Page 1: FAN Magazine Fault

FAN Magazine Fault

Page 2: FAN Magazine Fault
Page 3: FAN Magazine Fault

Ports on FAN Unit

• 1.Power branch A input from PDU

• 2.Supervision input (Either from RP or from other FAN unit extension port)

• 3.MIA LED

• 4.Supervision extension Port

• 5.Power branch B input from PDU

Page 4: FAN Magazine Fault
Page 5: FAN Magazine Fault

• where it is mounted as a normal low height sub rack. It can be placed above or below the magazine to be cooled. It is internally built up of three fans and a control board.

• SCB-RP controls the FAN units with DENIB protocol by means of supervision cable connected at V24 or V10 port of SCB-RP board.

• FAN units are connected in chain mode ,it mean all the units connected in chain are controlled by single SCB RP.

• This is mainly due to ,for the magazines GDM,APG,CP does not have any SCB-RP board for controlling the FAN units.

Page 6: FAN Magazine Fault

• the manual intervention on the fan unit is indicated by the Manual Intervention Allowed (MIA) Light Emitting Diode (LED). The controller RP provides access to the MIA LED on the fan unit magazine.

• The LED can be:• ON indicating that the fan unit can be removed without any system

disturbance. • OFF indicating that the fan unit cannot be removed without disturbance.

The MIA LED is illuminated (turned to ON) when there are faults on the fan units, indicated by the FAN MAGAZINE FAULT alarm.

• The MIA LED is extinguished (turned to OFF) when there is no fault on the fan unit.

• In the case that the LED is not turned ON, it could be due to one of the following reasons:

• The controller RP is already blocked or faulty. • The fan unit has hardware or communication faults. • The function is not supported. • If the LED is not turned OFF, it might be due to one of the above indicated

reasons.

Page 7: FAN Magazine Fault

Different kinds of alarms on FAN Magazine Unit:• TEMPERATURE>65* C

– The temperature on the fan unit exceeds 65 degrees Celsius.

• TEMPERATURE>55* C – The temperature on the fan unit exceeds 55 degrees Celsius.

• TEMPERATURE SENSOR OUT OF RANGE – The fan temperature sensor has detected a temperature which is out of

the range or the fan temperature sensor is faulty.

• MOTOR CURRENT OUT OF RANGE – One or more of fan motor current is out of range.

• FAN INTERNAL COMMUNICATION ERROR – The fan unit has an internal communication error.

• FAN MOTOR REGULATION ERROR – One or more of the fan motors have a current regulation fault.

Page 8: FAN Magazine Fault

• POWER BRANCH A ERROR – The power branch A of the fan unit is faulty.

• POWER BRANCH B ERROR – The power branch B of the fan unit is faulty.

• COMMUNICATION ERROR-PROTOCOL – There is a protocol communication fault between the fan unit and the

controller regional processor.• COMMUNICATION ERROR-FRAMING

– There is a framing communication fault between the fan unit and the controller regional processor.

• COMMUNICATION ERROR-CHECKSUM – There is a checksum error on exchanging data between the fan unit and

the controller regional processor.• COMMUNICATION ERROR-ADDRESS MODE

– There is an addressing mode communication fault between the fan unit and the controller regional processor.

• RP BLOCKED – The regional processor is blocked.

Page 9: FAN Magazine Fault

The fan magazine has a temperature sensor, which is located close to the fan air stream. The fan motor voltage is controlled according to the temperature of this temperature sensor.

The magazine contains current sensors and supervises the

-48V voltage distributed to the fans when the temperature rises up to 55 Celsius or it detects malfunction on the fan current or the power, the fan magazine sends signals to the RP via DENIB protocol for maintaining the fan.

Page 10: FAN Magazine Fault

• If temperature sensor of FAN unit detects more than >55*C ,then room temperature needs to be checked (like AC).

• If room temperature is found OK, then the supervision cable for maintaining the FAN may be faulty or loose connections. or the temperature sensor is faulty which is present inside the FAN unit, So in this case FAN unit need to be replaced.

• Sometimes this alarm may get hanged ,which can e be rectified by block/deblock the RP or by power cycling the FAN Unit.

Page 11: FAN Magazine Fault

• In case of Motor Current out of range and FAN Motor regulation error, the regulatory unit may got faulty or malfunctioning,

• To rectify this case, power cycle of FAN Unit or Unit to be replaced.

• Power branch A or B error case, power input of A or B need to be checked carefully (and voltage should be in range of -48V to -72V. ) and socket ports need to be tightened.

• Check any external alarms in node.Check the power cable fuse at the other end of the cable. Which is located in PDU.

Page 12: FAN Magazine Fault

• Communication Errors are mainly due to supervision cables/controlling RP problems. In this case,block,deblock the RP or supervision cable need to be changed from where the communication error alarm generating.

Page 13: FAN Magazine Fault

How to clear FAN unit alarm?

• Proceed with the following steps to clear this alarm.• 1.Analyse the alarm printout. find the RP No, FAN unit No

and the event of alarm.• 2.Trace the FAN unit ,by means of RP no and FAN unit No, if

unit no is 2 it indicates that the unit is 2nd one in chain. For finding the location use expop command. Expop:rp=<RP No>,EM=<FAN Unit No>; -Trace the unit by means of supervision cables. -The other way of tracing the unit is by means of MIA

LED on FAN unit by checking the unit for which LED glows and reconfirming the same by Serial Number, product number and revision number.

Page 14: FAN Magazine Fault

What expop gives and what it indicates:

• If alarm print out is like this:

FAN MAGAZINE FAULT

RP FANU EVENT

192 4 MOTOR CURRENT OUT OF RANGE <expop:rp=192,EM=4;DEVICE POSITIONRP EM POS192 4 RBSC1-2-18-3END

• Cabinet Position- Name-Cabinet No-vertical Position Y Position-Horizontal Position-Shelf/slot position

Page 15: FAN Magazine Fault

how to read the cabinet allocation drawing

Cabinet row * Cabinet no.

Magazine’s vertical position(Y-coordinate)

Cabinet type

Magazine no.Bus no.(when applicable)

Magazine’s horizontal position(X-coordinate)

Slot’s horizontal position(X-coordinate)

Page 16: FAN Magazine Fault

APZ 212 33C Cabinet, FAN unitS

EXPOI:RP=2, EM=3, POS=516-6-62-03;

EXPOI:RP=2, EM=2, POS=516-6-46-03;

EXPOI:RP=3, EM=1, POS=516-6-40-03;

EXPOI:RP=2, EM=1, POS=516-6-24-03;

DBTSI:TAB=OMSR501MAGS, BRNO=0, MAGNO=18, CABROW=516, CABNO=6, MAGXPOS=3, MAGYPOS=62, MAPPIND=NOTSUPP, UNEQPRN="FANU";

DBTSI:TAB=OMSR501MAGS, BRNO=0, MAGNO=17, CABROW=516, CABNO=6, MAGXPOS=3, MAGYPOS=46, MAPPIND=NOTSUPP, UNEQPRN="FANU";

DBTSI:TAB=OMSR501MAGS, BRNO=0, MAGNO=24, CABROW=516, CABNO=6, MAGXPOS=3, MAGYPOS=40, MAPPIND=NOTSUPP, UNEQPRN="FANU";

DBTSI:TAB=OMSR501MAGS, BRNO=0, MAGNO=16, CABROW=516, CABNO=6, MAGXPOS=3, MAGYPOS=24, MAPPIND=NOTSUPP, UNEQPRN="FANU";

DBTSI:TAB=OMSRCPMAGS, MAGNAM="FAN-0", CABROW=516, CABNO=6, MAGXPOS=3, MAGYPOS=62;

DBTSI:TAB=OMSRCPMAGS, MAGNAM="FAN-1", CABROW=516, CABNO=6, MAGXPOS=3, MAGYPOS=46;

DBTSI:TAB=OMSRCPMAGS, MAGNAM="FAN-2", CABROW=516, CABNO=6, MAGXPOS=3, MAGYPOS=40;

DBTSI:TAB=OMSRCPMAGS, MAGNAM="FAN-3", CABROW=516, CABNO=6, MAGXPOS=3, MAGYPOS=24;

FAN (RP=2, FANU=3)62

FAN (RP=2, FANU=2)46

FAN (RP=3, FANU=1)40

FAN (RP=2, FANU=1)24

MAG. VERTICAL POS.

POS=CABROW-CABNO-MAGYPOS-MAGXPOS

The magazine no. here is ‘fictive’. See ref. 1 for more details.

The numbering is from top to bottom

Magazine’s X-position is always “3”

Always “NOTSUPP”

POS=CABROW-CABNO-MAGYPOS-MAGXPOS

FANU=EM in EXPOI

516*06Cabinet position

Page 17: FAN Magazine Fault

dbtsp:tab=RPS501BOARDS;

By using this command ,Hardware details of FAN unit can be found.

Page 18: FAN Magazine Fault

• BRNO MAGNO SLOTNO PRODNO PRODREV• 6 0 0 ROJ 208 323/1 R2G• PRODNAM MANDATE SERNO MASTRP• SCB-RP 04W02 TF11361398 193• SLSTATE DATE TIME• 0 110610 050410

• BRNO MAGNO SLOTNO PRODNO PRODREV• 6 19 0 BFD50908/3 R1D• PRODNAM MANDATE SERNO MASTRP• FAN 06W13 S773426528 192• SLSTATE DATE TIME• 0 080409 003317

• BRNO MAGNO SLOTNO PRODNO PRODREV• 6 16 0 BFD 509 08/4 R1M• PRODNAM MANDATE SERNO MASTRP• FAN 20070212 BJ31096063 192• SLSTATE DATE TIME• 0 080409 003312• BRNO MAGNO SLOTNO PRODNO PRODREV• 6 17 0 BFD50908/3 R1D• PRODNAM MANDATE SERNO MASTRP• FAN 06W13 S773426751 192• SLSTATE DATE TIME• 0 080409 003313

• BRNO MAGNO SLOTNO PRODNO PRODREV• 6 20 0 BFD50908/3 R1C• PRODNAM MANDATE SERNO MASTRP• FAN 04W26 S773229513 192• SLSTATE DATE TIME• 0 080409 003555

• BRNO MAGNO SLOTNO PRODNO PRODREV• 6 18 0 BFD50908/3 R1D• PRODNAM MANDATE SERNO MASTRP• FAN 06W13 S773426530 192• SLSTATE DATE TIME• 0 080409 003315

Page 19: FAN Magazine Fault

• 4.Power cycle the FAN unit.Block the RP ,take out the A side power cable and measure the

voltage (should be between -48V to -72V)and replace the cable deblock the RP and check whether the alarm cleared or not. if not follow the same with B side .

Do not take out both the power cables at the same time.

5.Replace the FAN unit. Before this check the version and product number of the new

FAN unit. FAN unit product number should match with the units connected in chain.

And the units connected in upper chain be of upper version that is descending order can be allowed (personal experience in activity, not sure)

Page 20: FAN Magazine Fault

• 6.If alarm not cleared even after replacing, then need to check supervision cables connectivity.

Supervision cables are present in between every FAN Unit and they got faulty and can checked by swapping the cables or request for Supervision cables.

Page 21: FAN Magazine Fault

• Alex Links:

• C:\Users\esaiboy\AppData\Local\Temp\ALEX_TMP\1000\alex0000.htm

Page 22: FAN Magazine Fault

Magazine Power fault

• A MAGAZINE POWER FAULT alarm is received when a power fault is detected in one of the two -48V branches in a magazine, connected to a Regional Processor Bus of Serial type (RPB-S) or Regional Processor Bus of Ethernet type (RPB-E).

• Select action, depending on whether the magazine is supervised by one or two Regional Processors (RPs).

Page 23: FAN Magazine Fault

•   Magazine Power Supplied through Two Supervising RPs

Page 26: FAN Magazine Fault

• 1. Check that the power cables are properly connected/tightened to the RP board.

• 2.Check the Voltage coming through power cables ,if all found ok then jack in-out or SCB-RP needs to be replaced.

• 3.You can also swap the power cable with FAN unit power cable.

Page 27: FAN Magazine Fault

• MAGAZINE POWER FAULT

• MAGAZINE POWER FAULT• BRANCH  RP-A     RP-B     DETECTED• A         128      129        BOTH

• All RP's are working fine.• Group Switch is ok.

• All RP's will be working.

• Each SCB-RP in a mag has 03 input supply ports.

• The below print says power supply to the A-Plane(BRANCH-A) of the magazine is NOT OK..

• Which also means out of the 03 power supply cables to A-Plane of the mag atleast one power cable is not giving proper power supply to the SCB-RP.

Page 28: FAN Magazine Fault

• Solution:• 1) Block the RP of A-Plane SCBRP.• 2) remove the power cables from SCB-RP card one-by-one and

check the input voltage(should be 53-55V) with the help of multimeter.

• 3) Remove one power cable at a time and re-insert the same before you plug out the next cable.

• 4) Any cable that shows improper supply should be replaced.• 5) You may even find that all the cables are OK with proper power

supply in that case there is a problem with the connector of any one of the power cable.

• This is a common problem found in HD BSC's. To find which of the 03 cables is faulty the best and easy way is to plug out any one cable and replace it temporarily with a FAN power cable which should be close by and look if the Mgazine Power fault ceases.

• If it doesn't then you should follow the same step for remaining two cables.