Page 1: FINESSE - JS Air Curtains3 • If the curtain has been transported at tempe- ratures below 0° C, it will be necessary to let it sit for at least 2 hours under normal operating conditions

INSTALLATION

EN

FINESSE

Page 2: FINESSE - JS Air Curtains3 • If the curtain has been transported at tempe- ratures below 0° C, it will be necessary to let it sit for at least 2 hours under normal operating conditions

2

1. BEFORE YOU BEGIN

Meaning of symbols in the manual:

Before installation, thoroughly read the section “Safe use of air curtains”. It contains all instructions on the safe and correct use of the product.

This manual contains important instructions to ensure correct installation of the air curtain. Beforeinstallation, read all of the following instructions thoroughly and then adhere to them! The ma-nufacturer reserves the right to make changes, including to technical documentation without prior notice. Save this user manual for further use. The instructions in this manual are a part of the product.

Statement of complianceYou will find the details at the www.2vv.cz website

MANZÝVLOBMYS

VÝSTRAHA! Upozornění/varování

NEPŘEHLÉDNĚTE! Důležité instrukce

BUDETE POTŘEBOVAT POZNÁMKA

Praktické tipy a informace

TECHNICKÉ INFORMACE Podrobnější technické informace

ODKAZY Odkazy k dalším částem/sekcím manuálu

Warning/caution

Important instructions

Practical tips and information

More detailed technical information

Refer to other parts/sectionsof the manual

ATTENTION!

DO NOT OVERLOOK!

YOU WILL NEED NOTE

TECHNICAL INFORMATION

LINK

SYMBOL MEANING

Page 3: FINESSE - JS Air Curtains3 • If the curtain has been transported at tempe- ratures below 0° C, it will be necessary to let it sit for at least 2 hours under normal operating conditions

3

• If the curtain has been transported at tempe-ratures below 0° C, it will be necessary to let it sit for at least 2 hours under normal operating conditions after unpacking, without turning it on. This will allow the air curtain‘s interior te perature to stabilise.

• Caution! Before removing the curtain from the board, remove the cover.

1.

2.

2. UNPACKING

2.1 CHECK THE SHIPMENT

• After delivery, immediately check to see if the packaged product is damaged. If the pac-kaging is damaged contact the delivery servi-ce. If the complaint is not fi led in time, your claim may not be valid later.

• Check to see if it is the same product you orde-rot. If there are any discrepancies, do not un-pack the curtain, and immediately report the defect to the supplier.

• After unpacking, check to see if the curtain and other parts are in order. If you have any doubts, contact the supplier.

• Never install a damaged air curtain!• If you do not unpack the curtain immediately

after delivery, it must be storot in a dry indoor environment with an ambient temperature between +5 °C and +40 °C

2.2 UNPACK THE AIR CURTAIN

+5 oC

+40 oC

All used packaging materials are environ-mentally friendly and may be

reused or recycled. Take an active part in environmental protec-

tion and see that packagingmaterials are correctly disposed of

or repurposed.

Page 4: FINESSE - JS Air Curtains3 • If the curtain has been transported at tempe- ratures below 0° C, it will be necessary to let it sit for at least 2 hours under normal operating conditions

4

3. MAIN PARTS

1

2

3

3

4

5

5

6

Suspension holders

Electric heater/water/without

Power supply cable plug

Power supply connectors and fusse location

Control modul socket

Outlet grid

1

2

6

4

Page 5: FINESSE - JS Air Curtains3 • If the curtain has been transported at tempe- ratures below 0° C, it will be necessary to let it sit for at least 2 hours under normal operating conditions

5

4. DIMENSIONS594,6

299,3304,1

25

596,5

638,5

250

A

B

C

Type Spacing of installation

holes A [mm]

Length B

[mm]

Length of cover C

(mm)

VCF-x-100-x-... 1085 1124,1 1166,1

VCF-x-150-x-... 1585 1624,1 1666,1

VCF-x-200-x-... 2085 2124,1 2166,1

VCF-x-250-x-... 2465 2504,1 2546,1

Page 6: FINESSE - JS Air Curtains3 • If the curtain has been transported at tempe- ratures below 0° C, it will be necessary to let it sit for at least 2 hours under normal operating conditions

6

5. TECHNICAL PARAMETERS

The distance at which the average velocity of the air current flow drops to 3m/s. For optimal conditions and maximumperformance of the equipment.* Acoustic pressure at a distance of 3 m from the curtain.** With water temperature gradient of 90º/70° C and temperature of suctioned air at +18°C*** With water temperature gradient of 40º/30° C and temperature of suctioned air at +18°C

Type Max.

height

doors

[m]

Air

output

[m3/h]

Noise*

[dB(A)]

Heater

output

[kW]

Heater

power

supply

[V/A]

Fan power

supply

[V/A]

Weight

[kg]

VCF-B-100-E-...AC

4

2250 57,9 9,1 400/15,5 230/2,2 39,5

VCF-B-150-E-...AC 3230 60,2 14,7 400/25,2 230/3,3 54,5

VCF-B-200-E-...AC 4360 61,2 19,1 400/31,3 230/4,4 71

VCF-B-250-E-...AC 5300 62,8 24,5 400/41,1 230/5,4 85

VCF-B-100-V-...AC 2140 57,5 24,77** - 230/2,2 41

VCF-B-150-V-...AC 3100 59,6 38,77** - 230/3,3 56

VCF-B-200-V-...AC 4280 61 52,61** - 230/4,3 73

VCF-B-250-V-...AC 5140 62,5 62,29** - 230/5,4 87

VCF-B-100-S-... AC 2270 58,3 - - 230/2,2 37,5

VCF-B-150-S-... AC 3280 60,2 - - 230/3,4 51

VCF-B-200-S-... AC 4400 61,5 - - 230/4,2 66

VCF-B-250-S-... AC 5460 62,7 - - 230/5,4 80

VCF-C-100-E-... AC

5

2960 61,2 9,6 400/17,9 230/4,0 44

VCF-C-150-E-... AC 4080 62,7 14,7 400/27,2 230/5,2 60

VCF-C-200-E-... AC 5180 64 19 400/34,3 230/6,8 75,5

VCF-C-250-E-... AC 6020 65,8 23,6 400/42,8 230/7,9 90

VCF-C-100-V-... AC 2800 61,2 29,13** - 230/3,8 45,5

VCF-C-150-V-... AC 3900 62,5 44,57** - 230/5,2 61

VCF-C-200-V-... AC 5070 63,7 56,99** - 230/6,5 77

VCF-C-250-V-... AC 5860 65,6 67,3** - 230/7,6 91,5

VCF-C-100-W-... AC 2530 61,6 13,47*** - 230/3,6 51,5

VCF-C-150-W-... AC 3500 62,6 19,03*** - 230/4,8 70,5

VCF-C-200-W-... AC 4670 63,7 25,71*** - 230/6,0 89

VCF-C-250-W-... AC 5260 65,2 29,81*** - 230/7,1 106

VCF-C-100-S-... AC 3020 61,9 - - 230/3,9 42

VCF-C-150-S-... AC 4160 63 - - 230/5,2 56,5

VCF-C-200-S-... AC 5270 64,2 - - 230/6,7 71

VCF-C-250-S-... AC 6100 65,7 - - 230/7,9 84

Page 7: FINESSE - JS Air Curtains3 • If the curtain has been transported at tempe- ratures below 0° C, it will be necessary to let it sit for at least 2 hours under normal operating conditions

7

5. TECHNICAL PARAMETERS

All curtains with electric heater

Type Air flow

[m3/h]

Heater output

[kW]

Output temperature Δt

[°C]

VCF-B-100-E-... 2250 9,1 12,1

VCF-B-150-E-... 3230 14,7 13,5

VCF-B-200-E-... 4360 19,1 13,1

VCF-B-250-E-... 5300 24,5 13,8

VCF-C-100-E-... 2960 9,6 9,7

VCF-C-150-E-... 4080 14,7 10,7

VCF-C-200-E-... 5180 19 10,9

VCF-C-250-E-... 6020 23,6 11,7

VCFI4B-B100-E-...EC 1810 9,4 15.4

VCFI4B-B150-E-...EC 2710 15 16.5

VCFI4B-B200-E-...EC 3620 19 15.6

VCFI4B-B250-E-...EC 4520 24,5 16

Type Max.

height

doors

[m]

Air

output

[m3/h]

Noise*

[dB(A)]

Heater

output

[kW]

Heater

power

supply

[V/A]

Fan power

supply

[V/A]

Weight

[kg]

VCFI4B-100-E-...EC

4

1810 58,8 9,4 400/15,8 230/2,2 35,5

VCFI4B-150-E-...EC 2710 60,8 15 400/24,9 230/3,2 48,5

VCFI4B-200-E-...EC 3620 62,2 19 400/31,7 230/4,3 63

VCFI4B-250-E-...EC 4520 63,4 24,5 400/40,7 230/5,3 75

VCFI4B-100-V-...EC 1700 57,5 19,1*** - 230/2,2 37

VCFI4B-150-V-...EC 2550 59,3 29,7*** - 230/3,2 50

VCFI4B-200-V-...EC 3400 60,5 39,5*** - 230/4,3 65

VCFI4B-250-V-...EC 4250 61,8 48,4*** - 230/5,3 77

VCFI4B-100-S-... EC 1850 58,8 - - 230/2,2 33,5

VCFI4B-150-S-... EC 2760 60,8 - - 230/3,2 45

VCFI4B-200-S-... EC 3690 62,2 - - 230/4,3 58

VCFI4B-250-S-... EC 4610 63,4 - - 230/5,3 70

The distance at which the average velocity of the air current flow drops to 3m/s. For optimal conditions and maximumperformance of the equipment.* Acoustic pressure at a distance of 3 m from the curtain.** With water temperature gradient of 90º/70° C and temperature of suctioned air at +18°C*** With water temperature gradient of 40º/30° C and temperature of suctioned air at +18°C

Page 8: FINESSE - JS Air Curtains3 • If the curtain has been transported at tempe- ratures below 0° C, it will be necessary to let it sit for at least 2 hours under normal operating conditions

8

5. TECHNICAL PARAMETERS

Air curtains with a water coil for a water temperature gradient of 90º/70° C and at an intake air tempe-rature of +18° C

Type Air flow

[m3/h]

Heat output

[kW]

Outlet

temperature [°C]

Water flow

[l/s]

Pressure loss

[kPa]

VCF-B-100-V-...AC 2140 24,77 52,7 0,29 12

VCF-B-150-V-...AC 3100 38,77 55,5 0,46 29,1

VCF-B-200-V-...AC 4280 52,61 54,9 0,62 24,1

VCF-B-250-V-...AC 5140 62,29 54,4 0,74 17,8

VCFI4B-B100-V-...EC 1700 19,14 55,5 0,23 7,75

VCFI4B-B150-V-...EC 2550 29,7 57,1 0,36 21,39

VCFI4B-B200-V-...EC 3400 39,49 57 0,48 18,93

VCFI4B-B250-V-...EC 4250 48,4 56,2 0,59 20,01

VCF-C-100-V-...AC 2800 29,13 49,2 0,35 14,5

VCF-C-150-V-...AC 3900 44,57 52,3 0,53 35,1

VCF-C-200-V-...AC 5070 56,99 51,7 0,68 27

VCF-C-250-V-...AC 5860 62,29 54,4 0,74 17,8

Air curtains with a water coil for a water temperature gradient of 80º/60° C and at an intake air tempe-rature of +18° C

Type Air flow

[m3/h]

Heat output

[kW]

Outlet

temperature [°C]

Water flow

[l/s]

Pressure loss

[kPa]

VCF-B-100-V-...AC 2140 20,28 46,4 0,24 8,8

VCF-B-150-V-...AC 3100 31,78 48,8 0,38 20,8

VCF-B-200-V-...AC 4280 43,15 48,3 0,51 17,7

VCF-B-250-V-...AC 5140 51,07 47,8 0,61 13,4

VCFI4B-B100-V-...EC 1700 15,92 48,5 0,19 5,59

VCFI4B-B150-V-...EC 2550 24,92 50,1 0,30 15,89

VCFI4B-B200-V-...EC 3400 33,08 49,9 0,40 13,93

VCFI4B-B250-V-...EC 4250 40,53 49,2 0,49 14,52

VCF-C-100-V-...AC 2800 23,88 43,6 0,28 10,9

VCF-C-150-V-...AC 3900 36,57 46,1 0,43 25,3

VCF-C-200-V-...AC 5070 46,72 45,6 0,55 19,8

VCF-C-250-V-...AC 5860 51,07 47,8 0,61 13,4

Page 9: FINESSE - JS Air Curtains3 • If the curtain has been transported at tempe- ratures below 0° C, it will be necessary to let it sit for at least 2 hours under normal operating conditions

9

5. TECHNICAL PARAMETERS

Air curtains with a water coil for a water temperature gradient of 70º/50° C and at an intake air temperature of +18° C

Type Air flow

[m3/h]

Heat output

[kW]

Outlet

temperature [°C]

Water flow

[l/s]

Pressure loss

[kPa]

VCF-B-100-V-...AC 2140 15,98 40,4 0,19 6,2VCF-B-150-V-...AC 3100 25,07 42,3 0,3 14,2VCF-B-200-V-...AC 4280 34,05 41,9 0,4 12,4VCF-B-250-V-...AC 5140 40,28 41,5 0,48 9,7

VCFI4B-B100-V-...EC 1700 12,57 41,6 0.15 3,73VCFI4B-B150-V-...EC 2550 19,95 43,2 0.24 10,79VCFI4B-B200-V-...EC 3400 26,42 43 0.32 9,32VCFI4B-B250-V-...EC 4250 32,26 42,3 0.39 9,61VCF-C-100-V-...AC 2800 18,82 38,2 0,22 7,9VCF-C-150-V-...AC 3900 28,87 40,2 0,34 17,2VCF-C-200-V-...AC 5070 36,88 39,8 0,44 13,8

VCF-C-250-V-...AC 5860 40,28 41,5 0,48 9,7

Air curtains with a water coil for a water temperature gradient of 60º/40° C and at an intake air temperature of +18° C

Type Air flow

[m3/h]

Heat output

[kW]

Outlet

temperature [°C]

Water flow

[l/s]

Pressure loss

[kPa]

VCF-B-100-V-...AC 2140 11,83 34,6 0,14 4,1VCF-B-150-V-...AC 3100 18,59 36 0,22 8,8VCF-B-200-V-...AC 4280 25,25 35,7 0,3 8,1VCF-B-250-V-...AC 5140 29,85 35,4 0,35 6,6

VCFI4B-B100-V-...EC 1700 9,07 34,7 0.11 2,06

VCFI4B-B150-V-...EC 2550 14,76 36,2 0.18 6,38

VCFI4B-B200-V-...EC 3400 19,46 36 0.24 5,4

VCFI4B-B250-V-...EC 4250 23,6 35,4 0.29 5,49

VCF-C-100-V-...AC 2800 13,93 32,9 0,17 5,4VCF-C-150-V-...AC 3900 21,41 34,5 0,25 10,8VCF-C-200-V-...AC 5070 27,28 34,1 0,32 8,9VCF-C-250-V-...AC 5860 29,85 35,4 0,35 6,6

Page 10: FINESSE - JS Air Curtains3 • If the curtain has been transported at tempe- ratures below 0° C, it will be necessary to let it sit for at least 2 hours under normal operating conditions

10

5. TECHNICAL PARAMETERS

Air curtains with a water coil for a water temperature gradient of 40/30° C and at an intake air temperature of +18° C

Type Air flow

[m3/h]

Heat output

[kW]

Outlet

temperature [°C]

Water flow

[l/s]

Pressure loss

[kPa]

VCF-C-100-W-... 2530 13,47 34 0,2 13,2

VCF-C-150-W-... 3500 19,03 34,3 0,4 14,1

VCF-C-200-W-... 4670 25,71 34,5 0,5 13,3

VCF-C-250-W-... 5260 29,81 35 0,6 16,3

Air curtains with a water coil for a water temperature gradient of 35/25° C and at an intake air temperature of +18° C

Type Air flow

[m3/h]

Heat output

[kW]

Outlet

temperature [°C]

Water flow

[l/s]

Pressure loss

[kPa]

VCF-C-100-W-... 2530 9,4 29,2 0,2 8,6

VCF-C-150-W-... 3500 13,3 29,4 0,3 8,2

VCF-C-200-W-... 4670 18 29,6 0,3 8,4

VCF-C-250-W-... 5260 21 30 0,4 9,4

The warm-water temperature coil, made of copper-aluminium alloy, is designed for a maximum operational water temperature of +100° C and a maximum operating pre-ssure of 1.6 MPa.

Page 11: FINESSE - JS Air Curtains3 • If the curtain has been transported at tempe- ratures below 0° C, it will be necessary to let it sit for at least 2 hours under normal operating conditions

11

OK

OK

OK

OK

mm 001mm 100

mm 005mm 005

100

mm

100

mm

100 mm

100 mm

MATERIAL

MATERIAL

MATERIAL

MATERIAL

6.1 CHOOSE THE INSTALLATION SITE AND INSTALL THE AIR CURTAIN

6.1-1 Built up dimensions

• The air curtain must be installed only in a horizontal position!• The curtain can be installed over the door opening. All separation distances for flammable materials

and safe use of air curtain has to be kept.• The installed position of the air curtain can be chosen to accommodate the service hood.• It must be operated in dry, coverot indoor spaces with an ambient temperature between +5° C and

+40° C and relative humidity up to 80%• The air curtain is not intended for moving air that contains combustible or explosive mixtures, chemi-

cal fumes, coarse dust, soot, grease, poisons, infectious germs, etc.

6.1.-2 Clearance distance

594,6 mm min. 300 mm30

4,1

mm

594,6 mm min. 300 mm30

4,1

mm

6. INSTALLATION

Page 12: FINESSE - JS Air Curtains3 • If the curtain has been transported at tempe- ratures below 0° C, it will be necessary to let it sit for at least 2 hours under normal operating conditions

12

6.1-3 Measure the installation site

• Only nonflammable materials (those that do not burn, smoulder or carbonise) or fire-resistant ma-terials (those that do not burn, but mainly smoulder, e.g., plaster board) can be kept within 100 mm in any direction of the air curtain. However, these materials should not block the intake or outlet openings.

• For air curtains with an electric heater, safe distances from building structural surfaces and flammable objects are as follows:

• The safe distance for flammable materials in the direction of the main air flow (i.e., behind the outlet) is 500 mm,

• The safe distance for flammable materials above the air curtain is 500 mm,• The safe distance for flammable materials in other directions is 100 mm.

Recommended size of ceiling aperture for inserting the curtain:

TypeA

[mm]

B

[mm]

VCF-X-100-X… 1140 620

VCF-X-150-X… 1640 620

VCF-X-200-X… 2140 620

VCF-X-250-X… 2520 620

• Air curtain is fixed to the ceiling by 4 threaded rods, which are not included delivery.• It is necessary to ensure proper in the supply at the site according to the exact type of use of the air

curtain and based on its electric parameters.• When using water heated air curtain, please ensure connection of the flow and return pipes. • It is necessary to cut or otherwise make a hole according to the hereunder mentioned dimensions• Drill four holes into the ceiling construction according to the dimensions scheme (see “Dimensions”)

for hanging of the air curtain to 4 anchoring points.• Screw the air curtain directly to the ceiling without any space between its casing and ceiling, or use

four threaded bars to reach the required distance from the ceiling, according to the situation on the site (see “Conditions for safety and proper function of the air curtain”).

For wall installation use „Wall mounted bracket set“: VCS4-KONZ-STE. „Wall mounted bracket SET“ has to be ordered separately as an optional accessorie.

6. INSTALLATION

A B

OK

OK

3x 9

1015022

0280

114

57

470

40

38

L2

M8M8

M8M8L1

Page 13: FINESSE - JS Air Curtains3 • If the curtain has been transported at tempe- ratures below 0° C, it will be necessary to let it sit for at least 2 hours under normal operating conditions

13

L2

M8 8M8M8M

L1

For ceiling installation use „Ceiling holder SET”: VCS4-KONZ-STR. „Ceiling holder SET” has to beordered separately as an optional accessorie.

Type L1

[mm]

L2

[mm]

VCF-X-100-X… 250 1085

VCF-X-150-X… 250 1585

VCF-X-200-X… 250 2085

VCF-X-250-X… 250 2465

6.1-4 Suspend the air curtain on the threaded bars and ensure that the suspension will not come loose

• In consideration of the air curtain weight into account, it is necessary to use either a suitable lifting device (forklift, etc.) or use two additional individuals to support it, as long as it is not securely faste-ned.

• Suspension has to carry the weight of the air curtain!

6. INSTALLATION

31

9

15,5

95,5

175,5

255,5

302

114

4x

49

9

15,5

40

3x 9

1015022

0280

114

57

470

40

38

L2

M8M8

M8M8L1

Page 14: FINESSE - JS Air Curtains3 • If the curtain has been transported at tempe- ratures below 0° C, it will be necessary to let it sit for at least 2 hours under normal operating conditions

14

TV1/1

6.2 CONNECT THE WATER INTAKE AND OUTLET HOSES

VCF-x-xxx-V(W)-...

• A flexible hoses with a G3/4“ connection

• Connection and pressure testing of the heater must be carried out by a person with professional plumbing knowledge, who must observe current standards and regulations of the given country.

• The maximum water temperature is +100° C. The maximum pressure is 1.6 MPa. We recommend installing a stop valve on the intake and outlet of the heater to allow the water supply to be shut off .

6.2-1 Regulating the water coil with a thermostatic valve TV1/1 (Air curtains with water coil and BASIC control module: VCS-R2-BA-V-xx)

Thermostatic valve TV1/1 is an required accessorie for control module VCS-R2-BA-V-xx

Detailed description of water coil regulation by thermostatic valve (TV1/1), including it´s connection, refer the instruction manual for thermostatic valve TV1/1.

3/4"

3/4"

VCF-x-xxx-V(W)-...+

VCS-R2-BA-V-xx

6. INSTALLATION

Page 15: FINESSE - JS Air Curtains3 • If the curtain has been transported at tempe- ratures below 0° C, it will be necessary to let it sit for at least 2 hours under normal operating conditions

15

6.2-2 Regulating the water coil with a ZV-3 or RT zone valve (Air curtains with water coil and COMFORT control module: VCS-R2-CO-V-xx)

Zone valve ZV-3 is an required accessorie for control module VCS-R2-CO-V-xx

• Detailed description of water coil regulation by zone valve (ZV-3), including it´s connection, refer the instruction manual for zone valve ZV-3.

Zone valve RT is an required accessorie for control module VCS-R2-CO-V-xx

• Detailed description of water coil regulation by zone valve (RT), including it´s connection, refer the instruction manual for zone valve RT.

AB

AB

ZV-3

AB

AB

ZV-3

VCF-x-xxx-V(W)-...+

VCS-R2-CO-V-xx

6. INSTALLATION

www.first.siLet Firšt be your f irst choice.

www.first.siFIRŠT d.o.o. Koroška cesta 56 SI-3320 Velenje SLOVENIA

phone: +386 3 898 35 00 fax: +386 3 898 35 35 email: [email protected] web: www.first.si

A C T U A T O R S V A L V E S H E A T I N G C O N T R O L L E R S

Let Firšt be your f irst choice.

S9000-DIVDIVERTING/CHANGEOVER UNIT 3-way rotary brass valves with electric actuator S9000-DIV and Clip system

AA A

B

B B

FDV 231C FDV 232C FDV 233Cinternal threads external threads compression fittings

S9000-DIV 231C, internal threads

Code Type DN Kvs Voltage Rotation time Control Connection A B C Weight [kg] Price (€)

14230 S9iN0-DIV 231C DN15 Rp ½" 15 3 230 V~ 50 Hz 12s/90° 2P Rp ½" 36 72 115 0,89 14231 S9iN0-DIV 231C DN20 Rp ¾" 20 7 230 V~ 50 Hz 12s/90° 2P Rp ¾" 36 72 115 0,96 14232 S9iN0-DIV 231C DN25 Rp 1" 25 11 230 V~ 50 Hz 12s/90° 2P Rp 1" 41 82 115 0,99 14233 S9iN0-DIV 231C DN32 Rp 1 ¼" 32 15 230 V~ 50 Hz 12s/90° 2P Rp 1 ¼" 47 94 118 1,31

S9000-DIV 232C, external threads

Code Type DN Kvs Voltage Rotation time Control Connection A B C Weight [kg] Price (€)

14238 S9iN0-DIV 232C DN15 G ¾" 15 3 230 V~ 50 Hz 12s/90° 2P G ¾" 36 72 115 0,87 14239 S9iN0-DIV 232C DN20 G 1" 20 7 230 V~ 50 Hz 12s/90° 2P G 1" 36 72 115 0,91 14240 S9iN0-DIV 232C DN25 G 1 ¼" 25 11 230 V~ 50 Hz 12s/90° 2P G 1 ¼" 41 82 115 1,06 *14241 S9iN0-DIV 232C DN32 G 1 ½" 32 15 230 V~ 50 Hz 12s/90° 2P G 1 ½" 47 94 118 1,27

S9000-DIV 233C, compression fittings

Code Type DN Kvs Voltage Rotation time Control Connection A B C Weight [kg] Price (€)

14244 S9iN0-DIV 233C DN20 C22mm 20 7 230 V~ 50 Hz 12s/90° 2P CPF 22mm 36 72 115 0,95 14245 S9iN0-DIV 233C DN25 C28mm 25 11 230 V~ 50 Hz 12s/90° 2P CPF 28mm 41 82 115 1,08

* Units are available on special request.

S900

0-DI

V / F

IRŠT

d.o.o

. / Co

pyrig

ht 20

15

Installation examples Features and options ■ Auxiliary switch: one potential free auxiliary switch in the end position

of the actuator is available as an option. ■ Molex connector: optional Molex connector (IP40) and optional

specially sealed Molex cable (IP44). ■ Supply voltage: 230 VAC, 50 Hz, 24 VAC, 50 Hz. ■ Manual control handle: with or without manual control handle. ■ Solar/cooling adapter: Heat barrier for protection of the actuator in

solar or cooling systems.

Diverting application Changeover application In accordance with PED, LVD, RoHS2, EMC.

109

C

RT

Page 16: FINESSE - JS Air Curtains3 • If the curtain has been transported at tempe- ratures below 0° C, it will be necessary to let it sit for at least 2 hours under normal operating conditions

16

6. INSTALLATION

6.2-3 Regulating the water coil with an zone valve ZV-3-24V (Air curtains with water coil and SUPERIOR control module: VCS-R2-SU-V-xx)

Zone valve ZV-3-24V is an required accessorie for control module VCS-R2-SU-V-xx

Supply 24 V/ 50/60 Hz (24V external source, not included), control tension 0-10V

VCF-x-xxx-V(W)-...+

VCS-R2-SU-V-xx

• Detailed description of water coil regulation by zone valve (ZV-3-24V), including it´s connection, refer the instruction manual for zone valve ZV-3-24V.

AB

AB

ZV-3ZV-3-24V

Page 17: FINESSE - JS Air Curtains3 • If the curtain has been transported at tempe- ratures below 0° C, it will be necessary to let it sit for at least 2 hours under normal operating conditions

17

6.4 ELECTRO INSTALLATION

• The air curtain’s electrical connection must be based on a professional design by a qualifi ed electrical systems engineer.

• Installation must be carried out by a professionally trained electrical worker. All applicable national regulations and directives must be observed.

• The electrical schematics on the product take priority over those presented in this manual!• Prior to installation, check to see if the terminal markings correspond to the markings on the elect-

rical connections diagram. When in doubt, contact your supplier and do not connect the air curtain under any circumstances.

• Never reach inside the air curtain unless the main electrical supply has been turned off !• If the product is connected to any control system other than the original one, the regulation and me-

asurement components must be connected by the company that supplied the system.• The electrical contractor defines the minimum size of the feed cable according to the standards appli-

cable at the place of installation, the location for installing the cable, the surrounding conditions, and the curtain‘s technical parameters.

• Special attention should be paid to the capacity of the distribution network of the air curtain with electric heater in terms of the supply of the appropriate phase current values for limiting the voltage fluctuations and flickering in the network.

Minimal cable dimensions: Type Cable dimention

VCF-x-xxx-S… 3Cx1,5

VCF-x-xxx-V… 3Cx1,5

VCF-x-xxx-W… 3Cx1,5

VCF-x-100-E… 5Cx2,5

VCF-x-150-E… 5Cx4

VCF-x-200-E… 5Cx6

VCF-x-250-E… 5Cx10

Fuse specification:

VCF-x-xxx…x

B C

xxx

100 3,15A 5A

150 4A 6,3A

200 6,3A 8A

250 8A 12A

6. INSTALLATION

Page 18: FINESSE - JS Air Curtains3 • If the curtain has been transported at tempe- ratures below 0° C, it will be necessary to let it sit for at least 2 hours under normal operating conditions

18

• The air curtain must be pRotected by an appropriate circuit breaker, in accordance with its electrical parameters. For safety reasons, over-designed protection is not recommended.

• The air curtain must be connected using the TN-S system, which means that the neutral conductor must always be connected.

• A main cut-off switch must be placed in the electrical supply network, disconnecting all poles of the network.

• The electrical enclosure of the air curtain is IP 20.

FINESSE air curtains are equipped with a fuse (with T characteristic – slow-blow). This safety fuse pRo-tects the electronic panel and fans. It is located under the service cover next to the main power supply connectors.

6. 5 CONTROL MODULES

Air curtains FINESSE are produced with universal connection interface.Air curtains FINESSE can be controlled by one of following control modules: BASIC, COMFORT, SUPERIOR.Control modules are required accessories and has to be orderot separatelly.Air curtain is connected with control module by „Quick connection sockets“

• The electrical parameters are shown on the manufacturer‘s label, which is located under the air curtain‘s service cover.

6. INSTALLATION

Page 19: FINESSE - JS Air Curtains3 • If the curtain has been transported at tempe- ratures below 0° C, it will be necessary to let it sit for at least 2 hours under normal operating conditions

19

6.6 INSERT CONTROL MODULE TO THE AIR CURTAIN

6. INSTALLATION

2

1

Page 20: FINESSE - JS Air Curtains3 • If the curtain has been transported at tempe- ratures below 0° C, it will be necessary to let it sit for at least 2 hours under normal operating conditions

20

6. INSTALLATION

Connection to the regulation control panel and accessories

3

4

a) b)

c) d) e)Connect the remote control and accesso-ries to the terminals on the electronic board

Page 21: FINESSE - JS Air Curtains3 • If the curtain has been transported at tempe- ratures below 0° C, it will be necessary to let it sit for at least 2 hours under normal operating conditions

21

6. INSTALLATION

6.7 EXIT SIGN

- Exit sign marking of emergency exit

For all types of VCS4x- air curtains!

Not included in delivery.

6.8 COVERING THE AIR CURTAIN

EXIT

EXIT

Page 22: FINESSE - JS Air Curtains3 • If the curtain has been transported at tempe- ratures below 0° C, it will be necessary to let it sit for at least 2 hours under normal operating conditions

22

CAUTION!

Before starting up the unit check that:• No tools or other objects that may damage the unit have been left inside.• The power and heating water supply are well connected.• The unit is properly covered.• The control panel is properly connected

During the commissioning, check the proper function of the unit (fans, heating). Check the other possi-ble settings and functions according to the user manual of each regulator

7.1 SET AIR FLOW DIRECTION

This is set by tilting the air curtain’s fan louvers in the desirot direction..

7. INITIAL START-UP

Page 23: FINESSE - JS Air Curtains3 • If the curtain has been transported at tempe- ratures below 0° C, it will be necessary to let it sit for at least 2 hours under normal operating conditions

23

8. CLEANING AND MAINTENANCE

8.1 CLEANING

ATTENTION!

The main electrical supply must be switched off before any interference to the inside of the air curtain. The air cur-tain must be allowed to cool down!

Cleaning is forbidden to use compressed air, aggressive chemicals, solvents or water.Clean with a damp cloth, a soft cloth, or a vacuum cleaner.Clean the surface of the air curtain, including the suction part.Perform cleaning as needed, recommended at least every 3 months.Observe safety and use protective equipment.

9. SERVIS

9.1 WHEN YOU AREN‘T ABLE TO REMOVE DEFECT BY YOURSELF

If you are unable to resolve the problem, contact the supplier.For the fast removal of defects please provide the following information:

- product reference number - serial number - running time- used accessories- installation location- installation condition (including electrical)- detailed description of the problem and the steps that you have taken for its removal

Warranty and post-warranty service is performed by the manufacturer, supplier or authorized service organization. When ordering service intervention it is necessary to describe the defect, product type designation indicated on its label, and the location of installation.

9.2 PUTTING THE PRODUCT OUT OF OPERATION - DISPOSAL

Before disposing of the product, make the product unusable. Even old products contain raw materials that can be reused. Take them to a collection point of secondary raw materials.The product is good to dispose at the place, which is specialized for it, and thus it will be possible to recycle materials. Store unusable parts of the product at a controlled dump.

When disposing of materials, it is necessary to observe the relevant national regulations on waste disposal.

Page 24: FINESSE - JS Air Curtains3 • If the curtain has been transported at tempe- ratures below 0° C, it will be necessary to let it sit for at least 2 hours under normal operating conditions

24

10. ELECTRICAL SCHEMES

Types without heating - VCF-B-xxx-S-...VC

F-B-

100

VCF-

B-15

0

VCF-

B-20

0

VCF-

B-25

0

Fuse

Fuse

Page 25: FINESSE - JS Air Curtains3 • If the curtain has been transported at tempe- ratures below 0° C, it will be necessary to let it sit for at least 2 hours under normal operating conditions

25

Types with water coil VCF-B-xxx-V(W)-...

10. ELECTRICAL SCHEMES

Fuse

VCF-

B-10

0

VCF-

B-15

0

VCF-

B-20

0

Fuse

VCF-

B-25

0

ZV-3/RT

ZV-3/RT

Page 26: FINESSE - JS Air Curtains3 • If the curtain has been transported at tempe- ratures below 0° C, it will be necessary to let it sit for at least 2 hours under normal operating conditions

26

Types with electric heater VCF-B-xxx-E-...

VCF-B-100-E-...

VCF-B-150-E-...

10. ELECTRICAL SCHEMES

FuseFuse

Fuse

Page 27: FINESSE - JS Air Curtains3 • If the curtain has been transported at tempe- ratures below 0° C, it will be necessary to let it sit for at least 2 hours under normal operating conditions

27

VCF-B-200-E-...

VCF-B-250-E-...

10. ELECTRICAL SCHEMES

Fuse

Fuse

Page 28: FINESSE - JS Air Curtains3 • If the curtain has been transported at tempe- ratures below 0° C, it will be necessary to let it sit for at least 2 hours under normal operating conditions

28

VCF-C-100-S-...

VCF-C-...-S-...

10. ELECTRICAL SCHEMES

Types without heating - VCF-C-...-S-...

Fuse

Fuse

VCF-

C-15

0VC

F-C-

200

VCF-

C-25

0

Page 29: FINESSE - JS Air Curtains3 • If the curtain has been transported at tempe- ratures below 0° C, it will be necessary to let it sit for at least 2 hours under normal operating conditions

29

10. ELECTRICAL SCHEMES

Types with water coil VCF-C-xxx-V(W)-...

VCF-C-100-V(W)-...

VCF-C-...-V(W)-...

VCF-

C-10

0-...

Fuse

Fuse

VCF-

C-15

0-...

VCF-

C-20

0-...

VCF-

C-25

0-...

Page 30: FINESSE - JS Air Curtains3 • If the curtain has been transported at tempe- ratures below 0° C, it will be necessary to let it sit for at least 2 hours under normal operating conditions

30

10. ELECTRICAL SCHEMES

VCF-C-100-E-...

VCF-C-150-E-...

Types with electric heater VCF-C-xxx-E-...

Fuse

Fuse

Page 31: FINESSE - JS Air Curtains3 • If the curtain has been transported at tempe- ratures below 0° C, it will be necessary to let it sit for at least 2 hours under normal operating conditions

31

VCF-C-200-E-...

VCF-C-250-E-...

10. ELECTRICAL SCHEMES

Fuse

Fuse

Page 32: FINESSE - JS Air Curtains3 • If the curtain has been transported at tempe- ratures below 0° C, it will be necessary to let it sit for at least 2 hours under normal operating conditions

32

10. ELECTRICAL SCHEMES

VCFI4B-Bxxx--...EC

N N

PE PE

L L

1678 2345

1~M1~M

1~M

NL

NL

NL

RP

M

RP

M

RP

M

34

5

GN

D

PW

MG

ND

PW

MG

ND

PW

M

11~M

1~M

LN

NL

RP

M

PW

M

GN

DR

PM

2

GN

D

PW

M

PEPE

PEPE

PE

Název: VCSF4-B-250-S-EC

Verze: 1

Firma: 2VVKreslil: Krátkž

NPE

�ýslo : 3-010-S08575Datum: 2.8.2017

42439

52540

62641

72742

2338

8 28

9 29

10 30

11 31

1716151413321222237

31

43

44

33

123

VCSF4-B-250-S-EC-ELEKTRO

býlá

modrá

�lutá

rudá

10

V

rudá

�lutá

modrá

býlá

10

V

býlá

modrá

�lutá

rudá

10

V

býlá

modrá

�lutá

rudá

10

V

býlá

modrá

�lutá

rudá

10

V

VCFI4B-B100-S-...EC

VCFI

4B-B

100.

..EC

VCFI

4B-B

150

VCFI

4B-B

200

VCFI

4B-B

250

Nýzev: VCSF4-B-250-V-EC

Verze: 1

Firma: 2VVKreslil: KrýtkŤ

54

21

3

PEN N

L LPE

PL

Á�

0-1

0V

678 2345 1

Temperature sensor inlet

11~M

1~M1~M

1~M1~M

LN

NL

NL

NL

NL

RP

M

PW

M

GN

DR

PM

RP

M

RP

M

RP

M

23

45

GN

D

PW

MG

ND

PW

MG

ND

PW

MG

ND

PW

M

678 2345 1

PEPE

PEPE

PE

MU

T-V3M

zdroj

24

+ -

NL

+

GN

D

NPE

�Čslo : 3-010-S08574Datum: 2.8.2017

8 29

9 30

10 31

11 32

42541

52642

62743

72844

2440

2 12 33 13 14 15 16 17

23

39

46

45 18 34

3

1

35

VCSF4-B-250-V-EC-ELEKTRO

BČlýModrý

bČlý

modrý

�lutý

rudý

10V

rudý

�lutý

modrý

bČlý

10V

bČlý

modrý

�lutý

rudý

10V

bČlý

modrý

�lutý

rudý

10V

bČlý

modrý

�lutý

rudý

10V

VCFI4B-B100-V-...EC

VCFI

4B-B

100.

..EC

VCFI

4B-B

150

VCFI

4B-B

200

VCFI

4B-B

250

FUSE

FUSE

Page 33: FINESSE - JS Air Curtains3 • If the curtain has been transported at tempe- ratures below 0° C, it will be necessary to let it sit for at least 2 hours under normal operating conditions

33

10. ELECTRICAL SCHEMES

1234568 7

Nízev: VCSF4-B-100-E-EC

Verze: 1

Firma: 2VVKreslil: Krítkž

NN

PE

PE

L2L1

L2L1

L3L3C

YKY 5Cx10,0 400V/50H

z

2 1468 7 5 3 678 2345 1 1678 2345 123

Temperature sensor inlet

11~M

1~M

LN

PEN

L

RP

M

PW

M

GN

DR

PM

2

GN

D

PW

M

PEN

PE

8 79

R1

R1

R2

R2

2x 1580W / 230V

2x 1580W / 230V

R3

R3

2x 1580W / 230V

Th1

TH 10 80°C

Th1

TH 10 80°C

Th1

TH 10 80°C

THER

MO

STAT

�ýslo : 3-010-S08585Datum: 2.8.2017

1

3

2

19

26

33 34 35 36 37 38 7 8 39 40 41 42 43 44 4 15

910

165

61724

1825

28

27

20 21 22 23

3-010-S03298 VCSF4-10-S-EL-VYM

3-010-S03298 VCSF4-10-S-EL-VYM

VCSF4-B-100-E-EC-ELEKTRO

Rudí MODRÁ Býlí

býlí

modrí

�lutí

rudí

10V

býlí

modrí

�lutí

rudí

10V

VCFI4B-B100-E-...EC

VCFI4B-B150-E-...EC

1234568 7

2x 1250W / 230V

Th1

TH 10 80°C

R1

R1

9 8 7

2x 1250W / 230V

2x 1250W / 230V

2x 1250W / 230V

2x 1250W / 230V

2x 1250W / 230V

Th1

Th1

TH 10 80°C

TH 10 80°C

TH 10 80°C

Th1

R6

R6

R5

R5

R4

R4

R3

R3

Th1

TH 10 80°C

Th1

TH 10 80°C

R2

R2

THER

MO

STAT

Nízev: VCSF4-B-150-E-EC

Verze: 1

Firma: 2VVKreslil: Krítkž

NN

PE

PE

L2L1

L2L1

L3L3C

YKY 5Cx10,0 400V/50H

z

2 1468 7 5 3 678 2345 1 1678 2345 123

Temperature sensor inlet

11~M

1~M1~M

LN

PEN

LN

L

RP

M

PW

M

GN

DR

PM

RP

M

23

GN

D

PW

MG

ND

PW

M

PEPE

NPE

�ýslo :3-010-S08582Datum: 2.8.2017

52132

6 22

1930

42031

237

13

2

18

29

33

34

39 40 41 42 43 44 12 13 45 46 47 48 49 850 24 9 10 11

25 26 27

3-010-S03302 VCSF4-15-S-EL-VYM

3-010-S03302 VCSF4-15-S-EL-VYM

VCSF4-B-150-E-EC-ELEKTRO

Rudí MODRÁ Býlí

býlí

modrí

�lutí

rudí

10

V

býlí

modrí

�lutí

rudí

10

V

býlí

modrí

�lutí

rudí

10

V

FUSE

FUSE

Page 34: FINESSE - JS Air Curtains3 • If the curtain has been transported at tempe- ratures below 0° C, it will be necessary to let it sit for at least 2 hours under normal operating conditions

34

VCFI4B-B200-E-...EC

Nízev: VCSF4-B-200-E-EC

Verze: 1

Firma: 2VVKreslil: Krítkž

8 7 123456

NN

PE

PE

L2L1

L2L1

L3L3C

YKY 5Cx10,0 400V/50H

z

11~M

2 1468 7 5 3 678 2345 1 1678 2345 123

Temperature sensor inlet

1~M1~M

1~M

LN

PEN

LN

LN

LN

RP

M

PW

M

GN

DR

PM

RP

M

RP

M

23

4

GN

D

PW

MG

ND

PW

MG

ND

PW

M

PEPE

PEPE

2x 1580W / 230V

2x 1580W / 230V

2x 1580W / 230V

789R

4

R4

R5

R5

R6

R6

Th1

TH 10 80°C

TH 10 80°C

TH 10 80°C

Th1

Th1TH

ERM

OSTAT

2x 1580W / 230V

2x 1580W / 230V

R1

R1

TH 10 80°C

Th1

R2

R2

TH 10 80°C

TH 10 80°C

Th1

R3

2x 1580W / 230V

Th1R

3

�ýslo : 3-010-S08579Datum: 2.8.2017

2235

42336

52437

62538

267

278

289

14131210 29 11565554535251161550494847464539

40

34

1

3

2

21

30 31

3-010-S03306 VCSF4-20-S-EL-VYM

3-010-S03306 VCSF4-20-S-EL-VYM

VCSF4-B-200-E-EC-ELEKTRO

Rudí MODRÁ Býlí

rudí

�lutí

modrí

býlí

10V

býlí

modrí

�lutí

rudí

10V

býlí

modrí

�lutí

rudí10V

býlí

modrí

�lutí

rudí

10V

VCFI4B-B250-E-...EC

Nízev: VCSF4-B-250-E-EC

Verze: 1

Firma: 2VVKreslil: KrítkžDatum: 2.8.2017

9

2x 1580W / 230V

R7

R7

R6

2x 1250W / 230V

R6

R5

R5

2x 1580W / 230V

6 5 4

R4

R4

2x 1580W / 230V

3 2 1

R8

2x 1250W / 230V

R8

R9

R9

2x 1250W / 230V

9

Th1

Th1

TH 10 80°C

TH 10 80°C

TH 10 80°C

Th1

8 7

Th1

TH 10 80°C

TH 10 80°C

TH 10 80°C

Th1

Th1

78

2x 1250W / 230V

R2

R2

R3

R1

R1

2x 1250W / 230V

2x 1250W / 230V

R3

Th1

TH 10 80°C

TH 10 80°C

TH 10 80°C

Th1

Th1

8 7 123456

NN

PE

PE

L2L1

L2L1

L3L3C

YKY 5Cx10,0 400V/50H

z

THER

MO

STAT

11~M

2 1468 7 5 3 678 2345 1 1678 2345 123

Temperature sensor inlet

1~M1~M

1~M1~M

LN

PEN

LN

LN

LN

L

RP

M

PW

M

GN

DR

PM

RP

M

RP

M

RP

M

23

45

GN

D

PW

MG

ND

PW

MG

ND

PW

MG

ND

PW

M

PEPE

PEPE

NPE

�ýslo : 3-010-S08576

1 2

12 1617

3

34 13 14 15

42641

52742

62843

72944

2540

11 33

10 32

9 31

8 30

18 19

24

39

51 52 53 54 55 56 57 58 59 60 61 62

46

45

35

3-010-S03310 VCSF4-25-S-EL-VYM

3-010-S03310 VCSF4-25-S-EL-VYM

VCSF4-B-250-E-EC-ELEKTRO

Rudí MODRÁ Býlí

�lutí

modrí

býlí

rudí

10

V

býlí

modrí

�lutí

rudí

býlí

modrí

�lutí

rudí

býlí

modrí

�lutí

rudí

býlí

modrí

�lutí

rudí

10

V

10

V

10

V

10

V

10. ELECTRICAL SCHEMES

FUSE

FUSE

Page 35: FINESSE - JS Air Curtains3 • If the curtain has been transported at tempe- ratures below 0° C, it will be necessary to let it sit for at least 2 hours under normal operating conditions

35

After installing the air curtain, read carefully the Manual for the appropriate regulator. In case of any doubt or query, do not hesitate to contact our sales or technical support departments.