fire detection & alarm system

39

Upload: politeknik-sultan-haji-ahmad-shah

Post on 10-Aug-2015

139 views

Category:

Engineering


17 download

TRANSCRIPT

Page 1: Fire detection & alarm system
Page 2: Fire detection & alarm system

INTRODUCTIONINTRODUCTION

Fire detection and alarm system are design to Fire detection and alarm system are design to provide warning of the outbreak of fire and provide warning of the outbreak of fire and allow appropriate fire fighting action to taken allow appropriate fire fighting action to taken before the situation get out of control.before the situation get out of control.

The design depends on.The design depends on. A. Type of building –UBBL Requirement, A. Type of building –UBBL Requirement,

Bomba Requirements.Bomba Requirements. B. Type of system to be install.B. Type of system to be install. C. Type Of Fire Detection System.C. Type Of Fire Detection System.

Page 3: Fire detection & alarm system

DESIGN REQUIREMENTSDESIGN REQUIREMENTS

Codes & StandardsCodes & Standards Automatic fire alarm system shall be Automatic fire alarm system shall be

design based on B.S 5839 part 1 ~ part5: design based on B.S 5839 part 1 ~ part5: 1988, UBBL 1984 TENTH SCHEDULE.1988, UBBL 1984 TENTH SCHEDULE.

Others standard LBS 1014 Loss Others standard LBS 1014 Loss Prevention Certification Board Prevention Certification Board

Page 4: Fire detection & alarm system

PLANING THE SYSTEMPLANING THE SYSTEM

Things to be consideredThings to be considered..

What type system is proposed?What type system is proposed? What action is the system expected to initiate in What action is the system expected to initiate in

the even of fire?the even of fire? How big is the building and what type of How big is the building and what type of

building?building? Servicing arrangements. Servicing arrangements. Hidden cost to the user. Hidden cost to the user.

Page 5: Fire detection & alarm system

SELECTING THE TYPE OF SELECTING THE TYPE OF COVERAGECOVERAGE

Discussion with building owner, fire Discussion with building owner, fire authority regarding to type of protection to authority regarding to type of protection to be established for the particular building is be established for the particular building is crucial.crucial.

British Standard 5831 Part 1 1988 provide British Standard 5831 Part 1 1988 provide a on coding system which allow fire a on coding system which allow fire detection and alarm system design to be detection and alarm system design to be specified according to purpose and the specified according to purpose and the extent of protection to be afforded. extent of protection to be afforded.

Page 6: Fire detection & alarm system

SELECTING THE TYPE OF SELECTING THE TYPE OF COVERAGECOVERAGE

Classification of systemClassification of system

1. Manual Type (Type M)-System which 1. Manual Type (Type M)-System which provides manual alarm only.provides manual alarm only.

2. Life Protection (Type L)-System which 2. Life Protection (Type L)-System which provides for the protection of life that is the provides for the protection of life that is the safety of occupants. safety of occupants.

Page 7: Fire detection & alarm system

SELECTING THE TYPE OF SELECTING THE TYPE OF COVERAGECOVERAGE

• Detection of fire. Detection of fire.

• Initiate an alarm of fire.Initiate an alarm of fire.

• Provides sufficient time for occupants to Provides sufficient time for occupants to escape escape

Type L3-Covers escape routes and Type L3-Covers escape routes and adjoining room (detectors) should be adjoining room (detectors) should be situated on to the escape routes.situated on to the escape routes.

Page 8: Fire detection & alarm system

SELECTING THE TYPE OF SELECTING THE TYPE OF COVERAGECOVERAGE

Type L2-Covers escape routes and Type L2-Covers escape routes and adjacent rooms and any other areas adjacent rooms and any other areas where it is considered the occupants are where it is considered the occupants are vulnerable. vulnerable.

Type L1- Total Coverage.Type L1- Total Coverage.

Page 9: Fire detection & alarm system

SELECTING THE TYPE OF SELECTING THE TYPE OF COVERAGECOVERAGE

Property Protection (Type P)Property Protection (Type P)• Automatic detection of fire.Automatic detection of fire.• Initiate an alarm of fire Initiate an alarm of fire • Indicate the location of fire within the Indicate the location of fire within the

premisespremises

Type P2 covers all high risk areaType P2 covers all high risk areaType P1 Total coverage.Type P1 Total coverage.

Page 10: Fire detection & alarm system

HOW TO CONFIGURE ZONE HOW TO CONFIGURE ZONE WITHIN PREMISESWITHIN PREMISES

What is fire zone? What is fire zone?

The most positive and effective where of The most positive and effective where of limiting fire spread within the building is to limiting fire spread within the building is to subdivide it into the smallest practicable subdivide it into the smallest practicable such a compartment is known as a zone.such a compartment is known as a zone.

Each zone will have separate numbers, Each zone will have separate numbers, indications at the main fire alarm indicator.indications at the main fire alarm indicator.

Page 11: Fire detection & alarm system

ZONE CONFIGURATION ZONE CONFIGURATION GUIDELINESGUIDELINES

Maximum Floor Area Of A Zone Should Not Exceed 2000M Maximum Floor Area Of A Zone Should Not Exceed 2000M

The search distance , that is the distance that has to be traveled by a searcher within a fire zone The search distance , that is the distance that has to be traveled by a searcher within a fire zone in order to determine visually the position of fire (not reach the fire ) should not exceed 30m in order to determine visually the position of fire (not reach the fire ) should not exceed 30m

A single zone may be extend to several fire compartmentsA single zone may be extend to several fire compartments

If the total floor area of a building is 300m or less then the building need only be one zone If the total floor area of a building is 300m or less then the building need only be one zone regardless the number of floors.regardless the number of floors.

If the total floor area of a building is greater then 300m then each floor shall be a separate zone If the total floor area of a building is greater then 300m then each floor shall be a separate zone (or set of zones, if the floor area is large enough) There are however two exception for this rules (or set of zones, if the floor area is large enough) There are however two exception for this rules that is:that is:

1. If Communication between two adjacent vertical compartments is at the lowest level, only then 1. If Communication between two adjacent vertical compartments is at the lowest level, only then can each vertical compartment still be considered to be separate multi storied zones can each vertical compartment still be considered to be separate multi storied zones

2.Structures such as stairwell extending to more than one floor but remaining within the same 2.Structures such as stairwell extending to more than one floor but remaining within the same vertical compartment still be considered separate multi stories zone.vertical compartment still be considered separate multi stories zone.

For multi occupancy building, zone boundaries should not cross occupancy boundaries hence a For multi occupancy building, zone boundaries should not cross occupancy boundaries hence a zone should contain only one occupancy. This ruling may be relaxed for Type M system.zone should contain only one occupancy. This ruling may be relaxed for Type M system.

Page 12: Fire detection & alarm system

Zone SafeguardsZone Safeguards

Fault occurring at one zone should not effect the operation of Fault occurring at one zone should not effect the operation of another zone.another zone.

- Line/zone isolating device for addressable system.Line/zone isolating device for addressable system.

A single fault should not remove protection from an area greater A single fault should not remove protection from an area greater than that allowed for a single zonethan that allowed for a single zone

Two fault should not remove protection from an area greater than Two fault should not remove protection from an area greater than 10,000 sq meter.10,000 sq meter.

Short circuit should be reported by the control panel within 100 Short circuit should be reported by the control panel within 100 second of occurrence and open circuit should be reported within 60 second of occurrence and open circuit should be reported within 60 minutes of occurrenceminutes of occurrence

Page 13: Fire detection & alarm system
Page 14: Fire detection & alarm system

Type Of Alarm Detection Type Of Alarm Detection SystemSystem

Conventional SystemConventional System

-Two state Detector (Normal state , alarm state)-Two state Detector (Normal state , alarm state)

-Two wire connection -Two wire connection

-Separate indicator In the Main Fire Alarm Panel.-Separate indicator In the Main Fire Alarm Panel.

-Smoke detector to comply BS 5445 Pt 7 Heat Detector must comply BS 5445 -Smoke detector to comply BS 5445 Pt 7 Heat Detector must comply BS 5445 PT 5 1977- Respond time.PT 5 1977- Respond time.

-Manual Break Glass can share the same circuit as detectors-Manual Break Glass can share the same circuit as detectors

- The removal of any detector shall not prevent from the operating of any The removal of any detector shall not prevent from the operating of any break glassbreak glass

Page 15: Fire detection & alarm system

Type Of Alarm Detection Type Of Alarm Detection SystemSystem

Addressable SystemAddressable System - Addressable detector , call points,signals which is individually identified by Addressable detector , call points,signals which is individually identified by

the control panel the control panel - Addressable detectors shall be connected via two wire connection such that Addressable detectors shall be connected via two wire connection such that

the connection of the both wire to form a loop in order to provide circuit the connection of the both wire to form a loop in order to provide circuit integrity.integrity.

- Main difference between the conventional system is that the base of the Main difference between the conventional system is that the base of the addressable detector is addressed through soft addressing or dip switch.addressable detector is addressed through soft addressing or dip switch.

- Multiplex communication technique allow each detector to independently signals it Multiplex communication technique allow each detector to independently signals it status back to the control panel. status back to the control panel.

- Addressable system can also handle output device on the zone circuit, where the Addressable system can also handle output device on the zone circuit, where the address massage can be command instruction to an output device ( on/Off ) Example address massage can be command instruction to an output device ( on/Off ) Example : Sounder Module , Switching On/Off Relays: Sounder Module , Switching On/Off Relays

- Interface Module is a device that is used interface the conventional alarm system and Interface Module is a device that is used interface the conventional alarm system and the addressable system.the addressable system.

-

Page 16: Fire detection & alarm system
Page 17: Fire detection & alarm system

Type Of Alarm Detection Type Of Alarm Detection SystemSystem

Analog Addressable SystemAnalog Addressable SystemThe sensors gives an analog output signal representing the value of the sense The sensors gives an analog output signal representing the value of the sense phenomenon.phenomenon.The output of an analogue addressable detector is variable and it is The output of an analogue addressable detector is variable and it is proportional representation of the sense effect of fire , smoke and flame.proportional representation of the sense effect of fire , smoke and flame.Transition of this output from a detector is usually in a form of analog current toTransition of this output from a detector is usually in a form of analog current tothe control panel that tells the panel what condition of the room being sensethe control panel that tells the panel what condition of the room being sense/monitored./monitored.Three basic condition to be interpreted by the Control Panel Three basic condition to be interpreted by the Control Panel 1.1. Alarm Condition- Full Scale building evacuation Alarm Condition- Full Scale building evacuation 2.2. Pre Alarm Condition – Inspection and search for source Pre Alarm Condition – Inspection and search for source 3.3. Fault – Warning need to be repair.Fault – Warning need to be repair.In order for an analog addressable system to raise alarm , the analog valueIn order for an analog addressable system to raise alarm , the analog valueoutput by the detector must be in the alarm condition (above the alarm output by the detector must be in the alarm condition (above the alarm threshold) for a period equal to time taken to complete three successive threshold) for a period equal to time taken to complete three successive address sequence ( 6 sec).address sequence ( 6 sec).

Page 18: Fire detection & alarm system
Page 19: Fire detection & alarm system

Types Of DetectorsTypes Of Detectors1.1. Ion Chamber Smoke Detector1Ion Chamber Smoke Detector1Response quickly to small smoke particles however its respond slower to dense smoke.Response quickly to small smoke particles however its respond slower to dense smoke.  Mechanism :Mechanism :  The detector contains small radioactive source which ionizes the air within the samplingThe detector contains small radioactive source which ionizes the air within the sampling chamber. Thus small current established and set up the potential difference betweenchamber. Thus small current established and set up the potential difference between the collector electrode and the outer cover.. The magnitude of potential increment isthe collector electrode and the outer cover.. The magnitude of potential increment is used to indicate the smoke density. Exceeding the preset level will trigger the alarm.used to indicate the smoke density. Exceeding the preset level will trigger the alarm.  2.2. Photo Electric Scatter Smoke DetectorPhoto Electric Scatter Smoke Detector  Response quickly to large smoke particles but they have the tendency to ignore the smallResponse quickly to large smoke particles but they have the tendency to ignore the smallparticles.particles.  Mechanism:Mechanism:  The unit comprise of an optical system that contains an emitter and a sensor that haveThe unit comprise of an optical system that contains an emitter and a sensor that have lens. The emitter produce a beam of light that was prevented from reaching the sensorlens. The emitter produce a beam of light that was prevented from reaching the sensor by a baffle. However when smoke entering the chamber the light tend to be scatteredby a baffle. However when smoke entering the chamber the light tend to be scattered and apportion of light rays will eventually hit the sensor. The rate of light heating theand apportion of light rays will eventually hit the sensor. The rate of light heating the sensor is proportional to the smoke density. At per determined threshold the output of the sensor sensor is proportional to the smoke density. At per determined threshold the output of the sensor

signals an alarm to the Main Controller Panel.signals an alarm to the Main Controller Panel.

  

Page 20: Fire detection & alarm system

Types Of DetectorsTypes Of Detectors

3.3. High Performance Smoke DetectorHigh Performance Smoke Detector

  

It responses to the some in the same way as the Photo Electric detector, butIt responses to the some in the same way as the Photo Electric detector, but

there is a rapid rate of rise in temperature will be also taken into considerationsthere is a rapid rate of rise in temperature will be also taken into considerations

which in turn increase their sensitivity accordingly. Therefore this unit can alsowhich in turn increase their sensitivity accordingly. Therefore this unit can also

pick up a very small smoke particles as per ionization Chamber type detector.pick up a very small smoke particles as per ionization Chamber type detector.

Page 21: Fire detection & alarm system
Page 22: Fire detection & alarm system

Types Of DetectorsTypes Of DetectorsHeat Detector.Heat Detector.  Less sensitive alternative, to be use at the location where the smoke detector cannot be use.Less sensitive alternative, to be use at the location where the smoke detector cannot be use.To be use for monitoring product that will emit little smoke when burns.To be use for monitoring product that will emit little smoke when burns.  Types of Heat Detector.Types of Heat Detector.  1.1. Rate Of Rise DetectorsRate Of Rise DetectorsReact to abnormal high rise of change of temperature and provide fastest response over wide range React to abnormal high rise of change of temperature and provide fastest response over wide range Of ambient temperature.Of ambient temperature.Suitable to be use where large change of ambient temperature will signals the alarm condition toSuitable to be use where large change of ambient temperature will signals the alarm condition tocontrol panel.control panel.2.2. Fixed Temperature Static Heat DetectorFixed Temperature Static Heat Detector..  Similar to rate of rise detector but it react to a fix predetermined temperature rather than rate of Similar to rate of rise detector but it react to a fix predetermined temperature rather than rate of Rise temperature. Suitable for the use in an area where sudden large change in temperature isRise temperature. Suitable for the use in an area where sudden large change in temperature isconsidered normal such as kitchen and boiler room.considered normal such as kitchen and boiler room.  3.3. Line type detectorsLine type detectors  Not Commonly use , it comes in a log wire or tube and are design to sense the condition vicinity to Not Commonly use , it comes in a log wire or tube and are design to sense the condition vicinity to

thetheline. Suitable for cable tunnel, subways duct, aircraft hangers. line. Suitable for cable tunnel, subways duct, aircraft hangers. 

Page 23: Fire detection & alarm system
Page 24: Fire detection & alarm system

Types Of DetectorsTypes Of Detectors

4.4. Flame Detector Flame Detector

Detect electromagnetic radiation from aDetect electromagnetic radiation from a

flame (short wavelength 5 ~ 30 Hz )flame (short wavelength 5 ~ 30 Hz )

The detector cannot respond to fireThe detector cannot respond to fire

outbreak until there is a flame. It isoutbreak until there is a flame. It is

practical to use smoke detector inpractical to use smoke detector in

conjunction of flame detector.conjunction of flame detector.

Often used at the large open areas. AOften used at the large open areas. A

direct line of sight is required for effectivedirect line of sight is required for effective

detection.detection.

It response quickly to a clean burning fuelsIt response quickly to a clean burning fuels

such as methane, alcohol that cannot besuch as methane, alcohol that cannot be

detected by smoke detector.detected by smoke detector.

Page 25: Fire detection & alarm system

Types Of DetectorsTypes Of Detectors  1.1. Optical Beam DetectorOptical Beam Detector The detector consist of two gadgetThe detector consist of two gadgeta.a. Transmitter – Infrared light beam projection Transmitter – Infrared light beam projection b.b. Receiver – Received the projected infra red beam. Continuously Receiver – Received the projected infra red beam. Continuously

monitor the received beam.monitor the received beam.  Specifically design for interior uses in large open type areaSpecifically design for interior uses in large open type areasuch as warehouse , galleries, manufacturing plant workshopsuch as warehouse , galleries, manufacturing plant workshopand etc. Where the installation of point type detectors areand etc. Where the installation of point type detectors areimpossible, difficult.impossible, difficult.  Should be any fire outbreaks, smoke particles rising upwardsShould be any fire outbreaks, smoke particles rising upwardsInterrupts or partly deflect the light beam thus reducing theInterrupts or partly deflect the light beam thus reducing thestrength of beam received. If the reduction of signal receivedstrength of beam received. If the reduction of signal receivedby the receiver in the range of 40% to 90% for a periodby the receiver in the range of 40% to 90% for a periodgreater than five second it cause the system go to alarm.greater than five second it cause the system go to alarm.  For optimum /correct operation the transmitter and the receiver must beFor optimum /correct operation the transmitter and the receiver must beinstalled in the roof space or just below the ceiling.installed in the roof space or just below the ceiling.  Each detector is capable of protecting an area of 7 m each side of beamEach detector is capable of protecting an area of 7 m each side of beamcenter line for a distance up to 100 mcenter line for a distance up to 100 m

Page 26: Fire detection & alarm system

Types Of DetectorsTypes Of Detectors

6.6. Aspirating DetectorAspirating Detector  

The detection system includes a small pump that draws air sample from the room air through setsThe detection system includes a small pump that draws air sample from the room air through setsof tubes into a detector element. The tube can be split into several smaller tubes (each drawingof tubes into a detector element. The tube can be split into several smaller tubes (each drawingair from different location) air from different location)   Due to dilution of smoke the detector element is 100 times more sensitive than the conventionalDue to dilution of smoke the detector element is 100 times more sensitive than the conventionalpoint type. The sucked air is filtered to avoid false analysis from room dust.point type. The sucked air is filtered to avoid false analysis from room dust.  

Page 27: Fire detection & alarm system

Types Of DetectorsTypes Of Detectors

7. Duct Probe Unit. 

The detector is use to sense the presence of smoke/ combustion product in ventilation duct. Design to operate via principle of differential air pressure. Consist of 2 probe of different length, works on the differential air pressure created between the two probes that are inserted into the duct airflow. The longer probe which is the inlet port for sampling air will lead the samples passing through the sampling chamber for analysis and let the air goes by through the shorter tube.

Page 28: Fire detection & alarm system

Detector Coverage

1.Spacing Under Flat Ceiling  Smoke Detector : Every point should lie a horizontal distance of 7.5 m  

Heat Detector : Every point should lie a horizontal distance of 5.3m

Page 29: Fire detection & alarm system

Detector Coverage

2. Spacing Under Pitch Ceiling  If the difference in height between any apex and an adjacent valley or low point of the ceiling exceed 600mm for smoke detector or 150mm for heat detector, then the detector should be place on the apex If less, the ceiling can be considered as flat. For detector mounted on the apex the radius of cover of a detector can be increase by 1% over each degree of slope, up to a maximum 25 % . The increment of coverage area up tp 25% is only applying to detectors mounted on the apex row.For hemispherical dome or a semi cylindrical arch radius of cover of a detector in the center can be taken as 8.93 m for smoke and 6.31 for heat detector.

Page 30: Fire detection & alarm system

Detector Coverage

Spacing In corridors  In the corridors the constrains of walls cause the hot gas given of by fire to travel faster . Therefore the coverage area is allowed to be bigger. 

Page 31: Fire detection & alarm system

Detector Coverage

Obstruction  If the passage of smoke or hot gas is likely to be obstruct by ceiling obstruction such as beam which has depth greater than 150 mm but less than 10 % of the height of the ceiling then the normal coverage distance allowed for the smoke and heat detector should be decrease by twice the depth of the obstruction  Smoke Detector Coverage Area : 7.5 m – ( 2 x obstruction depth)  Heat detector Coverage Area : 5.3 m – (2 x obstruction depth)  Wall and ceiling reaching within 300 mm off the ceiling or obstruction such as beam that is deeper than 10% of the ceiling to floor height shall be treated as separate rooms. 

Page 32: Fire detection & alarm system

Detector CoverageCeiling Height.Ceiling Height.  

Detector should not be mounted higher than general limits in table 6 below however theDetector should not be mounted higher than general limits in table 6 below however theRapid attendance limit shall be accepted under below mention condition Rapid attendance limit shall be accepted under below mention condition   1.1.     1.     1. In the event of fire, alarm is automatically sent to the fire brigade service and their In the event of fire, alarm is automatically sent to the fire brigade service and their

usual attendance is 5 minutes or less.usual attendance is 5 minutes or less.2.2.      2.      2. There are small section of the ceiling which do not exceed 10% of total ceiling area.There are small section of the ceiling which do not exceed 10% of total ceiling area.

Page 33: Fire detection & alarm system

Detector Coverage

Wall and PartitionWall and Partition

  

Detector should not be mounted within 500 mm of any wall due to deadDetector should not be mounted within 500 mm of any wall due to dead

spot near wall.spot near wall.

  Void.Void.

Ceiling and Under Voids 800 mm or more in height should also be zoned andCeiling and Under Voids 800 mm or more in height should also be zoned and

protected by detectors. Void less the 800 mm need not to be protected. Unlessprotected by detectors. Void less the 800 mm need not to be protected. Unless

extensive spread of fire or its product , particularly between rooms and extensive spread of fire or its product , particularly between rooms and

compartments can take place within it before detection.compartments can take place within it before detection.

  

Page 34: Fire detection & alarm system

Detector Coverage

Ventilation Effect  

Movement of air can cause dilution of smoke /heat intensity until detectors install cant detect the fire outbreak .

• Smoke test to be conducted to find the most effectivelocation of mounting detectors.

2. Use infrared beam type detectors if suitable.3. Detectors should not be mount directly in the fresh air input

from air conditioning system. Generally spacing of detectors not less than 1 m from the air intake should be maintained.

4. Use duct probe sensor.

Page 35: Fire detection & alarm system

Detector Coverage

Manual Break Glass Call PointsManual Break Glass Call Points

  

1.1.                                        Comply with 30 m distance rule.Comply with 30 m distance rule.

2.2.                                        Use the same method of operation through out the building.Use the same method of operation through out the building.

3.3.                                        Should be located at the exit routs such as floor landing stairways Should be located at the exit routs such as floor landing stairways andand

exit to the open air.exit to the open air.

4.4.                                        The time between operation and the sounding of the alarm shouldThe time between operation and the sounding of the alarm should

ideally les than one second.ideally les than one second.

5.5.                                        Be mounted at the height of 1.4m from the floorBe mounted at the height of 1.4m from the floor

6.6.                                        Be mounted against contrasting background.Be mounted against contrasting background.

7.7.                                        Manual call points to be indicated separately from detectors.Manual call points to be indicated separately from detectors.

Page 36: Fire detection & alarm system

Audibility requirement of Alarm SoundersAudibility requirement of Alarm Sounders

Life Protection Requirement.Life Protection Requirement.

  

Where premises are occupied guidelines for alerting the occupant of the building in theWhere premises are occupied guidelines for alerting the occupant of the building in the

event of fire are as followsevent of fire are as follows

  

1.1.           1.1. The sounder should be located near the control panel.The sounder should be located near the control panel.

2.2.            2.            2. In normal surrounding the sound level should be at least 65 dBA or 5 dBAIn normal surrounding the sound level should be at least 65 dBA or 5 dBA

above ambient.above ambient.

3.3.            3.            3. If sleeping person are to be woken up , the sound level should be at leastIf sleeping person are to be woken up , the sound level should be at least

75dBA measured at the bed head.75dBA measured at the bed head.

4.4.            4.            4. Alarm sound should be the same for all parts of the buildingsAlarm sound should be the same for all parts of the buildings

5.5.            5.            5. Frequency of sounders should be between 500 hz to 1000 hzFrequency of sounders should be between 500 hz to 1000 hz

6.6.            6.            6. Visual alarm signal such as flashing beacon , etc should be provided in Visual alarm signal such as flashing beacon , etc should be provided in areas areas of high background noise where some occupants may have impaired of high background noise where some occupants may have impaired hearing.hearing.

7.7.            7.            7. Voice evacuation is an alternative to alarm sounder or bell is permitted.Voice evacuation is an alternative to alarm sounder or bell is permitted.

Page 37: Fire detection & alarm system

Audibility requirement of Alarm SoundersAudibility requirement of Alarm Sounders

Controller EquipmentsController Equipments

  

1.1. The sitting of MFP should be in the location of low fire risk The sitting of MFP should be in the location of low fire risk

2.2. Its indication should be quickly available to staff and those who might have to carry out Its indication should be quickly available to staff and those who might have to carry out actions in the event of fireactions in the event of fire

3.3. Indicator should be easily visible both in darkness and sunlight.Indicator should be easily visible both in darkness and sunlight.

4.4. If some ambient lighting is required it should be provided either by building emergency lighting If some ambient lighting is required it should be provided either by building emergency lighting supply or by special luminaries fed from the fire alarm system supply.supply or by special luminaries fed from the fire alarm system supply.

5.5. Noise or other sound level in the vicinity of MFP should not mask out the audible alarm of Noise or other sound level in the vicinity of MFP should not mask out the audible alarm of sounder located near the control equipmentssounder located near the control equipments

6.6. In multi occupancy building, sitting should be agreed with the other occupants.In multi occupancy building, sitting should be agreed with the other occupants.

7.7. Mimic diagram should be located along side the control panelMimic diagram should be located along side the control panel

8.8. Operation of fire alarm panel to be operated by authorized personnel only.Operation of fire alarm panel to be operated by authorized personnel only.

  

Page 38: Fire detection & alarm system

Power Supplies Power Supplies

Independent Power From Mains, Standby Independent Power From Mains, Standby Batteries with automatic charger Batteries with automatic charger

Battery life expectancy min of 4 years Battery life expectancy min of 4 years

Batteries capacity shall be able to support Batteries capacity shall be able to support running ampere of 24 hr supervisory load running ampere of 24 hr supervisory load and 30 min alarm mode. and 30 min alarm mode.

Page 39: Fire detection & alarm system

Battery calculation Battery calculation

If the premise is unoccupied from 6.00 p.m on If the premise is unoccupied from 6.00 p.m on Friday to 8.00 a.m on Monday. Given that the Friday to 8.00 a.m on Monday. Given that the operating current of the system is 350 mA and operating current of the system is 350 mA and the alarm running current is 2.0A Find the total the alarm running current is 2.0A Find the total capacity of suitable batteries.capacity of suitable batteries.

Formula: Formula:

Total Capacity req= ((Max Unsupervised Time+ 24 Total Capacity req= ((Max Unsupervised Time+ 24 HR) X Operating Current)+( Alarm Current x HR) X Operating Current)+( Alarm Current x Alarm Duration) Alarm Duration)