fire code provisions on sprinkler systems and standpipe systems
TRANSCRIPT
-
8/9/2019 Fire Code Provisions on Sprinkler Systems and Standpipe Systems
1/59
WELCOME
PARTICIPANTS
-
8/9/2019 Fire Code Provisions on Sprinkler Systems and Standpipe Systems
2/59
Code Provisionson Sprinkler Systems
and StandpipeSystems
-
8/9/2019 Fire Code Provisions on Sprinkler Systems and Standpipe Systems
3/59
Outline of Presentation
I – Sprinkler Systems
A. General Requirements
B. Provisions on SpecificTypes of Occupancies
“FIRE SAFETY
IS OUR MAIN
CONCERN”
-
8/9/2019 Fire Code Provisions on Sprinkler Systems and Standpipe Systems
4/59
Outline of Presentation
II- Standpipe and Hose
Systems
A. General RequirementsB. Specific Requirements
for Dry Standpipe Systemsand Wet Standpipes Systems
“FIRE SAFETY
IS OUR MAIN
CONCERN”
-
8/9/2019 Fire Code Provisions on Sprinkler Systems and Standpipe Systems
5/59
Outline of Presentation
III – Alternative Measures
DILG Memo Circular 2010 – 17“Guidelines in the Approval of
Alternative and/or RemedialFire Safety Measures”
“FIRE SAFETY
IS OUR MAIN
CONCERN”
-
8/9/2019 Fire Code Provisions on Sprinkler Systems and Standpipe Systems
6/59
Fundamental Principle on Fire Safety
“ Every building or structure shallbe designed , constructed,
equipped, maintained and
operated to avoid danger to thelives and ensure safety of its
occupants from fire, smoke, vapor
and fumes, during the period ofescape from the building or
structure.”“FIRE SAFETY
IS OUR MAIN
CONCERN”
“FIRE SAFETY
IS OUR MAIN
CONCERN”
-
8/9/2019 Fire Code Provisions on Sprinkler Systems and Standpipe Systems
7/59
Definition
Automatic Fire Suppression System. An
integrated system of underground or
overhead piping or both connected to a
source of extinguishing agent ormedium and designed in accordance with
fire protection engineering standards
which, when actuated by its automaticdetecting device, suppresses fires within
the area protected.“FIRE SAFETY
IS OUR MAIN
CONCERN”
-
8/9/2019 Fire Code Provisions on Sprinkler Systems and Standpipe Systems
8/59
Definition
Sprinkler System. An integrated network
of hydraulically designed piping system
installed in a building, structure or area
with outlets arranged in a systematicpattern which automatically discharges
water when activated by heat or
combustion products from a fire.
“FIRE SAFETY
IS OUR MAIN
CONCERN”
-
8/9/2019 Fire Code Provisions on Sprinkler Systems and Standpipe Systems
9/59
Sprinkler
Systems
“FIRE SAFETY
IS OUR MAIN
CONCERN”
-
8/9/2019 Fire Code Provisions on Sprinkler Systems and Standpipe Systems
10/59
Fire Code Provisions on Sprinkler Systems
• Design shall be in accordance with
NFPA 13.
• ITM shall be in accordance with NFPA25. Records shall be included in
FALAR 3.
General Requirements (Section 10.2.6.5)
“FIRE SAFETY
IS OUR MAIN
CONCERN”
-
8/9/2019 Fire Code Provisions on Sprinkler Systems and Standpipe Systems
11/59
Fire Code Provisions on Sprinkler Systems
Notification of the nearest fire
station if the sprinkler system is
out of service for more than 4
hours. Building management shall
designate a fire watch.
General Requirements (Section 10.2.6.5)
“FIRE SAFETY
IS OUR MAIN
CONCERN”
-
8/9/2019 Fire Code Provisions on Sprinkler Systems and Standpipe Systems
12/59
Where required?1. On Places of Assembly
Section 10.2.8.8.para E
o bars with live entertainment
o dance halls
Fire Code Provisions on Sprinkler Systems
“FIRE SAFETY
IS OUR MAIN
CONCERN”
-
8/9/2019 Fire Code Provisions on Sprinkler Systems and Standpipe Systems
13/59
Fire Code Provisions on Sprinkler Systems
Where required?
1. On Places of Assembly
o buildings containing assembly occupancies with
an occupant load of more than 300 persons
throughout the storey containing the assemblyoccupancy
throughout all storey below the storey containing
the assembly occupancy
in case of an assembly occupancy located below thelevel of exit discharge, throughout all storeys
intervening between that storey and the level of exit
discharge, including the level of exit discharge.“FIRE SAFETY
IS OUR MAIN
CONCERN”
-
8/9/2019 Fire Code Provisions on Sprinkler Systems and Standpipe Systems
14/59
Except !!!
• Assembly occupancies consisting
of single multipurpose room of
less than 1115 square metersthat are not used for exhibition
or display and are not part of
mixed occupancy
Fire Code Provisions on Sprinkler Systems
“FIRE SAFETY
IS OUR MAIN
CONCERN”
-
8/9/2019 Fire Code Provisions on Sprinkler Systems and Standpipe Systems
15/59
Fire Code Provisions on Sprinkler Systems
Except !!!
• All assembly occupancies with all
sides open
• Places of worship at the level ofexit discharge with sufficient
means of egress.
“FIRE SAFETY
IS OUR MAIN
CONCERN”
-
8/9/2019 Fire Code Provisions on Sprinkler Systems and Standpipe Systems
16/59
Every stage with fly galleries, gridiron andriggings for movable theater type andevery enclosed platform larger than 46.5
m
2
At the ceiling
Under the gridiron
Usable spaces under the stage or platform
In auxiliary spaces Dressing rooms
Storerooms
Workshops
Fire Code Provisions on Sprinkler Systems
Where required?
-
8/9/2019 Fire Code Provisions on Sprinkler Systems and Standpipe Systems
17/59
Where required?
2. On Educational Occupancies
Section 10.2.9.5 para E
o every portion of educational
buildings below the floor of exit
discharge.
Fire Code Provisions on Sprinkler Systems
“FIRE SAFETY
IS OUR MAIN
CONCERN”
-
8/9/2019 Fire Code Provisions on Sprinkler Systems and Standpipe Systems
18/59
2. On Educational Occupancies
Section 10.2.9.5 para F
o hazardous areas shall be
separated from other parts of
the building by 1-hr fireresistance rating construction
or shall be provided with AFSS
Fire Code Provisions on Sprinkler Systems
Where required?
-
8/9/2019 Fire Code Provisions on Sprinkler Systems and Standpipe Systems
19/59
2. On Educational Occupancies
Section 10.2.9.9
o Underground or Windowlesseducational buildings shall be
provided completely with AFSS
Fire Code Provisions on Sprinkler Systems
Where required?
-
8/9/2019 Fire Code Provisions on Sprinkler Systems and Standpipe Systems
20/59
2. On Educational OccupanciesSection 10.2.9.11Existing educational buildings
oThe provision of additional means ofegress, automatic fire suppressionsystem, area separations, emergencylighting and other alternate means ofprotection may be used to providereasonable life safety from fire andpanic.
Fire Code Provisions on Sprinkler Systems
Where required?
-
8/9/2019 Fire Code Provisions on Sprinkler Systems and Standpipe Systems
21/59
Fire Code Provisions on Sprinkler Systems
Where required?
3. On Health Care Facilities
Section 10.2.10.3 para F number 3
o throughout all hospitals
“FIRE SAFETY
IS OUR MAIN
CONCERN”
-
8/9/2019 Fire Code Provisions on Sprinkler Systems and Standpipe Systems
22/59
Where required?4. On Residential Occupancies
For Hotels and Dormitories
Section 10.2.12.3 para C number 5
o All buildings shall be protectedthroughout by sprinkler system exceptwhere all guest rooms or guest suiteshave a door opening directly outside at
the street or grade level or exterior exitaccess in buildings up to and includingthree (3) storeys in height.
Fire Code Provisions on Sprinkler Systems
“FIRE SAFETY
IS OUR MAIN
CONCERN”
-
8/9/2019 Fire Code Provisions on Sprinkler Systems and Standpipe Systems
23/59
Where required?
4. On Residential Occupancies
For Apartment Buildings
Section 10.2.12. para C number 5
o Throughout all buildings except whereall guest rooms or guest suites have adoor opening directly outside at the
street or grade level or exterior exitaccess in buildings up to and includingthree (3) storeys in height.
Fire Code Provisions on Sprinkler Systems
“FIRE SAFETY
IS OUR MAIN
CONCERN”
-
8/9/2019 Fire Code Provisions on Sprinkler Systems and Standpipe Systems
24/59
Where required?
5. On Mercantile OccupanciesSection 10.2.13.3. para D
o All mercantile occupancies three
or more storeys in height.
o All mercantile occupancies
exceeding 1115 square meters ingross area.
Fire Code Provisions on Sprinkler Systems
“FIRE SAFETY
IS OUR MAIN
CONCERN”
-
8/9/2019 Fire Code Provisions on Sprinkler Systems and Standpipe Systems
25/59
Fire Code Provisions on Sprinkler Systems
Where required?
5. On Mercantile OccupanciesSection 10.2.13.3. para D
o Throughout the floor below the
street floor with an area exceeding
232 square meters when used for
the sale, storage or handling of
combustible goods and
merchandise.“FIRE SAFETY
IS OUR MAIN
CONCERN”
-
8/9/2019 Fire Code Provisions on Sprinkler Systems and Standpipe Systems
26/59
-
8/9/2019 Fire Code Provisions on Sprinkler Systems and Standpipe Systems
27/59
-
8/9/2019 Fire Code Provisions on Sprinkler Systems and Standpipe Systems
28/59
Fire Code Provisions on Sprinkler Systems
Where required?
8. On Storage Occupancies
Section 10.2.16.2 para C
o Every high hazard occupancy
“FIRE SAFETY
IS OUR MAIN
CONCERN”
-
8/9/2019 Fire Code Provisions on Sprinkler Systems and Standpipe Systems
29/59
Where required?
9. On High Rise Buildings
Section 10.2.19.4
o throughout all floor spacesincluding every closet and
concealed spaces
Fire Code Provisions on Sprinkler Systems
“FIRE SAFETY
IS OUR MAIN
CONCERN”
-
8/9/2019 Fire Code Provisions on Sprinkler Systems and Standpipe Systems
30/59
General Requirements
Section 10.2.6.6.
Design shall be in accordance with
NFPA 14, Standard for theInstallation of Standpipe, Private
Hydrant and Hose Systems.
Fire Code Provisions on Standpipe Systems
“FIRE SAFETY
IS OUR MAIN
CONCERN”
-
8/9/2019 Fire Code Provisions on Sprinkler Systems and Standpipe Systems
31/59
Dry Standpipe
Where required?
Section 10.2.6.6 para C
All buildings with requiredenclosed stairway or smokeproof
enclosure
Fire Code Provisions on Standpipe Systems
“FIRE SAFETY
IS OUR MAIN
CONCERN”
-
8/9/2019 Fire Code Provisions on Sprinkler Systems and Standpipe Systems
32/59
Dry StandpipeSpecific Requirements
No point in a building shall be more
than 40 meters travel distance from adry standpoint outlet connection.
Dry standpipes shall not be concealed
in building walls or built into pilasters.
Fire Code Provisions on Standpipe Systems
“FIRE SAFETY
IS OUR MAIN
CONCERN”
-
8/9/2019 Fire Code Provisions on Sprinkler Systems and Standpipe Systems
33/59
Wet Standpipe Systems
Where required?
Assembly occupancies with an
occupant load exceeding 1000persons.
Educational, healthcare, business,
mercantile, industrial and hotels andapartments occupancies, of 4 or more
storeys in height.
Fire Code Provisions on Standpipe Systems
“FIRE SAFETY
IS OUR MAIN
CONCERN”
-
8/9/2019 Fire Code Provisions on Sprinkler Systems and Standpipe Systems
34/59
Fire Code Provisions on Standpipe Systems
Wet Standpipe Systems
Where required?
Hazardous storage, business and
mercantile occupancies having afloor area of exceeding 1,860
meters.
“FIRE SAFETY
IS OUR MAIN
CONCERN”
-
8/9/2019 Fire Code Provisions on Sprinkler Systems and Standpipe Systems
35/59
Wet Standpipe Systems
Specific Requirements
Wet standpipes shall be located so
that all portions of the buildingsare within 6 meters of a nozzle
attached to 22 m of hose.
Fire Code Provisions on Standpipe Systems
“FIRE SAFETY
IS OUR MAIN
CONCERN”
-
8/9/2019 Fire Code Provisions on Sprinkler Systems and Standpipe Systems
36/59
Fire Code Provisions on Standpipe Systems
Wet Standpipe Systems
Specific Requirements
In theaters, auditoriums and other
occupancies, where the occupant loadis more than 1000, outlets shall be
located on each side of the stage, on
each side of the rear of theauditorium and on each side of the
balcony.“FIRE SAFETYIS OUR MAINCONCERN”
-
8/9/2019 Fire Code Provisions on Sprinkler Systems and Standpipe Systems
37/59
Alternative Measures
• In cases of existing buildings which
when forced to comply will
compromise its structural
integrity/stability
• The Chief, BFP may accept adequate
alternative and/or remedial fire safetymeasures
Section 14.0.0.4 IRR of RA 9514
“FIRE SAFETY
IS OUR MAIN
CONCERN”
-
8/9/2019 Fire Code Provisions on Sprinkler Systems and Standpipe Systems
38/59
Technical Committee shall assist the
C, BFP in the determination of the
adequacy of the said alternative
measures.
Basis of evaluation shall be an
implementing guidelines approved bySILG.
Alternative Measures
Section 14.0.0.4 IRR of RA 9514
“FIRE SAFETY
IS OUR MAIN
CONCERN”
-
8/9/2019 Fire Code Provisions on Sprinkler Systems and Standpipe Systems
39/59
Guidelines in the
Approval of Alternative
and/or Remedial FireSafety Measures
February 25, 2010
Alternative Measures
MC 2010 - 17
“FIRE SAFETY
IS OUR MAIN
CONCERN”
-
8/9/2019 Fire Code Provisions on Sprinkler Systems and Standpipe Systems
40/59
- only the Chief, BFP
- decision of the C, BFP may beappealed to SILG
Alternative Measures
Authority to Grant Approval/
Exemption
“FIRE SAFETY
IS OUR MAIN
CONCERN”
i
-
8/9/2019 Fire Code Provisions on Sprinkler Systems and Standpipe Systems
41/59
Letter request;
As-built plans;
Occupancy Permit/s;FSCS/Checklist/Clearance/FSIC;
FSIR/NTC/NTCV
Alternative Measures
Requirements
“FIRE SAFETY
IS OUR MAIN
CONCERN”
Al i M
-
8/9/2019 Fire Code Provisions on Sprinkler Systems and Standpipe Systems
42/59
Certification from Structural
Engr that the bldg cannot
support additional load for AFSS;Proposed Alternative and/or
Remedial Fire Safety Measures;
Alternative Measures
Requirements
“FIRE SAFETY
IS OUR MAIN
CONCERN”
Al i M
-
8/9/2019 Fire Code Provisions on Sprinkler Systems and Standpipe Systems
43/59
Fire Safety and Prevention
Program;
Fire Drill Certificate; andAffidavit of Undertaking
Alternative Measures
Requirements
“FIRE SAFETY
IS OUR MAIN
CONCERN”
Al i M
-
8/9/2019 Fire Code Provisions on Sprinkler Systems and Standpipe Systems
44/59
1. Processing an approval of
application.
2. Issuance of Certificate ofExemption
Alternative Measures
Procedures
“FIRE SAFETY
IS OUR MAIN
CONCERN”
Persons Responsible
ACTIVITIES OWNER C/MFM REGIONAL CHAIRMAN CHIEF BFP
-
8/9/2019 Fire Code Provisions on Sprinkler Systems and Standpipe Systems
45/59
ACTIVITIES OWNER C/MFM REGIONAL
DIRECTOR
CHAIRMAN,
FSTC/FSTC
CHIEF, BFP
1. Submit application to the
C/MFM
2. Conduct pre-evaluationand endorse findings to
the Regional Director thru
channel
3. Evaluate the application
and recommend to the
C, BFP thru Chairman,FSTC
4. Conduct physical
inspection and evaluate
proposed alternative
measures
5. Deliberate the inspection
and evaluation reports
and recommend action to
the C, BFP
6. Approve/disapprove
application.
1
2
3
4
5
6
-
8/9/2019 Fire Code Provisions on Sprinkler Systems and Standpipe Systems
46/59
Bureau Order
◦ Name of the building
◦ Location/Address
◦ Name of owner/administrator
◦ Alternative Measures to be
installed/constructed◦ Conditions of approval
Alternative Measures
“FIRE SAFETY
IS OUR MAIN
CONCERN”
Persons ResponsibleACTIVITIES OWNER C/MFM REGIONAL CHAIRMAN CHIEF BFP
-
8/9/2019 Fire Code Provisions on Sprinkler Systems and Standpipe Systems
47/59
ACTIVITIES OWNER C/MFM REGIONAL
DIRECTOR
CHAIRMAN,
FSTC/FSTC
CHIEF, BFP
1. Request the C/MFM for
an inspection of the
completed fire safety
measures
2. Conduct inspection and
endorse findings to the
Regional Director thru
channel
3. Evaluate the findings and
recommend action to
the C, BFP thru Chairman,
FSTC
4. Conduct physical
inspection and evaluate
compliance with the
approved alternative
measures5. Deliberate the inspection
and evaluation reports
and recommend action to
the C, BFP
6. Approve/disapproveapplication.
1
2
3
4
5
6
-
8/9/2019 Fire Code Provisions on Sprinkler Systems and Standpipe Systems
48/59
Bureau Order◦ Name of the building
◦ Location/Address
◦ Name of owner/administrator
◦ Alternative Measures
installed/constructed◦ Conditions of approval
Alternative Measures
“FIRE SAFETY
IS OUR MAIN
CONCERN”
-
8/9/2019 Fire Code Provisions on Sprinkler Systems and Standpipe Systems
49/59
Compliance of Alternative Measures+
Certificate of approval by the C, BFP
=
ISSUANCE OF FSIC
Alternative Measures
“FIRE SAFETY
IS OUR MAIN
CONCERN”
Al i M
-
8/9/2019 Fire Code Provisions on Sprinkler Systems and Standpipe Systems
50/59
Fire Safety Construction
Occupancy Load
Fire ProtectionMeans of Egress
Fire Safety and PreventionPrograms
Alternative Measures
Areas of Emphasis
“FIRE SAFETY
IS OUR MAIN
CONCERN”
Alt ti M
-
8/9/2019 Fire Code Provisions on Sprinkler Systems and Standpipe Systems
51/59
1. All interior partitions must be made of
fire resistive materials including parts or
components, extending from slab to
slab.
2. Rooms, vertical and horizontal openings
or parts thereof must be totally
enclosed.3. All pipe chase must be constructed with
fire collar or fitted sealant.
Alternative Measures
Fire Safety Construction
“FIRE SAFETY
IS OUR MAIN
CONCERN”
Alt ti M
-
8/9/2019 Fire Code Provisions on Sprinkler Systems and Standpipe Systems
52/59
4. All exposed steel structure componentsmust be covered/coated with fire resistivematerials to protect its structural
integrity.5. All fire walls must be extended 20%more from the established standardrequirement.
6. All other fire safety constructioncomponents must be constructed inaccordance with established standard
Alternative Measures
Fire Safety Construction
“FIRE SAFETY
IS OUR MAIN
CONCERN”
Alt ti M
-
8/9/2019 Fire Code Provisions on Sprinkler Systems and Standpipe Systems
53/59
Actual occupant load and
egress capacity for all kinds of
occupancies must not exceedthe established occupant load
standard
Alternative Measures
Occupant Load
“FIRE SAFETY
IS OUR MAIN
CONCERN”
-
8/9/2019 Fire Code Provisions on Sprinkler Systems and Standpipe Systems
54/59
Alt ti M
-
8/9/2019 Fire Code Provisions on Sprinkler Systems and Standpipe Systems
55/59
2. Provision for 20% increase in fire
extinguishers.
3. Installation of wet and dry standpipe
system.
4. Provision for detection and alarm
system.
Alternative Measures
Fire Protection
“FIRE SAFETY
IS OUR MAIN
CONCERN”
Alt ti M
-
8/9/2019 Fire Code Provisions on Sprinkler Systems and Standpipe Systems
56/59
1. Provision for minimum of two (2)secondary fire exits, remote from eachother, travel distance of 20% less than
the standard requirements.a. panic deviceb. self-closing door of 20% more than thestandard.
c. emergency lightings in all stair landingsd. termination of all exits in public egress,continuous and unobstructed.
Alternative Measures
Means of Egress
“FIRE SAFETY
IS OUR MAIN
CONCERN”
Alt ti M
-
8/9/2019 Fire Code Provisions on Sprinkler Systems and Standpipe Systems
57/59
Fire Brigade with COC
Compulsory attendance of all members of
fire brigade in seminars conducted in the
building. Quarterly fire and evacuation drill.
Compulsory attendance of all occupants to
at least 2 seminars conducted in the building. Compulsory orientation on new tenants of
the building
Alternative Measures
Fire Safety and Prevention Programs
“FIRE SAFETY
IS OUR MAIN
CONCERN”
Alt ti M
-
8/9/2019 Fire Code Provisions on Sprinkler Systems and Standpipe Systems
58/59
Within 6 months after the
approval of the Alternative
and/or Remedial Measures
Alternative Measures
Grace Period
“FIRE SAFETY
IS OUR MAIN
CONCERN”
-
8/9/2019 Fire Code Provisions on Sprinkler Systems and Standpipe Systems
59/59
Thank You!
F/INSP JAN GARRY D LUNAS, Ph.D.
Registered Mechanical Engineer/
Fire Safety Engineer
Member, TWG-IRR of RA 9514