final report project a
TRANSCRIPT
A Study on The Predictability of an Air Conditioner
ME 406 – Experimental Design
Section 1
Austin Bonnes
November 18, 2016
Kenmore Model 580.72056 Air Conditioner
1
Executive Summary:
This study looked to experimentally determine if it was viable to be able to use this air
conditioner, a Kenmore model 580.72056, for testing purposes with engineering students. The
goal was to determine if the performance could be predicted at measurable and not measurable
conditions. After gathering data and calculating the Coefficient of Performance (COP) and
Energy Efficient Ratio (EER) of the air conditioner, could be determined. If the results
predictable, concise, and accurate then this air conditioner can be used to test and train
engineering students
To determine the performance of the air conditioner for this study, the air conditioner was
mounted into a wall. The exhaust of the unit went into what is referred to as the controlled room
– that was filled with heaters. This room was to act as the outside heat sink for the air
conditioner, where the temperature could be controlled via the heaters. Thermocouples were used
to measure the temperature of the room, and were attached on every major component of the air
conditioner, as well as the unit’s air inlet and outlet. Additional data taken was the inlet and
outlet air flow velocities, areas, and temperatures, the barometric pressure in the room, and the
kilowatt hours consumed by the air conditioner. In order to determine the predictability of this air
conditioner, the air conditioner needed to be tested at different external heat sink temperatures.
Using the controlled room allowed the air conditioner to be tested at 3 varying temperature
ranges. Those rangers were between about 22°C and 50°C. The rangers were to look at the
effects of the outside temperature on the air conditioner when the outside (the controlled room)
was at around room temperature, in a transition temperature range above room temperature, and
in a hot temperature range that was above 40°C.
Using thermocouples attached to the components of the air conditioner, the temperatures of each
stage of the air conditioner were gathered. Next, using thermodynamics and the temperature of
the R-22 coolant in the air conditioner, the enthalpies were calculated across the condenser and
the evaporator. The differences in these enthalpies led to the cooling power (output) of the air
conditioner, and factoring the amount of energy the air conditioner consumed overall allowed us
to calculate the COP and EER.
2
After comparing data from multiple trials, we concluded that - with the provided Kenmore air
conditioner - a general trend of the performance can be predicted, but predicting accurate and
precise data is unreliable. Thus, the use of the air conditioner for engineering students comes
down to if the students need to predict and calculate accurate and precise data for the
performance of the air conditioner. Ignoring the few outliers seen in the charts generated and
shown below, predictable results can be determined, though discretion is advised.
3
Table of Contents:
Executive Summary: 1
Introduction 4
Background Literature 5
Theory 6
Experiment 8
Uncertainties 9
Results 10
Conclusion 12
Works Cited 13
Appendix A - Experimental Layout 14
Appendix B - Additional Data 16
Appendix C - Sample Calculations 18
Appendix D - Uncertainty Calculations 20
4
Introduction Air conditioners, the most common consumer heat exchanger, are in approximately two-thirds of all
homes in the United States.1 All of these air conditioners cost American homeowners nearly $11 billion
each year, and account for approximately 5.2% of the nation's total power consumption in the process.
These units also release 100 million tons of carbon dioxide into the atmosphere each year.2 New research
must be done to maximize their efficiency to lower the power consumption and the emissions, especially
as the world shifts to a greener economy.
Prior research studies that have been done on air conditioners, and heat exchangers in general,
have focused on decreasing the volume and weight of the air conditioner itself. However, most
of this research does not factor in the external heat sink temperature, which can greatly determine
the transfer of heat between the hot and cold working fluids of the air conditioner. For future
reference, external temperature, external heat sink temperature, and outdoor temperature all refer
to the temperature of the controlled room being heated by the six small heaters. The larger lab
space was cooled by the air conditioner and averaged a steady 72°F.
The purpose behind this study was to determine how the external temperature of a building
affects the working capacity of the air conditioner. Understanding how air conditioners perform
under normal varying temperatures aid in current research, as well as contribute to increasing
future performance for both consumer and industrial purposes.
Dr. Sarma Pisupati, a professor working for the Department of Energy and Mineral Engineering,
says “Energy Efficient Ratio (EER) measures how efficiently a room air conditioner will operate
at a specific outdoor temperature,” and this will be the metric to compare and determine the use
of this air conditioner.3 Higher EER correlates to a more efficient system, with the accuracy of
the EER providing the ability to predict the performance of an air conditioner at varying
1 "Air Conditioning." Department of Energy. Accessed September 10, 2016. http://energy.go v/energysaver/air-conditioning.2 "U.S. Energy Information Administration - EIA - Independent Statistics and Analysis." How Much of U.S. Carbon Dioxide Emissions Are Associated with Electricity Generation? Accessed September 10, 2016. http://www.eia.gov/tools/faqs/faq.cfm?id=77.3 Dr. Pisupati, S. Air Conditioner Efficiency. EGEE 102: Energy Conservation and Environmental Protection. (n.d.). Retrieved from https://www.e-education.psu.edu/egee102/node/2106. September 12, 2016.
5
temperatures. The information gathered was used to determine the heat load, the power required
to operate the air conditioner, and the coefficient of performance of the tested air conditioner as
the simulated environment increased in temperature. The experimental EER will be compared
with the EER provide by the manufacturer, which is calculated by exclusively looking at an
external temperature of 95°F. Depending on the outcome of the study, it will also be determined
if future mechanical engineering students should carry out similar experiments.
Background Literature For air conditioners, it is the industry standard to determine the EER in order to meet the
Department of Energy’s efficiency requirements.4 The EER value manufacturers put on their air
conditioners are based on one outside temperature, which is generally 95°F. Therefore, there is a
benefit to experimentally determine the EER at varying external temperatures to confirm what is
provided by the manufacturer. In doing so, the ability to predict the performance of the air
conditioner at different external temperature becomes possible. Experiments and reviews
covering air conditioners look at determining performance and efficiencies. The air conditioners
these research papers review varied in their applications, from use in manufacturing to steam
engines, with none found to cover the external heat sink temperature.
This experiment looked at an air conditioner for residential use and its performance at varying
external temperatures. Standards were used throughout this experiment to ensure accuracy,
precision, and repeatability. Temperature measurements were a critical part of this experiment,
and the standards for thermocouples explained the need to verify the relative accuracy of the
thermocouples. To test this accuracy, we validated the temperature of the thermocouples by
using another standalone temperature measuring source.
In the ASME Standards for Air Cooled Heat Exchangers, the standard said to measure air cooled
heat exchangers is by collecting temperature data every thirty seconds to account for
fluctuations.5 The standard also stated that air conditioners need be turned on and running for a
4 Arlan Burdick IBACOS, Inc. Strategy Guideline: Accurate Heating and Cooling Load Calculations. The United States Department of Energy. Building Technology Program. June 2011.5 ASME. PTC 30 - 1991 Air Cooled Heat Exchangers. (1991).
6
period of three to five minute prior to collecting data, allowing the unit to reach a steady state
and avoid any temperature or power fluctuation. The last thing the standard required for properly
running an experiment on an air conditioner was to measure the air conditioner for at least one
hour to get steady data.
Much of the research performed on air conditioners look at determining the efficiencies dealing
with the type of heat exchanger and the type of fins the heat exchanger uses. Recent research
papers, like “A Novel “Partial Bypass” Concept to Augment the Performance of Air-Cooled
Heat Exchangers,” headed by Chi-Chung Wang, are good examples of how much of the recent
research has been around specific and important improvements.6 These different studies used
heat transfer theory and thermodynamics to analyze the changing of fins and other components
to the heat exchanger. Other research looks at new additions to the heat exchangers like new
compressors and new thermal conductive material and liquids. The purpose of our research was
to not look at improvements like many of the recent works on heat exchangers, but to understand
the performance of an air conditioner as the external temperature increased.
Theory
Air conditioners use two working fluids, in various flow and pass combinations, to transfer heat
from one fluid to the other. This experiment looked at the efficiency of the air conditioner by
measuring the inlet and outlet temperatures of the condenser and evaporator. In doing so, we
were able to determine the enthalpies at each stage of the heat transfer cycle and the
corresponding COP and EER.
6 Wang, C., Chen K., Liaw J. A Novel “Partial Bypass” Concept to Augment the Performance of Air-Cooled Heat Exchangers. Retrieved from International Journal of Heat and Mass Transfer website: http://www.elsevier.com/locat/ijhmt.(2012).
7
Figure 1: Air conditioner cycle and T-s diagram7
We found the enthalpies at each stage of the heat transfer cycle by following the diagram
depicted in figure 1 above. The enthalpies were calculated by using the temperatures gathered
from thermocouples on the condenser and evaporator, and from the assumption that the R-22
refrigerant was a liquid during the entire process. Using the enthalpies, the work in (W in) and
heat in (Qin) could be determined with the COP of the air conditioner calculated by dividing Q in
by Win. The EER of this air conditioner could be determined by multiplying the COP by 3.41.
As the temperature in the controlled room changed, thermodynamics suggest that the coefficient
of performance would also change. As the controlled room increased in temperature, the air
conditioner would become less efficient in generating cool air to dump into the lab space. Since
the controlled room temperature, and therefore the enthalpy, was higher, the difference between
the enthalpy of the controlled room and the enthalpy supplied was smaller. This relationship, as
noted by Penoncello, should be linear and noticeable.8
7 Penoncello, S. G. (2015). Thermal energy systems: Design and analysis (1st ed.). Moscow, ID: CRC Press.8 Penoncello, S. G. (2015).
8
Experiment
This experiment looked at determining the coefficient of performance for a horizontal room air
conditioner. We took the provided air conditioner, Kenmore 580.72056, and mounted it into the
wall of a small confined room. The air conditioner was positioned so that the exhaust would be
directed into the room with heating six small heaters. In the room were 20 thermocouples which
measured the temperature of the air in the room as well as the air conditioner’s condenser and
evaporator. Appendix A shows the setup of the room simulating the external environment, with
the location of each thermocouple and heater described in more detail.
Altering the total time, the experiment ran with different initial temperatures, temperature
measurements were taken every thirty seconds via an Agilent 34972A LXI Data Acquisition
/Switch Unit. The air conditioner was also allowed to warm up for five minutes before data
collection, removing any initial power fluctuations from the system and reaching a steady
operating state. Once the initial warm up was complete, the experiment was conducted in three
different ways, due to limited time available to run the experiment, with a total of 4 experimental
trials successfully carried out.
One way of collecting the data was with just the air conditioner running and the heaters turned
off inside the room simulating the external temperature. This was to see the performance of the
air conditioner when external temperature was similar to the set air conditioner temperature. For
the second method of data collection, the room simulating the external temperature was heated to
approximately 39°C before data collection began, with the heaters continuously running and the
air conditioner turned on. The third and final method consisted of allowing the air conditioner to
run for at least thirty minutes before turning on the heaters. For all of these methods, a fan was
used to circulate the air inside of the controlled room, with data collected for at least one hour.
As the air conditioner was running, the data logger collected the temperature readings from the
thermocouples arranged in the room. The kilowatt hours (kWh) used by the air conditioner were
measured by a P3 Kill A Watt, with measurements manually recorded every two minutes. This
data collection was done to see if any drastic changes in temperature would correlate to the rate
of power consumption.
9
To meet standards and to determine the reliability, a HT-L13 dual temperature meter was used to
measure various thermocouple temperatures, determining the accuracy of each thermocouple and
its uncertainty.
Uncertainties
As the equipment used to collect data in this experiment was not perfect, each had uncertainties that
needed to be calculated. With these, more accurate results could be attained. The calculations for these
uncertainties are provided in Appendix D.
Device Error Bias (B) Random (P)
Thermocouples ± 0.5155ºC
P3 Kill A Watt Resolution 0.004417 kWh
Tektronix Resolution .002°C ± .912908 ºC
TotalsTemperature Uncertainty 1.05°C
Power Uncertainty 0.004417 kWh
Table 1: measurement uncertainties
10
Results
After analyzing several days of data collection, we saw similar trends to those seen below in
figure 2. This trend was for each component of the air conditioner to gradually increase in
temperature until the heaters in the controlled room were turned on, at which point the
temperature increased more rapidly. Some of the data from these days were omitted due to
inconsistencies in this trend, such as the component temperatures oscillating back and forth.
Additional data can be found in appendix B.
Figure 3 below shows the temperatures of the R-22 refrigerant, which performed the cooling
work of the air conditioner. These temperatures described the internal cycle of the air
conditioner, and, in addition to the total work done in the system, were used to calculate the COP
and the EER. Appendix C gives a step by step process for each of these at given temperatures.
Figure 2: data compiled to determine enthalpies and work of cycle from September 15
Figures 3 and 4 show the relationship between EER and the room temperature. A trend can be
seen in figure 4, with an extreme outlier at 39°C. Likewise, figure 5 shows an upward trend with
11
outliers at 26.6°C and 27.35°C. These figures indicate that the EER can - to an extent - be
predicted with respect to the external temperature, though additional information should be
gathered to make definite conclusions. Even with these fluctuations, the predicted EER can be
used to model the performance of the air conditioner.
Figure 3: Relationship of EER with respect to room temperature
Figure 4: Relationship of EER with respect to room temperature over smaller temperature range
12
Conclusion
After analyzing our data, we found that you can predict the EER of an air conditioner based on
the external heat sink temperature. With the outliers seen in figures 3 and 4, however, caution
should be used when using this external temperature to predict the performance of the air
conditioner. As the EER increased from 11 to 14 BTU/W*h between 27.5 and 30°C, the
expected trend was for the EER to fluctuate around 14 BTU/W*h for hotter temperatures.
Instead, it plummeted to the lowest calculated value of 8.4 BTU/W*h at 39°C, before again
returning to 14 BTU/W*h. As the external temperature continued to increase past 45°C, the EER
began to follow a predictable downward trend.
Though we were able to determine the performance of the air conditioner, we do not recommend
this experiment to be carried out by future mechanical engineering students. There was a general
trend, but due to uncertainties and fluctuations in the data, the results are hard to accurately
predict. The method and process used in this study can be applied to experiments for students,
but they may require an air conditioner that is newer for the experiment to avoid fluctuations and
flawed data.
13
Works Cited
[1] "Air Conditioning." Department of Energy. Accessed September 10, 2016. http://energy.go v/energysaver/air-conditioning.
[2] Arlan Burdick IBACOS, Inc. Strategy Guideline: Accurate Heating and Cooling Load Calculations. The United States Department of Energy. Building Technology Program. June 2011.
[3] ASME. PTC 30 - 1991 Air Cooled Heat Exchangers. (1991).
[4] Dr. Pisupati, S. Air Conditioner Efficiency. EGEE 102: Energy Conservation and Environmental Protection. (n.d.). Retrieved from https://www.e-education.psu.edu/egee102/node/2106. September 12, 2016.
[5] Khaled, M., Harambat, F., Peerhossaini, H. Analytical and empirical determination of thermal performance of louvered heat exchanger - Effects of air flow statistics (54). Retrieved from International Journal of Heat and Mass Transfer website: http://www.elsevier.com/loca t/ijhmt. (2010).
[6] Kim, A. Performance of an Air-to-Air Heat Exchanger and an Exhaust Air Heat Recovery Heat Pump. National Research Council Canada. Retrieved from http://web.mit.edu/par mstr/Public/NRCan/brn235.pdf 1). November 1, 1985.
[7] Penoncello, S. G. (2015). Thermal energy systems: Design and analysis (1st ed.). Moscow, ID: CRC Press.
[8] Sears, Roebuck and Co. Owner's Manual: Room Air Conditioner Model 58072056.
[9] Stinnes W.H., von Backstrom T.W. Effect of Cross-flow on the performance of air-cooled heat exchanger fans. Department of Mechanical Engineering, University of Stellenbosch, Private Bag X1, 7602 Matieland, South Africa. Pergamon. Applied Thermal Engineering 22. (2002).
[10] "U.S. Energy Information Administration - EIA - Independent Statistics and Analysis." How Much of U.S. Carbon Dioxide Emissions Are Associated with Electricity Generation? Accessed September 10, 2016. http://www.eia.gov/tools/faqs/faq.cfm?id=77.
[11] Wang, C., Chen K., Liaw J. A Novel “Partial Bypass” Concept to Augment the Performance of Air-Cooled Heat Exchangers. Retrieved from International Journal of Heat and Mass Transfer website: http://www.elsevier.com/locat/ijhmt.(2012).
14
Appendix A - Experimental Layout
Figure 5: layout of the experiment
In this layout, the triangles represent thermocouples, the small boxes represent heaters, and the
largest box represents the air conditioner. While not to scale, this layout describes the
approximate location of each piece of equipment to the rest. Each numbered thermocouple is
defined in the table below.
15
Thermocouple Thermocouple Location Data Logger Units
1 Evaporator R-22 Refrigerant Inlet Temperature T-Type
2 Evaporator R-22 Refrigerant Midpoint Temperature T-Type
3 Evaporator R-22 Refrigerant Outlet Temperature T-Type
4 Condenser R-22 Refrigerant Inlet Temperature T-Type
5 Condenser R-22 Refrigerant Midpoint Temperature T-Type
6 Condenser R-22 Refrigerant Outlet Temperature T-Type
7 Evaporator Air Inlet Temperature #1 T-Type
8 Evaporator Air Inlet Temperature #2 T-Type
9 Evaporator Air Outlet Temperature #1 T-Type
10 Evaporator Air Outlet Temperature #2 T-Type
11 Evaporator Air Outlet Temperature #3 T-Type
12 Evaporator Air Outlet Temperature #4 T-Type
13 Condenser Air Inlet Temperature #1 T-Type
14 Condenser Air Inlet Temperature #2 T-Type
15 Condenser Air Outlet Temperature #1 T-Type
16 Condenser Air Outlet Temperature #2 T-Type
17 Condenser Air Outlet Temperature #3 T-Type
18 Condenser Air Outlet Temperature #4 T-Type
19 Control Room Air Temperature - North T-Type
20 Control Room Air Temperature - South T-Type
Table 2: numbered thermocouples
16
Appendix B - Additional Data
The following data was not included in the results section as it did not show any new
information. This data was used in analysis, but for the sake of reducing redundancy it was put in
this appendix.
Figure 6: data compiled to determine enthalpies and work of cycle from September 8
Figure 7: data compiled to determine enthalpies and work of cycle from September 20
17
Figure 8: T-s diagram of the R22 refrigerant
18
Appendix C - Sample Calculations
Using temperatures of
we found the enthalpies of the air conditioner’s cycle by using Engineering Equation Solver,
which gave us values of
19
Figure 9: air conditioner cycle showing enthalpy subscript locations
With these enthalpies, the work required for the compressor can be found from the difference
between points 1 and 2 on the diagram.
Similarly, heat load going into the cycle can be found
After determining the work and heat load of the system, the COP can be calculated
20
Finally, once the COP is calculated, the EER is calculated by multiplying the COP by a constant
21
Appendix D - Uncertainty Calculations
The expected error for a thermocouple is found by taking the difference of a reference
temperature and a thermocouple temperature, then dividing that quantity by two,
Averaging ten of these instances, the average temperature can be found
Comparing this average temperature to a reference temperature, the error for the thermocouple
can be calculated
The standard deviation for the Tektronix data logger is found by averaging the temperatures,
then squaring the difference between this average from each individual value. This summation is
dividing by the total number of samples before finally taking the square root of the entire
quantity.
22
The total uncertainties for each unit of error is found by squaring both the bias and precision
errors, adding them together, and finally taking the square root.
Temperature was the only unit of error that had both bias and precision errors, and its calculation
is as follows.