flow diagram for dehumidifier
TRANSCRIPT
-
7/25/2019 Flow Diagram for Dehumidifier
1/2
Bry-Air....# 1 in Dehumidification
RETURN
AIR
SUPPLYAIR
REACT O
REACT I
PROCESS OUT
PROCESS IN
FRESH AIR
BYPASS AIR
CONDITIONED SPACE
300 CFM
9043 CFM
2500 CFM
8743 CFM
6543 CFM ,
2200 CFM
Internal Latent Load :
Internal Sensible Load :
DBT RH Abs. Hum.
72 F 23.2 Grs/#
72 F
23.2 Grs/#
23.2 Grs/#72 F ,
23.2 Grs/#
72 F
55 F
64.4 Grs/# 70 F
28.1 Grs/#
96.9 F
6.2 Grs/#
78.9 F18.5 Grs/
9043CFM
58.5 F
18.5 Grs/#
86 F
167.2 Grs/#
46.9 BTU/# 23.2 BTU/#
LEGEND
H.B
F.B
React.
HEATER BANK
FILTER BANK
REACTIVATION
SYSTEM FLOW DIAGRAM
UTILITIES REQD.
Precoil Load
After Coil
Heat Addition by Dehumidifier
Electric
Process
=
=
=
=
30471.4 2.5
199235.4 16.6
=
=
BTUH
BTUH
BTUH67230
44
2.2
KW
KW
TOR
TOR
BNN
09-Jan-2012Date :
By :
ALKEM LABORATORIES TALOJAProject Name :ACD-2Area :
169485
REACTIVATION
131846
Steam =75.65 Kgs/Hr @ 7 Kgs/cm2
MOTOR DETAILS
Reactivation =1.1 KW
Electrical Connection ( V /Ph/Hz)415/3/50
Standard Unit Dimension( Bare Unit )=1050 1130 1770X Xmm mm mm
NMT25%
MODEL
Grs/Hr
BTUH
Precool Coil
After Coil
2500 CFM
FLP-4200 x 1
=
Dimensions shall increase for !"ass # other o"tions e$%$ After & 're coil ( fan etc$
Our scope
-
7/25/2019 Flow Diagram for Dehumidifier
2/2