fire requirements for foam plastic insulation and wrbs in exterior walls
DESCRIPTION
Fire Requirements For Foam Plastic Insulation and WRBs in Exterior Walls. Presented to By Jesse J. Beitel July 31, 2012. Learning Objectives. Code requirements for foam plastic in exterior walls History of NFPA 285 Fire test Other Fire tests required - PowerPoint PPT PresentationTRANSCRIPT
Fire Requirements For Foam Plastic Insulation and WRBs in
Exterior WallsPresented to
ByJesse J. Beitel
July 31, 2012
Learning Objectives
Code requirements for foam plastic in exterior walls
History of NFPA 285 Fire test Other Fire tests required Code requirements for Water-Resistive
Barriers Applicability and Use of NFPA 285
3
Continuous Insulation (CI)Concept
ASHRE 90.1 – Commercial IECC (Energy Code) – Commercial &
Residential Concept – Wrap building w/ insulation
outboard of studs Helps with thermal conduction, dew point,
etc. Creates high R-value walls
4
Insulation In Exterior Walls Location in walls – CI / Cavity / Both Can use noncombustible or combustible non-foam plastic
insulation Fiberglass, Mineral wool Cellulose, others Minimal fire requirements
Can use combustible foam plastic insulation Many types – XPS, EPS, Polyiso, SPF, etc. Characteristics different Regulated the same Fire requirements for walls and foam plastics vary based on Type
of Construction, etc.
5
Fire Requirements Vary
One & Two Family Dwellings – Exterior walls - IRC regulates
Type V – Exterior walls - combustible – IBC regulates
Types I, II, III, IV – Exterior walls to be noncombustible unless allowed – IBC regulates
6
IRC (2012) Fire Requirements
Non-foam plastic insulation Noncombustible or if combustible then FSI ≤25 &
SDI ≤450 Foam plastic insulation
Labeled FSI ≤75 & SDI ≤450 Protected by 15-minute Thermal Barrier Gable ends in attics – Protect with ignition barrier
Fire Resistance of exterior walls
7
IBC (2012) – Type V Fire Requirements
Non-foam plastic insulation Noncombustible or if combustible then FSI ≤25 &
SDI ≤450 Foam plastic insulation (Chapter 26)
Labeled FSI ≤75 & SDI ≤450 Protected by 15-minute Thermal Barrier Gable ends in attics – Protect with ignition barrier
Fire Resistance of exterior walls
8
IBC (2012) - Fire Requirements For Type I, II, III or IV – Part 1
Noncombustible Insulation - OK Fiberglass Mineral wool
Non-foam plastic combustible insulation Cellulose Insulation, etc. FSI ≤25 & SDI ≤450
Fire Resistance of exterior walls
9
IBC - Fire Requirements For Type I, II, III or IV – Part 2
Foam Plastic Insulation Regulated by §2603.5 Applies to exterior walls of Type I – IV
construction Applies to buildings of any height Exceptions:
• Type V buildings• Cold Storage – 1 story & meets other reqm’ts
10
IBC - Fire Requirements For Type I, II, III or IV – Foam Plastic
Meet the requirements of NFPA 285 For each combustible component - FSI ≤25 &
SDI ≤450 (ASTM E84) Maintain fire resistance rating (ASTM E119) Foam separated from interior of building by a
Thermal Barrier Gable ends in attics – Protect with ignition barrier
Limits on amount of foam (btu/ft2) (mJ/m2) No ignition when tested via NFPA 268
(Radiant heat exposure test)
11
History - Fire Test/Code Development
In mid 1970’s – use of foam plastic on or in noncombustible exterior walls was proposed. EIFS & Steel/Foam/Steel Panels
Problems with use: Exterior walls of Type I, II, III or IV Construction
must be noncombustible construction. Foam plastic is combustible Issues raised over potential for vertical and
horizontal fire spread due to the combustible foam plastic insulation
History (continued)
SPI began work in Codes and testing. Discussions w/ Code & Fire Officials. Drafting of Code language. Testing program
Testing was to determine efficacy of proposed wall systems to resist flame spread.
13
Multi-Story Fire Test
Can the wall covering, insulation & assembly resist: Flame propagation over face of the wall covering Vertical flame propagation within the combustible
core or components Flame propagation over interior surface from one
floor to the next Lateral Flame propagation to adjacent
compartments Does not address floor-line joint per se.
15
Fire Test/Code Development
Test program completed in late 1980 Code change to Plastics Section adopted in
1988 UBC Versions adopted by NBC and SBC Full-scale test was also adopted as UBC 17-6.
Used by all ESs. In 1994 edition of UBC – reorganization moved
plastics to Chapter 26 and test method became UBC 26-4.
16
Fire Test/Code Development (Cont’d)
In early 1990’s a “reduced-scale” fire test was developed.
New test adopted as UBC 26-9 in 1997 edition. Test submitted to NFPA Committee on Fire Tests and
it was adopted as NFPA 285 in 1998. NFPA 285 “Standard Fire Test Method for Evaluation
of Fire Propagation Characteristics of Exterior Non-load-bearing Wall Assemblies Containing Combustible Components”
ICC IBC specifies NFPA 285 Code requirements basically the same since 1988
UBC
18
IBC - Fire Requirements For Type I, II, III or IV – Foam Plastic
Meet the requirements of NFPA 285 For each combustible component - FSI ≤25 &
SDI ≤450 (ASTM E84) Maintain fire resistance rating (ASTM E119) Foam separated from interior of building by a
Thermal Barrier Gable ends in attics – Protect with ignition barrier
Limits on amount of foam (Btu/ft2) (MJ/m2) No ignition when tested via NFPA 268
(Radiant heat exposure test)
21
Thermal Barrier Requirement Code requires that foam plastic must be
separated from the interior of the building by a 15-minute thermal barrier.
Applies to any foam plastic application. Thermal barrier is typically 0.5 in. (12.7 mm)
thick gypsum wallboard or meets NFPA 275. Thermal barrier retards heat transmission to
the foam and delays its ignition.
22
Ignition Barrier Requirement
Applies to foam plastic insulation in attics & crawl spaces
Only where entrance is made to service utilities
Prescriptive ignition barriers provided in Code: wood, mineral fiber, gypsum wallboard or steel
Not a thermal barrier Alternative assemblies by special testing
23
NFPA 259Potential Heat Test
Code requires that the “potential heat” (calculated on areal basis) of the foam plastic not exceed that which is tested via NFPA 285
Uses NFPA 259 – Measures amount of heat released when burned in pure O2
Data from test expressed in Btu/lb (MJ/kg) Convert this to Btu/ft2 (MJ/m2) using thickness and
density of foam plastic. Allows calculation for different densities/thickness
combinations
WRB Definitions
My definition = Weather-resistive barriers include: Air barriers Vapor barriers Water barriers ???? Barriers
IBC: Water-resistive barrier
WRB Code Requirement2012 IBC
1403.5 Vertical and lateral flamepropagation. Exterior walls on buildings ofType I, II, III or IV construction that aregreater than 40 feet (12 192 mm) in height above grade plane and contain combustiblewater-resistive barrier shall be tested inaccordance with and comply with theacceptance criteria of NFPA 285.
Exterior veneer
Cavi
ty a
ir sp
ace
Interior wall membrane
Steel stud
Sheathing
Foam insulation
WRB
Insulation instud cavity
Potential Variations of Wall Systems
How Do WRBs Meet NFPA 285?
There is no one test or test assembly to qualify a WRB for use in all assemblies
Perform NFPA 285 test – WRB is one of several materials in assembly
Limited engineering analysis based on NFPA 285 tests in conjunction w/ small-scale tests.
Engineering Analysis
Use WRB X in a successful NFPA 285 test Develop fire performance parameters for
WRB X (ASTM E1354 Cone Calorimeter) Develop fire performance parameters for
WRB Y Compare fire performance parameters – if
same or better, then maybe substitute Y for X in tested assembly
30
Applicability of NFPA 285
285 is a test of a complete wall assembly 285 test results apply only to the tested
construction – similar to ASTM E119 Substitutions of one material for another
can cause different test results Addition of combustibles (insulation,
WRBs, etc.) can cause different test results
31
Applicability of NFPA 285 (Continued)
Changes in configurations (air gaps, attachment systems, etc.) can cause different results
Wall systems made of a number of previously NFPA 285 tested materials does not ensure a successful NFPA 285 test
Tests are required for many various veneers and other combustible wall components – insulation, WRBs
Applicability of NFPA 285 WRBs
Use of WRBs can cause different results
Substitution of WRBs can cause different results
Even tested WRBs cannot necessarily be applied to other foams, veneers, etc.
Same issues as with other NFPA 285 tests – materials, configuration., etc.
33
Summary
Insulation in exterior walls is regulated. Amount of regulation / tests for exterior
insulation and/or insulated exterior walls depends on: Code Type of Construction Type of insulation WRBs
34
Summary - Continued
NFPA 285 provides a determination of vertical fire performance of exterior wall assemblies.
NFPA 285 tested systems reduce the potential for vertical flame spread by exterior walls.
NFPA 285 data/results must be used in an appropriate manner.
Thank Youand
Questions?
Jesse J. BeitelSenior Scientist/PrincipalHughes Associates, Inc.