Alex Solar Private Limited
Assistance for Certification of ICB Process for setting up of 5 MW Solar Power Project in
the state of Orissa
Final Report
26 August 2011
CRISIL Risk and Infrastructure Solutions Limited
[Alex Solar Private Limited]
[i]
Contents
1. Background .......................................................................................................................... 1
Introduction .................................................................................................................................... 1
1.1 Alex Solar Private Limited (ASPL) ............................................................................................ 1
1.2 Background ............................................................................................................................. 2
1.2.1 Stage-1 ....................................................................................................................... 2
1.2.2 Stage-2 ....................................................................................................................... 2
1.2.3 Stage-3 ....................................................................................................................... 3
1.3 Timelines Followed for the ICB Process .................................................................................. 4
2. Observations ........................................................................................................................ 5
2.1 Approach ................................................................................................................................. 5
2.2 Detailed Technical Evaluation ................................................................................................. 7
2.2.1 Moser Baer Engineering and Constructions Limited (MBECL) .................................. 7
2.2.2 Abir Infrastructure Private Limited (AIPL) ............................................................... 10
2.2.3 Indure - Montealto .................................................................................................. 13
2.3 Summary of evaluation ......................................................................................................... 21
3. Financial Bid Opening ......................................................................................................... 23
3.1 Concluding Remarks .............................................................................................................. 23
4. Annexure: NIT Published in Economic Times ....................................................................... 24
5. Annexure: Addendum 1 ...................................................................................................... 25
6. Annexure: Addendum 2 ...................................................................................................... 26
7. Annexure: Financial Bid Opening ........................................................................................ 27
8. Annexure: MBECL- meeting PQ criteria ............................................................................... 28
9. Annexure: - AIPL- meeting PQ criteria ................................................................................. 31
10. Annexure: Indure Montealto- meeting PQ criteria ............................................................... 35
11. Annexure: MBECL- key data sheets in the bid ...................................................................... 48
12. Annexure: AIPL- key data sheets in the bid .......................................................................... 66
13. Annexure: Indure Montealto- key data sheets in the bid ..................................................... 79
[Alex Solar Private Limited]
[ii]
List of Tables
Table 1: List of Bidders at the EoI stage .................................................................................................. 2
Table 2: List of Bidders for RFP Stage...................................................................................................... 3
Table 3: Timelines followed for the ICB Process ..................................................................................... 4
Table 4: Information required to be submitted with Proposal ............................................................... 5
Table 5: Deficiencies in the proposal by MBECL ..................................................................................... 7
Table 6: Documents missing in the proposal by MBECL ......................................................................... 8
Table 7: Deficiencies in the proposal by AIPL ....................................................................................... 11
Table 8: Documents missing in the proposal by AIPL ........................................................................... 12
Table 9: Deficiencies in the proposal by Indure - Montealto ............................................................... 14
Table 10: Documents missing in the proposal by Indure - Montealto ................................................. 18
Table 11: Summary of Evaluation ......................................................................................................... 22
Table 12: Financial Quote for the Project ............................................................................................. 23
[Alex Solar Private Limited]
[1]
1. Background
The Government of India launched the Jawaharlal Nehru National Solar Mission to promote ecologically
sustainable growth while addressing India’s energy security challenges. NTPC Vidyut Vyapar Nigam Ltd (NVVN)
is responsible for the implementation of first phase of the mission. Under this scheme NVVN allotted capacity to
Independent Power Producers (IPPs) on the basis of reverse bidding of tariff and also signed a PPA with the
IPPs. Therefore Alex Solar Private Limited (ASPL), in order to derive benefit of the policy, intends to set up a 5
MW Solar Power Project in Orissa by procuring EPC contractor through ICB route.
The Jawaharlal Nehru National Solar Mission is a major initiative of the Government of India to
promote ecologically sustainable growth while addressing India’s energy security challenges. The
immediate aim of the Mission is to focus on setting up an enabling environment for solar technology
penetration in the country both at a centralized and decentralized level. The first phase of this
Mission aims to commission 1000 MW of grid-connected solar power projects by 2013. NTPC Vidyut
Vyapar Nigam Ltd (NVVN), a subsidiary of National Thermal Power Corporation, is the designated
nodal agency responsible for implementation of Phase-I of mission. NVVN selected the Independent
Power Producers (IPPs) on the basis of reverse bidding process and signed a power purchase
agreement with the selected developers.
In this context Alex Solar Private Limited (ASPL) proposes to set up a 5 MW Solar PV power plant in
the state of Orissa and intends to initiate an International Competitive Bid (ICB) process to select
Engineering, Procurement and Construction (EPC) contractor to execute the proposed project.
Introduction
1.1 Alex Solar Private Limited (ASPL)
M/s. Alex Solar Private Limited (now known as Aftab Solar Private Limited) is a company
incorporated in India and registered under the provisions of the Companies Act, 1956 at 90,
Pirphukur Road, Bansdroni, Kolkata – 700070, West Bengal, India. ASPL is setting up a 5MWp solar
PV power project in the State of Orissa, in the eastern part of India. ASPL invites bids from reputed
parties from across the globe for design, engineering, manufacturing, supply, erection, testing and
commissioning of the aforementioned solar power project on a turnkey Engineering, Procurement
and Construction (EPC) basis. The Project is being implemented under the NVVN, Government of
India, National Solar Mission– Phase-I. Power generated from the Project will be sold to NTPC Vidyut
Vyapar Nigam (NVVN).
[Alex Solar Private Limited]
[2]
1.2 Background
For the above mentioned 5 MW Solar PV power project, the company proposes to select reputed
parties through International Competitive Bidding for design, engineering, manufacturing, supply,
erection, testing and commissioning of the aforementioned solar power project on a turnkey
Engineering, Procurement and Construction (EPC) basis. The bidders are expected to carry out the
scope of work as provided in the Request for Proposal document. ASPL appointed CRISIL Risk and
Infrastructure Solutions Ltd (CRIS) to independently administer the international competitive bidding
process, as well as the selection of the final EPC contractor, for the aforementioned project.
CRIS in consultation with ASPL has followed a 3 stage process for the selection of EPC contractors for
aforesaid project.
� Stage-1: Issuance of ‘Notice Inviting Tender (NIT)’ and evaluation of the ‘Expression of
Interests (EOI)’ to validate whether the bidders meet the qualification criteria or not.
� Stage-2: Issuance of ‘Request for Proposal (RFP)’ document to the bidders qualified under
stage 1.
� Stage-3: Evaluation of the bids received and recommending the outcome to enable ASPL to
finalize the appointment of the EPC contractor.
1.2.1 Stage-1
The NIT for the project was published in the Economic Times on 16th
June 2011. The NIT published is
attached with this report as Annexure-1.
The NIT contained brief scope of work regarding the proposed project, the pre-qualification
requirements and the timelines for the submission of the EOI from the bidders and the issuance of
the RFP document. The last date for submission of EOI was 22nd
June 2011.
In response to the NIT, the following parties submitted their EOI for the project being set up by ASPL.
Table 1: List of Bidders at the EoI stage
Sr. No. Firm Unit / Consortium EOI - Status
1. Moser Baer Engineering and Constructions Limited Unit Qualified
2. Abir Infrastructure Private Limited Unit Qualified
3. Indure - Montealto Consortium Qualified
4. Akoda Group Consortium Qualified
Based on the EOI evaluation, all the above mentioned bidders were shortlisted for RFP stage.
1.2.2 Stage-2
The RFP document was issued to all other shortlisted bidders on 27th
June 2011.
[Alex Solar Private Limited]
[3]
As per the NIT, the last date for submission of bid documents was 13th
July 2011. However, most of
the bidders requested to extend the deadline for submission of the bid. Accordingly, two
addendums were issued based on repeated requests by the bidders in this regard so as to
facilitate detailed and thorough bid preparations.
� An addendum was issued on 12th
July 2011 wherein the last date for submission of the
techno-commercial and price proposal was extended till 27th
July 2011.
� Subsequently and as per the repeated requests from the bidders, another addendum was
issued on 27th
July 2011 wherein the last date for submission of techno-commercial and
price proposals was extended to 10th
August, 2011.
Finally, the following bidders submitted the techno-commercial and price proposals:
Table 2: List of Bidders for RFP Stage
Sr. No. Name of the Bidders
1. Moser Baer Engineering and Constructions Limited
2. Abir Infrastructure Private Limited
3. Indure - Montealto
1.2.3 Stage-3
As per the bidding documents, bidders were instructed to submit the proposal in two parts i.e. the
Techno-commercial proposal and the Price proposal.
Based on the assessment of the techno commercial proposals, it was observed that the bidders had
not submitted some of the required documents in the prescribed formats. The discrepancies found
in the bid proposals were analyzed and an email was sent on 18th
August 2011 to the respective
bidders regarding the deficiencies in bid proposal submitted, and bidders were directed to submit
the required clarification/documents by 20th
August 2011.
In response to the email, all the three bidders namely Moser Baer Engineering and Construction
Limited, Abir Infrastructure Private Limited and Indure – Montealto submitted the required
documents within the time limit.
This report is based on the assessment of the techno-commercial proposal submitted by the
qualified bidders (as well as the additional documents submitted by Moser Baser Engineering and
Constructions Limited, Abir Infrastructure Private Limited and Indure – Montealto on 20th
August
[Alex Solar Private Limited]
[4]
2011). The objective of this report (covered in chapter 2) is to assess the documents and evaluate, as
per the provisions of the bidding documents, whether the bidders qualify for the opening of price
proposal.
1.3 Timelines Followed for the ICB Process
Table 3: Timelines followed for the ICB Process
Sr. No. Activity Date\ Deadline
1. Publication of NIT for ASPL in Economic Times 16th
June, 2011
2. Last date for submission of EOI as per the NIT for ASPL 22nd
June, 2011
3. Issuance of RFP documents to the shortlisted bidders 27th
June, 2011
4. Last date for submission of bid documents as per RFP
documents 13
th July, 2011
5. Last date for submission of bids as per Addendum #1
27th
July, 2011
6. Last date for submission of bids as per Addendum #2
10th
August, 2011
7. Last date for submitting the documents which were deficient
in Techno – Commercial Proposal 20
th August, 2011
8. Date of opening the financial bid
25th
August, 2011
[Alex Solar Private Limited]
[5]
2. Observations
This chapter summarizes the approach that was followed during the bid evaluation and also highlights the key
observations which were made during the bid process management
2.1 Approach
The parameters for assessment of the Techno-commercial proposal for qualification have been
prescribed in the RFP bid document. Specifically, Clause 25 of the Volume I (Request for Proposal-
Information to Bidders) deals with evaluation of proposals. Sub Clause 25.1 of Volume I provides the
general framework for evaluation of proposals and also provides the framework for evaluation and
parameters to be considered for evaluation of Proposal. Clause 25.2 sets the tone for evaluating the
responsiveness of the proposal against the prescribed parameters, while Clauses 25.4 & 25.5
mandate that the evaluation of the Techno-commercial proposal for qualification shall be done as
per the contents submitted by the bidder specified in Clause 13 of the Request for Proposal -
Information to Bidders document.
As per the RFP document, the bidder has to submit the following details/documents:
Table 4: Information required to be submitted with Proposal
Clause No. Activity
12.1 Bid proposal letter on the Bidder's letterhead in accordance with the formats
furnished in Annexure 1.1 & 1.2 of the RFP.
12.2 Bid proposal forms with all required attachments as furnished under Volume II of
the bid document.
12.5 Cover page with the name of the bidding organization (and website), the
individual responsible for contract negotiation and contact information (address,
phone, fax, and email).
12.6 The bid documents in original with all pages numbered and signed.
12.7 Detailed contract master bar chart / contract master schedule indicating all
critical dates for each major item to meet the specified completion dates.
12.8 Head Office and site project management organization structures and list
showing designation of the bidder's key staff and personnel the bidder proposes
to deploy on the Project.
12.9 Company Profile and copies of supporting documents including, but not limited
to: (a) Business Permit, (b) Manpower and (c) Equipment capability.
Bidder/Consortium’s subcontractor(s) to likewise comply and submit all the
[Alex Solar Private Limited]
[6]
Clause No. Activity
above-mentioned requirements
12.10 Drawings, Documentation including catalogues for special/bought out items (if
any).
12.11 Design Summary Sheet in the form and substance
12.12 Quality assurance documentation.
12.13 Particulars of any sub-contractor / engineering contractors / consultants and
architects who will be associated with the execution of the Contract.
12.14 Last three years Audited Balance Sheets, Profit and Loss account, PAN & Service
Tax No. Last three years Audited Balance Sheets, Profit and Loss account, PAN &
Service Tax No.
12.15 The list of similar projects executed in last 5 years.
12.16 The list of projects on hand (which are being executed).
12.17 Relevant utility and Solar PV system construction experience
12.18 The completion certificates issued by the clients for projects executed earlier.
The approach followed for evaluation of the Techno-commercial proposal is segregated into two
stages:
� Stage 1: Study of all documents as required to be submitted by the bidder and
responsiveness of the proposal.
� Proposed Module should be Thin Film technology and have been used for at-least for 5
MW size single site project.
� Proposed Power Conditioning Unit (“PCU”) should have been used at-least for 100MW
Capacity.
� Guaranteed Performance Ratio.
� Compliance with requirements as specified in the RFP Document.
� Stage 2: In this stage the technical acumen, feasibility and operational viability shall be
assessed. The evaluation criteria is summarized below:
� Detailed design, installation and operations plan for the Project.
� Detailed Project critical path schedule identifying all important development elements
and their timing.
� Identification of the major equipment supplier(s) to be used for the Project.
[Alex Solar Private Limited]
[7]
� Stage 3: Financial evaluation
Evaluations of the Techno-commercial proposal submitted by the qualified bidders have been
provided in the following sections.
2.2 Detailed Technical Evaluation
2.2.1 Moser Baer Engineering and Constructions Limited (MBECL)
2.2.1.1 PQ Stage
The details submitted by Moser Baer Engineering and Constructions Limited against meeting the Pre
Qualification criteria were as mentioned below:
Technical- Completion certificate for ‘Sapphire Industrial Infrastructure Pvt Ltd.’ for 5 MW thin film
based solar power plant at Sivagangai in Tamil Nadu.
Financial- CA Certificate based on provisional accounts, certifying that turnover for the financial year
FY 2010-11 being more than Rs 200 crores.
2.2.1.2 Stage 1
All the documents submitted by the bidder were in order as per the RFP requirement and hence the
proposal was declared responsive and hence was assessed further.
2.2.1.3 Stage 2
Few deficiencies were found during the evaluation of details submitted along with proposal, which
were communicated to the bidder by query email dated 18.08.2011. The table below summarizes
the deficiencies found in the original technical bid and the clarifications received from the bidder as
reply to the queries.
Table 5: Deficiencies in the proposal by MBECL
RFP Table No. Parameter Values Evaluation Remarks Clarification provided by
the bidder (reply to query)
Final
Remarks
Table 14: Solar
PV System
String Combiner
Boxes
Details missing - Not
submitted by bidder
SMA/ ABB/ Bonfiglioli-
Vectron/ Schneider/
SKYTRON
Ok
Monitoring System Details missing - Not
submitted by bidder
SMA/ABB/ Bonfiglioli -
Vectron / Schneider
/SKYTRON
Ok
DC Wires (upto
25mm2)
Details missing - Not
submitted by bidder
Amercable/ Betaflam/
Keylios (Polycab)/ Lapp
Kabel/ Prysmian (Ravin
Cables)/ Solar Plast
Ok
DC Fuses Details missing - Not Cooper Bussmann/ Ok
[Alex Solar Private Limited]
[8]
RFP Table No. Parameter Values Evaluation Remarks Clarification provided by
the bidder (reply to query)
Final
Remarks
submitted by bidder Littelfuse/ Mersen/ Siba
Surge Protection
Devices
Details missing - Not
submitted by bidder
ABB/ Citel/ DEHNguard/
Erico/ Ferraz Shawmut Ok
Table 15: MV
System (11kV) All Components
Details missing - Not
submitted by bidder
Will comply with the
preferred makes Ok
Table 16: LV
System (<1kV) All Components
Details missing - Not
submitted by bidder
Will comply with the
preferred makes Ok
Table 18:
Project
Characteristics
Rated Power
Tolerance
+/-5% Preference will be
given to bidder who
has assured with +/-
3% power
tolerance.
Will comply with the
requirements Ok
Number of Strings 4687 Explanation
Required
Details will be given later
prior the execution start Accepted
String Combiner Box
(SCB) Power Capacity
240~25
0
Open Circuit Voltage
of SCB (Voc) 912
Short Circuit Current
of SCB (Isc) 30.8
Table 20:
Technical
Parameters of
String
Combiner Box
Maximum
permissible DC
current
320 Explanation
Required
Corrected the figure to 200 Ok
Summarized
Project
Execution Plan
Submitted in Gantt
Chart Form
In Gantt chart, the
project has been
shown started from
1st August, 2011
completing in 121
days by 29th Nov,
2011.
Revised Gantt chart would
depend on actual date of
award of contract
Accepted
Source: CRIS Analysis
Table 6: Documents missing in the proposal by MBECL
Sr. No. Documents Required Clarification provided by
the bidder (reply to query)
Final
Remarks
1. Handling plan of modules right through from loading at
manufacturer’s factory to installation. Submitted Ok
2.
General Arrangement drawing of module, showing front and
rear view, overall dimensions, installation plans, termination
arrangements, packing dimensions and weights.
Submitted Ok
3. Independent test characteristics- pertaining to the irradiance
levels & pertaining to the temperature variations Submitted Ok
4. General Arrangement drawing showing front and rear view,
overall dimensions, installation plans termination Submitted Ok
[Alex Solar Private Limited]
[9]
Sr. No. Documents Required Clarification provided by
the bidder (reply to query)
Final
Remarks
arrangements, packing dimensions and weights.
5. Technical literature giving complete specifications and
information. Submitted Ok
6. Installation guide for Inverter Submitted Ok
7. Independent test characteristics- pertaining to inverter
efficiency Submitted Ok
8.
Technical write-up giving complete design, specifications and
information of mounting structures, material used, fabrication
process, treatments performed, standards followed, types of
bolts used, etc.
Submitted Ok
9.
General arrangement drawing of mounting structures,
foundation plans, anchoring plans, overall dimensions,
installation plans, structural plans and elevation and framing
details.
Submitted Ok
10. Standard test certificates for various structure members from
independent testing laboratories. Submitted Ok
11. Hot dipped galvanisation thickness certificate from the factory. Submitted Ok
12. Installation method statements. Submitted Ok
13. BOQ for solar power plant not provided Submitted Ok
14. Solar resources reference details not enclosed as per clause
6.1, Volume -2 of RFP Submitted Ok
15. PV Syst simulation report not submitted Submitted Ok
16. Handling plan of modules right through from loading at
manufacturer’s factory to installation. Submitted Ok
17.
General Arrangement drawing of module, showing front and
rear view, overall dimensions, installation plans, termination
arrangements, packing dimensions and weights.
Submitted Ok
Moser Baer Engineering and Construction Ltd. submitted the required set of documents (as
mentioned in the above table) on 20th
August, 2011. An assessment of the submitted documents has
been provided in the subsequent paragraphs:
� Detailed design, installation and operations plan for the Project: The proposal submitted by
bidder covers in details the following topics- the technical selection, system description,
system configuration for various components & module mounting structures, inverters,
SCADA system, IT system comprising hardware and software), fire alarm & fire suppression
system and control room & inverter cooling system. These details are accompanied by
relevant bill of materials mentioning quality and quantity. A separate section of the proposal
describes the proposed substation equipment details including bill of material and single line
diagram. The quality assurance plan has been detailed in a separate section mentioning the
scope of activities, execution & commissioning details, the critical aspects and plant
[Alex Solar Private Limited]
[10]
production checking. The proposal also contains the simulation parameters, simulation
results and loss diagram for grid connected system and the characteristics of the PV module.
� Detailed Project critical path schedule: The project schedule has been presented as the
Gantt chart in the proposal. As per the proposed schedule, the entire project is to be
completed latest in 121 days which is within the project duration as per the RFP document.
� Identification of the major equipment supplier(s): The suppliers for each of major
equipment, along with the technical specification and the bill of material for spares, have
been mentioned in the proposal.
All of the above mentioned details are in conformity with the requirement for the project.
2.2.1.4 Conclusion
Based on the above analysis it has been concluded that the proposal submitted by Moser Baer
Engineering & Constructions Ltd is responsive and the proposal meets the prescribed Techno-
commercial parameters.
2.2.2 Abir Infrastructure Private Limited (AIPL)
2.2.2.1 PQ Stage
The details submitted by Abir Infrastructure Private Limited against meeting the Pre Qualification
criteria were as mentioned below:
Technical- Two projects: 1> EPC contractor with projects of 2x600 MW for Singhitari Thermal Power
Plant with the value of contract of Rs 1965 crores; and 2> EPC contractor (in a consortium) with the
value of work to Abir being more than 1550 crores.
Financial- Documents showing turnover of Rs 1135 crores approx for the financial year FY 2010-11.
2.2.2.2 Stage 1
All the documents submitted by the bidder were in order as per the RFP requirement and hence the
proposal was declared responsive and hence was assessed further.
2.2.2.3 Stage 2
Few deficiencies were found during the evaluation of details submitted along with proposal, which
were communicated to the bidder by query email dated 18.08.2011. The table below summarizes
the deficiencies found in the original technical bid and the clarifications received from the bidder as
reply to the queries.
[Alex Solar Private Limited]
[11]
Table 7: Deficiencies in the proposal by AIPL
RFP Table No. Parameter Values Evaluation Remarks Clarification provided by
the bidder (reply to query)
Final
Remarks
Table 14: Solar
PV System
String Combiner
Boxes
Details missing - Not
submitted by bidder
SMA/ ABB/ Bonfiglioli-
Vectron/ Schneider/
SKYTRON
Ok
Monitoring System Details missing - Not
submitted by bidder
SMA/ABB/ Bonfiglioli -
Vectron / Schneider
/SKYTRON
Ok
DC Wires (upto
25mm2)
Details missing - Not
submitted by bidder
Amercable/ Betaflam/
Keylios (Polycab)/ Lapp
Kabel/ Prysmian (Ravin
Cables)/ Solar Plast
Ok
DC Fuses
Details missing - Not
submitted by bidder
Cooper Bussmann/
Littelfuse/ Mersen/ Siba Ok
Surge Protection
Devices
Details missing - Not
submitted by bidder
ABB/ Citel/ DEHNguard/
Erico/ Ferraz Shawmut Ok
Table 15: MV
System (11kV) All Components
Details missing - Not
submitted by bidder
Will comply with the
preferred makes Ok
Table 16: LV
System (<1kV) All Components
Details missing - Not
submitted by bidder
Will comply with the
preferred makes Ok
Table 18:
Project
Characteristics
Rated Power
Tolerance
+/-5% Preference will be
given to bidder who
has assured with +/-
3% power
tolerance.
Will comply with the
requirements Ok
Number of Strings 4687 Explanation
Required
Details will be given later
prior the execution start Accepted
String Combiner Box
(SCB) Power Capacity
240~25
0
Open Circuit Voltage
of SCB (Voc) 912
Short Circuit Current
of SCB (Isc) 30.8
Table 20:
Technical
Parameters of
String
Combiner Box
Maximum
permissible DC
current
320 Explanation
Required
Corrected the figure to 200 Ok
Summarized
Project
Execution Plan
Submitted in Gantt
Chart Form
In Gantt chart, the
project has been
shown started from
1st August, 2011
completing in 121
days by 29th Nov,
2011.
Revised Gantt chart would
depend on actual date of
award of contract
Accepted
Source: CRIS Analysis
[Alex Solar Private Limited]
[12]
Table 8: Documents missing in the proposal by AIPL
Sr. No. Documents Required Clarification provided by
the bidder (reply to query)
Final
Remarks
1. Handling plan of modules right through from loading at
manufacturer’s factory to installation. Submitted Ok
2.
General Arrangement drawing of module, showing front and
rear view, overall dimensions, installation plans, termination
arrangements, packing dimensions and weights.
Submitted Ok
3. Independent test characteristics- pertaining to the irradiance
levels & pertaining to the temperature variations Submitted Ok
4.
General Arrangement drawing showing front and rear view,
overall dimensions, installation plans termination
arrangements, packing dimensions and weights.
Submitted Ok
5. Technical literature giving complete specifications and
information. Submitted Ok
6. Installation guide for Inverter Submitted Ok
7. Independent test characteristics- pertaining to inverter
efficiency Submitted Ok
8.
Technical write-up giving complete design, specifications and
information of mounting structures, material used, fabrication
process, treatments performed, standards followed, types of
bolts used, etc.
Submitted Ok
9.
General arrangement drawing of mounting structures,
foundation plans, anchoring plans, overall dimensions,
installation plans, structural plans and elevation and framing
details.
Submitted Ok
10. Standard test certificates for various structure members from
independent testing laboratories. Submitted Ok
11. Hot dipped galvanisation thickness certificate from the factory. Submitted Ok
12. Installation method statements. Submitted Ok
13. BOQ for solar power plant not provided Submitted Ok
14. Solar resources reference details not enclosed as per clause
6.1, Volume -2 of RFP Submitted Ok
15. PV Syst simulation report not submitted Submitted Ok
16. Handling plan of modules right through from loading at
manufacturer’s factory to installation. Submitted Ok
17.
General Arrangement drawing of module, showing front and
rear view, overall dimensions, installation plans, termination
arrangements, packing dimensions and weights.
Submitted Ok
Further Abir Infrastructure Private Limited submitted the required set of documents (as mentioned
in the above table) on 20th
August, 2011. An assessment of the submitted documents has been
provided in the subsequent paragraphs:
� Detailed design, installation and operations plan for the Project: The proposal submitted by
bidder covers in details the following topics- the technical selection, system description,
[Alex Solar Private Limited]
[13]
system configuration for various components & module mounting structures, inverters,
SCADA system, IT system comprising hardware and software), fire alarm & fire suppression
system and control room & inverter cooling system. These details are accompanied by
relevant bill of materials mentioning quality and quantity. A separate section of the proposal
describes the proposed substation equipment details including bill of material and single line
diagram. The quality assurance plan has been detailed in a separate section mentioning the
scope of activities, execution & commissioning details, the critical aspects and plant
production checking. The proposal also contains the simulation parameters, simulation
results and loss diagram for grid connected system and the characteristics of the PV module.
� Detailed Project critical path schedule: The project schedule has been presented as the
Gantt chart in the proposal. As per the proposed schedule, the entire project is to be
completed latest in 121 days which is within the project duration as per the RFP document.
� Identification of the major equipment supplier(s): The suppliers for each of major
equipment, along with the technical specification and the bill of material for spares, have
been mentioned in the proposal.
All of the above mentioned details are in conformity with the requirement for the project.
2.2.2.4 Conclusion
Based on the above analysis it has been concluded that the proposal submitted by Abir
Infrastructure Private Ltd is responsive and the proposal meets the prescribed Techno-commercial
parameters.
2.2.3 Indure - Montealto
2.2.3.1 PQ Stage
The details submitted by Indure- Montealto against meeting the Pre Qualification criteria were as
mentioned below:
Technical- Two projects: 1> Completed BoP Package including civil for 2X 525 MW coal fired power
plant for Orrisa (Contract value 1132.50 cr); and 2> Completed BoP package including civil work for
2X 250 MW coal fired power plant (Project Cost Rs 2200 Crores)
Financial- Profit and Loss account for the financial year FY 2009-10 for Indure and the balance sheet
for Montealto, showing that the consortium meets the minimum PQ criteria. Documents are
attached as annexure.
[Alex Solar Private Limited]
[14]
2.2.3.2 Stage 1
All the documents submitted by the bidder were in order as per the RFP requirement and hence the
proposal was declared responsive and hence was assessed further.
2.2.3.3 Stage 2
Several deficiencies were found during the evaluation of details submitted along with proposal,
which were communicated to the bidder by query email dated 18.08.2011. The table below
summarizes the deficiencies found in the original technical bid and the clarifications received from
the bidder as reply to the queries.
Table 9: Deficiencies in the proposal by Indure - Montealto
RFP Table No. Parameter Values Evaluation Remarks Clarification
provided by the
bidder
Final Remarks
Table 14: Solar
PV System
Solar PV Modules First
Solar or
Similar
No deviation
allowed First Solar modules
will be used
Considering
tight timelines,
single brand
might not be
feasible
Central Inverters
Bonfigli
oli,
Sungro
m or
Similar
No deviation
allowed
Bonfiglioli
Considering
tight timelines,
single brand
might not be
feasible
String Combiner
Boxes
Details missing - Not
submitted by bidder Bonfiglioni Ok
Monitoring System Details missing - Not
submitted by bidder Bonfiglioni Ok
DC Wires (upto
25mm2)
Details missing - Not
submitted by bidder
Prysmian,
Amercable, Keylios,
Betaflam, Lapp Kabel
or Solar Plast
Ok
DC Fuses
Details missing - Not
submitted by bidder
Cooper Bussmann,
Littlefuse, Mersen or
Siba
Ok
Surge Protection
Devices
Details missing - Not
submitted by bidder
ABB, Citel,
DEHNguard, Erico or
Ferraz Shawmut
Ok
Table 15: MV
System (11kV)
Transformers
(LV/11kV)
ABB /
Siemens
/
Schneid
er /
Ormaza
bal or
No deviation
allowed ABB / Siemens /
Schneider /
Ormazabal / Areva /
Crompton / Kirloskar
/ Voltamp
Ok
[Alex Solar Private Limited]
[15]
RFP Table No. Parameter Values Evaluation Remarks Clarification
provided by the
bidder
Final Remarks
Similar
Table 16: LV
System (<1kV) All Components
Details missing - Not
submitted by bidder
Will comply with the
preferred makes Ok
Table 17:
Modular Plot
Details
Number of String
Combiner Boxes
(SCB)
Details missing - Not
submitted by bidder
To be defined during
works of detailed
engineering
Mandatory for
evaluation SCB Power Capacity Details missing - Not
submitted by bidder
Open Circuit Voltage
of DC input
Details missing - Not
submitted by bidder
Mounting Structure
Summary
Details missing - Not
submitted by bidder
To be defined during
works of detailed
engineering
Mandatory for
evaluation
Table 18:
Project
Characteristics
Solar Resource Details missing - Not
submitted by bidder Data from Horizontal
Global Irradiation
Solar radiation
details source
unclear
Climate Details missing - Not
submitted by bidder Details provided Ok
Rated Power
Tolerance
+/-5% Preference will be
given to bidder who
has assured with +/-
3% power tolerance.
This is the tolerance
of Thin film modules
of the brand First
Solar, that it is the
bigger one for thin
film solar modules
Ok, But
Preference will
be given who
has bidded
with +/-3%
power
tolerance
Module efficiency Details missing - Not
submitted by bidder
Not available at this
moment
Mandatory for
evaluation
Fill factor Details missing - Not
submitted by bidder
Not available at this
moment
Mandatory for
evaluation
Commercial - Power
Warranty
Details missing - Not
submitted by bidder
Warranty of 5 years
for the material and
the workmanship
Ok
Inverter - Input Data Details missing - Not
submitted by bidder (No response)
Manufacturer’s
data sheet
required
Inverter - Output
Data
Details missing - Not
submitted by bidder
Not available at this
moment
Mandatory for
evaluation
Inverter - Efficiencies Details missing - Not
submitted by bidder
Not available at this
moment
Mandatory for
evaluation
String Array
Summary - Nominal
Power Ratio
1.19952 Explanation
Required (No response)
Calculation
details
required
String Array
Summary - Inverter
Maximum Power
(Pmax) at STC
1199.52
Data sheet differing
from details
provided in bid
document
It was a mistake. The
data included was
regarding Inverter
500 kW, but the
Correct details
required for
evaluation
[Alex Solar Private Limited]
[16]
RFP Table No. Parameter Values Evaluation Remarks Clarification
provided by the
bidder
Final Remarks
String Array
Summary - Maximum
power voltage
(Vmpp) at STC
679 inverter proposed it
is 1MW. Inverter
1MW works like a
block of 2 inverters
of 500kW String Array
Summary - Maximum
power current (Impp)
at STC 1774.08
Data sheet differing
from details
provided in bid
document
String Array
Summary - Open-
circuit voltage (Voc)
at STC 854
String Array
Summary - Short-
circuit current (Isc) at
STC 1995.84
String Array
Summary - Minimum
mpp voltage (Vmpp)
at 70ºC 596.5
String Array
Summary - Maximum
mpp voltage (Vmpp)
at 5ºC 719.74
String Array
Summary - Maximum
open circuit voltage
(Voc) at 5ºC 905.24
String Array
Summary - Maximum
open circuit voltage
(Voc) at 0ºC 896.7
String Array
Summary - Maximum
operating power 5566
String Array
Summary -
Temperature at
Maximum operating
power 50
Mounting Structure
Details
Details missing - Not
submitted by bidder
To be defined during
works of detailed
engineering. Not
available at this
moment
Accepted
System Loss Factors - 1% Please provide Frequent cleaning of Calculation
[Alex Solar Private Limited]
[17]
RFP Table No. Parameter Values Evaluation Remarks Clarification
provided by the
bidder
Final Remarks
Soiling methodology to
maintain 1% soiling
loss
the modules details
required
System Loss Factors –
Annual degradation
Details missing - Not
submitted by bidder (No response) Required
Table 19:
Technical
Parameters of
PV Modules
Power Output
Tolerance (%)
+/-5% Preference will be
given who has
bidded with +/-3%
power tolerance
This is the tolerance
of Thin film modules
of the brand First
Solar, that it is the
bigger one for thin
film solar modules
Ok, But
Preference will
be given to
bidder who has
bid with +/-3%
power
tolerance
Fill Factor Details missing - Not
submitted by bidder 0.707 Ok
Encapsulated Cell
Efficiency (%)
Details missing - Not
submitted by bidder Not available at this
moment
Mandatory for
evaluation
Module Efficiency (%) Details missing - Not
submitted by bidder Not available at this
moment
Mandatory for
evaluation
Temperature ratings
- Efficiency reduction
Details missing - Not
submitted by bidder Not available at this
moment
Mandatory for
evaluation
Temperature ratings
- (From 1000 W/sq m
to 200W/sq m)
Details missing - Not
submitted by bidder Not available at this
moment
Mandatory for
evaluation
Nominal Power
Output - 0 – 1 years
(W)
72.6-
80.3
15% Power derating
in first year itself This values are
calculated as follows:
· Peak Power Watts (85Wp)
· Maximun derating in the
first 10 years of 10%
· Including tolerance +/- 5%
Until year 10 (-5%) ---
85*0,9*0,95 = 72,6
Until year 10 (+5%) ---
85*0,9*1,05 = 80,3
Until year 25 (-5%) ---
85*0,8*0,95 = 64,6
Until year 25 (+5%) ---
85*0,8*1,05 = 71,4
Does not
comply RFP
requirement
Nominal Power
Output - 2 – 5 years
(W)
72.6-
80.3
Nominal Power
Output - 6 – 10 years
(W)
72.6-
80.3
Should be max 10%
in 12 Years
Nominal Power
Output - 11 – 25
years (W)
64.6-
71.4
24% power
derating, should be
max 20% in 25 Years
Table 20:
Technical
Parameters of
String
Combiner Box
Maximum
permissible DC
current
8 Explanation
Required Calculations would
be showed during
detailed engineering
works
Mandatory for
Evaluation
Number of 5 Explanation
[Alex Solar Private Limited]
[18]
RFP Table No. Parameter Values Evaluation Remarks Clarification
provided by the
bidder
Final Remarks
measuring channels Required
Maximum string
current per
measuring channel
3 Explanation
Required
Table 21:
Technical
Parameters of
Central
Inverters
Data sheet differing
from details
provided in Bid
document
It was due to
mistake. The data
included was
regarding Inverter
500 kW, but the
inverter proposed it
is 1MW. Inverter
1MW works like a
block of 2 inverters
of 500kW.
Correct details
required for
evaluation
Table 22:
Technical
Parameters of
LV/MV
Transformers
Rated voltage Data sheet differing
from details
provided in Bid
document
It was a mistake.
Details would be
provided later.
Correct data
not provided
Table 26:
Technical
Parameters For
33kV Circuit
Breaker and
Isolator
Details missing - Not
submitted by bidder
Details to be
provided later
Required for
evaluation
Summarized
Project
Execution Plan
The project
completion date is
mentioned as 10th
December, 2011. No
deviation required
as per clause 6.0,
Volume-1 of RFP
More than 1 month
of delayed have been
ocurred during the
bidding proposal. The
owner/developer
should assume this
delays. We can
assume the
finalization of the
plant in this time if
the owner of the
plants assumes other
delays than could
happen.
Ok
Source: CRIS Analysis
Table 10: Documents missing in the proposal by Indure - Montealto
Sr. No. Documents Required Clarification provided by
the bidder (reply to query)
Final Remarks
1. IEC Certificates of First Solar Module As indicated, the First Solar
modules have all the IEC
Certificate
required with
[Alex Solar Private Limited]
[19]
Sr. No. Documents Required Clarification provided by
the bidder (reply to query)
Final Remarks
Certificates bid
2. Handling plan of modules right through from loading at
manufacturer’s factory to installation.
As usual with this type of
loads. It can be an
assurance for the load and
transport until the solar
power plant.
Handling plan
required for
evaluation
3. General Arrangement drawing of module, showing front
and rear view, overall dimensions, installation plans,
termination arrangements, packing dimensions and
weights.
In the data sheets included
in the documentation that
we sent you can find all
this information
Information
not available
4. Independent test characteristics- pertaining to the
irradiance levels and pertaining to the temperature
variations
(No response) Required
5. Deviation in inverter selection. In data sheet table-21, 500
kW inverter has been mentioned, whereas in bid document
it is 1000kW
It is a mistake. The inverter
offered is the 1000kW
(included in the bid
document)
Ok
6. General Arrangement drawing showing front and rear view,
overall dimensions, installation plans, termination
arrangements, packing dimensions and weights.
In the data sheets included
in the documentation that
we sent you can find all
this information
Information
not available
7. Technical literature giving complete specifications and
information.
In the data sheets included
in the documentation that
we sent you can find all
this information
Information
not available
8. Installation guide for Inverter (No response) Required
9. Independent test characteristics- pertaining to inverter
efficiency
(No response) Required
10. Technical write-up giving complete design, specifications
and information of mounting structures, material used,
fabrication process, treatments performed, standards
followed, types of bolts used, etc.
Will be provided at the
later stage at the time of
detailed engineering
Accepted
11. General arrangement drawing of mounting structures,
foundation plans, anchoring plans, overall dimensions,
installation plans, structural plans and elevation and
framing details.
12. Standard test certificates for various structure members
from independent testing laboratories.
13. Hot dipped galvanisation thickness certificate from the
factory.
Provided with the supply of
the structure
Information
not there in
Bid
14. Installation method statements. As indicated, the structure
will be rammed into the
ground
No deviation
allowed
15. BOQ for solar power plant not provided (Not submitted) Required
16. Solar resources reference details not enclosed as per clause
6.1, Volume -2 of RFP
PVSyst (data basis -
Meteonorm) and NASA
Details
missing
[Alex Solar Private Limited]
[20]
Sr. No. Documents Required Clarification provided by
the bidder (reply to query)
Final Remarks
data basis
17. Recommended PV syst version has not considered as per
required version clause 6.2, Volume -2 of RFP
There are not important
differences on it. This
calculation can be detailed
in the moment of the
signature of the contract
between both parts
No deviation
allowed
18. Bidder should consider armoured cable only for all
underground cable of required standard and exposed cable
should be UV protected
To be discussed with
project owners
No deviation
allowed
19. Scope of work mentioned in RFP should be adhere without
considering any deviation, exclusion or assumption
All the exclusions and
assumptions indicate in the
offer define our proposal.
No deviation
allowed
20. Inverter efficiency is less than required as per RFP To be discussed with
project owners
No deviation
allowed
21. Drawings not available (Not submitted) Required
Further Indure Montealto submitted the very few of the required details (as mentioned in the table
above) on 20th
August, 2011. An assessment of the submitted documents has been provided in the
subsequent paragraphs:
� Detailed design, installation and operations plan for the Project: The proposal submitted by
bidder covers the following topics- the technical selection, system description, system
configuration for various components (crystalline module & module mounting structures,
inverters, SCADA system, IT system comprising hardware and software), fire alarm & fire
suppression system and control room & inverter cooling system. However the technical
evaluation committee found a lot of calculation mistakes, data inconsistency.
� The correct mounting structure and plant layout was also missing in the data submitted
along with the proposal.
� The rated power tolerance was also provided as +/- 5% whereas required tolerance has
to be +/- 3%.
� Deviation in inverter selection. In data sheet table-21, 500 kW inverter has been
mentioned, whereas in bid document it is 1000kW.
� The bidder is not able to guarantee the commissioning of project on or before 30th
November, 2011.
� BOQ for solar power plant has not been provided by the bidder which is must for
technical evaluation.
[Alex Solar Private Limited]
[21]
� Technical write-up giving complete design, specifications and information of mounting
structures, material used, fabrication process, treatments performed, standards
followed, types of bolts used, etc. have not been submitted.
� General arrangement drawing of mounting structures, foundation plans, anchoring
plans, overall dimensions, installation plans, structural plans and elevation and framing
details have not been submitted.
� IEC Certificates of First Solar Module have not been submitted which is a must for
technical evaluation.
� Independent test characteristics have not been submitted which are required for
technical evaluation.
� Detailed Project critical path schedule: The project schedule has been presented as the
Gantt chart in the proposal. As per the proposed schedule, the entire project is to be
completed latest by November 28, 2011 but the flow of activities doesn’t make the schedule
realistic.
� Identification of the major equipment supplier(s): The suppliers for each of major
equipment, along with the technical specification and the bill of material for spares, are not
mentioned in the proposal.
� Scope of work mentioned in the proposal has been considered with certain deviations,
exclusions and assumptions which doesn’t comply to the RFP requirements
2.2.3.4 Conclusion
Based on the above analysis it is concluded that though the proposal submitted by Indure –
Montealto Consortium is responsive but the proposal doesn’t meet the prescribed technical
specifications (as per the RFP) due to missing data and calculation errors. Also it seems that the
bidder has proposed for certain deviations, exclusions and assumptions which doesn’t comply with
RFP requirement. Thus, the bidder, Indure – Montealto Consortium is technically disqualified.
2.3 Summary of evaluation
The Techno-Commercial proposals submitted by the aforesaid 3 bidders have been examined. Based
on examination it is concluded that only Moser Baer Engineering and Constructions Ltd (MBECL) and
Abir Infrastructure Private Limited (AIPL) are capable in meeting the specified quantity and quality
requirements while complying with the applicable laws as well as the requirements of the project as
mentioned in the RFP document.
[Alex Solar Private Limited]
[22]
The strategies proposed by MBECL and AIPL have been studied and it is found that both MBECL and
AIPL are aware of the technical challenges inherent in the projects. The adequacy of proposed
experience and capability to execute the project is assessed as satisfactory.
The table below summarizes the status of evaluation of techno commercial proposal submitted by
the bidders for the reasons explained in the previous section:
Table 11: Summary of Evaluation
Project Name MBECL AIPL Indure - Montealto
Alex Solar Private Limited Qualified Qualified Dis - qualified
Source: CRIS Analysis
Thus, MBECL and AIPL are found to be technically qualified for executing the 5 MW Solar Power
Project. As such its price bid may now be opened.
[Alex Solar Private Limited]
[23]
3. Financial Bid Opening
As part of second stage of the biding process the disqualified bidders were intimated via email dated
24th
August, 2011. Further qualified bidders were also intimated about financial bid opening details.
The financial bid of successful bidder was opened on 25th
August, 2011 at 4.30 pm at CRISIL’s office
i.e. in front of officials of successful bidder.
In response to the RFP the following financial quotes were received:
Table 12: Financial Quote for the Project
Sr. No. Project Name Bidder Financial Quote (INR)
1. Alex Solar Private Ltd MBECL 67,76,17,750
2. Alex Solar Private Ltd AIPL 71,14,98,638
3.1 Concluding Remarks
Based upon the outcomes of technical and financial bids and the way entire process has been
managed, it is concluded that the bid process was conducted in a transparent manner. Since the
price quoted by Moser Baer Engineering & Constructions Ltd was the lowest and is therefore
considered the L1 bidder.
In view of the above, the project owner may initiate action as found appropriate.
[Alex Solar Private Limited]
[24]
4. Annexure: NIT Published in Economic Times
M/s Alex Solar Private Limited
[Alex Solar Private Limited]
[25]
5. Annexure: Addendum 1
[Alex Solar Private Limited]
[26]
6. Annexure: Addendum 2
[Alex Solar Private Limited]
[27]
7. Annexure: Financial Bid Opening
M/s Alex Solar Private Limited
[Alex Solar Private Limited]
[28]
8. Annexure: MBECL- meeting PQ criteria
(Next 2 pages)
[Alex Solar Private Limited]
[29]
[Alex Solar Private Limited]
[30]
[Alex Solar Private Limited]
[31]
9. Annexure: - AIPL- meeting PQ criteria
(Next 3 pages)
[Alex Solar Private Limited]
[32]
[Alex Solar Private Limited]
[33]
[Alex Solar Private Limited]
[34]
[Alex Solar Private Limited]
[35]
10. Annexure: Indure Montealto- meeting PQ criteria
(Next 12 pages)
[Alex Solar Private Limited]
[36]
[Alex Solar Private Limited]
[37]
[Alex Solar Private Limited]
[38]
[Alex Solar Private Limited]
[39]
[Alex Solar Private Limited]
[40]
[Alex Solar Private Limited]
[41]
[Alex Solar Private Limited]
[42]
[Alex Solar Private Limited]
[43]
[Alex Solar Private Limited]
[44]
[Alex Solar Private Limited]
[45]
[Alex Solar Private Limited]
[46]
[Alex Solar Private Limited]
[47]
[Alex Solar Private Limited]
[48]
11. Annexure: MBECL- key data sheets in the bid
(Next 17 pages)
[Alex Solar Private Limited]
[49]
[Alex Solar Private Limited]
[50]
[Alex Solar Private Limited]
[51]
[Alex Solar Private Limited]
[52]
[Alex Solar Private Limited]
[53]
[Alex Solar Private Limited]
[54]
[Alex Solar Private Limited]
[55]
[Alex Solar Private Limited]
[56]
[Alex Solar Private Limited]
[57]
[Alex Solar Private Limited]
[58]
[Alex Solar Private Limited]
[59]
[Alex Solar Private Limited]
[60]
[Alex Solar Private Limited]
[61]
[Alex Solar Private Limited]
[62]
[Alex Solar Private Limited]
[63]
[Alex Solar Private Limited]
[64]
[Alex Solar Private Limited]
[65]
[Alex Solar Private Limited]
[66]
12. Annexure: AIPL- key data sheets in the bid
(Next 12 pages)
[Alex Solar Private Limited]
[67]
[Alex Solar Private Limited]
[68]
[Alex Solar Private Limited]
[69]
[Alex Solar Private Limited]
[70]
[Alex Solar Private Limited]
[71]
[Alex Solar Private Limited]
[72]
[Alex Solar Private Limited]
[73]
[Alex Solar Private Limited]
[74]
[Alex Solar Private Limited]
[75]
[Alex Solar Private Limited]
[76]
[Alex Solar Private Limited]
[77]
[Alex Solar Private Limited]
[78]
[Alex Solar Private Limited]
[79]
13. Annexure: Indure Montealto- key data sheets in
the bid
(Next 16 pages)
[Alex Solar Private Limited]
[80]
[Alex Solar Private Limited]
[81]
[Alex Solar Private Limited]
[82]
[Alex Solar Private Limited]
[83]
[Alex Solar Private Limited]
[84]
[Alex Solar Private Limited]
[85]
[Alex Solar Private Limited]
[86]
[Alex Solar Private Limited]
[87]
[Alex Solar Private Limited]
[88]
[Alex Solar Private Limited]
[89]
[Alex Solar Private Limited]
[90]
[Alex Solar Private Limited]
[91]
[Alex Solar Private Limited]
[92]
[Alex Solar Private Limited]
[93]
[Alex Solar Private Limited]
[94]
[Alex Solar Private Limited]
[95]
[Alex Solar Private Limited]
Disclaimer
CRISIL Risk and Infrastructure Solutions Limited (CRIS), a subsidiary of CRISIL Limited, has taken due care and caution in preparation of this
Report. This Report is based on the information obtained by CRIS from sources, which it considers reliable. CRIS does not guarantee the
accuracy, adequacy or completeness of any information contained in this Report and is not responsible for any errors or omissions, or for
the results obtained from the use of such information. This Report should be used in its entirety only and shall not be reproduced in any
form without prior permission from CRIS.
CRIS has taken utmost care in independently administering the ICB process in fair and transparent manner, and ensured, on best effort
basis, to facilitate evaluation of the bids received as per the clauses mentioned in the RFP document provided by the project owner and
reviewed by CRIS.
CRIS and any director, representative or employees of CRIS do not accept any liability for any direct, consequential or perceived loss
arising from the use of this Report or its contents. CRIS specifically states that it has no financial liability whatsoever to the user/s of this
Report.
[Alex Solar Private Limited]
Registered Office – Mumbai
CRISIL House, Central Avenue,
Hiranandani Business Park,
Powai, Mumbai- 400 076
Phone : 91-22-3342 3000
Fax : 91-22-3342 3810
New Delhi
The Mira, G-1, 1st Floor, Plot No. 1 & 2
Ishwar Nagar, Mathura Road,
New Delhi - 110 065, India
Phone : 91-11-4250 5100
91-11-2693 0117 - 121
Fax : 91-11-2684 2213
Hyderabad
3rd Floor, Uma Chambers
Plot No. 9&10, Nagarjuna Hills,
Near Punjagutta Cross Road
Hyderabad - 500 082
Phone : 91-40-40328200
Fax : 91-40-2335 7507
Bengaluru
W-101, Sunrise Chambers,
22, Ulsoor Road,
Bengaluru - 560 042
Phone : 91-80-2558 0899
Fax : 91-80-2559 4801
Ahmedabad
706, Venus Atlantis,
Near Reliance Petrol Pump
Prahladnagar,
Ahmedabad -
Phone : 91-79-4024 4500
Fax : 91-79-2755 9863
Visit us at:
www.crisil.com
About CRISIL Infrastructure Advisory
CRISIL Infrastructure Advisory is a division of CRISIL
Risk and Infrastructure Solutions Limited, a 100%
subsidiary of CRISIL Limited – India’s leading
Ratings, Research, Risk and Policy Advisory
Company.
CRISIL Infrastructure Advisory is India’s premier
advisor focusing on policy issues, as well as
commercial and contractual issues in the areas of
transport, energy and urban infrastructure. We also
provide support to international firms planning
investments in India. Over a period of time, CRISIL
Infrastructure Advisory has built a unique position
for itself in these domains and is considered the
preferred consultant by governments, multilateral
agencies and private-sector clients. We have
extended our operations beyond India and are
present in other emerging markets in Africa, Middle
East and South Asia.