Field Application of Advanced Residential Air Conditioning
Systems
Presented By Greg Spencer, Residential Cooling Service Coordinator with Lennox Industries
![Page 2: Field Application of Advanced Residential Air Conditioning ... · Volume Tested Combination” (HSVTC) • SEER is a system measurement carried by the condensing ... 27 Room thermostat](https://reader033.vdocument.in/reader033/viewer/2022060601/6055c49044c124622e276896/html5/thumbnails/2.jpg)
2
How Ratings Are Established
Indoor
Outdoor
Size of Outdoor Coil
Size of Indoor Coil Type of expansion device
Efficiency of blower motor
Relative Energy Usage
Efficiency & type of compressor
![Page 3: Field Application of Advanced Residential Air Conditioning ... · Volume Tested Combination” (HSVTC) • SEER is a system measurement carried by the condensing ... 27 Room thermostat](https://reader033.vdocument.in/reader033/viewer/2022060601/6055c49044c124622e276896/html5/thumbnails/3.jpg)
3
How Ratings Are Established• Includes indoor blower energy.“Default Furnace”
measurement generous 365 watts per 1,000 CFM (W/Mcfm) ⇒ Most competitors will use default (A variable speed motor beats the default (Takes off roughly 100 W/Mcfm).
• There are many combinations, so a manufacturer must certify which coil combination will be the “Highest Sales Volume Tested Combination” (HSVTC)
• SEER is a system measurement carried by the condensing units & heat pumps
![Page 4: Field Application of Advanced Residential Air Conditioning ... · Volume Tested Combination” (HSVTC) • SEER is a system measurement carried by the condensing ... 27 Room thermostat](https://reader033.vdocument.in/reader033/viewer/2022060601/6055c49044c124622e276896/html5/thumbnails/4.jpg)
4
Energy Guide Labels(www.eere.energy.gov)
What is ENERGY GUIDE ?• Federal law requires the Energy Guide labels be placed on
central air conditioners and heat pumps.• Energy Guide labels feature energy use and operating cost
information to help shoppers compare appliance models.• ENERGY STAR labels marks appliances with superior
energy efficiency.• ENERGY STAR label may appear on the Energy Guide
label if a particular model qualifies.
![Page 5: Field Application of Advanced Residential Air Conditioning ... · Volume Tested Combination” (HSVTC) • SEER is a system measurement carried by the condensing ... 27 Room thermostat](https://reader033.vdocument.in/reader033/viewer/2022060601/6055c49044c124622e276896/html5/thumbnails/5.jpg)
5
Energy Guide Labels
TopYou’ll find the manufacturer name, model number, type of appliance, and capacity.
![Page 6: Field Application of Advanced Residential Air Conditioning ... · Volume Tested Combination” (HSVTC) • SEER is a system measurement carried by the condensing ... 27 Room thermostat](https://reader033.vdocument.in/reader033/viewer/2022060601/6055c49044c124622e276896/html5/thumbnails/6.jpg)
6
Energy Guide Labels
MiddleThe label shows how a particular model compares in energy efficiency with other models on the market of comparable size and type. Using a line scale, the label indicates where the model falls within a range of most and least efficient units.
![Page 7: Field Application of Advanced Residential Air Conditioning ... · Volume Tested Combination” (HSVTC) • SEER is a system measurement carried by the condensing ... 27 Room thermostat](https://reader033.vdocument.in/reader033/viewer/2022060601/6055c49044c124622e276896/html5/thumbnails/7.jpg)
7
Energy Guide Labels
MiddleCentral air conditioners and heat pumps list Seasonal Energy Efficiency Rating (SEER) or other similar efficiency measures.
![Page 8: Field Application of Advanced Residential Air Conditioning ... · Volume Tested Combination” (HSVTC) • SEER is a system measurement carried by the condensing ... 27 Room thermostat](https://reader033.vdocument.in/reader033/viewer/2022060601/6055c49044c124622e276896/html5/thumbnails/8.jpg)
8
Energy Guide Labels
BottomAn estimate of annual operating costs will appear for appliances that are rated by annual energy consumption. This estimate is based on a recent national average of energy prices and assumes typical operating characteristics.
![Page 9: Field Application of Advanced Residential Air Conditioning ... · Volume Tested Combination” (HSVTC) • SEER is a system measurement carried by the condensing ... 27 Room thermostat](https://reader033.vdocument.in/reader033/viewer/2022060601/6055c49044c124622e276896/html5/thumbnails/9.jpg)
9
Energy Star Program(www.energystar.gov)
What is Energy Star?• Voluntary product labeling program from the U.S.
Environmental Protection Agency and the Department of Energy.
• To earn the Energy Star, products must meet strictly established energy efficiency standards.
• Includes new homes, buildings and over 35 product categories, including HVAC.
• Label is recognized by over 40% of U.S. consumers.
![Page 10: Field Application of Advanced Residential Air Conditioning ... · Volume Tested Combination” (HSVTC) • SEER is a system measurement carried by the condensing ... 27 Room thermostat](https://reader033.vdocument.in/reader033/viewer/2022060601/6055c49044c124622e276896/html5/thumbnails/10.jpg)
10
Energy Star Program
Why?Government-backed symbol• Provides unique third-party credibility• Enhances the trust factor with consumers.• Major HVAC manufacturers currently participate as
ENERGY STAR Partners.• Wealth of consumer information.• Specific resources for HVAC contractors.
![Page 11: Field Application of Advanced Residential Air Conditioning ... · Volume Tested Combination” (HSVTC) • SEER is a system measurement carried by the condensing ... 27 Room thermostat](https://reader033.vdocument.in/reader033/viewer/2022060601/6055c49044c124622e276896/html5/thumbnails/11.jpg)
11
Three Cooling System Loading Conditions
• Full System Load (System working at design conditions – Designed sensible load)
• Part System Load (Minimum to maximum cooling loading – Reduced latent reduction due to run times)
• No System Loading (No sensible cooling requirements – could be need for latent but no sensible loading )
![Page 12: Field Application of Advanced Residential Air Conditioning ... · Volume Tested Combination” (HSVTC) • SEER is a system measurement carried by the condensing ... 27 Room thermostat](https://reader033.vdocument.in/reader033/viewer/2022060601/6055c49044c124622e276896/html5/thumbnails/12.jpg)
12
Full System Loading• System Load Calculation (Manual J –Version 8)
• Equipment Selection & SEER (ARI or manufacturer product catalogs)
• Duct Sizing, Layout and system air balance (Manual D)
• Proper install equipment per installation instructions
• Proper equipment Set up per installation instructions
![Page 13: Field Application of Advanced Residential Air Conditioning ... · Volume Tested Combination” (HSVTC) • SEER is a system measurement carried by the condensing ... 27 Room thermostat](https://reader033.vdocument.in/reader033/viewer/2022060601/6055c49044c124622e276896/html5/thumbnails/13.jpg)
13
Equipment Installation
Different configurations
Proper installation and set up
Correct sized metering device,
![Page 14: Field Application of Advanced Residential Air Conditioning ... · Volume Tested Combination” (HSVTC) • SEER is a system measurement carried by the condensing ... 27 Room thermostat](https://reader033.vdocument.in/reader033/viewer/2022060601/6055c49044c124622e276896/html5/thumbnails/14.jpg)
14
Equipment Installation
Fixed Orifice metering device
![Page 15: Field Application of Advanced Residential Air Conditioning ... · Volume Tested Combination” (HSVTC) • SEER is a system measurement carried by the condensing ... 27 Room thermostat](https://reader033.vdocument.in/reader033/viewer/2022060601/6055c49044c124622e276896/html5/thumbnails/15.jpg)
15
Equipment Installation
No metal to metal rubbing, proper refrigerant pipe routing, proper clearances around unit.
![Page 16: Field Application of Advanced Residential Air Conditioning ... · Volume Tested Combination” (HSVTC) • SEER is a system measurement carried by the condensing ... 27 Room thermostat](https://reader033.vdocument.in/reader033/viewer/2022060601/6055c49044c124622e276896/html5/thumbnails/16.jpg)
16
Equipment Set up (Indoor Blower)
![Page 17: Field Application of Advanced Residential Air Conditioning ... · Volume Tested Combination” (HSVTC) • SEER is a system measurement carried by the condensing ... 27 Room thermostat](https://reader033.vdocument.in/reader033/viewer/2022060601/6055c49044c124622e276896/html5/thumbnails/17.jpg)
17
Equipment Set up (Indoor Blower)
Proper blower speed setting
Balanced distribution system
Latent heat air adjustments
![Page 18: Field Application of Advanced Residential Air Conditioning ... · Volume Tested Combination” (HSVTC) • SEER is a system measurement carried by the condensing ... 27 Room thermostat](https://reader033.vdocument.in/reader033/viewer/2022060601/6055c49044c124622e276896/html5/thumbnails/18.jpg)
18
Equipment Set up (Charging)Several different ways of charging or checking charge in air conditioners and heat pumps in the installation instructions and service manuals.
Always use more than one method to charge or check charge in system.
•Weigh in
•Sub-cooling
•Superheat (Fixed Orifice, piston, flow-meter)
•Approach
![Page 19: Field Application of Advanced Residential Air Conditioning ... · Volume Tested Combination” (HSVTC) • SEER is a system measurement carried by the condensing ... 27 Room thermostat](https://reader033.vdocument.in/reader033/viewer/2022060601/6055c49044c124622e276896/html5/thumbnails/19.jpg)
19
Equipment Set up (Charging)
Fixed orifice charging by superheat
Under part load conditions, the fixed orifice will provide reduced latent capacity as compared to a TXV.
![Page 20: Field Application of Advanced Residential Air Conditioning ... · Volume Tested Combination” (HSVTC) • SEER is a system measurement carried by the condensing ... 27 Room thermostat](https://reader033.vdocument.in/reader033/viewer/2022060601/6055c49044c124622e276896/html5/thumbnails/20.jpg)
20
Equipment Set up (Charging)
![Page 21: Field Application of Advanced Residential Air Conditioning ... · Volume Tested Combination” (HSVTC) • SEER is a system measurement carried by the condensing ... 27 Room thermostat](https://reader033.vdocument.in/reader033/viewer/2022060601/6055c49044c124622e276896/html5/thumbnails/21.jpg)
Indoor Coil Outdoor Coil
High Pressure,High Temperature Vapor
SaturatedVapor
High Pressure, Sub-cooled Liquid
Low Pres.Liquid
SaturatedVapor
SuperheatedVapor
minus -
LL Pres. to Saturation
LL Temperature
equals =Sub-cooling
Basic Refrigeration CircuitProperly Charged Unit
SL Temperature
SL Pres. To Saturation
equals =Superheat
minus - Sub-cooling & SuperheatCalculation Explained
Sens
ible
Late
ntSe
nsib
le
Sens
ible
Late
nt
60°
15°45°
76#
98°10°
108°
220#
![Page 22: Field Application of Advanced Residential Air Conditioning ... · Volume Tested Combination” (HSVTC) • SEER is a system measurement carried by the condensing ... 27 Room thermostat](https://reader033.vdocument.in/reader033/viewer/2022060601/6055c49044c124622e276896/html5/thumbnails/22.jpg)
Indoor Coil Outdoor Coil
High Pressure,High Temperature Vapor
SaturatedVapor
High Pressure, Sub-cooled Liquid
Low Pres.Liquid
SaturatedVapor
SuperheatedVapor
minus -
LL Press. to Saturation
LL Temperature
equals =Sub-cooling
Basic Refrigeration CircuitOver Charged Unit
SL Temperature
SL Pres. To Saturation
equals =Superheat
minus - Sub-cooling & SuperheatCalculation Explained
Sens
ible
Late
ntSe
nsib
le
Sens
ible
Late
nt
60°
15°45°
76#
108°20°
128°
290#
![Page 23: Field Application of Advanced Residential Air Conditioning ... · Volume Tested Combination” (HSVTC) • SEER is a system measurement carried by the condensing ... 27 Room thermostat](https://reader033.vdocument.in/reader033/viewer/2022060601/6055c49044c124622e276896/html5/thumbnails/23.jpg)
Indoor Coil Outdoor Coil
High Pressure,High Temperature Vapor
SaturatedVapor
High Pressure, Sub-cooled Liquid
Low Pres.Liquid
SaturatedVapor
SuperheatedVapor
minus -
LL Press. to Saturation
LL Temperature
equals =Sub-cooling
Basic Refrigeration CircuitUnder Charged Unit
SL Temperature
SL Pres. To Saturation
equals =Superheat
minus - Sub-cooling & SuperheatCalculation Explained
Sens
ible
Late
ntSe
nsib
le
Sens
ible
Late
nt
68°
42°26°
50#
95°0°
182#
95°
![Page 24: Field Application of Advanced Residential Air Conditioning ... · Volume Tested Combination” (HSVTC) • SEER is a system measurement carried by the condensing ... 27 Room thermostat](https://reader033.vdocument.in/reader033/viewer/2022060601/6055c49044c124622e276896/html5/thumbnails/24.jpg)
24
Part and No System Loading• Maximize amount of dehumidification done
during cooling cycle.(Coldest coil)
• Prevent any re-evaporation of condensation back into the supply air system. (Cycle indoor supply fan, condensate management)
• Us of exhaust fans when high humidity is being added to home
• Proper venting of appliances (Ex:dryer)• Elimination of moisture sources.
![Page 25: Field Application of Advanced Residential Air Conditioning ... · Volume Tested Combination” (HSVTC) • SEER is a system measurement carried by the condensing ... 27 Room thermostat](https://reader033.vdocument.in/reader033/viewer/2022060601/6055c49044c124622e276896/html5/thumbnails/25.jpg)
25
Reduction Measures
![Page 26: Field Application of Advanced Residential Air Conditioning ... · Volume Tested Combination” (HSVTC) • SEER is a system measurement carried by the condensing ... 27 Room thermostat](https://reader033.vdocument.in/reader033/viewer/2022060601/6055c49044c124622e276896/html5/thumbnails/26.jpg)
26
Dehumidification Control• Room thermostat with dehumidification
features.• Indoor blower speed option setting• Outdoor fan motor option setting• Hot gas bypass • Reheat • Stand alone dehumidifiers
![Page 27: Field Application of Advanced Residential Air Conditioning ... · Volume Tested Combination” (HSVTC) • SEER is a system measurement carried by the condensing ... 27 Room thermostat](https://reader033.vdocument.in/reader033/viewer/2022060601/6055c49044c124622e276896/html5/thumbnails/27.jpg)
27
Room thermostat with dehumidification features
• Cooling call
• No cooling call
• Integrated with a reheat system
![Page 28: Field Application of Advanced Residential Air Conditioning ... · Volume Tested Combination” (HSVTC) • SEER is a system measurement carried by the condensing ... 27 Room thermostat](https://reader033.vdocument.in/reader033/viewer/2022060601/6055c49044c124622e276896/html5/thumbnails/28.jpg)
28
Equipment Set up (Indoor Blower)
GE ECM 2.3 or 2.5 Premium ECM
X13™Standard ECM
Motor can be programmed to have dedicated dehumidification speed taps.
![Page 29: Field Application of Advanced Residential Air Conditioning ... · Volume Tested Combination” (HSVTC) • SEER is a system measurement carried by the condensing ... 27 Room thermostat](https://reader033.vdocument.in/reader033/viewer/2022060601/6055c49044c124622e276896/html5/thumbnails/29.jpg)
29
Feature Benefit ComparisonFeature PSC X13 ECM 2.3/2.5Input Voltages 120 or 240 120 or 240 120/240Power Connection Relay Constant ConstantControl Signals High voltage Low voltage 24VAC / PWM / DSISettings 2 to 5 2 to 5 VariableAirflow Control Speed Torque Constant Speed Range 800- 1100 600-1100 200-1300Off Delay - Slew with external timer off delay - slew programmableOn Delay - Slews with external timer slew programmableOutput channel none none programmableBearings SB or BB BB BBControl Replacement Motor Motor Modules
![Page 30: Field Application of Advanced Residential Air Conditioning ... · Volume Tested Combination” (HSVTC) • SEER is a system measurement carried by the condensing ... 27 Room thermostat](https://reader033.vdocument.in/reader033/viewer/2022060601/6055c49044c124622e276896/html5/thumbnails/30.jpg)
1000
1050
1100
1150
1200
1250
1300
1350
1400
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8
Air
flow
(CFM
)
Pressure
X13 Airflow Example (300)
(318)(324)
(332) (338)
(348) (363) (372)
(Watts)
High Speed
Low Speed
(237) (247)
(255)
(264) (263)
1000
1050
1100
1150
1200
1250
1300
1350
1400
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8
Air
flow
(CFM
)
Pressure
PSC Airflow Example(535)
(523)
(502)
(475)
(466)
(454)
(417)
(390) (Watts)
High Speed
Low Speed
(462) (427)
(406) (396)
(385)
301000
1050
1100
1150
1200
1250
1300
1350
1400
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8
Air
flow
(CFM
)
Pressure
(215) (253) (282) (314) (348) (362) (409) (426)
ECM 2.3 Airflow Example
(Watts)
Constant CFM
![Page 31: Field Application of Advanced Residential Air Conditioning ... · Volume Tested Combination” (HSVTC) • SEER is a system measurement carried by the condensing ... 27 Room thermostat](https://reader033.vdocument.in/reader033/viewer/2022060601/6055c49044c124622e276896/html5/thumbnails/31.jpg)
31
OR
Connect to Connect to
The interface board (tap board) functions may be on a separate circuit board or built into the OEM’s main circuit board*.
Discrete field selection of airflow settings and comfort options.
• Cooling Airflow
• Heating Airflow
• Trim/Adjust Multipliers
• Climate (delay) Profiles
• Humidistat Option
2.3 or 2.5
![Page 32: Field Application of Advanced Residential Air Conditioning ... · Volume Tested Combination” (HSVTC) • SEER is a system measurement carried by the condensing ... 27 Room thermostat](https://reader033.vdocument.in/reader033/viewer/2022060601/6055c49044c124622e276896/html5/thumbnails/32.jpg)
32
Thermostat Mode (model 2.3)Most widely used method of control for residential systems
A 24vac thermostat can communicate directly to the motor or through an interface board (tap board).
Pin number
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
Common C1 W/W1 Common C2 Delay tap select Cool tap Select Y1 Adjust tap select Output -Return valve (heat pump only) Humidistat (BK) Heat tap select 24 VAC (R) 2nd stage heat (EM/W2) 2nd stage cool (Y/Y2) Fan (G) Output +
ECM 2.3Motor Control
Control (male)
![Page 33: Field Application of Advanced Residential Air Conditioning ... · Volume Tested Combination” (HSVTC) • SEER is a system measurement carried by the condensing ... 27 Room thermostat](https://reader033.vdocument.in/reader033/viewer/2022060601/6055c49044c124622e276896/html5/thumbnails/33.jpg)
33
PWM (Pulse Width Modulation) Mode (model 2.3)
Best suited for commercial systems although some OEM’s have, and are currently using it in residential applications
•Controlled by an external PWM (pulse width modulated) signal
•Suitable for fully variable speed systems (EX: Zoning)
• PWM simply uses two signals, a start/stop signal and a PWM signal
PWM (Duty Cycle)+23 V
+9 V
0 V
D% Demand = x 100(in torque or airflow)
D
T
T
![Page 34: Field Application of Advanced Residential Air Conditioning ... · Volume Tested Combination” (HSVTC) • SEER is a system measurement carried by the condensing ... 27 Room thermostat](https://reader033.vdocument.in/reader033/viewer/2022060601/6055c49044c124622e276896/html5/thumbnails/34.jpg)
34
PWM (Pulse Width Modulation) Mode Cont.Pin number
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
Connected to PWM common NC* Connected to PWM common NC* NC* NC* NC* NC* NC* PWM signal NC* NC* NC* NC* Start/Stop signal: 33VAC or 23VDC NC* * Not Connected
ECM 2.3Motor Control
OR
![Page 35: Field Application of Advanced Residential Air Conditioning ... · Volume Tested Combination” (HSVTC) • SEER is a system measurement carried by the condensing ... 27 Room thermostat](https://reader033.vdocument.in/reader033/viewer/2022060601/6055c49044c124622e276896/html5/thumbnails/35.jpg)
35
DSI (Digital Serial Interface) Mode (model 2.5)Next generation serial communicating systems
• Controlled by Digital Bus System Controller
• Digitally communicates with the motor: Speed, Airflow, Starts, Stops…
12 V
0 V
1000001 0011100 0001110
0.3 sec
Command
1 12 VDC
2 GND
3 Transmit/Receive
4 Transmit/Receive
16 pin connector on motor
Control Board Connection
– 2 leads for power (12 VDC)
– 2 leads for communication
Pin
Communication Example
![Page 36: Field Application of Advanced Residential Air Conditioning ... · Volume Tested Combination” (HSVTC) • SEER is a system measurement carried by the condensing ... 27 Room thermostat](https://reader033.vdocument.in/reader033/viewer/2022060601/6055c49044c124622e276896/html5/thumbnails/36.jpg)
36
X13™ Feature Set
Fully encapsulated electronics (all conductive surfaces potted)3 Phase Brushless DC (single phase AC input)Ball Bearing constructionIntegral control module FCC B EMI filter Approx 1 inch shorter than current Premium ECM 2.3/2.5
![Page 37: Field Application of Advanced Residential Air Conditioning ... · Volume Tested Combination” (HSVTC) • SEER is a system measurement carried by the condensing ... 27 Room thermostat](https://reader033.vdocument.in/reader033/viewer/2022060601/6055c49044c124622e276896/html5/thumbnails/37.jpg)
37
Harness Schematic Options(AC Low Voltage Control)X13™ System Control Board
L
N
G
C
T1
T2
T3
T4
T5
L
N
G
C
G
W
Y
NC *
NC *
Pow
erS
igna
l (1
to 5
+ c
omm
on)
Low
vol
tage
GE Customer * Could eliminate leads* Optional Cooling Selections
![Page 38: Field Application of Advanced Residential Air Conditioning ... · Volume Tested Combination” (HSVTC) • SEER is a system measurement carried by the condensing ... 27 Room thermostat](https://reader033.vdocument.in/reader033/viewer/2022060601/6055c49044c124622e276896/html5/thumbnails/38.jpg)
38
Harness Schematic Options(DC Low Voltage Control)X13™ System Control Board
L
N
G
C
T1
T2
T3
T4
T5
L
N
G
Return
Fan
Heat
Cool
Pow
erS
igna
l (1
to 5
+ c
omm
on)
Low
vol
tage
GE Customer
![Page 39: Field Application of Advanced Residential Air Conditioning ... · Volume Tested Combination” (HSVTC) • SEER is a system measurement carried by the condensing ... 27 Room thermostat](https://reader033.vdocument.in/reader033/viewer/2022060601/6055c49044c124622e276896/html5/thumbnails/39.jpg)
39
Outdoor fan motor option setting
• Motor can be programmed to have dedicated dehumidification speed taps.
• Inputs can be sent to the motor to vary or change speeds depending on demands
![Page 40: Field Application of Advanced Residential Air Conditioning ... · Volume Tested Combination” (HSVTC) • SEER is a system measurement carried by the condensing ... 27 Room thermostat](https://reader033.vdocument.in/reader033/viewer/2022060601/6055c49044c124622e276896/html5/thumbnails/40.jpg)
40
Other Residential HVAC ECM Motor Applications
Outdoor Condenser (ECM 142)
Similar to the 2.3/2.5 construction
Constant speed instead of constant airflow
240vac power input
Optional Remote Mounting
24vac Control Inputs
1/3 Hp
![Page 41: Field Application of Advanced Residential Air Conditioning ... · Volume Tested Combination” (HSVTC) • SEER is a system measurement carried by the condensing ... 27 Room thermostat](https://reader033.vdocument.in/reader033/viewer/2022060601/6055c49044c124622e276896/html5/thumbnails/41.jpg)
Outdoor Condenser (ECM 142)Two Power Inputs- Line voltage and 24vac inputs
Repair- One piece motor replacement- Form drip loops and mount per OEM specifications (center on stator area)
41
Y1 ---------Y2 ---------
![Page 42: Field Application of Advanced Residential Air Conditioning ... · Volume Tested Combination” (HSVTC) • SEER is a system measurement carried by the condensing ... 27 Room thermostat](https://reader033.vdocument.in/reader033/viewer/2022060601/6055c49044c124622e276896/html5/thumbnails/42.jpg)
42
Compressor option (Two stage)
Humidity Control (67% Part Load Capacity)
Simpler Design• Scroll Design• No Shutdown To Change Capacity• Less Applied Components
![Page 43: Field Application of Advanced Residential Air Conditioning ... · Volume Tested Combination” (HSVTC) • SEER is a system measurement carried by the condensing ... 27 Room thermostat](https://reader033.vdocument.in/reader033/viewer/2022060601/6055c49044c124622e276896/html5/thumbnails/43.jpg)
43
Compressor option (Two stage)
BypassPorts Closed
Bypass Ports Open
![Page 44: Field Application of Advanced Residential Air Conditioning ... · Volume Tested Combination” (HSVTC) • SEER is a system measurement carried by the condensing ... 27 Room thermostat](https://reader033.vdocument.in/reader033/viewer/2022060601/6055c49044c124622e276896/html5/thumbnails/44.jpg)
44
Compressor option (Two stage)
SolenoidActuator
Coil
ModulationRing/Bypass
Seals
SolenoidReturnSpring
![Page 45: Field Application of Advanced Residential Air Conditioning ... · Volume Tested Combination” (HSVTC) • SEER is a system measurement carried by the condensing ... 27 Room thermostat](https://reader033.vdocument.in/reader033/viewer/2022060601/6055c49044c124622e276896/html5/thumbnails/45.jpg)
45
Hot gas bypass
![Page 46: Field Application of Advanced Residential Air Conditioning ... · Volume Tested Combination” (HSVTC) • SEER is a system measurement carried by the condensing ... 27 Room thermostat](https://reader033.vdocument.in/reader033/viewer/2022060601/6055c49044c124622e276896/html5/thumbnails/46.jpg)
46
Reheat
![Page 47: Field Application of Advanced Residential Air Conditioning ... · Volume Tested Combination” (HSVTC) • SEER is a system measurement carried by the condensing ... 27 Room thermostat](https://reader033.vdocument.in/reader033/viewer/2022060601/6055c49044c124622e276896/html5/thumbnails/47.jpg)
47
![Page 48: Field Application of Advanced Residential Air Conditioning ... · Volume Tested Combination” (HSVTC) • SEER is a system measurement carried by the condensing ... 27 Room thermostat](https://reader033.vdocument.in/reader033/viewer/2022060601/6055c49044c124622e276896/html5/thumbnails/48.jpg)
48
Reports on Dehumidification
![Page 49: Field Application of Advanced Residential Air Conditioning ... · Volume Tested Combination” (HSVTC) • SEER is a system measurement carried by the condensing ... 27 Room thermostat](https://reader033.vdocument.in/reader033/viewer/2022060601/6055c49044c124622e276896/html5/thumbnails/49.jpg)
49
Report on Dehumidification
![Page 50: Field Application of Advanced Residential Air Conditioning ... · Volume Tested Combination” (HSVTC) • SEER is a system measurement carried by the condensing ... 27 Room thermostat](https://reader033.vdocument.in/reader033/viewer/2022060601/6055c49044c124622e276896/html5/thumbnails/50.jpg)
50
Report on Dehumidification
System research took 20 homes in the Houston area to evaluate the humidity control performance and operating cost of six different integrated dehumidification and ventilation systems
![Page 51: Field Application of Advanced Residential Air Conditioning ... · Volume Tested Combination” (HSVTC) • SEER is a system measurement carried by the condensing ... 27 Room thermostat](https://reader033.vdocument.in/reader033/viewer/2022060601/6055c49044c124622e276896/html5/thumbnails/51.jpg)
51
Report on Dehumidification
![Page 52: Field Application of Advanced Residential Air Conditioning ... · Volume Tested Combination” (HSVTC) • SEER is a system measurement carried by the condensing ... 27 Room thermostat](https://reader033.vdocument.in/reader033/viewer/2022060601/6055c49044c124622e276896/html5/thumbnails/52.jpg)
52
Stand Alone Dehumidifier
![Page 53: Field Application of Advanced Residential Air Conditioning ... · Volume Tested Combination” (HSVTC) • SEER is a system measurement carried by the condensing ... 27 Room thermostat](https://reader033.vdocument.in/reader033/viewer/2022060601/6055c49044c124622e276896/html5/thumbnails/53.jpg)
53
Stand Alone Dehumidifier
![Page 54: Field Application of Advanced Residential Air Conditioning ... · Volume Tested Combination” (HSVTC) • SEER is a system measurement carried by the condensing ... 27 Room thermostat](https://reader033.vdocument.in/reader033/viewer/2022060601/6055c49044c124622e276896/html5/thumbnails/54.jpg)
54
UltraAire System
![Page 55: Field Application of Advanced Residential Air Conditioning ... · Volume Tested Combination” (HSVTC) • SEER is a system measurement carried by the condensing ... 27 Room thermostat](https://reader033.vdocument.in/reader033/viewer/2022060601/6055c49044c124622e276896/html5/thumbnails/55.jpg)
55
UltraAire System
![Page 56: Field Application of Advanced Residential Air Conditioning ... · Volume Tested Combination” (HSVTC) • SEER is a system measurement carried by the condensing ... 27 Room thermostat](https://reader033.vdocument.in/reader033/viewer/2022060601/6055c49044c124622e276896/html5/thumbnails/56.jpg)
56
Filter-Vent System
![Page 57: Field Application of Advanced Residential Air Conditioning ... · Volume Tested Combination” (HSVTC) • SEER is a system measurement carried by the condensing ... 27 Room thermostat](https://reader033.vdocument.in/reader033/viewer/2022060601/6055c49044c124622e276896/html5/thumbnails/57.jpg)
57
Filter-Vent System
![Page 58: Field Application of Advanced Residential Air Conditioning ... · Volume Tested Combination” (HSVTC) • SEER is a system measurement carried by the condensing ... 27 Room thermostat](https://reader033.vdocument.in/reader033/viewer/2022060601/6055c49044c124622e276896/html5/thumbnails/58.jpg)
58
ERV System
![Page 59: Field Application of Advanced Residential Air Conditioning ... · Volume Tested Combination” (HSVTC) • SEER is a system measurement carried by the condensing ... 27 Room thermostat](https://reader033.vdocument.in/reader033/viewer/2022060601/6055c49044c124622e276896/html5/thumbnails/59.jpg)
59
ERV System
![Page 60: Field Application of Advanced Residential Air Conditioning ... · Volume Tested Combination” (HSVTC) • SEER is a system measurement carried by the condensing ... 27 Room thermostat](https://reader033.vdocument.in/reader033/viewer/2022060601/6055c49044c124622e276896/html5/thumbnails/60.jpg)
60
ECM fan & Thermidistat
![Page 61: Field Application of Advanced Residential Air Conditioning ... · Volume Tested Combination” (HSVTC) • SEER is a system measurement carried by the condensing ... 27 Room thermostat](https://reader033.vdocument.in/reader033/viewer/2022060601/6055c49044c124622e276896/html5/thumbnails/61.jpg)
61
ECM fan & Thermidistat
![Page 62: Field Application of Advanced Residential Air Conditioning ... · Volume Tested Combination” (HSVTC) • SEER is a system measurement carried by the condensing ... 27 Room thermostat](https://reader033.vdocument.in/reader033/viewer/2022060601/6055c49044c124622e276896/html5/thumbnails/62.jpg)
62
Conclusions
All of the systems with dehumidification of re-circulated air, separate from the cooling system, exhibited much better humidity control than those with dehumidification of ventilation air only (ERV) and those with dehumidification only as part of the cooling system.
![Page 63: Field Application of Advanced Residential Air Conditioning ... · Volume Tested Combination” (HSVTC) • SEER is a system measurement carried by the condensing ... 27 Room thermostat](https://reader033.vdocument.in/reader033/viewer/2022060601/6055c49044c124622e276896/html5/thumbnails/63.jpg)
63
Training Information• Lennox, Carrier and Trane all offer class-
room or on line training.• Air Conditioning Contractors Association
www.acca.org (Manuals and CDs)• Air Conditioning and Refrigeration Institute
www.ari.org - “CoolNet” for “Certified Products and Ratings”