fire protection design for structural steel cable
TRANSCRIPT
J U L Y 2 0 0 8
F I R E P R O T E C T I O N D E S I G N F O R S T R U C T U R A L S T E E L
C A B L E E N C L O S U R E & S E L F - S U P P O R T I N G D U C T
Screws at
190mm centres
steel anglefixed to concreteat 300mm centresSelf-tappingscrews at285mm centres
ERMICULUX® is a low density lightweightnon-combustible board made from a blend ofvermiculite and reinforced with selected
inorganic fibres and fillers. It is formulated and speciallydesigned to provide fire protection to structural steel.VERMICULUX® boards can provide up to 240 minutes of fireresistance in accordance with the criteria of BS476: Part 21: 1987;depending on the thickness of material used and the dimensions of thebeam or column being protected.VERMICULUX® boards are off-white in colour with a sanded finish on bothfaces. They can be left undecorated or easily painted.VERMICULUX® boards are resistant to moisture, will not disintegrate, warp or swell and canbe installed at any time during the building programme, even before external walls have beencompleted and the building made weathertight.VERMICULUX® boards are easy to work using normal woodworkingtools and are supplied with two rebated edges to allow cross joints to bemade without the noggings, cover strips or adhesives.
Fixed by edge screwing boards together, VERMICULUX® boards are fastand economic to install. It is also suitable for the protection of cast-ironcolumns and beams, and construction of ducts and services enclosures.
Typical examples of beamand column claddingsusing VERMICULUX® board
( T E C H N I C A L P R O P E R T I E S )( T E C H N I C A L P R O P E R T I E S )All VERMICULUX® board sizes are based on metric
equivalents of imperial dimensions rounded to the nearest
5mm. Standard sizes and board tolerances are outlined below.
Non-standard sizes sometimes are available upon request.
20mm, 25mm, 30mm, 35mm, 40mm, 45mm,
THICKNESS 50mm, 55mm and 60mm
LENGTH x WIDTH 1220mm x 610mm or 1220mm x 1220mm
TOLERANCES Thickness: +0mm to -0.8mm
Length: +0mm to -1.5mm
Width: +0mm to -1.5mm
ALKALINITY 7~10pH
NOMINAL DENSITY (dry) 500kg/m3
NOMINAL WEIGHT 20mm: 10.3kg/m2
(at ambient conditions and EMC) 25mm: 12.9kg/m2
30mm: 15.5kg/m2
35mm: 18.1kg/m2
40mm: 20.6kg/m2
45mm: 23.2kg/m2
50mm: 25.8kg/m2
55mm: 28.4kg/m2
60mm: 30.9kg/m2
FLEXURAL STRENGTH, Frupture (average, dry) 2.0N/mm2
MODULUS OF ELASTICITY, E (average, dry) 1.4GN/m2
Non-combustible in accordance with
COMBUSTIBILITY the criteria of BS 476: Part 4: 1984.
Class 1 (in accordance with
SURFACE SPREAD OF FLAME the criteria of BS 476: Part 7: 1987)
Class 0 (as defined in the appropriate
BUILDING REGULATIONS CLASSIFICATION Building Regulations)
NOMINAL MOISTURE CONTENT (air dried) 3%
MOISTURE MOVEMENT
(35% to 85% RH at 20OC, ambient to saturated) ≤0.1%
THERMAL CONDUCTIVITY (approximate at 20OC) 0.13W/mK
COEFFICIENT Of THERMAL EXPANSION
(20OC to 100OC per m/mK) 7.5 x 10-8
all figures are approximately based on average standard production values. If a particular property is important, please CONTACT Intumex AsiaPacific TO OBTAIN THE RELEVANT INFORMATION. a Material Safety Data Sheet IS ALSO AVAILABLE FOR REQUEST.
Encasement
(A)
Circular
hollow
section
(A)
4 sides (πD)
4 sides (2D + 2B) 3 sides (2D + 2B) 3 sides (2d + B) 2 sides (D + B) 1 side (B)
B
D
D
d
( S T r u c t u r a l s t e e l( S T r u c t u r a l s t e e lD E S I G N C O N S I D E R A T I O N )D E S I G N C O N S I D E R A T I O N )
Specifications of
Steelwork Section Factor
The Hp/A (Heated perimeter/Area) is a measure of the
rate at which a specific steel section will heat up when
exposed to fire.
The higher its value, the greater the thickness of fire
protection is required.
Hp/A = Rectangular perimeter of exposed steelwork (m)
(m-1) Cross-sectional area of the steel section (m-2)
Calculation of Hp/A factors
1) Find the actual depth (D) and width (B) in metres of
the steel section from supplier’s literature, or site
measurements.
2) Refer to T a b l e 1 for the extent of exposure, and
calculate Hp.
3) Find the cross-sectional area A in square metres of
the section from supplier’s literature, or site
measurements. For partial exposed members the A
value is still the total cross-sectional area.
4) Divide Hp by A to give Hp/A in m-1. Please refer to
supplier’s literature book for Hp/A values.
For partial exposed members, the value is still the total cross-sectional area.
An example for universal beam, exposed on 3 sides:
Serial size = 475mm x 152mm x 82kg/m
Actual size (D x B) = 465.1mm x 153.5mm
Hp (2D + B) = (2 x 465.1)mm + 153.5mm = 1083.7mm = 1.0837m
A = 104.5cm2 = 0.01045m2
Hp/A = 1.0837m / 0.01045m2 = 103.7m-1 = 104m-1
( S T r u c t u r a l s t e e l D E S I G N C O N S I D E R A T I O N )( S T r u c t u r a l s t e e l D E S I G N C O N S I D E R A T I O N )
260 260 260 260 260 260 260
250 ––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––250
240 –––––––––––––––––––––––––––––––––––––––35mm–––––––55mm ––––––––––––––––240
230 –––––––––––––––––––––––––––25mm ––––––––––––––––––––––––––––––––––––––––230
220 ––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––220
210–––––––––––––––––––––––––––––––––––––––––––––––––––50mm ––––––––––––––––210
200 ––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––200
190 –––––––––––––––––––––––––––––––––––––––30mm ––––––––––––––––––––––––––––190
180 ––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––180
170–––––––––––––––––––––––––––––––––––––––––––––––––––45mm ––––––––––––––––170
160 ––––––––––––––––––––––––––––––––––––––– –––––––––––––––––––––––––––––––– 160
150 ––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––150
140 –––––––––––––––––––––––––––––––––––––––25mm–––––––40mm ––––––––––––––––140
130––––20mm–––––––20mm –––––––––––––––––––––––––––––– –––– ––––––––––––––––130
120 ––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––120
110 ––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––110
100 –––––––––––––––––––––––––––20mm –––––––––––––––––––––––––––––– –––––––––100
090–––––––––––––––––––––––––––––––––––––––––––––––––––30mm–––––––40mm–––––900
080––––––––––––––––––––––––––––––––––––––––––––––––––– –––– ––––––––––––––––800
070–––––––––––––––––––––––––––––––––––––––––––––––––––25mm ––––––––––––––––700
060 –––––––––––––––––––––––––––––––––––––––20mm ––––––– –––– –––––––30mm–––––600
050 ––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––500
040 ––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––400
030–––––––––––––––––––––––––––––––––––––––––––––––––––20mm–––––––25mm–––––300
020 ––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––200
010 ––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––100
30 60 90 120 180 240
PERIOD OF FIRE RESISTANCE (minutes)
VERMICULUX® boards can provide up to 240 minutes of fire resistance period for structural steel in
accordance with the criteria of BS476: Part 21: 1987. The above table is based on critical steel temperature
of 550°C. Please consult Intumex Asia Pacific for other parameters or temperatures.
45mm
55mm
60mm
50mm
35mm
35mm
A/V
(m
-1)
–227–
–215–
–159–
–114–
–202–
–189–
–156–
–128–
–103–
–081–
–061–
–155–
–134–
–115–
–098–
–082–
–067–
–054–
–178–
A
Y X
1)
2)
3)
( S T r u c t u r a l( S T r u c t u r a l s t e e l b e a m )s t e e l b e a m )
Example of a three-sided
structural beam cladding
1) Steel angles are fixed on both sides of the
beam. Take the measurement between
the outside faces of the angles (A).
Measure the depth of the beam (Y) and
add 6mm plus the thickness of the
VERMICULUX® board (X). Cut the
boards, one to dimension A and two
to dimension X.
Fix the two boards using the self-tapping
screws or dry wall screws into the angles.
2) Fix the remaining board between the side
panels with all transverse joints staggered.
3) Repeat the above along the length of the
beam structure.
1)
2)
3)
( S T R U C T U R A L S T E E L C O L U M N )
Example of a four-sided
structural column cladding
1) Measure the column and add 6mm to
each dimension to provide 3mm all-
round clearance.
Add twice the thickness of the
VERMICULUX® board to the web
dimension. Determine the most
economic way to cut the boards, and
cut the board so that the rebate will be at
the transverse joint.
Make up a three-sided box by edge
screwing the VERMICULUX® boards.
2) Remove the rebate from the bottom of all
four sides of the first sections and ensure
that the casing is level and square.
Place the three-sided box in position and
fix the fourth side.
3) Repeat the above steps up to the column,
bearing in mind that the rebates are
reversed on alternate sections.
100mm
( C A B L E S E N C L O S U R E )
100mm
VERMICULUX® boards can provide up to 90 minutes of fire
resistance level (FRL) for cables and services enclosure in
external fire exposure in accordance with the criteria of BS476:
Part 20: 1987 thereby maintaining the functionality of essential
cables in a fire.
FRL30 60 90
minutes minutes minutes
Enclosure ≤100mm x 100mm(1)
size 350mm x 170mm to 760mm x 300mm(2)
Thickness30mm(1) 50mm/2 x 25mm(1) 2 x 35mm(1)
25mm(2) 45mm/20+25mm(2) 2 x 30mm(2)
(1) Type 1 of cables enclosure(2) Type 2 of cables enclosure
Casing
One or two layers of VERMICULUX® board
(see T a b l e 3 for thickness) edge screwed
at 200mm centres.
Cover strips
VERMICULUX® 25mm thick x 125mm
wide, fixed over joints. For single layer duct
constructions, cover strips should be fixed to
the external faces of the top and sides with
the bottom strip inside the duct.
For double layer constructions, board joints
are staggered and cover strips need only to
be fixed to the inside at the bottom of the
duct. Cables should be supported on trays
but these can be omitted if the bottom
internal cover strip has been fixed at
600mm centres.
Supports
M10 threaded rods fixed by means of plugs
into concrete soffit. Tensile stress in rods
should not exceed 6N/mm2.
100mm
100mm
Casing
Two layers of VERMICULUX® board
(see T a b l e 4 for thickness) edge screwed
with 60mm x 5mm woodscrews at 195mm
centres.
Layers offset at circumferential joints to
form 100mm lap; boards screwed together
with 35mm x 4mm, 45mm x 4mm and
50mm x 4mm woodscrews in three rows
100mm apart. The central row is located in
centre of lap, the screws in each row at
150mm centres. Screws must be inserted
from outside of the duct.
Supports
8mm diameter threaded rods and 15mm x
30mm x 15mm x 5 mm steel channel rails at
1220mm centres near circumferential joints.
Filler
Joints and screw heads are filled using
a m i x t u r e o f s o d i u m s i l i c a t e a n d
VERMICULUX® powder.
( S E L F - S U P P O R T I N G D U C T )( S E L F - S U P P O R T I N G D U C T )
FRL60 90 120
minutes minutes minutes
Internal layer
Thickness 2 x 20mm 2 x 25mm30mm,
external layer
25mm
VERMICULUX® boards are suitable for protecting smoke
extraction ducts in buildings where the means of escape could be
severely contaminated with smoke and become impassable.
The boards can provide up to 120 minutes fire resistance level
(FRL) for self-supporting integrity and insulation duct in
accordance with the criteria of BS476: Part 24: 1987.
Maximum duct size is up to 750mm x 300mm.
( W O R K I N G )( W O R K I N G )
General
Use normal woodworking tools.
Cutting
Use a fine-toothed panel saw. For shaped cuts
use a padsaw, keyhole saw or coping saw. Work
with fair face upwards and support the board as
cutting progresses. Quick and easy rough cuts
can be made by scoring thin boards with a
Stanley knife and snapping over a straight edge.
For power sawing use a tungsten carbide or
diamond tipped blade.
Drilling
Use normal low or high-speed drills. Place scrap
board under the drilling location to ensure a
clean hole.
Smoothing
Smooth cut edges with a Surform plane, rasp
or file.
Sanding
Sand with conventional papers. Garnet paper is
best for fine sanding.
( F I X I N G )( F I X I N G )
Refer to the specifications for full recom-
mendations for type, size and spacing of fixings.
All fixings should be rust proof.
Jointing
Board joints should be tight butted. Joints and
screw holes can be filled and sanded to a smooth
flat surface.
If the fire resistant system requires an expansion
or compression movement joint, please consult
Intumex Asia Pacific.
( D E C O R A T I N G )( D E C O R A T I N G )
Painting & Coating
Prime boards before painting. For water-based
paints apply a watered-down first coat; for oil-
based paints use a universal primer; for textured
paints use manufacturer’s recommended sealer.
Alkali-resistant primers are not required.
Where an easily-cleaned finish is required, apply
Steridex or similar liquid plastic coating.
Vapour transmission can be reduced by
applying a priming coat followed by two
undiluted coats of chlorinated rubber paint,
epoxy resin paint, polyurethane or liquid plastic.
Rendering
Resin-based textured finishes such as Highbuild
and Cullaplast can be applied after first sealing
the boards with Sandtex stabilising solution.
Cement-based rendering should only be applied
over expanded metal lathing.
Papering
Boards should be well sized before hanging
wallpaper. All types of paper and vinyl can be
used. Vinyl wall coverings can be easily stripped
from the boards for re-decoration.
Plastering
Boards may be plastered using:
1) Snowplast, applied after first sealing boards
with two coats of Cemprover PVA.
2) Artex, applied as a smooth coating direct to
the board.
3) Carlite Browning HSB (undercoat plaster for
high suction substrates) followed by Carlite
Finish.
( m a i n t e n a n c e & c l e a n i n g )( m a i n t e n a n c e & c l e a n i n g )
If VERMICULUX® boards are broken or cracked, they should be replaced rather than repaired in order to
ensure fire performance is maintained.
Undecorated boards do not require any special cleaning. Where cleaning is necessary for cosmetic
purposes, they may be vacuumed, or sanded to remove marks. Although moisture will not harm the boards,
excessive use of water in cleaning is not recommended as the boards will take time to dry out.
Decorated boards should be re-decorated as necessary to retain appearance, following the
recommendations of the manufacturer of the decorative system.
( H A N D L I N G & S T( H A N D L I N G & S T O R A G E )O R A G E )
Carry VERMICULUX® boards on edge and do not drop on their corners or onto trestles. All boards should
be stored under cover on a flat base, clear of the ground.
If stored in the open, the stack should be fully protected from the weather. If stored on racks or dunnage,
boards should be fully supported across their width at not more than 1000mm centres.
( H E A L( H E A L T H & S A F E T Y )T H & S A F E T Y )
VERMICULUX® boards will support their own weight, but are non-loadbearing. Horizontal boards must
not be walked on as they are not designed to take additional loads between supports. If there is a risk of this
occurring, warning notice should be displayed. Fixers must ensure that they work from adequate and safe
platforms where necessary.
VERMICULUX® products are formulated without inorganic fibres and no special precautions are necessary
in handling or working. However, when using power saws or sanders in a confined space or working with
materials which can create dust, dust extraction equipment is recommended and appropriate dust masks
and other P.P.E. should be worn at all times.
When machining, airborne dust may be released. Avoid contact with skin and eyes. Use dust extraction
equipment. Respect regulatory occupational exposure limits for total inhalable and respirable dust.
For more information, please contact your nearest Intumex Asia Pacific office for the Material
Safety Data Sheet.
Intumex Asia Pacific
HONG KONGRoom 1011, C.C. Wu Building
302-308 Hennessy RoadWanchai
Tel: +852 2895 0265Fax: +852 2576 0216
AUSTRALIAUnit 1, 175 Briens RoadNorthmead, NSW 2152Tel: +61 (2) 9683 2872Fax: +61 (2) 9630 0258
SINGAPORE10 Science Park Road
#03-14 The AlphaSingapore Science Park II
Singapore 117684Tel: +65 6292 7888Fax: +65 6294 2576
Email: [email protected]
www.intumex-ap.com
Your local supplier