RSIC ACOUSTIC ASSEMBLY FLOOR CEILING ASSEMBLY DIRECT FIX TO WOOD OPEN WEB TRUSS F4545.07 STC 61 IIC 54 CONSTRUCTION Hacker Industries, Inc. Firm-Fill Gypsum Concrete Hacker Industries, Inc. Firm-Fill SCM-250 Sound Control Mat Oriented Strand Board Sheathing Guardian Faces R-13 Fiberglass Insulation York PB Truss L/360 Open Web Truss @ 24" O.C. RSIC-1 Installed @ 24"x48" Clark Dietrich 087F125-18 Furring Channel @ 24" O.C. National Gypsum Gold Bond Fire-Shield C Gypsum Board STC 61 Test Number F4545.07 IIC 54 ©2016 PAC International, LLC. All Rights Reserved. • (866) 774-2100 • Fax (866) 649-2710 RSIC® is a registered Trade Mark of PAC International, LLC. STC IIC 1 Hour See www.UL.com World Leader in Noise Control Solutions

Upload: others

Post on 23-Nov-2020

2 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: FLOOR CEILING ASSEMBLY Solutions RSIC-1...Hacker Industries, Inc. Firm-Fill SCM-250 Sound Control Mat Oriented Strand Board Sheathing Guardian Faces R-13 Fiberglass Insulation York

RSIC ACOUSTIC ASSEMBLY

FLOOR CEILING ASSEMBLY

DIRECT FIX TO WOOD OPEN WEB TRUSS

F4545.07 STC 61 IIC 54

CONSTRUCTIONHacker Industries, Inc. Firm-Fill Gypsum ConcreteHacker Industries, Inc. Firm-Fill SCM-250 Sound Control MatOriented Strand Board SheathingGuardian Faces R-13 Fiberglass InsulationYork PB Truss L/360 Open Web Truss @ 24" O.C.RSIC-1 Installed @ 24"x48"Clark Dietrich 087F125-18 Furring Channel @ 24" O.C.National Gypsum Gold Bond Fire-Shield C Gypsum Board

STC 61Test Number F4545.07 IIC 54

©2016 PAC International, LLC. All Rights Reserved. • (866) 774-2100 • Fax (866) 649-2710RSIC® is a registered Trade Mark of PAC International, LLC.

ST

C

IIC

1 HourSee www.UL.com

World Leader in Noise Control

Solutions

Page 2: FLOOR CEILING ASSEMBLY Solutions RSIC-1...Hacker Industries, Inc. Firm-Fill SCM-250 Sound Control Mat Oriented Strand Board Sheathing Guardian Faces R-13 Fiberglass Insulation York

130 Derry Courtaa

York, PA 17406aa

p. 717.764.7700

f. 717.764.4129www.archtest.com · www.intertek.com/building

Ceiling Isolation: 28 mm PAC International RSIC-1 Classic Isolation Clips

Ceiling Isolation: 22.3 mm ClarkDietrich 087F125-18 Furring/Hat Channel

Ceiling: 15.9 mm National Gypsum Gold Bond® Fire-Shield C™ Gypsum Board

Reference should be made to Intertek-ATI Report F4545.07-113-11 for complete test specimen

description. This page alone is not a complete report.

Subfloor Topping: 25.4 mm Hacker Industries, Inc. FIRM-FILL® Brand Gypsum Concrete

Subfloor Underlayment: 6.5 mm Hacker Industries, Inc. FIRM-FILL® SCM-250e Sound Control Mat

Subfloor: 18.8 mm Oriented Strand Board Sheathing

Insulation: 88.9 mm Guardian Faced R-13 Fiberglass Insulation

Truss: 457.2 mm York PB Truss L/360 Open Web Truss

Test Specimen Identification:

Specimen Type: Open Web Truss - 457 mm

Overall Size: 3023 mm by 3632 mm

STC 63

IIC 54

Series/Model: FIRM-FILL® Brand Gypsum Concrete and FIRM-FILL® SCM-250e

Sound Control Mat - Bare

F4545.07-113-11-R1

ACOUSTICAL PERFORMANCE TEST REPORT

ASTM E 90 AND ASTM E 492

Rendered to

HACKER INDUSTRIES INC.

Page 3: FLOOR CEILING ASSEMBLY Solutions RSIC-1...Hacker Industries, Inc. Firm-Fill SCM-250 Sound Control Mat Oriented Strand Board Sheathing Guardian Faces R-13 Fiberglass Insulation York

130 Derry Courtaa

York, PA 17406aa

p. 717.764.7700

f. 717.764.4129www.archtest.com · www.intertek.com/building

ASTM E 989-06 (2012), Classification for Determination of Impact Insulation Class (IIC)

ASTM E 2235-04 (2012) Standard Test Method for Determination of Decay Rates for Use in

Sound Insulation Test Methods

Test Procedure

All testing was conducted in the VT test chambers at Intertek-ATI located in York,

Pennsylvania. The microphones were calibrated before conducting the tests.

The airborne transmission loss test was conducted in accordance with the ASTM E 90 test

method using the single direction method. Two background noise sound pressure level and five

sound absorption measurements were conducted at each of five microphone positions. Four

sound pressure level measurements were made simultaneously in both rooms, at each of five

microphone positions.

Test Methods

The acoustical tests were conducted in accordance with the following standards. The equipment

listed in the attachments meets the requirements of the following standards.

ASTM E 90-09, Standard Test Method for Laboratory Measurement of Airborne Sound

Transmission Loss of Building Partitions

ASTM E 413-10, Classification for Rating Sound Insulation

ASTM E 492-09, Standard Test Method for Laboratory Measurement of Impact Sound

Transmission Through Floor-Ceiling Assemblies Using the Tapping Machine

Report Date 03/15/16

Revision Date 04/29/16

Project Scope

Architectural Testing, Inc., a subsidiary of Intertek (Intertek-ATI), was contracted to conduct

airborne sound transmission loss and impact sound transmission tests. The complete test data is

included as attachments to this report. The client provided the test specimen. The specimen was

constructed on the date of testing.

Newport Beach, California 92660

Report F4545.07-113-11

Test Date 03/07/16

Page 1 of 4

Acoustical Performance Test Report

HACKER INDUSTRIES INC.

1600 Newport Center Drive, Suite 275

F4545.07-113-11-R1

Page 4: FLOOR CEILING ASSEMBLY Solutions RSIC-1...Hacker Industries, Inc. Firm-Fill SCM-250 Sound Control Mat Oriented Strand Board Sheathing Guardian Faces R-13 Fiberglass Insulation York

Isolation Clips76.9 by 35.6 28.0 PAC International RSIC-1 Classic 24 clips 0.06 kg/clip

Note: Fastened to joists in a 610 mm by 1220 mm traditional pattern.

Open Web Truss88.9 by 2933.7 457.2 York PB Truss L/360 7 m² 19.05 kg/m²

Note: Installed on 610 centers using JUS414 hanger brackets.

2962 by 584 88.9 Guardian Faced R-13 10.98 m² 1.33 kg/m²

Note: Installed in the cavity between trusses flush with the OSB. Hanger wire was used to keep

insulation secure on 305mm

Oriented Strand

Board Sheathing

1219 by 2438 18.8 N/A 10.98 m² 13.82 kg/m²

Note: The OSB was adhered to the trusses with Loctite PL 400 Subfloor adhesive. It was attached

with 9D nails on 203 mm centers along perimeter and 305 mm centers along trusses.

Fiberglass Insulation

Sound Control Mat1219 by 3023 6.5

Hacker Industries, Inc. FIRM-

FILL® SCM-250e10.98 m² 0.49 kg/m²

Note: Installed per manufacture's specifications with seams overlapping and taped

Gypsum Concrete3632 by 3023 25.4

Hacker Industries, Inc. FIRM-

FILL® Brand10.98 m² 41.99 kg/m²

Note: The gypsum concrete was allowed to cure for a minimum of 14 days. The gypsum layer had a

closed cell foam perimeter isolation. The product name was specified by client.

Test Specimen Materials and Installation Details

MaterialDimensions

(mm)

Thickness

(mm)Manufacturer and Series Quantity

Average

Weight

Average Relative Humidity 60% Average Relative Humidity 57%

Test Calculations

The STC (Sound Transmission Class) and IIC (Impact Insulation Class) ratings were calculated

in accordance with ASTM E 413 and ASTM E 989, respectively.

Test Conditions

Source Room Receive Room

Average Temperature 19.4°C Average Temperature 20.3°C

Page 2 of 4

Test Procedure (Continued)

The impact sound transmission test was conducted in accordance with the ASTM E 492 test

method. Two background noise sound pressure level, two sound pressure level measurements

with the tapping machine operating at each position specified by ASTM E 492, and five sound

absorption measurements were conducted at each of five microphone positions.

The air temperature and relative humidity conditions were monitored and recorded during all

measurements.

F4545.07-113-11-R1

Page 5: FLOOR CEILING ASSEMBLY Solutions RSIC-1...Hacker Industries, Inc. Firm-Fill SCM-250 Sound Control Mat Oriented Strand Board Sheathing Guardian Faces R-13 Fiberglass Insulation York

Technician II - Acoustical Testing Project Manager - Acoustical Testing

Attachments (6 Pages): This report is complete only when all attachments are included.

* Stated by Client/Manufacturer

N/A - Non Applicable

Intertek-ATI will service this report for the entire test record retention period. Test records,

such as detailed drawings, datasheets, representative samples of test specimens, or other

pertinent project documentation, will be retained by Intertek-ATI for the entire test record

retention period. The test record retention period ends four years after the test date.

This report does not constitute certification of this product nor an opinion or endorsement by

this laboratory. It is the exclusive property of the client so named herein and relates only to the

specimen tested. This report is intended to help in the client’s quality assurance program, but it

does not represent a continuous or exhaustive evaluation of the specimen tested or of other

products or materials that were not evaluated. The statements and data provided herein do not

constitute approval, disapproval, certification, or acceptance of performance or materials.

This report may not be reproduced, except in full, without the written approval of

Intertek-ATI.

FOR INTERTEK-ATI:

David M. Dacheux Jordan Strybos

Comments

The total weight of the floor/ceiling assembly was 892.8 kg. Intertek-ATI will store samples of

the test specimen for four years. A drawing of the test specimen is included in the attachments.

Gypsum Board1219 by 3023 15.9

National Gypsum Gold Bond®

Fire-Shield C™10.35 m² 10.74 kg/m²

Note: Fastened to furring channels on 305 mm centers with 25.4 mm type S screws. Seams finished

with joint compound. Perimeter sealed with acoustical caulk.

Furring/Hat Channel3658 by 76.2 22.3 ClarkDietrich 087F125-18 29.1 lin m 0.48 kg/m

Note: Installed into the PAC International RSIC-1 Classic, spaced 610 mm on center.

F4545.07-113-11-R1

Page 3 of 4

Test Specimen Materials and Installation Details (Continued)

MaterialDimensions

(mm)

Thickness

(mm)Manufacturer and Series Quantity

Average

Weight

Page 6: FLOOR CEILING ASSEMBLY Solutions RSIC-1...Hacker Industries, Inc. Firm-Fill SCM-250 Sound Control Mat Oriented Strand Board Sheathing Guardian Faces R-13 Fiberglass Insulation York

This report produced from controlled document template ATI 00629(d), Revised 02/09/15.

R0 03/15/16 N/A Original Report Issue

R1 04/29/16 Page 2 Clip spacing installation note corrected

F4545.07-113-11-R1

Page 4 of 4

Revision Log

Revision Date Page(s) Description

Page 7: FLOOR CEILING ASSEMBLY Solutions RSIC-1...Hacker Industries, Inc. Firm-Fill SCM-250 Sound Control Mat Oriented Strand Board Sheathing Guardian Faces R-13 Fiberglass Insulation York

Test Chambers

VT Receive Room Volume 155.77 m³

VT Source Room Volume 190 m³

Page 1 of 6

Tapping Machine Look Line s.r.l. EM50 (TM50) 65351 11/15

* The calibration frequency for this equipment is every two years per the manufacturer's recommendation.

Source Room Microphone Scantek 378B20 63741 04/15

Source Room Environmental

IndicatorComet T7510 63812 11/15

Source Room Microphone PCB Piezotronics 378B20 63740 04/15

Source Room Microphone PCB Piezotronics 378B20 63742 04/15

Source Room Microphone PCB Piezotronics 378B20 63738 04/15

Source Room Microphone PCB Piezotronics 378B20 63739 04/15

Receive Room Environmental

IndicatorComet T7510

63810

63811

10/15

10/15

Receive Room Microphone PCB Piezotronics 378B20 63746 05/15

Receive Room Microphone PCB Piezotronics 378B20 63747 05/15

Receive Room Microphone PCB Piezotronics 378B20 63744 05/15

Receive Room Microphone PCB Piezotronics 378B20 63745 05/15

Microphone Calibrator Norsonic 1251 Y002919 07/15

Receive Room Microphone Scantek 378B20 63748 05/15

Data Acquisition Unit National Instruments PXI-1033 63763 06/14 *

F4545.07-113-11-R1

Attachments

Instrumentation

Instrument Manufacturer Model ATI NumberDate of

Calibration

Page 8: FLOOR CEILING ASSEMBLY Solutions RSIC-1...Hacker Industries, Inc. Firm-Fill SCM-250 Sound Control Mat Oriented Strand Board Sheathing Guardian Faces R-13 Fiberglass Insulation York

STC Rating (Sound Transmission Class)

Deficiencies (Sum of Deficiencies)

Notes: 1) Receive Room levels less than 5 dB above the Background levels are highlighted in yellow.

2) Specimen TL levels listed in red indicate the lower limit of the transmission loss.

3) Specimen TL levels listed in green indicate that there has been a filler wall correction applied

ATI 00614 Revised 02/09/15 Page 2 of 6

29

63

0.70 -

10000 12.8 27.5 92 7 83 0.40 -

8000 13.0 21.9 97 12 83

0.60 -

6300 12.2 16.7 98 16 81 0.70 -

5000 12.2 13.3 105 28 76

0.30 0

4000 12.1 11.7 105 31 74 0.50 0

3150 11.6 10.4 104 32 73

0.40 0

2500 11.3 9.4 103 36 69 0.40 0

2000 14.6 8.7 105 38 68

0.50 0

1600 19.7 7.9 105 39 69 0.30 0

1250 22.0 8.0 105 40 68

0.20 1

1000 21.8 7.8 105 43 65 0.40 1

800 21.5 7.9 105 44 64

0.50 3

630 22.2 7.9 106 45 64 0.50 0

500 23.5 8.2 104 47 60

0.60 4

400 22.1 8.6 104 49 57 0.70 5

315 24.2 9.7 106 53 55

1.30 4

250 26.5 10.3 105 54 53 1.30 3

200 28.3 10.0 105 57 49

1.40 3

160 31.2 9.5 109 65 45 1.50 5

125 36.2 11.1 107 64 44

4.80 -

100 41.1 11.7 107 66 42 2.70 -

80 46.7 16.6 108 70 38

-

63 45.6 30.3 102 63 36 3.40 -

(dB) Limit Deficiencies

50 48.2 27.7 103 66 34 5.20

SPL SPL SPL Confidence of

(Hz) (dB) (m²) (dB) (dB)

Technician David M. Dacheux

FreqBackground

AbsorptionSource Receive Specimen

TL

95% Number

Client Hacker Industries Inc.

Description 25.4 mm Hacker Industries, Inc. FIRM-FILL® Brand Gypsum Concrete, 6.5 mm Hacker Industries, Inc. FIRM-FILL® SCM-

250e Sound Control Mat, 18.8 mm Oriented Strand Board Sheathing, 88.9 mm Guardian Faced R-13 Fiberglass Insulation, 457.2

mm York PB Truss L/360 Open Web Truss, 28 mm PAC International RSIC-1 Classic Isolation Clips, 22.3 mm ClarkDietrich

087F125-18 Furring/Hat Channel, 15.9 mm National Gypsum Gold Bond® Fire-Shield C™ Gypsum Board

Specimen Area 10.98 m²

F4545.07-113-11-R1

AIRBORNE SOUND TRANSMISSION LOSS

ASTM E 90

Test Date 03/07/16

Data File No. F4545.07

Page 9: FLOOR CEILING ASSEMBLY Solutions RSIC-1...Hacker Industries, Inc. Firm-Fill SCM-250 Sound Control Mat Oriented Strand Board Sheathing Guardian Faces R-13 Fiberglass Insulation York

Specimen Area 10.98 m²

Technician David M. Dacheux

ATI 00614 Revised 02/09/15 Page 3 of 6

Data File No. F4545.07

Client Hacker Industries Inc.

Description 25.4 mm Hacker Industries, Inc. FIRM-FILL® Brand Gypsum Concrete, 6.5 mm Hacker Industries, Inc. FIRM-FILL® SCM-

250e Sound Control Mat, 18.8 mm Oriented Strand Board Sheathing, 88.9 mm Guardian Faced R-13 Fiberglass Insulation, 457.2

mm York PB Truss L/360 Open Web Truss, 28 mm PAC International RSIC-1 Classic Isolation Clips, 22.3 mm ClarkDietrich

087F125-18 Furring/Hat Channel, 15.9 mm National Gypsum Gold Bond® Fire-Shield C™ Gypsum Board

F4545.07-113-11-R1

AIRBORNE SOUND TRANSMISSION LOSS

ASTM E 90

Test Date 03/07/16

0

10

20

30

40

50

60

70

80

90

100

63

125

250

500

100

0

200

0

400

0

800

0

Sou

nd

Tra

nsm

issi

on

Loss

(d

B)

Frequency (Hz)

Airborne Sound Transmission Loss

Specimen TL

Contour Curve

Page 10: FLOOR CEILING ASSEMBLY Solutions RSIC-1...Hacker Industries, Inc. Firm-Fill SCM-250 Sound Control Mat Oriented Strand Board Sheathing Guardian Faces R-13 Fiberglass Insulation York

IIC Rating (Impact Insulation Class)

Deficiencies (Sum of Deficiencies)

54

30

Note: Receive Room levels less than 5 dB above the Background levels are highlighted in yellow.

ATI 00615 Revised 02/09/15 Page 4 of 6

10000 7.4 27.5 12 0.2 -

8000 7.2 21.9 12 0.3 -

6300 7.6 16.9 14 0.4 -

5000 6.7 13.3 21 0.5 -

4000 6.8 11.7 28 0.4 -

3150 7.2 10.3 36 0.3 0

2500 9.5 9.4 45 0.2 4

2000 13.1 8.7 51 0.3 7

1600 20.3 7.9 51 0.3 4

1250 23.0 8.0 52 0.2 2

1000 23.1 7.9 56 0.8 3

800 24.0 7.9 57 0.4 3

630 21.3 7.7 58 0.4 3

500 23.3 8.2 57 0.3 1

400 20.3 8.6 57 0.4 0

315 23.3 10.0 57 0.6 0

250 25.1 10.5 58 0.9 0

200 26.0 10.3 58 0.8 0

160 30.1 9.5 60 1.1 2

125 34.3 10.0 58 1.4 0

100 44.8 12.3 59 0.9 1

80 47.9 16.9 62 2.3 -

63 45.5 26.9 61 3.7 -

50 43.6 23.2 64 1.4 -

(Hz) (dB) (m²) (dB) Limit Deficiencies

Technician David M. Dacheux

Freq Background SPL AbsorptionNormalized Impact

SPL

95% Number

Confidence of

Client Hacker Industries Inc.

Description 25.4 mm Hacker Industries, Inc. FIRM-FILL® Brand Gypsum Concrete, 6.5 mm Hacker Industries, Inc. FIRM-FILL® SCM-

250e Sound Control Mat, 18.8 mm Oriented Strand Board Sheathing, 88.9 mm Guardian Faced R-13 Fiberglass Insulation, 457.2

mm York PB Truss L/360 Open Web Truss, 28 mm PAC International RSIC-1 Classic Isolation Clips, 22.3 mm ClarkDietrich

087F125-18 Furring/Hat Channel, 15.9 mm National Gypsum Gold Bond® Fire-Shield C™ Gypsum Board

Specimen Area 10.98 m²

F4545.07-113-11-R1

IMPACT SOUND TRANSMISSION

ASTM E 492

Test Date 03/07/16

Data File No. F4545.07

Page 11: FLOOR CEILING ASSEMBLY Solutions RSIC-1...Hacker Industries, Inc. Firm-Fill SCM-250 Sound Control Mat Oriented Strand Board Sheathing Guardian Faces R-13 Fiberglass Insulation York

Technician David M. Dacheux

ATI 00615 Revised 02/09/15 Page 5 of 6

Client Hacker Industries Inc.

Description 25.4 mm Hacker Industries, Inc. FIRM-FILL® Brand Gypsum Concrete, 6.5 mm Hacker Industries, Inc. FIRM-FILL® SCM-

250e Sound Control Mat, 18.8 mm Oriented Strand Board Sheathing, 88.9 mm Guardian Faced R-13 Fiberglass Insulation, 457.2

mm York PB Truss L/360 Open Web Truss, 28 mm PAC International RSIC-1 Classic Isolation Clips, 22.3 mm ClarkDietrich

087F125-18 Furring/Hat Channel, 15.9 mm National Gypsum Gold Bond® Fire-Shield C™ Gypsum Board

Specimen Area 10.98 m²

F4545.07-113-11-R1

IMPACT SOUND TRANSMISSION

ASTM E 492

Test Date 03/07/16

Data File No. F4545.07

10

20

30

40

50

60

70

80

90

100

1100

10

20

30

40

50

60

70

80

90

100

63

125

250

500

100

0

200

0

400

0

800

0

Imp

act

In

sula

tion

Cla

ss (

IIC

)

So

un

d P

ress

ure

Lev

el (

dB

)

Frequency (Hz)

Impact Sound Transmission

Normalized Impact SPL

Contour Curve

Page 12: FLOOR CEILING ASSEMBLY Solutions RSIC-1...Hacker Industries, Inc. Firm-Fill SCM-250 Sound Control Mat Oriented Strand Board Sheathing Guardian Faces R-13 Fiberglass Insulation York

Page 6 of 6

3-Subfloor

4-Insulation

5-Truss

6-Ceiling Isolation

7-Ceiling

1-Subfloor Topping

2-Subfloor Underlayment

Drawing

F4545.07-113-11-R1