    Code Provisionson Sprinkler Systems

    and StandpipeSystems

  • 8/9/2019 Fire Code Provisions on Sprinkler Systems and Standpipe Systems

    3/59

    Outline of Presentation

    I – Sprinkler Systems

    A. General Requirements

    B. Provisions on SpecificTypes of Occupancies

    “FIRE SAFETY

    IS OUR MAIN

    CONCERN”

  • 8/9/2019 Fire Code Provisions on Sprinkler Systems and Standpipe Systems

    4/59

    Outline of Presentation

    II- Standpipe and Hose

    Systems

    A. General RequirementsB. Specific Requirements

    for Dry Standpipe Systemsand Wet Standpipes Systems

    “FIRE SAFETY

    IS OUR MAIN

    CONCERN”

  • 8/9/2019 Fire Code Provisions on Sprinkler Systems and Standpipe Systems

    5/59

    Outline of Presentation

    III – Alternative Measures

    DILG Memo Circular 2010 – 17“Guidelines in the Approval of

    Alternative and/or RemedialFire Safety Measures”

    “FIRE SAFETY

    IS OUR MAIN

    CONCERN”

  • 8/9/2019 Fire Code Provisions on Sprinkler Systems and Standpipe Systems

    6/59

    Fundamental Principle on Fire Safety

    “ Every building or structure shallbe designed , constructed,

    equipped, maintained and

    operated to avoid danger to thelives and ensure safety of its

    occupants from fire, smoke, vapor

    and fumes, during the period ofescape from the building or

    structure.”“FIRE SAFETY

    IS OUR MAIN

    CONCERN”

    “FIRE SAFETY

    IS OUR MAIN

    CONCERN”

  • 8/9/2019 Fire Code Provisions on Sprinkler Systems and Standpipe Systems

    7/59

    Definition

     Automatic Fire Suppression System. An

    integrated system of underground or

    overhead piping or both connected to a

    source of extinguishing agent ormedium and designed in accordance with

    fire protection engineering standards

    which, when actuated by its automaticdetecting device, suppresses fires within

    the area protected.“FIRE SAFETY

    IS OUR MAIN

    CONCERN”

  • 8/9/2019 Fire Code Provisions on Sprinkler Systems and Standpipe Systems

    8/59

    Definition

    Sprinkler System. An integrated network

    of hydraulically designed piping system

    installed in a building, structure or area

    with outlets arranged in a systematicpattern which automatically discharges

    water when activated by heat or

    combustion products from a fire.

    “FIRE SAFETY

    IS OUR MAIN

    CONCERN”

  • 8/9/2019 Fire Code Provisions on Sprinkler Systems and Standpipe Systems

    9/59

    Sprinkler

    Systems

    “FIRE SAFETY

    IS OUR MAIN

    CONCERN”

  • 8/9/2019 Fire Code Provisions on Sprinkler Systems and Standpipe Systems

    10/59

    Fire Code Provisions on Sprinkler Systems

    • Design shall be in accordance with

    NFPA 13.

    • ITM shall be in accordance with NFPA25. Records shall be included in

    FALAR 3.

    General Requirements (Section 10.2.6.5)

    “FIRE SAFETY

    IS OUR MAIN

    CONCERN”

  • 8/9/2019 Fire Code Provisions on Sprinkler Systems and Standpipe Systems

    11/59

    Fire Code Provisions on Sprinkler Systems

    Notification of the nearest fire

    station if the sprinkler system is

    out of service for more than 4

    hours. Building management shall

    designate a fire watch.

    General Requirements (Section 10.2.6.5)

    “FIRE SAFETY

    IS OUR MAIN

    CONCERN”

  • 8/9/2019 Fire Code Provisions on Sprinkler Systems and Standpipe Systems

    12/59

    Where required?1. On Places of Assembly

    Section 10.2.8.8.para E

    o bars with live entertainment

    o dance halls

    Fire Code Provisions on Sprinkler Systems

    “FIRE SAFETY

    IS OUR MAIN

    CONCERN”

  • 8/9/2019 Fire Code Provisions on Sprinkler Systems and Standpipe Systems

    13/59

    Fire Code Provisions on Sprinkler Systems

    Where required?

    1. On Places of Assembly

    o buildings containing assembly occupancies with

    an occupant load of more than 300 persons

    throughout the storey containing the assemblyoccupancy

    throughout all storey below the storey containing

    the assembly occupancy

    in case of an assembly occupancy located below thelevel of exit discharge, throughout all storeys

    intervening between that storey and the level of exit

    discharge, including the level of exit discharge.“FIRE SAFETY

    IS OUR MAIN

    CONCERN”

  • 8/9/2019 Fire Code Provisions on Sprinkler Systems and Standpipe Systems

    14/59

    Except !!!

    • Assembly occupancies consisting

    of single multipurpose room of

    less than 1115 square metersthat are not used for exhibition

    or display and are not part of

    mixed occupancy

    Fire Code Provisions on Sprinkler Systems

    “FIRE SAFETY

    IS OUR MAIN

    CONCERN”

  • 8/9/2019 Fire Code Provisions on Sprinkler Systems and Standpipe Systems

    15/59

    Fire Code Provisions on Sprinkler Systems

    Except !!!

    • All assembly occupancies with all

    sides open

    • Places of worship at the level ofexit discharge with sufficient

    means of egress.

    “FIRE SAFETY

    IS OUR MAIN

    CONCERN”

  • 8/9/2019 Fire Code Provisions on Sprinkler Systems and Standpipe Systems

    16/59

    Every stage with fly galleries, gridiron andriggings for movable theater type andevery enclosed platform larger than 46.5

    m

    2

    At the ceiling

    Under the gridiron

    Usable spaces under the stage or platform

    In auxiliary spaces Dressing rooms

    Storerooms

    Workshops

    Fire Code Provisions on Sprinkler Systems

    Where required?

  • 8/9/2019 Fire Code Provisions on Sprinkler Systems and Standpipe Systems

    17/59

    Where required?

    2. On Educational Occupancies

    Section 10.2.9.5 para E

    o every portion of educational

    buildings below the floor of exit

    discharge.

    Fire Code Provisions on Sprinkler Systems

    “FIRE SAFETY

    IS OUR MAIN

    CONCERN”

  • 8/9/2019 Fire Code Provisions on Sprinkler Systems and Standpipe Systems

    18/59

    2. On Educational Occupancies

    Section 10.2.9.5 para F 

    o hazardous areas shall be

    separated from other parts of

    the building by 1-hr fireresistance rating construction

    or shall be provided with AFSS

    Fire Code Provisions on Sprinkler Systems

    Where required?

  • 8/9/2019 Fire Code Provisions on Sprinkler Systems and Standpipe Systems

    19/59

    2. On Educational Occupancies

    Section 10.2.9.9

    o Underground or Windowlesseducational buildings shall be

    provided completely with AFSS

    Fire Code Provisions on Sprinkler Systems

    Where required?

  • 8/9/2019 Fire Code Provisions on Sprinkler Systems and Standpipe Systems

    20/59

    2. On Educational OccupanciesSection 10.2.9.11Existing educational buildings

    oThe provision of additional means ofegress, automatic fire suppressionsystem, area separations, emergencylighting and other alternate means ofprotection may be used to providereasonable life safety from fire andpanic.

    Fire Code Provisions on Sprinkler Systems

    Where required?

  • 8/9/2019 Fire Code Provisions on Sprinkler Systems and Standpipe Systems

    21/59

    Fire Code Provisions on Sprinkler Systems

    Where required?

    3. On Health Care Facilities

    Section 10.2.10.3 para F number 3

    o throughout all hospitals

    “FIRE SAFETY

    IS OUR MAIN

    CONCERN”

  • 8/9/2019 Fire Code Provisions on Sprinkler Systems and Standpipe Systems

    22/59

    Where required?4. On Residential Occupancies

    For Hotels and Dormitories

    Section 10.2.12.3 para C number 5

    o All buildings shall be protectedthroughout by sprinkler system exceptwhere all guest rooms or guest suiteshave a door opening directly outside at

    the street or grade level or exterior exitaccess in buildings up to and includingthree (3) storeys in height.

    Fire Code Provisions on Sprinkler Systems

    “FIRE SAFETY

    IS OUR MAIN

    CONCERN”

  • 8/9/2019 Fire Code Provisions on Sprinkler Systems and Standpipe Systems

    23/59

    Where required?

    4. On Residential Occupancies

    For Apartment Buildings

    Section 10.2.12. para C number 5

    o Throughout all buildings except whereall guest rooms or guest suites have adoor opening directly outside at the

    street or grade level or exterior exitaccess in buildings up to and includingthree (3) storeys in height.

    Fire Code Provisions on Sprinkler Systems

    “FIRE SAFETY

    IS OUR MAIN

    CONCERN”

  • 8/9/2019 Fire Code Provisions on Sprinkler Systems and Standpipe Systems

    24/59

    Where required?

    5. On Mercantile OccupanciesSection 10.2.13.3. para D

    o All mercantile occupancies three

    or more storeys in height.

    o All mercantile occupancies

    exceeding 1115 square meters ingross area.

    Fire Code Provisions on Sprinkler Systems

    “FIRE SAFETY

    IS OUR MAIN

    CONCERN”

  • 8/9/2019 Fire Code Provisions on Sprinkler Systems and Standpipe Systems

    25/59

    Fire Code Provisions on Sprinkler Systems

    Where required?

    5. On Mercantile OccupanciesSection 10.2.13.3. para D

    o Throughout the floor below the

    street floor with an area exceeding

    232 square meters when used for

    the sale, storage or handling of

    combustible goods and

    merchandise.“FIRE SAFETY

    IS OUR MAIN

    CONCERN”

  • 8/9/2019 Fire Code Provisions on Sprinkler Systems and Standpipe Systems

    26/59

  • 8/9/2019 Fire Code Provisions on Sprinkler Systems and Standpipe Systems

    27/59

  • 8/9/2019 Fire Code Provisions on Sprinkler Systems and Standpipe Systems

    28/59

    Fire Code Provisions on Sprinkler Systems

    Where required?

    8. On Storage Occupancies

    Section 10.2.16.2 para C

    o Every high hazard occupancy

    “FIRE SAFETY

    IS OUR MAIN

    CONCERN”

  • 8/9/2019 Fire Code Provisions on Sprinkler Systems and Standpipe Systems

    29/59

    Where required?

    9. On High Rise Buildings

    Section 10.2.19.4

    o throughout all floor spacesincluding every closet and

    concealed spaces

    Fire Code Provisions on Sprinkler Systems

    “FIRE SAFETY

    IS OUR MAIN

    CONCERN”

  • 8/9/2019 Fire Code Provisions on Sprinkler Systems and Standpipe Systems

    30/59

    General Requirements

    Section 10.2.6.6.

    Design shall be in accordance with

    NFPA 14, Standard for theInstallation of Standpipe, Private

    Hydrant and Hose Systems.

    Fire Code Provisions on Standpipe Systems

    “FIRE SAFETY

    IS OUR MAIN

    CONCERN”

  • 8/9/2019 Fire Code Provisions on Sprinkler Systems and Standpipe Systems

    31/59

    Dry Standpipe

    Where required? 

    Section 10.2.6.6 para C

    All buildings with requiredenclosed stairway or smokeproof 

    enclosure

    Fire Code Provisions on Standpipe Systems

    “FIRE SAFETY

    IS OUR MAIN

    CONCERN”

  • 8/9/2019 Fire Code Provisions on Sprinkler Systems and Standpipe Systems

    32/59

    Dry StandpipeSpecific Requirements

    No point in a building shall be more

    than 40 meters travel distance from adry standpoint outlet connection.

    Dry standpipes shall not be concealed

    in building walls or built into pilasters.

    Fire Code Provisions on Standpipe Systems

    “FIRE SAFETY

    IS OUR MAIN

    CONCERN”

  • 8/9/2019 Fire Code Provisions on Sprinkler Systems and Standpipe Systems

    33/59

    Wet Standpipe Systems

    Where required? 

    Assembly occupancies with an

    occupant load exceeding 1000persons.

    Educational, healthcare, business,

    mercantile, industrial and hotels andapartments occupancies, of 4 or more

    storeys in height.

    Fire Code Provisions on Standpipe Systems

    “FIRE SAFETY

    IS OUR MAIN

    CONCERN”

  • 8/9/2019 Fire Code Provisions on Sprinkler Systems and Standpipe Systems

    34/59

    Fire Code Provisions on Standpipe Systems

    Wet Standpipe Systems

    Where required? 

    Hazardous storage, business and

    mercantile occupancies having afloor area of exceeding 1,860

    meters.

    “FIRE SAFETY

    IS OUR MAIN

    CONCERN”

  • 8/9/2019 Fire Code Provisions on Sprinkler Systems and Standpipe Systems

    35/59

    Wet Standpipe Systems

    Specific Requirements

    Wet standpipes shall be located so

    that all portions of the buildingsare within 6 meters of a nozzle

    attached to 22 m of hose.

    Fire Code Provisions on Standpipe Systems

    “FIRE SAFETY

    IS OUR MAIN

    CONCERN”

  • 8/9/2019 Fire Code Provisions on Sprinkler Systems and Standpipe Systems

    36/59

    Fire Code Provisions on Standpipe Systems

    Wet Standpipe Systems

    Specific Requirements

    In theaters, auditoriums and other

    occupancies, where the occupant loadis more than 1000, outlets shall be

    located on each side of the stage, on

    each side of the rear of theauditorium and on each side of the

    balcony.“FIRE SAFETYIS OUR MAINCONCERN”

  • 8/9/2019 Fire Code Provisions on Sprinkler Systems and Standpipe Systems

    37/59

    Alternative Measures

    • In cases of existing buildings which

    when forced to comply will

    compromise its structural

    integrity/stability

    • The Chief, BFP may accept adequate

    alternative and/or remedial fire safetymeasures

    Section 14.0.0.4 IRR of RA 9514

    “FIRE SAFETY

    IS OUR MAIN

    CONCERN”

  • 8/9/2019 Fire Code Provisions on Sprinkler Systems and Standpipe Systems

    38/59

    Technical Committee shall assist the

    C, BFP in the determination of the

    adequacy of the said alternative

    measures.

    Basis of evaluation shall be an

    implementing guidelines approved bySILG.

    Alternative Measures

    Section 14.0.0.4 IRR of RA 9514

    “FIRE SAFETY

    IS OUR MAIN

    CONCERN”

  • 8/9/2019 Fire Code Provisions on Sprinkler Systems and Standpipe Systems

    39/59

    Guidelines in the

    Approval of Alternative

    and/or Remedial FireSafety Measures

    February 25, 2010

    Alternative Measures

    MC 2010 - 17

    “FIRE SAFETY

    IS OUR MAIN

    CONCERN”

  • 8/9/2019 Fire Code Provisions on Sprinkler Systems and Standpipe Systems

    40/59

    - only the Chief, BFP

    - decision of the C, BFP may beappealed to SILG

    Alternative Measures

    Authority to Grant Approval/

    Exemption

    “FIRE SAFETY

    IS OUR MAIN

    CONCERN”

    i

  • 8/9/2019 Fire Code Provisions on Sprinkler Systems and Standpipe Systems

    41/59

    Letter request;

    As-built plans;

    Occupancy Permit/s;FSCS/Checklist/Clearance/FSIC;

    FSIR/NTC/NTCV

    Alternative Measures

    Requirements

    “FIRE SAFETY

    IS OUR MAIN

    CONCERN”

    Al i M

  • 8/9/2019 Fire Code Provisions on Sprinkler Systems and Standpipe Systems

    42/59

    Certification from Structural

    Engr that the bldg cannot

    support additional load for AFSS;Proposed Alternative and/or

    Remedial Fire Safety Measures;

    Alternative Measures

    Requirements

    “FIRE SAFETY

    IS OUR MAIN

    CONCERN”

    Al i M

  • 8/9/2019 Fire Code Provisions on Sprinkler Systems and Standpipe Systems

    43/59

    Fire Safety and Prevention

    Program;

    Fire Drill Certificate; andAffidavit of Undertaking

    Alternative Measures

    Requirements

    “FIRE SAFETY

    IS OUR MAIN

    CONCERN”

    Al i M

  • 8/9/2019 Fire Code Provisions on Sprinkler Systems and Standpipe Systems

    44/59

    1. Processing an approval of

    application.

    2. Issuance of Certificate ofExemption

    Alternative Measures

    Procedures

    “FIRE SAFETY

    IS OUR MAIN

    CONCERN”

    Persons Responsible

    ACTIVITIES OWNER C/MFM REGIONAL CHAIRMAN CHIEF BFP

  • 8/9/2019 Fire Code Provisions on Sprinkler Systems and Standpipe Systems

    45/59

    ACTIVITIES OWNER C/MFM REGIONAL

    DIRECTOR

    CHAIRMAN,

    FSTC/FSTC

    CHIEF, BFP

    1. Submit application to the

    C/MFM

    2. Conduct pre-evaluationand endorse findings to

    the Regional Director thru

    channel

    3. Evaluate the application

    and recommend to the

    C, BFP thru Chairman,FSTC

    4. Conduct physical

    inspection and evaluate

    proposed alternative

    measures

    5. Deliberate the inspection

    and evaluation reports

    and recommend action to

    the C, BFP

    6. Approve/disapprove

    application.

    1

    2

    3

    4

    5

    6

  • 8/9/2019 Fire Code Provisions on Sprinkler Systems and Standpipe Systems

    46/59

    Bureau Order

    ◦ Name of the building

    ◦ Location/Address

    ◦ Name of owner/administrator

    ◦ Alternative Measures to be

    installed/constructed◦ Conditions of approval

    Alternative Measures

    “FIRE SAFETY

    IS OUR MAIN

    CONCERN”

    Persons ResponsibleACTIVITIES OWNER C/MFM REGIONAL CHAIRMAN CHIEF BFP

  • 8/9/2019 Fire Code Provisions on Sprinkler Systems and Standpipe Systems

    47/59

    ACTIVITIES OWNER C/MFM REGIONAL

    DIRECTOR

    CHAIRMAN,

    FSTC/FSTC

    CHIEF, BFP

    1. Request the C/MFM for

    an inspection of the

    completed fire safety

    measures

    2. Conduct inspection and

    endorse findings to the

    Regional Director thru

    channel

    3. Evaluate the findings and

    recommend action to

    the C, BFP thru Chairman,

    FSTC

    4. Conduct physical

    inspection and evaluate

    compliance with the

    approved alternative

    measures5. Deliberate the inspection

    and evaluation reports

    and recommend action to

    the C, BFP

    6. Approve/disapproveapplication.

    1

    2

    3

    4

    5

    6

  • 8/9/2019 Fire Code Provisions on Sprinkler Systems and Standpipe Systems

    48/59

    Bureau Order◦ Name of the building

    ◦ Location/Address

    ◦ Name of owner/administrator

    ◦ Alternative Measures

    installed/constructed◦ Conditions of approval

    Alternative Measures

    “FIRE SAFETY

    IS OUR MAIN

    CONCERN”

  • 8/9/2019 Fire Code Provisions on Sprinkler Systems and Standpipe Systems

    49/59

    Compliance of Alternative Measures+

    Certificate of approval by the C, BFP

    =

    ISSUANCE OF FSIC

    Alternative Measures

    “FIRE SAFETY

    IS OUR MAIN

    CONCERN”

    Al i M

  • 8/9/2019 Fire Code Provisions on Sprinkler Systems and Standpipe Systems

    50/59

    Fire Safety Construction

    Occupancy Load

    Fire ProtectionMeans of Egress

    Fire Safety and PreventionPrograms

    Alternative Measures

    Areas of Emphasis

    “FIRE SAFETY

    IS OUR MAIN

    CONCERN”

    Alt ti M

  • 8/9/2019 Fire Code Provisions on Sprinkler Systems and Standpipe Systems

    51/59

    1. All interior partitions must be made of

    fire resistive materials including parts or

    components, extending from slab to

    slab.

    2. Rooms, vertical and horizontal openings

    or parts thereof must be totally

    enclosed.3. All pipe chase must be constructed with

    fire collar or fitted sealant.

    Alternative Measures

    Fire Safety Construction

    “FIRE SAFETY

    IS OUR MAIN

    CONCERN”

    Alt ti M

  • 8/9/2019 Fire Code Provisions on Sprinkler Systems and Standpipe Systems

    52/59

    4. All exposed steel structure componentsmust be covered/coated with fire resistivematerials to protect its structural

    integrity.5. All fire walls must be extended 20%more from the established standardrequirement.

    6. All other fire safety constructioncomponents must be constructed inaccordance with established standard

    Alternative Measures

    Fire Safety Construction

    “FIRE SAFETY

    IS OUR MAIN

    CONCERN”

    Alt ti M

  • 8/9/2019 Fire Code Provisions on Sprinkler Systems and Standpipe Systems

    53/59

    Actual occupant load and

    egress capacity for all kinds of

    occupancies must not exceedthe established occupant load

    standard

    Alternative Measures

    Occupant Load

    “FIRE SAFETY

    IS OUR MAIN

    CONCERN”

  • 8/9/2019 Fire Code Provisions on Sprinkler Systems and Standpipe Systems

    54/59

    Alt ti M

  • 8/9/2019 Fire Code Provisions on Sprinkler Systems and Standpipe Systems

    55/59

    2. Provision for 20% increase in fire

    extinguishers.

    3. Installation of wet and dry standpipe

    system.

    4. Provision for detection and alarm

    system.

    Alternative Measures

    Fire Protection

    “FIRE SAFETY

    IS OUR MAIN

    CONCERN”

    Alt ti M

  • 8/9/2019 Fire Code Provisions on Sprinkler Systems and Standpipe Systems

    56/59

    1. Provision for minimum of two (2)secondary fire exits, remote from eachother, travel distance of 20% less than

    the standard requirements.a. panic deviceb. self-closing door of 20% more than thestandard.

    c. emergency lightings in all stair landingsd. termination of all exits in public egress,continuous and unobstructed.

    Alternative Measures

    Means of Egress

    “FIRE SAFETY

    IS OUR MAIN

    CONCERN”

    Alt ti M

  • 8/9/2019 Fire Code Provisions on Sprinkler Systems and Standpipe Systems

    57/59

    Fire Brigade with COC

    Compulsory attendance of all members of

    fire brigade in seminars conducted in the

    building. Quarterly fire and evacuation drill.

    Compulsory attendance of all occupants to

    at least 2 seminars conducted in the building. Compulsory orientation on new tenants of

    the building

    Alternative Measures

    Fire Safety and Prevention Programs

    “FIRE SAFETY

    IS OUR MAIN

    CONCERN”

    Alt ti M

  • 8/9/2019 Fire Code Provisions on Sprinkler Systems and Standpipe Systems

    58/59

    Within 6 months after the

    approval of the Alternative

    and/or Remedial Measures

    Alternative Measures

    Grace Period

    “FIRE SAFETY

    IS OUR MAIN

    CONCERN”

  • 8/9/2019 Fire Code Provisions on Sprinkler Systems and Standpipe Systems

    59/59

    Thank You!