float valves svp
DESCRIPTION
Talis Erhard Float valvesTRANSCRIPT
-
Float Valves SVP(Pilot controlled On-Off Valves)
-
ERHARD Float Valves SVP:Quality and Reliability
ERHARD Performance Your AdvantageFlow operated. Operating safety, no energy supply needed.
Large range of setting water levels: Field approved.50 - 4000 mm.
High quality materials: body of SG Robust and reliable.ductile cast iron High strength, long life.Internal and external EKB epoxy coating. Efficient surface protection.
Seat not subject to cavitation. No wear and tear.
Exclusive On-Off valve No risk of damages due to cavitation.
All internal parts accessible from above. Easy maintenance.Maintenance of pilot system withoutbreaking supply.
Position identified at a glance. Easy operation.Pressure gauge with isolating valve.
Float control easily mounted. Easy installation.
Adjustable closing velocity. Water hammer control.
-
Performance
Recommended Installations
The pilot controlled ERHARDFloat Valve is composed of mainvalve and pilot system. The mainvalve consists of: body, cover,plug with guide, diaphragm, andposition indicator.
Upstream pressure acts on chamber A.Downstream pressure acts onchamber B.Control pressure acts onchamber C.
The pilot system includes:Upstream pipe branch I, pilotpressure line II, 3/2-way pilotvalve III, counterweight IV, float V, two adjustable stops VIand VII, weight VIII, float cable IX, throttle valve andmanually operated valve.
These Float Valves maintainadjustable minimum and maximum water levels in a reservoir.
When the water level in thereservoir rises, the float guidedby the control cable slides up-wards to the upper stop. Thebuoyancy of the float lifts thecable with the weight and thecounterweight switches the 3/2-way valve. The upstream main isnow connected with the pilotpressure line. The upstream pres-sure in chamber C closes themain valve tightly.
With a decrease of water level inthe reservoir, the float guided bythe float cable slides down-wards. The main valve remainsclosed until the float reaches thelower stop (minimum level). Theadditional float weight causesthe counterweight to rise and toswitch the 3/2-way valve. Now,chamber C is connected to theambient pressure via the pilotpressure line. This pressure relief
causes the main valve to opencompletely.
The main valve operates withinthe range of the stops as On-OffValve. Intermediate positions arenot possible. The difference bet-ween the top and bottom waterlevels is adjustable from 50 mmto 4000 mm with an accuracy of 20 mm.
SizingThe valve is not sized to thepipeline diameter but in accor-dance with maximum flow con-ditions and installation situation.
For an optimum sizing of thevalve, we recommend a flowvelocity of v = 2 - 2,5 m/s (see flow table).
Recommended flow rate in l/s (m3/h)
Feeding from above
At the outlet of the valve werecommended to install a 90 elbow
the outlet of which ends abovethe water surface.
Feeding from belowFloat control inside
the reservoir
Feeding from belowFloat control outside
the reservoir
I Air Valve
II Isolating Valve
III Strainer: max.mesh size 2 mm
IV ERHARD-FloatValve
V 3/2-way Pilot Valve
Feeding the reser-voir can be doneeither from aboveor from below.When feeding isdone from below,the upstream pres-sure (Pu) has to beas follows:Pu > H + 0.5 bar.For feeding fromabove:Pu > 0.5 bar.
DN
V = 2,5 m/s
50
5 (18)
65
8,5 (30)
80
12,5 (45)
100
19,5 (70)
125
31 (111)
150
44 (158)
200
78,5 (283)
In exceptional cases, flow velocities of 4 m/s are admissible. Additional functions as flow limitation and sustaining the upstream pressure are possible. Please contact us.
I II III
V
IV
-
ERHARD Float Valve SVP PN 10/16 6020 54006021 5400
Material and Equipment
Dimensions
pilot controlled On-Off valve
Range of application: water max. 70 C
When placing the order, please specify max. flow rate, max. static pressure when the valve isclosed, minimum pressure upstream of the valve at max. flow rate, the minimum and maximum pressure downstream of the valve.
Flanges type B..., connecting dimensions to ISO 7005-2 Type 21, PN 16 or PN 10.
SizeDN
20050 - 200
250 - 600
Pressure ratingPN
1016
upon request
Prod. no.
6020 54006021 5400
Surface protection EKB epoxy coating, blue
Body and cover SG ductile cast iron to EN-JS 1040
Plug/clamping ring Injected cast iron / bronze
Body seat and guide Bronze
Sealing ring EPDM
Diaphragm Neoprene with fabric ply
Guide rod and screws Stainless steel
Position indicator Stainless steel / brass
Pilot circuit, fittings, and ball valve Stainless steel / brass, nickel-plated
3/2-way pilot valve, manual valve3) Brass
Throttle valve4), filter Brass / Stainless steel
Float dia. 150, float cable, Plastic / Stainless steelbrackets
Brackets for stilling Stainless steeltube dia. 200
Pressure gauge with isolating valve Upstream
Size
DN
506580
100
125150200
Face-to facedimension
Lmm
230290310350
400480600
Flangedia.D
mm
165185200220
250285340
h1mm
225245265290
385430730
Height Space requirement
h2mm
8595
105115
130145175
e1mm
220205210170
220235215
e2mm
135150155220
170185215
Weight
ca.kg
17232836
4973
116
Packingdimensions
l x b x hcm
70 x 40 x 4070 x 40 x 4070 x 40 x 4070 x 40 x 40
80 x 50 x 4080 x 50 x 4090 x 50 x 70
3) This manual valve facilitates opening and closing the float valve independent of the pilot unit.4) By means of the throttle valve, the opening time of the main valve can be controlled within a
certain range.ERHARD Float Valve with upstream pressure sustaining device. ERHARD Float Valve with flowlimiting device. Prices upon request.
250-600 on request
Stilling tube (PVC rigid dia. 200) and the copper tubes (dia. 8 x 1) for pilot circuit are notincluded in our supply.
Data corresponding to the latest level of development, modifications reserved.
Printed in Germany. 08/02
Postfach 1280 D-89502 HeidenheimPhone: +49(0)7321 320-0 Fax: +49(0)7321 320-525http://www.erhard.dee-mail: [email protected]