Types of Feedback ControlPrevious: System Model.
All the graphs shown in this section use parameter values for the thermal model that are typical of a small
domestic cooker and the set-point temperature Ts is indicated by the red lines.
On-Off Control
This is the simplest form of control, used by almost all domestic thermostats. When the oven is cooler than the
set-point temperature the heater is turned on at maximum power,M, and once the oven is hotter than the set-point temperature the heater is switched off completely. The turn-on and turn-off temperatures are deliberately
made to differ by a small amount, known as the hysteresisH, to prevent noise from switching the heater rapidly
and unnecessarily when the temperature is near the set-point. The fluctuations in temperature shown on the
graph are significantly larger than the hysteresis, as can be confirmed with the interactive simulation, due to the
significant heat capacity of the heating element.
Proportional Control
A proportional controller attempts to perform better than the On-Off type by applying power, W, to the heater
in proportion to the difference in temperature between the oven and the set-point,
wherePis known as theproportional gain of the controller. As its gain is increased the system responds fasterto changes in set-point but becomes progressively underdamped and eventually unstable. The final oven
temperature lies below the set-point for this system because some difference is required to keep the heater
supplying power. The heater power must always lie between zero and the maximumMbecause it can only
source, not sink, heat.
W = P ( ) T
s
T
o
http://www.ex.ac.uk/http://www.ex.ac.uk/http://newton.ex.ac.uk/http://newton.ex.ac.uk/http://newton.ex.ac.uk/http://newton.ex.ac.uk/teaching/CDHW/Feedback/ControlTypes.html#OnOffCtlhttp://newton.ex.ac.uk/cgi-bin/metaform?http://newton.ex.ac.uk/teaching/CDHW/Feedback/OvSimForm-gen.htmlhttp://newton.ex.ac.uk/teaching/CDHW/Feedback/SystemModel.htmlhttp://newton.ex.ac.uk/http://www.ex.ac.uk/ -
7/30/2019 Feedback and Temperature Control
2/3
4/27/13 Feedback and Temperature Control
newton.ex.ac.uk/teaching/CDHW/Feedback/ControlTypes.html 2/3
Proportional+Derivative ControlThe stability and overshoot problems that arise when aproportional controlleris used at high gain can be
mitigated by adding a term proportional to the time-derivative of the error signal,
This technique is known asPD control. The value of the damping constant, D, can be adjusted to achieve a
critically damped response to changes in the set-point temperature, as shown in the next figure.
Too little damping results in overshoot and ringing, too much causes an unnecessarily slow response.
Proportional+Integral+Derivative Control
Although PD control deals neatly with the overshoot and ringing problems associated withproportional control itdoes not cure the problem with the steady-state error. Fortunately it is possible to eliminate this while using
relatively low gain by adding an integral term to the control function which becomes
W = P ( ( ) + D ( ) ) T
s
T
o
d
d t
T
s
T
o
W = P ( ( ) + D ( ) + I ( ) d t )
s o
d
s o s o
http://newton.ex.ac.uk/teaching/CDHW/Feedback/ControlTypes.html#SSErrorhttp://newton.ex.ac.uk/teaching/CDHW/Feedback/ControlTypes.html#PropCtlhttp://newton.ex.ac.uk/teaching/CDHW/Feedback/ControlTypes.html#PDCtlhttp://newton.ex.ac.uk/teaching/CDHW/Feedback/ControlTypes.html#PropCtl -
7/30/2019 Feedback and Temperature Control
3/3
4/27/13 Feedback and Temperature Control
newton.ex.ac.uk/teaching/CDHW/Feedback/ControlTypes.html 3/3
whereI, the integral gain parameter is sometimes known as the controllerreset level. This form of function is
known as proportional-integral-differential, or PID, control. The effect of the integral term is to change the
heater power until the time-averaged value of the temperature error is zero. The method works quite well but
complicates the mathematical analysis slightly because the system is now third-order.
The figure shows that, as expected, adding the integral term has eliminated the steady-state error. The slight
undershoot in the power suggests that there may be scope for further tweaking.
Proportional+Integral ControlSometimes, particularly when the sensor measuring the oven temperature is susceptible to noise or other
electrical interference, derivative action can cause the heater power to fluctuate wildly. In these circumstances it
is often sensible use a PI controller or set the derivative action of a PID controller to zero.
Third-Order Systems
Systems controlled using an integral action controller are almost always at least third-order. Unlike second-
order systems, third-order systems are fairly uncommon in physics but the methods ofcontrol theory make the
analysis quite straightforward. For instance, applying the so-calledRouth-Hurwitz stability criterion, which is
a systematic way of classifying the complex roots of the auxiliary equation for the model, it can be shown that
provided the integral gain is kept sufficiently small then parameter values can be found to give an acceptably
damped response with the error temperature eventually tending to zero if the set-point is changed by a step or
linear ramp in time. Whereas derivative control improved the system damping, integral control eliminates steady-
state error at the expense of stability margin.
Next:Practical Matters.
W=
P ( ( ) + D ( ) + I ( ) d t ) T
s
T
o
d
d t
T
s
T
o
T
s
T
o
http://newton.ex.ac.uk/teaching/CDHW/Feedback/PracticalMatters.htmlhttp://newton.ex.ac.uk/teaching/CDHW/Feedback/PracticalMatters.html#CtlThry