    1 Fieldbus Foundation Norway Stavanger 2008

    FOUNDATIONTM Fieldbus inHazardous Areas

    Physical Layer Concept

    Einar S. Huse

    NOREX / MTL

  • 8/8/2019 Ff in Hazardous Area[1]

    2/34

    2 Fieldbus Foundation Norway Stavanger 2008

    FF Basic Information

    FIELD

    CONTROL ROOM

    FF Power Supply

    Fieldbus controlsystem (DCS)

    Trunk

    Spur

    Min. 9VMin. 10mA

    Typical 12-16devices.

    Tx @ 14 mAPos @ 22mA

    31,25 Kbit/s32 Address

    12 dev. @ 1s scan

    Field wiring hubw. Short circuit protect.

  • 8/8/2019 Ff in Hazardous Area[1]

    3/34

    3 Fieldbus Foundation Norway Stavanger 2008

    FF Basic Information

  • 8/8/2019 Ff in Hazardous Area[1]

    4/34

    4 Fieldbus Foundation Norway Stavanger 2008

    Fieldbus in hazardous areas

    Bulk power

    Hazardous area

    ?

    Hazardous Areaprotection?

    FOUNDATION Fieldbus Devices

    FIELD

    CONTROL ROOM

    Field Wiring

    Hub

    Whatapprovalsfor wiringhub andjunction

    box?

    What

    approvalsfor Fieldbusdevices?

    Specialprotectionfor fieldbus

    power

    supply?

    Fieldbus controlsystem (DCS)

  • 8/8/2019 Ff in Hazardous Area[1]

    5/34

    5 Fieldbus Foundation Norway Stavanger 2008

    Methods of protection

    Method of protection Zone 2 Zone 1

    Ex d field devices and Ex ejunction boxes

    Ex i/Intrinsically SafeENTITY or FISCO

    Exe Exi/Fieldbus Barrier

    Ex nL / FNICO

    Ex nA, Non-Arcing

  • 8/8/2019 Ff in Hazardous Area[1]

    6/34

    6 Fieldbus Foundation Norway Stavanger 2008

    Ex-d /Ex-e Fieldbus

    Ex-eField Wiring

    Hub

    Bulk power

    Hazardous areaFOUNDATION Fieldbus Devices

    FIELD

    CONTROL ROOM

    Ex-d / Ex-eInstruments

    Fieldbus controlsystem (DCS)

    Ordinary Safe Area Power SupplySingle or Redundant

    No livemaintenance!

  • 8/8/2019 Ff in Hazardous Area[1]

    7/34

    7 Fieldbus Foundation Norway Stavanger 2008

    Entity Intrinsically Safe Fieldbus

    ENTITYcertified

    devices!

    Bulk power

    Hazardous areaFOUNDATION Fieldbus Devices

    FIELD

    CONTROL ROOM

    Field Wiring

    Hub Max 4Fieldbudevices!

    Fieldbus controlsystem (DCS)

    IS Fieldbus power supplyTypical 80mA output

    For all Ui Uo

    For all Ii Io

    All Pi Po

    Ci + Cc Co

    Li + Lc Lo

  • 8/8/2019 Ff in Hazardous Area[1]

    8/34

    8 Fieldbus Foundation Norway Stavanger 2008

    Introducing FISCO Fieldbus Intrinsically Safe Concept, IEC 60079-27

    Provides more current to IS trunk than earlier Entitymodel, and hence more field instruments

    Proven by tests performed at PTB

    Simplifies design and installation

    Reduces documentation

    First simplification of explosion protection techniques formany years!

    3000 50 100 150 200 250

    273mA

    215mA

    280mA

    PowerSupply

    Supply with cable

    Supply with cableand Terminators

    Ignition current in mA(including Safety Factor)Source: Dr. Ulrich Johannsmeyer, PTB

  • 8/8/2019 Ff in Hazardous Area[1]

    9/34

    9 Fieldbus Foundation Norway Stavanger 2008

    All instruments FISCO certified

    Power Supply must be FISCO certified

    Field cables must conform to the followingspecification:

    loop resistance must be between 15 and 150ohms/km loop inductance must be between 0.4 and 1mH/km

    loop capacitance must be between 45 and 200nF/km

    maximum length of each spur cable is 60m in IIC and IIB

    maximum length of each trunk cable is 1km in IIC or 5km inIIB

    The limits are not restrictive

    typical Fieldbus cable has parameters of 50ohms/km,0.8mH/km and 120nF/km

    FISCO requirements

  • 8/8/2019 Ff in Hazardous Area[1]

    10/34

    10 Fieldbus Foundation Norway Stavanger 2008

    FISCO installation

    FISCO power supply(IIB / IIC)

    FIELD

    CONTROL ROOM

    Intrinsically SafeField wiring hub

    Intrinsically safe FISCO Fieldbus devices

    Zone 1Division 1

    24Vdc24Vdc

    Fieldbus controlsystem (DCS)

    LiveMaintenance

    !

    LiveMaintenance

    !

  • 8/8/2019 Ff in Hazardous Area[1]

    11/34

    11 Fieldbus Foundation Norway Stavanger 2008

    Multiple hazardous area trunks

    Intrinsically safe FISCO Fieldbus devices

    Zone 1Division 1

    24Vdc24Vdc

    Trunk #2 Trunk #3

    Directparallel

    connectionon safe

    area side

  • 8/8/2019 Ff in Hazardous Area[1]

    12/34

    12 Fieldbus Foundation Norway Stavanger 2008

    Redundant FISCO architecture

    Redundant FISCOpower supply

    FIELDZone 1

    CONTROL ROOM

    24Vdc24VdcBulk power input

    Intrinsically safe FISCO Fieldbus devices

    Intrinsically Safe

    Field wiring hub

    IntrinsicallySafe trunkand spurs

  • 8/8/2019 Ff in Hazardous Area[1]

    13/34

    13 Fieldbus Foundation Norway Stavanger 2008

    More field devices with FISCO

    Entity, IIC/IIB Gas Groups

    FISCO, IIC Gas Groups

    FISCO, IIB Gas Groups

    80mA available, typically3 - 4 devices

    120mA available, (140mA)typically 6-8 devices

    265mA available,(280 mA)typically 14-16 devices

    Zone 1Division 1

  • 8/8/2019 Ff in Hazardous Area[1]

    14/34

    14 Fieldbus Foundation Norway Stavanger 2008

    FB Fieldbus Barriers: Exe/Exi concept

    Galvanic isolation and IS barrier in the field.

    Ex-e trunk with higher current available

    Zone-1 mountable fieldbus wiring hub for Intrinsically safe fieldbusdevices

    Supports FISCO and Entity field devices

  • 8/8/2019 Ff in Hazardous Area[1]

    15/34

    15 Fieldbus Foundation Norway Stavanger 2008

    Fieldbus Barrier

    FIELD

    CONTROL ROOM

    Intrinsically safe Fieldbus Devices

    Increased safety(Ex e) trunk

    Fieldbus control system

    IS spurs

    FieldbusBarriers

    Power supplySingel or RedundantUp to 8 channel

    modules available

  • 8/8/2019 Ff in Hazardous Area[1]

    16/34

    16 Fieldbus Foundation Norway Stavanger 2008

    Fieldbus Barrier across Zones

    HOST / LAS

    PowerSupply

    POWERSUPPLIES

  • 8/8/2019 Ff in Hazardous Area[1]

    17/34

    17 Fieldbus Foundation Norway Stavanger 2008

    Comparision of Protection Techniquesused in

    Hazardous Area

  • 8/8/2019 Ff in Hazardous Area[1]

    18/34

    18 Fieldbus Foundation Norway Stavanger 2008

    Entity IS vs. FISCO

    Entity IS FISCO

    Intrinsically safe trunk andspurs?

    Live-working permitted in anypart of field network?

    Simple safety documentation?

    Eliminate cable parametercalculations?

    Gas Group IIB option?

    Max output current 80mA 265mA

    Max spur length 120m 60m

  • 8/8/2019 Ff in Hazardous Area[1]

    19/34

    19 Fieldbus Foundation Norway Stavanger 2008

    FISCO vs. Fieldbus Barrier

    FISCO Fieldbus

    Barrier

    IS Spur? Live Maintenance?

    IS Trunk? Live Maintenance?

    Simple documentation?

    Redundant Power

    Redundant Field Wiring Hub

    Compatible with FISCO fielddevices?

    Compatible with Entity fielddevices?

    Only with spur

    connector!

  • 8/8/2019 Ff in Hazardous Area[1]

    20/34

    20 Fieldbus Foundation Norway Stavanger 2008

    Introducing FNICO

    Fieldbus Non-Incendive Concept For fieldbus in Zone 2 and Division 2 hazardous

    areas

    Complete field network is Non-Incendive EEx nL

    Live-workable throughout without gas clearance,

    just like Intrinsic Safety Based on FISCO, the Fieldbus Intrinsically Safe

    Concept

    Easy to install, easy to document, easy to maintain.

  • 8/8/2019 Ff in Hazardous Area[1]

    21/34

    21 Fieldbus Foundation Norway Stavanger 2008

    Key benefits of FNICO

    Wide choice of suitable field devices: IS Entity certified

    FISCO certified

    Ex nL certified

    Relaxed installation rules Dont need to comply with IS segregation rules

    FNICO cables can share cable trunking with non-IScircuits

    More available current than FISCO inIIC/Group A: FISCO: 120mA

    FNICO: 180mA

  • 8/8/2019 Ff in Hazardous Area[1]

    22/34

    22 Fieldbus Foundation Norway Stavanger 2008

    Typical FNICO installation

    FNICO power supply

    Ex n or IntrinsicallySafe Field wiringhub

    Non-incendive or Intrinsically safe Fieldbus devices

    Division 2Zone 2

    24Vdc24Vdc

    FIELD

    CONTROL ROOM

    Live-workableNon-incendivetrunk and spurs

    Live-workableNon-incendivetrunk and spurs

    Fieldbus controlsystem (DCS)

    Also hasrepeater

    function formultipletrunks

  • 8/8/2019 Ff in Hazardous Area[1]

    23/34

    23 Fieldbus Foundation Norway Stavanger 2008

    How many field devices?FISCO / FNICO

    Entity, IIC/IIB Gas Groups

    FISCO, IIC Gas Groups

    FISCO, IIB Gas Groups

    80mA available, typically 3 - 4 devices

    120mA available, typically 6-8devices

    265mA available,typically 14-16devices

    FNICO, IIB Gas Groups320mA available, typically 18-20devicesZone 2/Division 2

    Assumes 17mA per

    field device

    Zone 1/Division 1

  • 8/8/2019 Ff in Hazardous Area[1]

    24/34

    24 Fieldbus Foundation Norway Stavanger 2008

    FF Installation Advices

  • 8/8/2019 Ff in Hazardous Area[1]

    25/34

    25 Fieldbus Foundation Norway Stavanger 2008

    Surge protection for fieldbus

    Host

    DIN rail mount Fieldbussurge protector for thepower supply, host andFieldbus Barrier

    Threaded entryFieldbus surge

    protector for fieldinstrument

    Recommended surge:

    If >100m between devices

    OR >10m vertically

    Fieldbus installations are more vulnerable to surge damage

    than conventional point-to-point wiring

  • 8/8/2019 Ff in Hazardous Area[1]

    26/34

    26 Fieldbus Foundation Norway Stavanger 2008

    Fieldbus Maintenance and Diagnosis

    Diagnostic modules

    Fieldbus testers

    Devices on net

    # transmissions

    # failed transmissions

    Retransmisson rate

    Average noise in diff.bandwidth

    Peak noise in diff.bandwidth

    Voltage level of all devices

    Signal level of all devices

    Short Circuit of all dev.

  • 8/8/2019 Ff in Hazardous Area[1]

    27/34

    27 Fieldbus Foundation Norway Stavanger 2008

    How to connectNon FF

    Field Devices to FF?

  • 8/8/2019 Ff in Hazardous Area[1]

    28/34

    28 Fieldbus Foundation Norway Stavanger 2008

    Digital IO and Temperatur Mux

    8 DI / 4 DO (low power)

    ATEX certified zone 1 & 2

    8 ch Temp. Multiplekser

    RTD and THC

  • 8/8/2019 Ff in Hazardous Area[1]

    29/34

    29 Fieldbus Foundation Norway Stavanger 2008

    FF Remote IO

    Remote IO for Zone1

    IO modules for Exi and Exe

  • 8/8/2019 Ff in Hazardous Area[1]

    30/34

    30 Fieldbus Foundation Norway Stavanger 2008

    Field Mounting

    Panel Mounting

    FF Displays

    1 Address on the net

    FISCO compliant

    ATEX certified zone 1 & 2

    Non-Hazardous area

  • 8/8/2019 Ff in Hazardous Area[1]

    31/34

    31 Fieldbus Foundation Norway Stavanger 2008

    FF Structure Example

  • 8/8/2019 Ff in Hazardous Area[1]

    32/34

    32 Fieldbus Foundation Norway Stavanger 2008

    Typical Cabinet Layout

    32 segments per cabinet side: 24 segments per cabinet side:

    with bulk power supply

  • 8/8/2019 Ff in Hazardous Area[1]

    33/34

    33 Fieldbus Foundation Norway Stavanger 2008

    In summary... FISCO - IS solution for Zone 1

    Intrinsically safe wiring: safe maintenance New IEC standard (60079-27: 2005)

    Fieldbus Barrier - High power Trunk Zone 1 More field devices per segment in IIC gases

    Compatible with FISCO and ENTITY

    FNICO delivers FISCO benefits in Zone 2

    Advanced Diagnosis available

    Many ways to include non-FF signals

    Dont forget surge protection! REMEMBER GROUNDING!