fire protection - riser
TRANSCRIPT
-
7/29/2019 Fire Protection - Riser
1/12
FIRE PROTECTION: RISERPrepared by: Nur Afiqah binti Mohd Bashir
Commonly known asstandpipes system for fireprotection.
It is designed to provide rapidaccess to water in the event
that a fire breaks out.Also bundled with sprinklersystems which providingautomatic or manual sprinklers.
-
7/29/2019 Fire Protection - Riser
2/12
RISER CONTD
This system also installed in high rise or large
buildings.
Difficult to get pressure, especially on high floors,
which makes it harder to pump water quickly
enough to put the fire out.
There are two types of riser systems which are dry
riser and wet riser systems.
-
7/29/2019 Fire Protection - Riser
3/12
DRY RISER SYSTEM
A dry riser does not normallycontain water, but is charged with
water by the fire brigade during
an outbreak of fire.
It is suitable for building between20mm-60mm.
Are usually fitted into a staircase
or similarly suitable location.
It must be installed within 18m of
fire engine access to the inlet box
and installed in a fire proof
enclosure.
-
7/29/2019 Fire Protection - Riser
4/12
DRY RISER SYSTEMCONTD
Comprises a riser pipe withlanding valves at each floor which
canvas hose with nozzles.
Breeching inlets into which the
firemen pump water are provided
at ground level and are connected
to the bottom of the dry risers.
A dry pipe system operates more
slowly and more expensive to
install and maintains than a wet
pipe type.
-
7/29/2019 Fire Protection - Riser
5/12
Components of Dryriser system
1. Fire Breeching point Should be located on the
external wall of the building at760 mm above ground level and< 12 m from the riser.
The inlets should be within 18 m
of an access road. 100 mm dia. dry riser 2 inlets
150 mm dia. dry riser 4 inlets
2. Dry riser (stand-pipe)
The fire brigade will connect riser
to the water supply The inlets at the ground level and
the pumps force water from themain into riser
Minimum diameter is 100 mm.
2) Dry riser
1) Fire Breechingpoint
-
7/29/2019 Fire Protection - Riser
6/12
Components of Dryriser system contd
3. Landing Valve Usually install at every
storey.
Space from floor not less
than 750mm Installed with metal box or
cabinet to avoid damage.
4. Automatic air valve
An automatic air valve atthe top of the riser opensto allow air in the pipe toescape, but closes whenthe pipe is full of water.
3) Landing Valve
4) Automatic air valve
-
7/29/2019 Fire Protection - Riser
7/12
Dry riser inlet box
Horizontal landing valve
Dry Riser Outlet Boxes
Twin Inlet Breeching
Four-way Inlet Breeching
-
7/29/2019 Fire Protection - Riser
8/12
Operation of Dry Riser System
Water is enteredfrom pillar hydrantby fire bridge when
fire occur
Outlet pump willconnected at Dry
riser inlet
Water will enterfor give the
pressure andremove pressure
air upside
Automatically,water valve located at thetop will open and remove
the air, but will closeagain once the
water has tomeet the dry riser
Firebridge will connec
t them inthe landing valve
and open it
Thensprayed towards
the firewith a pressurizedwater conditions
-
7/29/2019 Fire Protection - Riser
9/12
Components of Wet risersystem
1. Fire brigade breeching point/Hydrant Minimal diameter is 65mm.
Fitted with a coupling compatible withthe local fire brigade. (different hoseconnections)
2. Water Supply & Break Tank Supplied from break tank - >11.5 m,
water main - >27 litre/s
150 mm diameter, 64 mm int. dia.instantaneous male couplings(connection to pump) fire brigade
breeching inlet at street level.
3. Overflow Pipe capable of developing 375 litre/s to
the open air should be connected tothe break tank.
1) Fire brigade breeching
2) Water
Supply &Break Tank
OverflowPipe
-
7/29/2019 Fire Protection - Riser
10/12
4. Booster Pump seti. Jockey Pump
When the system pressure drop(150psi-230psi) to a preset level,jockey pump starts and charges
the system back to normalpressure
i. Stand-by Pump
Standby pump is startedautomatically when the duty
pump fails. Acts as supportpump.
ii. Duty pump
The duty pump starts when thepressure in the fire sprinkler
system drops below a threshold.
Components of Wet risersystem contd
4) Booster
Pump set
-
7/29/2019 Fire Protection - Riser
11/12
5. Pipe work & Valves The control valves are used in
combination with the pipe work
to control a direct the flow of
water.6. Riser (stand-pipe)
Have same function with dry
riser system
7. Landing valve
Landing valve from floor level
should not less than 750 mm
Its dia. 64 mm (minimum)
Components of Wet risersystem contd
5) Pipe work
& Valves
6) Riser
(stand-pipe)
7) Landing
valves
-
7/29/2019 Fire Protection - Riser
12/12
Operation of wet riser system
The drop in waterpressure is detectedby a pressure switch
which in turn startsthe booster pumps
Connectrubberpipe at
hosecoupling
Pump willbe
functioned
whenswitch is on
Openlanding
valve
At the bottom landing
valve,it has orifice platefunctioned as to limitpressure at landing
valve for high building,so it can be limit tomaximum, 520kPa
Water fromthe tank fill inthe riser and
flow torubber pipe.
Excessive water
will flow to drainpipe and it willflow back to thetank, then the
processrepeated
Close thelanding valve
after used.