Flue Installation High Efficiency Condensing Boilers

Upload: others

Post on 14-Feb-2021

1 views

Category:

Documents


0 download

TRANSCRIPT

  • Flue InstallationHigh Effi ciencyCondensing Boilers

  • Table of conTenTs

    - 3 -

    InTRoDUcTIon

    1 Instructionguidance...........................................................................................................................41.1 Productdocumentation...........................................................................................41.2 Explanationofsymbols..........................................................................................41.3 ImportantNotes.....................................................................................................4

    InsTallaTIon

    2 TelescopicDirectRearFlueKitØ60/100-Pt.No.A2043500...........................................................72.1 FlueLengthandTerminalPosition.........................................................................72.2 ExternalFlueInstallation........................................................................................82.3 InternalFlueInstallation........................................................................................8

    3 TopHorizontalTelescopicFlueKitØ60/100-Pt.No.A2043600.....................................................93.1 FlueLengthandTerminalPosition.........................................................................9

    4 TopHorizontalStandardFlueKitØ60/100-Pt.No.A2043400...................................................... 114.1 FlueLengthandTerminalPosition....................................................................... 114.2 FlueCutting.......................................................................................................... 114.3 FlueFitting............................................................................................................12

    5 VerticalConcentricFlueSystemØ60/100-Pt.No.A2043400.......................................................135.1 FlueLengthandTerminalPosition.......................................................................135.2 FlueInstallation....................................................................................................135.3 FlueTerminal........................................................................................................145.4 RidgeTileTerminal...............................................................................................155.5 FlueTerminalCutting............................................................................................155.6 FlueExtensionCompletion...................................................................................15

    6 Accessories......................................................................................................................................166.1 DeflectorFlueTerminalKitØ60/100.....................................................................166.2 Installation............................................................................................................166.3 BlackTerminalKitØ60/100..................................................................................176.4 Installation............................................................................................................176.5 PlumeManagementKitØ60/100.........................................................................186.6 TerminalSiting......................................................................................................196.7 Installation............................................................................................................206.8 Terminationaboveeaves......................................................................................226.9 Termination...........................................................................................................226.10 FixingInstructions.................................................................................................22

    7 FlueSystemsandComponents.......................................................................................................237.1 TopHorizontalStandardFlueØ80/125................................................................247.2 FlueLengthandTerminalPosition.......................................................................247.3 ExtensionCutting.................................................................................................247.4 InstallingtheSlidingSleeve.................................................................................247.5 FittingElbows.......................................................................................................257.6 FlueTerminalAssemblyFitting.............................................................................257.7 HorizontalFlueRoofTermination.........................................................................257.8 VerticalConcentricFlueØ80/125.........................................................................267.9 FlueLengthandTerminalPosition.......................................................................267.10 PitchedRoofTerminalInstallation........................................................................267.11 FlatRoofTerminalInstallation..............................................................................277.12 FlueTerminalCutting............................................................................................277.13 FittingAir/FlueDuctExtensions............................................................................277.14 FittingElbows.......................................................................................................27

  • 0020095198_02-06/11-Glow-worm

    INTRODUCTION

    - 4 -

    InTRoDUcTIon

    1 Instructions guidance

    1.1 Product documentation

    Theinstructionsareanintegralpartoftheapplianceandmustbehandedtotheuseroncompletionoftheinstallationinordertocomplywiththecurrentregulation.

    • Carefullyreadthemanual,tounderstandalltheinformationtoenablesafeinstallation,useandservicing.Noliabilitycanbeacceptedintheeventofdamagefornotcomplyingwiththeguidanceinthisinstructionmanual.

    1.2 explanation of symbols

    a DANGER: Risk of injuries.

    e DANGER: Risk of electric shock.ATTENTION: Risk of damage to the appliance or to its surroundings.

    IMPORTANT: Important information.

    1.3 Important notes

    Read the following before installing your flue system!

    flue options - 60/100

    Therearevariousfluesystemsasillustratedindiagramopposite.

    1.Directreartelescopicflue

    2.Tophorizontaltelescopicflue.

    3.Tophorizontalstandardflue.

    4.Verticalconcentricflueflue.

    Thesesystemsarecomplimentedwithvariousaccessories.

    flue systems concealed in Voids

    InaccordancewithBuildingRegulationsPartJ:2010andtheGasSafeRegisterTechnicalBulletinTB008:ForBoilerfluesystemsinstalledwithinanyconcealedenclosure(suchasaceilingspace,floorvoid,orapurposebuiltenclosure),theentirefluesystemshouldbeaccessible.Thisistoallowproperinspectionofthefluetodeterminethatitiscontinuousandfullysupportedthroughoutitslengthandalljointsarecorrectlyassembled.

    Themaximumequivalentfluelengthsarestatedintheinstructionsprovidedwitheachappliance.Thesevaluesmustneverbeexceeded.

    Multiple boiler chimney flue - 60/100 (flue category c43 natural draught)

    Verticalconcentricmultipleflueissuitableforusewith:-

    Tophorizontaltelescopicflue,

    Topstandardhorizontalflue,

    Refertoyourapplianceinstallationinstructionsforinformationrelatingtofluelengthandinstallation.

    flue options - 80/125

    Thetwofluesystemsavailableare:

    1.Topstandardhorizontalflue

    2.Verticalconcentric.

    flue systems

    ThefluelengthsavailablearedescribedintheappropriatesectionoftheInstallationInstructionssuppliedwithyourappliance.

    • Thefluesealsaresensitivetomineraloilbasedlubricants.Donotgreasetheseals.Ifthesealsdoneedtobelubricateduseonlywater.

    • Duringtheinstallationofthefluesystem,ensurethatdebrissuchasmortar,filingsorswarfareclearedfromthefluesystembeforecompletion.

    • Inspectthefluepipesbeforefittinganddonotinstalldamagedordentedfluecomponents.

    • Whenassemblingthefluesystem,ensurethattheinnersealsarenotdamaged,donotinstallafluecomponentwithadamagedseal.

    • Thefluecanbeinstalledfrominsidethebuilding,whenaccesstotheoutsidewallfaceisnotpracticable.

    • Whenextensionpipesareusedthefluesystemmustbedesignedtohaveacontinuousfalltotheapplianceofatleast2.5°44mm/metretoallowcondensatetorunbackintotheapplianceandoutviathecondensatedrain.

    • Longlengthsoffluesmustbesecuredtothewallsorceilingstheyrunagainst.Useatleastonefixingbracketforeveryflueextensionthatisused.

    • Aftercuttinginnerfluepipeensurethatyoude-burrandchamferthemaletubeendtopreventdamage.

    • Inspectthefluepipesbeforefittinganddonotinstalldamagedordentedfluecomponents.

    • Whenassemblingthefluesystem,ensurethattheinnersealsarenotdamaged,donotinstallafluecomponentwithadamagedseal.

    • Whenfittingflueelbowsensurethattheyarefittedatthecorrectangletoavoidstrain,thiswillensurethatthesealfitscorrectlypreventingleakage.

  • 0020095198_02-06/11-Glow-worm

    INTRODUCTION

    - 5 -

    flue clearances

    Thefluesshouldbepositionedsothatatleasttheminimumoperationalandservicingclearancesareprovided,refertotheappropriatesectionoftheinstallationliteraturesuppliedwithyourappliance.Additionalclearancesmaybebeneficialforinstallationandservicing.

    Forflueinstallationswhereexternalaccessisnotpracticable,considerationshouldbegivenforthespacerequiredtoinserttheflueinternally,whichmaynecessitateclearancelargerthanthosespecified.

    Timber frame buildings

    IftheflueistobeinstalledinatimberframebuildingitshouldbefittedinaccordancewiththeInstituteofGasEngineersdocumentIGE/UP/7/1998.

    IfindoubtseekadvicefromGlow-wormortheadvicelineforregisteredgasinstallersprovidedbythebodyapprovedatthetimebytheHealthandSafetyExecutive.

    combustible Material

    Theflueissuitableforinstallationontoandthroughcombustiblematerialsprovidedthataminimum5mmclearanceismaintainedaroundthecircumferenceoftheflue(airintake).

    1.3.1 local regulations

    Benchmarkplacesresponsibilitiesonbothmanufacturersandinstallers.Thepurposeistoensurethatcustomersareprovidedwiththecorrectequipmentfortheirneeds,thatitisinstalled,commissionedandservicedinaccordancewiththemanufacturer’sinstructionsbyacompetentpersonapprovedatthetimebytheHealthandSafetyExecutiveandthatitmeetstherequirementsoftheappropriateBuildingRegulations.TheBenchmarkChecklistcanbeusedtodemonstratecompliancewithBuildingRegulationsandshouldbeprovidedtothecustomerforfuturereference.

    Installersarerequiredtocarryoutinstallation,commissioningandservicingworkinaccordancewiththeBenchmarkCodeofPracticewhichisavailablefromtheHeatingandHotwaterIndustryCouncilwhomanageandpromotetheScheme.

    • Visitwww.centralheating.co.ukformoreinformation.

  • 0020095198_02-06/11-Glow-worm

    INTRODUCTION

    - 6 -

    Top HorizontalTelescopic Flue

    A2043600

    Ridge Tile Terminal

    A2043800

    Flue AdaptorA2024600

    Top HorizontalStandard Flue

    A2043400

    Direct RearTelescopic Flue

    A2043500

    Pitched RoofWeather Collar2000460479

    Flat RoofWeather Collar2000460478

    Special ordercontact: Tower Flue

    ComponentsMorley Road

    TonbridgeKent TN9 1RA

    Vertical Concentric

    Flue 2000460480

    Vertical Concentric Flue 60/100

    Flue Systems

    flue componentsØ60/100 Direct Toptelescopic Topstandard

    Vertical

    0.5mPtNo.20004604811mPtNo.20004604822mPtNo.2000460483incl.securingcollar

    45° elbowPtNo.2000460485(packof2) 87° elbowPtNo.2000460484 Verticalflueadaptor

    PtNo.A2024600

    SlidingsleevePtNo.2000460487 - - TelescopicextensionPtNo.2036900incl.securingcollar - - FixingbracketPtNo.2000460486100Ø

    Refer to section 2. Refer to section 3. Refer to section 1.

    Refer to section 4.

    15703

  • 0020095198_02-06/11-Glow-worm

    INSTALLATION

    - 7 -

    InsTallaTIon

    All the drawings dimensions are shown in mm.

    2 Telescopic Direct Rear flue Kit Ø60/100 - Pt. no. a2043500

    Direct rear flues are only possible with certain boilers, check the instructions provided with your boiler.

    Checkthecontentsofyourkit.

    SEALINGTAPE

    SEALINGCOLLAR

    FLUESECURINGSCREWS(3OFF)

    CLAMPINGBAND

    2.1 flue length and Terminal position

    RefertoyourInstallationinstructionssuppliedwiththeappliancetoconfirmthefluelengthavailableandlocationoftheflueterminal,thenproceedasfollows:

    • Measurethedistancefromtheexternalwalltotheappliancemountingface”Y”,seediagrambelow.

    • Setthefluetotherequiredlength‘Y’plus24mmminto28mmmax.

    *Y+24to28

    INSIDEWALLFACE

    OUTSIDEWALLFACE

    *noTe:Iffittingsealingcollaranadditional12mmisrequired

    noTe:Iffittingthesealingcollar,addafurther12mmtotheoveralllength.

    noTe:DONOTcutthetelescopicflue,ifthefluelengthcannotbeachieved,thestandardflueorextensionsshouldbeused.Howeverifnecessarythefluecanprojecttoamaximumof600mm.beyondtheoutsidewallface.

    • Aligntheairductseams.

    • Markanddrilla3mmholeintheairduct,takingcarenottopiercetheinnerflueduct.

    • Securethejointwiththescrewsandtapeprovided.

  • 0020095198_02-06/11-Glow-worm

    INSTALLATION

    - 8 -

    Alignairductseams

    Ø3mm

    2.2 external flue Installation

    • Ifrequired,fitthesealingcollarontothelocatingringoftheflueterminal.

    • Pushthetelescopicflueassemblyintothewallandthroughthegrips.

    • Pulltheflueassemblyforwardtotherequireddepthshownindiagram,thensecureusingoneofthedescribedmethodsopposite.

    2.3 Internal flue Installation

    • Ifrequired,fittheinternalsealingcollarontothelocatingringoftheflueterminal.

    • Pushthetelescopicflueassemblythroughthegripsandwall,untilthesealingcollarhasexitedthehole.

    • Pulltheflueassemblyforwardtotherequireddepthshownindiagramopposite,thensecureusingoneofthedescribedmethodsopposite:

    Method 1. securing screws (3)Therearesixholesprovidedinthegrips,threeoftheseshouldbeusedtosecuretheflue.Markanddrill3mmholesintheairductthensecuretothegripswiththescrewsprovided.

    Method 2. clamping bandSecurethetelescopicterminalassemblyusingtheclampingbandsupplied.Theclampingbandsecuringscrewmustbefittedinthecorrectorientation.

    MeTHoD 1

    Secure clamping band grips at three positions with screws provided

    Ø3mm

    MeTHoD 2

    Secure clamping band in position

    Check that the flue air duct has been securely retained by the clamping band and grips before fitting the appliance.

    Oncompletionofflueinstallation,continuewiththeapplianceinstallation,referringtotheappropriatesectionoftheapplianceinstallationinstructionssupplied.

  • 0020095198_02-06/11-Glow-worm

    INSTALLATION

    - 9 -

    3 Top Horizontal Telescopic flue Kit Ø60/100 - Pt. no. a2043600

    Checkthecontentsofyourkit.

    3.1 flue length and Terminal position

    RefertoyourInstallationinstructionssuppliedwiththeappliancetoconfirmthefluelengthavailableandlocationoftheflueterminal,thenproceedasfollows:

    • Withtheflueelbowtemporarilyfitted,measurethedistancefromtheexternalwalltotheelbow.

    noTe:*Iffittingthesealingcollar,addafurther12mmtotheoveralllength‘Y’,seediagramsbelow.

    • Settheflueductstotherequiredlength‘Y’.Ifthemeasurement‘Y’exceedsthetelescopicfluelength,thentheappropriatelengthofextensionpipewillberequired.

    15610

    ReaR flUe

    * ‘Y’

    15611

    sIDe flUe

    * ‘Y’

    DO NOT cut the telescopic flue, if the flue length cannot be achieved, the standard flue or extensions should be used.

    Ifdesirablethefluecanprojecttoamaximumof600mmbeyondtheoutsidewallface.

  • 0020095198_02-06/11-Glow-worm

    INSTALLATION

    - 10 -

    • Aligntheairductseams.

    • Markanddrilla3mmholeintheairduct,takingcarenottopiercetheinnerflueduct.

    • Securethejointwiththescrewsandtapeprovided.

    • Ifrequired,fitthesealingcollarontothelocatingringoftheflueterminal.

    • Removetheflueelbow.

    • Pushtheflueassemblyintothewall,untiltheendoftheassemblyprotrudesashortwayfromtheinsidefaceofthewall.Thiswillenabletheinternaltrimring(ifrequired)tobepositionedandallowtheflueassemblytobedrawnbackuptotheflueelbow.

    • Securetheflueelbowinpositionontopoftheappliancewithfourscrewssupplied.

    • Fittheflueassemblytotheelbow.

    • Fitthesecuringcollarintoposition.

    • Ensuringcorrectalignmentoftheairductseam,markthroughtwoofthepredrilledholesinthesecuringcollar.

    • Removesecuringcollaranddrilltwo3mmdiameterholesoneintheelbowandoneintheairduct,takecarenottopiercetheinnerflueduct.Securecollarandairductwithscrewsprovided.

    • Slidetheinternaltrimringbackagainstthewall,securinginplacewithasmallamountofsealantifrequired.

    • Checkthattheouterrubbersealingcollarmakesaneffectivesealagainstthewallface.

    Oncompletionofflueinstallation,continuewiththeapplianceinstallation,referringtotheappropriatesectionoftheapplianceinstallationinstructionssupplied.

  • 0020095198_02-06/11-Glow-worm

    INSTALLATION

    - 11 -

    4 Top Horizontal standard flue Kit Ø60/100 - Pt. no. a2043400

    Checkthecontentsofyourkit.

    4.1 flue length and Terminal position

    RefertoyourInstallationinstructionssuppliedwiththeappliancetoconfirmthefluelengthavailableandlocationoftheflueterminal,thenproceedasfollows:

    • Withtheflueelbowtemporarilyfitted,measurethedistancefromtheexternalwalltotheelbow.

    noTe:*Iffittingthesealingcollar,addafurther12mmtotheoveralllength‘Y’,seediagramsbelow.

    • Settheflueductstotherequiredlength‘Y’.Ifthemeasurement‘Y’exceedsthetelescopicfluelength,thentheappropriatelengthofextensionpipewillberequired.

    15610

    ReaR flUe

    * ‘Y’

    15611

    sIDe flUe

    * ‘Y’

    4.2 flue cutting• Separatetheflueductfromtheterminalbytwistingto

    releasetheterminalcatch.

    Theflueductcuttinglengthis(L+11mm),seediagram.

    noTe:Iffittingthesealingcollar,addafurther12mmtotheoveralllength.Howeverifdesirablethefluecanprojecttoamaximumof600mmbeyondtheoutsidewallface.

  • 0020095198_02-06/11-Glow-worm

    INSTALLATION

    - 12 -

    Theairductshouldbecutattheoppositeendtotheterminal

    andtheplasticflueductMUSTbecutattheoppositeendtotheterminalcatch.

    TheplasticflueductextensionsMUSTbecutattheoppositeendtoseal.

    • Inserttheflueductintotheairductterminalassembly,rememberingtoengagethecatchwithintheterminal.

    *noTe:Iffittingsealingcollaranadditional12mmisrequired

    4.3 flue fitting• Fitthesealingcollarontothelocatingringontheflue

    terminal,seediagram5.

    • Withtheflueterminalremoved,pushtheflueassemblyintothewall,externallyorinternally,untiltheendoftheassemblyprotrudesashortwayfromtheinsidefaceofthewall.Thiswillenabletheinternaltrimring(ifrequired)tobepositionedandallowtheflueassemblytobedrawnbackintotheflueelbow.

    • Securetheflueelbowinpositionontopoftheappliancewithfourscrewssupplied.

    • Fittheflueassemblytotheflueelbow.

    • Fitthesecuringcollarintoposition.

    • Ensuringcorrectalignmentoftheflue,markthroughtwoofthepredrilledholesinthesecuringcollar.

    • Removesecuringcollaranddrilltwo3mmdiameterholesoneintheelbowandoneintheairduct,takecarenottopiercetheinnerflueduct,securecollarwithscrewsprovided.

    • Slidetheinternaltrimringbackagainstthewall,securinginplacewithasmallamountofsealantifrequired.

    • Checkthattheouterrubbersealingcollarmakesaneffectivesealagainstthewallface.

    noTe:Iftheairandflueductshavebeencorrectlycuttotheinstructionsthesealingcollarshouldfitflushwiththeoutsidewall.Oncompletionofflueinstallation,continuewiththeapplianceinstallation,referringtotheappropriatesectionoftheapplianceinstallationinstructionssupplied.

  • 0020095198_02-06/11-Glow-worm

    INSTALLATION

    - 13 -

    5 Vertical concentric flue systemØ60/100 - Pt. no. 2000460480

    Comprisesofcomponentsselectedtosuityoursiterequirements,refertoFluecomponentstable.

    Makesureyouhaveallthenecessarycomponentsbeforeproceedingwiththeinstallation.

    X X X

    TerminalTerminal

    Terminal

    PITcHeD Roof

    flaT Roof RIDGe TeRMInal

    Themaximumlength“X”plusterminalassy,refertoinstallationinstructions.Foreach87.5ºor45ºX2bendsfitted,themaximumlengthmustbereducedby1metre.

    5.1 flue length and Terminal Position

    Themaximumfluelengthandterminalpositionaredescribedinyourinstallationinstructionssuppliedwithyourappliance.

    5.2 flue Installation

    Securetheflueadapterinpositionontopoftheappliancewithfourscrewssupplied.

  • 0020095198_02-06/11-Glow-worm

    INSTALLATION

    - 14 -

    Make sure the nib fits into the locating slot in the appliance casing to ensure correct orientation.

    Withtheflueadapterfitted,measurethefluelengthrequired.

    The use of a sliding sleeve will allow the appliance to be easily removed and replaced without dismantling the flue.

    Ensure that at least one fixing bracket supports each extension pipe used.

    DO NOT connect the final extension until the flue terminal has been positioned.

    • Securetheextensionpipetotheflueadapterwiththesecuringcollarsupplied,bypositioningthecollarcentrallyoverthejointthentighteningthetwoscrewsonthesecuringcollar.

    • Fitadditionalextensionpipesasrequiredusingthecollarandscrewssuppliedwitheachextensionpipe.

    • Tofit,positionthecollarcentrallyoverthejointandtightenthetwoscrewsonthesecuringcollar.

    • Usingtheholesprovidedinthesecuringcollardrillandinsertthetwoselftappingscrewssupplied,seediagram6.Therubber‘O’ringsofeachsectionshouldbelubricatedpriortoassembly.

    • Projecttheriseofthefluetorooflevel.Theflueterminalwillrequirea150mmhole.

    5.3 flue Terminal Installation

    Pitched Roof

    Fittherequiredpitchedroofweathercollaroverthe150mmholeintheroof.Makegoodthetilingorslatingaroundthecollarincorporatingtheflashingoftheweathercollar.Positiontheanglecapovertheweathercollarinthecorrectorientationtoattainthecorrectangleforyourroof.

    flat Roof

    Fitthealuminiumweathercollaroverthe150mmholeintheroofensuringaweathertightseal.

    Fromabovecarefullyplacetheflueterminalthroughtheweathercollar.

    5.4 Ridge Tile Terminal

    Aridgetileterminalisavailable-partno.A2043800,seeFlueSystemsatthefrontofthisliterature.Theinstallationofaridgetilewillberequired.Asuitableridgetileismanufacturedby:-AspectEastAngliaLimitedTheOldMillEastHarlingNORWICHNR162QWWebsite:www.aspectroofing.co.ukContact:ChrisHaythorpeGeneralManager-TileDivisionTel:01953717777Fax:01953717164

  • 0020095198_02-06/11-Glow-worm

    INSTALLATION

    - 15 -

    FLAT ROOF

    1.

    TERMINAL

    2.

    3.

    5.

    10

    0-11

    05 SECURING

    COLLAR

    SECURINGSCREW

    SECURINGSCREW

    6.

    DO NOTSECURE

    4.

    TERMINAL

    PITCHED ROOF

    10

    0-11

    05

    SECURINGCOLLAR

    1.

    2.

    3.

    4.

    5.

    SECURINGSCREW

    SECURINGSCREW

    6.

    DO NOTSECURE

    5.5 flue Terminal cutting

    Shouldtheclearancesabovetheappliancetotheflueterminalnotallowforextensions,itispermittedtocuttheflueterminalensuringtherelationshipofflueandairductlengthsareretained.

    5.6 flue extension completion

    Withtheflueterminalpositionedintheroof,measurethelengthofthepiperequiredtocompletetheconnectionbetweenterminalandextension.Ifatelescopiclengthcannotbeused,thenanextensionpipecanbecuttothecorrectlength.Cutthefluetothedesiredlengthmeasuringfromthe‘O’ringendanddiscardtheplainendofthetube.Thecutsmustbesquareandmadefreeofburrstoallowcorrectassembly.

    noTe:Thefluepipeis10mmlongerthantheairpipe.

    Carefullypushtheterminalassemblyupwardstoallowroomforfittingthefinalfluepiece.Fitafixingbrackettotheterminalassembly.Pulltheterminalassemblydownandjointothefluesystem.Ensurethattheterminalismakingaweathertightsealontheweathercollar.Securethefixingbracketfittedtotheterminaltotheroofingstrutsorapurposemadebatton.

  • 0020095198_02-06/11-Glow-worm

    INSTALLATION

    - 16 -

    6 accessories

    6.1 Deflector flue Terminal Kit Ø60/100

    Checkthecontentsofyourkit.

    Part no. 0020060582 - blackPart no. 0020060583 - White

    Installation Instructions

    www.glow-worm.co.uk

    Deflector flue terminal kit

    Part No. A200*****

    Because of our constant endeavour for improvement, details may vary slightly from those shown in these instructions.

    Glow-worm, Nottingham Road, Belper, Derbyshire. DE56 1JT

    00

    20

    06

    82

    79

    -02

    0

    4 .

    08

    General/Sales enquiries:

    Tel: (01773) 828100 Fax: (01773) 828070

    Installation refer to diagram 2.

    The terminal kit fits onto the telescopic and standard

    horizontal flue, see diagram 1 for contents.

    NOTE: The deflector terminal kit can be fitted after the boiler

    and flue have been installed.

    Remove the rubber collar (a).

    Use a 8mm. flat screwdriver to bend catches inwards (b).

    Remove the flue terminal and flue duct (c).

    Remove the flue pipe from the flue terminal by twisting them

    against each other (d).

    Push the flue duct into the deflector flue terminal.

    NOTE: the catch on top (inside) the terminal must lock firmly

    into the notch on top of the flue duct (e).

    Fit the rubber collar supplied with the kit (f).

    Push the flue duct and terminal into the air duct make sure

    the seals fit tightly.The deflector part of the deflector flue terminal can be

    rotated 45o to the left or right if required (g).

    NOTE: Do not fit the deflector flue terminal with the deflector

    positioned downwards.

    If the boiler has not been fitted, continue as described in the

    installation, servicing and user instructions supplied with the

    boiler.To remove the deflector flue terminal from the air duct pull

    the locking strap down (h), this will release the two side

    locking positions (f).

    14697

    14696

    Diagram 1

    Diagram 2

    For Use WithGlow-worm High Efficiency

    Condensing CombinationBoilers

    (a)

    (b)

    (c)

    (d)

    (e)

    (g)

    (h)

    (f)

    TheDeflectorFlueTerminalkitwillfiteitherthetelescopicorstandardhorizontalfluesystemsandisdesignedtoberotated45ºfromthetopcentre,directingtheplumeawayfromopenings,people,cars,windowsetc.

    Itcanbefittedaftertheapplianceandfluehavebeeninstalled.

    Shouldthedeflectorterminalbepositionedunderasoffitorhorizontalsurface,itisallowedtoprojecttheflue600mmfromthewall,toallowthedischargeoffluegasesproducedintofreeair.

    Do not fit the deflector flue terminal with the deflector positioned downwards.

    6.2 Installation

    (a)Ifpreviouslyfitted,removetherubbercollar.

    (b)Usinga8mm.flatscrewdrivertoreleasethecatch.

    (c)Withdrawtheflueterminalandpipefromtheduct.

    (d)Removethefluepipefromtheterminal,twistandpull,discardtheterminal.

    (e)Locatethe“notch”onthepipe,alignwiththe“catch”onthedeflectorterminalandpushthepipeintoposition,ensuringthattheengagementissecure.

    (f)Fittherubbercollar

    (g)Rotatethedeflectortosuityourrequirements.

    (h)ReleasingStrap.

    (a)

    (b)

    (c)

    (d)

    (e)

    (f)

    (g)

    (h)

    Pushthefluepipeandterminalintotheairduct,makesurethesealsfittightly.Toremovedeflectorflueterminalfromtheairductpulllockingstrapdown(h),thiswillreleasebothsidelockingpositions(f).

  • 0020095198_02-06/11-Glow-worm

    INSTALLATION

    - 17 -

    6.3 blacK Terminal Kit Ø60/100

    Checkthecontentsofyourkit.

    Part no. a2043700

    TheBlackTerminalkitwillfiteitherthetelescopicorstandardhorizontalfluesystemsandcanbefittedafter

    theapplianceandfluehavebeeninstalled.

    6.4 Installation

    (a)Usinga8mmflatscrewdrivertoreleasethecatch.

    (b)Withdrawtheflueterminalandpipefromtheduct.

    (c)Removethefluepipefromtheterminal,twistandpull,discardtheterminal.

    (d)Locatethe“notch”onthepipe,alignwiththe“catch”ontheBlackterminalandpushthepipeintoposition,ensuringthattheengagementissecure.

    (e)Fittherubbercollar.

    Pushtheflueductandterminalintotheairductmakesurethesealsfittightly.noTe:theseamoftheairductmustbeatthetop.

  • 0020095198_02-06/11-Glow-worm

    INSTALLATION

    - 18 -

    flue length-Theconcentricandplumepipecanvary,butthemaximumfluelength,mustnotbeexceeded.

    TheplumemanagementkitfitsontotheconcentrichorizontalflueterminaloftheGlow-wormhighefficiencyappliancesandenablestheflueproductstoberoutedfurtherawayfromtheapplianceflueterminal,therebyreducingthevisualimpactofpluming.Itshouldnotbeusedtoovercometerminalpositionswhichdonotcomplywithstandardsormanufacturersinstructions.

    Theflueoutletsuppliedterminatesat87obutcan,ifrequired,terminateverticallyorat45°bysimplyusingtheappropriateaccessory.

    Sitingcaneitherbeonawallfacewiththeterminalexhaustingatrightanglestothewallorabovetheeavesofabuilding.Werecommendthatterminalsexhaustingverticallyabovetheeavesaresecured.

    Theterminationoftheplumemanagementkit,shouldnotbelessthan2metresabovegroundlevel.

    6.5 Plume Management Kit Ø60/100

    Forusewithconcentricfluesystems60/100,partno.A2043400andpartno.A2043600.Checkthecontentsofyourkit.

    Wallconnector

    Pipe fixingbracket (3 off) 1M Pipe

    (2 off)

    87° bendwith birdprotection

    contents of KitWhitekit:A2044100,Blackkit:A2044000

    *noTe:Foreveryelbowthefluepipelengthshouldbereducedbythefollowingamounts:

    1x90°=1metre

    2x90°=2metres

    1x45°=0.5metres

    2x45°=1metre

    Thetotalfluelength(plumemanagementkit+concentric)mustnotexceedthemaximumtotalfluelengthoftheappliance.

    Example:Ultracom,“a”=4.0m+“b”=6.0m=10.0mmax.

    Plume and Concentric Flue Length

    a = flUe PIPe lenGTH (metres) a+bMaximum

    combinedfluelength0.5 1.0 1.5 2.0 2.5 3.0 3.5 4.0 4.5 5.0 5.5 6.0

    b =

    flU

    e le

    nG

    TH

    ULTRACOM2 9.5 9.0 8.5 8.0 7.5 7.0 6.5 6.0 5.5 5.0 4.5 4.0 10.0ULTRACOM235STORE 9.5 9.0 8.5 8.0 7.5 7.0 6.5 6.0 5.5 5.0 4.5 4.0 10.0

    ULTRACOM 9.5 9.0 8.5 8.0 7.5 7.0 6.5 6.0 5.5 5.0 4.5 4.0 10.0FLEXICOM 7.5 7.0 6.5 6.0 5.5 5.0 4.5 4.0 3.5 3.0 2.5 2.0 8.0ULTRAPOWER 7.5 7.0 6.5 6.0 5.5 5.0 4.5 4.0 3.5 3.0 2.5 2.0 8.0BETACOMa 5.5 5.0 4.5 4.0 3.5 3.0 2.5 2.0 1.5 1.0 - - 6.0

  • 0020095198_02-06/11-Glow-worm

    INSTALLATION

    - 19 -

    6.6 Terminal siting

    Refer to the diagram below and the appropriate clearances for the flue outlet terminal in relation to openings, air inlet etc., these must be adhered to.

    Theminimumsitingdimensionsfortheterminalpositions,A,B,Cstatedinthediagram,canbeappliedwhenaplumemanagementkitisfitted.

    MInIMUM sITInG foR HoRIZonTal flUe aIR InleT MM

    A)DIRECTLYBELOWANOPENINGWINDOW 50 DIRECTLYBELOWANOPENING,AIRBRICK 25

    B)DIRECTLYABOVEANOPENINGWINDOW 50 DIRECTLYABOVEANOPENING,AIRBRICK 25C) HORIZONTALLYTOANOPENINGWINDOW 50

    HORIZONTALLYTOANOPENING,AIRBRICK 25

    MInIMUM sITInG DIMensIons foR fanneD flUe TeRMInals PosITIon

    MInIMUM sITInG foR PlUMe ManaGeMenT KIT flUe oUTleT MM

    D)DIRECTLYBELOWANOPENING,AIRBRICK, OPENINGWINDOWS(HorizontalDischarge) 300

    E)DIRECTLYABOVEANOPENING,AIRBRICK, OPENINGWINDOWS(HorizontalDischarge) 300

    F) HORIZONTALLYTOANOPENING,AIRBRICK, OPENINGWINDOWS 300

    G) ABOVEROOFLINE 300

    ForfurtherguidanceonsitingrequirementsconsultBS5440-1:TableC.1

    a

    a

    b

    c

    G

    D,e

    f15572

    Theminimumlengthis500mm,threeexamplesareshowninthediagramsbelow.

    Additionalelbows,bendsand1Mextensionscanbeusedasrequired.

    1MExtension(white) A2044300 87°bend(white) A2044700 2x45°elbows(white) A2044500 1MExtension(black) A2044200 87°bend(black) A2044600 2x45°elbows(black) A2044400

    21/2°

    Horizontal Left or Right

    IMPORTANT:Flue must always slope at least(44mm / m) towards the boiler

    500

    min

    . dis

    tanc

    e

  • 0020095198_02-06/11-Glow-worm

    INSTALLATION

    - 20 -

    AIRINLET

    FLUEOUTLET

    6.7 Installation

    Theplumemanagementkitcanbefittedwhentheapplianceandfluearebeingfitted,oraftertheapplianceandfluehavebeeninstalled.

    Usea8mm.flatscrewdrivertobendcatchesinwards.

    8mmScrewdriver

    Horizontal Flue

    FlueTerminalAir

    Duct

    FlueDuct

    Removetheflueterminalandflueduct.

    Removethefluepipefromtheflueterminalbytwistingthemagainsteachother.

    45° Left or Right

    Minimum installationlength 500mm from air inletto top of vertical, horizontaland 45° outlet terminal.

    500

    min.

    dist

    ance

    Vertical

    Minimum installationlength 500mm from air inletto top of vertical, horizontaland 45° outlet terminal.

    500

    min

    . dis

    tanc

    e

    AIRINLET

    FLUEOUTLET

  • 0020095198_02-06/11-Glow-worm

    INSTALLATION

    - 21 -

    Pushthewallconnectorontotheflueduct.

    noTe:thecatchontop(inside)ofthewallconnectormustlockfirmlyintothenotchontopoftheflueduct.

    Fittherubbercollar.

    Pushtheflueductandwallconnectorintotheairductmakesurethesealsfittightly.

    Catch

    Wall Connector

    noTe:Theseamoftheairductmustbeatthetop.

    Iftheappliancehasnotbeenfitted,continueasdescribedintheinstallation,instructionssuppliedwiththeappliance.

    Usingthe1Mpipes,pipefixingclipsand87°bendwithbirdprotectionbuildthe(Allpushfit)plumemanagementkitfromthefittedwallconnectortotheselectedlocationfortheflueexit.Ensuringthejointsaretotallysealed.Thefluepipeswillexpandwhenheatedleave1cmexpansiongapineachconnection.

    The flue should always have a fall of at least 21/2° (44mm/metre) towards the appliance.

    Whencutting1Mpipestodesiredlength,cuttheoppositeendtothesealandremoveallburrs.

    The flue seals are sensitive to mineral oil based lubricants. Do not grease the seals. If the seals do need to be lubricated use only water.

    Take care when inserting not to push out the seals.

    Additionalpipe,87°bendsand45°elbowsmaybeusedasnecessary.

    Usingthepipefixingbracketssupplied,securethestraightpipetothewall.

    The first bracket must be positioned as close to the Wall Connector as possible.

    PIPEFIXINGBRACKETS

    Thestraightpipemustbesecuredeverymetreandateachchangeofdirectionsomorebracketsmayberequired(3supplied).

    55

    LockingPosition Collar

  • 0020095198_02-06/11-Glow-worm

    INSTALLATION

    - 22 -

    6.8 Termination above eaves

    TheHorizontalterminationshouldbeterminated100mmabovetheeaves.Theverticalflueoutletshouldbeaminimumdistanceof300mmabovetheeaves.

    Exposedsiteconditionsmayrequirethatthefluebesecuredasdescribedindiagram.

    6.9 Termination

    Theterminationcanbechangedfrom87°horizontalto45°orvertical.

    Toachievethisremovethewirebirdprotectionguardfromthe87°Bend.RemovetheO-ringsealfromthe1MPipeor45°elbowandfitthewirebirdprotectionguardintothe1MPipeor45°elbowwheretheO-ringsealwasfitted.

    Itisnotnecessarytofitaterminalguardovertheappliancemainflueoutlet.Howevershouldtheplumemanagementkitterminaldischargeinaplacewhereitrequiresprotection,aguardshouldbefitted.

    VerticalTerminal

    45°Terminal

    Wall plate

    Stud bolt

    Pipe fixing bracket

    IMPORTANT:Remove the seal and fit the bird protection wire from the 87° bird protection bend

    Bird protection wire

    Seal

    MinimumClearanceVertical 300mm900 or 450 100mm

    90°Terminal (supplied)

    WERECOMMENDTHATTERMINALSABOVEEAVESARESECURED

    6.10 fixing Instructions

    TheseinstructionsaresuppliedtoenablethefluepipefromthePlumeManagementAssemblytobesecurelyfixedeitherattheeavesoronthegableendofabuildingwhentheflueterminalistobeterminatedabovetheroof.

    Thestudboltandwallplatefixingscanbeobtainedfromkitpt.no.A2043900andusedwiththepipefixingbracketsupplied.

  • 0020095198_02-06/11-Glow-worm

    INSTALLATION

    - 23 -

    flue systems and components

    7 flue systems and components

    SECURINGCOLLAR

    STANDARDTERMINALASSEMBLY

    TRIMPLATE

    TRIM RING

    SECURINGCOLLAR

    87BEND

    SCREW x 2

    SCREW x 2 SCREWx 2

    SCREW x 2

    º

    0.5m Pt No. 00201045531m Pt No. 00201045542m Pt No. 0020104555(incl. securing collar)

    45° Pt No. 0020104557(pack of 2 incl.2 securing collars)

    87° Pt No. 0020104556(incl. securing collar)

    Vertical flueadaptorPt No. 0020104550(incl. securing collar)

    SlidingsleevePt No. 0020104558

    Refer to page 28

    Refer to page 31

    Fixing bracket (5)Pt No. 0020104559

    Flue components Ø80/125

    Flue accessories Ø80/125

    Flat RoofWeather CollarPt No. 2000460478

    Pitched RoofWeather CollarPt No. 2000460479

    Top horizontal standard flue terminal Pt No. 0020104551

    Vertical concentric flue Pt No. 0020104552

  • 0020095198_02-06/11-Glow-worm

    INSTALLATION

    - 24 -

    25 mm15 mm

    5 mm

    CUT THISEND ONLY

    AIR DUCT

    TWIST

    INNERSECURINGCATCH

    FLUEDUCT

    5 mm

    noTe:Forassemblyreasonsdonotshortenanyairducttoalengthoflessthan100mm.Ifnecessaryshortentwoadjacentextensionstoachievetheoverallrequiredlength. noTe:Forinstallationswherethereisinsufficientmovementtoallowfittingoftheflueintoflueoutlet,aslidingsleeveisavailablePartNo.0020104558.Whenusingtheslidingsleeveboththeairandflueductsofthelastextensionmustbeshortenedbyafurther85mm.

    7.4 Installing the sliding sleeve

    Pushtheslidingsleeve(1)overthecutendoftheflueduct(2).Pullbacktheslidingsleevesothatitengagesintothesocket(3)oftheboiler(4).Ensurethattheslidingsleevepenetratesthesocketsuchthatthereisatleast20mmengagementatbothendsoftheslidingsleeve.Fittheairductclamp(7)overtheairducts(5and6)oftheextension/terminalandboileroutlet.Closethesnapclamp.

    Drilltwoholes3mmdiameterthroughtheairductclamp(7)(thecentreoftheholesshouldbe6mmfromtheedgeoftheclamp).Ensurethatthedrilldoesnotpenetratetheinnerflueduct.Screwtheairductclamptotheairductofthesleeveusingthescrewsprovided.

    Completetheinstallationoftheflueasdetailedintheseinstructions.

    7.1 Top Horizontal standard flue Ø80/125

    Refertodiagram1andcheckthecontentsofyourkit.

    Makesureyouhaveallthenecessarycomponentsbeforeproceedingwiththeinstallation.

    7.2 flue length and Terminal Position

    RefertoyourInstallationinstructionssuppliedwiththeappliancetoconfirmthefluelengthavailableandlocationoftheflueterminal,thenproceedasfollows:

    • Securetheflueadapterinpositionontopoftheappliancewithfourscrewssupplied.

    noTe:Makesurethenibfitsintothelocatingslotintheappliancecasingtoensurecorrectorientation.

    • Withtheflueelbowtemporarilyfitted,measurethedistancefromtheexternalwalltotheelbow.

    SIDE FLUE

    * ‘Y’

    • Ifthemeasurement‘Y’exceedstheachievablefluelength,960mm.thentheappropriatelengthofextensionpipeisrequired.

    7.3 extension cutting

    • Separatetheflueductfromtheterminalbytwistingtoreleasefromthesecuringcatchinsidetheair/flueduct

    • Whencutting,cutequalamountsofftheairductandflueduct.

    • Whenjoiningextensionsleaveagapof5mmbetweeneachairductthiswillleaveacorrectflueductconnectionof30mm.

  • 0020095198_02-06/11-Glow-worm

    INSTALLATION

    - 25 -

    1. 2.

    3. 4.

    5. 7. 6.

    7.5 fitting elbows

    The elbows must be correctly aligned to avoid undue stress on the joints and risk of leakage.

    • Theelbowfittedtothetopoftheboiler(1)shouldbetwistedby3°toensurethatthesecond87°elbow(2)exitsthewallperpendicular.

    7.6 flue Terminal assembly fitting

    • Pushtheflueterminalassemblyintothewall,externallyorinternally,untiltheendoftheassemblyprotrudesashortwayfromtheinsidefaceofthewall.Thiswillenabletheassemblytobedrawnbackintotheflueelbowontopoftheflueadapter.

    • Fittheinternaltrimplate.

    • Securetheflueelbowwiththesecuringcollarinpositionontopoftheverticalflueadapter.

    • Ensuringcorrectalignmentoftheflueterminalassemblytotheflueelbowandsecurewiththesecuringcollar.

    • Markthroughtwoofthepredrilledholesinthesecuringcollars.

    • Drill3mmdiameterholes,takecarenottopiercetheinnerflueduct.

    • Securethesecuringcollarstotheairduct,seeinset1.

    • Makegoodtheexternalwallfaceandfittheexternaltrimring.

    noTe:Theairinletmustprotrudecompletelybeyondthefaceoftheexternalwallandtheexternaltrimring.

    Oncompletionofflueinstallation,continuewiththeapplianceinstallation,referringtotheappropriatesectionoftheapplianceinstallationinstructionssupplied.

    SECURINGCOLLAR

    SECURINGCOLLAR

    TERMINALASSEMBLY

    MAXIMUM220mm

    SECURINGSCREW(4 OFF)

    SECURINGSCREW(2 OFF)

    INSET 1.

    VERTICALFLUEADAPTER

    INSET 2.

    EXTERNAL TRIM RING

    INTERNAL TRIM PLATE

    AIR INLET

    7.7 Horizontal flue Roof Termination

    OrdertheflueflashingfromfromUbbink,Northants,Telephone01280700211.

    • Followthepreviousinstructionsandthediagrambelow,topreparetheflueandfollowtheinstructionssuppliedwiththeflashing.

    82 - 90

  • 0020095198_02-06/11-Glow-worm

    INSTALLATION

    - 26 -

    TERMINAL

    x x

    PITCHED ROOF FLAT ROOF

    TERMINAL

    The maximum length X plusterminal, refer to installationinstructions.For every 87º or 2 x 45º bendsfitted, the maximum lengthmust be reduced by 1 metre.

    7.8 Vertical concentric flue Ø80/125

    Checkthecontentsofyourkit.

    Makesureyouhaveallthenecessarycomponentsbeforeproceedingwiththeinstallation.

    7.9 flue length and Terminal Position

    Determineyourmaximumfluelengthandterminalpositionrequired,asdescribedinyourinstallationinstructionssuppliedwithyourappliance,thenproceedasfollows:

    • Securetheflueadapterinpositionontopoftheappliancewithfourscrewssupplied.

    noTe:Makesurethenibfitsintothelocatingslotintheappliancecasingtoensurecorrectorientation.

    • Fittheflueterminalsasdescribedinthefollowingparagraphs,pitchedorflatroof.

    • Measurethefluelengthsrequired.Incaseofinstallationdirectlytotheboilerwithoutelbows,itisessentialthattherooftile/collarisverticallyalignedwiththeair/flueductoftheboiler.

    7.10 Pitched Roof Terminal Installation

    • Determinethepointwheretheverticalair/flueductandterminalassemblywillexittheroof.

    • Fittheflexiblepitchedroofweathercollar(2).overthe125mm.holeintheroof.Makegoodthetilingorslatingaroundthecollarincorporatingtheflashingoftheweathercollar.

    • Positiontheanglecapovertheweathercollarinthecorrectorientationtoattainthecorrectangleforyourroof.

    • Workingfromabove,inserttheverticalroofduct(1)throughtherooftileandpushitfirmlyintoplace.

    • Verticallyaligntheroofductandattachittotheroofstructurewiththefixingbracket(3)supplied.

    • Fittheboilerhangingbracketandinstalltheappliancewithreferencetotheinstallationandservicinginstructionssuppliedwiththeappliance.

  • 0020095198_02-06/11-Glow-worm

    INSTALLATION

    - 27 -

    7.11 flat Roof Terminal Installation

    Determinethepointwheretheverticalair/flueductandterminalassemblywillexittheroof.

    • Fitthealuminiumweathercollar(2).

    • Sticktheflatroofpenetrationcollarfirmlyintoplacewithadhesiveinaccordancewiththecodesofpracticeforflatroofs(CP144)toensureawatertightseal.

    • Workingfromabove,inserttheverticalroofduct(1)throughtheflatroofcollarandpushitfirmlyintoplace.

    • Verticallyaligntheroofductandattachittotheroofstructurewiththefixingbracket(3)supplied.

    • Fittheboilerhangingbracketandinstalltheappliancewithreferencetotheinstallationandservicinginstructionssuppliedwiththeappliance.

    7.12 flue Terminal cutting

    DONOTCUTTHEFLUETERMINALshouldtheclearancesabovetheappliancetotheflueterminalnotallowforextensions.

    7.13 fitting air/flue Duct extensions

    Withtheflueterminalpositionedintheroof,completetheconnectionbetweenterminalandadapter.

    • Separatetheflueductfromtheterminalbytwistingtoreleasefromthesecuringcatchinsidetheair/flueduct

    • Whencutting,cutequalamountsofftheairductandflueduct.

    • Whenjoiningextensionsleaveagapof5mm.betweeneachairductthiswillleaveacorrectflueductconnectionof30mm.

    noTe: Forassemblyreasonsdonotshortenanyairducttoalengthoflessthan80mm.Ifnecessaryshortentwoadjacentextensionstoachievetheoverallrequiredlength.

    noTe:SeeFittingair/flueductextensions/Fittingelbowsforfurtherdetailsontheinstallationofextensionsandelbows.

    • Pushtheslidingsleeve(6)firmlyintoplaceontheextension.

    • Jointheverticalroofduct(1)totheextension(4).

    • Jointheslidingsleeve(6)totheverticalflueadapter(5).

    Using the sliding sleeve allows the appliance to be easily removed and replaced without dismantling the flue.

    • Drilltwoholes3mmØthroughtheairductoftheflue/boilerclampatthemostconvienientholesontheairductsecuringclamp.(Ensurethatthedrilldoesnotpenetratetheinnerflueduct).Screwtheairductsecuringclamptotheairductsoftheflueassemblyandtheverticalflueadapterusingthescrewssupplied.

    • Ensurethatanyairductsecuringclampsusedarepositionedcentrallyandfixedtotheairductusingtheselftappingscrewssupplied.

    The air duct securing clamp MUST NOT be screwed to the bottom of the vertical air/flue duct and terminal accessory, this will allow for any slight movement in the roof structure.

    • Ensurethatatleastonefixingbracketsupportstheair/flueductateachextensionfitted.

    7.14 fitting elbows

    The elbows must be correctly aligned to avoid undue stress on the joints and risk of leakage.

    • Theelbowfittedtothetopoftheboiler(1)shouldbetwistedby3°toensurethatthesecond87°elbow(2)exitsthewallperpendicular.

    TERMINAL

    PITCHED ROOF

    82

    - 90

    5

    SECURINGCOLLAR

    1.

    2.

    3.

    4.

    5.

    SECURINGSCREW

    SECURINGSCREW

    6.

    DO NOTSECURE

    FLAT ROOF

    1.

    TERMINAL

    2.

    3.

    5.

    82

    - 90

    5 SECURINGCOLLAR

    SECURINGSCREW

    SECURINGSCREW

    6.

    DO NOTSECURE

  • GLOW-WORM

    Nottingham Road, Belper, Derbyshire. DE56 1JT

    Because of our constant endeavour for improvement, details may vary slightly from those shown in these instructions.

    www.glow-worm.co.uk

    Subjecttoengineeringchanges

    0020095198_02-0