fast and modular energy system - demia.com.mx...flexible and safe for all current transformer...
TRANSCRIPT
L2 L3 NL1
FAMEFast and Modular Energy System
Switch 1 Switch 2
Test block 1
2 PHOENIX CONTACT
Flexible application In addition to the two marking grooves, the test blocks also offer two function shafts inside the control cabinet, which are used, for example, to form the star point with the help of plug-in bridges.
The new, modular FAME measuring
transducer test system enables all
transformer testing tasks to be carried out
quickly and safely.
The automatically generated transformer
short circuit and the shock-proof design
ensure the highest degree of safety during
measurement.
Consistent use of CLIPLINE complete
system accessories reduces mounting and
storage costs.
Maximum flexibility when testing Thanks to the optional use of plug-in bridges, all test circuits can be implemented in the plug. Staggered test sockets enable the use of safety test leads in a confined space.
FAMEFast and Modular Energy System
Firmly under controlThe robustly designed test plug guarantees user-friendly handling and provides fixing options for the test leads to be connected.
Modular designThe compact and modular design of the system, as well as the plugs and test blocks, provides the right number of positions for every application.
PHOENIX CONTACT 3
Safe applicationThe robust latching of the power plug can only be released with two-hand operation. An optional seal protects against unauthorized actuation.
Easy wall mountingThe patented wall fastening is easy to use and has a robust design. Large tolerances in the plate cutout of up to 4 mm are compensated for by the eccentric tappet function.
Optional DIN rail mountingThe pre-assembled measuring transducer test blocks can be mounted in a space-saving way by easily snapping the E-UTWE 6 adapter onto standard NS 35 DIN rails.
L2 L3 NL1
Safety in mindLarge-surface marking options and clearly recognizable positioning of the short-circuit jumpers on the outside of the control cabinet.
4 PHOENIX CONTACT
FAMEFlexible and safe for all current transformer circuits
Power plug inserted
Test plug inserted, thanks to the optional use of plug-in bridges, all test circuits can be implemented in the plug
Power plug removed, automatically leading transformer short circuit through the use of plug-in bridges
Test operation
Transformer short circuit
Normal operationL2
L3
N
L1
PHOENIX CONTACT 5
FAMEFlexible and safe for all voltage transducer circuits
Power plug inserted
Test plug inserted, thanks to the optional use of plug-in bridges, all test circuits can be implemented in the plug
Power plug removed
Test operation
Converter release
Normal operationL2
L3
N
L1
6 PHOENIX CONTACT
FAMESafe in every operating state
Normal operation Transformer short circuit Test operation
When the power plug is used, the transformer short circuit is automatically overridden and the measuring transducer operates safely.
If the plug is removed, the integrated switch contact automatically establishes a leading short circuit via the plug-in bridge used. Connected measuring transducers are safely protected against damage.
When inserting the test plug, the ammeter connected to the test plug is first of all looped into the circuit. Then the transformer short circuit is automatically overridden.
Switch contact open
Switch contact closed
Switch contact open
PHOENIX CONTACT 7
18
17
1614
1513
1210
119
86
75
42
31
10
9
8
7
6
5
4
3
2
1
FAME test block for current transformers
Circuit example Current transformers and voltage transducers
Test block, power plug, test plugOrder No. Type Required quantity
[Quantity]
3069064 UTWE 6/8+1 13069297 FWP 8+1 13069242 FTP 8+1 1
Plug-in bridge3030284 FBS 2-8 4
FAME test block for voltage transducers
Test block, power plug, test plugOrder No. Type Required quantity
[Quantity]
3069048 UTWE 6/4+1 13069271 FWP 4+1 13069223 FTP 4+1 1
L2
L3
N
L1
8 PHOENIX CONTACT
Measuring transducer test block
Type Order No. UTWE 6/4+1 3069048 UTWE 6/4+1 BI 3070008 UTWE 6/5+1 3069049
Number of disconnect terminal blocksMax. operating current/voltage [A] / [V]Nominal current/cross section [A] / [mm2]Rated surge voltage [kV]Solid/AWG [mm2]/—Stranded/AWG [mm2]/—Stranded with ferrule/AWG [mm2]/—Two conductors (of the same type) solid/stranded [mm2]/[mm2]Stripping length [mm]Tightening torque [Nm]Tightening torque for wall fastening [Nm]Insulation materialInflammability class according to UL 94
530 / 40024 / 640.2 - 10 / 24 - 80.2 - 10 / 24 - 80.25 - 6 / 24 - 10
0.2 - 2.5 / 0.2 - 2.5101.5 - 1.80.8 - 1PAV0
530 / 40024 / 640.2 - 10 / 24 - 80.2 - 10 / 24 - 80.25 - 6 / 24 - 10
0.2 - 2.5 / 0.2 - 2.5101.5 - 1.80.8 - 1PAV0
630 / 40024 / 640.2 - 10 / 24 - 80.2 - 10 / 24 - 80.25 - 6 / 24 - 10
0.2 - 2.5 / 0.2 - 2.5101.5 - 1.80.8 - 1PAV0
Power plug
Type Order No. FWP 4+1 3069271 FWP 4+1 3069271 FWP 5+1 3069272
Max. operating current/voltage [A] / [V]Nominal current/cross section [A] / [mm2]Rated surge voltage [kV]
30 / 40024 / 64
30 / 40024 / 64
30 / 40024 / 64
Test plug, with mounted test socket screws
Type Order No. FTP 4+1 3069223 FTP 4+1 3069223 FTP5+1 3069241
Max. operating current/voltage [A] / [V]Nominal current/cross section [A] / [mm2]Rated surge voltage [kV]Test socket torque [Nm]
24 / 40024 / 2.540.5 - 0.6
24 / 40024 / 2.540.5 - 0.6
24 / 40024 / 2.540.5 - 0.6
Blind plug
Type Order No. FBP 4+1 3069405 FBP 4+1 3069405 FBP 5+1 3069409
PHOENIX CONTACT 9
UTWE 6/6+1 3069051 UTWE 6/6+1 BI 3069996 UTWE 6/8+1 3069064 UTWE 6/12+1 3069077
730 / 40024 / 640.2 - 10 / 24 - 80.2 - 10 / 24 - 80.25 - 6 / 24 - 10
0.2 - 2.5 / 0.2 - 2.5101.5 - 1.80.8 - 1PAV0
730 / 40024 / 640.2 - 10 / 24 - 80.2 - 10 / 24 - 80.25 - 6 / 24 - 10
0.2 - 2.5 / 0.2 - 2.5101.5 - 1.80.8 - 1PAV0
930 / 40024 / 640.2 - 10 / 24 - 80.2 - 10 / 24 - 80.25 - 6 / 24 - 10
0.2 - 2.5 / 0.2 - 2.5101.5 - 1.80.8 - 1PAV0
1330 / 40024 / 640.2 - 10 / 24 - 80.2 - 10 / 24 - 80.25 - 6 / 24 - 10
0.2 - 2.5 / 0.2 - 2.5101.5 - 1.80.8 - 1PAV0
FWP 6+1 3069284 FWP 6+1 3069284 FWP 8+1 3069297 FWP 12+1 3069307
30 / 40024 / 64
30 / 40024 / 64
30 / 40024 / 64
30 / 40024 / 64
FTP 6+1 3069239 FTP 6+1 3069239 FTP 8+1 3069242 FTP 12+1 3069255
24 / 40024 / 2.540.5 - 0.6
24 / 40024 / 2.540.5 - 0.6
24 / 40024 / 2.540.5 - 0.6
24 / 40024 / 2.540.5 - 0.6
FBP 6+1 3069406 FBP 6+1 3069406 FBP 8+1 3069407 FBP 12+1 3069408
10 PHOENIX CONTACT
Plug-in bridges Plug-in bridges, pre-assembled and printed
2-pos. 3-pos. 4-pos. 5-pos. 6-pos. 10-pos. 3-pos.Pos. 1, 3
4-pos.Pos. 1, 4
5-pos.Pos. 1, 3, 5
10-pos.Pos. 1, 4, 7, 10
UTWE ... FBS 2-83030284
FBS 3-83030297
FBS 4-83030307
FBS 5-83030310
FBS 6-83032470
FBS 10-83030323
FBS 1/3-83032363
FBS 1/4-83032376
FBS 1/3/5-83032389
FBS 1/4/7/10-83032402
FTP ... FBS 2-83030284
FBS 3-83030297
FBS 4-83030307
FBS 5-83030310
FBS 6-83032470
FBS 10-83030323
FBS 1/3-83032363
FBS 1/4-83032376
FBS 1/3/5-83032389
FBS 1/4/7/10-83032402
Plug-in test plug adapter, 4 mmOrange Yellow Green Violet Black Blue Red Gray Brown
UTWE ... 1)FTP ...
PAI-4-FIX OG3034455
PAI-4-FIX YE3032745
PAI-4-FIX GN3032758
PAI-4-FIX VT3032761
PAI-4-FIX BK3032774
PAI-4-FIX BU3032729
PAI-4-FIX RD3032732
PAI-4-FIX GY3032790
PAI-4-FIX BN3032787
Plug-in bridges, with extraction tool Switching jumpers
2-pos. 3-pos. 4-pos. 2-pos. 3-pos. 4-pos.
UTWE ... 1) FBSRH 2-83033802 1)
FBSRH 3-83033803 1)
FBSRH 4-83033804 1) — — —
FTP ... FBSRH 2-83033802
FBSRH 3-83033803
FBSRH 4-83033804
SB-MER 2-83000587
SB-MER 3-83000588
SB-MER 4-83000589
1) Can only be used inside the control cabinet
FAME accessories
PHOENIX CONTACT 11
X
62
+3 -1
22 37
81
61
35,74�
1�
Order No. Type Width X[mm]
Housing panel thickness[mm]
3069048 UTWE 6/4+1 74 +0.5
1 4
3069049 UTWE 6/5+1 82.3 +0.53069051 UTWE 6/6+1 90.5 +0.53069064 UTWE 6/8+1 107 +0.53070008 UTWE 6/4+1 BI 107 +0.53069077 UTWE 6/12+1 139.5 +0.53069996 UTWE 6/6+1 BI 139.5 +0.5
FAME mounting
Cable lugs for use on screwable test sockets
Fork-type cable lug, uninsulated
Fork-type cable lug, uninsulated
Fork-type cable lug, insulated
Fork-type cable lug, insulated
Ring cable lug, uninsulated
Ring cable lug, uninsulated
Ring cable lug, insulated
Ring cable lug, insulated
FTP ... C-FC 1,5/M33240137
C-FC 2,5/M33240142
C-FCI 1,5/M33240032
C-FCI 2,5/M33240037
C-RC 1/M3 DIN3240070
C-RC 2,5/M3 DIN3240076
C-RCI 1,5/M33240016
C-RCI 2,5/M33240021
Screwable test sockets, 4 mmClear Red Blue Yellow Green Violet Black Gray Brown
FTP ...PSBJ-URTK 6
FARBLOS3026450
PSBJ-URTK 6 RD3026719
PSBJ-URTK 6 BU3026434
PSBJ-URTK 6 YE3026405
PSBJ-URTK 6 GN3026418
PSBJ-URTK 6 VT3026421
PSBJ-URTK 6 BK3026447
PSBJ-URTK 6 GY3026612
PSBJ-URTK 6 BN3026971
Screwdriver Marking 3) Transducer block cover, internal 4) Adapter for DIN rail
mounting 4)Uninsulated Insulated
Cover profile Cover profile holder
UTWE ... SF-SL 0,8X4,0-1001212551
SF-SL 0,8X4,0-100 S-VDE1212588 UC-TM 8 AP RSC-T
3059139APH-UTWE 6
3069056E-UTWE 63069055
FWP ... — — UC-TM 8 — — —FTP ... 2) SF-SL 0,8X4,0-100
1212551SF-SL 0,8X4,0-100 S-VDE
1212588 UC-TM 8 — — —FBP ... — — UC-TM 8 — — —
3) See Catalog 5 and the product area on the website, phoenixcontact.net
Panel cutout dimensions Side view dimensions
4) Without figure
2) For test sockets
12 PHOENIX CONTACT
Touch proofThe terminal points have been designed in such a way that they feature shock protection according to BGV A2. All clamping screws are enclosed within the housing, which means that it is not possible to come into contact with live parts.
The product range of compact rotary
switches up to 20 A has been designed for
the switch programs which are available
for application in energy technology.
The use of high-quality materials results in a
long mechanical and electrical service life.
The constructive design of the rotary
switches affords a high level of safety: non-
current-carrying parts are made of plastic,
meaning that voltage cannot be transmitted
to the control cabinet panel, for example.
Compact designThanks to their compact design and the direction of the conductor connection, the rotary switches are ideally suited for switchgear in which space is limited.
Rotary switches for use in the field of energy technology
Easy mountingThe rotary switches are attached by means of a robust four-hole attachment. The handle connection can be operated from the front, making it easy to install.
PHOENIX CONTACT 13
RoHS
A P
Individual markingMarker carriers with corresponding snap-in labels for individual printing are available to ensure clear identification of the rotary switches.
Universal and maintenance-freeNotable features of the 2.5 mm2 screw connection are: a plus-minus screw drive; captive screws, open in delivery state; safe screw-driver guidance; connection of conductors with and without a ferrule or fork-type cable lug.
Shock- and vibration-resistantThe rotary switches have been shock- and vibration-tested and are suitable for applications which involve extreme vibrations.
Worldwide useComprehensive approvals permit international use. The rotary switches are free from cadmium and compliant with the RoHS directive.
L2 L3 NL1
14 PHOENIX CONTACT
L2-L3
L1-L2 L3-L1
0
S00042 4 6 8
1 3 5 7
0
L1-L2
L2-L3
L3-L1
V2 4
L1
L2
L3
71 5
0
L2-N
L1-N
L3-N
L2-L3
L1-L2
L3-L1
S00072 4 6 8 10 12
1 3 5 7
L1-L2
L2-L3
0
L1-N
L3-L1
L2-N
L3-N
9 11
V1 3
L1
L2
L3
N
2610 12
L1-L2
L2-L3
L3-L1
S00232 4 6 8
1 3 5 7
L1-L2
L2-L3
L3-L1
V2 4
L1
L2
L3
71 5
0
1
2
3
S00382 4 6 8 10 12 16 18 20
1 3 5 7
1
0
2
3
9 11 15 17 19
A2 9
L1
L2
L3
1 6 1619 3 8
Voltmeter changeover switch with 0 position
Type Order No. RS20-US-S0004-0204-014H-001 3069700
Function
AngleNumber of positionsSwitching zonesTime program no.
0 — L1-L2 — L2-L3 — L3-L1, three linked voltages
45°—2S0004
Voltmeter changeover switch with 0 position
Type Order No. RS20-US-S0007-0307-014H-001 3069701
Function
AngleNumber of positionsSwitching zonesTime program no.
L3-L1 — L2-L3 — L1-L2 — 0 — L1-N — L2-N — L3-NThree linked voltages and three phases to N45°—3S0007
Voltmeter changeover switch with 0 position
Type Order No. RS20-US-S0023-0203-014H-001 3069702
Function
AngleNumber of positionsSwitching zonesTime program no.
L1-L2 — L2-L3 — L3-L1, three linked voltages
45°—2S0023
Ammeter changeover switch
Type Order No. RS20-US-S0038-0504-014H-001 3069703
Function
AngleNumber of positionsSwitching zonesTime program no.
0 — 1 — 2— 3, three transformer circuits with 0 position
90°25S0038
PHOENIX CONTACT 15
0
13
2
S00482 4 6 8 10 12
1 3 5 7
1
2
0
3
9 11
A3 9
L1
L2
L3
104 2
3
STARTSTOP
S01762 4
1 3
STOP
STARTN
L1
STOP0
START1
2 4
3
0
21
START START
S01772 4 6 8
1 3 5 7
START
START
1
0
2
6
6
01 2
N
L1
START START
1
2 6
5 7
8 4
3
0
1
S02002
1
1
0
Ammeter changeover switch
Type Order No. RS20-US-S0048-0304-014H-001 3069704
Function
AngleNumber of positionsSwitching zonesTime program no.
0 — 1 — 2 — 3, three transformer circuits with 0 position, All-round switching90°13S0048
Control switch
Type Order No. RS20-US-S0176-0102-014H-001 3069705
FunctionAngleNumber of positionsSwitching zonesTime program no.
STOP > < START, withdrawal30°11S0176
Control switch
Type Order No. RS20-US-S0177-0205-014H-001 3069726
Function
AngleNumber of positionsSwitching zonesTime program no.
START > 1 — 0 — 2 < START, withdrawal, double on/off button with snap-in operating positions (rotary switch)60°/30°—2S0177
Off switch
Type Order No. RS20 US-S0200-0102-014H-001 3069706
FunctionAngleNumber of positionsSwitching zonesTime program no.
0 — 160°11S0200
16 PHOENIX CONTACT
0
1
S02012 4
1 3
1
0
0
1
S02022 4 6
1 3 5
1
0
0
1
S02032 4 6 8
1 3 5 7
1
0
0
1 2
S02102 4
1 3
1
0
2
Off switch
Type Order No. RS20-US-S0201-0102-014H-001 3069707
FunctionAngleNumber of positionsSwitching zonesTime program no.
0 — 160°21S0201
Off switch
Type Order No. RS20-US-S0202-0202-014H-001 3069708
FunctionAngleNumber of positionsSwitching zonesTime program no.
0 — 160°32S0202
Off switch
Type Order No. RS20-US-S0203-0202-014H-001 3069709
FunctionAngleNumber of positionsSwitching zonesTime program no.
0 — 160°42S0203
Changeover switch with 0 position
Type Order No. RS20-US-S0210-0103-014H-001 3069710
FunctionAngleNumber of positionsSwitching zonesTime program no.
1 — 0 — 260°11S0210
PHOENIX CONTACT 17
01 2
S02112 4 6 8
1 3 5 7
1
0
2
2 4 6 8 10 12
1 3 5 7
1
0
2
9 11
0
1 2
S0212
2 4 6 8 10 12 1614
1 3 5 7
1
0
2
9 11 1513
0
1 2
S0213
201
S02142 4
1 3
1
2
0
Changeover switch with 0 position
Type Order No. RS20-US-S0211-0203-014H-001 3069711
FunctionAngleNumber of positionsSwitching zonesTime program no.
1 — 0 — 260°22S0211
Changeover switch with 0 position
Type Order No. RS20-US-S0212-0303-014H-001 3069712
FunctionAngleNumber of positionsSwitching zonesTime program no.
1 — 0 — 260°33S0212
Changeover switch with 0 position
Type Order No. RS20-US-S0213-0403-014H-001 3069713
FunctionAngleNumber of positionsSwitching zonesTime program no.
1 — 0 — 260°44S0213
Changeover switch with 0 position
Type Order No. RS20-US-S0214-0103-014H-001 3069723
FunctionAngleNumber of positionsSwitching zonesTime program no.
1 > 0 < 2 withdrawal30°11S0214
18 PHOENIX CONTACT
201
S02152 64 8
1 53 7
1
2
0
21
S02202 4
1 3
2
1
21
S02212 4 6 8
1 3 5 7
2
1
1
2
S05302 4
1 3
2
1
Changeover switch with 0 position
Type Order No. RS20-US-S0215-0203-014H-001 3069724
FunctionAngleNumber of positionsSwitching zonesTime program no.
1 > 0 < 2 withdrawal30°22S0215
Changeover switch without 0 position
Type Order No. RS20-US-S0220-0102-014H-001 3069714
FunctionAngleNumber of positionsSwitching zonesTime program no.
1 — 260°11S0220
Changeover switch without 0 position
Type Order No. RS20-US-S0221-0202-014H-001 3069715
FunctionAngleNumber of positionsSwitching zonesTime program no.
1 — 260°22S0221
Changeover switch without 0 position
Type Order No. RS20-US-S0530-0102-014H-001 3069725
FunctionAngleNumber of positionsSwitching zonesTime program no.
1 — 290°11S0530
PHOENIX CONTACT 19
1 2
S05752 4
1 3
1
2
1 2
S05762 4 6 8
1 3 5 7
1
2
1 2
S07202 4
1 3
1
2
1 32
0
S02412 4 6
1 3 5
1
0
2
3
1
2
3
5
Changeover switch without 0 position, with electrically isolated contacts
Type Order No. RS20-US-S0575-0102-014H-001 3069719
FunctionAngleNumber of positionsSwitching zonesTime program no.
1 — 2 symmetrical90°11S0575
Changeover switch without 0 position, with electrically isolated contacts
Type Order No. RS20-US-S0576-0202-014H-001 069720
FunctionAngleNumber of positionsSwitching zonesTime program no.
2 — 2 symmetrical90°22S0576
Changeover switch without 0 position, with electrically isolated contacts
Type Order No. RS20-US-S0720-0102-014H-001 3069722
FunctionAngleNumber of positionsSwitching zonesTime program no.
1 — 2 symmetrical60°11S0720
Step switch with 0 position
Type Order No. RS20-US-S0241-0204-014H-001 3069716
FunctionAngleNumber of positionsSwitching zonesTime program no.
0 — 1 — 2 — 345°12S0241
20 PHOENIX CONTACT
1 2
0
S02402 4
1 3
1
0
2
1
2
3
2 3
1
S02502 4 6 8 10 12
1 3 5 7
2
1
3
9 11
12
3 7
96
11 5
2
4
3
1
S02512 4 6 8 10 12 14 16
1 3 5 7
2
1
3
4
9 11 13 15
12
3
5 7
910
11
13 15
Step switch with 0 position
Type Order No. RS20-US-S0240-0103-014H-001 3069717
FunctionAngleNumber of positionsSwitching zonesTime program no.
0 — 1 — 260°11S0240
Step switch without 0 position
Type Order No. RS20-US-S0250-0303-014H-001 3069718
FunctionAngleNumber of positionsSwitching zonesTime program no.
1 — 2— 360°23S0250
Step switch without 0 position
Type Order No. RS20-US-S0251-0404-014H-001 3069721
FunctionAngleNumber of positionsSwitching zonesTime program no.
Four steps60°24S0251
PHOENIX CONTACT 21
Ø5
Ø8 - Ø15
6
48
36
A
43
48
4�
1�
29
Rotary switch mounting
Rotary switch internal dimensions AOrder No. Type Dim. A
[mm]3069700 RS20-US-S0004-0204-014H-001 433069701 RS20-US-S0007-0307-014H-001 52.53069702 RS20-US-S0023-0203-014H-001 433069703 RS20-US-S0038-0504-014H-001 71.53069704 RS20-US-S0048-0304-014H-001 52.53069705 RS20-US-S0176-0102-014H-001 33.53069706 RS20-US-S0200-0102-014H-001 33.53069707 RS20-US-S0201-0102-014H-001 33.53069708 RS20-US-S0202-0202-014H-001 433069709 RS20-US-S0203-0202-014H-001 433069710 RS20-US-S0210-0103-014H-001 33.53069711 RS20-US-S0211-0203-014H-001 433069712 RS20-US-S0212-0303-014H-001 52.53069713 RS20-US-S0213-0403-014H-001 623069714 RS20-US-S0220-0102-014H-001 33.53069715 RS20-US-S0221-0202-014H-001 433069716 RS20-US-S0241-0204-014H-001 433069717 RS20-US-S0240-0103-014H-001 33.53069718 RS20-US-S0250-0303-014H-001 52.53069719 RS20-US-S0575-0102-014H-001 33.53069720 RS20-US-S0576-0202-014H-001 433069721 RS20-US-S0251-0404-014H-001 623069722 RS20-US-S0720-0102-014H-001 33.53069723 RS20-US-S0214-0103-014H-001 33.53069724 RS20-US-S0215-0203-014H-001 433069725 RS20-US-S0530-0102-014H-001 33.53069726 RS20-US-S0177-0205-014H-001 43
Rotary switch dimensions Drilling diagram
22 PHOENIX CONTACT
Rotary switch, electrical values according to IEC 60947-3, VDE 0660 Part 107
Rated dataRated continuous current Iu/Ith 20 A
Rated insulation voltage Ui 690 V
Rated impulse withstand voltage Uimp 6 kV
Rated operating current IeAC-21A Switching of ohmic loads including small overloads 20 A
AC-22A Switching of mixed ohmic and inductive loads including small overloads220 V - 500 V 20 A
660 V - 690 V 20 A
AC-15 Switching of solenoid drives, contactors, valves, pulling electromagnets220 V - 240 V 5 A
380 V - 440 V 4 A
Switching capacity
AC-2 Starting of slip ring motors, reversing and plugging, star-delta startup 3-phase, 3-pos.
220 V - 240 V 4 kW
380 V - 440 V 7.5 kW
500 V 10 kW
660 V - 690 V 10 kW
AC-3Direct starting of squirrel-cage motors, switching off during operation, star-delta startup (CH16B)
3-phase, 3-pos.
220 V - 240 V 3 kW
380 V - 440 V 5.5 kW
500 V 5.5 kW
660 V - 690 V 5.5 kW
1-phase, 2-pos.
110 V - 120 V 0.6 kW
220 V - 240 V 2.2 kW
380 V - 440 V 3 kW
AC-4 Starting of squirrel-cage motors, reversing, plugging, inching
3-phase, 3-pos.
220 V - 240 V 0.55 kW
380 V - 440 V 1.5 kW
500 V 1.5 kW
660 V - 690 V 1.5 kW
1-phase, 2-pos.
110 V - 120 V 0.3 kW
220 V - 240 V 0.75 kW
380 V - 440 V 1.5 kW
AC-23A Frequent switching of motors or other highly inductive loads
3-phase, 3-pos.
220 V - 240 V 3.7 kW
380 V - 440 V 7.5 kW
500 V 7.5 kW
660 V - 690 V 7.5 kW
1-phase, 2-pos.
110 V - 120 V 0.75 kW
220 V - 240 V 2.5 kW
380 V - 440 V 3.7 kW
Breaking capacity220 V - 240 V 150 A
380 V - 440 V 150 A
660 V - 690 V 80 A
PHOENIX CONTACT 23
Power dissipation, vibration resistance, shock resistancePower dissipation per position at Iu 0.9 W
Vibration resistance min. 4 g, 2-100 Hz, 1.6 mm
Shock resistance min. 5 g, 6 ms
Short circuit stabilityMax. backup fuse, gL/gG characteristics 25 A
Rated short-time current resistance, (1 s current) 140 A
Connection cross sectionSolid 2 x 0.5 to 2 x 2.5 mm2
Stranded 2 x 0.75 to 2 x 2.5 mm2
Stranded with ferrules according to DIN 46228with insulating collar 2 x 1.5 mm2
without insulating collar 2 x 2.5 mm2
Max. ambient temperature of the contact unitOpen at 100% Iu/Ith 55°C over 24 hours
with peaks up to 60°C
Encapsulated at 100% Ithe 35°C over 24 hours with peaks up to 40°C
Switch types according to UL/CSA
Rated dataRated continuous current Iu/Ith 20 A
Rated insulation voltage Ui 300 V
Rated operating current IePilot Duty, Heavy, VAC A 300
Ampere Rating, non- or weakly inductive load 20 A
Connection cross sectionSingle- or multi-strand 2 x 12 AWG
AWG wire (without ferrules) 2 x 14 AWG
Switching capacity
Normal motor load, DOL rating (similar to AC-3)
3-phase, 3-pos.110 V - 120 V 1.5 HP
220 V - 240 V 3 HP
1-phase, 2-pos.
110 V - 120 V 0.5 HP
220 V - 240 V 1 HP
277 V 2 HP
Heavy-duty motor load, reversing rating (similar to AC - 4)
3-phase, 3-pos.110 V - 120 V 0.5 HP
220 V - 240 V 1 HP
1-phase, 2-pos.
110 V - 120 V 0.17 HP
220 V - 240 V 0.5 HP
277 V 0.6 HP
24 PHOENIX CONTACT
BLUEMARK CLEDHigh-speed printer with compact UV LED technology
Aluminum device marker
For high-quality device and system marking, a comprehensive product range of aluminum markers is available for sticking or screwing on as well as for riveting or snapping into marker carriers.The markers can be labeled quickly, easily, and cost-effectively with the BLUEMARK CLED.Further advantages: highly resistant and optimum printing quality, resistance to solvents, suitable for use even under harsh industrial conditions.
Wide range of materialsThe comprehensive range of UniCardmaterials is available in different versions, colors, and sizes, for all applications relating to marking terminal blocks, conductors, devices, and systems.
The new BLUEMARK CLED makes labeling
standardized UniCard materials for terminal
blocks, conductors, devices, and system
marking as easy as printing on paper.
State-of-the-art CLED UV technology,
energy consumption reduced by 90%,
special solvent-free fluid, and low-noise
operation make the printer an
environmentally friendly high-speed
printer, capable of printing up to
10,000 labels per hour.
Fast front feedRegardless of how the magazine is assembled, it is easy to feed in and print individual sheets.
PHOENIX CONTACT 25PHOENIX CONTACT 25
Perfect printing quality UV light ensures that the BLUEMARK CLED hardens the printing fluid quickly. This guarantees high-quality printing, immediate wipe- and scratch resistance, as well as high chemical resistance.
Printing to orderPrint jobs can be set up and printed without user intervention thanks to the exchangeable magazines. Printing can be rotated by 180° as required, thanks to automatic material detection.
Easy operationAn easy operating concept with a large color touchscreen, easy to understand symbols, and plain text messages offer the highest level of operating ease.
CLED - compact UV LED printing technologyBenefits:- Perfect printing quality- No drying time- High wipe and abrasion resistance- Excellent resistance to chemicals- Environmentally friendly, as the system is
solvent-free
Ready to print in an instant The BLUEMARK CLED is ready to print as soon as it is switched on without needing to warm up.
26 PHOENIX CONTACT
Terminal block width[mm] Markers per sheet Pcs. / Pkt. Type
Order No.
WH
4.2 120 10 UC-TM 4 0818111
5.2 96 10 UC-TM 5 0818108
6.2 80 10 UC-TM 6 0818085
8.2 56 10 UC-TM 8 0818072
10.2 48 10 UC-TM 10 0818069
12 40 10 UC-TM 12 0819194
16 32 10 UC-TM 16 0819217
UniCard UC-TM...The UC-TM 8 markers are ideal for fast and precise marking of the FAME measuring transducer test system. The markers are available in all accepted pitch dimensions and colors, and can also be used with standard modular terminal blocks from the CLIPLINE complete system.The multipartite marking strips can be easily separated if required and provide sufficient space for multi-row marking. Furthermore, the sheets provide space for including function texts
Other modular terminal block or conductor marking materials, e.g., for the THERMOMARK LINE printing system from Phoenix Contact can be found in Catalog 5 and in the product area on the website, phoenixcontact.net.
Terminal block width[mm]
Markers per
sheetType
Order No.
RD OG YE VT BU GN
4.2 120 UC-TM 4 0818250 0818221 0818234 0819084 0818247 0818263
5.2 96 UC-TM 5 0818302 0818276 0818289 0819107 0818292 0818315
6.2 80 UC-TM 6 0818357 0818328 0818331 0819110 0818344 0818360
8.2 56 UC-TM 8 0818409 0818373 0818386 0819123 0818399 0818412
10.2 48 UC-TM 10 0818454 0818425 0818438 0815936 0818441 0818467
12 40 UC-TM 12 0817701 0817691 0819204 0822660 0817785 0817808
16 32 UC-TM 16 0817798 0817772 0819220 0822673 0817769 0817756
Terminal marking for a tall marker groove
PHOENIX CONTACT 27
Aluminum device marking 1)For snapping into CARRIER-EMP... label frames
Lettering field size [mm] Pcs. / Pkt. Type Order No.
27 x 15 90 EMP-AL (27X15) 0830776
49 x 15 45 EMP-AL (49X15) 0830778
60 x 15 45 EMP-AL (60X15) 0830779
60 x 30 45 EMP-AL (60X30) 0830796
Designed for screwing/riveting
39 x 15 45 EMSP-AL (39X15) 083051050 x 15 45 EMSP-AL (50X15) 083077350 x 30 45 EMSP-AL (50X30) 0830502
75.6 x 54 15 EMSP-AL (75,6X54) 083050390 x 60 15 EMSP-AL (90X60) 0830504
UniCard device markingFor snapping into CARRIER-EMP... label frames
Lettering field size [mm] Markers per card Pcs. / Pkt. Type Order No.
WH YE SR
17 x 15 8 10 UC-EMP (17X15) 0825421 0825422 0825423
27 x 15 8 10 UC-EMP (27X15) 0825439 0825440 0825441
49 x 15 4 10 UC-EMP (49X15) 0825457 0825458 0825459
60 x 15 4 10 UC-EMP (60X15) 0822259 0825330 0827647
60 x 30 3 10 UC-EMP (60X30) 0822275 0825331 0827648Designed for screwing/riveting
50 x 15 8 10 UC-EMSP (50X15) 0828706 0828707 0828708
50 x 30 8 10 UC-EMSP (50X30) 0828709 0828710 0828711
UniCard and aluminum markersThe UC-EMP... and EMP-AL... markers can be quickly and easily snapped into the CARRIER-EMP... label frames. Furthermore, the UC-EMSP... and EMSP-AL... markers are available, which can be directly screwed or riveted in. The FAMEmeasuring transducer test system and the rotary switch can thereby be clearly marked.
Other device or system marking materials, e.g., for the THERMOMARK LINE printing system from Phoenix Contact, can be found in Catalog 5 and in the product area on the website, phoenixcontact.net.
Label frames designed for screwing/riveting Lettering field size [mm] Pcs. / Pkt. Type Order No.
17 x 15 80 CARRIER-EMP (17X15) 0827450
27 x 15 80 CARRIER-EMP (27X15) 0827451
49 x 15 40 CARRIER-EMP (49X15) 0827452
60 x 15 40 CARRIER-EMP (60X15) 0827453
60 x 30 30 CARRIER-EMP (60X30) 0827454
Marker carriers for device marking
1) Magazines for printing aluminum device markers can be found in Catalog 5 and in the product area on the website phoenixcontact.net
PHOENIX CONTACT GmbH & Co. KG32825 Blomberg, GermanyPhone: + 49 5235 3-12000Fax: + 49 5235 3-12999phoenixcontact.net
phoenixcontact.net
IC01
-13.
000.
L3.2
013
MN
R 5
2003
658/
2013
-04-
01/0
0
• Cables and connectors• Controllers and PLCs• DIN rail power supplies and UPS• Electronic reversing contactors and
motor control• Electronics housing• Ethernet networks• Fieldbus components and systems• Functional safety• HMIs and industrial PCs
• I/O systems• Industrial communication technology• Industrial lighting• Installation and mounting material• Marking and labeling • Measurement and control technology• Modular terminal blocks• Monitoring and signaling• PCB terminal blocks and
PCB connectors
• Plug-in connectors• Protective devices• Relays• Sensor cables and connectors• Software• Surge protection devices• System cabling for DCS and PLC• Tools• Wireless data communication
Product range
Prin
ted
in G
erm
any
© P
HO
ENIX
CO
NT
AC
T 2
013
Always up-to-date, always available to you. Here you'll find everything on our products, solutionsand service: