw in the middle of the filter spring, but do not remove this. 3. Press the filter spring down and rotate it out of the depression. 4. Remove the filter spring from the oil separator (g). 5. Pull the air de-oiling element out of the oil separator (g). 6. Make sure that the new air deoiling element is provided with a new O-

ring. 7. Install the air de-oiling element in such a way that the opening is

situated correctly in the holder in the oil separator (g). 8. Make sure that the tip of the screw in the middle of the filter spring

protrudes approx. 2–5 turns. 9. Install the filter spring in such a way that the ends are secured against

slipping by lugs in the receptacles in the oil separator (g) and the tip of the screw engages in the depression of the air de-oiling element.

10. Tighten the screw in the filter spring until the head of the screw impacts against the spring steel sheet.

11. Make sure that the seal under the ventilation cover (i) is clean and undamaged. Replace the seal if necessary.

12. Fasten the ventilation cover (i) with seal and hexagon-head screws to the oil separator (g).

The air de-oiling element becomes saturated with oil during operation. A slight lowering of the oil filling level after the air de-oiling element has been replaced is therefore quite normal.

FAM 10, Instructions, part 1/2 en(us) Page 48 / 68

BEWA FAM10-15 1-2 4170099 en-us 2016-10-18.doc 2016-10-18

Page 49: FAM 10 FAM 10/15 - hydac.com · FAM 10 FAM 10/15. FluidAqua Mobil Operating and maintenance instructions, ... HRB 1 7216 Executive director: Mathias Dieter, Dipl.Kfm. Wolfgang Haering

Clean the suction screen

Replacing the filter element on the fluid filter As soon as the error message "change fluid filter" appears on the display the filter should be taken out of the housing and be replaced by a new one. To change the filter element, proceed as follows:

1. Switch off the system and close the locking devices at the inlet and outlet ports. Make sure that the unit cannot be inadvertently switched back on during maintenance work.

2. Put a suitable container (1) in place to catch exiting medium. Depressurize the filter housing. Carefully open the drain plug (2) on the filter bowl and empty the filter housing completely using the drain screw (SW 6mm) on the bottom of the filter housing. The volume is approx. 2 liters. After draining, replace the drain plug on the filter bowl.

3. Undo the housing clamp (1) on the filter housing and then remove the housing by moving it downwards (2). Use an Allen wrench SW 6 mm (1).

FAM 10, Instructions, part 1/2 en(us) Page 49 / 68

BEWA FAM10-15 1-2 4170099 en-us 2016-10-18.doc 2016-10-18

Page 50: FAM 10 FAM 10/15 - hydac.com · FAM 10 FAM 10/15. FluidAqua Mobil Operating and maintenance instructions, ... HRB 1 7216 Executive director: Mathias Dieter, Dipl.Kfm. Wolfgang Haering

Clean the suction screen

4. Pull the filter bowl including filter element downwards.

5. Remove (2) the filter element from the

filter bowl by turning slightly (1). Dispose of the used filter element in an environmentally correct manner.

FAM 10, Instructions, part 1/2 en(us) Page 50 / 68

BEWA FAM10-15 1-2 4170099 en-us 2016-10-18.doc 2016-10-18

Page 51: FAM 10 FAM 10/15 - hydac.com · FAM 10 FAM 10/15. FluidAqua Mobil Operating and maintenance instructions, ... HRB 1 7216 Executive director: Mathias Dieter, Dipl.Kfm. Wolfgang Haering

Clean the suction screen

6. Clean the inside of the filter bowl of dirt and deposits.

7. Check the O-ring on the filter bowl for

damage. Replace it if necessary. Moisten the O-ring on the filter bowl with the operating medium.

8. Moisten the O-rings on the new filter element with the operating medium.

FAM 10, Instructions, part 1/2 en(us) Page 51 / 68

BEWA FAM10-15 1-2 4170099 en-us 2016-10-18.doc 2016-10-18

Page 52: FAM 10 FAM 10/15 - hydac.com · FAM 10 FAM 10/15. FluidAqua Mobil Operating and maintenance instructions, ... HRB 1 7216 Executive director: Mathias Dieter, Dipl.Kfm. Wolfgang Haering

Clean the suction screen

9. Turning it slightly, press the new filter element down into the mount on the filter bowl.

10. Push the filter bowl with the filter element

up into the mount on the filter head.

FAM 10, Instructions, part 1/2 en(us) Page 52 / 68

BEWA FAM10-15 1-2 4170099 en-us 2016-10-18.doc 2016-10-18

Page 53: FAM 10 FAM 10/15 - hydac.com · FAM 10 FAM 10/15. FluidAqua Mobil Operating and maintenance instructions, ... HRB 1 7216 Executive director: Mathias Dieter, Dipl.Kfm. Wolfgang Haering

Clean the suction screen

11. Push the housing clamp (1) up around the filter bowl over the bead on the filter bowl / filter head. Tighten the housing clamp with an Allen wrench SW 6mm in a clockwise direction. The tightening torque is 5 Nm.

12. Check that the drain plug on the filter

bowl is secure.

13. The filter element change is now

complete. After commissioning, check the filtration unit for leaks.

FAM 10, Instructions, part 1/2 en(us) Page 53 / 68

BEWA FAM10-15 1-2 4170099 en-us 2016-10-18.doc 2016-10-18

Page 54: FAM 10 FAM 10/15 - hydac.com · FAM 10 FAM 10/15. FluidAqua Mobil Operating and maintenance instructions, ... HRB 1 7216 Executive director: Mathias Dieter, Dipl.Kfm. Wolfgang Haering

Clean the suction screen

Testing the Float Switch in the Oil Pan Proceed as follows to test the float switch in the oil pan:

1. Use your fingers to raise the float switch in the oil pan.

2. The unit must switch off and the fault

message "Pan overfilled" must appear in display of the control panel.

3. Release the float switch and acknowledge the fault message by pressing the F3 key.

4. The unit continues to operate -> You have tested the function of the float switch positively.

5. If the unit does not switch off after the lifting of the float switch and no fault message appears, contact the HYDAC Service.

FAM 10, Instructions, part 1/2 en(us) Page 54 / 68

BEWA FAM10-15 1-2 4170099 en-us 2016-10-18.doc 2016-10-18

Page 55: FAM 10 FAM 10/15 - hydac.com · FAM 10 FAM 10/15. FluidAqua Mobil Operating and maintenance instructions, ... HRB 1 7216 Executive director: Mathias Dieter, Dipl.Kfm. Wolfgang Haering

Clean the suction screen

Check the safety thermostat on the heater Allow the heater to cool down before resetting. Undo the 4 screws and remove the cover from the heater terminal box. Press down the red button (B) so that it engages in the lower position. The mechanism is tripped by a bi-metal. This bi-metal must first cool down in order to recover. The cooling phase can indeed take up to 2 hours, depending on ambient conditions.

(A) = fluid temperature 55°C

(B) = safety thermostat 80°C

FAM 10, Instructions, part 1/2 en(us) Page 55 / 68

BEWA FAM10-15 1-2 4170099 en-us 2016-10-18.doc 2016-10-18

Page 56: FAM 10 FAM 10/15 - hydac.com · FAM 10 FAM 10/15. FluidAqua Mobil Operating and maintenance instructions, ... HRB 1 7216 Executive director: Mathias Dieter, Dipl.Kfm. Wolfgang Haering

Clean the suction screen

Reset safety thermostat on the heater The safety thermometer is triggered when the flow of oil through the heater is too low or if the thermostat is damaged. After the fault has been remedied, the safety thermostat can be reset by pressing the green key (C) in the head. To protect yourself from burns, wait until the heater has cooled down before doing so.

Checking the settings on the heater (optional) Under normal operating conditions the heater element is maintenance-free.

FAM 10, Instructions, part 1/2 en(us) Page 56 / 68

BEWA FAM10-15 1-2 4170099 en-us 2016-10-18.doc 2016-10-18

Page 57: FAM 10 FAM 10/15 - hydac.com · FAM 10 FAM 10/15. FluidAqua Mobil Operating and maintenance instructions, ... HRB 1 7216 Executive director: Mathias Dieter, Dipl.Kfm. Wolfgang Haering

Spare parts

Spare parts

FAM 10

Quantity

Description Part no.

1 Breather filter 0160 MU 003 M 1265765

1 Suction strainer 1" assy., consisting of:

635624

1x strainer insert, 250µm 6016797 1x sealing ring 6033969

1 Vacuum pressure gauge 639989

1 3/2-directional control valve 6014177

1 Pressure hose, Length = 5 m 6013308

1 Suction hose, Length = 5 m 6004781

1 Level switch (vacuum column) 120 4801 *) available on request

Fluid filter (OLF 5)

Quantity

Description Part no.

1 Filter element, filtration rating 2 µm N5DM002 349494

1 Filter element, filtration rating 5 µm N5DM005 3068101

1 Filter element, filtration rating 10 µm

N5DM010 3102924

1 Filter element, filtration rating 20 µm

N5DM020 3023508

*) available on request

FAM 10, Instructions, part 1/2 en(us) Page 57 / 68

BEWA FAM10-15 1-2 4170099 en-us 2016-10-18.doc 2016-10-18

Page 58: FAM 10 FAM 10/15 - hydac.com · FAM 10 FAM 10/15. FluidAqua Mobil Operating and maintenance instructions, ... HRB 1 7216 Executive director: Mathias Dieter, Dipl.Kfm. Wolfgang Haering

Taking the unit out of operation

Rotary vane vacuum pump

Quantity

Description Part no.

1 Service kit vacuum pump consisting of exhaust filter and seals

6014161

1 Vacuum pump oil VE101, 1 Liter 6018128

1 Vacuum pump oil VE101, 5 Liter 6018129 *) available on request

Taking the unit out of operation

Drain the unit completely, including all of its components, the same way as is done before putting it into storage. Pull out the power plug and securely fasten the hoses and power cord to the unit. Store the unit in a clean, dry (non-condensing) space.

Disposing of the unit

Dispose of the packaging material in an environmentally friendly manner. After dismantling the unit and separating the various materials, dispose of the unit in an environmentally-friendly manner.

FAM 10, Instructions, part 1/2 en(us) Page 58 / 68

BEWA FAM10-15 1-2 4170099 en-us 2016-10-18.doc 2016-10-18

Page 59: FAM 10 FAM 10/15 - hydac.com · FAM 10 FAM 10/15. FluidAqua Mobil Operating and maintenance instructions, ... HRB 1 7216 Executive director: Mathias Dieter, Dipl.Kfm. Wolfgang Haering

Technical Data

Technical Data

Refer to the type label for specific data of the unit. FAM 10 FAM10/15

Flow rate at inlet (IN) 10 l/min @ 50Hz 12 l/min @ 60Hz

12 l/min @ 50Hz 18 l/min @ 60Hz

Flow rate at outlet (OUT) 18 l/min @ 50Hz 22 l/min @ 60Hz

23 l/min @ 50Hz 28 l/min @ 60Hz

Electrical power consumption 1500 W without heater 4400 W with heater

2000 W without heater 4900 W with heater

Weight when empty ≈ 300 kg ≈ 300 kg

Operating pressure 0 – 6 bar

Permissible pressure at port (OUT)

0 – 3 bar

Permissible suction pressure at suction port (IN) (without suction hose)

-0.2 … 1 bar

Permissible viscosity range 15 to 800 mm²/s

Pump type Vacuum pump Rotary vane

vacuum pump Rotary vane vacuum pump

Filling pump Vane pump Vane pump Evacuation pump Gear pump Gear pump

Fluid filter size OLF5

Filter element type N5DMxxx

Contamination retention capacity according to ISO 4572

200 g

Clogging indicator VM 2 C.0

Power cable, length 10 m

IP class IP 54

Hoses, length 5 m

Hoses, material See the model code, page 61

Connection inlet/outlet see page31

FAM 10, Instructions, part 1/2 en(us) Page 59 / 68

BEWA FAM10-15 1-2 4170099 en-us 2016-10-18.doc 2016-10-18

Page 60: FAM 10 FAM 10/15 - hydac.com · FAM 10 FAM 10/15. FluidAqua Mobil Operating and maintenance instructions, ... HRB 1 7216 Executive director: Mathias Dieter, Dipl.Kfm. Wolfgang Haering

Technical Data

Material of sealings NBR / FKM (FPM, Viton®)

Permitted fluid temperature range

10 … 80°C

Permitted ambient temperature range

10 … 40°C

Permissable relative humidity maximum 90%, non-condensing

Permitted storage temperature range

10 … 50 °C

Achievable residual water content

< 100 ppm - Hydraulic and lube oils < 50 ppm - Turbine oils (ISO VG 32/46) < 10 ppm – Transformer oils (not suitable for online or onload operation)

Noise level according to VBG121 < 70 dB(A) at 1 m distance

FAM 10, Instructions, part 1/2 en(us) Page 60 / 68

BEWA FAM10-15 1-2 4170099 en-us 2016-10-18.doc 2016-10-18

Page 61: FAM 10 FAM 10/15 - hydac.com · FAM 10 FAM 10/15. FluidAqua Mobil Operating and maintenance instructions, ... HRB 1 7216 Executive director: Mathias Dieter, Dipl.Kfm. Wolfgang Haering

Attachment

Attachment

Contact Customer Service / Service For product information or technical support or if you have comments or suggestions concerning this manual, please contact: HYDAC FILTER SYSTEMS GMBH Phone: +49 6897 509 1174 Fax: +49 6897 509 9046 E-mail: [email protected] Regular inspection and maintenance work is indispensable for ensuring trouble-free operation and long service life for your FluidAqua Mobil. Our HYDAC Servicenter offers you these tasks within agreed-upon time frames and at fixed prices. HYDAC SERVICE GMBH Friedrichsthaler Str. 15A, Werk 13 66540 Neunkirchen-Heinitz Germany Phone: +49 681 509 9518 Fax: +49 681 509 2324 E-mail: [email protected]

FAM 10, Instructions, part 1/2 en(us) Page 61 / 68

BEWA FAM10-15 1-2 4170099 en-us 2016-10-18.doc 2016-10-18

Page 62: FAM 10 FAM 10/15 - hydac.com · FAM 10 FAM 10/15. FluidAqua Mobil Operating and maintenance instructions, ... HRB 1 7216 Executive director: Mathias Dieter, Dipl.Kfm. Wolfgang Haering

Attachment

Model Code FAM 10 M 2 a - 40 - R - H - C - a - 00 /-V Product FAM = FluidAqua Mobil Filter Size 10 = 10 l/min @ 50 Hz

12 l/min @ 60 Hz

10/15 = 15 l/min @ 50 Hz 18 l/min @ 60 Hz

Operating fluid M = Mineral oil – NBR seals I = Insulation oil – NBR seals X = HDF-R media – FKM seals B = Readily biologically degradable (on ester base)

FKM seals

Mechanical type 1 = stationary 2 = mobile (with rollers and hose holder) Voltage/frequency/power supply a = 400 V, 50 Hz, 3 Ph B = 415 V, 50 Hz, 3 Ph C = 200 V, 50 Hz, 3 Ph D = 200 V, 60 Hz, 3 Ph E = 220 V, 60 Hz, 3 Ph F = 230 V, 60 Hz, 3 Ph G = 380 V, 60 Hz, 3 Ph H = 440 V, 60 Hz, 3 Ph I = 500 V, 50 Hz, 3 Ph K = 480 V, 60 Hz, 3 Ph L = 220 V, 50 Hz, 3 Ph N = 575 V, 60 Hz, 3 Ph O = 460 V, 60 Hz, 3 Ph X = other voltage Filter size fluid filter 05 = OLF5 Type of vacuum pump R = Rotary vane

vacuum pump

Heater H = Heater z = without heater Control concept C = Comfort Instrumentation a = AquaSensor AC1 = AquaSensor + ContaminationSensor ISO4406:1999 AC2 = AquaSensor + ContaminationSensor SAE AS 4059(D) AC3 = AquaSensor + ContaminationSensor NAS 1638 Modification number 00 = You will always receive the current version. Supplementary details V = FKM seals

FAM 10, Instructions, part 1/2 en(us) Page 62 / 68

BEWA FAM10-15 1-2 4170099 en-us 2016-10-18.doc 2016-10-18

Page 63: FAM 10 FAM 10/15 - hydac.com · FAM 10 FAM 10/15. FluidAqua Mobil Operating and maintenance instructions, ... HRB 1 7216 Executive director: Mathias Dieter, Dipl.Kfm. Wolfgang Haering

Attachment

Explanation of terms and abbreviations An explanation of terms and abbreviations follows below:

%Sat. % water saturation

% saturation % water saturation

°C Degrees Celsius

°F Degrees Fahrenheit

abs. Absolute (e.g. in pressure specifications)

AC Alternating current

Air Bleed Ventilation / air bleed port

AquaSensor Sensor for water saturation in % and temperature

AS AquaSensor

ATEX ATmosphères Explosibles = Explosive atmosphere

OM Operating mode

Operation and Maintenance Instructions

Operating and Maintenance Instructions

ContaminationSensor Sensor for solid particle contamination in fluid.

CS ContaminationSensor

DC Direct current

DIN Deutsche Industrie Norm [German Industry Standard]

DN Nominal Diameter

Drain Drainage port

Rotary vane vacuum pump

Vacuum pump required as operating material for vacuum pump oil

EG European Community

ESC Escape

EU European Union

FAM FluidAqua Mobil

Solid particle contamination

Solid particles such as dirt, non-iron or metallic particles found in the fluid.

FPM (FKM / Viton®) Fluoroelastomer rubber

HFD Water-free synthetic fluids with a higher density than mineral oil or water. These fluids can cause problems with the intake

FAM 10, Instructions, part 1/2 en(us) Page 63 / 68

BEWA FAM10-15 1-2 4170099 en-us 2016-10-18.doc 2016-10-18

Page 64: FAM 10 FAM 10/15 - hydac.com · FAM 10 FAM 10/15. FluidAqua Mobil Operating and maintenance instructions, ... HRB 1 7216 Executive director: Mathias Dieter, Dipl.Kfm. Wolfgang Haering

Attachment

characteristics of pumps and attack many sealing materials. The fluid is fire resistant.

HFD-R Phosphoric acid ester

HLP Mineral oil–based hydraulic fluids with active ingredients for increasing rust protection, with high-pressure additives and aging resistance (also HLP to DIN 51 524, part 2)

IN Inlet

INLET Inlet

ISO Classification of the solid particle contamination.

kPa Kilopascal

m Meter

MAX Maximum

mbar Millibar (1 mbar = 0.001 bar)

MIN Minimum

mm Millimeter

NAS Classification of the solid particle contamination.

NBR Nitrile rubber

Nm Newton meters (torque specification)

OFF Switched off

OLF Offline filter = Bypass-flow filter unit

ON Switched on

OUT Outlet

OUTLET Outlet

Pa Pascal

PPM Parts per million (saturation specification)

PSI Pound-force per square inch

SAE Classification of the solid particle contamination.

sec seconds

PLC Programmable memory control

SW Wrench size for tools

Toploader Construction of a bypass-flow filter unit in which the filter element is removed upward.

VE101 Type of vacuum pump oil

FAM 10, Instructions, part 1/2 en(us) Page 64 / 68

BEWA FAM10-15 1-2 4170099 en-us 2016-10-18.doc 2016-10-18

Page 65: FAM 10 FAM 10/15 - hydac.com · FAM 10 FAM 10/15. FluidAqua Mobil Operating and maintenance instructions, ... HRB 1 7216 Executive director: Mathias Dieter, Dipl.Kfm. Wolfgang Haering

Attachment

Vent Ventilation / air bleed port

Water ring vacuum pump

Operating material required as operating material for water

Water Saturation Water Saturation

FAM 10, Instructions, part 1/2 en(us) Page 65 / 68

BEWA FAM10-15 1-2 4170099 en-us 2016-10-18.doc 2016-10-18

Page 66: FAM 10 FAM 10/15 - hydac.com · FAM 10 FAM 10/15. FluidAqua Mobil Operating and maintenance instructions, ... HRB 1 7216 Executive director: Mathias Dieter, Dipl.Kfm. Wolfgang Haering

Attachment

Index

A

accident prevention .............................................. 10 ambient temperature ................................ 20, 30, 60 AquaSensor ........... 22, 25, 29, 41, 42, 43, 44, 62, 63 ATEX .................................................................... 63

B

Breather filter ........................................................ 57

C

care ........................................................ 2, 6, 17, 34 Changing the filter element ................................... 42 Check valve .................................................... 25, 29 cleaning .......................................................... 23, 42 Clogging indicator ................................................. 59 Compressor oil ..................................................... 47 connecting ............................................................ 38 Connection ............................................... 19, 31, 59 Connection cable .................................................. 19 Contamination retention capacity ......................... 59 ContaminationSensor ......................... 22, 29, 62, 63 Content ................................................................... 3 Control ............................................................ 25, 62

D

degassing ................................................. 11, 19, 21 Density ................................................................. 33 Description......................... 18, 19, 25, 29, 39, 57, 58 dewatering .......................................... 11, 19, 20, 21 Dewatering ........................................................... 20 Dewatering performance ...................................... 20 Differential pressure ....................................... 29, 41 DIN ............................................... 11, 35, 42, 63, 64 Disposal ................................................................ 14 Documentation Representative .............................. 2 drain plug ........................................................ 49, 53 draining ................................................................. 49

F

Fault indicator lamp .............................................. 25 filling ...................... 21, 22, 25, 29, 35, 36, 42, 47, 48 Filter ............................................. 12, 20, 57, 59, 62 Filter element .................................................. 57, 59 Filter element type ................................................ 59 filtration ..................................................... 19, 53, 57 Float switch..................................................... 25, 29 Flow rate ......................................................... 33, 59 Fluid filter ...................................... 25, 29, 42, 57, 59 Fluid temperature ................................................. 20 Forwarding agent .................................................. 14

Function description ............................................. 21

G

Gear pump ........................................................... 59

H

Hazard symbol ....................................................... 8 Heater ....................................................... 25, 29, 62 HFD .......................................................... 11, 63, 64

I

Imprint .................................................................... 2 IN 25, 29, 32, 34, 41, 59, 64 Inlet....................................................................... 64 INLET ................................................................... 64 Inspection ............................................................. 41 installation ............................................................ 14 IP 59 IP class ................................................................. 59 ISO ................................................ 31, 35, 59, 60, 64 ISO4406 ............................................................... 62

1999 ......................................................................... 62

L

Level sensor ................................................... 25, 29 Level switch .................................................... 46, 57

M

Main switch ..................................................... 25, 39 Maintenance ........................................18, 40, 47, 63 Malfunction ........................................................... 22 Material of sealings............................................... 60 Measure ............................................................... 42 Measures .............................................................. 10 Mineral oil ............................................11, 33, 62, 64 mounting ............................................................... 30

N

NAS ................................................................ 62, 64 Noise level ............................................................ 60

O

OFF ...................................................................... 64 Offline filter ........................................................... 64 Oil filler neck ......................................................... 46 Oil separator ......................................................... 46

FAM 10, Instructions, part 1/2 en(us) Page 66 / 68

BEWA FAM10-15 1-2 4170099 en-us 2016-10-18.doc 2016-10-18

Page 67: FAM 10 FAM 10/15 - hydac.com · FAM 10 FAM 10/15. FluidAqua Mobil Operating and maintenance instructions, ... HRB 1 7216 Executive director: Mathias Dieter, Dipl.Kfm. Wolfgang Haering

Attachment

Oil sight glass ....................................................... 46 operating .. 6, 7, 8, 12, 13, 14, 21, 23, 35, 39, 43, 47,

51, 56, 63, 65 Operating elements .............................................. 39 Operation ..................... 12, 14, 18, 35, 39, 40, 45, 63 Operations control ................................................ 14 OUT .................................................... 32, 34, 59, 64 Outlet .............................................................. 30, 64 OUTLET ............................................................... 64

P

Pressure differential .............................................. 33 Pressure hose ................................................ 31, 57 Pressure sensor ....................................... 25, 29, 41 Proper/Designated Use ........................................ 11 Publisher ................................................................ 2 Pump ........................................................ 29, 35, 59

R

replacement .................................................... 43, 47 Rigid caster........................................................... 25 Rotary vane vacuum pump ......41, 46, 58, 59, 62, 63

S

SAE ................................................................ 62, 64 select ...................................................................... 7 Sensor .................................................................. 63 Service ..................................................... 54, 58, 61 setting ................................................. 21, 25, 29, 30 Signal word ............................................................. 9 signal words...................................................... 9, 10 Size ................................................................ 20, 62 Solid particle contamination .................................. 63

Spare part ............................................................. 57 Spare parts ........................................................... 57 Specialist personnel ....................................... 13, 14 Suction hose ............................................. 19, 31, 57 Suction port connection ........................................ 46 switching off .......................................................... 40 switching on .......................................................... 40 Synthetic ester ...................................................... 11

T

Temperature ................................................... 25, 29 Temperature sensor ....................................... 25, 29 to shut down ......................................................... 15 Transformer oil ..................................................... 60 Transport .............................................................. 14 transporting .......................................................... 16 troubleshooting ......................................... 14, 39, 40 Turbine oil ............................................................. 60

V

Vacuum ....................... 18, 25, 29, 35, 57, 58, 59, 63 Vacuum column .............................................. 25, 29 Vacuum pressure gauge ...................................... 57 Vacuum pump ......................... 18, 25, 29, 58, 59, 63 vacuum pump oil ........................... 30, 35, 36, 63, 64 Vane pump ........................................................... 59 Vegetable oils ....................................................... 11

W

Water content ....................................................... 20 Water ring vacuum pump ..................................... 65 Water Saturation .................................................. 65 Weight .................................................................. 59

FAM 10, Instructions, part 1/2 en(us) Page 67 / 68

BEWA FAM10-15 1-2 4170099 en-us 2016-10-18.doc 2016-10-18

Page 68: FAM 10 FAM 10/15 - hydac.com · FAM 10 FAM 10/15. FluidAqua Mobil Operating and maintenance instructions, ... HRB 1 7216 Executive director: Mathias Dieter, Dipl.Kfm. Wolfgang Haering

HYDAC FILTER SYSTEMS GMBH Industriegebiet Postfach 1251 66280 Sulzbach/Saar 66273 Sulzbach/Saar Germany Germany Phone: +49 6897 509 01 Central Fax: +49 6897 509 9046 Technical Department Fax: +49 6897 509 577 Sales Department Internet: www.hydac.com E-mail: [email protected]