Fire Fighting Systems Fi Fi Mains White System: This system has a lower output as far as volume goes. This main supplies 3x Eductor/Hydrants (500 gpm). All hydrants are located on the main deck. Two are at the aft Bulwarks, P&S and the other is just forward of the superstructure on port side. It also supplies the 1 inch hose reel located at the aft of the superstructure mounted overhead at the boat deck level. The White system is supplied by the # 3 Engine & # 7 Pump discharging 2000 gpm@250 psi. It is

Upload: christal-richard

Post on 17-Jan-2016

215 views

Category:

Documents


1 download

TRANSCRIPT

Page 1: Fire Fighting Systems Fi Fi Mains ●White System: This system has a lower output as far as volume goes. This main supplies 3x Eductor/Hydrants (500 gpm)

Fire Fighting Systems Fi Fi Mains ● White System: This system has a lower output as far as

volume goes. This main supplies 3x Eductor/Hydrants (500 gpm). All hydrants are located on the main deck. Two are at the aft Bulwarks, P&S and the other is just forward of the superstructure on port side. It also supplies the 1 inch hose reel located at the aft of the superstructure mounted overhead at the boat deck level. The White system is supplied by the # 3 Engine & # 7 Pump discharging 2000 gpm@250 psi. It is likely this system will be the most used on the boat.

Page 2: Fire Fighting Systems Fi Fi Mains ●White System: This system has a lower output as far as volume goes. This main supplies 3x Eductor/Hydrants (500 gpm)

Fire Fighting SystemsFi Fi Mains

Overboard discharge

Siphon Eductors

Hose reel

2000 GPM Pump 7

Page 3: Fire Fighting Systems Fi Fi Mains ●White System: This system has a lower output as far as volume goes. This main supplies 3x Eductor/Hydrants (500 gpm)

Fire Fighting Systems

A quick look at the controls on the panels in the wheelhouse. EZto follow.

The White system has its own control panel. The panel was not installed yet for us to show you.

Page 4: Fire Fighting Systems Fi Fi Mains ●White System: This system has a lower output as far as volume goes. This main supplies 3x Eductor/Hydrants (500 gpm)

Fire Fighting SystemsFire Pumps

● 1-SFP HP 150x200 FFS single stage centrifugal pump● Sealed bearings permanently greased no maintenance● Hard mounted with a direct flexible coupling drive off the C-12 Caterpillar● Nominal speed 1800 rpm● 2000 gpm @ 250 psi● Stand alone Pump and Engine. Can only be controlled from wheelhouse ● White System. Pump 7

Page 5: Fire Fighting Systems Fi Fi Mains ●White System: This system has a lower output as far as volume goes. This main supplies 3x Eductor/Hydrants (500 gpm)

Fire Fighting Systems

Fi Fi Pumps

Pump 7

Fi Fi Pumps

Page 6: Fire Fighting Systems Fi Fi Mains ●White System: This system has a lower output as far as volume goes. This main supplies 3x Eductor/Hydrants (500 gpm)

Fire Fighting SystemsFire Pumps

Notice how much larger the clutched fire pump assemblies are in comparison to the direct drive units.

Port Side RED system Stand alone C-12 White system

Aft Aft

Page 7: Fire Fighting Systems Fi Fi Mains ●White System: This system has a lower output as far as volume goes. This main supplies 3x Eductor/Hydrants (500 gpm)

Fire Fighting SystemsFire Pumps Fire Pumps White system Pump is rated at 2000 gpm 250 psi. This will be

the workhorse system. Most hand lines, (foam capable) dewatering of vessels and washdown/containment will derive from this system. Located aft and Starboard in the ER.

Pump 7

Aft

Page 8: Fire Fighting Systems Fi Fi Mains ●White System: This system has a lower output as far as volume goes. This main supplies 3x Eductor/Hydrants (500 gpm)

Fire Fighting Systems

Pump Intakes The White system (2000) gpm intake valve assembly is located just forward of # 7 Engine and Pump. Notice that the actuator sets right at the floor plate level.

C-12 Engine

Page 9: Fire Fighting Systems Fi Fi Mains ●White System: This system has a lower output as far as volume goes. This main supplies 3x Eductor/Hydrants (500 gpm)

Fire Fighting SystemsDischarge Piping

The Discharge piping consists of a series of valves, check valves (clappers) and bypasses. Also system pressure sensors. As previously mentioned, the Blue System has an Isolation valve to separate the system into two parts if wanted.

We are not going to trace all the systems out with a pictorial highway. To much to show. You will see it soon enough. But since these systems are all similar, a of couple of pictures will suffice. We will look at the bypasses, clappers and fire main overboard discharges.

It is important to remember that there are NO relief valves in these Fire Fighting Systems. The occurrence of a Water Hammer has to be constantly on the mind of the operator while pumping. Thousands of gallons (weight) in motion can not stop quicky without damaging something! Take your time!

Page 10: Fire Fighting Systems Fi Fi Mains ●White System: This system has a lower output as far as volume goes. This main supplies 3x Eductor/Hydrants (500 gpm)

Fire Fighting SystemsDischarge Piping

Clapper Valve

All discharge systems are identical in regards to the valving, clapper- valves and bypasses. Remember the discharge valves are remotely controlled from the wheelhouse FFS panels.

Page 11: Fire Fighting Systems Fi Fi Mains ●White System: This system has a lower output as far as volume goes. This main supplies 3x Eductor/Hydrants (500 gpm)

Fire Fighting SystemsBypass Systems

● Clapper Valve bypass (drain)

● Clapper Valve● Isolation Valves● Bypass Loop● (RC) Discharge

Valve● Sensors/Gages

The idea of the bypass loop is to be able to fill the system very slowly to minimize water hammer. In reality we will leave the isolation valve open and fill the system at idle, watching for a lazy discharge out the monitors. Possibly at times using the overboard discharges.

Page 12: Fire Fighting Systems Fi Fi Mains ●White System: This system has a lower output as far as volume goes. This main supplies 3x Eductor/Hydrants (500 gpm)

Fire Fighting Systems

Fire Main Overboards The overboard systems are remotely controlled from the FFS panels. The operator can use the Overboards to divert pressure or drain a system. The water flow is directed downward at the through hull for obvious reasons. Visualize the out flow.

Overboard Discharge Clapper Valve

(RC) Discharge Valve

Page 13: Fire Fighting Systems Fi Fi Mains ●White System: This system has a lower output as far as volume goes. This main supplies 3x Eductor/Hydrants (500 gpm)

Fire Fighting Systems

Observation/Security Drones They are camouflaged to look like Ospreys

Camera

Page 14: Fire Fighting Systems Fi Fi Mains ●White System: This system has a lower output as far as volume goes. This main supplies 3x Eductor/Hydrants (500 gpm)

Fire Fighting Systems

Fi Fi Controls The controls are 24v activated from the FFS panels. The discharge valves are Electric Motor driven. The intake valves are Electric/Air. Air being the driver.

Valves are slow Opening/Closing

Page 15: Fire Fighting Systems Fi Fi Mains ●White System: This system has a lower output as far as volume goes. This main supplies 3x Eductor/Hydrants (500 gpm)

Fire Fighting SystemFi Fi Controls

Valve Open/Close switch (momentary)

EZ to follow

Engine Run Indicator

Valve Open/Close Light

Clutch In/Out Button and indicator light

EZ to follow diagrams

Page 16: Fire Fighting Systems Fi Fi Mains ●White System: This system has a lower output as far as volume goes. This main supplies 3x Eductor/Hydrants (500 gpm)

Fire Fighting SystemFi Fi Controls

Pressure Gages are located on the fore and aft panels in the Wheel-House. Pick your color!

Notice there are two Blue gages. This is because the Blue system can be separated by theIsolation valve we mentioned earlier.

Page 17: Fire Fighting Systems Fi Fi Mains ●White System: This system has a lower output as far as volume goes. This main supplies 3x Eductor/Hydrants (500 gpm)

Fire Fighter SystemFi Fi Controls

Overview of forward panel. EZ to follow!

Notice they are installing the Engineer's chair! SWEET!

Page 18: Fire Fighting Systems Fi Fi Mains ●White System: This system has a lower output as far as volume goes. This main supplies 3x Eductor/Hydrants (500 gpm)

Fire Fighting System - White

Fi Fi OverviewAft Hose Reel300’x1” (Main Deck)

Fwd Hydrant(2) 2 ½” Valves

Aft Eductors(Port & Stbd) 500-GPM Fwd Eductor

(Port)500 GPM

Page 19: Fire Fighting Systems Fi Fi Mains ●White System: This system has a lower output as far as volume goes. This main supplies 3x Eductor/Hydrants (500 gpm)

Fire Fighting Systems

Fi Fi Hydrants/Manifolds White system Hydrants and Educators x3

Starboard AftPort Frwd

Identical Port- side