Page 1: February, March and April 2018 Julie Sievers Iowa DNR ... · Nitrification –The Good, the Bad, and the Ugly ... the breakpoint side of the curve ... Liquid Chlorine Dosage, mg/L

February, March and April 2018Julie Sievers

Iowa DNR Field Office 3

Page 2: February, March and April 2018 Julie Sievers Iowa DNR ... · Nitrification –The Good, the Bad, and the Ugly ... the breakpoint side of the curve ... Liquid Chlorine Dosage, mg/L

Available on the IRWA website

Go to www.iowaruralwater.org/

Then Resources

Then Downloads

You will find the presentation there

Page 3: February, March and April 2018 Julie Sievers Iowa DNR ... · Nitrification –The Good, the Bad, and the Ugly ... the breakpoint side of the curve ... Liquid Chlorine Dosage, mg/L

Introductions

Chlorine Chemistry, Ammonia Sources and Impact

Nitrification – The Good, the Bad, and the Ugly

Testing, Indicators, and Specific Examples

Flint Lead Event

Roundtable Discussion

Page 4: February, March and April 2018 Julie Sievers Iowa DNR ... · Nitrification –The Good, the Bad, and the Ugly ... the breakpoint side of the curve ... Liquid Chlorine Dosage, mg/L

Monochloramine, NH2Cl

Dichloramine, NHCl2 Combined Chlorine

Trichloramine, NCl3 Free Chlorine, OCl- (hypochlorite) or HOCl

(hypochlorous acid) – dependent on pH

Free Chlorine = Free Available Chlorine

Total Chlorine = Free + Combined

Chlorine Residual = Dose - Demand

Do you know which are present in your system?

Page 5: February, March and April 2018 Julie Sievers Iowa DNR ... · Nitrification –The Good, the Bad, and the Ugly ... the breakpoint side of the curve ... Liquid Chlorine Dosage, mg/L

Ammonia, NH3 or Ammonium ion, NH4

◦ In neutral or acidic natural waters, ammonia is present as ammonium ion

Nitrite, NO2

Nitrate, NO3

Kjeldahl Nitrogen, TKN◦ TKN = Organic nitrogen + ammonia

For systems adding ammonia◦ Ammonium sulfate (LAS), ammonium hydroxide, or

others

Page 6: February, March and April 2018 Julie Sievers Iowa DNR ... · Nitrification –The Good, the Bad, and the Ugly ... the breakpoint side of the curve ... Liquid Chlorine Dosage, mg/L

Naturally occurring in Iowa

When the nitrogen present in the well is ammonia it is not from surface source◦ Surface source is converted to nitrate before reaches

aquifer = nitrate in well, not ammonia

Ammonia is from the mineralization of organic material present from when aquifer was formed◦ Mineralization of organic matter to ammonium by

microorganisms in presence of organic carbon sources in an anaerobic (without oxygen) environment

◦ Most of Iowa was shallow seas

Found in all aquifers

Page 7: February, March and April 2018 Julie Sievers Iowa DNR ... · Nitrification –The Good, the Bad, and the Ugly ... the breakpoint side of the curve ... Liquid Chlorine Dosage, mg/L

Levels of 1 to 5 mg/L common◦ DNR/UHL study

◦ GSB data

◦ USGS data

◦ Ambient water quality data

◦ DNR 2013 study

◦ Raw water monitoring

Levels as high as 11 mg/L

Ammonia is NOT regulated in Iowa in drinking water

Ammonia Molecule3 hydrogen and 1 nitrogen atoms

Page 8: February, March and April 2018 Julie Sievers Iowa DNR ... · Nitrification –The Good, the Bad, and the Ugly ... the breakpoint side of the curve ... Liquid Chlorine Dosage, mg/L

Ammonia has a huge chlorine demand (10 – 12 mg/L of chlorine per 1 mg/L of ammonia)

Need to know what form of disinfectant you are using◦ Must meet minimum levels to protect public health

Taste and odor issues

Nitrification

Disinfection byproducts violations or issues◦ TTHM/HAA5 for free chlorine; Nitrosamines for chloramines

Water quality impacts

Do you know the ammonia level in your system?

Page 9: February, March and April 2018 Julie Sievers Iowa DNR ... · Nitrification –The Good, the Bad, and the Ugly ... the breakpoint side of the curve ... Liquid Chlorine Dosage, mg/L

From Bob Spon, OpFlow Article, June 2008

Page 10: February, March and April 2018 Julie Sievers Iowa DNR ... · Nitrification –The Good, the Bad, and the Ugly ... the breakpoint side of the curve ... Liquid Chlorine Dosage, mg/L

Chlorine typically added as gas chlorine or sodium hypochlorite (liquid chlorine)

Disassociates based on pH (and temperature)

Chlorine Hypochlorous Acid Hypochlorite Ion

Page 11: February, March and April 2018 Julie Sievers Iowa DNR ... · Nitrification –The Good, the Bad, and the Ugly ... the breakpoint side of the curve ... Liquid Chlorine Dosage, mg/L

Monochloramine Dichloramine TrichloramineAKA Nitrogen trichloride

If you add ammonia or have it present in the raw water, these reactions occur:

Formation is dependent on the pH and chlorine to ammonia ratio

Page 12: February, March and April 2018 Julie Sievers Iowa DNR ... · Nitrification –The Good, the Bad, and the Ugly ... the breakpoint side of the curve ... Liquid Chlorine Dosage, mg/L

There are competing reactions

Cl2 + H2O → HOCl + Cl- + H+

NH2Cl + HOCl → NHCl2 + H2O

NHCl2 + HOCl → NCl3 + H2O

NH3 + HOCl → NH2Cl + H2O

NaOCl + H2O → HOCl + NaOH Liquid chlorine

Gas chlorine

Monochloramine

Dichloramine

Trichloramine

Page 13: February, March and April 2018 Julie Sievers Iowa DNR ... · Nitrification –The Good, the Bad, and the Ugly ... the breakpoint side of the curve ... Liquid Chlorine Dosage, mg/L

For typical, traditional chloramination, the system adds chlorine and ammonia◦ The system can control both chlorine feed rate and

ammonia feed rate

◦ Typically, chlorine is added first, then ammonia

In systems with naturally occurring ammonia, chloraminating due to ammonia in source water◦ System can control chlorine feed rate BUT have no to

limited ability to change or control ammonia level

Do you have ammonia in your raw water?

Do you add ammonia?

Page 14: February, March and April 2018 Julie Sievers Iowa DNR ... · Nitrification –The Good, the Bad, and the Ugly ... the breakpoint side of the curve ... Liquid Chlorine Dosage, mg/L

Ammonia reacts with chlorine to form monochloramine, dichloramine, and trichloramine

Formation is dependent on the pH and chlorine to ammonia ratio

Monochloramine, dichloramine, and trichloramine are measured as a part of the total chlorine residual and are weak disinfectants

Trichloramine = Nitrogen trichloride

Page 15: February, March and April 2018 Julie Sievers Iowa DNR ... · Nitrification –The Good, the Bad, and the Ugly ... the breakpoint side of the curve ... Liquid Chlorine Dosage, mg/L

Monochloramine and dichloramine exist together at pH of 6.5 to 7.5◦ Chlorine to ammonia ratio determine which is formed

Dichloramine and trichloramine cause taste and odor problems

Small amounts of trichloramine (nitrogen trichloride) may exist past the breakpoint and may also cause taste and odor problems

Page 16: February, March and April 2018 Julie Sievers Iowa DNR ... · Nitrification –The Good, the Bad, and the Ugly ... the breakpoint side of the curve ... Liquid Chlorine Dosage, mg/L

From Bob Spon, OpFlow Article, June 2008

Page 17: February, March and April 2018 Julie Sievers Iowa DNR ... · Nitrification –The Good, the Bad, and the Ugly ... the breakpoint side of the curve ... Liquid Chlorine Dosage, mg/L

Ammonia results from a certified lab are for total ammonia

Free ammonia testing must be done immediately and is done on-site◦ Free ammonia and monochloramine are measured as a two

step test

Total chlorine = free + combined

Combined chlorine = monochloramine + dichloramine + trichloramine

Free chlorine in the presence of chloramines is “false” free

Page 18: February, March and April 2018 Julie Sievers Iowa DNR ... · Nitrification –The Good, the Bad, and the Ugly ... the breakpoint side of the curve ... Liquid Chlorine Dosage, mg/L

Minimum levels dependent on where you are at on the curve◦ Levels throughout the distribution system

Minimum of 0.3 mg/L free chlorine residual if on the breakpoint side of the curve

Minimum of 1.5 mg/L total chlorine residual if chloraminating

Maximum of 4.0 mg/L total chlorine◦ Based on Running Annual Average (RAA) = MRDL

Page 19: February, March and April 2018 Julie Sievers Iowa DNR ... · Nitrification –The Good, the Bad, and the Ugly ... the breakpoint side of the curve ... Liquid Chlorine Dosage, mg/L

From Bob Spon, OpFlow Article, June 2008

Minimum = 1.5 mg/L total chlorine Min = 0.3 mg/L free

Page 20: February, March and April 2018 Julie Sievers Iowa DNR ... · Nitrification –The Good, the Bad, and the Ugly ... the breakpoint side of the curve ... Liquid Chlorine Dosage, mg/L

Determine where you are at on the curve

Measure free chlorine immediately and at 30 second intervals to 2 minutes after adding reagent◦ Are the readings stable or do the readings increase?

◦ If the free residual increases more than 0.1 mg/L, you are on the chloramine side of the curve & do NOT have free chlorine.

This is often referred to as “false” free

Measure total chlorine residual◦ Rule of thumb is if the free residual is stable and about

80% of total, you are on the breakpoint side and have “true” free residual

Page 21: February, March and April 2018 Julie Sievers Iowa DNR ... · Nitrification –The Good, the Bad, and the Ugly ... the breakpoint side of the curve ... Liquid Chlorine Dosage, mg/L

“False” Free Chlorine Residuals

Zero Immediately = 0.08 30 seconds = 0.20

60 seconds = 0.36 90 seconds = 0.52 120 seconds= 0.76

All in mg/L

The rate of interference is dependent upon:• the

concentration of the chloramine

• the chloramine compound present

• and the sample temperature

Page 22: February, March and April 2018 Julie Sievers Iowa DNR ... · Nitrification –The Good, the Bad, and the Ugly ... the breakpoint side of the curve ... Liquid Chlorine Dosage, mg/L

Courtesy of Hach disinfection serieshttp://www.hach.com/DisinfectionSeries06

Where are You on the BP Curve?

Test Results = 3.0 mg/L total chlorine

Page 23: February, March and April 2018 Julie Sievers Iowa DNR ... · Nitrification –The Good, the Bad, and the Ugly ... the breakpoint side of the curve ... Liquid Chlorine Dosage, mg/L

From Bob Spon, OpFlow Article, June 2008

What else do you need to know?

Page 24: February, March and April 2018 Julie Sievers Iowa DNR ... · Nitrification –The Good, the Bad, and the Ugly ... the breakpoint side of the curve ... Liquid Chlorine Dosage, mg/L

What do we need to measure?

Where is the best spot to test for it?

What results are we looking for?

What do we do if we don’t get them?

Page 25: February, March and April 2018 Julie Sievers Iowa DNR ... · Nitrification –The Good, the Bad, and the Ugly ... the breakpoint side of the curve ... Liquid Chlorine Dosage, mg/L

All Systems: Free chlorine residual◦ Determine if true or false free

Total chlorine residual Chlorine dosage Total ammonia◦ In systems with naturally-occurring ammonia, to measure raw

water fluctuations ◦ Seasonal changes◦ Water levels◦ Usage, pumping rates◦ Well rotation

If no total ammonia but indications, test TKN

Page 26: February, March and April 2018 Julie Sievers Iowa DNR ... · Nitrification –The Good, the Bad, and the Ugly ... the breakpoint side of the curve ... Liquid Chlorine Dosage, mg/L

Chloraminating Systems:

Free Ammonia◦ To determine location on the curve

Monochloramine ◦ This is the target disinfectant for chloraminating systems◦ Total residual = Monochloramine ◦ In systems that add ammonia, you can achieve this

Nitrite and nitrate ◦ Important to determine if nitrification is occurring◦ Measure nitrite and nitrate separately◦ More on this later, including locations where to measure

For systems adding ammonia, measure free chlorine prior to ammonia addition to determine how much ammonia to add

Page 27: February, March and April 2018 Julie Sievers Iowa DNR ... · Nitrification –The Good, the Bad, and the Ugly ... the breakpoint side of the curve ... Liquid Chlorine Dosage, mg/L

Courtesy of Hach disinfection serieshttp://www.hach.com/DisinfectionSeries06

Testing Along the Curve

Assume a 1 mg/L ammonia-N dose

Page 28: February, March and April 2018 Julie Sievers Iowa DNR ... · Nitrification –The Good, the Bad, and the Ugly ... the breakpoint side of the curve ... Liquid Chlorine Dosage, mg/L

Dependent on system and location of chlorine addition

Always measure at the SEP

Always measure in the distribution system◦ Important to know residuals and levels at different water age

locations

May need to measure at specific treatment processes◦ More on this later

Page 29: February, March and April 2018 Julie Sievers Iowa DNR ... · Nitrification –The Good, the Bad, and the Ugly ... the breakpoint side of the curve ... Liquid Chlorine Dosage, mg/L

For chloraminating systems: The key is the chlorine to ammonia ratio◦ In systems that add ammonia, chlorine typically is added first,

then ammonia Free chlorine residual (not dose)

Ammonia dose

◦ In systems with natural ammonia, minimizing free ammonia as much as possible

◦ Chlorine dose – target is monochloramine

Other factors◦ pH◦ Temperature

Minimum total residual of 1.5 mg/L◦ If can show consistent treatment, may not be required to

measure free chlorine (false) – discuss with DNR FO

Page 30: February, March and April 2018 Julie Sievers Iowa DNR ... · Nitrification –The Good, the Bad, and the Ugly ... the breakpoint side of the curve ... Liquid Chlorine Dosage, mg/L

Systems that add ammonia can control the dosage of chlorine and ammonia

Measure Free Chlorine before ammonia addition◦ Target Monochloramine (NH2Cl) level

After ammonia addition:

Free Ammonia 0.04 – 0.1 mg/L

Monochloramine (NH2Cl) at the target

Total Chlorine = Monochloramine (NH2Cl)

Page 31: February, March and April 2018 Julie Sievers Iowa DNR ... · Nitrification –The Good, the Bad, and the Ugly ... the breakpoint side of the curve ... Liquid Chlorine Dosage, mg/L

Know your raw water ammonia levels◦ If you blend or rotate wells, do this is a way to get the most

consistent ammonia levels possible OR

◦ May need to have different chlorine dosages for different wells or combination of wells

Goal is to either chloraminate or use free chlorine –NO yo-yoing back and forth

Determine target chlorine residuals based on your system and work to meet them

Consistent chlorine residuals throughout the distribution system

Page 32: February, March and April 2018 Julie Sievers Iowa DNR ... · Nitrification –The Good, the Bad, and the Ugly ... the breakpoint side of the curve ... Liquid Chlorine Dosage, mg/L

For free chlorine systems:

The key is to always stay on the free chlorine side of the curve (past breakpoint)

Free chlorine residuals are stable

Free chlorine residuals within 80% of the total residuals throughout the system

Minimum free residual of 0.3 mg/L throughout the distribution system

Page 33: February, March and April 2018 Julie Sievers Iowa DNR ... · Nitrification –The Good, the Bad, and the Ugly ... the breakpoint side of the curve ... Liquid Chlorine Dosage, mg/L

Courtesy of Hach disinfection serieshttp://www.hach.com/DisinfectionSeries06

I Am Here!

NH2Cl = TCF NH3N > 0

NH2Cl < TCF NH3N = 0

NH2Cl = 0F NH3N = 0FC = stableFC=80% TC

TC = Total ChlorineF NH3N = Free Ammonia

Page 34: February, March and April 2018 Julie Sievers Iowa DNR ... · Nitrification –The Good, the Bad, and the Ugly ... the breakpoint side of the curve ... Liquid Chlorine Dosage, mg/L

Chloramination

Monochloramine is equal to Total Chlorine

Free Ammonia of 0.04 to 0.10 mg/L

Minimum of 1.5 mg/L total chlorine residual throughout the distribution system

Free Chlorine

No remaining ammonia True free chlorine

residual (reading does not increase)

Free chlorine is at least 80% of total ◦ Optimal is > 85%

Minimum of 0.3 mg/L free chlorine residual throughout the distribution system

Page 35: February, March and April 2018 Julie Sievers Iowa DNR ... · Nitrification –The Good, the Bad, and the Ugly ... the breakpoint side of the curve ... Liquid Chlorine Dosage, mg/L
Page 36: February, March and April 2018 Julie Sievers Iowa DNR ... · Nitrification –The Good, the Bad, and the Ugly ... the breakpoint side of the curve ... Liquid Chlorine Dosage, mg/L

Factors to consider:

Change in chlorine levels◦ What are the two reasons why chlorine residuals change?

Remember: Residual = Dose - Demand

Page 37: February, March and April 2018 Julie Sievers Iowa DNR ... · Nitrification –The Good, the Bad, and the Ugly ... the breakpoint side of the curve ... Liquid Chlorine Dosage, mg/L

Factors to consider: Dose

Calculate the chlorine dose, has it changed, if so, why?

Chlorine Gas Dosage, mg/L = Chlorine Used, lbs/day__ (Flow, MGD) (8.34 lbs/gal)

Liquid Chlorine Dosage, mg/L = (lbs of chlorine) (% available chlorine as decimal)

(Flow, MGD) (8.34 lbs/gal) OR Liquid Chlorine Dosage, mg/L = (gallons of chlorine) (% available chlorine as decimal)

(MGD)

Page 38: February, March and April 2018 Julie Sievers Iowa DNR ... · Nitrification –The Good, the Bad, and the Ugly ... the breakpoint side of the curve ... Liquid Chlorine Dosage, mg/L

Factors to consider: Demand Change in ammonia levels◦ Have the ammonia levels changed?

Changes in chlorine residuals after regeneration of softeners◦ Often see residuals change due to formation of chloramines rather

than free chlorine

Decrease in the chlorine residuals or areas where the minimum levels cannot be maintained◦ Nitrification or the bacterial conversion of ammonia to nitrite to

nitrate◦ Chloramine decay in distribution, especially in low use and dead

end areas

Others

Page 39: February, March and April 2018 Julie Sievers Iowa DNR ... · Nitrification –The Good, the Bad, and the Ugly ... the breakpoint side of the curve ... Liquid Chlorine Dosage, mg/L

Changes in other chlorine demand

Water Quality Parameter

Free Chlorine Demand

Multiplier x (Factor)

Iron 0.64 mg/L

Manganese 1.3

Hydrogen Sulfide 0.2 - 2.5

Nitrite (as N) 5

Ammonia (as N) 10 to 12

Organic Nitrogen 1

TOC 0.1

Page 40: February, March and April 2018 Julie Sievers Iowa DNR ... · Nitrification –The Good, the Bad, and the Ugly ... the breakpoint side of the curve ... Liquid Chlorine Dosage, mg/L

Example of changes in chlorine demand due to ammonia

Water Quality

Parameter

Free Chlorine

Demand Multiplier

x (Factor)

Input Water

Quality

Demand per

Parameter

Input Water

Quality

Demand per

Parameter

Iron 0.64 mg/L 1.2 0.768 1.2 0.768

Manganese 1.3 0.24 0.312 0.24 0.312

Hydrogen Sulfide 0.2 0 0 0 0

Nitrite (as N) 5 0 0 0 0

Ammonia (as N) 10 to 12 2 24 2.5 30

Organic Nitrogen 1 0 0 0 0

TOC 0.1 0 0 0 0

TOTAL Chlorine Demand 25.08 31.08

Page 41: February, March and April 2018 Julie Sievers Iowa DNR ... · Nitrification –The Good, the Bad, and the Ugly ... the breakpoint side of the curve ... Liquid Chlorine Dosage, mg/L

Example of changes in chlorine demand due to iron &manganese

Water Quality

Parameter

Free Chlorine

Demand Multiplier

x (Factor)

Input Water

Quality

Demand per

Parameter

Input Water

Quality

Demand per

Parameter

Iron 0.64 mg/L 1.2 0.768 1.8 1.152

Manganese 1.3 0.24 0.312 0.34 0.442

Hydrogen Sulfide 0.2 0 0 0 0

Nitrite (as N) 5 0 0 0 0

Ammonia (as N) 10 to 12 2 24 2 24

Organic Nitrogen 1 0 0 0 0

TOC 0.1 0 0 0 0

TOTAL Chlorine Demand 25.08 25.594

Page 42: February, March and April 2018 Julie Sievers Iowa DNR ... · Nitrification –The Good, the Bad, and the Ugly ... the breakpoint side of the curve ... Liquid Chlorine Dosage, mg/L

Free chlorine residuals are higher than total residuals False free Reaction not complete◦ Consider chemical feed location to sample tap location

Using same sample vials◦ Dedicated sample vial for free chlorine◦ Another dedicated sample vial for total chlorine◦ Zero each before analysis

Alkalinity and pH interference◦ According to Hach: After adding the DPD reagent, the sample pH

should measure 6.3 Samples with pH of 7.6 or above and alkalinity of 250 or above may not have pH of 6.3 after adding the reagent, causing small bubbles to form which increases the reading. After 1 minute the free residual will decrease as the bubbles dissipate.

Page 43: February, March and April 2018 Julie Sievers Iowa DNR ... · Nitrification –The Good, the Bad, and the Ugly ... the breakpoint side of the curve ... Liquid Chlorine Dosage, mg/L

• NH2Cl too high• Reduce NH3

• Reduce Cl2

• TC dropped after

NH3 addition• Increase NH3

• Reduce Cl2

• FAA too high• Reduce NH3

• Increase Cl2

• TC > NH2Cl• Reduce Cl2

IT’S A BALANCING ACT

Page 44: February, March and April 2018 Julie Sievers Iowa DNR ... · Nitrification –The Good, the Bad, and the Ugly ... the breakpoint side of the curve ... Liquid Chlorine Dosage, mg/L

From Bob Spon, OpFlow Article, June 2008

Page 45: February, March and April 2018 Julie Sievers Iowa DNR ... · Nitrification –The Good, the Bad, and the Ugly ... the breakpoint side of the curve ... Liquid Chlorine Dosage, mg/L

Drop in total chlorine residuals in storage and distribution

Free ammonia can convert to nitrite and nitrate

Taste and odor issues if form di or trichloramines

Page 46: February, March and April 2018 Julie Sievers Iowa DNR ... · Nitrification –The Good, the Bad, and the Ugly ... the breakpoint side of the curve ... Liquid Chlorine Dosage, mg/L

Hypochlorous Acid 20 mg/L

Monochloramine 5 mg/L

Dichloramine 0.8 mg/L

Trichloramine 0.02 mg/L

Typically “swimming pool” or other “chemical” or “chlorine” type smell

“Burning” of eyes, particularly in shower or other hot water uses

Page 47: February, March and April 2018 Julie Sievers Iowa DNR ... · Nitrification –The Good, the Bad, and the Ugly ... the breakpoint side of the curve ... Liquid Chlorine Dosage, mg/L

Break Time…

Then on to nitrification…

Page 48: February, March and April 2018 Julie Sievers Iowa DNR ... · Nitrification –The Good, the Bad, and the Ugly ... the breakpoint side of the curve ... Liquid Chlorine Dosage, mg/L

Ammonia, NH3

Ammonium ion, NH4

◦ In neutral or acidic natural waters, ammonia is present as ammonium ion

Nitrite, NO2

Nitrate, NO3

Kjeldahl Nitrogen, TKN◦ TKN = Organic nitrogen + ammonia

Page 50: February, March and April 2018 Julie Sievers Iowa DNR ... · Nitrification –The Good, the Bad, and the Ugly ... the breakpoint side of the curve ... Liquid Chlorine Dosage, mg/L
Page 51: February, March and April 2018 Julie Sievers Iowa DNR ... · Nitrification –The Good, the Bad, and the Ugly ... the breakpoint side of the curve ... Liquid Chlorine Dosage, mg/L

Ammonia

in Well

Treatment

Plant Ammonia,

Nitrite or

Nitrate

depending on

conditions

Nitrosomas and Nitrobacter

Storage and

Distribution Ammonia,

Nitrite or Nitrate

depending on

conditions

Page 52: February, March and April 2018 Julie Sievers Iowa DNR ... · Nitrification –The Good, the Bad, and the Ugly ... the breakpoint side of the curve ... Liquid Chlorine Dosage, mg/L

Can be a result of surface activities or contamination◦ When you find nitrite or nitrate in raw water samples

(directly from well) indicates it is a result of surface activity

Can be a result of bacterial nitrification of ammonia within the water system◦ Often find ammonia, nitrite and nitrate present in the

same SEP or system sample if nitrification is incomplete

Page 53: February, March and April 2018 Julie Sievers Iowa DNR ... · Nitrification –The Good, the Bad, and the Ugly ... the breakpoint side of the curve ... Liquid Chlorine Dosage, mg/L

Result of contamination from surface activities◦ When found in raw water samples (directly from well) indicates

close source of contamination or recent contamination

Result of bacterial nitrification of free ammonia◦ Conversion within transmission line, treatment plant, storage or

distribution system◦ Up to one nitrite formed for each ammonia

1 mg/L of ammonia can form 1 mg/L of nitrite

MCL in drinking water of 1.0 mg/L - ACUTE health concern

SDWA requirement is “one time only” sampling at SEP

Iowa DNR protocol implementation includes SEP and distribution system monitoring – more on these later

Page 54: February, March and April 2018 Julie Sievers Iowa DNR ... · Nitrification –The Good, the Bad, and the Ugly ... the breakpoint side of the curve ... Liquid Chlorine Dosage, mg/L

Result of contamination from surface activity◦ Find nitrate in raw water samples

Result of bacterial nitrification of nitrite

MCL of 10 mg/L - ACUTE health concern

Often find present with ammonia and nitrite if nitrification is incomplete

Up to one nitrate can be formed from each nitrite

Sampling at SEP:◦ 1/year

◦ 1/quarter if >5.0 mg/L <10

◦ 1/month if > 10

Page 55: February, March and April 2018 Julie Sievers Iowa DNR ... · Nitrification –The Good, the Bad, and the Ugly ... the breakpoint side of the curve ... Liquid Chlorine Dosage, mg/L

Health concerns the same for each but at different levels, both are ACUTE contaminants◦ Nitrite = 1.0 mg/L

◦ Nitrate = 10 mg/L

Blue baby syndrome◦ Difficult to identify

Failure to thrive

Many times appears to be formula intolerance◦ Change to premade formula and symptoms disappear

Some links to bladder and other cancers

Page 56: February, March and April 2018 Julie Sievers Iowa DNR ... · Nitrification –The Good, the Bad, and the Ugly ... the breakpoint side of the curve ... Liquid Chlorine Dosage, mg/L

Nitrosomonas convert ammonia to nitrite

Nitrobacter convert nitrite to nitrate

Present in treatment plants◦ Aerators, detention tanks, filters

Present in transmission lines, storage and distribution systems◦ Biofilm

Common in soil and environment

Not detected as part of total coliform test

Not always detected as part of HPC (heterotrophic or other total plate count)

Page 57: February, March and April 2018 Julie Sievers Iowa DNR ... · Nitrification –The Good, the Bad, and the Ugly ... the breakpoint side of the curve ... Liquid Chlorine Dosage, mg/L

Nitrosomonas◦ Convert ammonia to nitrite◦ Resistant to chloramines◦ Less sensitive to chlorine◦ If established, can protect themselves in presence of high

chlorine residuals

Nitrobacter◦ Very sensitive to ammonia

Any ammonia not consumed by Nitrosomonas will inhibit Nitrobacter

◦ Very sensitive to chlorine and chloramines Will be dormant (hibernate) in presence of chlorine or

chloramines, usually will not be killed except at high levels

◦ Thrive in narrow pH range – 7.6 to 7.8

Page 58: February, March and April 2018 Julie Sievers Iowa DNR ... · Nitrification –The Good, the Bad, and the Ugly ... the breakpoint side of the curve ... Liquid Chlorine Dosage, mg/L

Ammonia can convert to nitrite at 1:1 ratio

Nitrite can convert to nitrate at 1:1 ratio

IF no limiting factors present

Highest risk during low water use and warm water temperatures ◦ Spring and fall when warm water due to time in tower/storage and

low use

◦ Last few years in the summer: issues with nitrification in systems that had not had previous problems due to low water use and warm temperatures

Same bacterial action as in wastewater systems –conversion of ammonia to nitrate

Page 59: February, March and April 2018 Julie Sievers Iowa DNR ... · Nitrification –The Good, the Bad, and the Ugly ... the breakpoint side of the curve ... Liquid Chlorine Dosage, mg/L

Factor Nitrosomonas Nitrobacter

pH 5.8 – 9.5 5.7 – 10.2

Optimum pH 7.5 – 8.0 7.6 – 7.8

Temperature 5 – 30 C 5 – 40 C

Optimum Temp 30 C 28 C

Chlorine Less sensitive Very sensitive

Ammonia Consume Very sensitive

Page 60: February, March and April 2018 Julie Sievers Iowa DNR ... · Nitrification –The Good, the Bad, and the Ugly ... the breakpoint side of the curve ... Liquid Chlorine Dosage, mg/L

Amount of dissolved oxygen (DO)

Chlorine residuals Temperature Detention/retention

time Amount of free

ammonia present pH Light

Microbial community composition

Alkalinity Phosphate level

Carbon or TOC levels

Type of filter media

Backwash water –chlorinated or nonchlorinated

Others

Page 61: February, March and April 2018 Julie Sievers Iowa DNR ... · Nitrification –The Good, the Bad, and the Ugly ... the breakpoint side of the curve ... Liquid Chlorine Dosage, mg/L

For complete nitrification (conversion of ammonia to nitrate), 4.57 mg/L of oxygen is consumed per each 1 mg/L of ammonia◦ This is in addition to the oxygen needed for oxidation of iron and other

contaminants

◦ Often this is the limiting factor – conversion stops at nitrite leading to nitrite MCL violations

For complete nitrification, 7.1 mg/L (as CaCO3) of alkalinity is needed for each 1 mg/L of ammonia◦ Used to build cell walls by nitrifying bacteria

Page 62: February, March and April 2018 Julie Sievers Iowa DNR ... · Nitrification –The Good, the Bad, and the Ugly ... the breakpoint side of the curve ... Liquid Chlorine Dosage, mg/L

Drop in total chlorine residuals or no chlorine residual in ends or portions of the distribution system◦ May also be in the middle of a loop (water moving from both

directions with oldest water in the middle of the loop and little water movement)

Fluctuations in chlorine residuals with no apparent cause or reason such as changes wells or high service pumps

Decrease (drop) in pH and/or alkalinity in areas of distribution system

Page 63: February, March and April 2018 Julie Sievers Iowa DNR ... · Nitrification –The Good, the Bad, and the Ugly ... the breakpoint side of the curve ... Liquid Chlorine Dosage, mg/L

Changes in nitrogen compounds through system◦ No nitrite or nitrate in raw water but nitrite or nitrate at SEP, in or after

storage, or in portions of distribution system

◦ Look at historical data

Taste and odor complaints

Dirty water complaints

Changes in chlorine residuals (demand) after change of filter media or shock chlorination of filter media, particularly in iron removal plants

Page 64: February, March and April 2018 Julie Sievers Iowa DNR ... · Nitrification –The Good, the Bad, and the Ugly ... the breakpoint side of the curve ... Liquid Chlorine Dosage, mg/L

Disinfection depletion (drop in residuals)

Nitrite/nitrate formation

Dissolved oxygen (DO) depletion

Reduction in pH

Reduction in alkalinity

DBP formation changes

“Dirty water” complaints

Corrosion issues, commonly seen as lead and copper exceedances

Page 65: February, March and April 2018 Julie Sievers Iowa DNR ... · Nitrification –The Good, the Bad, and the Ugly ... the breakpoint side of the curve ... Liquid Chlorine Dosage, mg/L

On to control options…

Page 66: February, March and April 2018 Julie Sievers Iowa DNR ... · Nitrification –The Good, the Bad, and the Ugly ... the breakpoint side of the curve ... Liquid Chlorine Dosage, mg/L

1. Ammonia removalRunning filters in “bio” mode, also called biological ammonia removal treatment

2. Breakpoint chlorinationNo ammonia to nitrify

3. Combination of oxidants

4. Chloramination with operational control

Page 67: February, March and April 2018 Julie Sievers Iowa DNR ... · Nitrification –The Good, the Bad, and the Ugly ... the breakpoint side of the curve ... Liquid Chlorine Dosage, mg/L

Biological removal of ammonia through nitrification Ammonia to nitrite to nitrate◦ No ammonia or nitrite in finished water◦ Free chlorine residuals – past breakpoint on curve

Typically occurs in filters but may occur in aeration, detention – before SEP

No chlorination prior to filters Care must be taken during establishing to protect

nitrifying bacteria◦ Backwash rate◦ Backwash water – chlorinated or not chlorinated

Typically takes 8 – 12 or more weeks to establish

Page 68: February, March and April 2018 Julie Sievers Iowa DNR ... · Nitrification –The Good, the Bad, and the Ugly ... the breakpoint side of the curve ... Liquid Chlorine Dosage, mg/L

Limiting factor! Dissolved oxygen◦ If ammonia is greater than ~2 mg/L, there will not be enough oxygen

for complete nitrification◦ About 4.5 mg/L of oxygen is needed to completely nitrify 1 mg/L of

ammonia◦ Conversion stops at nitrite if not enough oxygen◦ Often have nitrite MCL violations at SEP as not enough oxygen to get

from nitrite to nitrate

Systems with higher ammonia levels now operating with air injection to get ammonia removal in contactors (new treatment step)

Page 69: February, March and April 2018 Julie Sievers Iowa DNR ... · Nitrification –The Good, the Bad, and the Ugly ... the breakpoint side of the curve ... Liquid Chlorine Dosage, mg/L

Destroys all ammonia so no “food” for the nitrifying bacteria◦ Ammonia to nitrogen gas

Disinfection by free chlorine – past breakpoint on free side of curve

Requires large dose of chlorine◦ In practice, 10 to 12 mg/L (or more) of chlorine per 1

mg/L of ammonia is common

TTHM/HAA5 concerns◦ Many systems with raw water ammonia have high raw water

TOC levels

Page 70: February, March and April 2018 Julie Sievers Iowa DNR ... · Nitrification –The Good, the Bad, and the Ugly ... the breakpoint side of the curve ... Liquid Chlorine Dosage, mg/L

Free chlorination may not be possible◦ Often cannot add enough chlorine to meet demand

May not be enough reaction time◦ Reaction time dependent on pH and temperature

◦ Must go through all reactions to get to free chlorine (past breakpoint)

◦ If reaction not complete, unstable water entering the system

Taste and odor complaints

Dirty water and corrosion issues common

Page 71: February, March and April 2018 Julie Sievers Iowa DNR ... · Nitrification –The Good, the Bad, and the Ugly ... the breakpoint side of the curve ... Liquid Chlorine Dosage, mg/L

Combination of oxidants◦ Consider use of multiple oxidants

◦ Permanganate, chlorine, others

Other oxidants◦ MIOX (Mixed oxidants) is in use in some systems

◦ Uses a salt mixture and DC cell to form oxidants, including ozone, hydrogen peroxide, chlorine, chlorine dioxide, etc.

Not common practice to control as has many operational challenges

Addition of sodium chlorite◦ Very specific monitoring requirements

◦ Must do pilot and show operational control

Page 72: February, March and April 2018 Julie Sievers Iowa DNR ... · Nitrification –The Good, the Bad, and the Ugly ... the breakpoint side of the curve ... Liquid Chlorine Dosage, mg/L

Minimize free ammonia as much as possible◦ For systems adding ammonia, target 0.04 – 0.1 mg/L free

ammonia

◦ For systems with natural ammonia, target consistent ammonia levels and maximum chlorine to ammonia ratio

Target disinfectant◦ Monochloramine = Total Chlorine

Page 73: February, March and April 2018 Julie Sievers Iowa DNR ... · Nitrification –The Good, the Bad, and the Ugly ... the breakpoint side of the curve ... Liquid Chlorine Dosage, mg/L

Increase residuals to control nitrifying bacteria◦ Necessary levels vary by system – typically 2 mg/L or

higher (total chlorine residual)◦ May need to go to breakpoint for a few weeks each

spring and/or fall to kill biofilm and then maintain higher chloramine residuals to inhibit growth Notify customers and DNR FO if change disinfection

practice

May still have free ammonia present so may have nitrite formation in low use areas, dead-ends, and storage facilities◦ Reversion to ammonia (breakdown of chloramines)

Page 74: February, March and April 2018 Julie Sievers Iowa DNR ... · Nitrification –The Good, the Bad, and the Ugly ... the breakpoint side of the curve ... Liquid Chlorine Dosage, mg/L

Other changes in operation to control depending on where nitrification is taking place, such as ◦ Changes to backwash◦ Increased flushing program◦ Addition of booster chlorine/ammonia feed◦ Loop deadends◦ Periodic forcing of water to move one direction

through looped areas◦ Changing to free chlorine periodically Frequency and duration varies

Page 75: February, March and April 2018 Julie Sievers Iowa DNR ... · Nitrification –The Good, the Bad, and the Ugly ... the breakpoint side of the curve ... Liquid Chlorine Dosage, mg/L

Nitrosamine formation◦ Nitrosamines are DBPs in chloraminating systems

◦ N-nitrosodimethylamine (NDMA) is most common

◦ Much on-going research

◦ Formation from reaction of natural organic matter (NOM), use of quaternary amine-based coagulants and anion exchange resins, or wastewater-impaired source waters

EPA is currently reviewing the existing microbial and disinfection byproducts regulations as part of the six year review process (SY3)

Page 76: February, March and April 2018 Julie Sievers Iowa DNR ... · Nitrification –The Good, the Bad, and the Ugly ... the breakpoint side of the curve ... Liquid Chlorine Dosage, mg/L

Very specific to each system

No magic fix that will work for all systems

Must know what disinfection practice you are using and where you are on the curve!

Page 77: February, March and April 2018 Julie Sievers Iowa DNR ... · Nitrification –The Good, the Bad, and the Ugly ... the breakpoint side of the curve ... Liquid Chlorine Dosage, mg/L

Many factors impact decision on how to control ammonia

Work with your engineer and/or technical service provider

Need to weigh all of the options and consequences – many unintended consequences such as nitrification, L/C corrosion, chlorine residuals, etc.

Communicate with DNR

Page 78: February, March and April 2018 Julie Sievers Iowa DNR ... · Nitrification –The Good, the Bad, and the Ugly ... the breakpoint side of the curve ... Liquid Chlorine Dosage, mg/L

Minimum = 1.5 mg/L total Minimum = 0.3 mg/L free

From Bob Spon, OpFlow Article, June 2008

Page 79: February, March and April 2018 Julie Sievers Iowa DNR ... · Nitrification –The Good, the Bad, and the Ugly ... the breakpoint side of the curve ... Liquid Chlorine Dosage, mg/L

On to DNR protocols, testing and system specific examples…

Page 80: February, March and April 2018 Julie Sievers Iowa DNR ... · Nitrification –The Good, the Bad, and the Ugly ... the breakpoint side of the curve ... Liquid Chlorine Dosage, mg/L

Systems have naturally occurring ammonia in their groundwater (source water)

Systems adding ammonia to form chloramines Significant potential exists for conversion of ammonia to

nitrite and nitrite to nitrate◦ MCL nitrite 1.0 mg/L◦ MCL nitrate 10 mg/L

Nitrite levels at SEP and/or distribution found ranging from ND (no detection) to 3.5 mg/L

A number of systems have not been meeting minimum disinfection residuals

Page 81: February, March and April 2018 Julie Sievers Iowa DNR ... · Nitrification –The Good, the Bad, and the Ugly ... the breakpoint side of the curve ... Liquid Chlorine Dosage, mg/L

Protocols for use:◦ During sanitary surveys

◦ Investigations of nitrite MCL violations

◦ Complaint investigations

◦ System not meeting minimum residual requirements

Training of all DNR staff in Nov. 2015

Protocols are being implemented

Systems are encouraged to sample each well or source if ammonia levels are not known

Page 82: February, March and April 2018 Julie Sievers Iowa DNR ... · Nitrification –The Good, the Bad, and the Ugly ... the breakpoint side of the curve ... Liquid Chlorine Dosage, mg/L

To determine if there is a need to sample

Assignment of monitoring determined classification:◦ Systems with complete nitrification at SEP and/or using free chlorine

for disinfection

◦ Systems with the potential for nitrite formation

◦ Systems with nitrite MCL exceedances

◦ Systems adding ammonia

◦ Consecutive systems using chloramines or not meeting minimum chlorine residuals

Interpretation of results

Any required monitoring will be included in a WS operation permit

Page 83: February, March and April 2018 Julie Sievers Iowa DNR ... · Nitrification –The Good, the Bad, and the Ugly ... the breakpoint side of the curve ... Liquid Chlorine Dosage, mg/L

Systems with Complete Nitrification at SEP and/or using Free Chlorine for Disinfection◦ Free and total chlorine residuals

◦ SEP ammonia 1/year for systems with ammonia >0.7 mg/L in combined raw water

Systems with the Potential for Nitrite Formation◦ Ammonia >0.7 mg/L in combined raw water and chloraminating or

nitrification occurring at any site

◦ Free and total residual - total only with FO approval

◦ SEP ammonia, SEP and distribution nitrite

◦ Self-monitoring for nitrite at SEP and distribution system

◦ Frequency dependent on if nitrification has occurred

Page 84: February, March and April 2018 Julie Sievers Iowa DNR ... · Nitrification –The Good, the Bad, and the Ugly ... the breakpoint side of the curve ... Liquid Chlorine Dosage, mg/L

Systems with Nitrite MCL Exceedances◦ For systems with current or historical nitrite MCL exceedances

◦ Free and total residual - total only with FO approval

◦ Quarterly SEP ammonia, monthly SEP and distribution nitrite

◦ Weekly self-monitoring for ammonia and nitrite at SEP and distribution system

Systems Adding Ammonia◦ For systems adding ammonia for chloramination

◦ Total chlorine residual, monochloramine, free ammonia, pH

◦ Distribution system nitrite

◦ Self-monitoring for nitrite

◦ Monitoring Plan with Alert and Action Levels

Page 85: February, March and April 2018 Julie Sievers Iowa DNR ... · Nitrification –The Good, the Bad, and the Ugly ... the breakpoint side of the curve ... Liquid Chlorine Dosage, mg/L

Consecutive Systems Using Chloramines

Systems purchasing water containing chloramines

If the producing system has naturally occurring ammonia:◦ Free and total residual - total only with FO approval

◦ Distribution system nitrite

◦ Self-monitoring for nitrite

If the producing system adds ammonia to chloraminate:◦ Total chlorine residual, monochloramine, free ammonia, pH

◦ Distribution system nitrite

◦ Self-monitoring for nitrite

Page 86: February, March and April 2018 Julie Sievers Iowa DNR ... · Nitrification –The Good, the Bad, and the Ugly ... the breakpoint side of the curve ... Liquid Chlorine Dosage, mg/L

Required for systems with monthly or quarterly distribution system monitoring

No template as system specific

Select location(s) with highest risk of nitrification

Often deadend or low use areas◦ May be in the middle of a loop

Use chlorine residuals, monochloramine, free ammonia, and pH levels; temperature; and taste and odor complaints as guide

Page 87: February, March and April 2018 Julie Sievers Iowa DNR ... · Nitrification –The Good, the Bad, and the Ugly ... the breakpoint side of the curve ... Liquid Chlorine Dosage, mg/L

Select locations with the highest potential for nitrification◦ Lowest total chlorine residual

◦ Largest separation between total chlorine and monochloramine

◦ Highest free ammonia levels

◦ Lowest pH (drop in pH indicates nitrification)

Submit to FO and use this location(s) for certified lab sampling◦ Remember to test this sample as part of self-monitoring (paired

samples)

Page 88: February, March and April 2018 Julie Sievers Iowa DNR ... · Nitrification –The Good, the Bad, and the Ugly ... the breakpoint side of the curve ... Liquid Chlorine Dosage, mg/L

Several options depending on:

Colorimeter/spectrophotometer model

Needed range of the system

Be aware of disposal requirements◦ Nessler reagent for ammonia contains mercury

Page 89: February, March and April 2018 Julie Sievers Iowa DNR ... · Nitrification –The Good, the Bad, and the Ugly ... the breakpoint side of the curve ... Liquid Chlorine Dosage, mg/L

Samples for nitrite need to be at room temperature for accurate results

Protocols require “paired” samples◦ Self-monitoring testing and certified lab testing of the same sample

◦ Results should be comparable, if not need to determine why

◦ Use self-monitoring to indicate when something has changed so results must be accurate and representative

Page 90: February, March and April 2018 Julie Sievers Iowa DNR ... · Nitrification –The Good, the Bad, and the Ugly ... the breakpoint side of the curve ... Liquid Chlorine Dosage, mg/L

Guidelines for systems changing from Chloramine to Free Chlorine or vise versa ◦ Pre-Transition

◦ Water Plant Activities

◦ Distribution Activities

Customer Notification Samples

Post Transition Strategy

Page 91: February, March and April 2018 Julie Sievers Iowa DNR ... · Nitrification –The Good, the Bad, and the Ugly ... the breakpoint side of the curve ... Liquid Chlorine Dosage, mg/L

On to System Specific Examples…

Page 92: February, March and April 2018 Julie Sievers Iowa DNR ... · Nitrification –The Good, the Bad, and the Ugly ... the breakpoint side of the curve ... Liquid Chlorine Dosage, mg/L

Curve is specific for each system

First example is from a system that Dale and Joe worked with to develop the curve for the system

Chlorine was added (dosed) after all treatment

Treatment = aeration, detention, filtration, ion exchange

Water dosed:

Iron 0.02, Manganese 0.044, Ammonia 0.39 (all mg/L)

Page 93: February, March and April 2018 Julie Sievers Iowa DNR ... · Nitrification –The Good, the Bad, and the Ugly ... the breakpoint side of the curve ... Liquid Chlorine Dosage, mg/L

Dose (mg/L) Free Chlorine Total Chlorine Monochloramine Free Ammonia Total Ammonia

0.00 0.00 0.00 0.00 0.00 0.39

0.25 0.00 0.05 0.00 0.38 0.40

0.50 0.00 0.29 0.22 0.37 0.40

0.75 0.00 0.46 0.40 0.35 0.41

1.00 0.00 0.62 0.58 0.33 0.41

1.25 0.00 0.74 0.66 0.30 0.41

1.50 0.00 0.85 0.74 0.26 0.40

1.75 0.00 0.98 0.85 0.23 0.40

2.00 0.00 1.11 0.95 0.19 0.39

2.25 0.00 1.24 1.07 0.20 0.39

2.50 0.00 1.37 1.18 0.21 0.39

2.75 0.00 1.48 1.29 0.16 0.38

3.00 0.00 1.58 1.39 0.11 0.38

3.25 0.00 1.61 1.40 0.08 0.39

3.50 0.00 1.63 1.41 0.06 0.38

3.75 0.00 1.66 1.41 0.03 0.37

4.00 0.00 1.68 1.42 0.00 0.27

4.25 0.00 1.65 1.32 0.00 0.25

4.50 0.00 1.62 1.22 0.00 0.24

4.75 0.00 1.58 1.11 0.00 0.22

Page 94: February, March and April 2018 Julie Sievers Iowa DNR ... · Nitrification –The Good, the Bad, and the Ugly ... the breakpoint side of the curve ... Liquid Chlorine Dosage, mg/L

5.00 0.00 1.55 1.01 0.00 0.20

5.25 0.00 1.44 0.90 0.00 0.18

5.50 0.00 1.34 0.80 0.00 0.16

5.75 0.00 1.23 0.69 0.00 0.13

6.00 0.00 1.12 0.58 0.00 0.11

6.25 0.00 1.05 0.51 0.00 0.10

6.50 0.00 0.97 0.43 0.00 0.09

6.75 0.00 0.90 0.36 0.00 0.08

7.00 0.00 0.82 0.28 0.00 0.07

7.25 0.00 0.90 0.25 0.00 0.07

7.50 0.00 0.98 0.21 0.00 0.07

7.75 0.00 1.06 0.18 0.00 0.06

8.00 0.00 1.14 0.14 0.00 0.06

8.25 0.00 1.21 0.12 0.00 0.03

8.50 0.91 1.28 0.09 0.00 0.00

8.75 1.05 1.34 0.05 0.00 0.00

9.00 1.18 1.40 0.00 0.00 0.00

9.25 1.51 1.74 0.00 0.00 0.00

9.50 1.84 2.08 0.00 0.00 0.00

9.75 2.17 2.42 0.00 0.00 0.00

10.00 2.50 2.76 0.00 0.00 0.00

Dose (mg/L) Free Chlorine Total Chlorine Monochloramine Free Ammonia Total Ammonia

Page 95: February, March and April 2018 Julie Sievers Iowa DNR ... · Nitrification –The Good, the Bad, and the Ugly ... the breakpoint side of the curve ... Liquid Chlorine Dosage, mg/L
Page 96: February, March and April 2018 Julie Sievers Iowa DNR ... · Nitrification –The Good, the Bad, and the Ugly ... the breakpoint side of the curve ... Liquid Chlorine Dosage, mg/L

mg/l SEP Mid-point End

Free Cl2

Initial – 1 minute

1.16 – 1.35

Initial – 1 minute

0.47 – 0.47

Initial – 1 minute

0.19 – 0.20

Total Cl2 1.39 0.62 0.26

Mono-chloramine

1.37 ND ND

Free Ammonia ND ND ND

Total Ammonia 0.23 ND ND

Nitrite ND ND0.005 (0.004

min)

Chloraminating or Breakpoint

Page 97: February, March and April 2018 Julie Sievers Iowa DNR ... · Nitrification –The Good, the Bad, and the Ugly ... the breakpoint side of the curve ... Liquid Chlorine Dosage, mg/L
Page 98: February, March and April 2018 Julie Sievers Iowa DNR ... · Nitrification –The Good, the Bad, and the Ugly ... the breakpoint side of the curve ... Liquid Chlorine Dosage, mg/L

Court

esy o

f M

ikael Bro

wn,

Bart

lett

and W

est,

Inc.

Determination of Chlorine Curve –System A

Raw water ammonia = 1.69 mg/L

pH = 7.6

Cl2 dose = 23.9 mg/L

Fe/Mn demand = 1.2 mg/L

Page 99: February, March and April 2018 Julie Sievers Iowa DNR ... · Nitrification –The Good, the Bad, and the Ugly ... the breakpoint side of the curve ... Liquid Chlorine Dosage, mg/L

Courtesy of Mikael Brown, Bartlett and West, Inc. Raw Water NH3 = 1.69

Plant A

Page 100: February, March and April 2018 Julie Sievers Iowa DNR ... · Nitrification –The Good, the Bad, and the Ugly ... the breakpoint side of the curve ... Liquid Chlorine Dosage, mg/L

• Chlorine demand measured over time

• At pH of 7.6, reaction 90% complete in 20 minutes

• At pH of 10.5, reaction 90% complete in 600 minutes (10 hours)

Courtesy of Mikael Brown, Bartlett and West, Inc.

Plant A

Page 101: February, March and April 2018 Julie Sievers Iowa DNR ... · Nitrification –The Good, the Bad, and the Ugly ... the breakpoint side of the curve ... Liquid Chlorine Dosage, mg/L

Courtesy of Mikael Brown, Bartlett and West, Inc.

Plant B

Raw water ammonia = 0.36 mg/L

Iron = 6.96 mg/L

Mn = 0.41 mg/L

Water Quality Parameter

Free Chlorine Demand

Multiplier x (Factor)

Iron 0.64 mg/L

Manganese 1.3

Hydrogen Sulfide 0.2

Nitrite (as N) 5

Ammonia (as N) 10 to 12

Organic Nitrogen 1

TOC 0.1

Page 102: February, March and April 2018 Julie Sievers Iowa DNR ... · Nitrification –The Good, the Bad, and the Ugly ... the breakpoint side of the curve ... Liquid Chlorine Dosage, mg/L

Courtesy of Mikael Brown, Bartlett and West, Inc.

Plant B

Page 103: February, March and April 2018 Julie Sievers Iowa DNR ... · Nitrification –The Good, the Bad, and the Ugly ... the breakpoint side of the curve ... Liquid Chlorine Dosage, mg/L

Courtesy of Mikael Brown, Bartlett and West, Inc.

Plant B

Page 104: February, March and April 2018 Julie Sievers Iowa DNR ... · Nitrification –The Good, the Bad, and the Ugly ... the breakpoint side of the curve ... Liquid Chlorine Dosage, mg/L
Page 105: February, March and April 2018 Julie Sievers Iowa DNR ... · Nitrification –The Good, the Bad, and the Ugly ... the breakpoint side of the curve ... Liquid Chlorine Dosage, mg/L

3 Dakota Aquifer Wells

Wells are within about 2 blocks of each other◦ Common to see variation in ammonia levels in wells in same aquifer

Lime softening Nitrification occurring in filters and distribution system

Page 106: February, March and April 2018 Julie Sievers Iowa DNR ... · Nitrification –The Good, the Bad, and the Ugly ... the breakpoint side of the curve ... Liquid Chlorine Dosage, mg/L

3 Dakota Wells

NH3 = 1.2 - 2.2NO2 = <0.02NO3 = <0.1

Aeration

Lime SofteningNH3 = 1.1

NO2 = <0.02NO3 = <0.1

Top of FiltersNH3 = 1.1

NO2 = <0.02-0.12NO3 = <0.1

Bottom of FiltersNH3 = 0.7 - 0.9

NO2 = 0.26 - 0.46NO3 = <0.1

Plant 1 – Natural Ammonia

Page 107: February, March and April 2018 Julie Sievers Iowa DNR ... · Nitrification –The Good, the Bad, and the Ugly ... the breakpoint side of the curve ... Liquid Chlorine Dosage, mg/L

S/EPNH3 = 0.4

NO2 = <0.02 - 0.24NO3 = 0.27

High Usage Area in

Distribution System

NH3 = 0.4NO2 = 0.32NO3 = 0.26

Dead EndNH3 = 0.1

NO2 = 0.19NO3 = 0.72

Page 108: February, March and April 2018 Julie Sievers Iowa DNR ... · Nitrification –The Good, the Bad, and the Ugly ... the breakpoint side of the curve ... Liquid Chlorine Dosage, mg/L

Location Ammonia Nitrite Nitrate

Raw 1.2 <0.02 <0.1

After lime

softening

1.1 <0.02 <0.1

Top of Filters 1.1 – 1.2 <0.02 – 0.12 <0.1

Bottom of

Filters

0.7 – 0.9 0.26 – 0.46 <0.1

S/EP 0.4 <0.02 – 0.24 0.27

End of System

High Usage

0.4 0.32 0.26

Deadend 0.1 0.19 0.72

Data - Plant 1

All results in mg/L

Page 109: February, March and April 2018 Julie Sievers Iowa DNR ... · Nitrification –The Good, the Bad, and the Ugly ... the breakpoint side of the curve ... Liquid Chlorine Dosage, mg/L

Initially using raw water to backwash

Now using chlorinated water to backwash filters

Flushing system regularly

Frequent monitoring (self-monitoring) to determine nitrite levels

Nitrite levels now typically <0.1 mg/L◦ During low use, warm temps 0.1 to 0.3 mg/L

Total chlorine ~2.2 – 3.0 in system

“False” free chlorine

Disinfection = chloramination

Page 110: February, March and April 2018 Julie Sievers Iowa DNR ... · Nitrification –The Good, the Bad, and the Ugly ... the breakpoint side of the curve ... Liquid Chlorine Dosage, mg/L

Jordan Wells

Treatment = Aeration, filtration, zeolite softening, chlorination, caustic soda addition

Saw significant decrease in chlorine levels when filter media was changed◦ No free, low total residual

Nitrifying bacteria re-established and conversion to nitrite to nitrate in filters

Total chlorine ~0.8 - 1.2 in system

Free chlorine ~ 0.6 - 1.1 in system

Disinfection = Free chlorine

Page 111: February, March and April 2018 Julie Sievers Iowa DNR ... · Nitrification –The Good, the Bad, and the Ugly ... the breakpoint side of the curve ... Liquid Chlorine Dosage, mg/L

Location Ammonia Nitrite Nitrate

Well 7 2.1 <0.1 <0.5

Well 8 2.1 <0.1 <0.5

Well 9 2.2 <0.1 <0.5

Well 10 1.9 <0.1 <0.5

S/EP <0.05 <0.1 1.62

Page 112: February, March and April 2018 Julie Sievers Iowa DNR ... · Nitrification –The Good, the Bad, and the Ugly ... the breakpoint side of the curve ... Liquid Chlorine Dosage, mg/L

Testing indicated no ammonia

No nitrite or nitrate in wells

Nitrate in SEP result

Nitrification occurring in the filters

Disinfectant = Free chlorine

Page 113: February, March and April 2018 Julie Sievers Iowa DNR ... · Nitrification –The Good, the Bad, and the Ugly ... the breakpoint side of the curve ... Liquid Chlorine Dosage, mg/L

Location Ammonia TKN Nitrite Nitrate

Well 3 <0.2 2.0 <0.1 <0.5

Well 4 <0.2 1.8 <0.1 <0.5

Filter

Effluent

<0.2 Not tested <0.1 1.6

S/EP <0.2 Not tested <0.1 1.6

All results in mg/L

Page 114: February, March and April 2018 Julie Sievers Iowa DNR ... · Nitrification –The Good, the Bad, and the Ugly ... the breakpoint side of the curve ... Liquid Chlorine Dosage, mg/L

2 Dakota wells◦ Naturally occurring ammonia

Iron removal◦ Aeration, detention, gravity filtration

Page 115: February, March and April 2018 Julie Sievers Iowa DNR ... · Nitrification –The Good, the Bad, and the Ugly ... the breakpoint side of the curve ... Liquid Chlorine Dosage, mg/L

2 Dakota Wells

NH3 = 3.4 - 3.8 NO2 = <0.02NO3 = <0.1

AerationNH3 = 3.5 NO2 = <0.02NO3 = <0.1 Detention

NH3 = 3.6NO2 = <0.02NO3 = <0.1

After FiltersNH3 = 2.5 - 2.9

NO2 = 0.66 - 0.85NO3 = <0.1 - 0.10

S/EPNH3 = 2.5

NO2 = 0.29NO3 = 0.55

Free chlorine = 0.3Total chlorine = 2.6

Page 116: February, March and April 2018 Julie Sievers Iowa DNR ... · Nitrification –The Good, the Bad, and the Ugly ... the breakpoint side of the curve ... Liquid Chlorine Dosage, mg/L

After TowerNH3 = 2.1

NO2 = 0.41NO3 = 0.72

Free chlorine = 0.1Total chlorine = 1.2

Dist System -Near Tower

NH3 = 2.0NO2 = 0.70NO3 = 0.59

Free chlorine = 0.2Total chlorine = 1.4

Dist System -Looped Line

NH3 = 2.2NO2 = 0.44NO3 = 0.67

Free chlorine = 0.2Total chlorine = 1.4

Dist System -Dead-end

NH3 = 0.51 - 1.1NO2 = 1.1 - 2.1

NO3 = 0.54 - 0.59Free chlorine = 0.1

Total chlorine = ND – 0.4

Page 117: February, March and April 2018 Julie Sievers Iowa DNR ... · Nitrification –The Good, the Bad, and the Ugly ... the breakpoint side of the curve ... Liquid Chlorine Dosage, mg/L

Tower with 2½ average day capacity

Tried breakpoint chlorination to control - could not feed enough chlorine to reach breakpoint, could not get reaction to be complete in plant/clearwell

Used MIOX to eliminate ammonia until unit failed

Exceeded lead and copper action levels

Now injecting air into contactors for biological ammonia removal

Complete nitrification in the plant

Free chlorine for disinfection

Page 118: February, March and April 2018 Julie Sievers Iowa DNR ... · Nitrification –The Good, the Bad, and the Ugly ... the breakpoint side of the curve ... Liquid Chlorine Dosage, mg/L

2 Buried Sand &

Gravel WellsNH3 = 3.3 - 3.6

NO2 = <0.02NO3 = <0.1

Line to TowerNH3 = 3.4

NO2 = <0.02NO3 = <0.1

Total Chlorine = 2.7

S/EPNH3 = 3.0

NO2 = <0.02NO3 = <0.1

Total Chlorine = 2.0

Treatment is an in-line air stone (atomerator), liquid chlorine addition, and pressure sand filtration

The water flows to the tower with splash aeration in the tower, then to the distribution system

Page 119: February, March and April 2018 Julie Sievers Iowa DNR ... · Nitrification –The Good, the Bad, and the Ugly ... the breakpoint side of the curve ... Liquid Chlorine Dosage, mg/L

Dist System - AverageNH3 = 2.1

NO2 = 0.59NO3 = <1.0

Total chlorine = 1.7

Dist System - Dead-endNH3 = 1.8NO2 = 1.2

NO3 = <1.0Total chlorine = 0.64

Page 120: February, March and April 2018 Julie Sievers Iowa DNR ... · Nitrification –The Good, the Bad, and the Ugly ... the breakpoint side of the curve ... Liquid Chlorine Dosage, mg/L

Tried breakpoint chlorination to control - could not feed enough chlorine to reach breakpoint with the time they have for the reaction

Too high of ammonia to get ammonia removal through nitrification in the plant◦ Did not have enough oxygen present in the filters to be able to sustain

complete nitrification

Aggressive flushing program to control nitrite formation

Page 121: February, March and April 2018 Julie Sievers Iowa DNR ... · Nitrification –The Good, the Bad, and the Ugly ... the breakpoint side of the curve ... Liquid Chlorine Dosage, mg/L

Surface Water Plant Clearwell

Prior to NH3 AddFree Chlorine =

0.8 – 1.0

Pump Station 1Consecutive System

Total NH3 = <1.0NO2 = 1.0NO3 = 0.9

Total Chlorine = 2.7

Surface Water Plant SEP

Free NH3 = 0.43Monochloramine =

3.00

Page 122: February, March and April 2018 Julie Sievers Iowa DNR ... · Nitrification –The Good, the Bad, and the Ugly ... the breakpoint side of the curve ... Liquid Chlorine Dosage, mg/L

Dist System - DownstreamTotal NH3 = 0.34Free NH3 = 0.28

NO2 = >0.69Total chlorine = 0.63

Monochloramine = 0.21

Dist System - Dead-endTotal NH3 = 0.17Free NH3 = 0.10

NO2 = >0.69Total chlorine = 0.17

Monochloramine = <0.12

Page 123: February, March and April 2018 Julie Sievers Iowa DNR ... · Nitrification –The Good, the Bad, and the Ugly ... the breakpoint side of the curve ... Liquid Chlorine Dosage, mg/L

Tried flushing – could not get velocity to strip biofilm and did not increase chlorine residuals

Switched to breakpoint chlorination to control nitrification◦ Stopped feeding ammonia, increased chlorine feed

After 8 weeks, started adding ammonia◦ Targets:

◦ Free ammonia <0.1

◦ Monochloramine = total chlorine

◦ All total chlorine residuals >1.5

Page 124: February, March and April 2018 Julie Sievers Iowa DNR ... · Nitrification –The Good, the Bad, and the Ugly ... the breakpoint side of the curve ... Liquid Chlorine Dosage, mg/L

Very specific to each system No magic fix that will work for all systems

Must know what disinfection practice you are using and where you are on the curve!

Page 125: February, March and April 2018 Julie Sievers Iowa DNR ... · Nitrification –The Good, the Bad, and the Ugly ... the breakpoint side of the curve ... Liquid Chlorine Dosage, mg/L

Minimum = 1.5 mg/L total Min = 0.3 mg/L free

From Bob Spon, OpFlow Article, June 2008

Page 126: February, March and April 2018 Julie Sievers Iowa DNR ... · Nitrification –The Good, the Bad, and the Ugly ... the breakpoint side of the curve ... Liquid Chlorine Dosage, mg/L

Julie Sievers

712-262-4177