ff in hazardous area[1]
TRANSCRIPT
-
8/8/2019 Ff in Hazardous Area[1]
1/34
1 Fieldbus Foundation Norway Stavanger 2008
FOUNDATIONTM Fieldbus inHazardous Areas
Physical Layer Concept
Einar S. Huse
NOREX / MTL
-
8/8/2019 Ff in Hazardous Area[1]
2/34
2 Fieldbus Foundation Norway Stavanger 2008
FF Basic Information
FIELD
CONTROL ROOM
FF Power Supply
Fieldbus controlsystem (DCS)
Trunk
Spur
Min. 9VMin. 10mA
Typical 12-16devices.
Tx @ 14 mAPos @ 22mA
31,25 Kbit/s32 Address
12 dev. @ 1s scan
Field wiring hubw. Short circuit protect.
-
8/8/2019 Ff in Hazardous Area[1]
3/34
3 Fieldbus Foundation Norway Stavanger 2008
FF Basic Information
-
8/8/2019 Ff in Hazardous Area[1]
4/34
4 Fieldbus Foundation Norway Stavanger 2008
Fieldbus in hazardous areas
Bulk power
Hazardous area
?
Hazardous Areaprotection?
FOUNDATION Fieldbus Devices
FIELD
CONTROL ROOM
Field Wiring
Hub
Whatapprovalsfor wiringhub andjunction
box?
What
approvalsfor Fieldbusdevices?
Specialprotectionfor fieldbus
power
supply?
Fieldbus controlsystem (DCS)
-
8/8/2019 Ff in Hazardous Area[1]
5/34
5 Fieldbus Foundation Norway Stavanger 2008
Methods of protection
Method of protection Zone 2 Zone 1
Ex d field devices and Ex ejunction boxes
Ex i/Intrinsically SafeENTITY or FISCO
Exe Exi/Fieldbus Barrier
Ex nL / FNICO
Ex nA, Non-Arcing
-
8/8/2019 Ff in Hazardous Area[1]
6/34
6 Fieldbus Foundation Norway Stavanger 2008
Ex-d /Ex-e Fieldbus
Ex-eField Wiring
Hub
Bulk power
Hazardous areaFOUNDATION Fieldbus Devices
FIELD
CONTROL ROOM
Ex-d / Ex-eInstruments
Fieldbus controlsystem (DCS)
Ordinary Safe Area Power SupplySingle or Redundant
No livemaintenance!
-
8/8/2019 Ff in Hazardous Area[1]
7/34
7 Fieldbus Foundation Norway Stavanger 2008
Entity Intrinsically Safe Fieldbus
ENTITYcertified
devices!
Bulk power
Hazardous areaFOUNDATION Fieldbus Devices
FIELD
CONTROL ROOM
Field Wiring
Hub Max 4Fieldbudevices!
Fieldbus controlsystem (DCS)
IS Fieldbus power supplyTypical 80mA output
For all Ui Uo
For all Ii Io
All Pi Po
Ci + Cc Co
Li + Lc Lo
-
8/8/2019 Ff in Hazardous Area[1]
8/34
8 Fieldbus Foundation Norway Stavanger 2008
Introducing FISCO Fieldbus Intrinsically Safe Concept, IEC 60079-27
Provides more current to IS trunk than earlier Entitymodel, and hence more field instruments
Proven by tests performed at PTB
Simplifies design and installation
Reduces documentation
First simplification of explosion protection techniques formany years!
3000 50 100 150 200 250
273mA
215mA
280mA
PowerSupply
Supply with cable
Supply with cableand Terminators
Ignition current in mA(including Safety Factor)Source: Dr. Ulrich Johannsmeyer, PTB
-
8/8/2019 Ff in Hazardous Area[1]
9/34
9 Fieldbus Foundation Norway Stavanger 2008
All instruments FISCO certified
Power Supply must be FISCO certified
Field cables must conform to the followingspecification:
loop resistance must be between 15 and 150ohms/km loop inductance must be between 0.4 and 1mH/km
loop capacitance must be between 45 and 200nF/km
maximum length of each spur cable is 60m in IIC and IIB
maximum length of each trunk cable is 1km in IIC or 5km inIIB
The limits are not restrictive
typical Fieldbus cable has parameters of 50ohms/km,0.8mH/km and 120nF/km
FISCO requirements
-
8/8/2019 Ff in Hazardous Area[1]
10/34
10 Fieldbus Foundation Norway Stavanger 2008
FISCO installation
FISCO power supply(IIB / IIC)
FIELD
CONTROL ROOM
Intrinsically SafeField wiring hub
Intrinsically safe FISCO Fieldbus devices
Zone 1Division 1
24Vdc24Vdc
Fieldbus controlsystem (DCS)
LiveMaintenance
!
LiveMaintenance
!
-
8/8/2019 Ff in Hazardous Area[1]
11/34
11 Fieldbus Foundation Norway Stavanger 2008
Multiple hazardous area trunks
Intrinsically safe FISCO Fieldbus devices
Zone 1Division 1
24Vdc24Vdc
Trunk #2 Trunk #3
Directparallel
connectionon safe
area side
-
8/8/2019 Ff in Hazardous Area[1]
12/34
12 Fieldbus Foundation Norway Stavanger 2008
Redundant FISCO architecture
Redundant FISCOpower supply
FIELDZone 1
CONTROL ROOM
24Vdc24VdcBulk power input
Intrinsically safe FISCO Fieldbus devices
Intrinsically Safe
Field wiring hub
IntrinsicallySafe trunkand spurs
-
8/8/2019 Ff in Hazardous Area[1]
13/34
13 Fieldbus Foundation Norway Stavanger 2008
More field devices with FISCO
Entity, IIC/IIB Gas Groups
FISCO, IIC Gas Groups
FISCO, IIB Gas Groups
80mA available, typically3 - 4 devices
120mA available, (140mA)typically 6-8 devices
265mA available,(280 mA)typically 14-16 devices
Zone 1Division 1
-
8/8/2019 Ff in Hazardous Area[1]
14/34
14 Fieldbus Foundation Norway Stavanger 2008
FB Fieldbus Barriers: Exe/Exi concept
Galvanic isolation and IS barrier in the field.
Ex-e trunk with higher current available
Zone-1 mountable fieldbus wiring hub for Intrinsically safe fieldbusdevices
Supports FISCO and Entity field devices
-
8/8/2019 Ff in Hazardous Area[1]
15/34
15 Fieldbus Foundation Norway Stavanger 2008
Fieldbus Barrier
FIELD
CONTROL ROOM
Intrinsically safe Fieldbus Devices
Increased safety(Ex e) trunk
Fieldbus control system
IS spurs
FieldbusBarriers
Power supplySingel or RedundantUp to 8 channel
modules available
-
8/8/2019 Ff in Hazardous Area[1]
16/34
16 Fieldbus Foundation Norway Stavanger 2008
Fieldbus Barrier across Zones
HOST / LAS
PowerSupply
POWERSUPPLIES
-
8/8/2019 Ff in Hazardous Area[1]
17/34
17 Fieldbus Foundation Norway Stavanger 2008
Comparision of Protection Techniquesused in
Hazardous Area
-
8/8/2019 Ff in Hazardous Area[1]
18/34
18 Fieldbus Foundation Norway Stavanger 2008
Entity IS vs. FISCO
Entity IS FISCO
Intrinsically safe trunk andspurs?
Live-working permitted in anypart of field network?
Simple safety documentation?
Eliminate cable parametercalculations?
Gas Group IIB option?
Max output current 80mA 265mA
Max spur length 120m 60m
-
8/8/2019 Ff in Hazardous Area[1]
19/34
19 Fieldbus Foundation Norway Stavanger 2008
FISCO vs. Fieldbus Barrier
FISCO Fieldbus
Barrier
IS Spur? Live Maintenance?
IS Trunk? Live Maintenance?
Simple documentation?
Redundant Power
Redundant Field Wiring Hub
Compatible with FISCO fielddevices?
Compatible with Entity fielddevices?
Only with spur
connector!
-
8/8/2019 Ff in Hazardous Area[1]
20/34
20 Fieldbus Foundation Norway Stavanger 2008
Introducing FNICO
Fieldbus Non-Incendive Concept For fieldbus in Zone 2 and Division 2 hazardous
areas
Complete field network is Non-Incendive EEx nL
Live-workable throughout without gas clearance,
just like Intrinsic Safety Based on FISCO, the Fieldbus Intrinsically Safe
Concept
Easy to install, easy to document, easy to maintain.
-
8/8/2019 Ff in Hazardous Area[1]
21/34
21 Fieldbus Foundation Norway Stavanger 2008
Key benefits of FNICO
Wide choice of suitable field devices: IS Entity certified
FISCO certified
Ex nL certified
Relaxed installation rules Dont need to comply with IS segregation rules
FNICO cables can share cable trunking with non-IScircuits
More available current than FISCO inIIC/Group A: FISCO: 120mA
FNICO: 180mA
-
8/8/2019 Ff in Hazardous Area[1]
22/34
22 Fieldbus Foundation Norway Stavanger 2008
Typical FNICO installation
FNICO power supply
Ex n or IntrinsicallySafe Field wiringhub
Non-incendive or Intrinsically safe Fieldbus devices
Division 2Zone 2
24Vdc24Vdc
FIELD
CONTROL ROOM
Live-workableNon-incendivetrunk and spurs
Live-workableNon-incendivetrunk and spurs
Fieldbus controlsystem (DCS)
Also hasrepeater
function formultipletrunks
-
8/8/2019 Ff in Hazardous Area[1]
23/34
23 Fieldbus Foundation Norway Stavanger 2008
How many field devices?FISCO / FNICO
Entity, IIC/IIB Gas Groups
FISCO, IIC Gas Groups
FISCO, IIB Gas Groups
80mA available, typically 3 - 4 devices
120mA available, typically 6-8devices
265mA available,typically 14-16devices
FNICO, IIB Gas Groups320mA available, typically 18-20devicesZone 2/Division 2
Assumes 17mA per
field device
Zone 1/Division 1
-
8/8/2019 Ff in Hazardous Area[1]
24/34
24 Fieldbus Foundation Norway Stavanger 2008
FF Installation Advices
-
8/8/2019 Ff in Hazardous Area[1]
25/34
25 Fieldbus Foundation Norway Stavanger 2008
Surge protection for fieldbus
Host
DIN rail mount Fieldbussurge protector for thepower supply, host andFieldbus Barrier
Threaded entryFieldbus surge
protector for fieldinstrument
Recommended surge:
If >100m between devices
OR >10m vertically
Fieldbus installations are more vulnerable to surge damage
than conventional point-to-point wiring
-
8/8/2019 Ff in Hazardous Area[1]
26/34
26 Fieldbus Foundation Norway Stavanger 2008
Fieldbus Maintenance and Diagnosis
Diagnostic modules
Fieldbus testers
Devices on net
# transmissions
# failed transmissions
Retransmisson rate
Average noise in diff.bandwidth
Peak noise in diff.bandwidth
Voltage level of all devices
Signal level of all devices
Short Circuit of all dev.
-
8/8/2019 Ff in Hazardous Area[1]
27/34
27 Fieldbus Foundation Norway Stavanger 2008
How to connectNon FF
Field Devices to FF?
-
8/8/2019 Ff in Hazardous Area[1]
28/34
28 Fieldbus Foundation Norway Stavanger 2008
Digital IO and Temperatur Mux
8 DI / 4 DO (low power)
ATEX certified zone 1 & 2
8 ch Temp. Multiplekser
RTD and THC
-
8/8/2019 Ff in Hazardous Area[1]
29/34
29 Fieldbus Foundation Norway Stavanger 2008
FF Remote IO
Remote IO for Zone1
IO modules for Exi and Exe
-
8/8/2019 Ff in Hazardous Area[1]
30/34
30 Fieldbus Foundation Norway Stavanger 2008
Field Mounting
Panel Mounting
FF Displays
1 Address on the net
FISCO compliant
ATEX certified zone 1 & 2
Non-Hazardous area
-
8/8/2019 Ff in Hazardous Area[1]
31/34
31 Fieldbus Foundation Norway Stavanger 2008
FF Structure Example
-
8/8/2019 Ff in Hazardous Area[1]
32/34
32 Fieldbus Foundation Norway Stavanger 2008
Typical Cabinet Layout
32 segments per cabinet side: 24 segments per cabinet side:
with bulk power supply
-
8/8/2019 Ff in Hazardous Area[1]
33/34
33 Fieldbus Foundation Norway Stavanger 2008
In summary... FISCO - IS solution for Zone 1
Intrinsically safe wiring: safe maintenance New IEC standard (60079-27: 2005)
Fieldbus Barrier - High power Trunk Zone 1 More field devices per segment in IIC gases
Compatible with FISCO and ENTITY
FNICO delivers FISCO benefits in Zone 2
Advanced Diagnosis available
Many ways to include non-FF signals
Dont forget surge protection! REMEMBER GROUNDING!
-