FIELDBUSSYSTEMSsensoplex®2sensoplex®2Ex
F 038/07
2 /0802 Hans Turck GmbH & Co.KG • D–45466 Mülheim/Ruhr • Tel. 0208/4952-0 • Fax 0208/4952-264 • E-Mail: [email protected] • www.turck.com
Fieldbus Components
InterlinkBT – a BANNER-TURCK Company for Bus Products
InterlinkBT was founded by the companies TURCK and BANNER and combines the experience and know-how of these two pioneers inthe field of industrial automation, resulting in one of the most complete and diversified lines of bus products.The range of products comprises stations, junctions and connection products for all customary industrial fieldbus systems.
InterlinkBT is the distributor for the American market.
Hans Turck GmbH & Co.KG • D–45466 Mülheim/Ruhr • Tel. 0208/4952-0 • Fax 0208/4952-264 • E-Mail: [email protected] • www.turck.com 3 /0802
System Overview
sensoplex® Ex/sensoplex®2 Ex Bus Systems Page
sensoplex®2 – Overview 4
sensoplex®2 – Master Stations 6
sensoplex®2 – Input/Output Stations 8
sensoplex®2 Ex – Overview 14
sensoplex®2 Ex – Junction Boxes 16
sensoplex®2 Ex – Input Modules 18
sensoplex®2 Ex – Output Modules 22
sensoplex®2 Ex – Terminal Modules 24
Terminating Resistors 26
System Accessories 28
Coaxial Components 30
Special Cables 32
Special Plugs 36
4 /0802 Hans Turck GmbH & Co.KG • D–45466 Mülheim/Ruhr • Tel. 0208/4952-0 • Fax 0208/4952-264 • E-Mail: [email protected] • www.turck.com
Fieldbus Components
The Fieldbus Systemfor Factory Automation
In the industrial automation segment,field bus systems are used in industrialmanufacturing to cope with increasingcompetitive pressures and for costeffectiveness. Here too, like in mostautomated processes, the automotiveindustry has been a pioneer to newtechnologies.
Time consuming tool changes andmaintenance in more and more complexmanufacturing tools are creating wiringnightmares. The conventional connectionmethods such as hardwiring of hundredsand hundreds of sensors and actuators,one by one, are generating a lot ofdown-time on the tools (cables breakfrequently in the first 50 cm). Becausethese methods are costly and result indelay and disruption, the automotiveindustry has been searching for a moreprogressive solution.
Efforts were made to replace the conven-tional connection methods (point to pointwiring) between sensors and actuatorswith a new alternative by bundling themtogether in the main control cubicles.This new wiring system consisted of:
– main cabinets on the platform– auxiliary cabinet boxes on the tools– plug-in subdistribution boards
(junction boxes) on the tools
Although this system did reducemaintenance times, it also proved to beextremely time consuming and expensive(see figure 1).
The next step came logically: A rugged,industrial fieldbus was needed to adjustmore flexibly to the prevailing methodsand at the same time keep wiring andinstallation during tooling changes,retrofitting and for new installations costeffective.
For this task, namely the direct fieldconnection of the sensor/actuator level,TURCK developed in 1987 the master-slave fieldbus system sensoplex® as anew alternative for networking sensors andactuators with various controls.Since then, the user friendly and practicalapproach of the sensoplex® remote I/O
system has been utilized in numerousapplications and is the ”fieldbus system”of choice for machine integratedinstallations.
Not only end users were able to benefitfrom these advantages; many first timeusers have jumped on the bus to increasetheir competitiveness, to lower first timeinstallation costs, and to reduce ever risinggeneral costs.
Meeting User Requirements
sensoplex® removes system limitations forthe user by providing all the prerequisitesfor the use of fieldbusses in machine engi-neering and production system planning:
1. Connection to the PLC Without Additional Software
The main stations have direct access tothe PLC bus structure, they are engi-neered and developed in conjunction withmajor control manufacturers (andapproved by them). Because of the PLCspecific interface of the master stations, noadditional software is required and the usercan operate with the original programming.In addition, he can benefit from the fullsupport of the PLC manufacturer becauseno ”foreign cards” are used in the PLCs.One master station can have up to 32substations connected and its modularconfiguration matches all kinds of differentrequirements.
2. Sturdy Substations –Suitable for Direct Mountingon the Machine
The substations are compact I/O stationsmade of die-cast aluminium or stainlesssteel housings, Protection Class IP67.They can be mounted directly on themachine. Up to 8 sensors or actuatorscan be linked to each substation.
3. Peripheral Interface -Made Possible Through Simpleand Safe Connections
All system components are connectedwith standard M12 x 1 connectors, sothey are easy to install and ensure safeconnections.
4. Data Transmission - Reliable -Fast Response Times
To transfer the huge amount of datagenerated and to provide power supplyto the input substations, point-to-pointconnections between the stations aremade by means of a coaxial cable with75 Ω surge impedance, providingmaximum data security against externalinfluences, very low interference suscep-tibility, and a high data transfer rate.To eliminate possible transmission errors,sensoplex® operates with the FSK (fre-quency shift keying) method that providesadditional data security through exclusiveOR monitoring and time integration.
These safety measures are vital for all de-vices that reside at the lowest level of thebus hierarchy, where 100% of the datamust be available all the time to satisfythe time critical processes of this level.
Depending on the system configuration,sensoplex® operates at a response timeof max. 5 ms. which meets the require-ments for real time processing.
5. Power Supply to Substations -Without Any Additional Wiring
All substations as well as all connectedsensors and small loads are powered bythe coaxial cable which is also used fordata interchange. This eliminates the needfor many additional supply cables.
sensoplex® 2 – Overview
Hans Turck GmbH & Co.KG • D–45466 Mülheim/Ruhr • Tel. 0208/4952-0 • Fax 0208/4952-264 • E-Mail: [email protected] • www.turck.com 5 /0802
6. Retrofitting & Expansion –Without Additional Software
Compared to bus systems in ring topo-logy, with sensoplex® it is always possibleto increase or decrease the number ofsubstations within the network processeswithout any additional software. Theaddress of each single station is not deter-mined by its physical location - eachstation is identified by an address pro-grammed by the user with DIP-switcheslocated on the stations itself. This is ofspecial advantage in systems expansionsor updates.
7. Implemented System Diagnostics -For Fast ”On The Spot”Error Detection
Because of the high mechanical stress onthe lowest field level where all sensors,actuators, substations, etc. reside, exter-nal faults can occur such as a break inthe coaxial cable due to a mechanicaldisturbance. Therefore, the user has tohave a system that allows possible errorsto be detected immediately ”on the spot”and eliminated through easy replacementof the connected field devices.sensoplex® provides the followingstandard diagnostics:– bus cable malfunction
(wire-break/short-circuit)– configuration error– wire-break/short-circuit in the sensor/
actuator bus– non reporting substation
sensoplex® Bus Systems – for LimitlessApplications
sensoplex® is available in the followingversions for a variety of industrialapplications:
sensoplex®2The multifunctional bus system for abroad spectrum of applications
sensoplex®2 ExThe intrinsically safe bus system
sensoplex®2 Ex, the intrinsically safesystem for use in potentially hazardousareas was developed upon suggestionsfrom large users in the chemical and
petrochemical industry after their positiveexperiences with the standard sensoplex®.The intrinsically safe sensoplex®2 Ex hasbrought lasting improvements and greatcost advantages to the a. m. industry:
Standard Class I intrinsically safe field de-vices can be directly connected to the busstations, without any additional safetymeasures (such as explosion-proof enclo-sures), thus reducing installation costs toan absolute minimum because there is noneed to install the main cabinets intoexpensive enclosures.Obviously, sensoplex®2 Ex offers thesame advantages as the basicsensoplex®2 system.
sensoplex®2 is the natural extension ofthe sensoplex® system. The principalcharacteristics of the basic system(pages 4 + 5, points 1…7) are the same,but its functionality has been extendedthus offering more opportunities such as:
1. Master station with PROFIBUSinterface, allowing the user to communi-cate with different-brand PLCs with aPROFIBUS Master interface.
Depending on the type used, up to64 substations can be connected toone of the new master stations. Also,these new master stations can easilybe added to already existing installa-tions without reconfiguring the entiresystem. Their advantage includeextended system diagnostics andincreased address capabilities.
2. Substations in various configurations,such as:
… Die-cast aluminium housings withProtection Class IP67 with four, sixand eight channels. The four channelsubstations make sensoplex®2easier to apply for material handlingapplications where sensors andactuators are widely distributed.
… 8 channel terminal versions withProtection Class IP20 for directmounting in main cabinets (andoperator control terminals in thefield).
Important Hints Regarding theCompatibility of the Bus Systems:
1. With a few exceptions (see therespective references in the specificsections), all sensoplex® compo-nents can operate with sensoplex®2master stations. That means thatadditional new components can beadded at any time to a sensoplex®
system that has a sensoplex®2master station.
2. sensoplex®2 substations work onlyin connection with sensoplex®2master stations.
6 /0802 Hans Turck GmbH & Co.KG • D–45466 Mülheim/Ruhr • Tel. 0208/4952-0 • Fax 0208/4952-264 • E-Mail: [email protected] • www.turck.com
Fieldbus Components
Design and Functions
The sensoplex® master station consists ofthese three primary components:
– The sensoplex® master board whichconducts continuous cyclic polls of allsubstations; each master station hasthe same identical master board.
– Dual Port-Memory (DPM) for datainterchange between the PLC andMaster.
– PLC specific interface card forcommunication between the PLC andthe master station; this is typicallya standard card of the specificmanufacturer (for instance theSiemens IM318/IM318M).
Together, the above components makethe best possible interface to the specificoperative controls and eliminate the needfor any special synchronization methods.
Such an arrangement providessignificant advantages for the user:
Regardless of what PLC is used,sensoplex® always performs in thesame manner.
Communication with the substationsoccurs according to the standarddigital I/O processing level.
For the most part, the existing PLCspecific user program can be used.
The warranties provided by the PLCmanufacturers remain fully effective.
This improved diagnostic function of themaster station greatly simplifies faultdetection and system restart.
This check procedure makes shorttransmission/response times of thesystem possible and allows functionaltesting of all units to see whether thesystem configuration is correct.
Configuration
Because of the different addresspossibilities, a configuration cycle isperformed by the master station atsystem start-up. The master station canexecute that in several different ways:
The configuration cycle is initiated byactivating the respective function key(accessible after opening the cover)followed by switching the power supplyON. If the supply voltage is already turnedON, a cold start must be effected with theactivated function key by pressing RESET.
At each additional start-up, the masterstation compares the actual status of thesystem with the memory configuration.For different applications that involvetooling/device changes, up to eightdifferent system configurations can bestored.
The following configuration cycles arepossible:
– Auto key: automatic addressing.– Load key: address allocation via internal
assignment EEPROM (part of masterstation). If a memory card is plugged in,its content is first written to theEEPROM. Then the addresses areassigned.
– Save key: determines the busconfiguration at the moment, savesthis configuration into the EEPROM,and if available, into the memory card.
Moreover, the sensoplex® system alsooffers extended system diagnostics:
Example: Normally, an alarm condition or amalfunction such as a short-circuit or wirebreak in a PLC input card would generate anumber of measurements to identify thefault location. All interface terminals wouldhave to be undone to find the source of thefault. - Not so with sensoplex®. Thesensoplex® master can rapidly identify theexact location of the source of theproblem.
Therefore:
– No additional measurements - simplyreplace the defective part (sensor orprewired cable).
– Installation times reduced to aminimum.
Additionally, the master stations are alsoused as central power supply for allconnected components; 24 VDC, max. 4 Acan be supplied via a M12 x 1 connector,thereby supplying the necessary power toall substations and connected sensors.
The sensoplex®Ex system also suppliespower via the bus to all connectedactuators.
Another remarkable characteristic of thesensoplex® system is the system start-up.
The sensoplex®2 master automaticallyscans the existing configuration to verifywhether it is identical to what the user hasprogrammed and checks if the entiresystem is properly connected right downto the terminating resistor.
At every system start-up (power supplyOFF/ON or RESET), all data memory of themaster station is cleared and reset to 0.The master station then checks the entirecoaxial cable for short-circuit or wire-breakas well as the data line terminating resistorand all the connected stations.If a fault is detected during the first check,the master station will interrupt the restart(indicated by an error LED on the masterstation). Any malfunctions within thesystem and the error location, for instancein case of bus errors, is indicated via thehandheld diagnostic monitor whichidentifies the location of the malfunction(wire-break or short-circuit) in the bussegment.
sensoplex®2 – Master Stations
!"#
$"%&
!"
$'
Hans Turck GmbH & Co.KG • D–45466 Mülheim/Ruhr • Tel. 0208/4952-0 • Fax 0208/4952-264 • E-Mail: [email protected] • www.turck.com 7 /0802
sensoplex®2 – Master Stations
Type
Ident-No.
Type of interface
Master stations (HS) per PLC
Input stations (ES) per master (HS)
Output stations (AS) per master (HS)
Input stations/output stations(ES/AS) per master (HS)
I/O points per PLC
Cycle time each ES/AS
Housing description
Dimensions (w x h x d)
Housing material
Degree of protectionIEC 60529/EN 60925 (DIN 40050-9)Operating temperature
Display/diagnostics
Operating voltage
Output current
Signal attenuation
Isolation
Accessories
HS-S5 04
68 901 12
PROFIBUS-DP
122
32
32
64
62 464
150 µs
modular
120 x 180 x 66
die-cast aluminium,black, with epoxy
resin powder coating
IP65
0...60 °C
LEDs/ hand-held
24 VDC ± 10 %including ripple
≤ 4 A
≤ 15 dB
yes
9 pole Sub-DSinec L2-DP cabel
HS-DN 03/04
68 901 35/68 901 36
DeviceNet™
63
8/32
8/32
8/64
4 032/32 256
150 µs
modular
120 x 180 x 66
die-cast aluminium,black, with epoxy
resin powder coating
IP65
0...60 °C
LEDs/hand-held
24 VDC ± 10 %including ripple
≤ 4 A
≤ 15 dB
yes
5 pole 7/8”connector
HS-MOD 03
68 901 30
Modbus Plus
32
32
32
64
16 384
150 µs
modular
120 x 180 x 66
die-cast aluminium,black, with epoxy
resin powder coating
IP65
0...60 °C
LEDs/hand-held
24 VDC ± 10 %including ripple
≤ 4 A
≤ 15 dB
yes
Modbus Plusconnector
HS-MB 03/04
68 0901 19/68 0901 20
ModbusRS232 / RS485
1/32
32
32
64
512/16384
150 µs
modular
120 x 180 x 66
die-cast aluminium,black, with epoxy
resin powder coating
IP65
0...60 °C
LEDs/ hand-held
24 VDC ± 10 %including ripple
≤ 4 A
≤ 15 dB
yes
9 pole Sub-D
8 /0802 Hans Turck GmbH & Co.KG • D–45466 Mülheim/Ruhr • Tel. 0208/4952-0 • Fax 0208/4952-264 • E-Mail: [email protected] • www.turck.com
Fieldbus Components
Substations for the sensoplex® system areseparate modules for either input or outputfunctions.
– Input stations:ES 40, ES 80, ES 82, ESM 80, ESK 80
– Output stations:AS 40, AS 80, ASK 80
Mechanical Characteristics
Plug-in substations with M12 x 1connectors are designed to meetprotection class IP67.They are: shock resistant impervious to dust, moisture
or foreign material they offer protection against
the immersion in water for 30 minutesat 1 meter (IEC 60529/EN 60529)
They are rated for an operatingtemperature from -25...+70 ºC.
The terminal versions are rated forProtection Class IP20 and are suitable formounting into control cabinets. They canbe used at an operating temperatureof 0...60 ºC.
Electrical Characteristics
Power (24 VDC) is supplied to all buscomponents and connected sensors viathe coaxial cable. The common of thesystem is on the external conductor(shield) of the coaxial cable and thereforeon the coaxial plugs also. For safety duringmaintenance and operation, make surethat the entire system is isolated fromearth.
The coax receptacles are isolated from thehousing of the sensoplex® substations, sothey can be installed anywhere in thesystem. To guarantee faultfree operation,a check of isolation between the inner andouter conductor, and of isolation fromearth of all coax cables before systemstart-up is required.
Attenuation
The throughput attenuation of onesubstation is 0.3 dB. The maximumattenuation of the whole system is 15 dBfor each master station, including allcomponents and coaxial cables. If this
value is higher, or if the data line distance isgreater than 300 m, an amplifier must beinstalled (see section ”Accessories”). Thesystem will not work properly if theattenuation values are too high.
Input Stations
Input stations are used to receive binarysignals from the field. Input data is scannedby the master station in a cyclic manner.For proper functioning, each input stationmust be assigned to a specific address.
Each input station accommodates up to8 sensors.– Power supply via the coaxial bus.– Total current consumption ≤ 150 mA.– Supply voltage: 10...30 VDC.
The inputs accept current sourcing signalsfrom:– 3-wire pnp sensors– 2-wire DC sensors– dry contacts
The connections are made either withM12 x 1 connectors, or with screwterminals.
The following function parameters of theinput stations can be set eitherautomatically or via DIP-switches:– switching output
(either 3- or 2 wire DC sensors)– input delay time
Versions with terminal clamps are used tosend binary signals to the coaxial bus viathe mother board ESM 80. They areconnected by ribbon cables.
Output Stations
The output stations supply binary processsignals to the connected loads (actuators).The data received from the master stationis retained in the output area of the outputstation.Power supply for the output stations isprovided through an additional connector.If a power failure occurs, all output circuitsare set to 0 (turned off) until new data istransmitted.Various types of output devices can beconnected to each output station.These include:– valves– relays– indicators
The specifications for all output devices are:– Operating voltage: 18...30 VDC– The output current per channel is
0.5 A for all versions.
Each output station has separate,programmable functions that can be seteither automatically or via DIP-switches:– Switching status of outputs– Double scanning
I/O Allocation
I/O allocation addressing is done manuallywith built-in DIP-switches or automaticallyduring system start-up (built-in EEPROM -sensoplex®2 substations only). It isimportant to make sure that there is onlyone address in the system for each station(automatic response check withsensoplex®2)
Diagnostics
All substations are equipped with statusand diagnostic LEDs. These makediagnostics and monitoring during start-upand operation of the system possible(check for wire-break or short-circuit).In addition, system diagnostics can alsobe done via the hand-held monitor,DEA 80 for sensoplex®2 only.
Important:sensoplex®2 substations work only inconnection with sensoplex®2 masterstations!
sensoplex®2 – Input/Output stations
Hans Turck GmbH & Co.KG • D–45466 Mülheim/Ruhr • Tel. 0208/4952-0 • Fax 0208/4952-264 • E-Mail: [email protected] • www.turck.com 9 /0802
Programming and parameterisation of the ES8...
185,
5
6491
56
175,
5
ø 4,3
b5
b6
b7
b8
Function
Power
Fault
b4
b3
b2
b1
12345678910
1248
163264
12345678910
1248
163264
onoffonoff
DIP switches
Address 127
Decimal value
Input delay (on = 2 ms, off = 0,25 ms)
Fault monitoring (on = active, off = off)
Signal flow direction(on = NAMUR, off = permaprox®)
Address
Selectable
Specified value via user programmable bus parameters Addressing via DIP switches
Important:
Pins 2 of two adjacentcouplings (1/2;3/4;5/6;7/8)are linked internally,see fig.
4
2
4
2
Bridge-connectorRS 4.4-ES
!"
!"
!"
###
$%&' (
&' (
)*
+,,))%(-
.-* / %/-*,) /-,- %/-,-/
01
01
*-,,*.
-,-
Programming and parameterisation of the AS8...
10 /0802 Hans Turck GmbH & Co.KG • D–45466 Mülheim/Ruhr • Tel. 0208/4952-0 • Fax 0208/4952-264 • E-Mail: [email protected] • www.turck.com
Fieldbus Components
Dimensions – Input Station
(
%&
%
!
"
!!
)(*) *) *)*
)*)+*),*)-*
"
!
)(*) *) *)*
)*)+*),*)-*
.
!
Hans Turck GmbH & Co.KG • D–45466 Mülheim/Ruhr • Tel. 0208/4952-0 • Fax 0208/4952-264 • E-Mail: [email protected] • www.turck.com 11 /0802
/(
/
/
/
%&
!
"
!!
!
!!
/-
/,
/+
/
%&
/
/
/
/(
!!
"
!!
!!
!!
/(*
/ *
/ *
/*
/*
/+*
/,*
/-*
.
!
Dimensions – Output Station
12 /0802 Hans Turck GmbH & Co.KG • D–45466 Mülheim/Ruhr • Tel. 0208/4952-0 • Fax 0208/4952-264 • E-Mail: [email protected] • www.turck.com
Fieldbus Components
ESM 80
68 902 01
ABS plastic
80 x 160 x 60IP20
via twothrough-holes,
DIN rail0...+60 °C
8
12...30 VDC(via coaxial cable)
–
≤ 50 mA
8 sensors ormechanical contacts,
pnp, 24 VDC10...30 VDC
≤ 150 mA≤ 500 Hz
electronic
–
DIP-switchEEPROM
0.2 dB
coaxial ribbon cable,screw terminal
–LEDs
hand-held DEA 80
both
ESK 80
68 902 03
ABS plastic
80 x 160 x 60IP20
via twothrough-holes,
DIN rail0...+60 °C
8
12...30 VDC(ribbon cable)
–
≤ 50 mA
8 sensors ormechanical contacts,
pnp, 24 VDC10...30 VDC
≤ 150 mA≤ 500 Hz
electronic
–
DIP-switchEEPROM
–
ribbon cable,screw terminal
–LEDs
hand-held DEA 80
both
sensoplex®2 – Input Stations
Type
Ident-No.
Housing material
Dimensions (w x h x d)Protection class(IEC 60529/EN 60529)Mounting
Operating temperature
Input circuits
Supply voltage
Load circuits
Power/Current consumption
Inputs
– Supply voltage– Current consumption– Switching frequency
Short-circuit protection
Signal isolation
Adjustments and address selectionParameter assignmentSignal attenuationConnections:– Data line– Inputs/outputs– Current supplyDiagnostics
Alarm indication for malfunctions,short-circuits and wire-break
ES 40
68 902 04
die-cast aluminium,black, with epoxy
resin powder coating
64 x 115 x 35IP67
via twothrough-holes
-25...+70 °C
4
12...30 VDC(via coaxial cable)
–
≤ 50 mA
4 sensors ormechanical contacts,
pnp, 24 VDC10...30 VDC
≤ 150 mA≤ 500 Hz
electronic
–
DIP-switchEEPROM
0.2 dB
coaxial plugM12 x 1
–LEDs
hand-held DEA 80
both
ES 80/82
68 902 08 / 68 902 11
die-cast aluminium,black, with epoxy
resin powder coating
64 x 185 x 35IP67
via twothrough-holes
-25...+70 °C
8
12...30 VDC(via coaxial cable)
–
≤ 50 mA
8 sensors ormechanical contacts,
pnp, 24 VDC10...30 VDC
≤ 150 mA / 200 mA≤ 500 Hz
electronic
–
DIP-switchEEPROM
0.2 dB
coaxial plugM12 x 1
–LEDs
hand-held DEA 80
both
Hans Turck GmbH & Co.KG • D–45466 Mülheim/Ruhr • Tel. 0208/4952-0 • Fax 0208/4952-264 • E-Mail: [email protected] • www.turck.com 13 /0802
sensoplex®2 – Output Stations
AS 40
68 903 04
die-cast aluminium,black, with epoxy
resin powder coating
64 x 115 x 35IP67
via twothrough-holes
-25...+70 °C
4
12...30 VDC(via coaxial cable)
18...30 VDC
≤ 50 mA
4 actuators,24 VDC, 0.5 A18...30 VDC
0.5 A/100 % ED100 Hz
electronicpower off/
disconnecting loadbetween supply voltage,
outputs and coaxialcable
DIP-switchEEPROM
0.2 dB
coaxial plugM12 x 1M12 x 1
LEDshand-held DEA 80
short-circuit
ASK 80
68 903 03
ABS plastic
80 x 160 x 60IP20
via two through-holes,
DIN rail
0...+60 °C
8
12...30 VDC(ribbon cable)18...30 VDC
≤ 50 mA
8 actuators,24 VDC, 1.6 A18...30 VDC
1.6 A/100 % ED100 Hz
electronicpower off/
disconnecting loadbetween supply voltage,
outputs and coaxialcable
DIP-switchEEPROM
–
coaxial ribbonscrew terminalscrew terminal
LEDshand-held DEA 80
short-circuit
AS 80
68 903 08
die-cast aluminium,black, with epoxy
resin powder coating
64 x 185 x 35IP67
via two through-holes
-25...+70 °C
8
12...30 VDC(via coaxial cable)
18...30 VDC
≤ 50 mA
8 actuators,24 VDC, 0.5 A18...30 VDC
0.5 A/100 % ED100 Hz
electronicpower off/
disconnecting loadbetween supply voltage,
outputs and coaxialcable
DIP-switch EEPROM
0.2 dB
coaxial plugM12 x 1M12 x 1
LEDshand-held DEA 80
short-circuit
Type
Ident-No.
Housing material
Dimensions (w x h x d)Protection class(IEC 60529/EN 60529)Mounting
Operating temperature
Input circuits
Supply voltage
Load circuits
Power/Current consumption
Outputs
– Output voltage– Output current– Switching frequency
Short-circuit protectionreset
Signal isolation
AdjustmentsParameter assignmentSignal attenuationConnections:– Data line– Inputs/outputs– Current supplyDiagnostics
Alarm indication for malfunctions,short-circuits and wire-break
14 /0802 Hans Turck GmbH & Co.KG • D–45466 Mülheim/Ruhr • Tel. 0208/4952-0 • Fax 0208/4952-264 • E-Mail: [email protected] • www.turck.com
Fieldbus Components
Bus system sensoplex®2 Ex –system configuration
sensoplex®2 was developed for standardapplications and is based on the first gene-ration sensoplex® system. sensoplex®2 Exoffers the extended scope of operationsprovided by the sensoplex®2 systemincluding a variety of modules, improveddiagnostic features, a comprehensiverange of functions and extended cablelengths.
The system configuration of sensoplex®2Ex is shown in Fig. 1 (see page 15).
All sensoplex® components arecompatible with sensoplex®2, i.e. allsensoplex® devices apart from the mastercan be used in sensoplex®2 installations.The main features of the sensoplex®2 Exmaster are:
„force“ functions automatic addressing wire-break and short-circuit monitoring
of the bus line including errorlocalisation
extended address area (depending onthe control system)
The intrinsically safe junction box VB 14-Exseparates the non-intrinsically safe bus linefrom the intrinsically safe bus line. The non-intrinsically safe bus line is separated intofour intrinsically safe branches. Eachbranch provides connection for up to 8substations amounting to a total of 32stations without additional I.S. safetymeasures.
8-channel I/O modules for binary sensorsand actuators are available.Up to 256 I/O points can be connected viaone VB 14-Ex/CS in the hazardous area.
The terminal version, featuring degree ofprotection IP20, is suitable for use incabinets. For direct mounting on themachine, the plug-in version, degree ofprotection IP67, is recommended.
Fieldbus systems have played animportant role in industry for some timenow. Most industrial applications whichrequire complex interconnection arerealized with bus systems because theyoffer simple and error-free installation,quick diagnostics and savings in materialand installation times.
TURCK has been one of the firstmanufacturers of bus systems forindustrial applications.Today TURCKoffers busstop® solutions for the entirespectrum of automation, whether youwant to integrate binary sensors andactuators into a bus system or plan tonetwork intelligent field devices.
The bus system sensoplex®2 Ex isspecially designed for installation inhazardous areas. This intrinsically safe bussystem is the natural extension of the bussystem sensoplex® which is widely used inbody and assembly lines in the automotiveindustry as well as in many different anddemanding industrial environments.
Having been developed for suchdemanding applications, the main systemcharacteristics also meet the high require-ments of the chemical industry in regardsto data security, EMC, RFI etc.
Bus system sensoplex®2 Exsystem characteristics:
deterministic master/slavesystem for intrinsically safe applications
high noise immunity short reaction cycles < 5 ms degree of protection IP67 all components pluggable data and power supply via one cable
(coaxial cable) - no additional powersupply for peripheral componentsnecessary
I/O-modules can be mounted directlyin the hazardous area without additio-nal protective measures.
sensoplex®2 Ex – Overview
Sensors according to EN 60947-5-6(NAMUR) or volt-free contacts can beconnected to the input stations. Theoutputs are designed for connection oflow-power loads.
The optimised electronics allow for cablelengths of up to 250 m per branch evenwith a fully configured system.
Hans Turck GmbH & Co.KG • D–45466 Mülheim/Ruhr • Tel. 0208/4952-0 • Fax 0208/4952-264 • E-Mail: [email protected] • www.turck.com 15 /0802
Fig. 1 System configuration bus system sensoplex®2 Ex
+) +!23'456&78+'9-'*-% 1399-
!)
:+
$+2+
72;< +
2+
$+2+ 2+
1$984
$+
'8
$
2+
$+
2+/2+#2;$+/$+2;
'=
5$> *
9
);#-/!&<5
. *)!)
:?-@2;
5$> *);#)$
)-*
sensoplex®2 Ex – System configuration
16 /0802 Hans Turck GmbH & Co.KG • D–45466 Mülheim/Ruhr • Tel. 0208/4952-0 • Fax 0208/4952-264 • E-Mail: [email protected] • www.turck.com
Fieldbus Components
1- or 4-channel junction boxesfor separation of the coax-businto one or four intrinsically safebranches
Die-cast aluminium housing,degree of protection IP67
1 up to 4 intrinsically safe outputs[EEx ib] IIB
Intrinsically safe bus linesswitched individually
Intrinsically safe junction box VB 11-Ex
The intrinsically safe VB 11-Ex serves forcurrent- and voltage reduction on thecoax-bus branch to provide an intrinsicallysafe bus line.The intrinsically safe junction-box is anassociated apparatus and must beinstalled in the safe area.
The max. cable lenght off the intrinsicallysafe bus line is limited to 250 m. Up toeight 8-channel substations can beconnected to the intrinsically safe bus line.
Intrinsically safe junction-boxVB 14-Ex/CS
The junction-box VB 14-Ex/CS separatesthe coax-bus into four intrinsically safecoax-bus branches for installation in thehazardous area. The intrinsically safejunction-box is an associated apparatusand must be installed in the safe area.
The intrinsically safe junction-box VB 14-Ex/CSprovides full sensoplex®2 functionalityincluding automatic addressing of thesubstations, error localisation on thecoaxial-bus and bus operations such asparameterisation, configuration and forcingvia the handheld DEA 80 (see page 28)test and service unit.The max. length of the coax-cable in thehazardous area is 250 m when the systemis fully configured with 8 substations perbranch. If 8-channel sensoplex®2 Ex
substations (input stations ES 8.-Ex andoutput station AS 80-Ex) are used, amaximum of 256 signals can be collectedby each intrinsically safe junction-boxVB 14-Ex/CS.
To provide the full range of thesensoplex®2 functions, 8-channel sub-stations must be used. Complete compa-tibility to the sensoplex®-system enables8-channel sensoplex®2 Ex substations.The LEDs assigned to the accordingoutputs ensure voltage supply monitoring.Each branch can optionally be switchedindividually by means of the channel-selector (5-pole-M12 x 1 connector).
sensoplex®2 Ex – Intrinsically safe junction boxes
!
!
!
(
$(0
1&
203&"'
4--
56(7,8
#
# -
)
203
(-9
%
#
: :
!"
#$%&!$#$%&!$
%''()%%*+
,-+.++!/ 01123,
4!%)5!6: :: :
::
::
7 8795":";*7<5":";*71"<;5":"=<*>'-+!!
))?155);11/1)--)11 @1
!
!
!
$((0
!"
%''()%%*+
,-+.++!!01123,
4!%)5!6
#
56(8
7 8 79 5":";*7<A5":";*71"<;A5 ":"=<*>'-+!!
# -
203
%
#
))?1 55);1 1/1
#$%&!$
#$%&!$
)-- )1 1 @1
(-9
0&"'
4--
)
The last sensoplex®2 Ex-substation ofeach branch must be equipped with thesmart terminating resistor KOAX-75/671-Ex.
Unused outputs of the intrinsically safejunction-box VB 14-Ex/CS should beterminated with the sensoplex® 2Ex-KOAX-75/67-Ex.
For correct system set-up, it is essential toconfigure the number of the installed smartterminating resistors KOAX-75/671-Exvia the DIP-switch at the sensoplex®2 mainstation.
Hans Turck GmbH & Co.KG • D–45466 Mülheim/Ruhr • Tel. 0208/4952-0 • Fax 0208/4952-264 • E-Mail: [email protected] • www.turck.com 17 /0802
Specification
BusOperating voltage UB
Current- /total current consumption
Output Data (operation values)Output voltageOutput current per channelThroughput attenuationDecoupling of outputsShort-circuit protection per channelShort-circuit threshold per channel
Hazardous Area Approvals (max. values)BVS No.Type of protectionOpen-circuit voltageShort-circuit currentExternal inductivities/capacitancesInternal inductivities/capacitances
LED IndicationsAvailability of data outputs
Mechanical FeaturesHousing Material
WeightDimensions (w x h x d) [mm]Degree of protection (IEC 60529/EN 60529)Temperature ratingMountingBus connectionChannel selector
Pin Connection
seen from the view of the contacts
4-channel intrinsicallysafe junction-box
sensoplex®224 VDC ± 15%via coaxial cable
–
4 intrinsically safe outputs12 VDC300 mA
8 dB30 dB
electronic320 mA
BVS No. 95.D.2065 X[EEx ib] IIB13.1 VDC
320 mA current limited150 µH / 68 nF
negligible
4 x green
black die-castaluminium
powder coated1500 g
180 x 120 x 66IP67
-25...+60 °C4 through-holes
coaxial connectors5-pole, M12 x 1
(
-,,*.
(
(
! (
1-channel intrinsicallysafe junction-box
sensoplex®224 VDC ± 15%via coaxial cable
–
1 intrinsically safe output12 VDC300 mA
1 dB–
electronic320 mA
BVS No. 92.C.2007[EEx ib] IIB13.1 VDC
320 mA current limited150 µH / 68 nF
negligible
–
black die-castaluminium
powder coated1750 g
180 x 120 x 45IP67
-25...+60 °C4 through-holes
coaxial connectors–
TypeIdent-No.
VB 11-Ex68 831 11
VB 14-Ex/CS68 904 18
sensoplex®2 Ex – Intrinsically safe junction boxes
channel selector
18 /0802 Hans Turck GmbH & Co.KG • D–45466 Mülheim/Ruhr • Tel. 0208/4952-0 • Fax 0208/4952-264 • E-Mail: [email protected] • www.turck.com
Fieldbus Components
8-channel (ES 8.-Ex) input modules
Connection of 8 sensorsaccord. to EN 60947-5-6 (NAMUR)or volt-free contacts
Die-cast aluminium housing,degree of protection IP67
Protection to EEx ib IIB T4
Input short-circuit and wire-breakmonitoring
Programming andparameterisation via the bus (int.EEPROM, ES8.-Ex) or integratedDIP-switches
LEDs for status and faultindication
0
%&
%
,-.++!112,
5B!!%)#$&!$
4--
: :: :
-
,
+
(
!A5!
!!
"
!!
The sensor circuits are monitored for wire-breakage and short-circuit. Circuit-moni-toring can be disabled via the integratedDIP-switches. Should circuit-monitoring berequired when volt-free contacts areconnected, the standard resistor circuitmust be implemented (see page 15). Ifwire-break and short-circuit monitoring isactivated, unused inputs must beequipped with the resistive connectorRS4.2-DB (see chapter „Accessories“).
The substation ES 8.-Ex, providing thecomplete range of sensoplex®2functions, must be used in the hazardousarea in conjunction with the intrinsically safesensoplex®2 junction-boxVB 14-Ex/CS.
The LEDs indicate input status, defectstations, missing power supply as well aswire-breakage and short-circuits in theinput circuits.
The input stations ES 8.-Ex are classifiedfor protection type EEx ib IIB T4 and canbe mounted directly in the hazardous areawithout additional I.S. protectivemeasures. The input stations are equipped8 (ES 8.-Ex) inputs for connection ofsensors according to EN 60947-5-6(NAMUR) or volt-free contacts.
Two sensors or a dual sensor can beconnected to the ES 81-Ex or the ES 83-Ex via one connector. For this, always twoadjacent connectors are internally linked(for configuration refer to technical datasection). If this method is applied, do notuse the linked unused connector. Forconnection of the dual sensor typeNi4-DS20-2Y1X2-H1141 use the cabletypes RK4.4T...RS4.41T.
The ES 82-Ex provides a supply currentof up to 2.5 mA for some types ofNAMUR sensors which have increasedcurrent requirements but please observethe admissible total current consumptionof 300 mA/per branch of a VB 14-Ex/CS.
sensoplex®2 Ex – Input modules
The ES 8.-Ex) can be addressed auto-matically and its paramters cannot bechanged via the bus. Diagnostic features(status indication and force-functions viathe handheld) are available.
The DIP-switches for adjusting theaddresses and functions are located inthe station and are easily accessible afterremoving the station’s cover.
Hans Turck GmbH & Co.KG • D–45466 Mülheim/Ruhr • Tel. 0208/4952-0 • Fax 0208/4952-264 • E-Mail: [email protected] • www.turck.com 19 /0802
185,
5
6491
56
175,
5
ø 4,3
b5
b6
b7
b8
Function
Power
Fault
b4
b3
b2
b1
12345678910
1248
163264
12345678910
1248
163264
onoffonoff
DIP switches
Address 127
Decimal value
Input delay (on = 2 ms, off = 0,25 ms)
Fault monitoring (on = active, off = off)
Signal flow direction(on = NAMUR, off = permaprox®)
Address
Selectable
Specified value via user programmable bus parameters Addressing via DIP switches
Programming and parameterisation of the ES 8.-Ex
Pin connection (seen from the view of the contacts)
A
A
A
/
/
PIN 1/2 PIN 3/4b2 b1b4 b3b5 b6b7 b8
(+) 1
(–) 2b1b3b6b8
B
B
resistor circuit forvolt-free contacts:
ES 80/82 ES 81 ES 83
2–
4–
1+ 3+
3 , 4= b2
1 , 2= b1
PIN 1/2 PIN 3/4b1 b2b3 b4b5 b6b7 b8
(+) 1
(–) 2 b2b4b6b8
B
B
resistor circuit forvolt-free contacts:
B
B
resistor circuit forvolt-free contacts:
20 /0802 Hans Turck GmbH & Co.KG • D–45466 Mülheim/Ruhr • Tel. 0208/4952-0 • Fax 0208/4952-264 • E-Mail: [email protected] • www.turck.com
Fieldbus Components
Specification
BusOperating voltage UB
Current-/total current consumption
Input Data (operation values)Switching thresholdHysteresisVoltageShort-circuit /wire-breaking monitoringCurrent limitationThroughput attenuationHazardous Area Approval (max. values)BVS No.Type of protectionOpen-circuit voltageShort-circuit currentExternal inductivities/capacitancesInternal inductivities/capacitances
LED-IndicationsPower supplyAvailability (data exchange with
the master o.k.)Switching statusFault indication (short-circuit / wire-breakage in
the input circuit)
Mechanical Features/Operating ElementsHousing material/colour
WeightDimensions ( w x h x d) [mm]Degree of protection (IEC 60529/EN 60529)Temperature ratingMountingBus connectionInput circuit connectionAdjustment of addresses and functions
1) ≤ 15 VDC for hazardous area applications via VB 13-Ex/CS
NAMUR 8-channelinput station
sensoplex®
9.5...30 VDC 2)via coaxial cable
≤ 36 mA/12 V (all inputsshort-circuited)
for 8 NAMUR inputs1.55 mA0.2 mA
8 Vper EN 60947-5-6 (NAMUR)
1.9 mA≤ 0.2 dB
BVS No. 95.D.2054EEx ib IIB T4
14.7 V16 mA
15 mH/2.1 µFnegligible
greenyellow
8 x yellowred
die-cast aluminium/black,powder coated
800 g64 x 185 x 35
IP67-25...+70°C
2 through-holescoaxial connector
4-pole M12 x 110-pole DIP-switch
2) ≤ 15 VDC for hazardous area applications via VB 14-Ex/CS
NAMUR 8-channelinput station
sensoplex®
9.5...30 VDC 2)via coaxial cable
≤ 36 mA/12 V (all inputsshort-circuited)
for 8 NAMUR inputs1.55 mA0.2 mA
8 Vper EN 60947-5-6 (NAMUR)
1.9 mA≤ 0.2 dB
BVS No. 95.D.2054EEx ib IIB T4
14.7 V16 mA
15 mH/2.1 µFnegligible
greenyellow
8 x yellowred
die-cast aluminium/black,powder coated
800 g64 x 185 x 35
IP67-25...+70°C
2 through-holescoaxial connector
4-pole M12 x 110-pole DIP-switch
TypeIdent-No.
ES 80-Ex68 902 09
ES 81-Ex68 902 12
sensoplex®2 Ex – Input Modules
Hans Turck GmbH & Co.KG • D–45466 Mülheim/Ruhr • Tel. 0208/4952-0 • Fax 0208/4952-264 • E-Mail: [email protected] • www.turck.com 21 /0802
Specification
BusOperating voltage UB
Current- /total current consumption
Input Data (operation values)Switching thresholdHysteresisVoltageShort-circuit /wire-breaking monitoringCurrent limitationThroughput attenuationHazardous Area Approval (max. values)BVS No.Type of protectionOpen-circuit voltageShort-circuit currentExternal inductivities/capacitancesInternal inductivities/capacitances
LED-IndicationsPower supplyAvailability (data exchange with
the master o.k.)Switching statusFault indication (short-circuit / wire-breakage in
the input circuit)
Mechanical Features/Operating ElementsHousing material/colour
WeightDimensions ( w x h x d) [mm]Degree of protection (IEC 60529/EN 60529)Temperature ratingMountingBus connectionInput circuit connectionAdjustment of addresses and functions
NAMUR 8-channelinput station
sensoplex®
9.5...30 VDC 1)via coaxial cable
≤ 40 mA/12 V (all inputsshort-circuited)
for 8 NAMUR inputs1.55 mA0.2 mA
8 Vper EN 60947-5-6 (NAMUR)
2.3 mA≤ 0.2 dB
BVS No. 95.D.2054EEx ib IIB T4
14.7 V16 mA
15 mH/2.1 µFnegligible
greenyellow
8 x yellowred
die-cast aluminium/black,powder coated
800 g64 x 185 x 35
IP67-25...+70°C
2 through-holescoaxial connector
4-pole M12 x 110-pole DIP-switch
1) ≤ 15 VDC for hazardous area applications via VB 13-Ex/CS
NAMUR 8-channelinput station
sensoplex®
9.5...30 VDC 2)via coaxial cable
≤ 36 mA/12 V (all inputs short-circuited)
for 8 NAMUR inputs1.55 mA0.2 mA
8 Vper EN 60947-5-6 (NAMUR)
1.9 mA≤ 0.2 dB
BVS No. 95.D.2054EEx ib IIB T4
14.7 V16 mA
15 mH/2.1 µFnegligible
greenyellow
8 x yellowred
die-cast aluminium/black,powder coated
800 g64 x 185 x 35
IP67-25...+70°C
2 through-holescoaxial connector
4-pole M12 x 110-pole DIP-switch
2) ≤ 15 VDC for hazardous area applications via VB 14-Ex/CS
TypeIdent-No.
ES 82-Ex68 902 14
ES 83-Ex68 902 16
sensoplex®2 Ex – Input Modules
22 /0802 Hans Turck GmbH & Co.KG • D–45466 Mülheim/Ruhr • Tel. 0208/4952-0 • Fax 0208/4952-264 • E-Mail: [email protected] • www.turck.com
Fieldbus Components
8-channel (AS 80-Ex) outputmodules
Connection of 8 low loadactuators (8 VDC, 2.7 mA)
Die-cast aluminium housing,degree of protection IP67
Protection to EEx ib IIB T4
Short-circuit and wire-breakmonitoring of the outputs
Programming and parameterisationvia the bus (int. EEPROM, AS 80-Ex)or integrated DIP-switch
LEDs for status and faultindication
The output station AS 80-Ex is classifiedfor protection type EEx ib IIB T4 and canbe mounted directly in the hazardous areawithout additional I.S. safety precautions.The output stationis equipped with 8outputs (AS 80-Ex) and enable connectionof low power consumers (8 VDC, 2.7 mA).Separate voltage supply is not necessarybecause the whole system is supplied viathe coaxial line.
The output station AS 80-Ex providing thecomplete range of sensoplex®2 functions(see page 15) must be used in thehazardous area in conjunction with theintrinsically safe sensoplex®2 junction-boxVB 14-Ex/CS.
The output circuits are monitored for wire-breakage and short-circuit. Circuit-moni-toring can be disabled via the integratedDIP-switches. Should sensor circuit-moni-toring be required when volt-free contactsare connected, the standard resistor cir-cuit must be implemented.If wire-break and short-circuit monitoring isactivated unused inputs must be equippedwith the resistive connector RS4.2-DB(see page 36).
The LEDs indicate output status, defectstations, missing power supply as well aswire-breakage and short-circuits in theoutput circuits.
The AS 80-Ex cant be addressedautomatically and its parameters cannotbe changed via the bus. Diagnosticfeatures (status indication and force-functions via the handheld) are available.The DIP-switches for adjusting theaddresses and functions are located in thestation and are easily accessible afterremoving the station’s cover.
Programming and parameterisation ofthe AS 80-Ex
0
%&
%
,-.++!112,
4--
/-
/,
/+
/
/
/
/
/(
!A5!5B!!%)#$&!$: :
: :
"
!!
!!
sensoplex®2 Ex – Output modules
!
"
!
"
)*%*-
+, ,))%(-
-*C-/ %/ %#
5-,---/-,- %/-,-/DB)#/ %/ %#
###
$%&' (
--
Hans Turck GmbH & Co.KG • D–45466 Mülheim/Ruhr • Tel. 0208/4952-0 • Fax 0208/4952-264 • E-Mail: [email protected] • www.turck.com 23 /0802
1) ≤ 15 VDC for hazardous area applications via VB13-Ex/CS
Specification
BusOperating voltage UB
Current- /total current consumption
Output data (operation values)
Output voltageRated load currentShort-circuit protectionShort-circuit thresholdWire-break thresholdDelay-time (from signal 0 to 1 or 1 to 0)Throughput attenuationHazardous Area Approval (max. values)BVS No.Type of protectionopen-circuit voltageShort-circuit currentExternal inductivities/capacitancesInternal inductivities/capacitancesLED-IndicationsOperation voltageAvailability (data exchange with
master o.k.)Switching statusFault indication (short-circuit/wire-breakage in
the output circuit)Mechanical features/Operating elementsHousing material
WeightDimension (w x h x d) [mm]Degree of protection (IEC 60529/EN 60529)Temperature ratingMountingBus connectionConnection input circuitAdjustment of Addresss and functions
Pin connection
seen from the view of the contacts
8-channel output station for low power
consumerssensoplex®2
10...30 VDC2)via coaxial cable
≤ 40 mA/12 V(rated load current)
for 8 low powerconsumers
8 V (IL = 2.7 mA)2.7 mA
electr., current limited3.5 mA100 µA
ca. 100 µs≤ 0.2 dB
BVS No. 95.D.2055EEx ib IIB T4
14.7 V≤ 20 mA
15 mH/2.1 µFnegligible
greenyellow
8 x yellowred
black die-castaluminium
powder coated800 g
64 x 150 x 35IP67
-25...+70 °C2 through-holes
coaxial connectors4-pole M12 x 1
10-pole DIP-switch
A
2) ≤ 15 VDC for hazardous area applications via VB14-Ex/CS
TypeIdent-No.
AS 80-Ex68 903 09
sensoplex®2 Ex – Output Modules
24 /0802 Hans Turck GmbH & Co.KG • D–45466 Mülheim/Ruhr • Tel. 0208/4952-0 • Fax 0208/4952-264 • E-Mail: [email protected] • www.turck.com
Fieldbus Components
8-channel input-/output modulesfor cabinet mounting
Connection of 8 sensorsaccording to EN 60947-5-6 (NAMUR)or low power loads (8 VDC, 2.7 mA)
ABS-plastic housing,degree of protection IP20
Protection to EEx ib IIB T4
Input and output monitoring forshort-circuit and wire breakage
Programming and parameteradjustment via the bus(int. EEPROM) or integratedDIP-switch
LEDs for status and faultmonitoring
,-
.++!.
112,
5B !!%)
!A5 !
*'%*!+++!$
)(*) *) *)*
)*)+*),*)-*
&1
';
<9
=
,-.++!..0
!
The substations ESK 80-Ex and ASK 80-Ex are classified for protection type EEx ibIIB T4 and can be mounted directly in thehazardous area. The input station ESK 80-Ex enables connection of 8 sensorsaccording to EN 60947-5-6 (NAMUR) ordry contacts.
The output station ASK 80-Ex serves forconnection of low power loads (8 VDC,2.7 mA). The signals are transferred viaremovable screw-terminals so that thestations can be mounted in a cabinet orintegrated in an operator desk.
All sensoplex®2 functions are available, e.g.automatic addressing, error locali-sationon the bus line and bus operations such asparameterisation, configuration and force-functions via the handheld DEA 80 serviceunit (see page 15).The input- or output stations are moni-tored for wire-breakage and short-circuit.Monitoring can be de-activated via theDIP-switch in the station or via the bus bymeans of the handheld. (Input station ESK80-Ex: monitoring is required with volt-freecontacts, a double resistor circuit isrequired).The LEDs indicate input or output status,defect stations, missing power supply aswell as wire-breakage and short-circuits.
DIP-switches for setting of addresses andfunctions are located under the display.To provide the full range of thesensoplex®2 features in the hazardous
!
"
!
"
)*%*-
+, ,))%(-
-*C-/ %/ %#
5-,---/-,- %/-,-/DB)#/ %/ %#
###
$%&' (
--
!
"
!
"
###
$%&' (
--
)*%*-
+ (*./)/!)
+, ,))%(-
-*)#/ %/ %
+ (,/1$984/
Programming and parameterisation ofthe ESK 80-Ex
Programming and parameterisation ofthe ASK 80-Ex
sensoplex®2 Ex – Terminal modules
area the substations can only be used inconjunction with the sensoplex®2 Exjunction-box VB 14-Ex/CS.
Hans Turck GmbH & Co.KG • D–45466 Mülheim/Ruhr • Tel. 0208/4952-0 • Fax 0208/4952-264 • E-Mail: [email protected] • www.turck.com 25 /0802
Specification
BusOperating voltage UB
Current- /total current consumption
Input-/output data (operation values)
Switching threshold/output voltageHysteresis/rated load currentShort-circuit/wire-breaking monitoringCurrent limitation/short-circuit thresholdWire-breakage thresholdDelay-time (from signal 0 to 1 or from 1 to 0)Throughput attenuationHazardous Area Approval (max. values)BVS. No.Type of protectionOpen-circuit voltageShort-circuit currentExternal inductivities/capacitancesInternal inductivities/capacitancesLED-IndicationsSupply voltageAvailability (data exchange with
master o.k.)Switching statusFault indication (short-circuit /wire-breakage
in the input circuit)Mechanical features/Operating elementsHousing materialWeightDimension (w x h x d) [mm]Degree of protection (IEC 60529/EN 60529)Temperature ratingMounting
Bus connectionConnection of input-/output circuitsAdjustment of addresses and functions
8-channel NAMURinput stationsensoplex®
9.5...30 VDC1)via coaxial cable
≤ 36 mA/12 V (all inputsshort-circuited)
for 8 NAMUR inputs
1.55 mA0.2 mA
per EN 60947-5-6 (NAMUR)1.9 mA
––
≤ 0.2 dB
BVS No. 97.D.2019EEx ib IIB T4
14.3 V15.6 mA
15 mH/2.8 µFnegligible
greenyellow
6 x yellowred
ABS-plastic350 g
80 x 160 x 60IP20
0...60 °C2 through-holes
or hat-rail mountingcoaxial connectors
4-pole M12 x 110-pole DIP-switch
Pin Connection
seen from the view of the contacts
1) ≤ 15 VDC for hazardous area applications via VB 14-Ex/CS
8-channel output station forlow-power loads
sensoplex®29.5...30 VDC1)
via coaxial cable≤ 40 mA/12 V (rated output
current)
for 8 low power loads8 V (IL = 2.7 mA)
–2.7 mA
electr., current limited3.5 mA100 µA
ca. 100 µs≤ 0.2 dB
BVS No. 97.D.2019EEx ib IIB T4
14.7 V≤ 20 mA
15 mH/2.1 µFnegligible
greenyellow
8 x yellowred
ABS-plastic350 g
80 x 160 x 60IP20
0...60 °C2 through-holes
or hat-rail mountingcoaxial connectors
4-pole M12 x 1
A
A
&,- -
1$984
AE
A
=,%*%
5-,- -
B
B
resistor circuitfor volt-free contacts:
TypeIdent-No.
ESK 80-Ex68 902 02
ASK 80-Ex6890302
sensoplex®2 Ex – Terminal modules
26 /0802 Hans Turck GmbH & Co.KG • D–45466 Mülheim/Ruhr • Tel. 0208/4952-0 • Fax 0208/4952-264 • E-Mail: [email protected] • www.turck.com
Fieldbus Components
Die-cast aluminium housing,with nickel-plated brass connector,degree of protection IP67
Protection to EEx ib IIB T4
75 ΩΩΩΩΩ terminating resistor for the bus systems sensoplex® and sensoplex®2
Connection via coaxialconnector or plug-in connectorsat the substation
LED for bus voltage indication (KOAX-75/671-Ex only)
.>+-?,+(0
4--
,-.++!112,A5 !5B!!%)C$&!$
!!
!
KOAX-75/671-Ex
!
KOAX-75/67-Ex
Terminating resistor
Each sensoplex® line must be terminated(at the last substation) with a coaxialterminating resistor.
Incorrectly terminated or open lines willcause signal distortions or standingwaves. Only if the lines are terminated withthe original terminating resistor standingwaves can be avoided.
Unused VB 14-Ex/CS outputs must alsobe equipped with the terminating resistorKOAX-75/67-Ex.The treminating resistor is plugged directlyinto thr unused output
Terminating resistor KOAX-75/671
The smart terminating resistor KOAX-75/671 serves for termination ofsensoplex®2 Ex lines. The terminatingresistor is identified by the sensoplex®2master and so special sensoplex®2features such as automatic addressing ofsensoplex®2 substations are provided.
The resistor is connected via a coaxialcable to the last sensoplex®substation ineach safe line.
Terminating resistors
Terminating resistor KOAX-75/671-Ex
The smart terminating resistor KOAX-75/671-Ex must only be used in conjunctionwith the sensoplex® Ex junction-boxVB 11-Ex and VB 14-Ex/CS.To assure sensoplex® 2 functionality,a smart terminating resistor KOAX-75/671-Ex must be connected to each of thelast stations in the line. This refers tosensoplex®2 stations only.
!
!
!
.>+-?,+(
KOAX-75/671
Hans Turck GmbH & Co.KG • D–45466 Mülheim/Ruhr • Tel. 0208/4952-0 • Fax 0208/4952-264 • E-Mail: [email protected] • www.turck.com 27 /0802
Specification
BusOperating voltage UB
Contact ratingNominal voltage
Plug-in connectorsCoupling nut material/platingGasketsConductor insulation
Mechanical dataDimension (w x h x l) [mm]Housing material
Temperature ratingDegree of protection (IEC 60529/EN 60529)
(if connected)Surge impedanceCapacityWeightBus connection
LED-IndicationsSupply voltage
Hazardous Area Approval (max. values)BVS No.Type of protectionVoltageCurrentEffective internal capacitancesEffective internal inductances
Terminating resistorfor sensoplex®Ex-
componentssensoplex®
10...30 VDC1)via coaxial cable
30 VDC
brass, nickel-platedPolyurethane
PTFE
––
-25 ... +70 °CIP67
75 Ω11 nF50 g
–
––
––––––
terminating resistorfor sensoplex®2 Ex-
componentssensoplex®2
9.5...15 VDC2)via coaxial cable
–
–––
64 x 58 x 35black die-cast
aluminiumpowder coated-25 ... +70 °C
IP67
75 Ω–
240 gcoaxial-connector
green
BVS No. 95.D.2057EEx ib IIB T4max. 15 VDCmax. 400 mA
≤ 27 nFnegligible
1) ≤ 15 VDC for hazardous are applications via VB 13-Ex/CS 2) ≤ 15 VDC for hazardous area applications via VB 14-Ex/CS
TypeIdent-No.
KOAX-75/67-Ex68 824 02
KOAX-75/671-Ex68 909 19
Terminating resistors
terminating resistorfor sensoplex®2 Ex-
componentssensoplex®2
10...30 VDC1)via coaxial cable
–
–––
64 x 58 x 35black die-cast
aluminiumpowder coated-25 ... +70 °C
IP67
75 Ω–
240 gcoaxial-connector
green
BVS No. 95.D.2057EEx ib IIB T4max. 15 VDCmax. 400 mA
≤ 27 nFnegligible
KOAX-75/67168 909 20
28 /0802 Hans Turck GmbH & Co.KG • D–45466 Mülheim/Ruhr • Tel. 0208/4952-0 • Fax 0208/4952-264 • E-Mail: [email protected] • www.turck.com
Fieldbus Components
The accessories for the sensoplex®
system include all the hardware used toexpand the system such as systemcomponents for diagnostics, amplificationand auxiliary power supplies, as well as avariety of wiring components for theelectrical connections of the system.
System Components
Diagnostic Station DEA 80
The hand-held monitor DEA 80 is availableto monitor the sensoplex® system (only inconnection with sensoplex®2 master) aswell as sensoplex®2. Further, the DEA 80is used to write the EEPROM of thesensoplex®2 master station for start-upverification. That is, the actual network(type of stations and address) must matchthe respective EEPROM configuration.
Wiring Devices
Wiring devices, or connecting cables andcordsets, are the hardware that is neededto wire up the sensoplex® system.These are all coaxial components that areexclusively used for point to pointconnection of sensoplex® components,and prewired connection cables(M12 x 1)for sensors and actuators.
Coaxial Components
Coaxial Cable:Coaxial cables are available in twoversions: pre-assembled or field-wireable.In the sensoplex® system, the coaxialcable is used to provide data transfer andpower supply to the connectedsensoplex®2 components. Because thesensoplex®2 system is used at the fieldlevel of an automated process where it isexposed to the roughest of operatingconditions, the cable must be rugged,both electrically and mechanically, andwithstand the effects of disturbances.The coaxial cable allows power to be sentat the same time as it transfers high speedsignals.Coaxial Connector KOAX-12/67:To connect field-wireable coaxial cablesto all data line components, the fieldselectable coaxial connector KOAX-12/67must be used.
Coaxial Accessories:
– Terminating resistor KOAX-75/67:Each sensoplex® branch must beterminated with a coaxial terminationresistor. Branches that are open, ornot properly terminated, can causesignal distortions or stationary waves.Operation of the system withoutstationary waves can only be ensuredif all branches are terminated with aself surge impedance.
– Terminating resistor KOAX-75/671:For faultless operation of thesensoplex®2 system, this terminationresistor must be used to terminatesensoplex®2 lines.
– KOAX-KV01:The KOAX-KV01 is an in-line doublesided female connector used tocouple two coaxial cables with maleconnectors.
– KOAX-FB:The coaxial flanged field-wireablereceptacle KOAX-FB is used toconnect foreign components to thesensoplex® system.
System Accessories
#@#
"
Connector components
The connector system is used for theconnection of field devices (sensors andactuators) and to connect the powersupply of the sensoplex®2 system. Thesystem consists of molded extensioncordsets, cables, receptacles and fieldwireable connectors.
The cordsets have a connector on eitherone or both ends and a molded-on cable indifferent lengths and cable materials.
Field-wireable connectors can beconnected to existing cables.
Hans Turck GmbH & Co.KG • D–45466 Mülheim/Ruhr • Tel. 0208/4952-0 • Fax 0208/4952-264 • E-Mail: [email protected] • www.turck.com 29 /0802
System Accessories
DEA 80
68 904 10hand-held monitor
ABS plastic
101 x 195 x 44
IP20
portableor plug-in0...+60 °C
–5 VDC
≤ 250 mA (via IM 01)5 VDC (IM 01 logic)
50 mA––
LCD displaymembrane keyboard
poweraddress absenttype of stationno check back
transmission errorshort-circuit/wire-break
statusaddressing
“forced passing”configuration cycledocum. via RS232
save data withMEM-CARD
via IM 01 or Master12 pin circ. connectorRS232 (9 pin Sub-D)
RS485 (12 pin circ. connector)
–12 conductor cableDEA 80-AK-5 (5 m),
IM 01 interface module, MEM-CardMEM-Card with“forced passing”
Type
Ident-No.Application
Housing material
Dimensions (w x h x d)
Degree of protection(IEC 60529/EN 60529)Mounting
Operating temperatureInput circuitsSupply voltage
Power/Current consumptionOutput voltageOutput currentIsolationShort-circuit protectionDiagnosticsAdjustmentsAlarm indications
Connections:
– Data line– Interface
– Current supplyAccessories
Capacity/features
30 /0802 Hans Turck GmbH & Co.KG • D–45466 Mülheim/Ruhr • Tel. 0208/4952-0 • Fax 0208/4952-264 • E-Mail: [email protected] • www.turck.com
Fieldbus Components
Coaxial Components
Type
Ident-No.
Application
LengthMaterial– Inner conductor
– Outer conductor/housing
– Cable jacket
– Conductor insulation– Contact carrier– Cable sleeve/grip material– Contact material/plating– Coupling nut material/plating– Gaskets
Conductor insulation/colorCable jacket/colorOuter diameterDimensions
Number of conduct./cross sectionNumber of strands/sizeMinimum bending radiusOperating temperature
Heat resistance(VDE 0472, Part 609/6.85)Short term rating(when in contact with hot objects> 140 °C)Short-circuit resistance according toVDE 0298Chemicals-resistant
ImpedanceSignal attenuation/100 mDegree of shielding (f ≥ 470 MHz)Ohmic resistanceInductanceCapacitancePulse shortening factorCurrent ratingVoltage ratingProtection Class(IEC 60529/EN 60529) – connectedMeets other specificationsConnections
KOAX-FB
68 817 03
coaxial flangedreceptacle
–
–
–
–
PTFEcopper alloy, silv. plat.
––
brass,silverPolyurethane/PTFE
white––
M14 x 1,19.5 mm long
–––
-25...+70 °C
–
–
–
–
75 Ω––––––
4 A30 VDC
IP67
––
KOAX-12/67
68 822 00
straight or right anglecoaxial connector
–
–
–
–
PTFEcopper alloy, silv. plat.copper alloy, silv. plat.copper alloy, silv. plat.copper alloy, silv. plat.
PUR, soft copper, silverplated
–––
42 x 35 (right angle)
–––
-25...+70 °C
–
–
–
–
75 Ω––––––
4 A30 VDC
IP67
–IEC 169-2
KOAX-KV01
68 817 02
coupling and extensionof coaxial cables
–
–
–
–
–
PTFE.copper alloy, silv. plat.copper alloy, silv. plat.copper alloy, silv. plat.copper alloy, silv. plat.
–
white––
M14 x 1,28 mm long
–––
-25...+70 °C
–
–
–––
75 Ω––––––
4 A30 VDC
IP67fixing dimensions
accord. to IEC 169-2
Hans Turck GmbH & Co.KG • D–45466 Mülheim/Ruhr • Tel. 0208/4952-0 • Fax 0208/4952-264 • E-Mail: [email protected] • www.turck.com 31 /0802
"!
9;
( B
( B 9;
9;
"!
!
Dimensions – Coaxial Components
KOAX-FB KOAX-KV01 KOAX-12/67
32 /0802 Hans Turck GmbH & Co.KG • D–45466 Mülheim/Ruhr • Tel. 0208/4952-0 • Fax 0208/4952-264 • E-Mail: [email protected] • www.turck.com
Fieldbus Components
Cable installation
The installed coaxial cable should not beexposed to extreme bending or defor-mation. The min. bending radius of 70 mmmust be observed. A strongly deformedcable changes the wave impedance and cancause reflections and standing waves.Standing waves will disturb bus communi-cation and lead to faulty messages withinthe sensoplex® system.
Earth-free operation of the system mustbe ensured with regards to the outerconductor of the coaxial cable. The outerconductor is connected to system groundand must not be damaged to avoid groundloops, i.e. the outer conductor plaid shouldnot come into contact with groundedobjects.For connection of the field-wireable coaxialcable to sensoplex®2 components (e.g.substation ES 80-Ex or AS 80-Ex), the fieldwireable coaxial plug-in connector KOAX-12/67 (Ident-No. 68 822 00) should beused.Please note: the outer conductor of thecoaxial cable is connected to the connectorhousing and must not come into contactwith any earthed object.
Pre-assembled coaxial cableKOAX-WS-...BFLEX-WS
Pre-assembled flexible coaxial cables arealso available in several lengths. Both endsof the flexible coaxial cables are equippedwith moulded right-angle connectors coatedwith Polyurethane. The preassem-bledcoaxial cables can be ordered in thefollowing lengths:
0.3 m KOAX-WS-0.3BFLEX-WSIdent-No. 68 825 21
0.6 m KOAX-WS-0.6BFLEX-WSIdent-No. 68 825 22
1.0 m KOAX-WS-1.0BFLEX-WSIdent-No. 68 825 23
1.5 m KOAX-WS-1.5BFLEX-WSIdent-No. 68 825 24
2.0 m KOAX-WS-2.0BFLEX-WSIdent-No. 68 825 25
3.0 m KOAX-WS-3.0BFLEX-WSIdent-No. 68 825 29
5.0 m KOAX-WS-5.0BFLEX-WSIdent-No. 68 825 28
Coaxial cable for data andpower supply
Versions with rigid or flexibleinner conductor
Pre-assembled or field-wireablecable (in meters) available
Temperature andchemicals resistantTPE-cable jacket
75 ΩΩΩΩΩ impedance
F
F
KOAX-75/B-FLEX
KOAX-75/B
!"
!"
Coaxial Cable
KOAX-WS-…BFLEX-WS
Pre-assembled coaxial cables as well ascoaxial cables by the meter are availableand are used to provide data transfer andpower supply to the connectedsensoplex®2 components.Because bus systems are used at the fieldlevel of an automated process, the coaxialcable has to meet special requirementswith regards to its mechanical andelectrical characteristics.
The coaxial cables KOAX-75/B-FLEX andKOAX-WS-…B-FLEX-WS are equippedwith a highly resistant and flexible copperalloy inner conductor which withstandshigh levels of mechanical stress. The innerconductor of the coaxial cableKOAX-75/B is inflexible and made of asolid copper alloy allowing for longer cablelengths due to reduced attenuation.
The coaxial cable jacket is made ofTPE (Thermoplastic Elastomer) and isresistant to heat, contact with hot objectsand chemicals. In accordance with itsinstallation in hazardous areas, the cablejacket of the coaxial cable is blue.
Hans Turck GmbH & Co.KG • D–45466 Mülheim/Ruhr • Tel. 0208/4952-0 • Fax 0208/4952-264 • E-Mail: [email protected] • www.turck.com 33 /0802
Specification
Bus
CableLengthInner conductor material
Outer conductor material
Cable jacket material/colour
Outer diameterConductor insulation material/colourNumber of strandsConductor cross sectionMinimum bending radiusElectrical dataImpedanceSignal attenuation (pro 100 m)Ohmic resistanceInductancesCapacitancePulse shortening factorDegree of shielding (f ≥ 470 MHz)
General dataAmbient temperature range (when not moved)Heat resistance (VDE 0472, part 609/6.85)Short term rating (when in contact with hotobjects > 140 °C)
Short-circuit resistance (VDE 0298)Chemical resistance
Weight
Right-angle plug-in connectorsContact carrier materialCable sleeve/grip materialContact material /platingCoupling nut material/platingGaskets
pre-assembledcoaxial cable
sensoplex®
sensoplex®2
0.3 - 5.0 mspecial high resistance
flexible copper alloyAl-PP-Al-foil,100 % cover
tin-plated copper braidcover > 45 %
TPE (Thermoplastic Elastomer),blue
7 mm ± 0.2 mmCell-PE, white
1 / 119 x 0.22 mm ∅
70 mm
75 Ω2.7 dB (8/12 MHz)
43 m Ω/m450 nH/m55 pF/m
0.7875 dB
-25...+80 °C110 °C
up to 250 °Cno distortion, no melting,
no short-circuit
test temperature 250 °Cresistant to solvents and
oils, no swelling
50 g/m
copper alloy, silver-platedPolyurethane
copper alloy, silver-platedcopper alloy, nickel-plated
Polyurethane
coaxial cable withrigid inner conductor
sensoplex®
sensoplex®2
by the metersolid copper
alloyAl-PP-Al-foil100 % cover
tin-plated copper braidcover > 45 %
TPE (Thermoplastic Elastomer),blue
7 mm ± 0.2 mmCell-PE, white
1 / 11.1 mm ∅
70 mm
75 Ω1.9 dB (8/12 MHz)
43 m Ω/m450 nH/m55 pF/m
0.7875 dB
-25...+80 °C110 °C
up to 250 °Cno distortion, no melting,
no short-circuit
test temperature 250 °Cresistant to solvents and
oils, no swelling
50 g/m
––––
coaxial cable withflexible inner conductor
sensoplex®
sensoplex®2
by the meterspecial high resistance
flexible copper alloyAl-PP-Al-foil,100 % cover
tin-plated copper braidcover > 45 %
TPE (Thermoplastic Elastomer),blue
7 mm ± 0.2 mmCell-PE, white
1 / 119 x 0.22 mm ∅
70 mm
75 Ω2.7 dB (8/12 MHz)
43 m Ω/m450 nH/m55 pF/m
0.7875 dB
-25...+80 °C110 °C
up to 250 °Cno distortion, no melting,
no short-circuit
test temperature 250 °Cresistant to solvents and
oils, no swelling
50 g/m
––––
TypeIdent-No.
KOAX-75/B-FLEX68 82701
KOAX-75/B68 827 02
KOAX-WS...BFLEX-WSsee chartpage 30
Coaxial Cable
34 /0802 Hans Turck GmbH & Co.KG • D–45466 Mülheim/Ruhr • Tel. 0208/4952-0 • Fax 0208/4952-264 • E-Mail: [email protected] • www.turck.com
Fieldbus Components
Coaxial cable
Type
Ident-No.
Application
LengthMaterial– Inner conductor
– Outer conductor/housing
– Cable jacket
– Conductor insulation– Contact carrier– Cable sleeve/grip material– Contact material/plating– Coupling nut material/plating– Gaskets
Conductor insulation/colorCable jacket/colorOuter diameterDimensions
Number of conduct./cross sectionNumber of strands/sizeMinimum bending radiusOperating temperature
Heat resistance(VDE 0472, Part 609/6.85)Short term rating(when in contact with hot objects> 140 °C)Short-circuit resistance according toVDE 0298Chemicals-resistant
ImpedanceSignal attenuation/100 mDegree of shielding (f ≥ 470 MHz)Ohmic resistanceInductanceCapacitancePulse shortening factorCurrent ratingVoltage ratingProtection Class(IEC 60529/EN 60529) – connectedMeets other specifications
KOAX-75/OR-FLEX
68 827
coaxial cablefor data transfer and
power supplyany
highly flexible andresistant,
special copper alloyAl-PP-Al foil100 % cover
tin plated copperbraid, > 45% cover
TPEElastomer thermopl.
Cell-PE–––––
whiteorange
7 mm ± 0.2 mm–
19 x 0.22 mm Ø1/1
70 mm-25...+80 °C
110 °Cup to 250 °C
resistance to melting,no distortion,
no short-circuittest temperature
250 °Cresistant to solvents
and oils, no distortion75 Ω
2.7dB (8/12 MHz)75 dB
43 mΩ/m450 nH/m55 pF/m
0.784 A
30 VDC–
–
KOAX-WS-0,3/0,6/1,0/1,5/2,0 XOR/
BFLEX-WS68 825...BFLEX
coaxial cablefor data transfer and
power supply0.3/0.6/1.0/1.5/2.0 m
highly flexible andresistant,
special copper alloyAl-PP-Al foil100 % cover
tin plated copperbraid, > 45% cover
TPEElastomer thermopl.
halide-free PVCcopper alloy, silv. plat.
Polyurethanecopper alloy, silv. plat.copper alloy, silv. plat.
Polyurethane
whiteorange/blue
7 mm ± 0.2 mm–
19 x 0.22 mm Ø1/1
70 mm-25...+80 °C
110 °Cup to 250 °C
resistance to melting,no distortion,
no short-circuittest temperature
250 °Cresistant to solvents
and oils, no distortion75 Ω
2.7dB (8/12 MHz)75 dB
43 mΩ/m450 nH/m55 pF/m
0.784 A
30 VDCIP67
–
Hans Turck GmbH & Co.KG • D–45466 Mülheim/Ruhr • Tel. 0208/4952-0 • Fax 0208/4952-264 • E-Mail: [email protected] • www.turck.com 35 /0802
Special Cables
TypeIdent-No.
Application
LengthMaterial– Inner conductor– Outer conductor/housing
– Cable jacket
– Conductor insulationConductor insulation/colorCable jacket/colorOuter diameterDimensionsNumber of conduct./cross sectionNumber of strands/sizeMinimum bending radiusOperating temperatureHeat resistance(VDE 0472, part 609/6.85)Short term rating (when in contact with hotobjects > 140 °C)
Short-circuit resistance according to VDE 0298Chemicals-resistant
ImpedanceSignal attenuation (8/12 MHz)Degree of shielding (f ≥ 470 MHz)Ohmic resistanceInductanceCapacitancePulse shortening factorCurrent ratingVoltage ratingDegree of protection(IEC 60529/EN60529) – connectedMeets other specificationsConnections
FBK-0,0668 904 13
ribbon connection cable(Subbus) forsensoplex®2
terminal versionsESM, ESK, ASK 80
0.06 m
Cu–
–
––––––––
0...60 °C–
–
–
–
––––––
1.2 A12...30 VDC
IP20
–plug-in connectorfor ribbon cable
FBK-TCP 0168 909 21
terminating codeplug for sensoplex®2
terminal versions ESM,ESK, ASK 80
–
Cu–
–
––––––––
0...60 °C–
–
–
–
––––––––
IP20
–plug-in connectorfor ribbon cable
DEA 80-AK-568 904 14
12 conductor circularconnector
(to connect theDEA 80 with IM 01or master station,
RS485)
5.0 m
Cu–
–
– –––––––
0...60 °C–
–
–
–
––––––––
IP20TURCK WORLD-WIDE
HEADQUARTERS
GERMANYHans Turck GmbH &
Co. KGWitzlebenstraße 7D-45472 Mülheim an
der RuhrP. O. Box 45466
Mülheim an der RuhrPhone (+49) (208)
4952-0Fax (+49) (208)
36 /0802 Hans Turck GmbH & Co.KG • D–45466 Mülheim/Ruhr • Tel. 0208/4952-0 • Fax 0208/4952-264 • E-Mail: [email protected] • www.turck.com
Fieldbus Components
Jumper plug for supply voltagedistribution for all output branches(accessory for the intrinsically safejunction boxes VB 14-Ex/CS)
Resistive connector for terminationof unused inputs and outputs
Plug-in connector M12 x 1
Degree of protection IP67
!
9;
F
Jumper Plug RS4.5-VB
The jumper plug RS4.5-VB links thecontacts of the „channel selector” input atthe intrinsically safe VB 14-Ex/CS. Thejumper plug is an easy to handle plug-incomponent and supplies the four outputbranches of the intrinsically safe junction-box with voltage.
All intrinsically safe junction-boxes aresupplied together with the jumper plug.The channel-selector of the junction-boxenables individual decoupling of singleoutput branches from power supply, e.g.for emergency stops.
Resistive Connector RS4.2-DB
The resistive connector RS4.2-DB is usedto terminate unused inputs and outputs ofsensoplex® and sensoplex®2 Exsubstations.
If short-circuit and wire-breakage moni-toring is activated (via DIP-switch in thestations or programmable via the bus) theresistive connector will suppress errormessages. The resistive plug-in connectoris connected to the M12 x1-connector ofthe substation.
Special Plugs
Hans Turck GmbH & Co.KG • D–45466 Mülheim/Ruhr • Tel. 0208/4952-0 • Fax 0208/4952-264 • E-Mail: [email protected] • www.turck.com 37 /0802
Pin connection
seen from the view of the contacts
Specification
Bus
Plug-in connectorContact carrier materialContact carrier colourCable sleeve/grip materialCable sleeve/grip colourContact material/plating
Coupling nut material/plating
General dataInsulation resistanceTemperature rating of connectorTemperature rating of cableDegree of protection (IEC 60529/EN 60529)Clearences and creepage distances(VDE 0110b)
Resistive connector forunused
inputs/outputssensoplex®
sensoplex®2
PA12-GF30yellow (like RAL 1021)
thermopl. PURyellow (like RAL 1021)
CuZn, nickel- andgold-plated
CuZn, nickel-plated
≥ 109 Ω-25...+80 °C-25...+80 °C
IP67250 VAC/300 VDC
Gr. C
Jumper plug forjunction-box
VB 14-Ex/CSsensoplex®
PA12-GF30yellow (like RAL 1021)
thermopl. PURyellow (like RAL 1021)
CuZn, nickel- andgold-plated
CuZn, nickel-plated
≥ 109 Ω-25...+80 °C-25...+80 °C
IP67250 VAC/300 VDC
Gr. C
!
!
4$/B
TypeIdent-No.
RS4.5-VB68 817 09
RS4.2-DB68 817 01
Special Plugs
38 /0802 Hans Turck GmbH & Co.KG • D–45466 Mülheim/Ruhr • Tel. 0208/4952-0 • Fax 0208/4952-264 • E-Mail: [email protected] • www.turck.com
Fieldbus Components
Notes
Hans Turck GmbH & Co.KG • D–45466 Mülheim/Ruhr • Tel. 0208/4952-0 • Fax 0208/4952-264 • E-Mail: [email protected] • www.turck.com 39 /0802
Absender/Sender:
Name:Firma/Company:Abt./Position:Adresse/Address:
Tel./Phone: Fax:E-Mail:
Hans Turck GmbH & Co. KGD–45466 Mülheim an der RuhrPhone (+49) (2 08) 49 52-0Fax (+49) (2 08) 49 52-264E-Mail [email protected] www.turck.com
Bitte senden Sie mir Unterlagen:
Sensortechnik Induktive Sensoren Induktive Sensoren für
Schwenkantriebe uprox® induktive Sensoren Kapazitive Sensoren Magnetfeldsensoren Opto-Sensoren Geräte für den Personenschutz Ultraschall-Sensoren levelprox-Füllstandssensoren Strömungswächter Druckwächter Temperaturwächter Linearweg-Sensoren Drehweg-Sensoren Steckverbinder CD-ROM Sensortechnik
Interfacetechnik Interfacetechnik im Aufbaugehäuse
– Bauform multimodul– Bauform multisafe®
Allgemeine Informationen Interfacetechnik auf 19"-Karte
– Bauform multicart®
Miniaturrelais, Industrierelais,Zeitwürfel, Sockel
Zeit- und Überwachungsrelais Ex-Schutz – Grundlagen für
die Praxis (Übersichtsposter) CD-ROM Interfacetechnik
Feldbustechnik busstop®-Feldbuskomponenten Bussystem sensoplex®2 Bussystem sensoplex®2Ex Bussystem sensoplex®MC Bussystem AS-Interface®
Bussystem DeviceNet™ Ethernet Netzwerkkomponenten BL20 I/O-Busklemmensystem Bussystem FOUNDATION™ fieldbus Bussystem PROFIBUS-DP Bussystem PROFIBUS-PA Bussystem piconet®
Remote I/O excom®
……………………………………
Please send me more information:
Sensors inductive sensors inductive sensors for rotary
actuators uprox® inductive sensors capacitive sensors magnetic-field sensors photoelectric sensors machine safety equipment ultrasonic sensors levelprox level sensors flow controls pressure controls temperature controls linear position sensors rotary position sensors connectors CD-ROM Sensors
Interface technology devices in modular housings
– multimodul style– multisafe® stylegeneral information
devices on 19" card– multicart® style
miniature relays, industrialrelays, time cubes, sockets
programmable relays and timers explosion protection –
basics for practicalapplication (overview poster)
CD-ROM Interface technology
Fieldbus technology busstop® fieldbus components bus system sensoplex®2 bus system sensoplex®2Ex bus system sensoplex®MC bus system AS-Interface®
bus system DeviceNet™ Ethernet network components BL20 I/O bus terminal system bus system FOUNDATION™ fieldbus bus system PROFIBUS-DP bus system PROFIBUS-PA bus system piconet®
Remote I/O excom®
………………………………………
FAX-ANTWORT/FAX REPLY
Subject to change without notice
*D300447ßß0602*
D300447 0802
www.turck.com
... and more than 60 representatives and agencies world-wide.
ITALYTURCK BANNER S. R. L.Via Adamello, 9I-20010 Bareggio (MI)Phone (+39) (02) 90364291Fax (+39) (02) 90364838E-Mail [email protected]
KOREATurck Korea Branch OfficeSangwoo Building 4th Floor, 1576-1Jeongwang-Dong, Shiheung-CityROK-Kyunggi-do, KoreaPhone (+82) (31) 4 98 84 33Fax (+82) (31) 4 98 84 36E-Mail [email protected]
THE NETHERLANDSTURCK B. V.Postbus 297NL-8000 AG ZwollePhone (+31) (38) 4227750Fax (+31) (38) 4227451E-Mail [email protected]
POLANDTurck sp.z o.oul. Kepska 2PL-45-129 OpolePhone (+48) (77) 4434800Fax (+48) (77) 4434801E-Mail [email protected]
RUSSIATURCK Avtomatizazija O.O.O2-ojWerchne-Michajlovskij proesd, 9RU-117419 MoskauPhone (+7) (095) 9 52 08 20Fax (+7) (095) 9 55 73 48E-Mail [email protected]
USATURCK Inc.3000 Campus DriveUSA-Minneapolis, MN 55441-2656Phone (+1) (763) 553-9224
553-7300Fax (+1) (763) 553-0708E-Mail [email protected]
NORTH AND SOUTH AMERICAFieldbuses and Industrial NetworksInterlinkBT™3000 Campus DriveUSA-Minneapolis, MN 55441-2656Phone (+1) (763) 694-2300Fax (+1) (763) 694-2399E-Mail [email protected]
TURCK WORLD-WIDE HEADQUARTERS
GERMANYHans Turck GmbH & Co. KGWitzlebenstraße 7D-45472 Mülheim an der RuhrP. O. Box 45466 Mülheim an der RuhrPhone (+49) (208) 4952-0Fax (+49) (208) 4952-2 64E-Mail [email protected]
BELGIUMMultiprox N. V.P. B. 71Lion d’Orweg 12B-9300 AalstPhone (+32) (53) 766566Fax (+32) (53) 783977E-Mail [email protected]
BRAZILTURCK Ltda.Rua Apucarana 134BR-83324-040 PinhaisPhone (+55) (41) 6682053Fax (+55) (41) 6681794E-Mail [email protected]
CZECH REPUBLICTURCK s.r.o.Hradecká 1151CZ-500 03 Hradec Králové 3Phone (+ 420) (49) 5 21 07 66Fax (+ 420) (49) 5 21 07 67E-Mail [email protected]
PR OF CHINATURCK (Tianjin) Sensor Co. Ltd.40, Yibin Road/Nankai DistrictTJ-300113 TianjinPhone (+86) (22) 27623140Fax (+86) (22) 27614650E-Mail [email protected]
EASTERN EUROPE / ASIAHans Turck GmbH & Co. KGAm Bockwald 2D-08340 BeierfeldPhone (+49) (3774) 1 35-0Fax (+49) (3774) 1 35-2 22
FRANCETURCK BANNER S.A.S3, Rue de CourtalinMagny-Le-HongreF-77703 Marne-La-Vallee Cedex 4Phone (+33) (1) 60436070Fax (+33) (1) 60431018E-Mail [email protected]
GREAT BRITAINTURCK BANNER LIMITEDStephenson RoadGB-Leigh-on-Sea, Essex SS9 5LSPhone (+44) (1702) 525186Fax (+44) (1702) 420934E-Mail [email protected]
HUNGARYTURCK Hungary kft.Könyves Kalman Krt.76H-1087. BudapestPhone (+36) (1) 4770740Fax (+36) (1) 4770741E-Mail [email protected]