Auto-swing Auto-air direction control 5-level air direction setting 10° 70° Auto-swing from 10° to 70° Settable to 5 different levels between 10° to 70° The air direction is set automatically to the memorised position of the previous air direction. (Initial setting is 10° for c ooling and 70° for heating.) 10° 70° 10° 70° Drastic size reduction Reduced size (by 22% in volume, 32% in installation area)makes installation possible in a very limited space. Sophisticated extension design Easier to install and service Compact and stylish design that does not detract from the decor of the room. Improved airflow modes realise comfortable air distribution across the entire room Switchable fan speed: High/Low Programme "Dry" To carry air to the far side of long rooms, extra- high airflow adds 10% more fan speed the "high" setting. Air discharge strength is selected from the remote controller. Conventional (FAY71FAVE) New model 21 Kg 13 Kg Easier to install and service Maintenance possible from the front of the unit All maintenance tasks can be carried out via front access. During service work, attachment and detachment of parts is easier. Low gas pressure detection Insufficient gas charging is normally hard to detect. During post-installation trials and regular inspection procedures, the refrigerant level is monitored by microprocessor to maintain proper gas pressure. WALL MOUNTED TYPE Made more compact, stylish, and quieter 23 24 Guide Line up P. 3–4, 7–8 Outdoor units P. 33–34 Options P. 58 Outer dimension drawings P. 62, 63 Remote controllers P. 35–36 Standard specifications P. 41, 51 Two selectable temperature-sensors Both indoor unit and wired remote controller (option) contain temperature- sensors. Temperature sensing can be set at the unit or, to further improve comfort level, closer to the target area at the wired remote control. Flap is closed when not operating Drain pan and air filter can be kept clean by mould-proof polystyrene Removable and washable grille DIII-NET connection is standard specification. Adapter is not required. Light weight Reduced weight by 8kg greatly facilitates installation. *Temperature-sensor on indoor unit must be used when the air c onditioner is c ontrolled from another room. **Wireless remote controller does not have a BRC7E619 Wired LCD remote controller Wireless LCD remote controller A signal receiver must be added to the indoor unit. Wireless remote controller and signal receiver unit are sold as a set. Note: Remote controller cable not included. Cables must be procured locally. Accessory required for indoor unit (option) BRC1C61 Cooling only BRC7EA618 Heat pump BRC7C611W Cooling only BRC7C610W Heat pump WALL MOUNTED TYPE FAY FAY71LVE / FAY100FAVE Cooling only FAY71LVE / FAY100FAVE FAY71LVE FAY71L FAY100F FAY100FAVE Heat pump Mould prevention Comfort Work & Servicing Control features Others Features (Features are explained on P. 37–38.) Feature Model Heat pump Cooling only * 1 Applicable when wired remote controller is used * 2 Applicable to R71LU/R100LU outdoor units (for temp. down to – 15°C) (An option is required.) * 3 Applicable to RY71LU/RY100LU outdoor units (for temp. down to – 5°C) * 4 Applicable to R(Y)71LU/100LU outdoor units Dehumidification is microprocessor controlled to prevent abrupt and uncomfortable changes in air temperature. *4 *4 *4 *4 *1 *1 *3 *2 Switchable fan speed Auto s wing Programme "Dry" High fan speed mode Draft prevention func tion Upward Hot start Year-round cooling applicable Timer selector Pre charged for up to 30 m Drain pump mechanism Mould-proofing drain pan Mould resistant treatment for filter Filter sign Low gas pressure detection Emergency operation Self-diagnosis function C ontrol by 2 remote c ontrollers Auto-c ooling/heating change-over Auto-restart PE fin C ontrol by 1 remote c ontroller External command c ontrol C entral remote c ontrol Interloc k c ontrol Two selectable temperature-sensors 1,050 mm 290 mm -70 mm -200 mm (FAY71FAVE) Conventional model Height of drain up Drain-pump kit Indoor unit Installs onto side of unit. 1,000 mm (Available to be installed onto right side.) Comfort even on the far side of the room Drain enclosure can be used on either left and right side. Drain pump kit is available as option. Below features only apply to FAY71L. Signal receiver unit (Installed type) (FAY71LVE) 45 / 41 dB(A) FAY100FA High Low Sound level 43 / 37 dB(A) FAY71L High Low Sound level

Upload: others

Post on 17-Feb-2021

0 views

Category:

Documents


0 download

TRANSCRIPT

  • Auto-swing Auto-air direction control5-level air direction setting

    10°

    70°Auto-swing from 10° to 70°

    S ettable to 5 different levels between 10° to 70°

    The air direc tion is set automatic ally to the memorised pos ition of the previous air direc tion. (Initial setting is 10° for c ooling and 70° for heating.)

    10°

    70°

    10°

    70°

    Drastic size reduction

    Reduced size (by 22% in volume, 32% in installation area)makes installation possible in a very limited space.

    Sophisticated extension design

    Easier to install and service

    Compact and stylish design that does not detract from the decor of the room.

    Improved airflow modes realise comfortable air distribution across the entire room

    Switchable fan speed: High/Low

    Programme "Dry"

    To carry air to the far side of long rooms, extra-high airflow adds 10% more fan speed the "high" setting. Air discharge strength is selected from the remote controller.

    Conventional(FAY71FAVE)

    New model

    21 Kg 13 Kg

    Easier to install and service

    Maintenance possible from the front of the unitAll maintenance tasks can be carried out via front access. During service work, attachment and detachment of parts is easier.

    Low gas pressure detectionInsufficient gas charging is normally hard to detect. During post-installation trials and regular inspection procedures, the refrigerant level is monitored by microprocessor to maintain proper gas pressure.

    WALL MOUNTED TYPE

    Made more compact, stylish, and quieter

    23 24Guide Line up

    P. 3–4, 7–8Outdoor unitsP. 33–34

    OptionsP. 58

    Outer dimension drawingsP. 62, 63

    Remote controllersP. 35–36

    Standard specificationsP. 41, 51

    Two selectable temperature-sensorsBoth indoor unit and wired remote controller (option) contain temperature-sensors. Temperature sensing can be set at the unit or, to further improve comfort level, closer to the target area at the wired remote control.

    Flap is closed when not operating

    Drain pan and air filter can be kept clean by mould-proof polystyrene

    Removable and washable grille

    DIII-NET connection is standard specification. Adapter is not required.

    Light weightReduced weight by 8kg greatlyfacilitates installation.

    *Temperature-sensor on indoor unit must be used when the air c onditioner is c ontrolled from another room.

    **Wireless remote c ontroller does not have a

    BRC7E619

    Wired LCD remote controller Wireless LCD remote controllerA s ignal rec eiver must be added to the indoor unit.

    Wireless remote c ontroller and s ignal rec eiver unit are sold as a set.

    Note: R emote c ontroller c able not inc luded. C ables must be proc ured loc ally.

    Accessory required for indoor unit (option)

    BRC1C61

    Cooling only

    BRC7EA618Heat pump

    BRC7C611WCooling only

    BRC7C610WHeat pump

    WALL MOUNTEDTYPE

    FAYFAY71LVE / FAY100FAVECooling onlyFAY71LVE / FAY100FAVE

    FAY71LVE

    FAY71L

    FAY100F

    FAY100FAVE

    Heat pump

    MouldpreventionComfort Work & Servicing Control features Others

    Features (Features are explained on P. 37–38.)Feature

    Model

    Heat pumpCooling only

    *1Applic able when wired remote c ontroller is used*2Applic able to R 71LU/R 100LU outdoor units (for temp. down to – 15°C ) (An option is required.)*3Applic able to R Y71LU/R Y100LU outdoor units (for temp. down to – 5°C )*4Applic able to R (Y)71LU/100LU outdoor units

    Dehumidification is microprocessor controlled to prevent abrupt and uncomfortable changes in air temperature.

    *4

    *4

    *4

    *4

    *1

    *1

    *3

    *2

    Sw

    itch

    ab

    le

    fan

    sp

    ee

    d

    Au

    to

    swin

    g

    Pro

    gra

    mm

    e

    "Dry

    "

    Hig

    h

    fan

    sp

    ee

    d

    mo

    de

    Dra

    ft

    pre

    ven

    tion

    fu

    nc

    tion

    Up

    wa

    rd

    Ho

    t st

    art

    Ye

    ar-

    rou

    nd

    c

    oo

    ling

    a

    pp

    lica

    ble

    Tim

    er

    sele

    cto

    r

    Pre

    c

    ha

    rge

    d

    for

    up

    to

    3

    0

    m

    Dra

    in

    pu

    mp

    m

    ec

    ha

    nis

    m

    Mo

    uld

    -pro

    ofin

    g

    dra

    in

    pa

    n

    Mo

    uld

    re

    sist

    an

    t tr

    ea

    tme

    nt

    for

    filte

    r

    Filt

    er

    sig

    n

    Lo

    w

    ga

    s p

    ress

    ure

    d

    ete

    ctio

    n

    Em

    erg

    en

    cy

    op

    era

    tion

    Se

    lf-d

    iag

    no

    sis

    fun

    ctio

    n

    Co

    ntr

    ol

    by

    2

    rem

    ote

    c

    on

    tro

    llers

    Au

    to-c

    oo

    ling

    /he

    atin

    g

    ch

    an

    ge

    -ove

    r

    Au

    to-r

    est

    art

    PE

    fin

    Co

    ntr

    ol

    by

    1

    rem

    ote

    c

    on

    tro

    ller

    Ext

    ern

    al

    co

    mm

    an

    d

    co

    ntr

    ol

    Ce

    ntr

    al

    rem

    ote

    c

    on

    tro

    l

    Inte

    rlo

    ck

    co

    ntr

    ol

    Tw

    o

    sele

    cta

    ble

    te

    mp

    era

    ture

    -se

    nso

    rs

    1,050 mm

    290 mm

    -70 mm-200 mm

    (FAY71FAVE)Conventional model

    Height of drain up

    Drain-pump kitIndoor unit

    Installs onto side of unit.

    1,000 mm

    (Available to be installed onto right side.)

    Comfort even on the far side of the room

    Drain enclosure can be used on either left and right side.

    Drain pump kit is available as option.

    Below features only apply to FAY71L.

    Signal receiver unit(Installed type)

    (FAY71LVE)

    45/41dB(A)FAY100FA

    High Low

    Sound level

    43/37dB(A)FAY71L

    High Low

    Sound level

  • Guide Existing models:P.3 ~ 4

    Outdoor units:P.25 ~ 26

    Options:P.36 ~ 37

    Outer dimension drawings:P.38 ~ 45

    Remote controllers:P.27 ~ 28

    Standard specifications:P.34

    Guide Line up P. 3–4, 7–8

    Outdoor unitsP. 33–34

    OptionsP. 58

    Outer dimension drawingsP. 63

    Remote controllersP. 35–36

    Standard specificationsP. 42, 52

    Note: For optimal installation, space factors should be accurately calculated.

    FLOOR STANDING TYPE

    A good choice for spaces with ceilings so high that heating by ceiling-mounted units is inefficient.

    Vertical airflow adjustment is possible when (changing between cooling and heating or) to match interior spaces and partitions.

    Auto-swing Manual setting of vertical airflow louvers

    71LA 41 35

    Quiet operation Easier to install and service

    LightweightIndoor unit High Low

    125LA 49 43100LA 46 40

    The unit can be easily transported and installed.

    Auto-swing delivers comfort to every corner of the room

    FVY units have swinging louver spreads comfortable airflow. Any uncomfortable sensation of sudden change is avoided by a slow cycle of 2 to 3 full swings per minute.

    Switchable fan speed: High/Low

    Long-life filter lasts about 1 year * Maintenance not required*For dust concentration of 0.15 mg/m3

    Dehumidification is microprocessor con-trolled to prevent abrupt and uncomfort-able changes in air temperature.

    Low gas pressure detectionInsufficient gas charging is normally hard to detect. During post-installation trials and regular inspection procedures, the refrigerant level is monitored by microprocessor to maintain proper gas pressure.

    The floor-standingconfiguration meansthe FVY is easy to installand maintain. It can also be installedunder high ceilings.

    Easy-to-operate, handy LCD control panel

    The LCD displays text, numbers and graphics to indicate the temperature setting, timer setting, auto-swing, fan speed, and more. Furthermore, the LCD panel can be detached and used as a remote controller, so air conditioning can be controlled from another room or from the cash register. (Remote controller cable not included. Cables must be procured locally.)

    Programme "Dry"

    25 26

    Note: This remote c ontroller has a temperature-sensor.

    71 class 45 kg 39 kg

    Indoor unit ConventionalFVY-F New model

    125 class 67 kg 47 kg100 class 63 kg 46 kg

    Weight

    Two selectable temperature-sensorsTemperature-sensors on both indoor unit and wired remote controller. Temperature sensing can be set closer to the target area to further improve comfort level.

    2 weeks AnnualConventional

    filterLong-life filter

    Filter exchange intervalLCD control panel is standard

    FLOOR STANDINGTYPE

    FVYFVY71LAVE–125LAVECooling onlyFVY71LAVE–125LAVEHeat pump

    MouldpreventionComfort Work & Servicing Control features Others

    Features (Features are explained on P. 37–38.)Feature

    Model

    Heat pumpCooling only

    *1Applic able to R 71LU– R 125LU outdoor units (for temp. down to – 15°C ) (An option is required.)*2Applic able to R Y71LU– R Y125LU outdoor units (for temp. down to – 5°C ) *3Applic able to R (Y)71LU– 125LU outdoor units

    *3

    *3

    *3

    *3

    *2

    *1

    Sw

    itch

    ab

    le

    fan

    sp

    ee

    d

    Au

    to

    swin

    g

    Pro

    gra

    mm

    e

    "Dry

    "

    Ho

    t st

    art

    Tw

    o

    sele

    cta

    ble

    te

    mp

    era

    ture

    -se

    nso

    rs

    Ye

    ar-

    rou

    nd

    c

    oo

    ling

    a

    pp

    lica

    ble

    Tim

    er

    sele

    cto

    r

    Pre

    c

    ha

    rge

    d

    for

    up

    to

    3

    0

    m

    Lo

    ng

    -life

    fil

    ter

    Mo

    uld

    re

    sist

    an

    t tr

    ea

    tme

    nt

    for

    filte

    r

    Filt

    er

    sig

    n

    Lo

    w

    ga

    s p

    ress

    ure

    d

    ete

    ctio

    n

    Em

    erg

    en

    cy

    op

    era

    tion

    Se

    lf-d

    iag

    no

    sis

    fun

    ctio

    n

    Co

    ntr

    ol

    by

    2

    rem

    ote

    c

    on

    tro

    llers

    Au

    to-c

    oo

    ling

    /he

    atin

    g

    ch

    an

    ge

    -ove

    r

    Au

    to-r

    est

    art

    Co

    ntr

    ol

    by

    1

    rem

    ote

    c

    on

    tro

    ller

    Ext

    ern

    al

    co

    mm

    an

    d

    co

    ntr

    ol

    Ce

    ntr

    al

    rem

    ote

    c

    on

    tro

    l

    Inte

    rlo

    ck

    co

    ntr

    ol

    PE

    fin

    *Temperature-sensor on indoor unit must be used when the air c onditioner is c ontrolled from another room. **Wireless remote c ontroller does not have a temperature-sensor.

    Note : Anec hoic c hamber c onvers ion value, measured ac c ording to J IS parameters and

    41/35dB(A)FVY71LA

    High Low

    Sound level

    dB(A)

  • DUCT CONNECTION MIDDLE STATIC PRESSURE TYPE

    2827

    FDMG71A

    Freedom of layout Quiet operation

    Middle static pressure type is available in a larger than standard space

    Duct connection is simpler with standard rear intake chambers

    The duct system allows the efficient location of discharge outlets in accordance with the room layout Indoor unit High

    FDMG125A 45FDMG100A 44

    42LOW38

    FDMG140AFDMG180A

    4647

    3736

    3637

    FDYM03FA

    FDYM05FA 44FDYM04FA 39

    39

    FDYM06FA 46

    Switchable fan speed: High/Low

    Programme "Dry"Dehumidification is microprocessor controlled to prevent abrupt and un-comfortable changes in air temperature.

    Low gas pressure detectionInsufficient gas charging is normally hard to detect. During post-installation trials and regular inspection procedures, the refrigerant level is monitored by microprocessor to maintain proper gas pressure.

    Compact, 295 mm high design makes installation possible where the ceiling space is limited (For FDYM)

    Air c onditioner295 mm

    Ordinary duc t(proc ured loc ally)

    Ordinary duc t(proc ured loc ally)

    Air blow Air intake

    305 mm or more

    See pages 31–32 for details of the Multi Series.

    Supports simultaneous running of the twin and triple multi operations.Twin Multi Operation Triple Multi Operation

    Simultaneous air conditioning of two rooms and ventilation grille (ventilation opening)

    Ventilation grille

    Door-installedventilation grille

    Ventilation grille

    Wall-installedventilation grille

    Under-door c utout

    Under-door cutoutWhen air conditioning two rooms simultaneously, the air discharged into each room must be circulated back to the air conditioner. To achieve this, a ventilation duct should be installed for each room or one of the indicated ventilation grilles should be installed on the partitioning wall or under the door between the rooms.

    Ventilates air through the partitioning wall. (S ee right)

    Partitioning wall

    Note: The under-door cutout method should be used only when there is a small volume of airflow.

    FDYM03FA

    FDMG100A

    39dB(A)FDYM03FA

    (220V)

    High

    Sound level

    Guide Line upP. 3–10

    Outdoor unitsP. 33–34

    OptionsP. 59

    Outer dimension drawingsP. 64, 65

    Remote controllersP. 35–36

    Standard specificationsP. 43, 48, 53, 56

    Unit can be mounted in the ceiling and air can be delivered freely by duct.

    DUCT CONNECTIONMIDDLE STATIC PRESSURE TYPE

    FDMG/FDYMFDMG71AV1–180AV1FDYM03FAV1–06FAV1

    Cooling only

    FDYM03FAV1–06FAV1Heat pump

    Comfort Work & Servicing Control features OthersFeatures (Features are explained on P. 37–38.)

    *3

    *3

    *3

    *3

    *2

    *1

    Feature

    Model

    Heat pump

    Cooling only

    FDMGFDYM

    *1Applic able to R 71LU– R 140LU outdoor units (for temp. down to – 15°C ) (An option is required.)*2Applic able to R Y71LU– R Y140LU outdoor units (for temp. down to – 5°C ) and R Y200LU– R Y250LU outdoor units (for temp. down to – 0°C )*3Applic able to R (Y)71LU– 140LU outdoor units

    Sw

    itch

    ab

    le

    fan

    sp

    ee

    d

    Pro

    gra

    mm

    e

    "Dry

    "

    Ho

    t st

    art

    Tim

    er

    sele

    cto

    r

    Pre

    c

    ha

    rge

    d

    for

    up

    to

    3

    0

    m

    Lo

    w

    ga

    s p

    ress

    ure

    d

    ete

    ctio

    n

    Em

    erg

    en

    cy

    op

    era

    tion

    Se

    lf-d

    iag

    no

    sis

    fun

    ctio

    n

    Co

    ntr

    ol

    by

    2

    rem

    ote

    c

    on

    tro

    llers

    Au

    to-r

    est

    art

    Ad

    just

    ab

    le

    ext

    ern

    al

    sta

    tic

    pre

    ssu

    re

    Gro

    up

    cont

    rol

    by

    1 re

    mot

    e co

    ntro

    ller

    Ext

    ern

    al

    co

    mm

    an

    d

    co

    ntr

    ol

    Ce

    ntr

    al

    rem

    ote

    c

    on

    tro

    l

    Inte

    rlo

    ck

    co

    ntr

    ol

    PE

    fin

    Twin

    an

    d

    trip

    le

    mul

    ti op

    erat

    ion

    Au

    tom

    atic

    c

    oo

    l/h

    ea

    tc

    ha

    ng

    e

    -ove

    r

    Ye

    ar-

    rou

    nd

    c

    oo

    ling

    a

    pp

    lica

    ble

    BRC4C64

    Wired LCD remote controller Wireless LCD remote controller

    Wireless remote c ontroller and s ignal rec eiver unit are sold as a set.

    Note: R emote c ontroller c able not inc luded. C ables must be proc ured loc ally.

    Accessory required for indoor unit (option)

    BRC1C61 Cooling only

    BRC4C62Heat pump

    Signal receiver unit(Separate type)

    For FDYM

    For FDMGDigital remote controller

    KRC47-2AKRC47-4A

    Remote controller

    Note : Anec hoic c hamber c onvers ion value, measured ac c ording to J IS parameters and

    dB(A) (220V)

    KRC47-1A

  • 3029

    Supports simultaneous running of the triple and double twin multi operations.

    Triple Multi Operation Double twin Multi Operation

    To achieve increased durability by improved resistance to salt corrosion and atmospheric pollution, coated PE fins (with special acryl pretreatment) are used for the heat exchanger of the outdoor unit.

    Durable

    Quiet operationSmall, lightweight, and easy-to-install outdoor unit.

    Compact

    51dB(A)FDY06KA

    Sound level

    Highly durable outdoor unit has PE fins for improved resistance to salt corrosion and atmospheric pollution.

    DurableMany options are available for use with large-scale and advanced-function centrally controlled systems

    Central controlQuiet operation

    S uc tion c hamber

    Air filter[Duc t c onnec tion]

    To prevent increased operation sound, avoid installing the air suction grille directly below the suction chamber.

    FDYB50KA FDY06KA

    38dB(A)FDYB50KA

    LOW

    Sound level

    Ideal for quiet, beautiful living spacesSuitable for condominiums and apartments, houses and hotels

    Recommended for spacious and large-volume areas because of its flexible installationSuitable for large stores, factories, and other large areas, and for use with housing ducts in homes

    Digital remote controller Remote controller

    High

    See pages 31–32 for details of the Multi Series.

    Guide Line upP. 3–10

    Outdoor unitsP. 33–34

    OptionsP. 59

    Outer dimension drawingsP. 64

    Remote controllersP. 35–36

    Standard specificationsP. 42, 52, 56

    GuideLine upP. 3–4, 7–8Outdoor unitsP. 33–34

    OptionsP. 59Outer dimension drawingsP. 65–67

    Remote controllersP. 35–36Standard specificationsP. 44, 45, 53

    Simultaneous air conditioning of two rooms and ventilation grille (ventilation opening)

    Ventilation grille

    Door-installedventilation grille

    Ventilation grille

    Wall-installedventilation grille

    Under-door c utout

    Under-door cutoutWhen air conditioning two rooms simultaneously, the air discharged into each room must be circulated back to the air conditioner. To achieve this, a ventilation duct should be installed for each room or one of the indicate ventilation grilles should be installed on the partitioning wall or under the door between the rooms.

    Ventilates air through the partitioning wall. (S ee right)

    Partitioning wall

    Note: The under-door cutout method should be used only when there is a small volume of airflow.

    Cooling only

    Heat pump

    KRC47-2AKRC47-4A

    KRC47-1A

    Remote controllerCooling only

    KRC47-3A

    Wired LCD remote controller Wireless LCD remote controller

    Wireless remote c ontroller and s ignal rec eiver unit are sold as a set.

    Note: R emote c ontroller c able not inc luded. C ables must be proc ured loc ally.

    Accessory required for indoor unit (option)

    BRC1C61

    BRC4C62

    Heat pumpWired LCD remote controller Wireless LCD remote controller

    Wireless remote c ontroller and s ignal rec eiver unit are sold as a set.

    Note: R emote c ontroller c able not inc luded. C ables must be proc ured loc ally.

    Accessory required for indoor unit (option)

    BRC1C61

    BRC4C62

    DUCT CONNECTIONLOW STATIC PRESSURE TYPE

    FDBG/FDYBFDBG25AVE–71AVECooling onlyFDYB35KAVE–71KAVEHeat pump

    DUCT CONNECTIONHIGH STATIC PRESSURE TYPE

    FD(Y)FD03KY1–20KY1Cooling onlyFDY06KAY1–20KAY1Heat pump

    *2 *3

    *3

    *2*4 *4*1

    Features (Features are explained on P. 37–38.)Feature

    Model

    Heat pumpCooling only

    *1Applic able to R Y140LU outdoor units (for temp. down to – 5°C ) and R Y200LU– R Y250LU outdoor units (for temp. down to – 0°C )*2Applic able to R (Y)140LU outdoor units*3R equired to c hange the pulley*4FDY06-10 only

    Comfort Work & Servicing Control features Others

    Ho

    t st

    art

    Tim

    er

    sele

    cto

    r

    Pre

    c

    ha

    rge

    d

    for

    up

    to

    3

    0

    m

    Lo

    w

    ga

    s p

    ress

    ure

    d

    ete

    ctio

    n

    Em

    erg

    en

    cy

    op

    era

    tion

    Se

    lf-d

    iag

    no

    sis

    fun

    ctio

    n

    Co

    ntr

    ol

    by

    2

    rem

    ote

    c

    on

    tro

    llers

    Au

    to-r

    est

    art

    Ad

    just

    ab

    le

    ext

    ern

    al

    sta

    tic

    pre

    ssu

    re

    Gro

    up

    cont

    rol

    by

    1 re

    mot

    e co

    ntro

    ller

    Ext

    ern

    al

    co

    mm

    an

    d

    co

    ntr

    ol

    Ce

    ntr

    al

    rem

    ote

    c

    on

    tro

    l

    Inte

    rlo

    ck

    co

    ntr

    ol

    PE

    fin

    Au

    tom

    atic

    c

    oo

    l/h

    ea

    tc

    ha

    ng

    e

    -ove

    r

    Ye

    ar-

    rou

    nd

    c

    oo

    ling

    a

    pp

    lica

    ble

    Comfort Work & Servicing Control features Others

    *2*2*1

    Features (Features are explained on P. 37–38.)Feature

    Model

    Heat pumpCooling only *1Applic able to R Y71LU outdoor units (for temp. down to – 5°C )

    and R Y200LU– R Y250LU outdoor units (for temp. down to – 0°C )*2Applic able to R Y71LU outdoor units

    Sw

    itch

    ab

    le

    fan

    sp

    ee

    d

    Pro

    gra

    mm

    e

    "Dry

    "

    Ho

    t st

    art

    Tim

    er

    sele

    cto

    r

    Pre

    c

    ha

    rge

    d

    for

    up

    to

    3

    0

    m

    Lo

    w

    ga

    s p

    ress

    ure

    d

    ete

    ctio

    n

    Em

    erg

    en

    cy

    op

    era

    tion

    Se

    lf-d

    iag

    no

    sis

    fun

    ctio

    n

    Co

    ntr

    ol

    by

    2

    rem

    ote

    c

    on

    tro

    llers

    Au

    to-r

    est

    art

    Ad

    just

    ab

    le

    ext

    ern

    al

    sta

    tic

    pre

    ssu

    re

    Gro

    up

    cont

    rol

    by

    1 re

    mot

    e co

    ntro

    ller

    Ext

    ern

    al

    co

    mm

    an

    d

    co

    ntr

    ol

    Ce

    ntr

    al

    rem

    ote

    c

    on

    tro

    l

    Inte

    rlo

    ck

    co

    ntr

    ol

    PE

    fin

    Trip

    le

    and

    d

    oub

    le

    twin

    m

    ulti

    oper

    atio

    n

    Au

    tom

    atic

    c

    oo

    l/h

    ea

    tc

    ha

    ng

    e

    -ove

    r

    Ye

    ar-

    rou

    nd

    c

    oo

    ling

    a

    pp

    lica

    ble

    (220V)

    Signal receiver unit(Separate type)

    Signal receiver unit(Separate type)

    Note : Anec hoic c hamber c onvers ion value, measured ac c ording to J IS parameters and c riteria.

    FDBG60AVE 42 39Indoor unit High Low

    dB(A)

  • MULTI SERIES

    MULTI SERIESTwin, Triple, and Double Twin Multi-Operation

    Simultaneous operation system

    Note: This type of system does not allow individual control or independent operation of indoor units. It is not the best choice for large rooms with partitions.

    In a single-floor restaurant, for example, positioning 4 units at strategic locations realises comfortable airflow that reaches every inch of the room.

    Double Twin Multi operation

    4 indoor units can be run simultaneously with a single outdoor unit.

    Improved comfort level and space-saving for outdoor unit installation

    Required about 40% less installation space for outdoor unit

    4 indoor units distribute comfortable airflow throughout the room. Simultaneous operation of four indoor units can be controlled from a single remote controller. Requires a single refrigerant piping system.

    Triple Multi operation Twin Multi operation

    Indoor units include ceiling mounted cassette type, ceiling suspended type, and duct connection middle and low static pressure type.

    Before5 HP x 2 units

    R(Y)125KU x 2 units

    10 HP double twin multi operation

    R(Y)200KU or R(Y)250KU x 1 unit

    New

    Before New

    Installing multiple units is economical and realises comfortLower cost of installation than for individual pair typeReduced installation space for outdoor unitsEnhanced comfort from distributed indoor units

    Branch piping kitBranch piping kit

    Branch piping kitBranch piping kit

    Branch piping kit

    In large interior spaces a single indoor unit may not be able to provide uniform comfort. Installation of 2 to 4 units, can provide an effective solution.

    Dea

    d zo

    ne

    Dea

    d zo

    ne

    31

    500 mm

    300 mm

    300 mm

    1000 mm

    Simultaneous operation system

    Remote controllers for the Multi Series

    Simultaneously operates 2 to 4 indoor units using a single outdoor unit.

    32

    (Branch piping kits are sold separately. Please use the model indicated on page 59) Refrigerant piping uses terminal branching to facilitate installation.

    Main pipeRemote controller

    Outdoor unit

    Branch piping kit

    Sub unit Main

    unit

    L

    L2L1

    Piping Guideline

    Main pipeRemote controller

    Outdoor unit

    Branch piping kit

    Sub unit Main

    unit

    L

    L3L2

    Sub unit

    L1

    Sub unit Sub

    unit

    Main pipeRemote controller

    Outdoor unit

    Branch piping kit

    Sub unit Main

    unit

    L

    L6L5L4

    L3

    L1

    L2

    Max. branch piping length

    *1 Max. (L1, L2) means maximum length out of L1 and L2. *2 Min. (L1, L2) means minimum length out of L1 and L2.

    Max. (L1, L2)*1 20 m

    Simultaneous operation system

    Max. level difference between outdoor unit and indoor units

    Max. (L1, L2 , L3) 20 m Max. (L1, L2) Max. (L3, L4, L5, L6) 20 m

    30 m 30 m 30 m

    Max. level difference between indoor units 0.5 m 0.5 m 0.5 m

    Max. piping length L Max. (L1, L2) 50 m L Max. (L1, L2, L3) 50 m L Max. (L1, L2) Max. (L3, L4, L5, L6) 50 m

    Max. branch pipe length difference Max. (L1, L2) Min. (L1, L2)*2 10 m L2 L1 10 m L4 L3 10 m L6 L5 10 m

    (L2 L6) (L1 L3) 10 mMax. (L1, L2, L3) Min. (L1, L2, L3) 10 m

    Double Twin Multi OperationTwin Multi Operation

    Twin Multi Operation Triple Multi Operation Double Twin Multi Operation

    Triple Multi Operation

    In case of L1 L2, L3 L4, L5 L6

    Guide Line upP. 5–6, 9–10

    Outdoor unitsP. 33–34

    OptionsP. 57–59

    Outer dimension drawingsP. 60–74

    Remote controllersP. 35–36

    Standard specificationsP. 46–48, 54–56

    (For Triple Multi)(For Twin Multi) (For Double Twin Multi)

    (Option)

    Connect the wired remote controller to turn an indoor unit into the master unit.

    Install the signal receiver unit (part of the optional wireless remote controller) to turn an indoor unit into the master unit.

    Wired remote controller has a temperature-sensor. Depending on the installation conditions, select and set the temperature-sensor of a selected indoor unit or the temperature-sensor of the remote controller.

    Because the wireless remote controller does not have a temperature-sensor, select the temperature-sensor of the indoor master unit.

    Wired LCD remote controller

    BRC1C61

    Wireless LCD remote controller

    CEILING MOUNTED CASSETTE TYPE

    A single remote controller controls simultaneous operation of multiple indoor units.

    Supports Two selectable temperature-sensor functions.

    Note: An indoor unit's temperature-sensor must be used when the air conditioners are controlled from another room.

    INDOOR UNIT(Option)

    CEILING SUSPENDED TYPE

    DUCT CONNECTIONLOW STATIC PRESSURE TYPE

    Note: Selectable temperature sensing is available with ceiling-mounted cassette and ceiling-suspended models, but not with middle static-pressure models.

    DUCT CONNECTIONMIDDLE STATIC PRESSURE TYPE

    BRC7C612WCooling only BRC7C613W

    Heat pump

    BRC7E63WCooling only BRC7EA66

    Heat pump

    Heat pump BRC4C62

    BRC4C62Cooling only BRC4C64

    Heat pump

  • Fully shaped aerodynamic propellers are designed to push air with a large wing surface, providing both high blow volume and quiet operation with turbulence.

    Fitted with wide inlet fan (Applies to R(Y)71LU–140LU)

    Compactly designed outdoor unit with interior layout optimised for the smooth airflow.

    The design curved Super Aero Grille restricts the spread of exhaust gas and fits in the same space as conventional outdoor units.

    Slim and low-profile design outdoor units (Applies to R(Y)71LU–140LU)

    The light weight makes delivery and installation easier.

    Reduced weight (Applies to R(Y)71LU-125LU)

    To suppress turbulence and achieve quiet operation, the curved ribs of the grille are optimised to meet the outflow of air.

    Fitted with Super Aero Grille(Applies to R(Y)71LU–140LU)

    Smooth running, minimal vibration, low operating sound.

    Equipped with scroll compressor for quiet operation (Applies to R(Y)125LU and 140LU)

    Operation soundWide inlet fan (Applies to R(Y)71LU–140LU)

    C o m pa c t

    Compact unit provides quiet operation.

    Defrost control delivers powerful heating in extremely cold climates(Applies to RY71LU–140LU) (Heat pump only)

    If refrigerant piping length does not exceed 30 m, there is no need for on-site gas charging.(Applies to R(Y)71LU–140LU)

    I n s t a l la t io n a n d m a in t e n a n c e

    Pre charged for up to 30 metres

    Heat pumpOutdoor unit Sound level (cool/heating)

    dB(A)

    RY71LU 48/49RY100LU 49/52RY125LU 49/52RY140LU 54/56

    Max

    . poi

    nt o

    f in

    tegr

    al c

    apac

    ity

    Difference between indoor heat exchange temperature and intake air temperature ( T)

    Integral heating capacity

    Def

    rost

    and

    hot

    sta

    rt

    Defrost begins in this area

    00

    5

    10

    15

    20

    25°C

    10 20 30 40 50 60 70 80Elapses operation time (min.)

    Defrost operation complete(heating operation restart)

    Defrost monitoring start (monitors to maximum point)

    Integral heating capacity and temperature difference (actual measurement when outdoor temperature is -1.5°C)

    Cooling onlyOutdoor unit Sound level

    R71LU 48R100LU 49R125LU 49R140LU 54

    OUTDOOR UNIT

    Allowed refrigerant pipe length and level difference

    Max. length Max. leveldifference

    Pre charged*1

    25 m10 mR25J20 m10 mRY35F25 m10 mR35J

    30 mRY71LUR71LU

    30 mRY100LUR100LU50 m

    (Equivalent length 70 m)

    50 m(Equivalent length 70 m)

    10 mRY50GAR50G 30 m

    5 mRY60GAR60G 30 m

    50 m(Equivalent length 70 m)

    50 m(Equivalent length 70 m)

    30 mRY125LUR125LU

    30 mRY140LUR140LURG71ARA140ARG180A

    Note: 1Additional refrigerant charging is required if the refrigerant pipe is longer than the length.

    P o w e r fu lUses "Receiver" to enhance refrigerant control (Applies to R(Y)71LU–140LU)

    Instead of the using an accumulator to ab-sorb excess refrigerant, Daikin outdoor units have a receiver in the piping located away from the compressor. By preventing the return of liquid to the compressor, the receiver enhances reliability.

    Cooling is efficient even in winter when indoor temperatures are higher than those outside, such as in underground public spaces or offices with many computers.

    Suited for year-round cooling applications

    RY200KU and250KU can adapt up to 0°C.

    Also adapts to year-round cooling

    A pump-down switch is provided to make it easier to collect refrigerant if the unit is to be moved or layout modified.

    4-direction piping offers greater layout freedom(Applies to R(Y)71LU–140LU)

    Facilitates pump down (Refrigerant recovery function)

    Effective gas monitoring reduces the labor required for operation, maintenance, and repairs.

    Piping can be run from the front, bottom, right or rear surface according to how the unit is installed.

    Low gas level detection function(Applies to R(Y)71LU–140LU)

    • Heat pump/RY71–140LU: possible up to -5°C• Cooling only/R71–140LU: possible up to -15°C• The year-round cooling kit is required as option.

    OUTDOOR UNIT

    (Applies to all outdoor units)

    To achieve increased durability by improved resistance to salt corrosion and atmospheric pollution, coated PE fins (with special acryl pretreatment) are used for the heat exchanger of the outdoor unit.

    D u r a bi l i t yHeat exchange fins provided with anti-corrosion treatment

    ConstructionNon-treated fin

    PE fin

    Aluminium

    AluminiumC orros ion res is tantac rylic res in

    Hydrophilic film

    Common width and depth make series installation easy.

    200 and 250 class models canbe combined for centralised, horizontal-series installation

    R(Y)250KU

    1280 mm

    R(Y)200KU

    1280 mm

    R(Y)200KU

    1280 mm

    690 mm

    Max. length Max. leveldifference

    Pre charged*1

    50 m(Equivalent length 70 m) 30 m

    50 m(Equivalent length 70 m) 30 m

    5 mR(Y)200KU

    5 mR(Y)250KU

    Piping can be drawn out from three directions - front, left side, or below.

    33 34

    Flexible design for large roomor multi-use

    Q u ie t O pe r a t io n

    (Heat pump only)

    R(Y)71LU R(Y)100LU R(Y)125LU R(Y)140LU

    500

    50

    (mm)

    conventional

    108 kgRY100KUV1

    New

    89 kgRY100LUV1

    Note: 1Additional refrigerant charging is required if the refrigerant pipe is longer than the length.

    Allowed refrigerant pipe length and level difference

    To optimise heating performance, by monitoring the difference in air temperature in the indoor/outdoor heat exchanger and the intake air temperature, the system accurately adjusts to provide the best operating parameters. This enables defrost mode to be initiated and so minimise indoor declines in temperature caused by frost. For example, if the outdoor airtemperature falls to -1.5°C, the integrated heating capacity is raised about 20%.

    RU08/10KU models are factory shipped with refrigerant charged for 5 m of piping.RU08/10K models are factory shipped with no refrigerant charged.

    RU08/10K models are available in two type depending on installation conditions

    15 m15 m15 m

    30 m

    30 m

    15 m

    15 m

    30 m

    30 m

    50 m(Equivalent length 70 m)5 m

    R100FUR125FU 30 m

    50 m(Equivalent length 70 m)5 m 30 m

    Note : Anec hoic c hamber c onvers ion value, measured ac c ording to J IS parameters and

  • LCD REMOTE CONTROLLER

    Remote controller options are shown on the page introducing each indoor unit model.

    Wireless LCD remote controllerThe wireless remote controller is supplied in a set with a signal receiver.Shape of signal receiver unit differs according to the indoor unit.

    Note: The s ignal rec eiver unit shown in the photograph is for mounting ins ide the dec oration panel of the c eiling mounted c assette type.

    N o n -po la r , do u ble -c o r e c o n n e c t io n s pe c i f ic a t io n s s im pl i fy w ir in g

    S k y A ir s h a r e s c o m m o n c o n t r o l w it h H R V (h e a t r e c la im v e n t i la t io n ) a n d t h e o t h e r D a ik in a i r -c o n dit io n in g u n it s , t h u s s im pl i fy in g in t e r lo c k in g o pe r a t io n s .

    Easily adaptable to large-scale, high-function, centralised remote control systems.Installing and connecting control wiring between SkyAir and other Daikin air-conditioning equipment is easy.

    Optional adaptor for external commands or remote control of external equipment has been standardised to one type.

    F a c i l i t a t e s m a in t e n a n c e a n d r e pa ir

    Non-polar, double-core remote controller wire prevents wiring mistakes. signal receiver unit (or decoration panel) of wireless type is also easy to connect.

    All initial settings can be set from the remote controller. After interior construction is complete, ceiling mounted units can be remotely set without having to use stepladder access for manual setting.Setting contents: High ceiling use, air direction, filter type, address for centralised control (group control address is set automatically).Remote controller is equipped with model name and failure display functions. This facilitates service in the unlikely event of a malfunction.

    Signal receiver unit (For ceiling mounted cassette type)

    Wireless remote controller

    Note: When a wireless remote c ontroller is used, remote c ontrol by two remote c ontrollers is not poss ible.

    L C D pa n e l s h o w s o pe r a t in g s t a t u s in le t t e r s , n u m be r s , a n d m o t io n .Airflow / swing display Displays auto-swing operating status and setting position of air discharge angle.

    (Not available for ceiling mounted built-in type and duct connection type )Preset temperature / operation mode display Displays preset room temperature and operating status (fan, dry, cool).

    Programming time display Operation start and stop time can be set for individual timers up to 72 hours. The liquid crystal display also shows when it is time to clean the filter, when changeover is under centralised control, and ventilation/cleaning.

    Self-diagnosis function Monitors operating status within the system covering 40 items, and displays a message to indicate as soon as a malfunction occurs.

    LCD REMOTECONTROLLERS

    signal receiver mounted type

    For easier operation, louver switches, which are frequently used, have been made larger.Oil-resistant plastic casing. Only 17 mm thick. Can be installed either recessed or exposed.

    W ir e d r e m o t e c o n t r o l le r h a s bu i l t -in t e m pe r a t u r e -s e n s o r (Applies to wired remote controllers)

    Enables temperature sensing closer to target area for improved comfort. (When using remote control from another room, temperature-sensor in indoor unit's air inlet must be selected.)Note: The indoor unit’s temperature-sensor is specified at the time of

    shipment. Temperature sensing with the wired remote controller is not available with the ceiling mounted cassette corner, ceiling-mounted built-in, and duct connection type.

    Easier to read because LCD screen is larger.

    35 36

    Wired LCD remote controller

    *1. When the auto-swing function is not available, the message, THIS FUNCTION IS NOT AVAILABLE is displayed when the wind direction adjustment button is pressed.*2. Applicable to only heat pump type.

    C e n t r a l r e m o t e c o n t r o l le r

    Easily adaptable to large-scale, high-function, centralised remote control system.

    Centralised control, with setting as simple as it is with a standardremote controller, of up to 64 groups (1,024 indoor units) is possible.

    DCS302CA61 (Option)

    With its high functionality, the full color “all-in-one” graphic controller facilitates management of Skyair System in a variety of ways.

    DCS601C51 (Option)U n if ie d o n /o ff c o n t r o l le r

    Centralised control of on/off by group or all at once for up to 256 indoor units.

    DCS301BA61 (Option)S c h e du le t im e r

    Unified control of weekly schedule for up to 1,024 indoor units.

    DST301BA61 (Option)

    Indoor units applicable for the remote controller

    S im ple s y s t e m pr o v ide s a d iv e r s e a s s o r t m e n t o f c o n t r o l m o de s .

    Interface adaptorfor SkyAir series

    Enables centralised control via connection to a high-speed, DIII-NET communication system, adopted for the Daikin VRV system.Necessary for interface adaptor for SkyAir series with the central remote control units shown at above.

    DTA102A52 (Option)

    Central control adaptor kit *2

    DTA107A55 (Option)

    Schedule timer sets on/off time in 1 minute units to be executed twice a day for a week at a time.

    BRC1C61

    CEILING MOUNTED CASSETTE TYPECEILING SUSPENDED TYPECEILING SUSPENDED CASSETTE TYPECEILING MOUNTED CASSETTE CORNER TYPEWALL MOUNTED TYPE CEILING MOUNTED BUILT-IN TYPE*1DUCT CONNECTION LOW STATIC PRESSURE TYPE *2DUCT CONNECTION MIDDLE STATIC PRESSURE TYPEDUCT CONNECTION HIGH STATIC PRESSURE TYPE *2

    *1. When the auto-swing function is not available, the message, THIS FUNCTION IS NOT AVAILABLE is displayed when the wind direction adjustment button is pressed.*2. Applicable to only heat pump type.•Standard remote controller (BRC1C61) is not required.•If the BRC1D61 is connected to the centralised remote controller, the schedule function is not available.

    Indoor units applicable for the remote controller

    BRC1D61

    CEILING MOUNTED CASSETTE TYPECEILING SUSPENDED TYPECEILING SUSPENDED CASSETTE TYPECEILING MOUNTED CASSETTE CORNER TYPEWALL MOUNTED TYPE CEILING MOUNTED BUILT-IN TYPE*1DUCT CONNECTION LOW STATIC PRESSURE TYPE *2DUCT CONNECTION MIDDLE STATIC PRESSURE TYPEDUCT CONNECTION HIGH STATIC PRESSURE TYPE *2

    BRC1C61

    24-hour clock function (1-hour backup for power failures)Programming function for each day of week.Scheduling possible of start/stop and temperature limit (5 settings/day)Programming can be enabled or disabled. Copy function for programmed schedules.

    Remote control is equipped with weekly timer function.Wired LCD remote controller with weekly schedule timer

    BRC1D61

    Indoor units applicable for the remote controller

    Signal receiver unit is contained inside decoration panel or indoor unit

    CEILING MOUNTED CASSETTE TYPE

    DUCT CONNECTION LOW STATIC PRESSURE TYPEDUCT CONNECTION MIDDLE STATIC PRESSURE TYPEDUCT CONNECTION HIGH STATIC PRESSURE TYPE

    WALL MOUNTED TYPE

    CEILING SUSPENDED CASSETTE TYPE

    BRC7C612W BRC7C613W

    BRC7E63W BRC7EA66

    BRC7C528W BRC7C529W

    BRC7EA618 BRC7E619BRC7C610W

    FAY71LFAY100FA BRC7C611W

    BRC4C62

    BRC4C62 BRC4C64

    BRC4C62

    CEILING SUSPENDED TYPE

    Heat pump Cooling only

    Necessary optional accessory

    Control by 1remote controller

    Control pattern Wired remote controller Wireless remote controller

    Control by 2remote controllers

    Group control

    Control by external command

    Centralised remotecontrol

    Interlock controlwith HRV

    (Basic system)

    Link by remote controller group control.

    Zone link control by centralised control.

    For control from 2 locations such as in room and control room, exits, etc.

    For simultaneous control of up to 16 indoor units.

    Centralised control of up to 64 indoor groups from remote locationup to 1 kilometer away.

    C ontrol by 1 wireless remote c ontroller and 1 wired remotec ontroller (S ee note 1)

    S ignal rec eiver unit installed on indoor unit

    Automatic address setting func tion

    S ignal rec eiver unit installed on 1 indoor unit

    S ignal rec eiver unit installed on indoor unit

    Optional wiring adaptor for elec tric al appendic es is nec essary

    Optional S kyAir series interfac e adaptor required. *1

    C an be operated s imultaneously by remote c ontroller (set by ventilation mode)

    HR V for indoor units within a zone are operated by interloc kingOptional interfac e adaptor for S kyAir seriesis nec essary *1

    (C ommand from outs ide)

    C entral remote c ontroller (option)

    C entral remote c ontroller (option)

    HR V

    Non-polar, double-c ore (max. wiring length 500 m)

    C onnec ts 2 wired remote c ontrollers

    Automatic address setting func tion

    Optional S kyAir series interfac e adaptor required. *1

    C an be operated s imultaneously or independently by remote c ontroller (set by ventilation mode)

    HR V for indoor units within a zone are operated by interloc kingC an also be operated independently by remote c ontroller.Optional interfac e adaptor for S kyAir seriesis nec essary *1

    (C ommand from outs ide)

    C entral remote c ontroller (option)

    C entral remote c ontroller (option)

    HR V

    HR V HR V

    Note : DIII-net adaptor function is standard equipment for the FAY71L.

    Operation and surveillance is carried out using the contact signal from the operation control box in the building surveillance (security) room.

    *Please refer to the page 59 for the details.

    (for FD series)

    *2.The central control adaptor kit for FDB series can be made to order.

    *1. DIII-net adaptor function is standard equipment for the FAY71L.

    Optional wiring adaptor for elec tric al appendic es is nec essary

    Easy-to-read LCD remote controller allows various system control configurations and can control multiple indoor units.

  • C o m f o r t

    A u t o -s w in g

    Air discharge direction angle can be set (fixed setting)

    D r a ft pr e v e n t io n fu n c t io n (heating)

    You can increase fan speed approximately 10% higher than the "high" setting.

    M o u l d p r e v e n t i o n

    H ig h fa n s pe e d m o de

    Dehumidification is microprocessor controlled to prevent uncomfortable changes in air temperature. Useful for reducing uncomfortable humidity without uncomfortable cooling.

    P r o g r a m m e " D r y "

    Delivers air-conditioning comfort all the way down to the floor in air-conditioning zones with high ceilings.

    H ig h -c e i l in g a ppl ic a t io n

    Uncomfortable cold air draft is not discharged when heating operation starts or when switching to heat after defrosting.

    H o t s t a r t (after defrost)

    Efficient cooling even in winter when indoor temperatures are higher than those outside, such as in underground pub-lic spaces or offices with many computers.

    Y e a r -r o u n d c o o l in g a ppl ic a ble

    Operation starts when the preset time of the ON timer elapses and stops when the preset time of the OFF timer elapses.

    T im e r s e le c t o r

    Sanitary filter has mould-resistant treatment.M o u ld-r e s is t a n t t r e a t m e n t fo r f i l t e r

    Mould-proofing maintains hygiene by preventing growth in highly humid conditions.

    M o u ld-pr o o f in g dr a in pa nO p t i o n s

    Two types are available: 65% and 90% colorimetry.H ig h -e ff ic ie n c y f i l t e r u n it

    Requires no maintenance for about 4 years* (10,000 h) in stores and offices. * For dust concentration of 0.15 mg/m3

    U lt r a lo n g -l i fe f i l t e r

    You can provide air-conditioning with fresh air from outside. Convenient for places where a ventilation fan cannot be installed.

    F r e s h -a ir in t a k e k i t

    W o r k a n d S e r v i c i n g

    Steeper gradient realises more efficient condensate drainage. High-lift is especially useful for long lengths of drain piping.

    D r a in pu m p m e c h a n is m

    Maintenance is not required for one year (two years when a ceiling mounted cassette type is used).

    L o n g -l i fe f i l t e r

    Daikin's innovative air discharge mechanism keeps airflow away from the ceiling. Ceiling cleaning is less frequently required.

    C e i l in g s o i l in g pr e v e n t io n fu n c t io n

    If refrigerant piping length does not exceed 30 m, there is no need for on-site gas charging.

    P r e c h a r g e d fo r u p t o 3 0 m e t r e s

    If there is a malfunction elsewhere in the system, the fan or compressor can still be operated.

    E m e r g e n c y o pe r a t io n

    The operating parameters of indoor and outdoor units, and sensor data at critical locations throughout the system, are constantly monitored using a microcomputer. To facilitate quick response in the event of a malfunction, a message appears on the LCD of the remote controller and an LED on the unit illuminates.

    S e l f d ia g n o s is fu n c t io n

    C o n t r o l f e a t u r e s

    If there is a power outage while the equipment is op-erating, operations will restart in the same mode as before the power cut when electricity is restored.

    A u t o -r e s t a r t

    A u t o c o o l/h e a t c h a n g e -o v e r

    Using 2 remote controllers you can operate the equipment locally or from a remote location.

    C o n t r o l by 2 r e m o t e c o n t r o l le r s

    Note: When a wireless remote controller is used, remote control by two remote controllers is not possible.

    You can turn up to 16 indoor units on/off with a single remote controller. (When using connected indoor units, the settings must all be the same and on/off will be simultaneous.)

    C o n t r o l by 1 r e m o t e c o n t r o l le r

    E x t e r n a l c o m m a n d c o n t r o l

    Optional central remote controller enables centralised control of up to 1024 indoor units (64 groups) from up to 1 kilometer away.

    C e n t r a l r e m o t e c o n t r o l

    Enables interlocking control with external equipment such as heat reclaim ventilation (HRV).

    I n t e r lo c k c o n t r o l

    Delivers comfortable air-conditioning to all areas, near to and far from the air-conditioner.

    To prevent cold air drafts, automatically adjusts airflow to horizontal vector when heating initially starts or when the thermostat turns off.

    Detects difference in preset temperature and actual room temperature and automatically switches to cooling or heating accordingly.

    Operation and surveillance is carried out using the contact signal from the operation control box in the building surveillance (security) room.

    (1) Air direction in standard position

    (2) Air direction in draft prevention position

    (3) Air direction in ceiling soiling prevention position

    You can freely set 3 air discharge positions by remote controller.

    S w in g pa t t e r n s e le c t io n (draft prevention, standard, ceiling soiling prevention)

    High setting provides maximum reach while low setting minimises drafts.

    S w it c h a ble fa n s pe e d

    O t h e r s

    To achieve increased durability by improved resistance to salt corro-sion and atmospheric pollution, coated PE fins (with special acryl pre-treatment) are used for the heat exchanger of the outdoor unit.In high corrosive areas, regular maintenance needs to be carried out.

    P E f in

    Simultaneously operates 2–4 indoor units with a single outdoor unit.

    T w in / t r iple / do u ble t w in m u lt i o pe r a t io n

    37 38

    Use the temperature-sensor in the indoor unit when controlling air conditioning from another room.

    T w o s e le c t a ble t e m pe r a t u r e -s e n s o r s

    Temperature-sensors are included in the indoor unit and op-tional wired remote controller. Temperature sensing closer to target area is possible to further

    Note: Wireless remote controllers have no temperature-sensor.

    (Heat pump only)

    • Heat pump/RY71—140LU: possible up to -5°C• Cooling only/R71—140LU: possible up to -15°C• The year-round cooling kit is required as option.

    Applicable for ceiling mounted cassette type and ceiling mounted cassette corner type.

    Abundance of functions that provide comfortable air-conditioning in stores and offices. Note: Some features only available on selected models. See model pages for full list of features applicable to each unit.

    Applicable for wall mounted type

    Note:When units are installed on high ceilings, depending on the model, various restrictions concerning maximum height, air discharge direction, and choice of options may apply.

    The filter sign warns you when it is time to clean the filter. *When using a wired remote controller the sign is displayed in the LCD. When using a wireless remote controller the filter sign lamp illuminates on the signal receiver unit.

    F i l t e r s ig n

    L o w g a s pr e s s u r e de t e c t io n

    Insufficient gas charging is normally hard to detect. During post-installation trials and regular inspection procedures, the refrigerant level is monitored by microprocessor to maintain proper gas pressure.Reliability is assured and maintenance and inspection can be carried out more quickly.

    (Horizontal air disc harge)

    (Applies to R(Y)71LU–140LU)

    *Connecting ducts, insect nets, fire dampers, air filters, and other parts should, as required, be procured locally.

    **Outside Air fan interlocked with air conditioning unit is necessary. Optional PCB(KRP1C63)is required for interlocking.

    ***It is recommended that the volume of outdoor air introduced through the kit is limited to 10% of the maximum airflow rate of the indoor unit. Introducing higher quantities will increase the operating noise and may also influence temperature sending.

    Note:

  • 15 30

    39 40

    CEILING MOUNTED CASSETTE CORNER TYPE

    White

    35

    12,100/11,6003.54/3.4

    FHK35FV1

    R35GV1

    3,040/2,930

    1.41/1.40

    12423

    39/33215X1,110X710

    30

    Ivory white Hermetically sealed rotary type

    1.11.10 (Charged for 10 m)

    48540X750X270

    37

    45

    17,700/17,5005.19/5.1

    FHK45FV1

    R50GV1

    4,460/4,400

    2.25/2.24

    12423

    39/34215X1,110X710

    31

    1.71.20 (Charged for 10 m)

    49540X750X270

    42

    60

    22,760/22,2006.6/6.5

    FHK60FV1

    R60GV1

    5,690/5,600

    2.76/2.74 3.07/3.07 (V1)3.05/3.05 (Y1)

    17600

    41/36215X1,310X710

    3370X1,240X800

    8.5

    70X1,240X800

    8.5

    70X1,440X800

    9.5

    2.21.50 (Charged for 5 m)

    54685X800X300

    61

    71

    26,600/26,2007.8/7.7

    FHYK71FJV1R71LUV1R71LUY1

    6,700/6,600

    17600

    41/36215X1,310X710

    3370X1,440X800

    9.5

    2.24Hermetically sealed scroll type

    2.8 (Charged for 30 m)48

    770X900X32072 (V1), 71 (Y1)

    CEILING MOUNTED CASSETTE TYPE

    White

    35

    12,100/11,6003.54/3.4

    FH35BVE

    R35GV1

    3,040/2,930

    13458

    37/32195X960X680

    23

    Ivory white Hermetically sealed rotary type Hermetically sealed scroll type

    1.11.10

    48540X750X270

    37

    50

    17,700/17,5005.19/5.1

    FH50BVE

    R50GV1

    4,460/4,400

    13458

    38/33195X960X680

    24

    1.71.20

    49540X750X270

    42

    60

    22,760/22,2006.6/6.5

    FH60BVE

    R60GV1 R125LUY1

    5,690/5,600

    1.51/1.50 2.16/2.15 2.80/2.78 4.92/4.92

    16564

    38/33195X1,160X680

    26

    2.21.50

    54685X800X300

    61

    71

    26,600/26,2007.8/7.7

    FHY71BVER71LUV1R71LUY1

    6,700/6,600

    17600

    39/35195X1,160X680

    27

    2.242.8

    48770X900X320

    72 (V1), 71 (Y1)

    100

    36,100/35,70010.6/10.5

    FHY100BVER100LUV1R100LUY1

    9,100/9,000

    24847

    42/37195X1,400X680

    32

    3.003.7

    491,170X900X32087 (V1), 84 (Y1)

    125

    44,500/43,60013.0/12.8

    FHY125BVE

    11,200/11,000

    301,05944/39

    195X1,590X68035

    3.753.7

    491,170X900X320

    98

    White

    35

    12,100/11,9003.54/3.5

    FHC35KVE

    R35GV1

    3,040/3,010

    1.20/1.20

    14494

    230X840X840

    24

    Ivory white Hermetically sealed scroll typeHermetically sealed rotary type

    1.11.10

    48540X750X270

    37

    50

    18,200/18,1005.34/5.3

    FHC50KVE

    R50GV1

    4,590/4,560

    2.02/2.01

    15529

    230X840X840

    24

    1.71.20

    49540X750X270

    42

    60

    22,000/21,8006.44/6.4

    FHC60KVE

    R60GV1 R125LUY1

    5,540/5,500

    2.45/2.44 4.96/4.96 5.02/5.02

    19670

    230X840X840

    24

    2.21.50

    54685X800X300

    61

    71

    26,600/26,2007.8/7.7

    FHYC71KVER71LUV1R71LUY1

    6,700/6,6003.07/3.07 (V1)3.05/3.05 (Y1)

    4.01/4.01 (V1)3.96/3.96 (Y1)

    19670

    230X840X840

    24

    2.242.8

    48770X900X320

    72 (V1), 71 (Y1)

    100

    36,100/35,70010.6/10.5

    FHYC100KVER100LUV1R100LUY1

    9,100/9,000

    28988

    288X840X840

    28

    3.003.7

    491,170X900X32087 (V1), 84 (Y1)

    125

    44,500/43,60013.0/12.8

    FHYC125KVE

    R140LUY1

    140FHYC140KVE

    11,200/11,000

    331,16442/3633/29 33/29 35/30 35/30 39/34

    288X840X84040X950X950 40X950X950 40X950X950 40X950X950 40X950X950 40X950X950

    285 5 5 5 5 5

    3.753.7

    49 541,170X900X320

    98

    Both liquid and gas piping

    CEILING SUSPENDED TYPE

    Both liquid and gas pipingBoth liquid and gas piping

    49,400/48,40014.5/14.2

    12,500/12,200

    351,23544/37

    288X840X84040X950X950

    285

    4.504.1

    1,345X900X320109

    ----------

    19.4 to 54 19.4 to 4619.4 to 46

    19.4 to 5419.4 to 46 19.4 to 46

    21 to 46, -15 to 46 3 (Option installed)

    14 to 23 14 to 25

    21 to 46, -15 to 46 3 (Option installed)

    14 to 25

    21 to 46-15 to 46 3 (Option installed)

    14 to 25

    ----------

    3015

    14 to 23

    3015

    14 to 23

    50 (equivalent length 70 m)25 30

    Cooling capacity 1a/1b kWBtu/hkcal/h

    kWPower consumption 1a/1b

    °CDB

    °CWBCertified operation range

    ModelName

    Indoorunit

    Indoor unit

    Outdoor unit

    Dimensions(HXWXD)

    Colour

    mmmm

    Sound level (H/L) 2 dB(A)

    Refrigerant charge (R-22) kg

    Sound level 2 dB(A)Dimensions (HXWXD) mmMachine weight kg

    Unit

    Piping connections

    mmLiquid (Flare)

    Heat insulation

    mmGas (Flare)mmDrain Indoor unit

    Outdoor unit

    Decoration panel

    UnitDecoration panel

    Machine weight kgkgUnit

    Decoration panel

    Airflow rate (H) m3/mincfm

    Outdoorunit

    Colour

    mm

    Certified operation range

    Max. interunit piping length mmMax. installation level difference

    50 (equivalent length 70 m)3025

    Cooling capacity 1a/1b kWBtu/hkcal/h

    kWPower consumption 1a/1b

    ModelName

    Indoorunit

    Indoor unit

    Outdoor unit

    Sound level (H/L) 2 dB(A)

    Refrigerant charge (R-22) kg

    Sound level 2 dB(A)Dimensions (HXWXD) mmMachine weight kg

    Machine weight kg

    Certified operation range °CDB

    Certified operation range °CWB

    Piping connections

    mmLiquid (Flare)

    Heat insulation

    mmGas (Flare)mmDrain Indoor unit

    Outdoor unit

    Airflow rate (H) m3/mincfm

    Outdoorunit

    Colour

    mm

    Dimensions (HXWXD)

    Colour

    mm

    Max. interunit piping length mmMax. installation level difference

    50 (equivalent length 70 m)25 30

    Cooling capacity 1a/1b kWBtu/hkcal/h

    kWPower consumption 1a/1b

    °CDB

    °CWBCertified operation range

    ModelName

    Indoorunit

    Indoor unit

    Outdoor unit

    Dimensions(HXWXD)

    Colour

    mmmm

    Sound level (H/L) 2 dB(A)

    Refrigerant charge (R-22)Sound level 2

    kgdB(A)

    Dimensions (HXWXD) mmMachine weight kg

    Unit

    Piping connections

    mmLiquid (Flare)

    Max. installation level differenceHeat insulation

    mmGas (Flare)mmDrain Indoor unit

    Outdoor unit

    Decoration panel

    UnitDecoration panel

    Machine weight kgkgUnit

    Decoration panel

    Airflow rate (H) m3/mincfm

    Outdoorunit

    Colour

    mm

    Certified operation range

    Max. interunit piping length mm

    CEILING SUSPENDED CASSETTE TYPE

    White

    Ivory white Hermetically sealed scroll type

    R125LUY1

    71

    26,600/26,2007.8/7.7

    FUY71FJV1R71LUV1R71LUY1

    6,700/6,600

    40/35

    19670

    165X895X89525

    2.242.8 (Charged for 30 m)

    48770X900X320

    72 (V1), 71 (Y1)

    100

    36,100/35,70010.6/10.5

    FUY100FJV1R100LUV1R100LUY1

    9,100/9,000

    43/381,023

    29

    230X895X89531

    3.003.7 (Charged for 30 m)

    491,170X900X32087 (V1), 84 (Y1)

    125

    44,500/43,60013.0/12.8

    FUY125FJV1

    11,200/11,000

    4.97/4.97

    44/391,129

    32

    230X895X89531

    3.753.7 (Charged for 30 m)

    491,170X900X320

    98

    30

    21 to 46, -15 to 46 3 (Option installed)

    14 to 25

    50 (equivalent length 70 m)

    3.08/3.08 (V1)3.06/3.06 (Y1)

    4.07/4.07 (V1)4.02/4.02 (Y1)

    Cooling capacity 1a/1b kWBtu/hkcal/h

    kWPower consumption 1a/1b

    ModelName

    Indoorunit

    Indoor unit

    Outdoor unit

    Sound level (H/L) 2 dB(A)

    Refrigerant charge (R-22) kgSound level 2 dB(A)Dimensions (HXWXD) mmMachine weight kg

    Machine weight kg

    Certified operation range °CDB

    Certified operation range °CWB

    Piping connections

    mmLiquid (Flare)

    Max. installation level differenceBoth liquid and gas pipingHeat insulation

    mmGas (Flare)mmDrain Indoor unit

    Outdoor unit

    Airflow rate (H) m3/mincfm

    Outdoorunit

    Colour

    mm

    Dimensions (HXWXD)

    Colour

    mm

    Max. interunit piping length mm

    Power supply V1: 1 Phase, 220–240 V, 50 Hz Y1: 3 Phase, 380–415 V, 50 Hz

    Power supply V1: 1 Phase, 220–240 V, 50 Hz Y1: 3 Phase, 380–415 V, 50 Hz

    Power supply VE: 1 Phase, 220–240/220 V, 50/60 Hz V1: 1 Phase, 220–240 V, 50 Hz Y1: 3 Phase, 380–415 V, 50 Hz

    Power supply VE: 1 Phase, 220–240/220 V, 50/60 Hz V1: 1 Phase, 220–240 V, 50 Hz Y1: 3 Phase, 380–415 V, 50 Hz

    19.4 to 5419.4 to 46 19.4 to 46

    3.10/3.10 (V1)3.08/3.08 (Y1)

    3.90/3.90 (V1)3.85/3.85 (Y1)

    (Charged for 10 m)

    (Charged for 10 m) (Charged for 10 m) (Charged for 5 m) (Charged for 30 m) (Charged for 30 m) (Charged for 30 m)

    (Charged for 10 m) (Charged for 5 m) (Charged for 30 m) (Charged for 30 m) (Charged for 30 m) (Charged for 30 m)

    kWMotor outputCompressor Type

    kWMotor outputCompressor Type

    kWMotor outputCompressor Type

    kWMotor outputCompressor Type

    Note : 1Rated cooling capacities are based on the following conditions: 1aIndoor temp., 27°CDB, 19.5°CWB; outdoor temp. 35°CDB. Equiv. refrigeration piping, 5 m (horizontal). 1bIndoor temp., 27°CDB, 19.0°CWB; outdoor temp. 35°CDB. Equiv. refrigeration piping, 5 m (horizontal). (R71LU-R140LU is 7.5 m.)2Anechoic chamber conversion value, measured according to JIS parameters and criteria. During operation these values are somewhat higher owing to ambient conditions.

    3This value is for when year-round cooling kit (option) is installed.

    Note : 1Rated cooling capacities are based on the following conditions: 1aIndoor temp., 27°CDB, 19.5°CWB; outdoor temp. 35°CDB. Equiv. refrigeration piping, 5 m (horizontal). 1bIndoor temp., 27°CDB, 19.0°CWB; outdoor temp. 35°CDB. Equiv. refrigeration piping, 5 m (horizontal). (R71LU-R125LU is 7.5 m.)2Anechoic chamber conversion value, measured according to JIS parameters and criteria. During operation these values are somewhat higher owing to ambient conditions.

    3This value is for when year-round cooling kit (option) is installed.

    o/ 6.4o/ 12.7

    o/ 6.4o/ 15.9

    I.Do/ 25XO.Do/ 32 I.Do/ 25XO.Do/ 32 I.Do/ 25XO.Do/ 32 I.Do/ 25XO.Do/ 32 I.Do/ 25XO.Do/ 32 I.Do/ 25XO.Do/ 32 I.Do/ 25XO.Do/ 32

    o/ 6.4o/ 15.9

    o/ 9.5o/ 15.9

    o/ 9.5o/ 19.1

    o/ 9.5o/ 19.1

    o/ 18.0 (Hole) o/ 18.0 (Hole) o/ 18.0 (Hole) o/ 26.0 (Hole) o/ 26.0 (Hole) o/ 26.0 (Hole)

    o/ 9.5o/ 19.1

    o/ 26.0 (Hole)

    o/ 6.4o/ 12.7

    o/ 6.4o/ 15.9

    I.Do/ 20XO.Do/ 26 I.Do/ 20XO.Do/ 26 I.Do/ 20XO.Do/ 26 I.Do/ 20XO.Do/ 26 I.Do/ 20XO.Do/ 26 I.Do/ 20XO.Do/ 26

    o/ 6.4o/ 15.9

    o/ 9.5o/ 15.9

    o/ 9.5o/ 19.1

    o/ 9.5o/ 19.1

    o/ 18.0 (Hole) o/ 18.0 (Hole) o/ 18.0 (Hole) o/ 26.0 (Hole) o/ 26.0 (Hole) o/ 26.0 (Hole)

    o/ 9.5o/ 15.9

    o/ 9.5o/ 19.1

    o/ 9.5o/ 19.1

    I.Do/ 20XO.Do/ 26 I.Do/ 20XO.Do/ 26 I.Do/ 20XO.Do/ 26o/ 26.0 (Hole) o/ 26.0 (Hole)o/ 26.0 (Hole)

    o/ 6.4o/ 12.7

    o/ 6.4o/ 15.9

    I.Do/ 25XO.Do/ 32 I.Do/ 25XO.Do/ 32 I.Do/ 25XO.Do/ 32 I.Do/ 25XO.Do/ 32

    o/ 6.4o/ 15.9

    o/ 9.5o/ 15.9

    o/ 18.0 (Hole) o/ 18.0 (Hole) o/ 18.0 (Hole) o/ 26.0 (Hole)

  • White

    2.98/ 2.98(V1)2.96/2.96(Y1)

    3.90/3.90 (V1)3.85/3.85 (Y1)

    Ivory white Hermetically sealed scroll type

    71

    26,600/26,2007.8/7.7

    FAY71LVER71LUV1R71LUY1

    6,700/6,600

    19670

    43/37290X1,050X230

    13

    2.242.8 (Charged for 30 m)

    48770X900X320

    72 (V1), 71 (Y1)

    100

    36,100/35,70010.6/10.5

    FAY100FAVER100LUV1R100LUY1

    9,100/9,000

    23811

    45/41360X1,570X200

    26

    3.003.7 (Charged for 30 m)

    491,170X900X32087 (V1), 84 (Y1)

    WALL MOUNTED TYPE

    30

    21 to 46, -15 to 46 3 (Option installed)

    14 to 25

    50 (equivalent length 70 m)

    Cooling capacity 1a/1b kWBtu/hkcal/h

    kWPower consumption 1a/1b

    ModelName

    Indoorunit

    Indoor unit

    Outdoor unit

    Sound level (H/L) 2 dB(A)

    Refrigerant charge (R-22) kgSound level 2 dB(A)Dimensions (HXWXD) mmMachine weight kg

    Machine weight kg

    Certified operation range °CDB

    Certified operation range °CWB

    Piping connections

    mmLiquid (Flare)

    Max. installation level differenceBoth liquid and gas pipingHeat insulation

    mmGas (Flare)mmDrain Indoor unit

    Outdoor unit

    Airflow rate (H) m3/mincfm

    Outdoorunit

    Colour

    mm

    Dimensions (HXWXD)

    Colour

    mm

    Max. interunit piping length mm

    FLOOR STANDING TYPE

    White

    Ivory white Hermetically sealed scroll type

    R125LUY1

    71

    26,600/26,2007.8/7.7

    FVY71LAVER71LUV1R71LUY1

    6,700/6,600

    41/35

    18635

    1,850X600X27039

    2.242.8 (Charged for 30 m)

    48770X900X320

    72 (V1), 71 (Y1)

    100

    36,100/35,70010.6/10.5

    FVY100LAVER100LUV1R100LUY1

    9,100/9,000

    46/4098828

    1,850X600X35046

    3.003.7 (Charged for 30 m)

    491,170X900X32087 (V1), 84 (Y1)

    125

    44,500/43,60013.0/12.8

    FVY125LAVE

    11,200/11,000

    5.06/5.06

    49/431,129

    32

    1,850X600X35047

    3.753.7 (Charged for 30 m)

    491,170X900X320

    98

    30

    21 to 46, -15 to 46 3 (Option installed)

    14 to 25

    50 (equivalent length 70 m)

    3.18/3.18 (V1)3.16/3.16 (Y1)

    4.03/4.03 (V1)3.98/3.98 (Y1)

    Cooling capacity 1a/1b kWBtu/hkcal/h

    kWPower consumption 1a/1b

    ModelName

    Indoorunit

    Indoor unit

    Outdoor unit

    Sound level (H/L) 2 dB(A)

    Refrigerant charge (R-22) kgSound level 2 dB(A)Dimensions (HXWXD) mmMachine weight kg

    Machine weight kg

    Certified operation range °CDB

    Certified operation range °CWB

    Piping connections

    mmLiquid (Flare)

    Max. installation level differenceBoth liquid and gas pipingHeat insulation

    mmGas (Flare)mmDrain Indoor unit

    Outdoor unit

    Airflow rate (H) m3/mincfm

    Outdoorunit

    Colour

    mm

    Dimensions (HXWXD)

    Colour

    mm

    Max. interunit piping length mm

    White

    35

    12,100/11,6003.54/3.4

    FHB35FV1

    R35GV1

    3,040/2,930

    11.5405

    38/32300X700X800

    30

    1.11.10

    48540X750X270

    37

    45

    17,700/17,5005.19/5.1

    FHB45FV1

    R50GV1

    4,460/4,400

    14494

    39/34300X700X800

    31

    1.71.20

    49540X750X270

    42

    60

    22,760/22,2006.6/6.5

    FHB60FV1

    R60GV1 R125LUY1

    5,690/5,600

    17600

    41/35300X1,000X800

    41

    2.21.50

    54685X800X300

    61

    71

    26,600/26,2007.8/7.7

    FHYB71FV1R71LUV1R71LUY1

    6,700/6,600

    19670

    41/35300X1,000X800

    41

    2.242.8

    48770X900X320

    72 (V1), 71 (Y1)

    100

    36,100/35,70010.6/10.5

    FHYB100FV1R100LUV1R100LUY1

    9,100/9,000

    27953

    41/35300X1,400X800

    51

    3.003.7

    491,170X900X32087 (V1), 84 (Y1)

    125

    44,500/43,60013.0/12.8

    FHYB125FV1

    11,200/11,000

    351,23544/38

    300X1,400X800

    5255X880X500

    3.5

    55X880X500

    3.5

    55X1,100X500

    4.5

    55X1,100X500

    4.5

    55X1,500X500

    6.5

    55X1,500X500

    6.5

    3.753.7

    491,170X900X320

    98

    CEILING MOUNTED BUILT-IN TYPE

    Ivory white Hermetically sealed scroll typeHermetically sealed rotary type

    3.13/3.13 (V1)3.11/3.11 (Y1)

    4.00/4.00 (V1)3.95/3.95 (Y1)1.47/1.46 2.33/2.32 2.78/2.76 4.74/4.74

    Both liquid and gas piping

    21 to 46, -15 to 46 3 (Option installed)

    14 to 25

    ----------

    ----------

    3015

    14 to 23

    50 (equivalent length 70 m)3025

    Cooling capacity 1a/1b kWBtu/hkcal/h

    kWPower consumption 1a/1b

    °CDB

    °CWBCertified operation range

    ModelName

    Indoorunit

    Indoor unit

    Outdoor unit

    Dimensions(HXWXD)

    Colour

    mmmm

    Sound level (H/L) 2 dB(A)

    Refrigerant charge (R-22) kg

    Sound level 2 dB(A)Dimensions (HXWXD) mmMachine weight kg

    Unit

    Piping connections

    mmLiquid (Flare)

    Heat insulationMax. installation level difference

    mmGas (Flare)mmDrain Indoor unit

    Outdoor unit

    Decoration panel

    UnitDecoration panel

    Machine weight kgkgUnit

    Decoration panel

    Airflow rate (H) m3/mincfm

    Outdoorunit

    Colour

    mm

    Certified operation range

    Max. interunit piping length mm

    41 42

    9,000/8,9002.64/2.60

    2,270/2,250

    13458

    41/38260X900X580

    22

    12,100/11,9003.54/3.50

    3,040/3,010

    13458

    41/38260X900X580

    22

    18,200/18,1005.34/5.30

    4,590/4,560

    13458

    41/38260X900X580

    23

    24,000/23,8007.03/6.97

    6,050/6,00026,600/26,200

    7.80/7.70

    6,700/6,600

    18635

    42/39260X1,300X580

    31

    18635

    42/39260X1,300X580

    31

    Cooling capacity 1a/1b, 4 kWBtu/hkcal/h

    kWPower consumption 1a/1b

    °CDB

    °CWBCertified operation range

    ModelName

    Indoor unit

    Outdoor unit

    Dimensions (HXWXD) mmSound level (H/L) 2 dB(A)

    Refrigerant charge (R-22) kg

    Sound level 2 dB(A)Dimensions (HXWXD) mmMachine weight kg

    Piping connections

    mmLiquid (Flare)

    Heat insulation

    mmGas (Flare)mmDrain Indoor unit

    Outdoor unit

    kg

    Airflow rate (H)

    Fan Driving system

    m3/mincfm

    Outdoorunit

    mm

    Certified operation range

    Max. interunit piping length mm

    Machine weight

    Indoorunit

    Colour

    Max. installation level difference

    R25JV1 R35JV1 R50GV1 R60GV1 R71FUV1R71FUY1

    2.82/2.802.06/2.051.25/1.240.88/0.87 2.76/2.75

    14 to 2514 to 23

    Direct drive (2 speed)

    Colour

    Power supply V1: 1 Phase, 220–240 V, 50 Hz Y1: 3 Phase, 380–415 V, 50 Hz

    Power supply VE: 1 Phase, 220–240/220 V, 50/60 Hz V1: 1 Phase, 220–240 V, 50 Hz Y1: 3 Phase, 380–415 V, 50 Hz

    Power supply VE: 1 Phase, 220–240/220 V, 50/60 Hz V1: 1 Phase, 220–240 V, 50 Hz Y1: 3 Phase, 380–415 V, 50 Hz

    Power supply VE: 1 Phase, 220–240/220 V, 50/60 Hz V1: 1 Phase, 220–240 V, 50 Hz Y1: 3 Phase, 380–415 V, 50 Hz

    19.4 to 5419.4 to 46 19.4 to 46

    (Charged for 10 m) (Charged for 10 m) (Charged for 5 m) (Charged for 30 m) (Charged for 30 m) (Charged for 30 m)

    kWMotor outputCompressor Type

    kWMotor outputCompressor Type

    kWMotor outputCompressor Type

    kWMotor outputCompressor Type

    1.11.0

    48560X695X265

    33

    1.71.20

    49540X750X270

    42

    2.21.50

    54685X800X300

    61

    2.22.10

    52816X880X370

    87 (V1), 84 (Y1)

    Ivory white Hermetically sealed typeHermetically sealed rotary type

    Both liquid and gas piping

    21 to 52

    301550 (equivalent length 70 m)3025

    19.4 to 5419.4 to 46 19.4 to 46

    (Charged for 10 m)

    0.70.8

    46560X695X265

    27

    (Charged for 10 m) (Charged for 10 m) (Charged for 5 m) (Charged for 5 m)

    DUCT CONNECTION LOW STATIC PRESSURE TYPE

    Note : 1Rated cooling capacities are based on the following conditions:(FHB) 1aSuction temp., 27°CDB, 19.5°CWB; outdoor temp. 35°CDB. Equiv. refrigeration piping, 5 m (horizontal). 1bSuction temp., 27°CDB, 19.0°CWB; outdoor temp. 35°CDB. Equiv. refrigeration piping, 5 m (horizontal). (R71LU-R125LU is 7.5 m.)(FAY) 1aIndoor temp., 27°CDB, 19.5°CWB; outdoor temp. 35°CDB. Equiv. refrigeration piping, 5 m (horizontal). 1bIndoor temp., 27°CDB, 19.0°CWB; outdoor temp. 35°CDB. Equiv. refrigeration piping, 5 m (horizontal). (R71LU-R100LU is 7.5 m.)2Anechoic chamber conversion value, measured according to JIS parameters and criteria. During operation these values are somewhat higher owing to ambient conditions.

    3This value is for when year-round cooling kit (option) is installed.

    Note : 1Rated cooling capacities are based on the following conditions:(FVY) 1aIndoor temp., 27°CDB, 19.5°CWB; outdoor temp. 35°CDB. Equiv. refrigeration piping, 5 m (horizontal). 1bIndoor temp., 27°CDB, 19.0°CWB; outdoor temp. 35°CDB. Equiv. refrigeration piping, 5 m (horizontal). (R71LU-R125LU is 7.5 m.)(FDBG) 1aSuction temp., 27°CDB, 19.5°CWB; outdoor temp. 35°CDB. Equiv. refrigeration piping, 5 m (horizontal). 1bSuction temp., 27°CDB, 19.0°CWB; outdoor temp. 35°CDB. Equiv. refrigeration piping, 5 m (horizontal).2Anechoic chamber conversion value, measured according to JIS parameters and criteria. During operation these values are somewhat higher owing to ambient conditions.

    3This value is for when year-round cooling kit (option) is installed.4Capacities are gross, with no deduction made for evaporator fan motor heat.

    o/ 6.4o/ 12.7

    o/ 6.4o/ 15.9

    I.Do/ 25XO.Do/ 32 I.Do/ 25XO.Do/ 32 I.Do/ 25XO.Do/ 32 I.Do/ 25XO.Do/ 32 I.Do/ 25XO.Do/ 32 I.Do/ 25XO.Do/ 32

    o/ 6.4o/ 15.9

    o/ 9.5o/ 15.9

    o/ 9.5o/ 19.1

    o/ 9.5o/ 19.1

    o/ 18.0 (Hole) o/ 18.0 (Hole) o/ 18.0 (Hole) o/ 26.0 (Hole) o/ 26.0 (Hole) o/ 26.0 (Hole)

    o/ 9.5o/ 15.9

    I.Do/ 13XO.Do/ 18

    o/ 9.5o/ 19.1

    I.Do/ 20XO.Do/ 26o/ 26.0 (Hole) o/ 26.0 (Hole)

    o/ 9.5o/ 15.9

    I.Do/ 20XO.Do/ 26

    o/ 9.5o/ 19.1

    I.Do/ 20XO.Do/ 26

    o/ 9.5o/ 19.1

    I.Do/ 20XO.Do/ 26o/ 26.0 (Hole) o/ 26.0 (Hole) o/ 26.0 (Hole)

    o/ 6.4o/ 12.7

    o/ 6.4o/ 15.9

    3/4B 3/4B 3/4B 3/4B

    o/ 6.4o/ 15.9

    o/ 9.5o/ 15.9

    o/ 18.0 (Hole)

    o/ 6.4o/ 9.53/4B

    o/ 18.0 (Hole) o/ 18.0 (Hole) o/ 18.0 (Hole) o/ 26.0 (Hole)

    25FDBG25AVE

    35FDBG35AVE

    50FDBG50AVE

    60 71FDBG60AVE FDBG71AVE

  • 43 44

    DUCT CONNECTION HIGH STATIC PRESSURE TYPE

    Cooling capacity 1a/1b kWBtu/hkcal/h

    kWPower consumption 1a/1b

    °CDB

    °CWBCertified operation range

    ModelName

    Indoor unitOutdoor unit

    Dimensions (HXWXD) mmSound level (H) 2 dB(A)

    Refrigerant charge (R-22) kg

    Sound level 2 dB(A)Dimensions (HXWXD) mmMachine weight kg

    Piping connections

    mmLiquid (Flare)

    Heat insulation

    mmGas (Brazing)mmDrain Indoor unit

    Outdoor unit

    kg

    Airflow rate (H)

    Fan External static pressureDriving system

    m3/mincfm

    Pa(mmH2O)

    Outdoorunit

    mm

    Certified operation range

    Max. interunit piping length mm

    Machine weight

    Indoorunit

    Colour

    Max. installation level difference

    Colour

    Power supply

    kWMotor outputCompressor Type

    ----------

    Ivory white

    Both liquid and gas piping30

    50 (equivalent length 70 m)

    14 to 25

    Belt drive98 (10) 147 (15)

    Y1: 3 phase, 380–415 V, 50 Hz

    21 to 52

    Hermetically sealed scroll type

    3/4B 1B

    200 250 400 500FD08KY1 FD10KY1

    24.3/24.0 29.7/29.2

    RU08KUY1 RU10KUY1

    682,400

    832,929

    500X1,130X850 500X1,330X85093 104

    53

    FD15KY1 FD20KY1RU08KUY1X2

    48.6/47.9 59.3/58.4

    RU10KUY1X2

    1364,800

    1665,859

    625X1,620X850 625X1,980X850161 187

    58 60

    83,000/81,800 101,200/99,600 166,000/163,500 202,400/199,40020,900/20,600 25,500/25,100 41,800/41,200 51,000/50,200

    51

    7.5/7.4 9.9/9.8 15.0/14.8 19.8/19.6

    185 200

    60 61

    5.0 (Charged for 5 m)

    6.1 (Charged for 5 m)

    185X2 200X2

    60 3 61 3

    5.0 (Charged for 5 m)X2

    6.1 (Charged for 5 m)X2

    1,220X1,280X690 1,440X1,280X690 (1,220X1,280X690)X2 (1,440X1,280X690)X2

    7.5 9.0 7.5X2 9.0X2

    o/ 12.7 o/ 15.9 o/ 12.7X2 o/ 15.9X2o/ 25.4 o/ 31.8 o/ 25.4X2 o/ 31.8X2

    ----------

    Note : Models RU08K(U)Y1 and RU10K(U)Y1 are recommended for commercial facilities.1Rated cooling capacities are based on the following conditions: 1aSuction temp., 27°CDB, 19.5°CWB; outdoor temp. 35°CDB. Equiv. refrigeration piping, 5 m (horizontal). 1bSuction temp., 27°CDB, 19.0°CWB; outdoor temp. 35°CDB. Equiv. refrigeration piping, 5 m (horizontal). 2Anechoic chamber conversion value, measured according to JIS parameters and criteria. During operation these values are somewhat higher owing to ambient conditions.

    3Specification for outdoor unit is for a single unit only.

    ----------

    DUCT CONNECTION MIDDLE STATIC PRESSURE TYPE

    71

    26,600/26,2007.8/7.7

    FDYM03FAV1

    6,700/6,600

    20706

    39295X1,100X680

    42

    2.242.8 (Charged for 30 m)

    48770X900X320

    72 (V1), 71 (Y1)

    100

    36,100/35,70010.6/10.5

    FDYM04FAV1

    9,100/9,000

    26917

    39295X1,500X680

    56

    3.003.7 (Charged for 30 m)

    491,170X900X32087 (V1), 84 (Y1)

    125

    44,500/43,60013.0/12.8

    FDYM05FAV1

    11,200/11,000

    351,235

    44295X1,500X680

    57

    3.753.7 (Charged for 30 m)

    491,170X900X320

    98

    140

    49,400/48,40014.5/14.2

    FDYM06FAV1

    12,500/12,200

    371,306

    98(10) 98(10) 98(10) 98(10)46

    295X1,500X68057

    4.504.1 (Charged for 30 m)

    541,345X900X320

    109

    Both liquid and gas piping

    Cooling capacity 1a/1b kWBtu/hkcal/h

    kWPower consumption 1a/1b

    °CDB

    °CWBCertified operation range

    ModelName

    Indoor unit

    Outdoor unit

    Dimensions (HXWXD) mmSound level (H) 2 dB(A)

    Refrigerant charge (R-22) kgSound level 2 dB(A)Dimensions (HXWXD) mmMachine weight kg

    Piping connections

    mmLiquid (Flare)

    Heat insulation

    mmGas (Flare)mmDrain Indoor unit

    Outdoor unit

    kg

    Airflow rate (H)Fan

    External static pressure

    m3/mincfm

    Pa(mmH2O)

    Outdoorunit

    mm

    Certified operation range

    Max. interunit piping length mm

    Machine weight

    Indoorunit

    Colour

    Max. installation level difference

    R71LUV1R71LUY1

    R100LUV1R100LUY1 R125LUY1 R140LUY1

    3.25/3.25 (V1)3.23/3.23 (Y1)

    4.08/4.08 (V1)4.03/4.03 (Y1) 5.06/5.06 5.18/5.18

    Hermetically sealed scroll type

    21 to 46, -15 to 46 3 (Option installed)

    14 to 25

    3050 (equivalent length 70 m)

    Ivory white

    Colour

    Power supply V1: 1 Phase, 220–240 V, 50 Hz Y1: 3 Phase, 380–415 V, 50 Hz

    kWMotor outputCompressor Type

    ----------

    71 100 125 140

    Cooling capacity 1a/1b kWBtu/hkcal/h

    kWPower consumption 1a/1b

    °CDB

    °CWBCertified operation range

    ModelName

    Indoor unitOutdoor unit

    Dimensions (HXWXD) mmSound level (H) 2 dB(A)

    Refrigerant charge (R-22) kg

    Sound level 2 dB(A)Dimensions (HXWXD) mmMachine weight kg

    Piping connections

    mmLiquid (Flare)

    Heat insulation

    mmGas (Flare)mmDrain Indoor unit

    Outdoor unit

    kg

    Airflow rate (H)

    Fan External static pressureDriving system

    m3/mincfm

    Pa(mmH2O)

    Outdoorunit

    mm

    Certified operation range

    Max. interunit piping length mm

    Machine weight

    Indoorunit

    Colour

    Max. installation level difference

    Colour

    Power supply

    kWMotor outputCompressor Type

    Ivory white

    Both liquid and gas piping30

    50 (equivalent length 70 m)

    14 to 25

    FD03KY1 FD04KY1 FD05KY1R71FUY1

    8.1/ 7.927,800/27,000

    11.0/10.8 14.0/13.8

    R100FUY1 R125FUY1

    26917

    301,059

    461,623

    450X650X85051 59 72

    4946Belt drive

    88 (9)69 (7)

    Y1: 3 phase, 380–415 V, 50 Hz

    FD06KY1RU06KY1

    17.4/17.237,700/36,900 47,600/46,800 59,500/58,800

    7,000/6,800 9,500/9,300 12,000/11,800 15,000/14,800

    521,835

    450X1,130X85079

    51

    2.50/2.48 3.52/3.48 4.19/4.15 5.7/5.7

    450X900X850

    Hermetically sealed type

    84 109 110

    52 56 57

    21 to 52

    2.1 (Charged for 5 m)

    2.4 (Charged for 5 m)

    2.8 (Charged for 5 m)

    Hermetically sealed scroll type

    112

    59

    3.0 (Charged for 5 m)

    816X880X370 1,215X880X370 1,345X880X320

    3.0 3.8 4.5 4.5

    Note : 1Rated cooling capacities are based on the following conditions: 1aSuction temp., 27°CDB, 19.5°CWB; outdoor temp. 35°CDB. Equiv. refrigeration piping, 5 m (horizontal). 1bSuction temp., 27°CDB, 19.0°CWB; outdoor temp. 35°CDB. Equiv. refrigeration piping, 5 m (horizontal). (R71LU-R140LU is 7.5 m.)2Anechoic chamber conversion value, measured according to JIS parameters and criteria. During operation these values are somewhat higher owing to ambient conditions.

    3This value is for when year-round cooling kit (option) is installed.

    o/ 9.5o/ 15.9

    o/ 9.5o/ 19.1

    o/ 9.5o/ 19.1

    o/ 9.5o/ 19.1

    o/ 26.0 (Hole) o/ 26.0 (Hole) o/ 26.0 (Hole) o/ 26.0 (Hole)I.Do/ 25XO.Do/ 32 I.Do/ 25XO.Do/ 32 I.Do/ 25XO.Do/ 32 I.Do/ 25XO.Do/ 32

    3/4B

    o/ 9.5 o/ 9.5 o/ 9.5 o/ 9.5o/ 15.9 o/ 19.1 o/ 19.1 o/ 19.1

    o/ 26.0 (Hole) o/ 26.0 (Hole) o/ 26.0 (Hole) ----------

    ----------

    71

    30,000/29,6008.8/8.7

    FDMG71AV1

    7,600/7,500

    2381142

    305X1,350X68043

    2.202.4 (Charged for 5 m)

    52816X880X370

    87 (V1), 84 (Y1)

    100

    36,100/35,70010.6/10.5

    FDMG100AV1

    9,100/9,000

    341,200

    44305X1,550X680

    51

    3.002.4 (Charged for 5 m)

    561,215X880X370

    117 (V1), 109 (Y1)

    125

    44,500/43,60013.1/12.9

    FDMG125AV1

    11,200/11,000

    371,306

    45305X1,550X680

    52

    3.752.8 (Charged for 5 m)

    571,215X880X370

    110

    140

    49,400/48,40014.5/14.2

    FDMG140AV1

    12,500/12,200

    421,412

    46305X1,550X680

    52

    4.50Hermetically sealed scroll type

    2.9 (Charged for 5 m)55

    1,345X880X370113

    Both liquid and gas piping

    Cooling capacity 1a/1b kWBtu/hkcal/h

    kWPower consumption 1a/1b

    °CDB

    °CWBCertified operation range

    ModelName

    Indoor unit

    Outdoor unit

    Dimensions (HXWXD) mmSound level (H) 2 dB(A)

    Refrigerant charge (R-22) kgSound level 2 dB(A)Dimensions (HXWXD) mmMachine weight kg

    Piping connections

    mmLiquid (Flare)

    Heat insulation

    mmGas (Flare)mmDrain Indoor unit

    Outdoor unit

    kg

    Airflow rate (H)Fan m3/mincfm

    Outdoorunit

    mm

    Certified operation range

    Max. interunit piping length mm

    Machine weight

    Indoorunit

    Colour

    Max. installation level difference

    RG71AV1RG71AY1

    R100FUV1R100FUY1 R125FUY1 RG140AY1

    3.15/3.13 4.08/4.04 4.89/4.85 5.25/5.25

    Hermetically sealed type

    21 to 52 21 to 50

    14 to 25

    3050 (equivalent length 70 m)

    Ivory white

    Colour

    Power supply V1: 1 Phase, 220–240 V, 50 Hz Y1: 3 Phase, 380–415 V, 50 Hz

    kWMotor outputCompressor Type

    o/ 9.5o/ 15.9

    o/ 9.5o/ 19.1

    o/ 9.5o/ 19.1

    o/ 9.5o/ 19.1

    o/ 26.0 (Hole) o/ 26.0 (Hole) o/ 26.0 (Hole) o/ 26.0 (Hole)3/4B 3/4B 3/4B 3/4B

    180

    58,700/57,50017.2/16.8

    FDMG180AV1

    14,700/14,400

    421,482

    47305X1,900X680

    58

    4.502.8 (Charged for 5 m)

    561,345X880X370

    114

    RG180AY1

    6.45/6.45

    o/ 9.5o/ 19.1

    o/ 26.0 (Hole)3/4B

  • 45 46

    DUCT CONNECTION HIGH STATIC PRESSURE TYPE

    Cooling capacity 1a/1b kWBtu/hkcal/h

    kWPower consumption 1a/1b

    °CDB

    °CWBCertified operation range

    ModelName

    Indoor unitOutdoor unit

    Dimensions (HXWXD) mmSound level (H) 2 dB(A)

    Refrigerant charge (R-22) kg

    Sound level 2 dB(A)Dimensions (HXWXD) mmMachine weight kg

    Piping connections

    mmLiquid (Brazing)

    Heat insulation

    mmGas (Brazing)mmDrain Indoor unit

    Outdoor unit

    kg

    Airflow rate (H)

    Fan External static pressureDriving system

    m3/mincfm

    Pa(mmH2O)

    Outdoorunit

    mm

    Certified operation range

    Max. interunit piping length mm

    Machine weight

    Indoorunit

    Colour

    Max. installation level difference

    Colour

    Power supply

    kWMotor outputCompressor Type

    Note : Models RU08K(U)Y1 and RU10K(U)Y1 are recommended for commercial facilities.1Rated cooling capacities are based on the following conditions: 1aSuction temp., 27°CDB, 19.5°CWB; outdoor temp. 35°CDB. Equiv. refrigeration piping, 5 m (horizontal). 1bSuction temp., 27°CDB, 19.0°CWB; outdoor temp. 35°CDB. Equiv. refrigeration piping, 5 m (horizontal). 2Anechoic chamber conversion value, measured according to JIS parameters and criteria. During operation these values are somewhat higher owing to ambient conditions.

    3Specification for outdoor unit is for a single unit only.4This is the amount of refrigerant required for piping of five meters or less. Since the unit does not contain refrigerant when shipped from the factory, it must be added at the installation site. For details, please refer to the installation manual.

    ----------

    Ivory white

    Both liquid and gas piping30

    50 (equivalent length 70 m)

    14 to 25

    Belt drive98 (10) 147 (15)

    Y1: 3 phase, 380–415 V, 50 Hz

    21 to 52

    Hermetically sealed scroll type

    3/4B 1B

    200 250 400 500FD08KY1 FD10KY1

    24.3/24.0 29.7/29.2

    RU08KY1 RU10KY1

    682,400

    832,929

    500X1,130X850 500X1,330X85093 104

    53

    FD15KY1 FD20KY1RU08KY1X2

    48.6/47.9 59.3/58.4

    RU10KY1X2

    1364,800

    1665,859

    625X1,620X850 625X1,980X850161 187

    58 60

    83