flow diagram for dehumidifier

Upload: amitbslpawar

Post on 28-Feb-2018

214 views

Category:

Documents


0 download

TRANSCRIPT

  • 7/25/2019 Flow Diagram for Dehumidifier

    1/2

    Bry-Air....# 1 in Dehumidification

    RETURN

    AIR

    SUPPLYAIR

    REACT O

    REACT I

    PROCESS OUT

    PROCESS IN

    FRESH AIR

    BYPASS AIR

    CONDITIONED SPACE

    300 CFM

    9043 CFM

    2500 CFM

    8743 CFM

    6543 CFM ,

    2200 CFM

    Internal Latent Load :

    Internal Sensible Load :

    DBT RH Abs. Hum.

    72 F 23.2 Grs/#

    72 F

    23.2 Grs/#

    23.2 Grs/#72 F ,

    23.2 Grs/#

    72 F

    55 F

    64.4 Grs/# 70 F

    28.1 Grs/#

    96.9 F

    6.2 Grs/#

    78.9 F18.5 Grs/

    9043CFM

    58.5 F

    18.5 Grs/#

    86 F

    167.2 Grs/#

    46.9 BTU/# 23.2 BTU/#

    LEGEND

    H.B

    F.B

    React.

    HEATER BANK

    FILTER BANK

    REACTIVATION

    SYSTEM FLOW DIAGRAM

    UTILITIES REQD.

    Precoil Load

    After Coil

    Heat Addition by Dehumidifier

    Electric

    Process

    =

    =

    =

    =

    30471.4 2.5

    199235.4 16.6

    =

    =

    BTUH

    BTUH

    BTUH67230

    44

    2.2

    KW

    KW

    TOR

    TOR

    BNN

    09-Jan-2012Date :

    By :

    ALKEM LABORATORIES TALOJAProject Name :ACD-2Area :

    169485

    REACTIVATION

    131846

    Steam =75.65 Kgs/Hr @ 7 Kgs/cm2

    MOTOR DETAILS

    Reactivation =1.1 KW

    Electrical Connection ( V /Ph/Hz)415/3/50

    Standard Unit Dimension( Bare Unit )=1050 1130 1770X Xmm mm mm

    NMT25%

    MODEL

    Grs/Hr

    BTUH

    Precool Coil

    After Coil

    2500 CFM

    FLP-4200 x 1

    =

    Dimensions shall increase for !"ass # other o"tions e$%$ After & 're coil ( fan etc$

    Our scope

  • 7/25/2019 Flow Diagram for Dehumidifier

    2/2