fcu-6000 system manual
TRANSCRIPT
-
8/10/2019 FCU-6000 system manual
1/68
Fire Alarm Control Panel
N 6000
Manual
REV B
DATE 2007-08-08
-
8/10/2019 FCU-6000 system manual
2/68
-
8/10/2019 FCU-6000 system manual
3/68
against telephone line failure, backup radio transmission
systems are recommended.
The most common causeof fire alarm malfunction is
inadequate maintenance. To keep the entire fire alarm
system in excellent working order, ongoing maintenance
is required per the manufacturer's recommendations.
Environments with large amounts of dust, dirt or high air
velocity require more frequent maintenance. A
maintenance agreement should be arranged through the
local manufacturer's representative. Maintenance should
be scheduled or as required by National and/or local fire
codes and should be performed by authorized professional
fire alarm installers only. Adequate written records of all
inspections should be kept.
-
8/10/2019 FCU-6000 system manual
4/68
Installation Precautions
Adherence to the following will aid in problem-free installation with long-term reliability:
Several different sources of power can be
connected to the fire alarm control panel. Disconnectall
sources of power before servicing. Control unit and
associated equipment may be damaged by removing
and/or inserting cards, modules, or interconnecting cables
while the unit is energized. Do not attempt to install, service,
or operate this unit until this manual is read and
understood.
System Reacceptin g Test after Software
Changes. To ensure proper system operation, thisproduct
must be tested after any programming operation or change
in site-specific software.
All components, circuits, system operations, or software
functions known to be affected by a change must be 100%
tested. In addition, to ensure that other operations are not
inadvertently affected, at least 10% of initiating devices that
are not directly affected by the change, up to a maximum of
50 devices, must also be tested and proper system
operation verified.
Verify that w ire sizes are adequate for all initiating and
indicating device loops. Most devices cannot tolerate more
than a 10% I.R. drop from the specified device voltage.
Like all solid state electronic devices, this system may
operate erratically or can be damaged when subjected to
lightning-induced transients. Although no system is
completely immune from lightning transients and
interferences, proper grounding will reduce susceptibility.
Overhead or outside aerial wiring is not recommended,
due to an increased susceptibility to nearby lightning strikes.
Consult with the Technical Services Department if any
problems are anticipated or encountered.
Disconnect AC power and batteries prior to removing
or inserting circuit boards. Failure to do so can damage
circuits.
Remove all electronic assemblies prior to any drilling,
filing, reaming, or punching of the enclosure. When
possible,
make all cable entries from the sides or rear. Before making
modifications, verify that they will not interfere with battery,
transformer, and printed circuit board location.
-
8/10/2019 FCU-6000 system manual
5/68
Table of ContentSection 1:About This Manual ................................................................................................................. 6
1.1Notes, Cautions & Warnings......................................................................................................... 6
1.2Font Definition .............................................................................................................................. 6Section 2:System Overview.................................................................................................................... 7
2.1Introduction ................................................................................................................................... 7
2.2Characteristics of the Product........................................................................................................ 7
Section 3:System Configuration & Installation ...................................................................................... 9
3.1Features Main Performances ......................................................................................................... 9
3.2Electrical Specifications................................................................................................................ 9
3.3System Configuration.................................................................................................................... 9
3.4System Block Diagram................................................................................................................ 10
3.5Installation & Connection ........................................................................................................... 11
3.5.1Enclosures............................................................................................................................ 11
3.5.2Connection Requirements.................................................................................................... 12
3.5.3Connection of Circuit Board Terminals............................................................................... 12
3.5.3.1CPU Diagram............................................................................................................... 12
3.5.3.2Power Supply Connection............................................................................................ 15
3.5.3.3NIC-EC......................................................................................................................... 17
3.5.3.4Loop Control Module Connection................................................................................ 19
3.5.3.5MCU-16B Annunciator Control Module Connection.................................................. 21
3.6Equipment Debugging ............................................................................................................ 23
3.6.1Connection Inspection..................................................................................................... 23
3.6.2Power-on Inspection........................................................................................................ 24
3.6.3External Connection........................................................................................................ 24
3.6.4Important Points .............................................................................................................. 24
3.6.5Inspection Methods for Addressable Device Connections.............................................. 25
Section 4:Operation .............................................................................................................................. 26
4.1LED Indicators and Keys ............................................................................................................ 26
4.1.1Control Panel Display LED Indicators and Keys ................................................................ 26
4.1.2Annunciator Control Module LED Indicators and Keys ..................................................... 29
4.2Power-on ..................................................................................................................................... 304.3System Self-test........................................................................................................................... 30
4.4Event Display .............................................................................................................................. 32
4.4.1Trouble Screen..................................................................................................................... 32
4.4.2Fire Alarm Screen................................................................................................................ 33
4.4.3Supervisory Screen .............................................................................................................. 34
4.4.4Point Disabled Screen.......................................................................................................... 35
4.4.5CBE Screen.......................................................................................................................... 36
4.4.6Pre-alarm Screen.................................................................................................................. 36
4.4.7Horn / strobe Screen ............................................................................................................ 37
4.4.8Feedback Screen .................................................................................................................. 37
-
8/10/2019 FCU-6000 system manual
6/68
Section 5:Programming ........................................................................................................................ 38
5.1Menu....................................................................................................................................... 38
5.2System Management............................................................................................................... 40
5.2.1System setting ................................................................................................................. 41
5.2.2Password modification .................................................................................................... 425.2.3Main Reset....................................................................................................................... 43
5.3Device Configuration.............................................................................................................. 44
5.3.1Loop card......................................................................................................................... 45
5.3.1.1Parameter setting .......................................................................................................... 45
5.3.1.2Auto Programming....................................................................................................... 47
5.3.1.3Point Programming....................................................................................................... 49
5.3.2Annunciator Control Module .......................................................................................... 50
5.3.2.1Parameter setting .......................................................................................................... 51
5.3.2.2Point Programming....................................................................................................... 51
5.3.3Remote Display ............................................................................................................... 52
5.3.3.1Parameter setting .......................................................................................................... 53
5.3.3.2Label Download ........................................................................................................... 53
5.3.3.3Point Programming....................................................................................................... 54
5.3.4CBE Programming............................................................................................................... 54
5.3.4.1General Zone ................................................................................................................ 55
5.3.4.2Logic Zone ................................................................................................................... 55
5.3.5Device Control..................................................................................................................... 56
5.3.5.1Manual Output.............................................................................................................. 57
5.3.5.2Status Tracking............................................................................................................. 58
5.3.5.3Walk Test ..................................................................................................................... 58
5.3.5.4Loop Drill ..................................................................................................................... 60
5.3.5.5Power Supply Management.......................................................................................... 60
5.3.6History Events .......................................................................................................................... 61
Section 6:Miscellaneous ....................................................................................................................... 62
6.1Safety Protection Device............................................................................................................. 62
6.2Usage and Maintenance............................................................................................................... 62
6.3Common Troubles....................................................................................................................... 62
6.4Transportation & Storage ............................................................................................................ 636.5Out-of-box Audit......................................................................................................................... 63
Appendix A........................................................................................................................................... 64
-
8/10/2019 FCU-6000 system manual
7/68
Section 1:About This Manual
1.1Notes, Cautions & Warnings
The following graphics appear in this manual to indicate a note, a caution, or
warning:
Note:Information that highlights an important part of the preceding orsubsequent text or illustration.
Cautions:Information about procedures that could cause programming
errors, runtime errors, or equipment damage.
Warnings: Indicates information about procedures that could causeirreversible damage to the control panel, irreversible loss of programming data or
personal injury.
1.2Font Definition
Special font styles used in this manual are listed in Table 1-1, Specifications of
Manual Characters:
Font Meaning Example
Bold
Key on the control panel Press the key Signals
Silenced
Script Name of document N-6000 User Manual
Table 1-1 Specifications of Manual Characters
-
8/10/2019 FCU-6000 system manual
8/68
Section 2:System Overview
2.1Introduction
The N-6000 is a new generation intelligent fire alarm control panel recently
released by Notifier. This panel satisfies all related requirements defined in
GB4717-2005.
This control panel combines both alarm and CBE control functions. The N-6000
can also be programmed off-line when using a PC with Notifier Verifire Tools
(NVT).
The N-6000 fire alarm control panel has many intelligent characteristics; these
include but are not limited to drift compensation, sensitivity adjustment andself-optimizing alarm.
The N-6000 control panel with CBE (control by event) control can manage both
alarm paging and gas extinguishing systems. The N-6000 connected with a CRT
display terminal forms a comprehensive and reliable fire alarm control system,
perfect for medium to large-scale facilities.
2.2Characteristics of the Product
Large LCD Display
This system uses a large 320x240 pixel LCD display. To ensure accurate and
timely detection the LCD displays a full Chinese interface (up to 320 Chinese
characters), equipment type, location, alarm level, loop number and address
number upon alarming.
User Friendly Interface
The Menu contains all programming options. Software supports both English and
Chinese input, full suggest and user friendly dialogue prompts. A user can
conveniently toggle between the alarm information and CBE information screens.
Convenient Programming Options
Multilevel pre-alarm and alarm sensitivity enable localizing detector sensitivity for
different applications. Have the function of trouble disenable also can choose to
disenable any addressing unit in loop bus. Auto programming allows the N-6000
to learn what devices are physically connected and automatically load them in
the program with default values for all parameters. The functions mentioned above
significantly ease system operation while reducing daily maintenance.
Real-time Analogue Display Curve
Real-time threshold value variation monitoring is possible for both intelligent
analogue detectors and/or compound detectors.
Powerful CBE Equations
-
8/10/2019 FCU-6000 system manual
9/68
Accurate and Detailed Event Records
The system automatically and categorically stores and records the latest fire alarm,
trouble or system event. It can display and store up to 8000 historical events.
Automatic Compensation Functions
Drift compensation allows the detector to retain its original ability to detect actualsmoke, and resist false alarms, even as dirt or dust accumulates. It reduces
maintenance requirements by allowing the system to automatically perform
periodic sensitivity measurements. Smoothing filters are also provided by software
to remove transient noise signals, usually caused by electrical interference.
Printing Settings
The system can be networked and prompted to print the latest alarm event using a
Chinese printer.
Equipped With 8 Bus Control Modules.
Built-in Degraded Mode option. In the event of a CPU failure, the system iscapable of general alarm if a fire condition is present.
Off-line Programming and CRT display terminal
Connected with PC through the RS-232 interface, Screen of the control panel to
realize programming setting on circuit configuration, CBE control relation of the
control panel. Also can be connected with NCS through this Screen to carry out
centralized management.
-
8/10/2019 FCU-6000 system manual
10/68
Section 3:System Configuration &Installation
3.1Features Main Performances
Supports 1 to 30 Signaling Line Circuits (SLCs). Up to 199 detectors and 99modules (N.O. manual stations, two-wire smoke, notification or relay) per
SLC
Loop connection ports available, expandable up to 15 loop circuit cards
Supports up to 64 remote LCD displays
Supports up to 32 MCU control card
Micro printer port
N-CRT port provided - seamless connection to a third party system
Fire alarm output and trouble output relays
Real-time clock
3.2Electrical Specifications
Voltage range
Input voltage: 220 VAC
Output voltage:
Two 24 VDC non-resetable outputs
One 24 VDC resetable output
Two 5 VDC outputs
Several dry contacts - power supply trouble relay output
Maximum output current: 14.6A
3.3System Configuration
Intelligent control panel: N-6000
Remote display: LCD-100B, LDM-64B
Intelligent detectors:
Intelligent photoelectric smoke detector: ND-751P
Intelligent heat detector: ND-751T
Intelligent laser smoke detector: FSL-751
-
8/10/2019 FCU-6000 system manual
11/68
Intelligent smoke detector: FSB-200S
Intelligent base:
B601
B501
Intelligent modules:
Intelligent monitor module: MMX-7
Intelligent monitor/control module: CMX-7
Intelligent control module: CMX-7C
Monitor module for two-wire 24 VDC conventional detectors:MMX-7P
Isolator: ISO-7
Intelligent manual call point: M500K
Intelligent manual call point: M700K
Micro printer: uPRT-380S
Chinese graphic and text management software: N-NCS, N-VFT
3.4System Block Diagram
Fig. 3-1 System Block Diagram
If there are many addressable units in the loop bus, user should install the
shortcut isolator in front of the loop bus. The addressable units are less than 25
units between adjacent two isolators.
-
8/10/2019 FCU-6000 system manual
12/68
3.5Installation & Connection
3.5.1Enclosures
Wall-mount designs use a standard NOTIFIER C-type cabinet. This cabinet is
shown in Fig. 3-2 Cabinet Appearance:
Fig. 3-2 Cabinet Appearance
Detailed cabinet dimensions are shown in Fig. 3-3:
Fig. 3-3 C-type Cabinet Dimension Diagram
All NOTIFIER cabinets are fabricated from 16-gauge steel. The cabinet assemblyconsists of two basic parts: a backbox and a locking door. The backbox has been
-
8/10/2019 FCU-6000 system manual
13/68
engineered to provide ease-of-entry for the installer. Knockouts are positioned at
numerous points to aid the installer in bringing a conduit into the enclosure.
3.5.2Connection Requirements
All incoming/outgoing external conduits should use the control panel cabinetsbottom knockout or opening for terminal connections.
Loop transmission line adopts twisted pair cable, the type and specification are:
RVSP21.5mm2
Loop resistance (refers to loop resistance between the machine and two leads ofthe farthest addressing unit) should be less than 50 .
Power wiring should use two-color multiple plastic cable, red for male terminal,
black for female terminal. The type and specification are: RV-22.5mm2
3.5.3Connection of Circuit Board
Terminals
3.5.3.1CPU Diagram
Control panel includes in a circuit board, it has CPU and extend device interface.
You can order the board supports for 8, 16, 30 loops. The connections terminals,
jumper and status lights are showed below:
-
8/10/2019 FCU-6000 system manual
14/68
Fig. 3-4 CPU Diagram
Connections terminal illuminate table:
Terminal Illumination
TB1 System Event Relay1programmableDefault is fire alarm trigger
TB2 System Event Relay12programmableDefault is trouble trigger
TB3 System Event Relay13programmableDefault is reset trigger
TB4 24VDCPower
TB5 RS-232 Micro printer port
TB6 RS-232 NIC port
TB7 N-CRT PortVFTthird party system
TB8 RPT port
TB9 Loop communication port
TB10 Extended device portMCU/POM-8C/MPS
J10 Loudspeaker see J15
J13 Power, loop and extended device channel aggregate terminal
-
8/10/2019 FCU-6000 system manual
15/68
J15 Buzzer; user can select J10 or J15 to be system sound component
Table 3-1 CPU-6000 Board Terminal Illuminate
Jumper illuminate table:
Terminal Illumination
JP2 System Event Relay 1output selection 24Vor trunk node
JP3 System Event Relay 2output selection 24Vor trunk node
JP5 System Event Relay 3output selection 24Vor trunk node
JP9 ISP program write down jumper, user should cover jumper cap whenISP upgrade program
JP18 Loop RS485 communication match terminal resistance selection
jumper
JP19 Loop RS485 communication match terminal capacitance selection
jumper
JP21 Extended device RS485 communication match terminal resistanceselection jumper
JP22 Extended device RS485 communication match terminal capacitance
selection jumper
JP23 RPT RS485 communication match terminal resistance selectionjumper
JP24 RPT RS485 communication match terminal capacitance selectionjumper
Table 3-2 CPU-6000 Board Jumper Illuminate
LED status illuminate table:
Terminal Illumination
LED1 System status normalGreen
LED2 System fire alarm and CBE eventRed
LED3 System trouble eventYellow
LED4 System supervise eventBlue
LED5 Relay1relay close is green
LED6Relay2
relay close is green
LED7 Relay3relay close is green
LED8 24VDCGreen
LED9 5VDCGreen
LED10 Micro printer channel signal send; signal on is green
LED11 N-CRT protocol channel signal send; signal on is green
LED12 Micro printer channel signal receive; signal on is green
LED13 N-CRT protocol channel signal receive; signal on is green
LED15 RPT channel signal receive; signal on is green
-
8/10/2019 FCU-6000 system manual
16/68
LED17 RPT channel signal send; signal on is green
LED18 Extended device channel signal receive; signal on is green
LED19 Loop channel signal receive; signal on is green
LED20 Extended device channel signal send; signal on is green
LED21 Loop channel signal send; signal on is green
Table 3-3 CPU-6000 Status Light Illumination
3.5.3.2Power Supply Connection
The N-6000 fire alarm control panel is powered by the MPS-350W power supply
module. This power module provides multi-path 24 VDC and 5 VDC outputs.
During a power loss the MPS-350W battery will automatically engage and provide
power. LED displays indicate the status of multiple functions, including: main
power trouble, reserve power trouble, grounding trouble, storage battery chargingtrouble and power supply relay output trouble.
Refer to the MPS-350W user manual for additional information regarding function,
connection and/or application of the MPS-350W power supply.
Fig. 3-5 Power Supply Connection Diagram
Connections terminal illuminate table:
Terminal Illumination
-
8/10/2019 FCU-6000 system manual
17/68
TB1 Non-resetable 24VDC terminal
TB2 Non-resetable 24VDC terminal
TB3 Resetable 24VDC terminal
TB4 Non-resetable 24VDC terminal
TB5 Non-resetable 24VDC terminal
TB12 Trouble relay trunk node terminal
TB13 RS-485 serial communication port terminal
TB14 Extended system supervise signal terminal
Table 3-4 MPS-350 Terminal Illumination
Jumper illuminate table:
Terminal Illumination
JP1 Program jumper, user can not change
JP2 RS-485 bus terminal match capacitance
JP3 RS-485bus terminal match resistance
JP4/ JP5 Earth trouble function enable, disable
Table 3-5 MPS-350 Jumper Illumination
LED status illuminate table:
LED Illumination
LED1 Non-resetable 24VDC fuse melt indication
LED2 Non-resetable 24VDC fuse melt indication
LED3 Resetable 24VDC fuse melt indication
LED13 Non-resetable 5VDC fuse melt indication
LED19 Non-resetable 5VDC fuse melt indication
LED23 Battery cut protect indication
LED24 Battery fuse melt indication
LED25 Power normal indication
LED26 Power trouble indication
LED27 Battery normal indication
LED28 Battery trouble indication
LED29 System running indication
LED30 Earth trouble indication
Table 3-6 MPS-350 Status Light Illumination
-
8/10/2019 FCU-6000 system manual
18/68
3.5.3.3NIC-EC
When N-6000 connect into N-NET fire alarm network, each control panel must
install a NIC-EC card. Connection terminal, jumper and indicative show as below:
Fig. 3-6 NIC-EC Connection Diagram
Connections terminal illuminate table:
Terminal Illumination
TB1 Network port A
TB2 24VDC power port
TB3 NIC-EC and CPU-6000 communication portRS232
TB5 Network port A
Table 3-7 NIC-EC Terminal Illumination
Jumper illuminate table:
Terminal Illumination
JP6 RS232 modeleave factory set, not to change
JP7 Open leave factory set, not to change
JP8 Open leave factory set, not to change
JP9 RS232 modeleave factory set, not to change
Table 3-8 NIC-EC Jumper Illumination
LED status illuminate table:
-
8/10/2019 FCU-6000 system manual
19/68
LED1 Green Port B signal outputBlink when signal output
otherwise off
LED2 Green Port B signal inputBlink when signal input
otherwise off
LED23 Green Port B informationstatus
Status overturn after send or
receive a frame informationcorrectly
LED24 Yellow Port B troubleLED on when send or receive aframe information wrongly or
check out communication error
LED25 Red Port B circuit trouble LED on when any trouble occur
LED3 Green Port A signal outputBlink when signal output
otherwise off
LED4 Green Port A signal inputBlink when signal input
otherwise off
LED20 GreenPort A information
status
Status overturn after send or
receive a frame informationcorrectly
LED21 Yellow Port A trouble
LED on when send or receive a
frame information wrongly orcheck out communication error
LED22 Red Port A circuit trouble LED on when any trouble occur
LED5 GreenSystem running
indicationBlink when running normally
LED6 YellowControl panel type
indicationLED on when connect to
CPU-6000
LED7 RedControl panel type
indicationLED on when connect to N-NCS
LED8 Green+24V power status
lightLED on when +24V power
supply normally
LED9 Green+5V power status
lightLED on when +5V power supply
normally
LED10 GreenTB3 port signal
inputBlink when signal input
otherwise off
LED11 Green J9 signal inputindication
Blink when signal inputotherwise off
LED12 GreenTB3 port signal
outputBlink when signal output
otherwise off
LED13 GreenJ9 signal output
indication
Blink when signal output
otherwise off
LED14 Green Function reserve
LED15 Green Function reserve
LED16 Red Function reserve
LED17 Green TB3 portinformation
Status overturn after send or
receive a frame information
-
8/10/2019 FCU-6000 system manual
20/68
correctly
LED18 Yellow TB3 port troubleLED on when receive
information error
LED19 RedTB3 port circuit
troubleLED on when receive
information error
LED26 Blue Function reserve
Table 3-9 NIC-EC Indicative Light Illumination
DIP switch network address setting table:
SW2 status Function
ON1
OFF
ON2
OFFON
3OFF
ON4
OFF
ON5
OFF
ON6
OFF
1~6bits switch
ON for 1OFF for 0
Composing a 6 bits binary number,
this number infer network cardaddress. Network card address
range is the number between 0~63.
Network card address must be same
as the connect devices address.
ON Relay mode7
OFF Bus mode
ON N-NCS8
OFF CPU-6000
Table 3-10 NIC-EC Address Setting
3.5.3.4Loop Control Module Connection
N-6000 support 15 LCM-2 cards, and 30 loops. LCM-2 support style 4 or T-type
wiring. TB2 in LCM-2 board connect to CUP-6000 interface, the rest connect each
other. LCM-2 can connect with twisted shielded pair cable: signal connect to TB2,
power connect to TB3; also can connect each other through J2 and J4.
-
8/10/2019 FCU-6000 system manual
21/68
Fig. 3-7 Loop Control Module Connection Diagram
Connection terminal illuminate table:
Terminal Illumination
TB2 Connect to CPU-6000RS485also can connect to LCM card
TB3 24VDC power port
TB4 Loop 1 portthe loop number is SW1s value
TB5 Loop 2 portthe loop number is SW1s value1
J2 Interlink port
J4 Interlink port
Table 3-11 LCM-2 Card Terminal Illumination
Jumper illuminate table:
Terminal Illumination
JP1 Communication to CPU-6000 port terminal resistance (normal open)
JP2 Communication to CPU-6000 port terminal capacitance (normalopen)
JP4 Switch to RS232 modeleave factory set, not to change
JP5 Switch to RS232 modeleave factory set, not to change
Table 3-12 LCM-2 Card Jumper Illumination
LED Status Illuminate table:
Terminal Illumination
LED1 3.3V system power supply indication
LED2 24 V system power supply indication
-
8/10/2019 FCU-6000 system manual
22/68
LED3 5 V system power supply indication
LED4 CPU-6000 communication/LCM card local mode indecation
LED5 Loop 1 running indication
LED6 Loop 1 trouble indication
LED7 Loop 1 fire alarm indication
LED8 Loop 2 running indication
LED9 Loop 2 trouble indication
LED10 Loop 2 fire alarm indication
LED11 Communication to CPU-6000send indication
LED12 Communication to CPU-6000send indication
Table 3-13 LCM-2 Card Status Light Illumination
DIP Switch Loop Number Setting table:
SW1~8 1~8bits switch
ON for 1OFF for 0
Composing a 8 bits binary number, infer LCM card
address. SW1 setting range is the odd number between1~29
Table 3-14 LCM-2 Loop Number Setting
3.5.3.5MCU-16B Annunciator Control Module
ConnectionN-6000 can connect MCU-16B. Support the manual control to output point of
control module, and use LED to show the status of controlled points.
MCU-16B includes 16 output indicative light, 16 feedback statuses light, 16 button
to manual control, a complex function button, a enable/disable button and a
manual/auto status light.
Each manual control module can be programmed to any control module. Each
feedback statuses light can be programmed to control an input device.
Enable/disable button use to enable or disable 16 manual control buttons.
MCU-16B connects to N-6000 by RS-485 port, this port can support 32MCU-16B.
-
8/10/2019 FCU-6000 system manual
23/68
Fig. 3-8 Annunciator Control Module Connection Diagram
Connection terminal illuminate table:
Terminal Illumination
TB1 24VDC power port
TB2 Connect to CPU-6000RS485
J1 Interlink port
J3 Interlink port
Table 3-15 MCU-16B Terminal Illumination
Jumper illuminate table:
Terminal Illumination
JP1Open
leave factory set, not to change
JP2 Communication to CPU-6000 port terminal resistance (normalopen)
JP3 Communication to CPU-6000 port terminal capacitance (normal
open)
JP4 Switch to RS232 modeleave factory set, not to change
JP5 Switch to RS232 modeleave factory set, not to change
JP6 Buzzer switchdefault shortcut, enable
Table 3-16 MCU-16B Jumper Illumination
LED Status Illuminate table:
-
8/10/2019 FCU-6000 system manual
24/68
Terminal Illumination
LED1 24 V system power supply indication
LED2 5 V system power supply indication
LED3 3.3 V system power supply indication
LED4 System running indication
LED39 Communication to CPU-6000send indication
LED40 Communication to CPU-6000send indication
Table 3-17 MCU-16B Status Light Illumination
DIP Switch Loop Number Setting table:
SW2 status function
ON1
OFF
ON2
OFF
ON3
OFF
ON4
OFF
ON5
OFF
1~8bits switch
ON for 1OFF for 0
Composing a 5 bits binary number, thisnumber +1 infer MCUs address.
MCUs address range is the numberbetween 1~29
ON6
OFFNONE
ON7
OFFNONE
8 ON NONE
Table 3-18 MCU-16B Network address setting
3.6Equipment Debugging
3.6.1Connection Inspection
Visually inspect the control panel condition
Visually inspect the external connection ports
Open the control panel and visually inspect all connections. Confirm connectionsare correct, that there are no loose connections, no short circuits, unplugged or
-
8/10/2019 FCU-6000 system manual
25/68
disconnected connectors as well as confirm the power supply does not have
any short circuit trouble.
Visually inspect the jumpers in the circuit to confirm there are no duplicatenumbers.
3.6.2Power-on Inspection
After you have finished the visual inspection, power-on the battery power supply.
With the battery started a buzzer should be heard and the LCD should temporarily
function normally. Once the control panel enters normal operation status, a buzzer
and LED horn/strobe will indicate a troubled status because main power is not
connected. Power-down and disconnect the battery power supply then connect and
power on the main power supply. Once the control panel enters normal operation
status, a buzzer and LED horn/strobe will indicate a troubled status because the
battery power supply is not connected. At this time, connect the battery power
supply. Soon after the control panel will return to normal operating status.
During normal operation, if both the main and battery power supplies are
connected the power supply status lamp (on the main panel of the control panel)
will maintain normal illumination.
When the main power supply fails because of loss of power, poor power
connection, an over-voltage or under-voltage of 5V and 24V, or a short circuit with
rack earth and communication trouble with the mainframe, the power supply status
lamp (on main panel of the control panel) illumination will stop. Then both a
buzzer and LED horn/strobe will indicate a troubled status while additional
information will be shown on the control panel LCD.
3.6.3External Connection
Look for any short-circuits or disconnections to and from the control panel. Once
everything has been inspected, connect the control panel.
Batch installation -- connecting 10-20 detectors or modules on the loop per time --
is highly recommended. After installing the detectors or modules restart the control
panel to ensure the newly installed devices are recognized and installed correctly.
If the control panel gives a trouble signal recheck the circuit and addressable
devices are installed properly. Once the trouble signal has been solved, continuebatch installation and power testing. After all the devices have been installed, the
simulated trouble, fire alarm and CBE event functions maybe tested. Confirm that
the control panel alarms normally, properly links field equipment and accurately
prints corresponding alarm information. Continue testing and adjusting until panel
maintains normal operating status.
3.6.4Important Points
Avoid touching the circuit board IC chip during installation
Pay attention to polarity during connection and installation
-
8/10/2019 FCU-6000 system manual
26/68
Before starting the system, check for short circuits, disconnection or reversepolarity
Connectors among leads shall be wielded and inter-line insulation shall beguaranteed.
3.6.5Inspection Methods for Addressable Device
Connections
To test the function of the multi-meter, connect the loop in reverse polarity (the
positive pole connects with the loop negative and the negative pole connects with
the loop positive). The multi-meter should indicate a bias value for the diode.
Then connect the multi-meter normally (positive pole connects with the loop
positive and negative pole connects with the loop negative). The multi-meter
should indicate a low resistance value that increases with the charging of the loop
capacitor. If after proper polarity connection the multi-meter still indicates a biasvalue for the diode, there is one or more addressable device(s) connected in reverse
polarity.
-
8/10/2019 FCU-6000 system manual
27/68
Section 4:Operation
4.1LED Indicators and Keys
4.1.1Control Panel Display LED
Indicators and Keys
The N-6000 is an intelligent addressable Fire Alarm Control Panel (FACP) with
advanced features ideal for a variety of applications. The CPU-6000 includes a
front display/keypad enabling localized control panel viewing and programming.The display/keypad provides an easy-to-use keypad and large LCD (liquid crystal
display) that simplifies the programming process.
The display is 53 characters wide by 20 lines long and displays all programming
screens. These include the events, history, devices as well as other additional
information.
Fields may be entered or changed and commands may be issued using the display
keypad.
Fig. 4-1 Display/Keypad Diagram
-
8/10/2019 FCU-6000 system manual
28/68
LED Lamp Status
LED Indicator Color Functions
Fire alarm Red Illuminates when at least one fire alarm event exists. It will
flash if any of these events are unacknowledged.
Pre-alarm Red Illuminates when at least one pre-alarm event exists. It will
flash if any of these events are unacknowledged.
Trouble Yellow Illuminates when at least one trouble event exists. It will flash
if any of these events are unacknowledged.
Power Green Indicates current status of the power supply. During normal
communication with the power supply, the lamp will flash.
Self-test Yellow Indicates the system is in self-test status. The LED will
remain lit during the self-test.
CBE Red I/O module is functioning properly or there is a feedback
signal.
Delay Red If the control panel has a delayed control output the LED will
remain illuminated throughout the delay period. It will turn
off upon termination of the delay period.
Signal Silenced Yellow Illuminates if NFS-3030 Notification Appliances have been
silenced. It flashes if some but not all of the N-6000 NACs
have been silenced.
Point Disabled Yellow Illuminates when at least one device has been disabled. It will
flash until all disabled points have been acknowledged.
Supervisory Red Illuminates when at least one supervisory event exists. It will
flash if any of these events are unacknowledged.
CPU Failure Yellow Illuminates if there is an abnormal hardware or software
condition. Contact technical support. The panel is out of
service when this LED is illuminated or flashing.
Table 4-1 LED Indicator Description
Operation Keys:
A-a: Caps lock key
Space: During programming, change the status of the check boxto and change back to when finished
Backspace: Backspace key
Menu: Press to enter the menu
Help: Help key
PREV/NEXT: Press to skip to the previous/next control screen
-
8/10/2019 FCU-6000 system manual
29/68
ESC: Escape key
Enter: Key to acknowledge input
TAB: Switch key, same as the NEXTkey
: Previous page/next page/ : Previous event/next event
Fixed Function Keys:
Acknowledge: Acknowledge event operation
Signals Silenced:
1. Press for less than 1 second: carries out silencing operation onperipheral equipment
2. Press for longer than 1 second: system exercise (please refer to
relevant topics under loop card setting)
Fire alarm/Pre-alarm:
1. Press for less than 1 second: query fire alarm event
2. Press for longer than 1 second: query pre-alarm event
Trouble/ Horn / Strobe: Carry out query operation during troubleevent
1. Press for less than 1 second: query trouble event
2. Press for longer than 1 second: query horn/strobe event
Supervision/Feedback: Carry out query operation on supervisionevent
1. Press for less than 1 second: query supervision event
2. Press for longer than 1 second: query feedback event
CBE/Delay:
1. Press for less than 1 second: query CBE event information
2. Press for longer than 1 second: query the logic zone in delay status
with a logic value of TRUE
Manual/Automatic: Control manual/automatic execution link
Lamp inspection/Self-test: System lamp inspection/self-test
Reset: Reset system operation
-
8/10/2019 FCU-6000 system manual
30/68
4.1.2Annunciator Control Module LED
Indicators and Keys
Fig. 4-2 Bus Control Module Schematic Diagram
The annunciator control module has a total of 32 indicating lamps, 16 keys and 16
feedback signals.
One composite button: Time function key has 3 functions
1Press for about 1 second: LED lamp below the key will illuminate locking thecontrol key module
2Press for more than 1 second: LED lamp on the right side of the key willilluminate with manual/automatic allowed
3Press for more than 4 seconds: horn/strobe self-test
No. 1-16 Start Keys:
-Press a key and the corresponding feedback signal a (Lamp 1-16) flash, whichmeans corresponding key has been pressed.
-
8/10/2019 FCU-6000 system manual
31/68
-When a feedback indicating lamp (Lamp 1-16) flashes, it indicates that anoperational signal from CBE equipment has been received and the
corresponding CBE equipment will be started.
4.2Power-onConnect 220V AC power, and then turn on the main power supply using the switch
inside the cabinet. Power-on Screen is shown in Fig. 4-4:
Fig.4-3 Power-on Screen
4.3System Self-test
Fig. 4-4 System Self-test Screen
After the N-6000 has been turned on, it will self-test both the hardware and
software of the system. During the self-test all LED indicating lamps on the left
side of the mainframe panel will flash. Once the self-test has finished a buzzer willsound and LEDs will temporarily illuminate after which the panel will return to a
-
8/10/2019 FCU-6000 system manual
32/68
normal operation status. Additionally, the system will show the display screen
while the power supply indicating lamp continues to flash.
After a self-test, the system will show the following screen:
Fig. 4-5 Normal System Screen
The normal system screen is divided into three bars; these include the event
statistics bar, the alarm screen bar and the status bar. The event statistics bar shows
fire alarms, trouble alarms, supervision, CBE and point disabled locations. The
status bar shows the node number, manual/automatic status, transmission
equipment status, main or reserved power supply status, the current date/delay
status of the latest logic zone as well as the current time.
Manual/Automatic Status
System in manual status
System in automatic status
Transmission Equipment Status
Both delivery and feedback
Transmission equipment in delivery status
Transmission equipment in feedback status
Transmission equipment in normal status without delivery or feedback
Transmission equipment in Point disabled status
Transmission equipment in trouble status
Operation Status of the Main or Reserved Power Supply
Main power normal
Low voltage in main power
Trouble in main power
Battery normal
-
8/10/2019 FCU-6000 system manual
33/68
Low voltage in battery
Battery disconnected
Current date/delay status of the latest logic zone, this item can show the current
date. When CBE appears, it will also show delay status information of the latest
logic zone. For example: , where ZL0099 means logic zonenumber 99 and 00001 means that CBE will output after a 1 second delay.
4.4Event Display
Event Order:
First: Fire alarm, CBE, feedback
Second: Supervision
Third: Trouble
Fourth: Point Disabled - disabled
4.4.1Trouble Screen
Fig. 4-6 Trouble Screen
When the control panel detects a failing power supply or other trouble, it will
execute a series of operations:
A trouble relay will be activated and the control panel will alarm
A system trouble indicating lamp on the control panel display will flash and theLCD will show a trouble screen
Detailed trouble type will show the exact geographic location and occurrencetime on the LCD
-
8/10/2019 FCU-6000 system manual
34/68
A trouble event will be saved to the native Flash ROM and the printer will print arecord of the trouble event
Press the key or the key on the main panel to review the previous or
next trouble event and press thekey to page up or down. Press
ACKkey on the main panel to acknowledge, and all trouble events will beshown one by one. Once the alarm has silenced and all trouble events have beenacknowledged, the system trouble indicating lamp on the main panel will return to
its normal illumination.
The most common trouble events include but are not limited to: equipment off-line,
grounding the equipments positive terminal, grounding the equipments negative
terminal, the equipments positive terminal is disconnected, the equipments
negative terminal is disconnected, power supply shows low voltage, power supply
shows high voltage, unmatched load types, low threshold values, database errors.
4.4.2Fire Alarm Screen
Fig. 4-7 Fire Alarm Screen
When a detector or monitoring module is activated (fire alarm detected), the
control panel will execute a series of operations:
A system alarm relay will be activated and the control panel will alarm
A fire alarm indicating lamp on control panel display will flash and the LCD willshow a fire alarm screen.
Detailed fire alarm name will show the exact geographic location and occurrencetime on the LCD.
Alarm information will be saved to the native Flash and the printer will print arecord of the alarm event.
Press thekey or thekey on main panel to review the previous or next
fire alarm event and press thekey to page up or down. Press
the OKkey on main panel to acknowledge, and all fire alarm events will beshown one by one. Once the alarm has silenced and all fire alarm events have been
-
8/10/2019 FCU-6000 system manual
35/68
acknowledged, the system fire alarm indicating lamp on the main panel will return
to its normal illumination.
4.4.3Supervisory Screen
Fig. 4-8 Supervision Screen
The monitoring modules produce monitoring style codes. Once a monitoring
module has been activated, the control panel will execute a series of operations:
A monitoring relay will be activated and the control panel will alarm
A supervision indicating lamp on the control panel will flash and the display willshow the supervision screen
Monitoring information will be saved to the native Flash and the printer will printa record of the supervision event
Press the key or the key on main panel review the previous or next
fire alarm event and press thekey to page up or down. Press
theOKkey on main panel to acknowledge all supervision information has beenshown. Once the alarm has silenced and all the supervision events have been
acknowledged, the supervision indicating lamp on the main panel will return to its
normal illumination.
-
8/10/2019 FCU-6000 system manual
36/68
4.4.4Point Disabled Screen
Fig. 4-9 Point Disabled Screen
When a point disabled location exists in a loop, each disabled point (detector,
module, and loop) will be shown one by one (see Fig. 4-10). The control panel will
execute a series of operations:
A point disabled indicating lamp on the control panel will flash but the controlpanel will not alarm
A point disabled indicating lamp will be illuminated
The point disabled information will be saved to the native Flash and the printerwill print the current point disabled information
Press thekey or thekey on main panel of the control panel to review
the previous or next point disabled event and press the key
to page up or down. Press OK key on main panel of the control panel toacknowledge all Point disabled information has been shown. Once the alarm has
silenced and all point disabled events have been acknowledged, the point disabled
indicating lamp on the main panel will return to its normal illumination.
-
8/10/2019 FCU-6000 system manual
37/68
4.4.5CBE Screen
Fig. 4-10 CBE Screen
4.4.6Pre-alarm Screen
To enter the pre-alarm screen and also query the pre-alarm screen keep pressing the
Fire alarm/Pre-alarmcomposite key on the main panel. The pre-alarm screen isshown below:
Fig. 4-11 Pre-alarm Screen
-
8/10/2019 FCU-6000 system manual
38/68
4.4.7Horn / strobe Screen
To enter the horn/strobe screen and also query the horn/strobe screen keep pressing
the Trouble/Horn/Strobecomposite key on the main panel. The horn/strobe
screen is shown below:
Fig. 4-12 Horn/Strobe Screen
4.4.8Feedback Screen
To enter the supervision/feedback screen and also query the supervision/feedbackscreen keep pressing theSupervision/Feedbackcomposite key on the main panel.The supervision/feedback screen is shown below:
Fig. 4-13 Feedback Screen
-
8/10/2019 FCU-6000 system manual
39/68
Section 5:Programming
5.1Menu
-
8/10/2019 FCU-6000 system manual
40/68
System Management
Device Configuration
CBE Programming
Device Control
History Event
System Setting
Modify Password
Main Reset
LCM
DCU
MCU
Remote Display
General Zone
Logic Zone
Manual Output
Status Track
Walk Test
Power Management
Setting
Auto Programming
Point Programming
Setting
Point Programming
Setting
Point Programming
Setting
Point Programming
Status Track
Download Labels
Menu
Fig. 5-1 N-6000 Schematic Menu Diagram
-
8/10/2019 FCU-6000 system manual
41/68
When programming the control panel or reviewing history events, press the
Menukey to view thefollowing screen:
Fig. 5-2 User Login Screen
Once a user has entered the correct password, he/she will enter the main menu and
view the following screen. In the main menu screen, he/she can update or change
the system management, device configuration, CBE programming, device control
and history events.
Fig. 5-3 Main Menu Screen
5.2System Management
Under System management the operator has 3 options; (1) System setting, (2)
Modify Password, or (3) Main Reset. The system management screen is shown as
follows:
-
8/10/2019 FCU-6000 system manual
42/68
Fig. 5-4 System Management Screen
5.2.1System setting
Under System Setting the following screen will be shown:
Fig. 5-5 System Setting Screen
Line 1: The node is the control panels address within the network while the label is
a description of the control panel
Line 2: If (YES) is selected for the time server option, then this control panel is
the time master within the network and all other panels will synchronous
accordingly. Click the button time & date to set the time and date of the control
panel
Line 3: Languagedetermines the language of the control panel display. At
present two languages are currently available: Chinese and English
Line 4: Backlightthe duration of time the LED display remains lit. There are fourchoices available: Normal Open, Normal Close, Off in 30 Seconds and No Display.
-
8/10/2019 FCU-6000 system manual
43/68
Line 5 to Line 7: Relaysthere are 3 relays each with 7 operational modes:
Disabledthe relay is disabled
Fire alarm outputthe relay will close upon fire alarm
Trouble outputthe relay will close during trouble status
CBEthe relay will close during CBE
Supervisionthe relay will close during supervision
CBE logic outputthe relay will only be used in CBE output expression.When the value of located expression is true, the relay will close and re-open in
the opposite condition
Reset outputthe relay will close during normal operation or when the systemis being reset.
Line 8& Line 9: COM2 serial ports each with 4 operational modes:
Degradation CBE: (YES)/ (NO). The default status (YES) is
Normal Open. Degradation CBE only works when enabled
Fire Alarm Verification: (YES)/ (NO). The default status is (YES).
This function has a time sensitive fire alarm, ensuring an alarmed status will be
accurate. This setting can greatly reduce false alarms and improve system
efficiency
Failover: (YES)/ (NO). The default status is (NO). Failover is the
trouble display switch for the whole control panel. If (YES) is chosen, all
trouble signals will be disabled without any display or alarm although a history
record is still maintainedMain Power Supply: (YES)/ (NO). The default status is (YES),
which installs the main power supply for the control panel
Reserved Power Supply: (YES)/ (NO). The default status is (YES),
which installs the reserved power supply for the control panel
Reset Verification: (YES)/ (NO). The default status is (NO). If
(YES) is chosen, a password needs to be entered before resetting. If (NO) is
chosen, a password does not need to be entered before resetting
5.2.2Password modificationUnder Password modification, a user can modify his/her password according to
their system status (Admin, Engineer, or Guest). The password modification screen
is shown below:
-
8/10/2019 FCU-6000 system manual
44/68
Fig. 5-6 Password Modification Screen
The N-6000 has 3 different user levels, each level is password protected. The three
levels are (ordered from highest to lowest) Administrator, Engineer and User. Each
level has its own password. The Administrator user can modify any password in
the system (including the Administrator level). The User can only operate on the
4th setting, Device Control and the 5th setting, History event. The Engineer
can operate all five settings in the menu but will be interrupted (exit programming)
when an alarm event occurs. The Administrator can operate all five settings in the
menu and will not be interrupted during an alarm event.
Factory default passwords are as follows: 333333 for Administrator, 222222 for
Engineer and 111111 for User.
After the initial login the user will enter the password modification screen. He/she
can change the password by entering a new password in the Enter new password
dialogue box and then re-entering the new password in the Confirm new
password dialogue box. Once the system has confirmed the two passwords are the
same, the user should pressOKto confirm the password change. After the user
has pressed OK the password will be successfully modified, to cancel the
previous operation press the Cancelbutton.
Note: If an incorrect password is entered, the system will show another dialogue
box requesting the correct password be entered.
5.2.3Main Reset
In the System Setting screen choose Main Reset to reset the system to all
default factory settings.
-
8/10/2019 FCU-6000 system manual
45/68
Fig. 5-7 Main Reset Screen
After the correct Administrator password has been entered, a dialogue box will
prompt to verify the Main Reset choice. Press OK to confirm the reset and
restore default factory settings. Press Cancel to cancel the operation and exit the
screen.
5.3Device Configuration
Choose the Device Configuration screen to adjust the settings of the loop cards,
multi-line control modules, annunciator control modules and repeaters. Screen
shown below:
-
8/10/2019 FCU-6000 system manual
46/68
Fig. 5-8 Device Configuration Screen
5.3.1Loop card
In the Device Configuration screen, choose the LCM option to enter the screen
shown below in Fig. 4-23:
Fig. 5-9 Loop Card Screen
5.3.1.1Parameter setting
In the LCM screen, to adjust the settings and program options, choose Setting,
Auto Programming, or Point programming. The screen is shown in Fig. 4-24:
-
8/10/2019 FCU-6000 system manual
47/68
Fig. 5-10 Parameter Setting Screen
Line 1: LCM- Loop number.
Line 2: Name- Loop Description
Line 3: Installation status these include: Uninstalled, Normal, and Disabled.
Line 4: Time Rapid Polling - the number of preferential in-process checks, the
default value is 0. This option controls both the point and card level settings. The
card level setting determines the preferential times while the point level setting
determines whether the point needs the preferential in-process check. The loop
card will carry out preferential in-process checks on the load points where
Preferential in-process check has been activated.
Line 5: Style 4 Wiring - (YES)/ (NO). The system default status is
(YES). Using style 4 wiring the circuit status can be monitored through the
ring circuit line voltage. The system will detect differences between the positive
and negative circuits to monitor if a disconnection trouble within the loop occurs. If
the wiring connection does not use style 4 configuration, the mainframe will report
a disconnection trouble.
Line 6: Local Mode - (YES)/ (NO). If (YES) is selected, the local
CBE setting will be effective within the loop.
Line 7: Silenceable - (YES)/ (NO). This option controls both the point and
card level settings. By programming definition the point level setting is the same asthe card level setting. When (YES) is chosen and a horn/strobe alarm or alarm
bell activates, the user can press Signals Silencedon main panel of the controlpanel to silence the alarmed equipment. If (NO) is selected, the user cannot
silence the alarmed equipment using the Signals Silencedbutton.
Line 8: Address Conflict - (YES)/ (NO). If (YES) is selected, during
inspection the system will search for device address duplications within a loop. If
duplication is found, the panel will show a prompt with further instructions. If
(NO) is chosen, the detector will not report duplicate addresses.
Line 9: L+ Ground Fault Detect - (YES)/ (NO). When (YES) is
selected and a positive end of the loop is grounded, the system will report positive
-
8/10/2019 FCU-6000 system manual
48/68
end grounding trouble. If (NO) is chosen, the system will not report positive
end grounding trouble.
There are three function keys, Sync, Save, and Quit in the status bar. The
Sync button allows the operator to download parameter settings (both card level
and point level settings). The Save button saves the changes that have been
selected. The Quit button allows the user to quit without saving the changes.
5.3.1.2Auto Programming
Fig. 5-1 Automatic Login Screen
Each loop has 3 status options: Installed, Uninstalled, and Disabled. During normalinstallation, the programmer may enter the Auto Programming screen. When
he/she selects a loop number for automatic programming and then presses OK,
the system will verify each device on the selected loop.
Caution: When either a CMX-2 control module or a M500K call point are on
a loop using Auto Programming the control panel will misidentify the CMX-2 as
a CMX-7(C) and misidentify the M500K as an MMX-7. When this happens, the
user should enter 4.5.2.1.3 Point Programming screen (device configuration
LCMpoint programming) to modify the device identity by selecting the proper
equipment type.
-
8/10/2019 FCU-6000 system manual
49/68
Fig. 5-12 Automatic Programming
Upon completion of auto-programming, the quantity, type, and status of each
device on the loop will be automatically shown. This is a convenient time for
system operators to inspect, check, and manage the connected field devices. Press
thekey or thekey to review the address and type of each point installedon the loop. The screen is shown in Fig. 5-13:
Fig. 5-13 Auto Programming
-
8/10/2019 FCU-6000 system manual
50/68
-
8/10/2019 FCU-6000 system manual
51/68
Local Mode: (YES)/ (NO). The factory default setting is (NO). Thisoption controls both the point and card level settings. By programming
definition the point level setting is the same as the card level setting. If the loop
card and mainframe have a communication failure all selected modules
(degradation mode) will automatically output a fire alarm signal.
Silenceable: (YES)/ (NO). When (YES) is chosen and a horn/strobe
alarm or alarm bell activates, the user can press Signals Silencedon mainpanel of the control panel to silence the alarmed equipment. If (NO) is
selected, the user cannot silence the alarmed equipment using the Signals
Silencedbutton.
Switch Inhibited: (YES)/ (NO). When (YES) is chosen manualoutput point operation is inhibited.
Resetable: (YES)/ (NO). When (YES) is selected, the equipmentwill automatically reset all output signals when the system is reset.
Drift Compensation: (YES)/ (NO). When (YES) is selected, thesystem will restrain individual sensors from automatically performing drift
compensation.
Rapid Polling: (YES)/ (NO). When (YES) is selected, the systemwill increase the frequency of in-process inspection on the loop thus increasing
the sensitivity of the equipment.
Alarm Verification: (YES)/ (NO). When (YES) is selected, therewill be an adjustable delay in the alarm period after a preliminary alarm has
registered, allowing time for the alarm to be verified before sending a general
alarm. Should an alarm condition still exist after verification, the panel willthen go into alarm. Verification time is adjustable (in seconds intervals) and
can be customized by using the edit feature on the right side of the alarm
verification label.
5.3.2Annunciator Control Module
In the MCU screen, a programmer can access the Setting and Point
programming options for an annunciator control module.
-
8/10/2019 FCU-6000 system manual
52/68
Fig. 5-15 Annunciator Control Module Screen
5.3.2.1Parameter setting
Fig. 5-16 Parameter setting Screen
Line 1: MCUSelect the MCU number.
Line 2: DescriptionDescribe the selected MCU.
Line 3: Set the current MCU status. These include: Uninstalled, Normal and
Disabled.
Press Save to save the current settings. If the user presses Exit without saving,
the following dialogue box will be prompted. At this time the user can also save the
current settings. The user can also exit the current screen to retain previous settings;
the current settings will not be saved.
5.3.2.2Point Programming
Point Programming of MCU can access to set the relative module address of keys
and feedback led.
-
8/10/2019 FCU-6000 system manual
53/68
Fig. 5-17 Point Programming Screen
5.3.3Remote Display
In the Remote Display screen, a programmer can access the Setting,
Download Label and Point Programming option screens. One N-6000 fire
alarm control panel can have up to 64 remote displays.
Fig. 5-18 Remote Display Screen
-
8/10/2019 FCU-6000 system manual
54/68
5.3.3.1Parameter setting
Fig. 5-19 Parameter setting Screen
Line 1: Remote displayDisplays the remote display number.
Line 2: DescriptionDescribes the selected remote display.
Line 3: Set the current remote display status. These include: Normal, Disabled and
Uninstalled.
Press Save to save the current settings. If the user presses Exit without saving,
the following dialogue box will be prompted. At this time the user can also save the
current settings. The user can also exit the current screen to retain previous settings;
the current settings will not be saved.
5.3.3.2Label Download
Fig. 5-20 Download Label Screen
In the Download Label screen a programmer can view detailed information byselecting the desired floor repeater number and pressing OK. At this time, the
-
8/10/2019 FCU-6000 system manual
55/68
system will download relative content for each point in the selected repeater floor
display. If past events have occurred in the selected equipment points, all
previously downloaded contents will also be shown on the remote display. This
allows field operators to update equipment settings for optimal device function.
5.3.3.3Point Programming
Fig. 5-21 Point Programming Screen
Line 1: Displays the remote display number, point number and installation status.
These include: Uninstalled, Normal, and Disabled.
Line 2: Displays the current remote display point description
Line 3: Point MappingEach remote display can have up to 64 points. Each point
must have a specific zone and loop address. After each point has been mapped,
during an event (fire alarm, trouble, etc) the mapped equipments location and
event will be shown on the relative remote display screen.
Press Save to save the current settings. If the user presses Exit without saving,
the following dialogue box will be prompted. At this time the user can also save the
current settings. The user can also exit the current screen to retain previous settings;
the current settings will not be saved.
5.3.4CBE Programming
In the CBE Programming screen programmers can access both the General
Zone and Logic Zone setting screens.
-
8/10/2019 FCU-6000 system manual
56/68
Fig. 5-22 CBE Programming Screen
5.3.4.1General Zone
Within the General Zone screen a user can select zones 0-499 to review the
relative logic equation of a particular zone. Use the VFT programming software to
modify the logic equations as necessary.
Fig. 5-23 General Zone
5.3.4.2Logic Zone
Within the Logic Zone screen a user can select zones 0-999 to review the relative
equation of a particular zone. Use the VFT programming software equation to
modify the logic equations as necessary.
-
8/10/2019 FCU-6000 system manual
57/68
Fig. 5-24 Logic Zone
5.3.5Device Control
In the Device Control screen a user can access the Point Output, Status
Tracking, Walking Test, Loop Exercise and Power Supply Management
setting screens.
Fig. 5-25 Device Control Screen
-
8/10/2019 FCU-6000 system manual
58/68
5.3.5.1Manual Output
Fig. 5-26 Manual Output Screen
Within the Point Output screen a user can set the loop number, address number,
type of equipment, label and the inspection lamp ON/OFF status. Press the
key or the key to review a points status.
Line 1: Displays the current loop number, address and status. These include:
Uninstalled, Normal and Disabled.
Line 2 & Line 3: Displays the current point description and extended description.
Line 4: Displays the current point alarm type. These include: Fire Alarm,Supervision, Feedback and General Output.
Line 5 & Line 6: Displays the current equipment type and model.
Line 7: Displays the selected output module status. If the user chooses Start and
then presses OK, the point in the current loop will be output by the module; if set
at Close, the point will not be output by the module.
-
8/10/2019 FCU-6000 system manual
59/68
5.3.5.2Status Tracking
Fig. 5-27 Status Tracking Screen
Within the Status Track screen a user can set the loop number, address number,
address type as well as monitor the point.
Line 1: Displays the current loop number, loop address and its status. These include:
Uninstalled, Normal and Disabled.
Line 2 & Line 3: Displays the current point description and extended description.
Line 4: Displays the current point alarm type. These include: Fire Alarm,
Supervision, Feedback and General Output.
Line 5 & Line 6: Display the current equipment type and model.
Line 7: Displays the current point status.
5.3.5.3Walk Test
Fig. 5-28 Walk Test Screen
-
8/10/2019 FCU-6000 system manual
60/68
Within the Walk Test screen a user can set the loop number, address number,
address type as well as run a walking test on a particular loop.
Line 1: Displays the loop number, current address and installation status. These
include: Uninstalled, Normal and Disabled.
Line 2 & Line 3: Displays the current point description and extended description.Line 4: Displays the current point alarm type. These include: Fire Alarm,
Supervision, Feedback and General Output.
Line 5 & Line 6: Displays the current equipment type and model.
After adjusting the systems settings, pressing theLamp inspection/Self-testkeyon main panel will cause the control panel to run a self-test on the current loop.
During this test, both the self-test indicating lamp and the load verification lamp
will be normally illuminated. Press Review the Result to view every address in
the current walk test, the addresses will be displayed on the right hand side of the
walk test interface screen (Fig. 4-50).
Fig. 5-29 Walk Test Address Screen
Press OK to control current point set in the loop.
-
8/10/2019 FCU-6000 system manual
61/68
5.3.5.4Loop Drill
Fig. 5-30 Loop Drill Screen
5.3.5.5Power Supply Management
Fig. 5-31 Power Management Screen
N-6000 fire alarm control panel uses the MPS-350W power supply. Within the
Power Management screen the user can review the current status of each power
supply.
Line 1: Displays the currently connected power supply type. The MPS-350W is the
primary power supply for the N-6000.
Line 2: Displays the current status and voltage of the main power supply.
Line 3: Displays the current status and voltage of the reserved power supply.
Line 4: Press Dischargeto discharge the power supply. Press Stopto stop
discharging. Press Exitto exit the power supply control screen.
-
8/10/2019 FCU-6000 system manual
62/68
5.3.6History Events
Within the History Events screen a user can access the systems history
records/events. This screen is seen below:
Fig. 5-32 History Event Screen
Line 1: Displays the type of history event. History event types include but are not
limited to: fire alarm, trouble, supervision, CBE and Isolation. When All Events
is selected, detailed information will be provided for each event. If All Events is
not selected the user must select a particular event to view the additional and
detailed information.
Line 2: Displays the total number of events that can be reviewed.
Line 3: Displays the status of the current event. The operator may obtain detailed
information about the current event including location, type, time of occurrence,
serial number, as well as additional information from the following text box.
Line 4: Press Exitto exit the history event screen.
Pressing theNEXTkey or thePREVkey on main panel of the control panel,a user can review the detailed description of the next or previous history event.
N-6000 can record and display up to 8000 individual history events.
-
8/10/2019 FCU-6000 system manual
63/68
Section 6:Miscellaneous
6.1Safety Protection Device
The N-6000 has been designed with built-in safety devices to protect both the operator and
control panel in case of improper use and/or installation. These devices include an anti-misplugterminal which can endure extremely high voltage and current ensuring the safety of both
operators as well as the control panel. Additionally the control panel has current limitingprotection for the power supply, protection circuits for communication devices, and special
grounding terminals provided within the cabinet.
6.2Usage and MaintenanceTo ensure consistent and reliable operation the following items should be observed andfollowed:
The control panel must be installed and debugged by qualified technicians
The operator on duty should be familiar with the current building structure as well asunderstand all possible control panel events and operations
An operator should monitor the control panel status to eliminate various trouble signals andprevent alarm signals when possible
If a power failure exceeds 8 hours, the reserve power supply should be disconnected to avoid
damage due to over-dischargeIf additional construction is performed in the protected building, shut down the control panel
to ensure fire detection capabilities are not compromised
During any status other than operation (transportation, storage, etc), the reserve power supplyshould be disconnected from the control panel
6.3Common Troubles
The N-6000 has advanced features such as self-diagnosis and self-protection; however even
with the advanced technology an occasional trouble signal is unavoidable. Table 5-1 has
additional information regarding common troubles.
Trouble Cause analysis Solution
Poor AC220V connectionRe-connect the AC220V
power supplyMain power supply
trouble Fuse blowing out due to external
short circuit or over-currentReplace the fuse
Poor plug connection Check connectorsReserved power
supply trouble
Reserved power supply damagedReplace reserved power
supply
-
8/10/2019 FCU-6000 system manual
64/68
Trouble Cause analysis Solution
Fuse blowing out due to external
short circuit or over-currentReplace the fuse
Poor connection between LCD and
display module cardCheck connectors
Failure to regulate the luminance Regulate the luminanceLCD display fails
Backlight socket connected
improperly
Disconnect and plug the
socket in again
Keypad failsSoft panel socket block connected
improperly
Disconnect and plug the
socket in again
No soundLoudspeaker socket connected
improperly
Disconnect and plug the
socket in again
Short circuit in loop bus Clear short circuit
Short circuit in loop Reverse connection of addressing
unit
Check connection of the
addressing unit
Inaccurate clockClock chip M410T socket
connected improperly or damagedReplace clock chip M410T
Table 5-1 Common Troubles
For additional trouble not found in Table 5-1 please contact the dealer or manufacturer directly.
6.4Transportation & StorageAfter a post-factory inspection, the control panel can be stored. During storage the control
panel must be stored under normal atmospheric condition, ambient temperature and in a dryroom for a maximum of 6-months. During transportation the control panel must be kept
right-side up and protected from heavy overhead weight. The control panel can be transportedby train, truck, plane or ship.
Once the control panel has been opened, the user must use the control panel in accordance withthis manual. When used in conjunction with this manual all operation results will meet the
performance and functional requirements defined by this manual.
6.5Out-of-box Audit
When opening the control panel box for the first time the user should carry out an out-of-boxaudit to ensure the control panel is complete, untouched and undamaged from transportation.
The control panel should include: a CPU, loop card, MCU, POM-8A, MPS-350W,complement keys and connecting wires, etc.
Open the control panel door to ensure all internal connections are normal and that there are noloose connections, short circuits and/or disconnected items. Check the power supply status to
ensure it is normal and does not have any short circuits, etc.
-
8/10/2019 FCU-6000 system manual
65/68
Appendix A
Alarm level cross-reference table for the ND682 photoelectric smoke detector:
Alarm level setting
Actual physical threshold range of
alarm
(Unit: 0.1 OBS%/FT)
LEVEL 1 0 -2.5
LEVEL 2 2.5 5
LEVEL 3 5 - 7.5
LEVEL 4 7.5 10
LEVEL 5 10 -14
LEVEL 6 14 16
LEVEL 7 16 -18
LEVEL 8 18 20
LEVEL 9 over 20
LEVEL 10 Over 20
Table 1: Alarm level cross-reference table for the ND682
Alarm level cross-reference table for the ND685 heat detector:
Alarm level setting
Actual physical threshold range ofalarm
(Unit C)
LEVEL 1 30 34
LEVEL 2 34 37
LEVEL 3 37 40
LEVEL 4 40 45
LEVEL 5 45 50
LEVEL 6 50 55
LEVEL 7 55 60
LEVEL 8 60 65
LEVEL 9 Over 65
LEVEL 10 Over 65
Table 2: Alarm level cross-reference table for the ND685
Alarm level cross-reference table for the FSL-751 detector:
Alarm level setting Actual physical threshold range of
-
8/10/2019 FCU-6000 system manual
66/68
alarm
(Unit: 0.01%/ft)
LEVEL 1 0 2
LEVEL 2 2 3
LEVEL 3 3 10
LEVEL 4 10 50
LEVEL 5 50 100
LEVEL 6 100 150
LEVEL 7 150 200
Table 3: Alarm level cross-reference table for FSL-751
The following is the trouble level cross-reference table for drift compensation:
Alarm level settingPhysical value of drift compensation
(Unit: 0.01%/ft)
LEVEL 1Warning 30
LEVEL 2Warning 60
LEVEL 3Trouble 90
Table 4: Alarm level cross-reference table for FSL-751
-
8/10/2019 FCU-6000 system manual
67/68
Limited Warranty
NOTIFIERwarrants its products to be free from defects in materials and
workmanship for eighteen (18) months from the date of manufacture, undernormal use and service. Products are date stamped at time of manufacture.The sole and exclusive obligation ofNOTIFIERis to repair or replace, at its
option, free of charge for parts and labor, any part which is defective inmaterials or workmanship under normal use and service. For products notunder NOTIFIERmanufacturing datestamp control, the warranty is eighteen
(18) months from date of original purchase byNOTIFIER 's distributor
unless the installation instructions or catalog sets forth a shorter period, inwhich case the shorter period shall apply. This warranty is void if the productis altered, repaired or serviced by anyone other than NOTIFIERor its
authorized distributors or if there is a failure to maintain the products andsystems in which they operate in a proper and workable manner. In case ofdefect, secure a Return Material Authorization form from our customerservice department. Return product, transportation prepaid, toNOTIFIER, 12
Clintonville Road, Northford, Connecticut 06472-1653.
This writing constitutes the only warranty made by NOTIFIERwith respect toits products. NOTIFIERdoes not represent that its products will prevent any
loss by fire or otherwise, or that its products will in all cases provide theprotection for which they are installed or intended. Buyer acknowledges thatNOTIFIER
is not an insurer and assumes no risk for loss or damages or the
cost of any inconvenience,transportation, damage, misuse, abuse, accident or similar incident.
NOTIFIERGIVES NO WARRANTY, EXPRESSED OR IMPLIED, OF
MERCHANTABILITY, FITNESS FOR ANY PARTICULAR PURPOSE, OROTHERWISE WHICH EXTEND BEYOND THE DESCRIPTION ON THEFACE HEREOF. UNDER NO CIRCUMSTANCES SHALL NOTIFIERBE
LIABLE FOR ANY LOSS OF OR DAMAGE TO PROPERTY, DIRECT,INCIDENTAL OR CONSEQUENTIAL, ARISING OUT OF THE USE OF, ORINABILITY TO USE NOTIFIERPRODUCTS. FURTHERMORE, NOTIFIER
SHALL NOT BE LIABLE FOR ANY PERSONAL INJURY OR DEATH WHICHMAY ARISE IN THE COURSE OF, OR AS A RESULT OF, PERSONAL,COMMERCIAL OR INDUSTRIAL USE OF ITS PRODUCTS.
This warranty replaces all previous warranties and is the only warranty madeby NOTIFIER. No increase or alteration, written or verbal, of the obligation of
this warranty is authorized.
"NOTIFIER" is a registered trademark.
-
8/10/2019 FCU-6000 system manual
68/68