  • 8/12/2019 Fired Heaters - GET

    1/25

    FIRED HEATERS

  • 8/12/2019 Fired Heaters - GET

    2/25

    Chemical reactions and processes take place at high

    temperatures and hence heat sources are required.

    Various sources of heat

    Direct fired heaters

    Steam heaters

    Thermal fluid heaters, e.g., Dowtherm

    Electrical heaters

  • 8/12/2019 Fired Heaters - GET

    3/25

    Fluid In Fluid Out

    DIRECT FIRED HEATER

  • 8/12/2019 Fired Heaters - GET

    4/25

    Steam to various users

    including turbines,

    charge heaters,Reboilers etc.

    Condensate returnto boilers

  • 8/12/2019 Fired Heaters - GET

    5/25

    Fluid In Fluid Out

    to

    heatexchangers

    THERMAL FLUID HEATER

  • 8/12/2019 Fired Heaters - GET

    6/25

    Fluid In

    Fluid Out

    Electrical Power IN

  • 8/12/2019 Fired Heaters - GET

    7/25

    RADIATIONZONE

    FUEL OIL

    FUEL GASSTEAM

    CONVECTIONZONE

    STACK

    DAMPER

    NATURAL DRAFT FIRED HEATER

    AIR

  • 8/12/2019 Fired Heaters - GET

    8/25

    RADIATIONZONE

    FUEL OIL

    FUEL GASSTEAM

    PLENUM

    CHAMBER

    CONVECTIONZONE

    STACK

    FD FAN

    DAMPER

    FORCED DRAFT FIRED HEATER

    AIR FROM ATMOS.

  • 8/12/2019 Fired Heaters - GET

    9/25

    RADIATIONZONE

    FUEL OIL

    FUEL GASSTEAM

    PLENUM

    CHAMBER

    CONVECTIONZONE

    STACK

    ID FAN

    FD FAN

    DAMPER

    BALANCED

    DRAFT FIRED

    HEATER

  • 8/12/2019 Fired Heaters - GET

    10/25

    RADIATIONZONE

    FUEL OILFUEL GAS

    STEAM

    PLENUM

    CHAMBER

    CONVECTIONZONE

    STACK

    AIR PREHEATER

    ID FAN

    FD FAN

    DAMPER

    STEAM

    APH

  • 8/12/2019 Fired Heaters - GET

    11/25

    BOTTOM OR UPFIRED

    SIDE OR END FIRED

    TOP OR DOWNFIRED

  • 8/12/2019 Fired Heaters - GET

    12/25

    CYLINDRICAL HEATER WITH VERTICAL COIL

  • 8/12/2019 Fired Heaters - GET

    13/25

    SECTION

  • 8/12/2019 Fired Heaters - GET

    14/25

    Arbor type

    Inlet header Outlet header

  • 8/12/2019 Fired Heaters - GET

    15/25

    Utube

  • 8/12/2019 Fired Heaters - GET

    16/25

    FINNED TUBES - CONVECTION

    STUDDED TUBES - CONVECTION

  • 8/12/2019 Fired Heaters - GET

    17/25

    Bare

    tubes

  • 8/12/2019 Fired Heaters - GET

    18/25

    150mm TO

    200mm thick

    castablerefractory

    Bottomfloor

    200mm

    thick

    castable

    refractory

    with one

    layer of

    brick

    lining

    1300 - 1600 C

    800 - 900 C

    350 - 450 C

    CERAWOOL

    LINING CANBE APPLIED

    INSTEAD OF

    REFRACTORY

  • 8/12/2019 Fired Heaters - GET

    19/25

    DETAIL OF CERAWOOL LINING

    Heater steelexternal

    shell

    Bitumasticpaint coating

    SS304 foil 0.2mm thick for

    corrosion resistance

    25mm thick cerawool

    pads laid one after another.

    Cerawool blankets hold

    down bolts

    Cerawool is not used in

    furnaces with oil fired burners.

    Cost is high

  • 8/12/2019 Fired Heaters - GET

    20/25

    Burner floor

    refractory

    Air

    register

    Fuel gas

    Fuel oilPilot

    burner

    Burner

    tile

    BURNER ASSEMBLY

  • 8/12/2019 Fired Heaters - GET

    21/25

    METALLURGY OF TUBES

    Depends on the fluid inside and the temperature to which the

    fluid is to be heated

    Tube metallurgy Max. temp (C)

    Carbon steel 540

    1.25% Cr - 0.5%Mo 5952.25% Cr - 1%Mo 650

    5%Cr-1%Mo 650

    9%Cr-0.5%Mo 705

    SS304,SS316,SS321 815

    HK40(25Cr-20Ni) 1010

    For any selected metallurgy of tubes the design life shall be

    minimum 100 000 hours

  • 8/12/2019 Fired Heaters - GET

    22/25

    Metallurgy of tube supports

    Tube metallurgy Max. temp (C)

    Carbon steel 427 C

    2.25%Cr-1%Mo 649

    19%Cr-9%Ni 816

    25%Cr-12%Ni (Plate) 87125%Cr-12%Ni (cast) 982

    25%Cr-20%Ni(Plate) 871

    25%Cr-20%Ni(Cast) 1093

    50%Cr-50%Ni 982

    If the fuel oil has more than 100ppm vanadium then the

    supports shall be 50%Cr-50%Ni or refractory lined for

    corrosion resistance purposes.

  • 8/12/2019 Fired Heaters - GET

    23/25

    IMPORTANT DOCUMENTS TO BE REFERRED

    Process licensor datasheet

    Vendor datasheet

    API 560 - Fired heaters for general refinery services

    API 530 - Calculation of heater tube thickness

    Equipment drawings for individual heater for more details

  • 8/12/2019 Fired Heaters - GET

    24/25

    END

    STACK

  • 8/12/2019 Fired Heaters - GET

    25/25

    RADIATIONZONE

    FUEL OILFUEL GAS

    STEAM

    PLENUM

    CHAMBER

    CONVECTION

    ZONE

    STACK

    AIR PREHEATER

    ID FAN

    FD FAN

    DAMPER