INTRODUCTION Model ADBX-11 The SIEMENS Model ADBX-11 Audible Base consists of a standard Series 11 base combined with an audible device. All field wiring terminates at two four- position terminal blocks located on the back of the unit. The ADBX-11 is used with FP-11 and FPT-11 detectors, P/N 315-095921, and FS-DP, FS-DPT, and FS-DT detectors, P/N 315-699481. The ADBX-11 operates as described below (Refer to Figures 1, 2, 3, 4, and 5). The ADBX-11 can generate either steady or temporal tone with the insertion of a jumper at the terminal block. Refer to Tone Selection on page 11. APPLICATION NOTE The ADBX-11 is a UL268 listed smoke detector supplementary device which combines detector base and audible device functions. It meets or exceeds the 85 dB at 10 foot audibility requirement for smoke alarms as specified in UL217, Single and Multiple Station Smoke Alarms and NFPA 72 for sleeping areas. When used in conjunction with listed, compatible Siemens equipment, the ADBX-11 may be used in lieu of single/multiple station smoke alarms to achieve enhanced, system-level functionality. Typical applications are sleeping rooms in hotels, guest suites, dormitories, day-care, and residential board and care facilities as designated in NFPA 72. ELECTRICAL RATINGS AND CONSTRAINTS Model ADBX-11 Voltage Rating: 17-31 VDC Current: Supervisory 0A Alarm 24mA at 25 VDC Constraints: 1. The maximum number of ADBX-11s per an MMB-1/2, SMB-1/2, or CSM-4 notification appliance circuit is 60, with no other devices connected, and with the maximum loop current available. Note: The number of ADBX-11s cannot exceed the maximum current available to the loop. See the MXL Manual, P/N 315-092036, or the MXL-IQ Manual, P/N 315-093624, for the compatibility details of ALD and notification appliance circuit wiring. P/N 315-096228-7 Fire Safety Installation Instructions Model ADBX-11 Audible Base Siemens Building Technologies, Inc. 8 Fernwood Road Florham Park, New Jersey 07932 Siemens Building Technologies, Ltd. 2 Kenview Boulevard Brampton, Ontario L6T 5E4 CN

Upload: hoanganh

Post on 26-Jul-2018

238 views

Category:

Documents


1 download

TRANSCRIPT

Page 1: Fire Safety - Fire Alarm Resourcesfirealarmresources.com/wp-content/uploads/2015/05/Adbx-11.pdf · UL217, Single and Multiple ... Fire Safety Installation Instructions ... as referred

INTRODUCTION

Model ADBX-11The SIEMENS Model ADBX-11 Audible Base consists of a standard Series 11base combined with an audible device. All field wiring terminates at two four-position terminal blocks located on the back of the unit. The ADBX-11 is usedwith FP-11 and FPT-11 detectors, P/N 315-095921, and FS-DP, FS-DPT, andFS-DT detectors, P/N 315-699481. The ADBX-11 operates as described below(Refer to Figures 1, 2, 3, 4, and 5).

The ADBX-11 can generate either steady or temporal tone with the insertion ofa jumper at the terminal block. Refer to Tone Selection on page 11.

APPLICATION NOTEThe ADBX-11 is a UL268 listed smoke detector supplementary device whichcombines detector base and audible device functions. It meets or exceeds the85 dB at 10 foot audibility requirement for smoke alarms as specified inUL217, Single and Multiple Station Smoke Alarms and NFPA 72 for sleepingareas. When used in conjunction with listed, compatible Siemens equipment,the ADBX-11 may be used in lieu of single/multiple station smoke alarms toachieve enhanced, system-level functionality. Typical applications aresleeping rooms in hotels, guest suites, dormitories, day-care, and residentialboard and care facilities as designated in NFPA 72.

ELECTRICAL RATINGS AND CONSTRAINTS

Model ADBX-11Voltage Rating: 17-31 VDCCurrent: Supervisory � 0A

Alarm � 24mA at 25 VDC

Constraints:1. The maximum number of ADBX-11s per an MMB-1/2, SMB-1/2, or

CSM-4 notification appliance circuit is 60, with no other devicesconnected, and with the maximum loop current available.

Note: The number of ADBX-11s cannot exceed the maximum currentavailable to the loop. See the MXL Manual, P/N 315-092036,or the MXL-IQ Manual, P/N 315-093624, for the compatibilitydetails of ALD and notification appliance circuit wiring.

P/N 315-096228-7

Fire Safety

Installation InstructionsModel ADBX-11Audible Base

Siemens Building Technologies, Inc.8 Fernwood RoadFlorham Park, New Jersey 07932

Siemens Building Technologies, Ltd.2 Kenview BoulevardBrampton, Ontario L6T 5E4 CN

Page 2: Fire Safety - Fire Alarm Resourcesfirealarmresources.com/wp-content/uploads/2015/05/Adbx-11.pdf · UL217, Single and Multiple ... Fire Safety Installation Instructions ... as referred

2

Figure 1Installation/Wiring Diagram for ADBX-11 Powered

by Auxiliary Power Supply with Battery Backup

* 3.6K, 1/4W RESISTOR, MODEL EL-31.

** POLARITY SHOWN IN NORMAL SUPERVISORY STATE AT TERMINALS 1 AND 2 OF ADBX-11. PROPERPOLARITY MUST BE MAINTAINED OR AUDIBLE BASE WILL NOT OPERATE PROPERLY. EACH AUDIBLEBASE MUST BE TESTED TO VERIFY OPERATION.

† USE A MODEL MPX-2 MOUNTING PLATE TO MOUNT A TRI-2R, TRI-B6 OR TRI-60R IN A SYSTEM 3ENCLOSURE.

†† TONE SELECTION (SEE PAGE 11).

‡ USE A MODEL MPI-2 MOUNTING PLATE TO MOUNT A TRI-R OR FS-TRI-R IN A SYSTEM 3 ENCLOSURE.

‡‡ FOR MORE DETAILED WIRING INFORMATION, REFER TO THE FOLLOWING INSTALLATIONINSTRUCTIONS, AS APPLICABLE; TRI-2R, P/N 315-090556; TRI-B6R, P/N 315-093315; TRI-60R,P/N 315-092329; TRI-R, P/N 315-096242; OR FS-TRI-R, P/N 315-699484.

Page 3: Fire Safety - Fire Alarm Resourcesfirealarmresources.com/wp-content/uploads/2015/05/Adbx-11.pdf · UL217, Single and Multiple ... Fire Safety Installation Instructions ... as referred

3

Page 4: Fire Safety - Fire Alarm Resourcesfirealarmresources.com/wp-content/uploads/2015/05/Adbx-11.pdf · UL217, Single and Multiple ... Fire Safety Installation Instructions ... as referred

4

Figure 2Installation/Wiring Diagram for ADBX-11 Audibles Powered

by Auxiliary Power Supply (No Battery Backup)

* 3.6K, 1/4W RESISTOR, MODEL EL-31.

** POLARITY SHOWN IN NORMALSUPERVISORY STATE ATTERMINALS 1 AND 2 OF ADBX-11.PROPER POLARITY MUST BEMAINTAINED OR AUDIBLE BASEWILL NOT OPERATE PROPERLY.EACH AUDIBLE BASE MUST BETESTED TO VERIFY OPERATION.

† TONE SELECTION (SEE PAGE 11).

Page 5: Fire Safety - Fire Alarm Resourcesfirealarmresources.com/wp-content/uploads/2015/05/Adbx-11.pdf · UL217, Single and Multiple ... Fire Safety Installation Instructions ... as referred

5

NOTE:FOR MOUNTING A TRI RELAY MODULE IN A SYSTEM 3ENCLOSURE: USE A MODEL MPX-2 MOUNTING PLATETO MOUNT A TRI-2R, TRI-B6R, OR TRI-60R, OR USE AMODEL MPI-2 MOUNTING PLATE TO MOUNT A TRI-R ORFS-TRI-R.

FOR MORE DETAILED WIRING INFORMATION, REFERTO THE FOLLOWING INSTALLATION INSTRUCTIONS, ASAPPLICABLE: TRI-2R, P/N 315-090556; TRI-B6R, P/N 315-093315; TRI-60R, P/N 315-092329; TRI-R, P/N 315-096242,OR FS-TRI-R, P/N 315-699484.

Page 6: Fire Safety - Fire Alarm Resourcesfirealarmresources.com/wp-content/uploads/2015/05/Adbx-11.pdf · UL217, Single and Multiple ... Fire Safety Installation Instructions ... as referred

6

Fig

ure

3In

stal

lati

on

/Wir

ing

Dia

gra

m f

or

AD

BX

-11

Au

dib

les

Po

wer

ed b

y S

yste

m M

XL

/MX

L-I

Q M

ain

Bo

ard

Page 7: Fire Safety - Fire Alarm Resourcesfirealarmresources.com/wp-content/uploads/2015/05/Adbx-11.pdf · UL217, Single and Multiple ... Fire Safety Installation Instructions ... as referred

7

Fig

ure

4In

stal

lati

on

/Wir

ing

Dia

gra

m f

or

AD

BX

-11

Au

dib

les

Po

wer

ed b

y S

yste

m M

XL

/MX

L-I

Q M

od

ule

s

Make

this

connect

ion

to a

ny

of

the f

ollo

win

gte

rmin

atio

ns:

���

��

��

��

��

�����

������

���

����

����

�����

�����

���

������

����������������

������������������

���

��

������

�����������������

������������������

���

��

�����

��������� ���

������� ���

���

���

��������������

������ �

������

��������

��������������

�����

������������

����

��� ��������

���

���

!�����������

���

������������

���

���

�� ! �������

���

��� �

�� ���������

6 5

1b

1a

87

65

12

34

87

65

12

34

FR

OM

ALD

LO

OP

OF

SY

ST

EM

MX

L/M

XL-I

QC

ON

TR

OL

PA

NE

L

AD

BX

-11

AU

DIB

LE

SIG

NA

LC

IRC

UIT

SH

OW

NS

TY

LE

Y(C

LA

SS

B)

MA

YB

ES

TY

LE

Z(C

LA

SS

A)

TO

NE

XT

AD

BX

-11,

DB

-11,D

B-3

S,

OR

DB

-X3R

S

EO

LD

EV

ICE

2.2

K,1/2

WP

/N140-8

20380

TO

NE

SE

LE

CT

ION

(SE

EP

AG

E11)

*

-

-

--

+

+

++

**

**

**N

AC

CIR

CU

ITS

PO

LA

RIT

YS

HO

WN

INS

UP

ER

VIS

OR

YS

TA

TE

.P

RO

PE

RP

OL

AR

ITY

MU

ST

BE

MA

INTA

INE

DO

RA

UD

IBL

EB

AS

EO

PE

RA

TE

PR

OP

ER

LY.

EA

CH

AU

DIB

LE

BA

SE

MU

ST

BE

TE

ST

ED

TO

VE

RIF

YO

PE

RA

TIO

N.

WIL

LN

OT

Page 8: Fire Safety - Fire Alarm Resourcesfirealarmresources.com/wp-content/uploads/2015/05/Adbx-11.pdf · UL217, Single and Multiple ... Fire Safety Installation Instructions ... as referred

8

+

+

-

-

POWERLIMITED

STYLE Y

15K, 1/2W, 5%EOL RESISTORP/N 140-820400

TO NEXT ADBX-11,DB-11,DB-3S, OR

DB-X3RS

SUPERVISED STROBE ACTIVATIONSUPV: 9VDC, .5mA

ACTIVATED: 24VDC, 1.5A MAXPOLARITY SHOWN IN SUPV. CONDITION

DC INPUT RATED24 - 27.3 VDC FWR

SUPV: 12mAACTIVATED: 1.5A MAX

24-27.3 VDC, 18mA MAX9 VDC, 0.5mA24 VDC, 1.5A, POWER LIMITED

+

+

+

+ --

-

-

ICP-B6

PROGRAMPLUG

TB2

TB1

6

6

5

5

4

4

3

3

2

2

1

1

+ +- -

ANALOGLOOP

CONNECTION

SUPERVISED

MODULE INPUTSUPPLY FROM

PS-35, PSR-1,ORUL LISTED

POWER SUPPLY

ELECTRICAL:

INPUT DC SUPPLY:SUPERVISORY OUTPUT:

ACTIVATED:

JP2

JP1

**

*

*

EARTH

SHIELD

1

2

3

4

8

7

6

5

ADBX-11

1

2

3

4

8

7

6

5

ADBX-11

5 6

1a 1b

Figure 5Using ICP-B6 to Supervise Power to ADBX-11

Page 9: Fire Safety - Fire Alarm Resourcesfirealarmresources.com/wp-content/uploads/2015/05/Adbx-11.pdf · UL217, Single and Multiple ... Fire Safety Installation Instructions ... as referred

9

STYLE Z

15K, 1/2W, 5% EOL RESISTORP/N 140-820400

TO NEXT ADBX-11,DB-11,DB-3S, OR

DB-X3RS

NOTE: All wiring must comply with national and local codes.

+

+

-

ICP-B6

PROGRAMPLUG

TB1 654321

+ +- -

-

TONE SELECTION(SEE PAGE 11)

JP2

*

**

**

*

*

JP1

+ + --TB2 6 5 4 3 2 1

EARTH

SHIELD

1

2

3

4

8

7

6

5

ADBX-11

1

2

3

4

8

7

6

5

ADBX-11

5 6

1a 1b

NAC CIRCUITSPOLARITY SHOWN INSUPERVISORY STATE.PROPER POLARITY MUSTBE MAINTAINED ORAUDIBLE BASEOPERATE PROPERLY.

WILL NOT

Page 10: Fire Safety - Fire Alarm Resourcesfirealarmresources.com/wp-content/uploads/2015/05/Adbx-11.pdf · UL217, Single and Multiple ... Fire Safety Installation Instructions ... as referred

10

2. Maximum line resistance permitted (both wires), not including the endof line resistor, is 3 ohms. A minimum of 14 AWG wire must be used.

3. T-tapping of the notification appliance circuit (Figures 1, 2, 3, 4, and 5)is not allowed.

4. If the ADBX-11 is powered by System MXL/MXL-IQ (Figures 3, 4, and5) or FS-100 (Figure 6), the notification appliance circuits supply 1.5A. Ifmore than 1.5A is required, use the configuration in Figure 1 or Figure 2for auxiliary power. See Note on page 1.

5. Connect terminal 6 of the PS-35 (Figures 1 and 2) to the minus DC side ofthe MXL/MXL-IQ main power supply for proper ground fault supervision.

Note: For additional information on the modules used in anindividual system, refer to the Installation Instructions forthat particular module or contact your authorized SiemensBuilding Technologies, Inc. representative.

DETECTOR PLACEMENT

The FP-11, FPT-11, FS-DP, FS-DT and FS-DPT detectors can be used withthe ADBX-11 Detector Base. Refer to the FP-11/FPT-11 InstallationInstructions, P/N 315-095921, or the FS-DP/FS-DT/FS-DPT InstallationInstructions, P/N 315-699481, as applicable for further information.

Figure 6Installation/Wiring Diagram for ADBX-11 Audbiles

Powered by System FS-100 Main Board

Page 11: Fire Safety - Fire Alarm Resourcesfirealarmresources.com/wp-content/uploads/2015/05/Adbx-11.pdf · UL217, Single and Multiple ... Fire Safety Installation Instructions ... as referred

11

Even though no specific spacings are allocated to the detectors used with thisbase, use 30 foot center spacing (900 sq ft), as referred to in NFPA Standard72 National Fire Alarm Code, Chapter 5 and CAN/ULC-S524, as a guide orstarting point, if practical, in a detector installation layout. This spacing is basedon ideal conditions�smooth ceiling, no air movement, and no physicalobstructions.

In all installations (except in special circumstances like computer roomunderfloors), locate the detector on the ceiling, a minimum of 6 inches from aside wall, or on a wall, between 4 and 6 inches from the ceiling.

If questions arise regarding detector placement, it is extremely important thatthe drawings provided or approved by Siemens Building Technologies, Inc. orby its authorized distributors be followed! The detector placements shown onthese drawings were chosen after a careful evaluation of all facets ofprotecting the area. Environmental factors such as air current, temperature,humidity, air pressure, and the nature of the fire load are carefully considered.Special consideration is given to room or area configuration and the type ofceiling (sloped or flat, smooth or beamed). Siemens Building Technologies,Inc.'s extensive experience in the design of fire detection systems assuresoptimum detector placement and is reflected in these drawings. Follow soundengineer-ing judgment made by qualified personnel.

DETECTOR WIRING(USING THE ADBX-11 BASE)

(Refer to Figure 6.) Audible base model ADBX-11 should be interconnected asshown in the Installation/Wiring Diagrams above and wired to the specificsystem modules and control panels following the appropriate instructions. Foroperation with System MXL/MXL-IQ, note any limitations on the number ofaudible bases permitted on each MMB-1/2, SMB-1/2, or CSM-4 audible circuit,depending on the total cable resistance for each audible signal circuit. (SeeELECTRICAL RATINGS section.)

TONE SELECTION

With audible base Model ADBX-11, the user can choose either temporal toneor steady tone. (Refer to Figure 7.)

For Temporal Tone: Terminals 3 and 4 are shorted (insert a jumper).

For Steady Tone: Terminals 3 and 4 are not connected (without a jumper).

DETECTOR MOUNTING(USING THE ADBX-11 BASE)

The detector base comes from the factory prewired. All signaling and initiatingcircuits are connected directly to the back of the ADBX-11 audible base usingthe four-position terminal blocks.

Note: The Audible Base Model ADBX-11 attaches only to a 4-inch squareelectrical box with extension.

Page 12: Fire Safety - Fire Alarm Resourcesfirealarmresources.com/wp-content/uploads/2015/05/Adbx-11.pdf · UL217, Single and Multiple ... Fire Safety Installation Instructions ... as referred

P/N 315-096228-7

Figure 8Positioning the Alarm LED

BASE

MOUNTING

HOLES

ALARM LED

LOCATION WITH

DETECTOR

INSTALLED

IN BASE

DO

NO

TPA

INT

Siemens Building Technologies, Inc.8 Fernwood RoadFlorham Park, New Jersey 07932

Siemens Building Technologies, Ltd.2 Kenview BoulevardBrampton, Ontario L6T 5E4 CN

Mounting the Detector Base

1. Route all wires out from the outlet box.

2. When the alarm LED viewing is critical, position the LED mark on the basein the intended direction (Refer to Figure 8).

3. Make connections directly to the audible base terminals located on the backof the base. Refer to the related lnstallation/Wiring Diagram.

4. After all bases are installed, check loop continuity. For ADBX-11 loopcontinuity check, refer to the System MXL or MXL-IQ Manual CheckoutProcedure.

5. If loop continuity is acceptable, proceed with detector head installation.

Figure 7ADBX-11 Audbile Base Terminal Blocks