fan filter unit - price industries · fan filter unit product overview before you start inspect all...
TRANSCRIPT
v100 – Issue Date: 05/15/19© 2018 Price Industries Limited. All rights reserved.
MANUAL – INSTALLATION + SERVICE
Fan Filter UnitFFU Series
ii priceindustries.com | FAN FILTER UNIT - ManualFAN FILTER UNIT - Manual | priceindustries.com
FAN FILTER UNITTABLE OF CONTENTS
Product Overview
Read & save these instructions ....................................1
Before you start ............................................................2
Introduction ..................................................................3
Installation & Service Instructions
Diffuser Module Installation ...........................................4
Speed Controllers .........................................................6
PSCSC/WK Speed Controller
Installation & Operation ..............................................6
ECMSC/WK Speed Controller
Installation & Operation ...............................................7
ECMDX/WK Speed Controller
Installation & Operation ...............................................8
BACnet Flow Controller (BFC)
Installation & Operation ..............................................10
Filter Installation ..........................................................11
Room Side Replaceable Filter (RSR) ........................11
Bench Top Replaceable Filter (BTR)) ........................13
Optional Accessories ..................................................15
Aerosol Sample Port, Static Port and
Aerosol Injection Port (INJ).......................................15
Filter/Motor Indicator LED (ML/FL) – RSR ................17
Filter/Motor Indicator LED (ML/FL) – BTR ...............19
Motor/Filter Indicator BAS (MBAS/FBAS) ................22
Service Introductions ..................................................23
Pre-Filter Cleaning ...................................................23
RSR Filter Removal and Replacement .....................24
BTR Filter Removal and Replacement .....................25
Motor Change ............................................................26
Top Access Motor/Blower Assembly .......................26
Room Side accessible Motor/Blower Assembly .......28
Technical Note: Aerosol Sample and Static Port..........32
Room Side Replaceable (RSR) ................................32
Bench Top Replaceable (BTR) .................................33
Controls ......................................................................34
ECMSC ...................................................................34
ECMDX ...................................................................37
BFC ........................................................................39
Technical Note: Design with VAV/Constant Flow Boxes
and Ducted Applications .............................................41
Balancing ...................................................................42
Un-ducted Supply Units ..........................................42
Ducted Supply – Pressure Independent and
Dependent Airflow Control .......................................43
Ducted Supply – Pressure Independent and
Dependent Airflow Control .......................................45
Troubleshooting ..........................................................46
Changing Motor Programs ......................................46
Tips .........................................................................47
BTR Unit Replacement Parts ......................................48
RSR Unit Replacement Parts ......................................49
Wiring Diagrams .........................................................50
Warranty .....................................................................61
priceindustries.com | FAN FILTER UNIT - Manual
FAN FILTER UNITPRODUCT OVERVIEW
priceindustries.com | FAN FILTER UNIT - Manual
Read and Save These InstructionsWarning! To reduce the risk of fire, electrical shock, or injury to persons, observe the following:
A. Installation work and electrical wiring must be done by qualified person(s) in accordance with all applicable codes and standards, including fire-rated construction.
B. When cutting or drilling into wall or ceiling, do not damage electrical wiring and other hidden utilities.
C. Use this unit only in the manner intended by the manufacturer. If you have any questions, contact the manufacturer:
In the United States2975 Shawnee Ridge CourtSuwanee, Georgia USA 30024Ph: 770.623.8050 Fax: 770.623.6404
In Canada / International Export Sales Office638 Raleigh StreetWinnipeg, Manitoba Canada R2K 3Z9Ph: 204.669.4220 Fax: 204.663.2715
D. Before servicing or cleaning unit, switch power off at service panel and lock service panel to prevent power from being switched on accidentally.
E. To reduce the risk of injury to persons, install the unit at least 7ft above grade or in ceiling.
1priceindustries.com | FAN FILTER UNIT - Manual
FAN FILTER UNITPRODUCT OVERVIEW
Before You StartInspect all cartons and boxes for flaws and shipping damages.
If anything is discovered to be damaged, contact the shipping company and file a freight claim.
Ensure that all HEPA/ULPA filters are stored in a clean, dry location in a vertical position, as labeled on the carton.
Ensure ductwork is balanced to scheduled flow prior to proceeding.
NOTE: Extreme caution should be taken to avoid contact with filter media. Touching filter media may result in filter failure. Damage to filters can occur during installation or during leak qualification testing. The filters supplied by Price have been 100% tested and certified by the manufacturer to be free of defects and leaks. Price cannot accept responsibility for damage that occurs after shipment, whether through transit, handling or installation, and will not replace filters under Price standard warranty.
To ensure fan filter units are properly balanced, read Technical Note: Design with VAV/Constant Flow Boxes and Ducted Applications prior to starting installation.
A minimum of two (2) people will be required to install the filters.
2 priceindustries.com | FAN FILTER UNIT - ManualFAN FILTER UNIT - Manual | priceindustries.com
FAN FILTER UNITPRODUCT OVERVIEW
IntroductionPrice Fan Filter Units (FFU) are ceiling module diffusers consisting of a fan/motor assembly and Roomside Removable (RSR), or Bench Top Replaceable (BTR) filters. The module is designed to provide unidirectional vertical airflow of filtered, clean air over a cleanroom space.
Fan Filter Units (FFU) models will have three (3) stickers located on the back of the plenum. For ease of troubleshooting assistance, replacement parts, and general factory assistance, it is recommended that the order number, and model line string be used as reference. This information can be found on the Factory Label.
ETL LABEL
FACTORY LABEL
FACTORY PERFORMANCE LABEL
SPEED CONTROLLER
EYEBOLT
OPTIONAL PRE-FILTER
OPTIONAL DUCT COLLAR
MOTOR/BLOWER ASSEMBLY
3priceindustries.com | FAN FILTER UNIT - Manual
FAN FILTER UNITINSTALLATION & SERVICE INSTRUCTIONS
Diffuser Module InstallationThe Price FFU will come completely assembled from the factory with the exception of the HEPA/ULPA filters, which will ship in its own carton, and the speed controller wall kits (if selected).
NOTE: Do not open the HEPA/ULPA filters until they are ready to be installed in the FFU units. All construction in the space should be complete, the site and upstream air should be clean so as not to unnecessarily load the filter.
Sample line string for Room Side Replaceable filter:
FFU-1-X//I/24/48/RSR/FC/ECM/115/10//CF//HEPA//BFC////DSW-115////RMB/ASSP/INJ//FL+ML+BACnet///WPFH/PL-AL/F-AL//PL-B12/F-B12
STEP 1: Remove FFU from shipping carton and inspect for any damage.
NOTE: Ensure the HEPA/ULPA filter has been safely stored in a vertical position, per carton label, until ready for use.
STEP 2: If unit is Bench Top Replaceable (BTR) refer to page 13 for filter installation prior to proceeding. Once BTR filter is installed, proceed to the next step. If unit is Room Side Replaceable (RSR), proceed directly to next step.
Sample line string for Bench Top Replaceable filter: FFU-1-X//I/24/48/BTR/FC/ECM/115/10//CF//HEPA//BFC////DSW-115////TMB/ASSP///FL+ML+BACnet///WPFH/PL-AL///PL-B12/
STEP 3: Raise the unit through the ceiling grid at an angle until entire unit is above the grid
STEP 4: Lower unit onto the backside of the tees.
STEP 5: Secure the unit to the overhead structure using the eyebolts located on the back of the unit.
FIGURE 1: UNIT UNPACKING
4 priceindustries.com | FAN FILTER UNIT - ManualFAN FILTER UNIT - Manual | priceindustries.com
FAN FILTER UNITINSTALLATION & SERVICE INSTRUCTIONS
FIGURE 2: UNIT EYEBOLTS FOR MOUNTING
STEP 6: Adjust and level the unit so that it rests on the tees and there is adequate compression on the gasket to warrant a tight seal.
Ensure that ceiling grid is properly gasket/sealed to prevent infiltration of unfiltered air from the ceiling plenum into the room side.
Above steps are manufacturer's suggested hanging techniques, always make sure to follow all local building codes, including seismic, where applicable.
STEP 7: Refer to Factory Label to determine which speed controller is on the unit and use the following table for appropriate reference page for the particular speed controller on your unit.
Sample line string:
FFU-1-X//I/24/48/RSR/FC/ECM/115/10//CF//HEPA//BFC////DSW-115////RMB/ASSP/INJ//FL+ML+BACnet///WPFH/PL-AL/F-AL//PL-B12/F-B12
Speed Controller Page Reference
PSCSC/WK 6
ECMSC/WK 7
ECMDX/WK 8
BFC 10
NOTE: Depending on unit ordered, speed controller will be mounted on the unit itself, or, if a wall-kit option was selected, shipped loose for field installation
5priceindustries.com | FAN FILTER UNIT - Manual
FAN FILTER UNITINSTALLATION & SERVICE INSTRUCTIONS
Speed ControllersPSCSC/WK Speed Controller Installation & Operation
Sample line string:
FFU-1-X//I/24/48/BTR/FC/PSC/115/10////HEPA//PSCSC//WK-PSC//DSW-115////TMB/ASSP//////WPFH/PL-AL///PL-B12/
If unit does not have the wall kit (WK) option, proceed to step 11A.
Sample line string:
FFU-1-X//I/24/48/BTR/FC/PSC/115/10////HEPA//PSCSC/////DSW-115////TMB/ASSP//////WPFH/PL-AL///PL-B12/
STEP 8A: Locate pre-installed electric box for wall-mounted speed controller.
STEP 9A: Wire speed controller according to wiring diagram found on page 57. Wall-mounted speed controller will be wired in series with the motor.
NOTE: Wiring should be carried out by a certified electrician and meet national and local electrical codes.
STEP 10A: Attach the wall-mounted controls faceplate to the electrical box using the screws provided.
STEP 11A: Wire the unit according to appropriate wiring diagram. If Power Cord (PC) option is selected, simply insert plug end into electrical socket.
Sample line string:
FFU-1-X//I/24/48/BTR/FC/PSC/115/10////HEPA//PSCSC/////DSW-115/PC-115///TMB/ASSP//////WPFH/PL-AL///PL-B12/
NOTE: Wiring should be carried out by a certified electrician and meet national and local electrical codes.
STEP 12A: If using RSR filter, refer to page 11 for filter installation instructions.
NOTE: Ensure that the space is clean, free of debris, and ducts are cleaned and ready for operation prior to installation of filter.
STEP 13A: Ensure proper voltage is hooked up to the unit.
STEP 14A: Proceed to controls and balancing section on page 42.
NOTE: Clockwise rotation will increase airflow, counter-clockwise rotation will decrease airflow.
NOTE: If unit is ducted, refer to Technical Note: Balancing Ducted Units on page 44 of this manual.
FIGURE 3: PSC SPEED CONTROLLER WITH WALL KIT OPTION
6 priceindustries.com | FAN FILTER UNIT - ManualFAN FILTER UNIT - Manual | priceindustries.com
FAN FILTER UNITINSTALLATION & SERVICE INSTRUCTIONS
ECMSC/WK Speed Controller Installation and Operation
Sample line string below:
FFU-HE/24/48/RSR/BC/ECM/115/10//CT//HEPA//ECMSC// WK /DSW/PC/TMB/ATS/ML/FL/WPF/PL-AL/F-AL/PL-B12/F-B12
If unit does not have the wall kit (WK) option, proceed to STEP 11B.
Sample line string:
FFU-1-X//I/24/48/RSR/FC/ECM/115/10//CF//HEPA//ECMSC/////DSW-115////RMB/ASSP//////WPFH/PL-AL/F-AL//PL-B12/F-B12
STEP 8B: Locate pre-installed electrical box for wall-mounted speed controller.
STEP 9B: Wire speed controller according to wiring diagram found on page 58 - 60. Motor speed controller will have color coded wires and must be wired to the matching colors on the wall-mounted portion.
NOTE: Wiring should be carried out by a certified electrician and meet national and local electrical codes.
STEP 10B: Attach the wall-mounted controls faceplate to the electrical box using the screws provided.
STEP 11B: Wire the unit according to appropriate wiring diagram. If Power Cord (PC) option is selected, simply insert plug end into electrical socket.
Sample line string:
FFU-1-X//I/24/48/RSR/FC/ECM/115/10//CF//HEPA//ECMSC//WK-ECMSC//DSW-115//PC-115/RMB/ASSP//////WPFH/PL-AL/F-AL//PL-B12/F-B12
NOTE: Wiring should be carried out by a certified electrician and meet national and local electrical codes.
STEP 12B: If using RSR filter, refer to page 11 for filter installation instructions.
NOTE: Ensure that the space is clean, free of debris, and that ducts are cleaned and ready for operation prior to installation of filter
STEP 13B: Ensure proper Voltage is hooked up to the unit.
STEP 14B: Proceed to controls and balancing section on pages 42.
FIGURE 4: ECMSC/WK
7priceindustries.com | FAN FILTER UNIT - Manual
FAN FILTER UNITINSTALLATION & SERVICE INSTRUCTIONS
Speed ControllersECMDX/WK Speed Controller Installation and Operation
Sample line string:
FFU-HE/24/48/RSR/BC/ECM/115/10//CT//HEPA//ECMDX// /DSW/PC/TMB/ATS/ML/FL/WPF/PL-AL/F-AL/PL-B12/F-B12
If unit does not have the wall kit (WK) option, proceed to STEP 11C.
Sample line string:
FFU-HE/24/48/RSR/BC/ECM/115/10//CT//HEPA//ECMDX//WK/DSW/PC/TMB/ATS/ML/FL/WPF/PL-AL/F-AL/PL-B12/F-B12
STEP 8C: Locate pre-installed electrical box for wall-mounted speed controller.
NOTE: Wall kit must be mounted horizontally, as shown above.
STEP 9C: Wire unit according to wiring diagram found on page 58 - 60. Motor speed controller will have color coded wires and must be wired to the matching colors on the wall-mounted portion.
NOTE: 24VAC and COMMON will need to be run from the terminal block in the control box to the terminals listed 24VAC HOT, and COMMON on the wall-mounted portion.
NOTE: Wiring should be carried out by a certified electrician and meet national and local electrical codes.
STEP 10C: Attach the wall-mounted controls faceplate to the electrical box using the screws provided.
STEP 11C: Wire the unit according to appropriate wiring diagram. If Power Cord (PC) option is selected, simply insert plug end into electrical socket
FIGURE 5: ECMDX WALL KIT SPEED CONTROLLER
FIGURE 6: ECMDX WALL KIT SPEED CONTROLLER
8 priceindustries.com | FAN FILTER UNIT - ManualFAN FILTER UNIT - Manual | priceindustries.com
FAN FILTER UNITINSTALLATION & SERVICE INSTRUCTIONS
Sample line string:
FFU-HE/24/48/RSR/BC/ECM/115/10//CT//HEPA//ECMSC///DSW/PC/TMB/ATS/ML/FL/WPF/PL-AL/F-AL/PL-B12/F-B12
NOTE: Wiring should be carried out by a certified electrician and meet national and local electrical codes.
STEP 12C: If using RSR filter, refer to page 11 for filter installation instructions.
NOTE: Ensure that the space is clean, free of debris, and that ducts are cleaned and ready for operation prior to installation of filter
STEP 13C: Ensure proper Voltage is hooked up.
NOTE: ECMDX Speed Controllers have multiple modes, which are listed below:
Display Mode Range
L.SEt Local Set point – Manual speed adjust mode (use UP / DOWN to adjust) 0 - 100%
rPnRPM – Shows current RPM of motor 1
If E001 – no RPM pulses are being read, check 6 position cableIf E002 – RPM reading is above 2000 RPM, check primary air
0 - 2500 RPM
bAS.r BAS Remote – BAS Mode – Voltage signal (Max reading is 9.99 VDC) 0 - 9.99 VDC
bAS.S BAS Set point – Current BAS set point 0 - 100%
STEP 14C: Proceed to controls and balancing section on page 42.
TABLE I: ECMDX SPEED CONTROLLER DISPLAY CODES
9priceindustries.com | FAN FILTER UNIT - Manual
FAN FILTER UNITINSTALLATION & SERVICE INSTRUCTIONS
Speed ControllersBACnet Flow Controller (BFC) Installation and Operation
Sample line string:
FFU-1-1//I/24/48/RSR/FC/ECM/115/10//CF//HEPA//BFC////DSW-115////RMB/ASSP/INJ//FL+ML+BACnet///WPFH/PL-AL/F-AL//PL-B12/F-B12
STEP 8D: Wire unit according to appropriate wiring diagram. If Power Cord (PC) option is selected, simply insert plug end into electrical socket.
NOTE: Polarity is important and must be observed. It is also vital that the 24 VAC common side of the transformer be Earth grounded.
STEP 9D: Hook up applicable BACnet, and/or local Building Automation System (BAS) according to wiring diagram found on page 58 - 60. Multiple units can be daisy chained together using optional RJ45 cables. If using BAS or Local Set point, reference the BFC controls section on page 39 for applicable instructions.
NOTE: For additional information on BACnet, and the BFC controller, refer to the BACnet Wiring Guidelines, and BFC Manual which are available on the Price Industries website @ priceindustries.com
STEP 10D: Wire the unit according to the appropriate wiring diagram found on page 58 – 60. If power cord option is selected, simply insert the plug end into the electric socket.
Sample line string:
FFU-1-1//I/24/48/RSR/FC/ECM/115/10//CF//HEPA//BFC////DSW-115//PC-115//RMB/ASSP/INJ//FL+ML+BACnet///WPFH/PL-AL/F-AL//PL-B12/F-B12
NOTE: Wiring should be carried out by a certified electrician and meet national and local electrical codes.
STEP 11D: If using RSR filter, refer to page 11 for installation instructions.
NOTE: Ensure that the space is clean, free of debris, and that ducts are cleaned and ready for operation prior to installation of filter.
STEP 12D: Ensure proper Voltage is hooked up to the unit.
STEP 13D: Proceed to controls and balancing section on page 42.
FIGURE 7: DAISY CHAINED FFU UNITS
10 priceindustries.com | FAN FILTER UNIT - ManualFAN FILTER UNIT - Manual | priceindustries.com
FAN FILTER UNITINSTALLATION & SERVICE INSTRUCTIONS
Filter Installation Room Side Replaceable Filter (RSR)
Sample line string:
FFU-1-1//I/24/48/RSR/FC/ECM/115/10//CF//HEPA//BFC////DSW-115//PC-115//RMB/ASSP/INJ//FL+ML+BACnet/// WPFH/PL-AL/F-AL//PL-B12/F-B12
NOTE: Extreme caution should be taken to avoid contact with filter media. Touching filter media may result in filter failure. Damage to filters can occur during installation or during leak qualification testing. The filters supplied by Price have been 100% tested and certified by the manufacturer to be free of defects and leaks. Price cannot accept responsibility for damage that occurs after shipment, whether through transit, handling or installation, and will not replace filters under our standard warranty. shipment, whether through transit, handling or installation, and will not replace filters under our standard warranty.
STEP 2
STEP 4
STEP 1
STEP 3
Remove filter from box using handles Place filter on flat surface or table.
Cut plastic bag and remove filter with care. To handle the filter, grasp by the frame only.
11priceindustries.com | FAN FILTER UNIT - Manual
FAN FILTER UNITINSTALLATION & SERVICE INSTRUCTIONS
STEP 7
STEP 5
STEP 6
STEP 8
Loosen cam locks on diffuser to prepare filter for installation. Be sure latches are turned inwards so as not to interfere with filter frame.
NOTE: Note location of filter alignment guides (minimum one per side, dependent on size).
Raise the filter in place using two people and being careful not to contact the filter media.
Secure filter in place using the cam locks. Tighten until no further rotations can be made. No tools are required to tighten, and using one may cause damage to filter gel seal.
Ensure HEPA filter outer frame is in contact with horizontal knife edge of frame. Note that diffuser knife edge cannot bottom out in HEPA filter gel seal.
Using the alignment guides, raise the filter into place, ensuring filter gel seal channel seat into knife edge of plenum.
NOTE: Do not bottom out gel seal in plenum knife edge. The gel seal needs to ‘float’ in gel seal to ensure proper seal.
FILTER MEDIA
GEL SEAL
CONTACT POINT
CAM LOCK
HEPA FILTER OUTER FRAME
KNIFE EDGE
12 priceindustries.com | FAN FILTER UNIT - ManualFAN FILTER UNIT - Manual | priceindustries.com
FAN FILTER UNITINSTALLATION & SERVICE INSTRUCTIONS
Filter Installation Bench Top Replaceable Filter (BTR)
Sample line string:
FFU-1-1//I/24/48/BTR/FC/ECM/115/10//CF//HEPA//BFC////DSW-115//PC-115//TMB/ASSP///FL+ML+BACnet/// WPFH/PL-AL///PL-B12/
NOTE: Extreme caution should be taken to avoid contact with filter media. Touching filter media may result in filter failure. Damage to filters can occur during installation or during leak qualification testing. The filters supplied by Price have been 100% tested and certified by the manufacturer to be free of defects and leaks. Price cannot accept responsibility for damage that occurs after shipment, whether through transit, handling or installation, and will not replace filters under our standard warranty.
NOTE: If ordered with Filter or Motor LED Indicator (ML/FL), refer to LED installation instructions which must be done at same time as filter installation.
FFU-HE/24/48/BTR/BC/ECM/115/10//CT//HEPA//ECMDX//WK/DSW/PC/TMB///ML/FL/WPF/PL-AL///PL-MILL//
STEP 2 STEP 1
Place filter box on floor, careful to set box in correct orientation, as per the arrow.
Remove filter from box being careful not to touch filter media.
STEP 4 STEP 3
Place the filter gently on the floor, remove the tape, and take the filter out of the bag.
Place filter on a flat, clean, protecting surface with the expanded face screen on the bottom. Make sure to protect face LED if this has been selected as an option.
13priceindustries.com | FAN FILTER UNIT - Manual
FAN FILTER UNITINSTALLATION & SERVICE INSTRUCTIONS
STEP 6 STEP 5
Place FFU top cap assembly onto filter’s gasket flange/ frame, being careful to not damage the filter media.
Attach filter to top cap assembly by hooking and securing latches. Gasket may need to be compressed to grab channel with latch.
14 priceindustries.com | FAN FILTER UNIT - ManualFAN FILTER UNIT - Manual | priceindustries.com
FAN FILTER UNITINSTALLATION & SERVICE INSTRUCTIONS
UNIT PORT LOCATIONS
ATS PORT
KNIFE EDGE
STATIC PRESSURE PORT DIFFUSER FACE
FRAME
Optional AccessoriesAerosol Sample Port, Static Port and Aerosol Injection Port (INJ)
Sample line string below:
FFU-HE/24/48/RSR/BC/ECM/115/10//CT//HEPA//ECMDX//WK/DSW/PC/TMB/ATS/ML/FL/WPF/PL-AL/F-AL/PL-B12/F-B12
STEP 1: If unit has room side removable filter (RSR), remove diffusers perforated face by turning quarter turn fasteners holding face in place.
FFU-HE/24/48/RSR/BC/ECM/115/10//CT//HEPA//ECMDX//WK/DSW/PC/TMB/ATS/ML/FL/WPF/PL-AL/F-AL/PL-B12/F-B12
NOTE: Safety cables will be attached to the diffuser face, but care should be taken to ensure that diffuser face does not swing and injure anyone.
If unit is bench top removable (BTR), proceed to next step.
STEP 2: Remove threaded plug covering ATS port using a 5/16” hex screw driver.
STEP 3: Insert aerosol test fitting or adaptor (the aerosol injection port has a 3/8” NPT internal thread) into Aerosol Injection port.
NOTE: An adaptor/test fitting that is longer than 1.5” and/or wider than 1” will not fit.
STEP 4: Inject aerosol test agent and measure particulate counts according to local codes.
NOTE: Aerosol Sample port can be used to measure upstream particle counts. Refer to page 15 for static pressure port details.
STEP 5: Disconnect test equipment, and reinstall plugs in the static pressure (if applicable) and aerosol injection ports. Reinstall diffuser face (if applicable).
If the safety cables were also disconnected when removing the face, they must be reattached. When reinstalling the face, care should be taken to tuck safety cables in place without damaging the filter.
NOTE: Airflow and aerosol challenge concentration should be kept uniform during the test. Static pressure and concentration may be sampled through the static pressure port during the test, if required, to verify flow and concentration.
15priceindustries.com | FAN FILTER UNIT - Manual
FAN FILTER UNITINSTALLATION & SERVICE INSTRUCTIONS
TABLE II outlines a few possible problems that may be encountered during leakage testing. This chart is intended as a quick troubleshooting guide, and is not exhaustive. All local and applicable codes should be followed.
Display Mode Range
Leakage at the perimeter of the filter
Improper filter installationGently remove the filter, verify that the gel seal is intact and
undam- aged, and carefully reseat the filter in the knife edge frame and latch in place.
Pinhole leaks detected in filterImproper handling of
filter/damage during installationFilter may be repaired by a trained technician.
Leakage at the perimeter of the fan filter unit
Improper seal between unit and ceiling plenum
Check seal between unit and ceiling plenum and seal as required.
Particle Counter is beeping at multiple locations, even away from
filter face
Possible leakage through adjacent lights, diffusers, and/or
ceiling panels
Isolate unit by placing cardboard or sheet metal to create vertical 'walls' extending 2ft below the ceiling plane. If filter passes, sealing of adjacent lights, diffusers, and/or ceiling
panels may be required.
TABLE II: LEAKAGE TEST OUTCOMES & POSSIBLE SOLUTIONS
16 priceindustries.com | FAN FILTER UNIT - ManualFAN FILTER UNIT - Manual | priceindustries.com
FAN FILTER UNITINSTALLATION & SERVICE INSTRUCTIONS
Filter/Motor Indicator LED (ML/FL) – RSRSample line string:
FFU-1-1//I/24/48/RSR/FC/ECM/115/10//CF//HEPA//BFC////DSW-115//PC-115//RMB/ASSP/INJ//FL+ML+BACnet/// WPFH/PL-AL/F-AL//PL-B12/F-B12
LED Operation
Option CodeLED
ColorAction Notes
Filter LED FLGreen None Indicates normal operation until filter pressure drop exceeds
calibrated pressure drop (factory set at 1.5x clean filter pressure).
Yellow Change FilterIndicates filter pressure drop has exceeded calbirated setting (factory set at 1.5x clean filter pressure.
Motor LED
MLGreen None
Indicates normal motor operation when the static pressure is above 0.2" w.g.
Red Troubleshoot Motor Indicates motor is not in operation, and that unit static pressure is below 0.2" w.g.
Calibration
Filter LED will come factory set to activate at the pressure drops listed in the Table below.
Filter Pressure @ 90fpm [in w.g.] 1.5x Clean Filter [in w.g.]
HEPA 0.4 0.6
ULPA 0.6 0.9
If different set points are desired, they can be adjusted as follows:
STEP 1: Remove Loctite from adjustment screw hole.
FIGURE 9: PRESSURE SWITCH ADJUSTMENT SCREW.
Filter Indicator Set Points
17priceindustries.com | FAN FILTER UNIT - Manual
FAN FILTER UNITINSTALLATION & SERVICE INSTRUCTIONS
STEP 2: Calculate number of turns required based on difference between factory set point and desired set point using the following chart.
Example:
HEPA filter with desired set point of 0.9 in w.g.
Number of turns at 0.9 in w.g. = 4
Number of turns at factory set point of 0.6 in w.g. = 2.2
Number of turns to field set = 4 – 2.2 = 1.8 (approximately)
NOTE: Maximum available pressure setting is 1.0” w.g. Do not exceed 4 ½ turns (total).
STEP 3: Turn screw clockwise the number of turns calculated above. You will need a 1.5mm hex Allen wrench
STEP 4: To check filter pressure set point and/or to fine tune, insert Magnehelic gauge into the static pressure port (located along knife edge of diffuser – diffuser face must be removed to access).
STEP 5: Using an obstruction (piece of cardboard or equivalent), slowly increasing pressure on the unit by blocking off more and more of the diffuser face until the LED turns from green to yellow.
STEP 6: Take pressure measurement at point the LED changed color and rotate the adjustment screw until desired pressure set point is reached.
FIGURE 10: RSR FILTER LED SET POINT ADJUSTMENT.
Set P
oint
in In
ches
w.g
.
Turns of Set Point Adjustment Screw(from starting point at 0.25” w.g.)
1.00
0.90
0.80
0.70
0.60
0.50
0.40
0.30
0.20
0.10
0.00
Table 2. Set Point Adjustment
Turns of Set Point Adjustment Screw(from starting point at 0.25” w.g.)
Set P
oin
t in
in
ch
es w
.g.
0 1 2 3 4 5
1.000.900.800.700.600.500.400.300.200.100.00
0 1 2 3 4 5
18 priceindustries.com | FAN FILTER UNIT - ManualFAN FILTER UNIT - Manual | priceindustries.com
FAN FILTER UNITINSTALLATION & SERVICE INSTRUCTIONS
Filter/Motor Indicator LED (FL/ML) – BTRSample line string:
FFU-1-1//I/24/48/BTR/FC/ECM/115/10//CF//HEPA//BFC////DSW-115//PC-115//TMB/ASSP///FL+ML+BACnet/// WPFH/PL-AL///PL-B12/
LED Operation
Option CodeLED
ColorAction Notes
Filter LED FLGreen None Indicates normal operation until filter pressure drop exceeds
calibrated pressure drop (factory set at 1.5x clean filter pressure).
Yellow Change FilterIndicates filter pressure drop has exceeded calbirated setting (factory set at 1.5x clean filter pressure).
Motor LED
MLGreen None
Indicates normal motor operation when the static pressure is above 0.2" w.g.
Red Troubleshoot Motor Indicates motor is not in operation, and that unit static pressure is below 0.2" w.g.
FIGURE 12: STATIC PRESSURE PORT. FIGURE 11: CABLE ASSEMBLY.
Installation
STEP 1: Remove BTR filter from box by following the instructions found on page 23 of this installation manual.
STEP 2: Take LED cable assembly out of FFU-HE Plenum
STEP 3: Remove well nut in center port of BTR filter.
19priceindustries.com | FAN FILTER UNIT - Manual
FAN FILTER UNITINSTALLATION & SERVICE INSTRUCTIONS
STEP 4: Remove threaded standoff and lock washer from LED cable assembly.
THREADED STANDOFF
LOCK WASHER
RUBBER WASHER
METAL WASHER
LED
FIGURE 13: LED THREADED STANDOFF. FIGURE 14: FILTER POSITION FOR LED INSTALLATION.
FIGURE 15: BTR FACE INSTALLED LED.
STEP 5: Thread cable through static pressure port on face of BTR filter.
NOTE: It is recommended to rest the filter frame on 2x4 lumber to protect the LED light from breaking.
STEP 6: Put lock washer and threaded standoff back on cable and tighten to LED.
20 priceindustries.com | FAN FILTER UNIT - ManualFAN FILTER UNIT - Manual | priceindustries.com
FAN FILTER UNITINSTALLATION & SERVICE INSTRUCTIONS
STEP 7: With two (2) people holding the unit, pull cable back through plenum until plenum can rest on top of filter.
STEP 8: Refer to BTR Filter Instructions found on page 13 for proper filter installation.
STEP 9: Refer to wiring diagram (located in control box) to connect LED leads to terminal block.
NOTE: If unit has BFC speed controller, LED leads will need to be connected to the BFC controller instead of the terminal block.
Calibration
All pressure transducers are factory calibrated. If a different pressure transducer set point is desired, refer to page 17.
FIGURE 17: CABLE ASSEMBLY.
FIGURE 16: THREADED STANDOFF THROUGH FILTER CHANNEL.
21priceindustries.com | FAN FILTER UNIT - Manual
FAN FILTER UNITINSTALLATION & SERVICE INSTRUCTIONS
Motor/Filter Indicator BAS (MBAS/FBAS)Sample line string below:
FFU/24/48/RSR/BC/ECM/115/10//CT//HEPA//ECMDX//WK/DSW/PC/TMB/ATS/MBAS/FBAS/WPF/PL-AL/F-AL/PL-B12/F-B12
Operation
Option Code Action Notes
Motor BAS MBASTroubleshoot
MotorCloses a dry contact to let the BAS signal pass through when the static pressure is less than 0.2" w.g. indicating the motor is not operating.
Filter BAS FBASChange
Filter
Closes a dry contact to let the BAS signal pass through when the static pressure is greater than the calibrated pressure drop (factory set at 1.5x clean filter).
Unit will come factory calibrated; no additional field modifications are required.
Wire unit terminal block according to wiring diagrams found starting on page 50 onwards in this manual.
NOTE: Wiring should be carried out by a certified electrician and meet national and local electrical codes.
FFU-HE
Pressure switch(es) completes signal when failure is reached (as per chart above)
BAS Signal In
FIGURE 18: MBAS/FBAS PRESSURE SWITCH DIAGRAM.
22 priceindustries.com | FAN FILTER UNIT - ManualFAN FILTER UNIT - Manual | priceindustries.com
FAN FILTER UNITINSTALLATION & SERVICE INSTRUCTIONS
Service InstructionsPre-Filter Cleaning
NOTE: Disconnect the unit from the electrical power source before attempting any service. Electrical service should be performed by a licensed electrician or authorized service technician.
NOTE: When performing any type of maintenance on the FFU be careful to reduce as much as possible the potential for introducing the internals of the unit to dirt, dust, and debris that may be present in the unit’s external environment.
STEP 1: Gain access to the top of the unit by removing adjacent ceiling, or access panel.
STEP 2: Remove filter by pushing filter to one side and sliding it out from under the brackets (non-ducted), or remove filter access door (ducted). Reference the below figures for further details.
STEP 3: Clean pre-filter by hand washing in water with a mild detergent or by using a vacuum cleaner. Allow pre-filter to dry completely before replacing.
STEP 4: Reverse above steps to install the pre-filter.
FIGURE 19: NON-DUCTED UNIT FILTER REMOVAL.
FIGURE 20: DUCTED UNIT FILTER REMOVAL.
23priceindustries.com | FAN FILTER UNIT - Manual
FAN FILTER UNITINSTALLATION & SERVICE INSTRUCTIONS
RSR Filter Removal and ReplacementReplacement filters can be ordered through your local Sales Representative. Visit Price Industries website to locate your local representative (http://www.priceindustries.com/contact/reps-dealers).
STEP 1: Remove diffuser perforated face by turning quarter turn fasteners holding face in place.
NOTE: Safety cables will be attached to the diffuser face, but care should be taken to ensure that diffuser face does not swing and injure anyone.
STEP 2: Remove filter by loosening cam latch bolts (filter retainer clips) by turning counter clockwise using your hands.
STEP 3: Turn all cam latch filter retainers to the open position
STEP 4: Remove filter by handling frame; do not touch filter media if re-using filter.
NOTE: Extreme caution should be taken when removing the filter if the filter is to be reinstalled. Touch the filter by the frame only; never touch the filter media as it can damage the filter.
STEP 5: Follow the step on page 21, Installation of RSR Filters to install new filter.
FIGURE 21: DIFFUSER FACE WITH QUARTER TURN FASTENERS.
FIGURE 22: CAM LATCH BOLTS.
24 priceindustries.com | FAN FILTER UNIT - ManualFAN FILTER UNIT - Manual | priceindustries.com
FAN FILTER UNITINSTALLATION & SERVICE INSTRUCTIONS
2.5.3. BTR Filter Removal and ReplacementReplacement filters can be ordered through your local Sales Representative. Visit Price Industries website to locate your local representative (http://www.priceindustries.com/contact/reps-dealers).
STEP 1: Remove unit from ceiling, gently placing FFU on a clean, dry surface.
NOTE: If the FL or ML filter option has been selected, it is recommended to rest the filter frame on 2x4 lumber to protect the LED light.
STEP 2: Unhook latches attaching bench top replaceable filter to fan filter body.
STEP 3: Remove filter by handling frame; do not touch filter media if re-using filter.
NOTE: Extreme caution should be taken when removing the filter if the filter is to be reinstalled. Touch the filter by the frame only; never touch the filter media as it can damage the filter.
STEP 4: For installation of new filter, follow steps on page 13.
FIGURE 23: FILTER LATCHES.
25priceindustries.com | FAN FILTER UNIT - Manual
FAN FILTER UNITINSTALLATION & SERVICE INSTRUCTIONS
Motor ChangeTop Access Motor/Blower Assembly
Sample line string:
FFU-1-X//I/24/48/RSR/BC/ECM/115/10//CT//HEPA//ECMSC//WK-ECMSC//DSW-115//PC-115//TMB/ASSP/INJ/////WPFH/PL-AL/F-AL//PL-B12/F-B12
NOTE: Disconnect the unit from the electrical power source before attempting any service. Electrical service should be performed by a licensed electrician or authorized service technician.
NOTE: When performing any type of maintenance on the FFU, be careful to reduce as much as possible the potential for introducing the internals of the unit to dirt, dust, and debris that may be present in the unit’s external environment.
STEP 1: Gain access to the top of the unit by removing adjacent ceiling, or access panel.
STEP 2: Remove filter by pushing filter to one side and sliding it out from under the brackets (non-ducted), or remove the duct collar/pre-filter housing and pre-filter (if applicable) via screws (ducted) to expose motor assembly. Reference the below figures for further detail.
FIGURE 24: UN-DUCTED UNIT FILTER REMOVAL.
FIGURE 25: DUCTED UNIT FILTER REMOVAL.
26 priceindustries.com | FAN FILTER UNIT - ManualFAN FILTER UNIT - Manual | priceindustries.com
FAN FILTER UNITINSTALLATION & SERVICE INSTRUCTIONS
STEP 3: Make note of all wire locations for re-installation later. It is recommended to take a picture of all applicable wires.
STEP 4: Open control box and disconnect wires at the terminal block, referencing applicable wiring diagram.
STEP 5: Remove the 6 bolts to free the motor/blower assembly, using a 7/16” socket wrench (or equivalent).
STEP 6: Remove motor/blower assembly.
STEP 7: Inspect and/or replace parts.
STEP 8: Replace with the new motor/blower assembly and reassemble by reversing the above steps.
NOTE: For information on how to order replacement motor/blowers, contact your local Price Sales Representative. Visit Price’s website (http://www.priceindustries.com/contact/reps-dealers) to locate your local Representative.
STEP 9: Double check airflow to ensure that set point has not changed.
FIGURE 26: MOTOR - BLOWER ASSEMBLY.
27priceindustries.com | FAN FILTER UNIT - Manual
FAN FILTER UNITINSTALLATION & SERVICE INSTRUCTIONS
Room Side Accessible Motor/Blower AssemblySample line string:
FFU-1-X//I/24/48/RSR/FC/ECM/115/10//CF//HEPA//BFC////DSW-115//PC-115//RMB/ASSP/INJ//FL+ML+BACnet///WPFH/PL-AL/F-AL//PL-B12/F-B12
NOTE: Disconnect the unit from the electrical power source before attempting any service. Electrical service should be performed by a licensed electrician or authorized service technician.
NOTE: Disconnect the unit from the electrical power source before attempting any service. Electrical service should be performed by a licensed electrician or authorized service technician.
STEP 1: Remove diffuser perforated face by turning quarter turn fasteners holding face in place.
NOTE: Safety cables will be attached to the diffuser face, but care should be taken to ensure that diffuser face does not swing and injure anyone.
STEP 2: Remove filter by loosening cam latch bolts (filter retainer clips) by turning counter clockwise using your hands, or hex key as required to fully tighten latches.
STEP 3: Turn all cam latch filter retainers to the open position.
STEP 4: Remove filter by handling frame; do not touch filter media.
FIGURE 27: DIFFUSER FACE WITH QUARTER TURN FASTENERS.
FIGURE 28: CAM LATCH BOLTS.
28 priceindustries.com | FAN FILTER UNIT - ManualFAN FILTER UNIT - Manual | priceindustries.com
FAN FILTER UNITINSTALLATION & SERVICE INSTRUCTIONS
NOTE: Extreme caution should be taken when removing the filter if the filter is to be reinstalled. Touch the filter by the frame only; never touch the filter media as it can damage the filter.
STEP 5: Remove the nuts securing the blower housing using a 7/16” socket wrench (or equivalent).
NOTE: A 7/16” ratchet with extension is recommended for ease of access for unfastening.
FIGURE 29: 2X2 FORWARD CURVED BLOWER HOUSING.
FIGURE 30: 2X3 AND 2X4 FORWARD CURVED BLOWER HOUSING.
FIGURE 31: 2X3 AND 2X4 BACKWARD CURVED BLOWER HOUSING.
NUTS LOCATED ON TOP OF BLOWER HOUSING
29priceindustries.com | FAN FILTER UNIT - Manual
FAN FILTER UNITINSTALLATION & SERVICE INSTRUCTIONS
STEP 6: Remove the housing exposing the motor/blower assembly.
STEP 7: Remove 7/16” nuts holding motor/blower assembly in place.
STEP 8: Drop motor/blower assembly out of unit. Be careful as wire connection are still in place.
STEP 9: Disconnect plug and play connection connecting wires from motor to control box.
FIGURE 32: 2X2 MOTOR-BLOWER HOUSING REMOVAL (STEP 1).
FIGURE 34: SPEED CONTROL AND MOTOR HARNESS CABLES 115V SHOWN.
FIGURE 33: MOTOR-BLOWER HOUSING REMOVAL (STEP 2).
30 priceindustries.com | FAN FILTER UNIT - ManualFAN FILTER UNIT - Manual | priceindustries.com
FAN FILTER UNITINSTALLATION & SERVICE INSTRUCTIONS
STEP 10: Remove motor/blower assembly.
STEP 11: Inspect and/or replace parts.
STEP 12: Replace with the new motor/blower assembly and reassemble by reversing the above steps.
STEP 13: Double check airflow to ensure that set point has not changed. Applicable speed controller found on page 6 onwards.
NOTE: For information on how to order replacement motor/blowers, contact your local Price Sales Representative. Visit Price’s website (http://www.priceindustries.com/contact/reps-dealers) to locate your local Representative.
31priceindustries.com | FAN FILTER UNIT - Manual
FAN FILTER UNITINSTALLATION & SERVICE INSTRUCTIONS
Technical Note: Aerosol Sample and Static PortRoom Side Replaceable (RSR)
Sample line string below:
FFU-1-X//I/24/48/RSR/FC/ECM/115/10//CF//HEPA//BFC////DSW-115//PC-115//RMB/ASSP/INJ//FL+ML+BACnet///WPFH/PL-AL/F-AL//PL-B12/F-B12
STEP 1: Remove diffuser perforated face by turning quarter turn fasteners holding face in place.
NOTE: Safety cables will be attached to the diffuser face, but care should be taken to ensure that diffuser face does not swing and injure anyone.
Step 2: Remove gasketed bolt
STEP 3: Insert pressure measuring gauge (eg. Magnehelic) to read pressure drop across filter or upstream aerosol concentration. Hole size is 5/16”.
FIGURE 35: DIFFUSER FACE QUARTER TURN FASTENERS.
FIGURE 36: AEROSOL SAMPLE AND STATIC PORT
32 priceindustries.com | FAN FILTER UNIT - ManualFAN FILTER UNIT - Manual | priceindustries.com
FAN FILTER UNITINSTALLATION & SERVICE INSTRUCTIONS
Bench Top Replaceable (BTR)
Sample line string:
FFU-1-1//I/24/48/BTR/FC/ECM/115/10//CF//HEPA//BFC////DSW-115//PC-115//RMB/ASSP/INJ//FL+ML+BACnet/// WPFH/PL-AL/F-AL//PL-B12/F-B12
NOTE: Safety cables will be attached to the diffuser face, but care should be taken to ensure that diffuser face does not swing and injure anyone.
STEP 1: STEP 1. Remove gasketed bolt located along center channel of BTR filter. There are two ports that can be used, but with LED indicator option, one port will be used for the LED installation.
STEP 2: Remove gasketed bolt.
STEP 3: Insert pressure measuring gauge (eg. Magnehelic) to read pressure drop across filter or upstream aerosol concentration. Hole size is 5/16”.
FIGURE 37: AEROSOL SAMPLE AND STATIC PORT.
33priceindustries.com | FAN FILTER UNIT - Manual
FAN FILTER UNITINSTALLATION & SERVICE INSTRUCTIONS
STEP 1: Determine test point voltage (VDC) from the formula based on the desired airflow using the appropriate chart below.
Constant Flow – Clean Filters (Forward Curved)
Voltage Velocity 24x24 24x36 24x48
Volt FPM BTR - FC RSR - FC BTR - FC RSR - FC BTR - FC RSR - FC
115 45-135 VDC = VDC = VDC = VDC = VDC = VDC =
240 45-135 VDC = VDC = VDC = VDC = VDC = VDC =
277 45-135 VDC = VDC = VDC = VDC = VDC = VDC =
Constant Torque – Clean Filters (Backwards Curved)
Voltage Velocity 24x24 24x36 24x48
Volt FPM BTR - BC RSR - BC BTR - BC RSR - BC BTR - BC RSR - BC
115 45-135 Not Available Not Available VDC = VDC = VDC = VDC =
240 45-135 Not Available Not Available VDC = VDC = VDC = VDC =
277 45-135 Not Available Not Available VDC = VDC = VDC = VDC =
CFM-71145
POTENTIOMETER(POT)
MEASURE (+) VDC MEASURE (-) VDC
FIGURE 38: ECMSC SPEED CONTROLLER.
CFM-50 96
CFM-4597
CFM-4895
CFM-3967
CFM-3967
CFM-3167
CFM-78144
CFM-76145
CFM-35118
CFM-39116
CFM-31118
CFM-91198
CFM-88198
CFM-85199
CFM-72155
CFM-64156
CFM-63153
CFM + 233449
CFM + 267437
CFM + 226486
CFM + 302517
CFM + 240450
CFM + 193393
CFM + 185459
CFM + 313522
CFM + 233444
CFM + 208399
CFM + 165448
CFM + 307512
34 priceindustries.com | FAN FILTER UNIT - ManualFAN FILTER UNIT - Manual | priceindustries.com
FAN FILTER UNITINSTALLATION & SERVICE INSTRUCTIONS
Constant Torque – Clean Filters (Forward Curved)Voltage Velocity 24x24 24x36 24x48
Volt FPM BTR/FC RSR/FC BTR/FC RSR/FC BTR/FC RSR/FC
115
45-90 VDC = VDC = VDC = VDC = VDC = VDC =
90-135 VDC = VDC = VDC = VDC = VDC = VDC =
240
45-90 VDC = VDC = VDC = VDC = VDC = VDC =
90-135 VDC = VDC = VDC = VDC = VDC = VDC =
277
45-90 VDC = VDC = VDC = VDC = VDC = VDC =
90-135 VDC = VDC = VDC = VDC = VDC = VDC =
Example: 24” x 48”, FC Wheel, 115V @ 450cfm VDC = (CFM - 72)/155
VDC = (450 - 72)/155 VDC = 2.44V
NOTE: The calculated VDC value is intended as a starting point; actual VDC value may differ slightly depending on field variables.
STEP 2: If using potentiometer/manual adjustment, rotate the potentiometer (POT/DIAL) dial on the outside of the box with a screwdriver until the test point voltage is achieved.
NOTE: ECM Speed Controllers have 2 modes: manual adjust and BAS (Building Automation System). Standard manual control outputs are shown below:
Measurement Tab Voltage Motor Control
0 - 1 VDC Off
1 - 4.5 VDC 0-100%
4.5 - 5 VDC 100%
The speed controller will automatically ignore the potentiometer (POT/DIAL) when a BAS signal is detected (BAS Input Signal >1).
VDC equations are for potentiometer (POT/DIAL) manual adjustment only (0-1 BAS input signal). The VDC equations are based on a 1-5 Volt scale. The BAS input voltage is a 2-10 VDC scale, and therefore VDC calculated for a given CFM using the equation must be doubled to achieve that CFM using the BAS input.
BAS Voltage Response Notes
0 - 1 VDC Local control mode using push buttons Local setpoint can be adjusted from 0 - 100% using push buttons
1 - 2 VDC Motor Off Recommended sending a 1.5 VDC signal to command motor off
2 - 9 VDC Modulating Control 2 - 9 VDC modulates motor from 0 - 100%
9 - 10 VDC Maximum Speed Motor is running at maximum speed (100%)
EXAMPLE: If using a BAS signal, to calculate appropriate starting voltage, first calculate the VDC (as shown in above example)
VDC = 2.44 V
Then double this value
BAS Input Voltage = VDC*2
BAS Input Voltage = 2.44*2
BAS Input Voltage = 4.88V
CFM + 179310
CFM + 19207
CFM + 188292
CFM + 93224
CFM + 156312
CFM - 70197
CFM + 142338
CFM - 138212
CFM + 155306
CFM + 63250
CFM + 212367
CFM - 55224
CFM + 20207
CFM + 140283
CFM + 87220
CFM + 194295
CFM - 81193
CFM + 147314
CFM - 138212
CFM + 140335
CFM + 35232
CFM + 170317
CFM - 59223
CFM + 216365
CFM + 174309
CFM + 22207
CFM + 233322
CFM + 88220
CFM + 177322
CFM - 33221
CFM + 139336
CFM - 142209
CFM + 195330
CFM + 24226
CFM + 207363
CFM - 64365
35priceindustries.com | FAN FILTER UNIT - Manual
FAN FILTER UNITINSTALLATION & SERVICE INSTRUCTIONS
POTENTIOMETER/DIAL ADJUST
GREEN STATUS LED MUST BE BLINKING. (CODE 1 THRU 4)
STEP 3: Wait a few seconds for the ECM motor to adjust its speed and then verify fan airflow with measurements at the unit face using a flow hood. Adjust the POT/DIAL, or BAS input signal to reach desired airflow as required.
STEP 4: Proceed to balancing sections starting on page 42.
FIGURE 39: SPEED CONTROLLER ADJUSTMENT.
36 priceindustries.com | FAN FILTER UNIT - ManualFAN FILTER UNIT - Manual | priceindustries.com
FAN FILTER UNITINSTALLATION & SERVICE INSTRUCTIONS
ECMDX
STEP 1: Determine Local Set-point from the formula based on the desired airflow using the appropriate chart below.
Constant Flow – Clean Filters (Forward Curved)Voltage Velocity 24x24 24x36
Volt FPM BTR - FC RSR - FC BTR - FC RSR - FC
115 45-135 Lset = (CFM/3.35) - 44 Lset = (CFM/2.33) - 46 Lset = (CFM/5.03) - 44 Lset = (CFM/4.13) - 38
240 45-135 Lset = (CFM/3.38) - 42 Lset = (CFM/2.33) - 46 Lset = (CFM/5.06) - 44 Lset = (CFM/4.06) - 39
277 45-135 Lset = (CFM/3.31) - 43 Lset = (CFM/2.35) - 42 Lset = (CFM/5.08) - 43 Lset = (CFM/4.12) - 37
Voltage Velocity 24x48
Volt FPM BTR - FC RSR - FC
115 45-135 Lset = (CFM/6.94) - 42 Lset = (CFM/5.42) - 42
240 45-135 Lset = (CFM/6.91) - 42 Lset = (CFM/5.45) - 41
277 45-135 Lset = (CFM/6.97) - 41 Lset = (CFM/5.37) - 41
Constant Torque – Clean Filters (Backwards Curved)
Voltage Velocity 24x24 24x36
Volt FPM BTR - BC RSR - BC BTR - BC RSR - BC
115 45-135 Not Available Not Available Lset = (CFM/15.74) - 14 Lset = (CFM/15.29) - 12
240 45-135 Not Available Not Available Lset = (CFM/15.78) - 14 Lset = (CFM/13.76) - 15
277 45-135 Not Available Not Available Lset = (CFM/15.56) - 14 Lset = (CFM/13.99) - 14
Voltage Velocity 24x48
Volt FPM BTR - BC RSR - BC
115 45-135 Lset = (CFM/17.03) - 16 Lset = (CFM/18.1) - 12
240 45-135 Lset = (CFM/16.09) - 18 Lset = (CFM/18.28) - 12
277 45-135 Lset = (CFM/15.68) - 19 Lset = (CFM/17.92) - 12
Constant Torque – Clean Filters (Forward Curved)Voltage Velocity 24x24 24x36
Volt FPM BTR/FC RSR/FC BTR/FC RSR/FC
11545-90 Lset = (CFM/10.87) - 13 Lset = (CFM/10.23) - 11 Lset = (CFM/10.93) - 15 Lset = (CFM/10.73) - 15
90-135 Lset = (CFM/7.26) - 26 Lset = (CFM/7.72) - 18 Lset = (CFM/6.78) - 41 Lset = (CFM/8.12) - 25
24045-90 Lset = (CFM/10.82) - 13 Lset = (CFM/11.28) - 8 Lset = (CFM/11.3) - 13 Lset = (CFM/11.58) - 12
90-135 Lset = (CFM/7.27) - 26 Lset = (CFM/7.84) - 17 Lset = (CFM/6.92) - 39 Lset = (CFM/8.75) - 22
27745-90 Lset = (CFM/9.93) - 15 Lset = (CFM/10.32) - 10 Lset = (CFM/11.02) - 16 Lset = (CFM/11.12) - 14
90-135 Lset = (CFM/7.26) - 26 Lset = (CFM/7.71) - 18 Lset = (CFM/7.74) - 33 Lset = (CFM/7.92) - 26
Voltage Velocity 24x48
Volt FPM BTR/FC RSR/FC
11545-90 Lset = (CFM/11.84) - 17 Lset = (CFM/12.86) - 13
90-135 Lset = (CFM/7.43) - 48 Lset = (CFM/7.82) - 37
24045-90 Lset = (CFM/11.78) - 17 Lset = (CFM/12.72) - 13
90-135 Lset = (CFM/7.42) - 48 Lset = (CFM/7.86) - 36
27745-90 Lset = (CFM/11.74) - 17 Lset = (CFM/12.79) - 12
90-135 Lset = (CFM/7.33) - 49 Lset = (CFM/7.67) - 38
37priceindustries.com | FAN FILTER UNIT - Manual
FAN FILTER UNITINSTALLATION & SERVICE INSTRUCTIONS
STEP 2: If manually adjusting at the speed controller ensure controller is in Local Setpoint mode (L.SEt). To change modes, press the up and down arrows simultaneously until you reach L.SEt
STEP 3: Enter the Local Setpoint value (L. Set) you have found from the chart by using the up/down buttons.
NOTE: The L.Set calculated above is a starting point; actual value may differ slightly depending on field variables.
NOTE: The BAS signal will override the local setpoint using a remote 0 – 10 VDC signal. If the BAS signal drops below 1 VDC local control (via the up/down buttons) is restored.
The ECMDX speed controller can be controlled using multiple strategies; these are outlined in the chart below.
BAS Voltage Response Notes
0 - 1 VDC Local control mode using push buttons Local setpoint can be adjusted from 0 - 100% using push buttons
1 - 2 VDC Motor Off Recommended sending a 1.5 VDC signal to command motor off
2 - 9 VDC Modulating Control 2 - 9 VDC modulates motor from 0 - 100%
9 - 10 VDC Maximum Speed Motor is running at maximum speed (100%)
The VDC equations are based on a 1-5 Volt scale. The BAS input voltage is a 2-10 VDC scale, and therefore VDC calculated for a given CFM using the equations (refer to ECM speed controller on page 34) must be doubled to achieve that CFM using the BAS input.
STEP 4: Wait a few seconds for the ECM motor to adjust its speed and then verify fan airflow with measurements at the supply outlets using a flow hood. Adjust voltage to reach desired airflow as required.
STEP 5: Proceed to balancing sections starting on page 42
38 priceindustries.com | FAN FILTER UNIT - ManualFAN FILTER UNIT - Manual | priceindustries.com
FAN FILTER UNITINSTALLATION & SERVICE INSTRUCTIONS
BFC
STEP 1: Configure BACnet addressing (if applicable).
Step 2: Using the desired method of control (local, BAS, or BACnet) set unit airflow.
• Local Set-point:
- Refer to page 37 for the ECMDX Speed Controller instructions for calculating Local Set-point value.
- Hold down ‘Enter/Menu’ button for 5 seconds, display will show ‘Passcode”. Use the ‘Up’ and ‘Down’ arrow keys to enter this sequence: Down, Up, Up, Down.
- Use ‘Up’ and ‘Down’ arrow keys to manually enter Local Set-point value; numbers will be displayed on LCD screen.
• BAS:
- Refer to page 34 for the ECM Speed Controller instructions for calculating VDC.
• BACnet:
- Log into Building Management System, or Price supplied FFUFE front end.
- Calculate Local Set-point value using the equations on page 34 from the ECMDX instructions.
- Write this value into ECM Set-point BACnet point.
39priceindustries.com | FAN FILTER UNIT - Manual
FAN FILTER UNITINSTALLATION & SERVICE INSTRUCTIONS
STEP 3: Check airflow using flow hood and adjust ECM Set-point as required until desired airflow is reached.
NOTE: Before proceeding to next step, ensure unit is operating at desired airflow. Any changes to the airflow will require the filter status to be reset.
STEP 4: To calibrate clean filter pressure drop, scroll, scroll through the ‘Service Menus’ until reaching ‘Filter’, select this menu by pressing the ‘Enter/Menu’ button (far right).
STEP 5: Scroll through the ‘Filter’ menu until reaching ‘Reset Filter’ select by pressing the ‘Enter/Menu’ button.
NOTE: Make sure the area directly beneath and around the unit is clear of any personnel or equipment as this can affect the reading of the clean filter static pressure.
STEP 6: Press the ‘Enter/Menu’ button to confirm reset of filter; this will begin calibration. This will take approximately 2 minutes.
After filter calibration is complete, LCD will display: ‘RESET COMPLETED’.
STEP 7: Proceed to balancing sections starting on page 42
FIGURE 40: FILTER RESET SCREEN.
FIGURE 41: FILTER CALIBRATION SCREEN.
40 priceindustries.com | FAN FILTER UNIT - ManualFAN FILTER UNIT - Manual | priceindustries.com
FAN FILTER UNITINSTALLATION & SERVICE INSTRUCTIONS
Technical Note: Design with VAV/Constant Flow Boxes and Ducted ApplicationsIn applications where the fan filter unit will be ducted with upstream VAV, constant flow boxes, valves, or other airflow devices that may have varying airflows, or modes, a constant flow program is not recommended.
In systems where two controllers are trying to compensate to adjust to a constant airflow, the system will be unable to stabilize. This results in constant adjustment of both controllers until the FFU motor shuts off. The ECM with constant torque motor program or PSC motor is suggested for this type of application.
The FFU is designed to overcome the pressure drop of the filter only. The motor is not intended to pull air down supply ductwork, nor to experience a positive static pressure at the inlet forcing air through the fan. Fan filter units should be installed in a system where the inlet static will be neutral or slightly negative.
In ducted applications, it is critical that primary air be balanced prior to installing the FFU. The primary air controls should be locked in position post balancing, and the FFU is installed and running. Similarly, the FFU should be bench-set by using a flow hood and adjusting the speed controller, as required, to the same balanced, primary airflow rate before the FFU is mated with the duct. Alternatively, the Technical Note: Design with VAV/Constant Flow Boxes and Ducted Applications can also be followed on page 41 of this manual.
To prevent a high static pressure build up at the FFU during start up, the FFU’s should be energized prior to the system. This helps to prevent the possibility of backwards rotations of the blower wheel, which will eventually lead to the motor shutting off.
For any additional information, or troubleshooting assistance on systems and design with fan filter units used in sequence with a variable upstream air source, contact Price Industries Fan Filter help at [email protected], or dial (204) 654- 5613 option 5.
41priceindustries.com | FAN FILTER UNIT - Manual
FAN FILTER UNITINSTALLATION & SERVICE INSTRUCTIONS
BalancingUn-ducted Supply Units
STEP 1: Ensure the unit and filter is properly installed.
STEP 2: Turn on FFU and set to desired flow using appropriate speed controller set up (Page 34).
STEP 3: Measure airflow using flow hood and compare against scheduled flow. Adjust speed controller as necessary to achieve design airflow.
FIGURE 42: UN-DUCTED SUPPLY UNITS, NEGATIVE PRESSURE PLENUM.
42 priceindustries.com | FAN FILTER UNIT - ManualFAN FILTER UNIT - Manual | priceindustries.com
FAN FILTER UNITINSTALLATION & SERVICE INSTRUCTIONS
Ducted Supply – Pressure Independent and Dependent Airflow ControlNOTE: If there is a pressure independent device upstream of the FFU then PSC or ECM with constant torque motors should be used.
If FFU is not already installed:
STEP 1: Set FFU with filter installed, on benchtop and set to desired airflow using appropriate speed controller flow equations (Page 34).
STEP 2: Confirm airflow using a flow hood and adjust speed controller as required.
STEP 3: Ensure each supply air duct is balanced to scheduled airflow and matches FFU set point.
STEP 4: Turn off primary air source.
STEP 5: Install FFU into ceiling, connect ductwork.
STEP 6: Turn all FFUs on – ensure all FFUs are running before proceeding to next step.
STEP 7: Turn on primary air source.
STEP 8: Measure airflow using flow hood and compare against scheduled flow. FFU inlet static should be verified to be neutral. See table below if proper operation is not achieved.
FIGURE 43: DUCTED UNIT: CONSTANT TORQUE FFU WITH UPSTREAM PRESSURE INDEPENDENT TERMINAL.
FIGURE 44: DUCTED UNIT: CONSTANT FLOW FFU WITH UPSTREAM PRESSURE DEPENDENT TERMINAL AND MANUAL DAMPER.
43priceindustries.com | FAN FILTER UNIT - Manual
FAN FILTER UNITINSTALLATION & SERVICE INSTRUCTIONS
If the FFU is ducted and removing the duct is not possible, follow the below instructions for balancing:
STEP 1: Turn off primary air source.
STEP 2: Install an air pressure measurement device (i.e. Pitot tube) in the duct prior to the FFU inlet.
STEP 3: Power up FFU and set speed controller to calculated set-point using flow equations (Page 34).
STEP 4: Power up the airflow control device. (Ductwork should have been previously balanced)
STEP 5: Read the inlet pressure.
STEP 6: Measure airflow using flow hood.
STEP 7: Using the table below, adjust FFU controller, or upstream airflow device as required
Repeat steps 4-6 until desired airflow and inlet pressure (0.0 ± 0.05” w.g.) is achieved..
FFU Airflow FFU Inlet Static (measured) Action
Above Set point Above desired pressure Decrease airflow on airflow control device
Above Set point Below desired pressure Decrease FFU control setting
Above Set point At desired pressure Decrease Both FFU and airflow control device
Below Set point At desired pressure Increase Both FFU and airflow control device
Below Set point Below desired pressure Increase airflow on airflow control device
Below Set point Above desired pressure Increase FFU control setting
44 priceindustries.com | FAN FILTER UNIT - ManualFAN FILTER UNIT - Manual | priceindustries.com
FAN FILTER UNITINSTALLATION & SERVICE INSTRUCTIONS
Ducted Supply – Pressure Independent and Dependent Airflow ControlNOTE: If a ducted return or return mixing box is used, a PSC, ECM Constant Torque or ECM Constant Flow (preferred) can be used.
STEP 1: If return mixing box is used, turn primary air off. If ducted return, proceed directly to Step 2.
STEP 2: Set FFU to desired flow using appropriate speed controller flow equations (Page 34).
STEP 3: Confirm airflow using flow hood and adjust speed controller as required.
STEP 4: Power up the primary airflow control device. (Ductwork should have been previously balanced).
STEP 5: Measure airflow using flow hood and compare against scheduled flow. Adjust speed controller as necessary to achieve design airflow.
FIGURE 45: FFU WITH DUCTED RETURN.
FIGURE 46: FFU WITH RETURN MIXING BOX.
45priceindustries.com | FAN FILTER UNIT - Manual
FAN FILTER UNITINSTALLATION & SERVICE INSTRUCTIONS
Troubleshooting: Changing Motor ProgramsRoom Side Replaceable (RSR)
The motors have the ability to function as either constant flow or constant torque. This provides the ability to change motor programs without the need to reprogram the motor.
NOTE: Changes will only take effect upon restarting the motor (must be powered off and then back on) and cannot be made live.
Switching from constant flow to constant torque:
To switch the motor from constant flow to constant torque all that is required is to open the connection of the white wire as shown.
Switching from constant torque to constant flow:
To switch the motor from constant torque to constant flow all that is required is to close the connection of the white wire as shown.
The motor will be factory wired to the motor program selected on the order.
FIGURE 47: MOTOR SETTING - CONSTANT TORQUE.
FIGURE 48: MOTOR SETTING - CONSTANT FLOW.
46 priceindustries.com | FAN FILTER UNIT - ManualFAN FILTER UNIT - Manual | priceindustries.com
FAN FILTER UNITINSTALLATION & SERVICE INSTRUCTIONS
Tips
Low Air Velocity
1. Check pre-filter media (only with optional pre-filter); replace or clean as necessary
2. Adjust variable speed control for higher blower output.
3. Check power for proper voltage, amperage, and distribution frequency.
4. Replace HEPA/ULPA filter if the velocity remains low.
High Air Velocity 1. Adjust variable speed control for lower blower output.
Non-Laminar Flow and/or Excessive Contamination
1. Ensure that no large obstructions are upstream of airflow pattern.
2. Determine that no other air-moving devices are operating in or around cleanroom which could disrupt the room's airflow pattern.
3. Check air velocity and if low, conduct the 'Low Air Velocity' procedure outlined above.
4. Conduct smoke and photometer test on HEPA/ULPA filter. Seal or replace.
Motor Keeps Shutting Off
1. Check if unit is ducted.
2. If no, contact Price at [email protected].
3. If yes, check inlet pressure, if positive, re-balance until inlet pressure is zero.
LED Light Turned Red 1. Refer to 'Motor Will Not Run' procedure outlined below.
LED light Turned Yellow 1. Replace filter.
Motor Will Not Run1. Check that motor has power at correct voltage.
2. Check that the speed controller has power.
If experiencing further issues with unit, contact Price Industries Fan Filter help at:
By Email: [email protected]
By Phone: (204) 654-5613 option 5
47priceindustries.com | FAN FILTER UNIT - Manual
FAN FILTER UNITINSTALLATION & SERVICE INSTRUCTIONS
BTR Unit Replacement PartsHEPA Filters
Size Quantity Description Price Part Number2x2 1 Filter, HEPA, 99.99% FFU 24 x 24 x 3.06" 042299-0112x3 1 Filter, HEPA, 99.99% FFU 24 x 36 x 3.06" 042299-0122x4 1 Filter, HEPA, 99.99% FFU 24 x 48 x 3.06" 042299-013
ULPA Filters
Size Quantity Description Price Part Number2x2 1 Filter, ULPA, 99.9995% FFU 24 x 24 x 3.06" 042299-0142x3 1 Filter, ULPA, 99.9995% FFU 24 x 36 x 3.06" 042299-0152x4 1 Filter, ULPA, 99.9995% FFU 24 x 48 x 3.06" 042299-016
Parts Quantity Description Price Part NumberWashable Pre-filter (FC Unit) 1 Foam Filter 16x20x.437 045964-001Washable Pre-filter (BC Unit) 1 Foam Filter 20x20x.437 045964-002Washable Pre-filter (FC Unit) 1 Foam Filter 15.5x19.5x.437 045964-004
ECM Standard Speed Controller 1 USC 8A speed control 232953-100ECM Speed Controller Cable 1 Cable ECM Speed Control 2ft 019186-001
ECM-WK Speed Controller Main Board 1 Wall Mounted Speed Controller 232953-300ECM-WK Speed Controller
Remote Board1 Wall Mounted Remote for ECM Speed Controller 232953-350
ECMDX WK Speed Controller 1 Deluxe Wall Mounted Speed Control for EC Motor 232953-400ECMDX Motor Cable 1 Wall Mounted Remote for ECM Motor 019186-006ECMDX Wall Cable 1 ECMDX/BFC Speed Control, 2 ft 019186-004
ECM Power Cable 1Power Cable Harness – 115V 019187-003Power Cable Harness – 208V,240V, 277V 019187-004
Transformer Quantity Description Price Part Number115V 1 Transformer 120/24 50VA FT-MT 019436-001
208-240V 1 Transformer (208/240V)/24V 50VA FT-MT 019436-011277V 1 Transformer 277/24V 50VA FT-MT 019439-001
Blower Wheel Quantity Description Price Part Number2x2 1 WHL 1/2 Bore w/ REV Hub 100080-001
2x3, 2x4 1 WHL 1/2 (FC) 100090-0022x3, 2x4 1 WHL 1/2 (BC) 100090-003
Disconnect Switch 1Disconnect Switch 15A, 1-Pole (115/277) 019903-001Disconnect Switch 30A, 2-Pole (208/240V) 019903-003
PSC MotorSize Quantity Description Price Part Number
2x4, 2x3, 2x2 1 115V – PSC Motor 1/4HP 019152-0022x4, 2x3, 2x2 1 208-240V – PSC Motor 1/4HP 019589-0022x4, 2x3, 2x2 1 277V – PSC Motor 1/4HP 019153-002
ECM Motor
Size Quantity Description Price Part Number2x4, 2x3, 2x2 1 115/208/240/277V - ECM Motor 1/3HP 019219-001
48 priceindustries.com | FAN FILTER UNIT - ManualFAN FILTER UNIT - Manual | priceindustries.com
FAN FILTER UNITINSTALLATION & SERVICE INSTRUCTIONS
RSR Unit Replacement Parts HEPA Filters
Size Quantity Description Price Part Number2x2 1 Filter, HEPA, 99.99% FFU 24 x 24 x 3.5" 042299-0052x3 1 Filter, HEPA, 99.99% FFU 24 x 36 x 3.5" 042299-0062x4 1 Filter, HEPA, 99.99% FFU 24 x 48 x 3.5" 042299-007
ULPA Filters
Size Quantity Description Price Part Number2x2 1 Filter, ULPA, 99.9995% FFU 24 x 24 x 3.5" 042299-0082x3 1 Filter, ULPA, 99.9995% FFU 24 x 36 x 3.5" 042299-0092x4 1 Filter, ULPA, 99.9995% FFU 24 x 48 x 3.5" 042299-010
Parts Quantity Description Price Part NumberWashable Pre-filter (FC Unit) 1 Foam Filter 16x20x.437 045964-001Washable Pre-filter (BC Unit) 1 Foam Filter 20x20x.437 045964-002Washable Pre-filter (FC Unit) 1 Foam Filter 15.5x19.5x.437 045964-004
ECM Standard Speed Controller 1 USC 8A speed control 232953-100ECM Speed Controller Cable 1 Cable ECM Speed Control 2ft 019186-001
ECM-WK Speed Controller Main Board 1 Wall Mounted Speed Controller 232953-300ECM-WK Speed Controller
Remote Board1 Wall Mounted Remote for ECM Speed Controller 232953-350
ECMDX WK Speed Controller 1 Deluxe Wall Mounted Speed Control for EC Motor 232953-400ECMDX Motor Cable 1 Wall Mounted Remote for ECM Motor 019186-006ECMDX Wall Cable 1 ECMDX/BFC Speed Control, 2 ft 019186-004
ECM Power Cable 1Power Cable Harness – 115V 019187-003Power Cable Harness – 208V,240V, 277V 019187-004
Transformer Quantity Description Price Part Number115V 1 Transformer 120/24 50VA FT-MT 019436-001
208-240V 1 Transformer (208/240V)/24V 50VA FT-MT 019436-011277V 1 Transformer 277/24V 50VA FT-MT 019439-001
Blower Wheel Quantity Description Price Part Number2x2 1 WHL 1/2 Bore w/ REV Hub 100080-001
2x3, 2x4 1 WHL 1/2 (FC) 100090-0022x3, 2x4 1 WHL 1/2 (BC) 100090-003
Disconnect Switch 1Disconnect Switch 15A, 1-Pole (115/277) 019903-001Disconnect Switch 30A, 2-Pole (208/240V) 019903-003
PSC MotorSize Quantity Description Price Part Number
2x4, 2x3, 2x2 1 115V – PSC Motor 1/4HP 019152-0022x4, 2x3, 2x2 1 208-240V – PSC Motor 1/4HP 019589-0022x4, 2x3, 2x2 1 277V – PSC Motor 1/4HP 019153-002
ECM Motor
Size Quantity Description Price Part Number2x4, 2x3, 2x2 1 115/208/240/277V - ECM Motor 1/3HP 019219-001
49priceindustries.com | FAN FILTER UNIT - Manual
FAN FILTER UNITINSTALLATION & SERVICE INSTRUCTIONS
FAN FILTER UNIT - HIGH EFFICIENCYINSTALLATION & SERVICE INSTRUCTIONS
WIRING DIAGRAM - FFU LED - FILTER LOADING
WIRING DIAGRAM - FFU LED - MOTOR LOADING
50 priceindustries.com | FAN FILTER UNIT - ManualFAN FILTER UNIT - Manual | priceindustries.com
FAN FILTER UNITINSTALLATION & SERVICE INSTRUCTIONS
FAN FILTER UNIT - HIGH EFFICIENCYINSTALLATION & SERVICE INSTRUCTIONS
WIRING DIAGRAM - FFU - FILTER BAS
WIRING DIAGRAM - FFU - MOTOR BAS
51priceindustries.com | FAN FILTER UNIT - Manual
FAN FILTER UNITINSTALLATION & SERVICE INSTRUCTIONS
FAN FILTER UNIT - HIGH EFFICIENCYINSTALLATION & SERVICE INSTRUCTIONS
WIRING DIAGRAM - FFU LED - MOTOR LOADING & FILTER LOADING
WIRING DIAGRAM - FFU LED - FILTER LOADING & FILTER BAS
52 priceindustries.com | FAN FILTER UNIT - ManualFAN FILTER UNIT - Manual | priceindustries.com
FAN FILTER UNITINSTALLATION & SERVICE INSTRUCTIONS
FAN FILTER UNIT - HIGH EFFICIENCYINSTALLATION & SERVICE INSTRUCTIONS
WIRING DIAGRAM - FFU LED - MOTOR BAS & FILTER LOADING
WIRING DIAGRAM - FFU LED - MOTOR LOADING & FILTER BAS
53priceindustries.com | FAN FILTER UNIT - Manual
FAN FILTER UNITINSTALLATION & SERVICE INSTRUCTIONS
FAN FILTER UNIT - HIGH EFFICIENCYINSTALLATION & SERVICE INSTRUCTIONS
WIRING DIAGRAM - FFU LED - MOTOR LOADING & MOTOR BAS
WIRING DIAGRAM - FFU - MOTOR BAS & FILTER BAS
54 priceindustries.com | FAN FILTER UNIT - ManualFAN FILTER UNIT - Manual | priceindustries.com
FAN FILTER UNITINSTALLATION & SERVICE INSTRUCTIONS
FAN FILTER UNIT - HIGH EFFICIENCYINSTALLATION & SERVICE INSTRUCTIONS
WIRING DIAGRAM - FFU LED - MOTOR LOADING, FILTER LOADING & FILTER BAS
WIRING DIAGRAM - FFU LED - MOTOR LOADING, FILTER LOADING & MOTOR BAS
55priceindustries.com | FAN FILTER UNIT - Manual
FAN FILTER UNITINSTALLATION & SERVICE INSTRUCTIONS
FAN FILTER UNIT - HIGH EFFICIENCYINSTALLATION & SERVICE INSTRUCTIONS
WIRING DIAGRAM - FFU LED - MOTOR LOADING, FILTER LOADING, MOTOR BAS & FILTER BAS
WIRING DIAGRAM - FFU LED - MOTOR LOADING, FILTER LOADING, MOTOR BAC & FILTER BAC
56 priceindustries.com | FAN FILTER UNIT - ManualFAN FILTER UNIT - Manual | priceindustries.com
FAN FILTER UNITINSTALLATION & SERVICE INSTRUCTIONS
FAN FILTER UNIT - HIGH EFFICIENCYINSTALLATION & SERVICE INSTRUCTIONS
WIRING DIAGRAM - FFU - 115/277V, 1ø PSC (STANDARD MOTOR)
WIRING DIAGRAM - FFU - 208/240V, 1ø MOTOR (STANDARD/PSC)
57priceindustries.com | FAN FILTER UNIT - Manual
FAN FILTER UNITINSTALLATION & SERVICE INSTRUCTIONS
FAN FILTER UNIT - HIGH EFFICIENCYINSTALLATION & SERVICE INSTRUCTIONS
WIRING DIAGRAM - FFU - 115/277V, 1ø ECM MOTOR W/ STANDARD ECM SPEED CONTROL (ECMSC)
WIRING DIAGRAM - FFU - 115/277V, 1ø ECM MOTOR W/ DELUXE ECM SPEED CONTROL (ECMDX)
58 priceindustries.com | FAN FILTER UNIT - ManualFAN FILTER UNIT - Manual | priceindustries.com
FAN FILTER UNITINSTALLATION & SERVICE INSTRUCTIONS
FAN FILTER UNIT - HIGH EFFICIENCYINSTALLATION & SERVICE INSTRUCTIONS
WIRING DIAGRAM - FFU - 115/277V, 1ø ECM MOTOR W/ BACNET FLOW CONTROL (BFC)
WIRING DIAGRAM - FFU - 240VV, 1ø ECM MOTOR W/ STANDARD ECM SPEED CONTROL (ECMSC)
59priceindustries.com | FAN FILTER UNIT - Manual
FAN FILTER UNITINSTALLATION & SERVICE INSTRUCTIONS
FAN FILTER UNIT - HIGH EFFICIENCYINSTALLATION & SERVICE INSTRUCTIONS
WIRING DIAGRAM - FFU - 240VV, 1ø ECM MOTOR W/ DELUXE ECM SPEED CONTROLLER (ECMDX)
WIRING DIAGRAM - FFU - 240VV, 1ø ECM MOTOR W/ BACNET FLOW CONRTOLLER (BFC)
60 priceindustries.com | FAN FILTER UNIT - ManualFAN FILTER UNIT - Manual | priceindustries.com
FAN FILTER UNITINSTALLATION & SERVICE INSTRUCTIONS
FAN FILTER UNIT - HIGH EFFICIENCYINSTALLATION & SERVICE INSTRUCTIONS
WarrantyThe Company warrants and guarantees that all goods within this catalog that have been manufactured by the Company have been manufactured in accordance with the specifications published herein and will be free from defects in material and workmanship for a period of twelve (12) months from the date of Bill of Lading issued by the Company. The Company will replace defective product at its option, but will not be responsible for labor or material charges in replacing product or consequential damages. Any installation not conforming with the Company's specifications, manuals, bulletins or instructions or any misuse or any modification not authorized by the Company voids this warranty. This warranty is in lieu of all Provincial, State, and Federal statutory warranties and the conditions herein are in substitution and replacement of such warranties, statutory or otherwise.
61priceindustries.com | FAN FILTER UNIT - Manual
This document contains the most current product information as of this printing. For the most up-to-date product information, please go to priceindustries.com
© 2019 Price Industries Limited. All rights reserved.