field experience controlling a dedicated outdoor air system (doas) stanley a. mumma, ph.d., p.e.,...
TRANSCRIPT
Field Experience Controlling a
Dedicated Outdoor Air System (DOAS)
Stanley A. Mumma, Ph.D., P.E., Prof.
Jae-Weon Jeong, Ph.D., Instructor
Department of Architectural Engineering
Penn State University, @ Univ. Park, PA
http://doas-radiant.psu.edu
ASHRAE Denver Symp #2June 26, 2005
2
Presentation outline DOAS and Test Site Defined Controlled Devices, Instrumentation,
and Control The Why & How of Continual
Performance Monitoring Measured Air Diffusion Performance
Index (ADPI) of System:f (Effective Draft Temperature)
Measured Thermal Comfort, PPD Conclusions
3
DOAS Defined for this presentation
100% OA No Recirc.
DOAS Unit W/ Energy Recovery
Cool/Dry Supply, CV
Parallel Sensible Cooling System
High Induction Diffuser
Building With
Sensible and Latent
cooling decoupled
4
Fan Coil UnitsFan Coil Units
Air Handling UnitsAir Handling Units Unitary ACsUnitary ACs
Parallel Terminal Systems
Radiant Cooling PanelsRadiant Cooling Panels
Chilled Beams
DOAS air
Induction Nozzle
Sen Cooling Coil
Room air
5
Building Site
6
An Inside View
7
Another inside view
8
T7FM1
DOAS Schematic
DRY BULB TEMPERATURE (F)
80
40
40
6050
50
60
70
70
80 90 100 120
90
.004
.016
.012
.008
HUMIDITY RATIO (Lbv/Lba)
.028
.024
.020
28
140
168
196
112
84
56
Hu
mid
ity r
atio
(g
rain
s/lb
)wet
dry
EW full Speed
EW Off
EW Modulate
10
Continual PerformanceMonitoring—the Need
Dr. J Woods reports that 5-10% of entire non industrial building stock has building related illnesses.
And 10-25% of the Stock has sick building syndrome.
These are facilities that began their life with no known problems, then degraded.
Also, DOE reports that monitoring could save 0.45 Quads/yr of energy.
11
Categories of performancedegradation
Insufficient diagnostic and alarm tools for early warning of degradation.
Management’s lack of awareness of the economic consequences.
Management’s Indifference.
12
Avoiding Potential Degradation in a DOAS-
Radiant System Compromised SA quantity: equipment
problems, dirt, etc: FM 1 used to detect. Compromised building pressurization,
(infiltration): FM 5 used to detect. Compromised supply air temperature:
detect EW using T6-7-10, or CC T8. Condensation: Cond sensor to detect.Note: sensors color coded with next slide
13
T7FM1
DOAS Schematic
14
ADPI achieved w/ the DOAS system For the test facility, the air flow rate
was about 0.3 cfm/ft2, or about 30% of a VAV (at design). Some have expressed concern about satisfactory air motion.
Experiments were performed in the winter, when convective action was not supplemented by the overhead cooling panels (no panel cooling).
Even in the winter the space has a cooling load—so no convective impact from heating.
15
ADPI Defined An indication of the %of the locations
in a space with a velocity of 70 fpm or less and an EDT between -3F and +2F.
Effective Draft Temperature (EDT):
=(TL-TR)-0.07*(VL-30)Where
, EDT, °FTL, local mean air stream DBT, °F
TR, average room DBT, °F
VL, local mean air stream velocity, fpm
16
Figure 4, Effective Draft Temperature,
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
-5 -4 -3 -2 -1 0 1 2 3
T-Tc (F), [local - ambient air temperature]
Lo
cal M
ean
Air
Vel
oci
ty, f
t/m
in
=2=- 3
ADPI=(34/35)*100=97%, or 97% of the observations were between -3<2 F
=0
The mean velocity at the
35 stations ranged from 12 to 30 fpm (all
below 70 fpm). The EDT for 34
of the 35 locations ranged
from -3<EDT+2.
Therefore theADPI was
[34/35]*100=97%
17
ADPI conclusion
DOAS can deliver exceptionally high ADPI’s; a very favorable finding!
18
Thermal Comfort Thermal comfort is a function of the
following variables that influence metabolic heat transfer: 1. Dry-bulb temperature (DBT),2. Relative humidity,3. Mean radiant temperature,4. Air movement,5. Metabolism, and6. Clothing worn by the occupants.
Comfort, then, is almost completely a function of the space air distribution, provided there is sufficient heating or cooling to meet the thermal and humidity control requirements. (i.e. ADPI important).
19
Measuring Thermal Comfort: Thermal
Comfort Meter
20
Thermal Comfort Test Results
-0.01<PMV<+0.07
Where, PMV subjective scale: +3 hot+2 warm+1 slightly warm0 neutral-1 slightly cool-2 cool-3 cold
21
Predicted Percent Dissatisfied (PPD)
Thermal Comfort Index
51525354555657585
-2.5 -2
-1.5 -1
-0.5 0
0.5 1
1.5 2
2.5
PMV(Predicted Mean Vote)
PP
D
(Pre
dic
ted
% D
issa
stif
ied
)
22
Predicted Percent Dissatisfied (PPD) test
results The PPD for the tests:5.1%<PPD<5.4%
That means almost 95% of the occupants were satisfied.
ASHRAE’s accepted thermal comfort design guidelines permits PPD to be as high as 20%. Satisfying nearly 95% of the occupants is certainly far superior to the ASHRAE target of 80% satisfied .
23
Conclusions Dedicated outdoor air systems (DOAS),
when properly designed and controlled, are capable of delivering very stable and comfortable environments (PPD = 5%).
The authors have experienced no difficulties making the system and controls perform as designed/desired.
Perhaps the keys to success are:– the proper control of the enthalpy wheel,
and – the control of the cooling equipment to
assure that the space latent loads are completely handled by the ventilation air.
24
Conclusions It has been demonstrated that good air
motion is achieved (ADPI of 97%) with ventilation air flow alone (typically around 20-30% of that required for thermal control),
It is not necessary to deliver large quantities of primary air to provide thermal comfort.
As a result, there can be significant air movement energy savings when a CRCP hydronic parallel system is used to meet the balance of the space sensible load not met with the ventilation air.
25
Conclusions Finally, because of the ability of the
DOAS to decouple the space latent control from the sensible control, space relative humidity levels are maintained at the desired design level.
27
Inherent problems with VAV Systems
Poor air distribution. Poor humidity control. Poor acoustical properties. Poor use of plenum and mechanical shaft space. Serious control problems, particularly with
tracking return fan systems. Poor energy transport medium, air. Poor resistance to the threat of biological and
chemical terrorism, and Poor and unpredictable ventilation performance.
28
VAV problems solved with DOAS/Radiant
Poor air distribution. Poor humidity control. Poor acoustical properties. Poor use of plenum and mechanical
shaft space. Serious control problems, particularly
with tracking return fan systems. Poor energy transport medium, air. Poor resistance to the threat of
biological and chemical terrorism, and
Poor and unpredictable ventilation performance.
29
Consequences of system degradation—Ref: Dr. Jim
Woods 20% of US workers experiencing health related symptoms
Another 20% of US workers are experiencing hampered performance
50% of US workers have lost confidence in management’s ability to deal with the situation.
A major economic investment is needed to mitigate each problem and recover workers “goodwill”.
30
Computing Occupancy From Measured CO2 Data Steady state vs transient
computations. Why count people in light of
ASHRAE Std. 62.1-2004?– Floor component.– Occupant component.
– Causes space CO2 concentration to change with occupancy.
– DCV made more difficult.
31
Computing Occupancy From Measured CO2 Data
Transient equation in difference form:
Pep=(V*(N-N1)/+ SA*(N-Ci))/(G*1,000,000)where
Pep = number of occupantsV = the space air volume, ft3
N = the space CO2 concentration at the present timestep, ppmN1= the space CO2 concentration one time step back,
ppm = the time step, min.SA = the supply airflow rate, scfmCi = the CO2 concentration in the supply air, ppm
G = the CO2 generation rate per person, scfm
32
Computing Occupancy From Measured CO2 Data How well does it work?
– As long as the temperatures remain nearly steady, the accuracy is remarkably good (within 2 people for a 40 person space).
– But when the OA temperature drops, error is introduced in the CO2 measurements.
When the SA flow is large (many people), the counts can be off by many people. For the test site, by about +5 people.
33
Measuring Thermal Comfort A thermal comfort meter can measure
the influence the six variables. The instrument uses a heated ellipsoidal
transducer designed to simulate the thermal pattern of a human being. It contains a surface temperature sensor, and a surface-heating element whose power is adjusted automatically by the thermal comfort meter to bring the surface to a temperature similar to that of a thermally comfortable human.
The rate of heat production needed to attain this temperature is used as a measure of the environmental conditions.