Pinpoint power problems faster, safer and in greater detail The Fluke 434 and 435 three-phase power quality analyzers help you locate, predict, prevent and troubleshoot problems in three- and single-phase power distribution systems. Troubleshooting is faster with on-screen display of trends and cap- tured events, even while background recording continues. The new IEC standards for flicker, harmonics and power quality are built right in to take the guess work out of power quality. Fluke 430 Series Three-Phase Power Quality Analyzers Technical Data Troubleshoot real-time: Analyze the trends using the cursors and zoom tools-even while background recording continues Highest safety rating in the industry: 600 V CAT IV/1000 V CAT III rated for use at the service entrance Automatic Transient Mode: Capture 200 kHz waveform data on all phases simultaneously up to 6 kV Fully Class-A compliant: Conduct tests according to the stringent international IEC 61000-4-30 Class-A standard Measure all three phases and neutral: With included four current probes AutoTrend: Every measurement you see is always automatically recorded, without any setup System-Monitor: Up to ten power quality parameters on one screen according to EN50160 power quality standard Inrush mode: For troubleshooting nuisance circuit breaker tripping View graphs and generate reports: With included analysis software Logger function: Configure for any test condi- tion with memory for over 400 parameters at user defined intervals Mains signaling: Measure interference from ripple control signals at specific frequencies Battery Life: Seven hours operating time per charge on NiMH battery pack Warranty: Rugged, handheld troubleshooter with Fluke three-year warranty

Upload: nguyenhanh

Post on 15-May-2018

219 views

Category:

Documents


0 download

TRANSCRIPT

Pinpoint power problems faster, safer and in greater detail

The Fluke 434 and 435 three-phase power quality analyzers help you locate, predict, prevent and troubleshoot problems in three- and single-phase power distribution systems. Troubleshooting is faster with on-screen display of trends and cap-tured events, even while background recording continues. The new IEC standards for flicker, harmonics and power quality are built right in to take the guess work out of power quality.

Fluke 430 Series Three-Phase Power Quality Analyzers

Technical Data

•Troubleshoot real-time:Analyzethetrendsusingthecursorsandzoomtools-evenwhilebackgroundrecordingcontinues

•Highest safety rating in the industry:600VCATIV/1000VCATIIIratedforuseattheserviceentrance

•Automatic Transient Mode: Capture200kHzwaveformdataonallphasessimultaneouslyupto6kV

•Fully Class-A compliant:ConducttestsaccordingtothestringentinternationalIEC61000-4-30Class-Astandard

•Measure all three phases and neutral:Withincludedfourcurrentprobes

•AutoTrend:Everymeasurementyouseeisalwaysautomaticallyrecorded,withoutanysetup

•System-Monitor:UptotenpowerqualityparametersononescreenaccordingtoEN50160powerqualitystandard

• Inrush mode:Fortroubleshootingnuisancecircuitbreakertripping

•View graphs and generate reports:Withincludedanalysissoftware

•Logger function:Configureforanytestcondi-tionwithmemoryforover400parametersatuserdefinedintervals

•Mains signaling:Measureinterferencefromripplecontrolsignalsatspecificfrequencies

•Battery Life:SevenhoursoperatingtimeperchargeonNiMHbatterypack

•Warranty:Rugged,handheldtroubleshooterwithFlukethree-yearwarranty

ApplicationsFrontline troubleshooting –quicklydiagnoseproblemson-screentogetyouroperationbackonlinePredictive maintenance –detectandpreventpowerqualityissuesbeforetheycausedowntimeQuality of service compliance –validateincomingpowerqualityattheserviceentranceLong-term analysis –uncoverhard-to-findorintermittentissuesLoad studies –verifyelectricalsystemcapacitybeforeaddingloadsEnergy assessments –quantifyenergycon-sumptionbeforeandafterimprovementstojustifyenergysavingdevices

2FlukeCorporationFluke430SeriesThree-PhasePowerQualityAnalyzers

Measureallpowerparameters,findeventsandanomaliesinseconds

CAT IV 600 V and CAT III 1000 V safety ratingDesignedtohelpprotectyouandyourequip-ment,theFluke430SeriesanalyzersandaccessoriesareallcertifiedtomeetthestringentstandardsforuseinCATIV600VandCATIII1000Venvironments.TheyarethefirsttoolsoftheirkindtocarrytheCATIVratingforuseinpowerconnectionsandoutletsthroughoutalow-voltagepowerdistributionsystem.

Troubleshoot real-timeAutoTrendfeatureprovidesfastinsightintochangesovertime.Everydisplayedreadingisautomaticallyrecordedwithouthavingtosetthresholdsorintervals.Analyzethetrendsusingthecursorsandzoomtools—evenwhileback-groundrecordingcontinues.

AutoTrendautomaticallyrecordsalldisplayedparam-etersinthebackground.Togglebetweendataandtrendview,andusecursorsandzoomtoanalyzemea-surementswithoutinterrupt-ingtherecording.

Simplemenustructurewithlogicalfunctiongroup-inggivesfastaccesstokeymeasurements.

3FlukeCorporationFluke430SeriesThree-PhasePowerQualityAnalyzers

Inrushfunctionautomaticallytriggersoffofcurrent,andcapturesstartupmeasure-mentsonmotorsandotherdevicestohelpdeterminetriplevels.

Measures everything Measuretrue-rmsandpeakvoltageandcur-rent,frequency,dipsandswells,transients,interruptions,powerandpowerconsumption,peakdemand,harmonicsuptothe50th,inter-harmonics,flicker,mainssignaling,inrushandunbalance.

Logger: record the detail you needUser-configurable,long-termrecordingofMIN,MAXandAVGreadingsforupto100parametersonall4phases.Enoughmemoryisavailabletorecord400parametersforuptoamonthwith10minuteresolution,orcapturesmallervariationswithresolutiondownto0.5seconds.

What is Class-A conformity? Powerqualitymeasurementisarelativelynew,andquicklyevolvingfield.Therearehundredsofmanufacturersaroundtheworldwithuniquemeasurementmethodologies.Whereasbasicsingle-andthree-phaseelectricalmeasurementslikermsvolt-ageandcurrentweredefinedlongago,manypowerqualityparameterswerenotpreviouslydefined,forcingmanufactur-erstodeveloptheirownalgorithms.Withsomuchvariationbetweeninstruments,electricianstendtowastetoomuchtimetryingtounderstandaninstrument’scapabilitiesandmeasure-mentalgorithmsinsteadofunderstandingthequalityofthepoweritself!

ThenewIEC61000-4-30Class-Astandardtakestheguess-workoutofselectingapowerqualityinstrument.ThestandardIEC61000-4-30definesthemeasurementmethodsforeachparametertoobtainreliable,repeatableandcomparableresults.Inaddition,theaccuracy,bandwidthandminimumsetofparametersareallclearlydefined.

Fully Class-A compliant TheFluke435isfullycompliantwiththenewIEC61000-4-30Class-Astandard.Withthispowerfulcapability,allmeasurementswillbeconsistentandreliableinaccordancewiththelatestinternationalstandard.

IEC 61000-4-30 Class-A Compliance435 434

Measurementalgorithms • •

Voltageaccuracy 0.1%ofVnom 0.5%ofVnom

Timesynchronization optionalwithGPS430accessory

Automatic transient display Everytimeaneventorvoltagedistortionisdetected,theinstrumenttriggersandautomati-callystoresvoltageandcurrentwaveformsonallthreephasesandneutral.Theanalyzerwillalsotriggerwhenacertaincurrentlevelisexceeded.Upto40dips,swells,interruptionsandtran-sientscanbecapturedthisway.Youcanseevoltagetransientsashighas6kVandasfastas5microseconds.

System-Monitor: Summary screen of overall power quality health AsinglepushoftheMONITORbuttondeliversadashboarddisplayofrmsvoltage,harmon-ics,flicker,interruptions,rapidvoltagechanges,swells,unbalance,frequencyandmainssignal-ing.Thedashboardisupdatedlive,showingcomplianceofeachparametertoEN50160limitsoryourownlimits.Color-codedbarsclearlyshowwhichparametersareinside(pass)oroutsidelimits(fail).Duringamonitorsession,youcaneasilydrilldowntomoredetailofanyparametertoviewandcaptureitstrendforareport.

Extensive data analysis possibilities TheFluke430Seriesprovidesthreewaystoanalyzemeasurements.Cursorsandzoomtoolscanbeused‘live’whiletakingmeasure-ments,or‘offline’onstoredmeasurementdata.Additionally,thestoredmeasurementscanbetransferredtoaPCwiththeincludedsoftwaretoperformcustomanalysisandcreatereports.Measurementdatacanalsobeexportedtocom-monspreadsheetprograms.Storeupto10mea-surementdatasetsandupto50screencapturesforuseinreports.

TheSystem-Monitorover-viewscreengivesinstantinsightintowhetherthevoltage,harmonics,flicker,frequencyandthenumberofdipsandswellsfalloutsidethesetlimits.

Adetailedlistisgivenofalleventsfallingoutsidethesetlimits.Byscrollingthroughtheeventslistandselectinganevent,theeventcanbeanalyzedindetail.

4FlukeCorporationFluke430SeriesThree-PhasePowerQualityAnalyzers

Performcustomanalysisandcreatereportswithincludedsoftware.Measurementdatacanalsobeexportedtocom-monspreadsheetprograms.

5FlukeCorporationFluke430SeriesThree-PhasePowerQualityAnalyzers

Easy-to-use Pre-programmedsetupsanduser-friendlyscreensmakepowerqualitytestingassimpleasyouwouldexpectfromFluke.Thehigh-resolu-tioncolorscreenupdatesevery200mSanddisplayswaveformsandwiringdiagramscolorcodedtoindustrystandards.Handyon-screenwiringdiagramsforallcommonlyusedthree-phaseandsingle-phaseconfigurationsguideyouthroughconnections.

Scopeviewshowsvoltageandcurrentwaveformsforthreephaseinstallations.Youcantoggletoaphasordiagramatanytime.

Phasordiagramshowsvolt-ageandcurrentunbalance,andhelpsverifyconnections.

Thefullcolordisplayusesregionspecificindustry-standardcolor-coding(userselectable)tocorrelatemeasurementswithactualwiring.

Viewrecordeddatainsimplegraphsandtables.

Easilycustom-izethereportbyselectingtimeperiodandmeasurementstoinclude.

Generate reports and view graphs with Fluke Power Log SoftwareDesignedtoquicklyviewrecordeddata,theincludedPowerLogsoftwaredisplaysallrecordedparametersoninteractivetrends.Generateaprofessionalreportwiththe‘ReportWriter’function,orcopyandpasteimagesintoreportdocumentmanually.

Createprofessionalreportsquicklyandeasily.

6FlukeCorporationFluke430SeriesThree-PhasePowerQualityAnalyzers

Technical specifications

Thespecificationsoftheinstrumentareverifiedusingthe“implementationverification”table3asspecifiedinIEC61000-4-302002Chapter6.2.Accuracyisspecifiedin%ofreadingunlessotherwisespecified.SpecificationsarevalidformodelsFluke435andFluke434unlessotherwisespecified.

Input characteristicsVoltage inputs

Number of inputs 4(3phases+neutral)dc-coupled

Maximum input voltage 1000Vrms

Nominal voltage range 50Vto500VaccordingIEC61000-4-30.Selectablefrom1Vto1000V.

Maximum peak measurement voltage 6kV

Input impedance 4MΩ//5pF

Bandwidth >10kHz,upto100kHzfortransientdisplay

Scaling 1:1,10:1,100:1,1000:1andvariable

Current inputs

Number of inputs 4(3phases+neutral)dc-coupled

Type ClamponcurrenttransformerwithmVoutput

Range 1Armsto400Armswithincludedclamps(i400s/Fluke434)30Ato3000Armswithincludedclamps(i430-flex/Fluke435)1Armsto3000Armswithoptionalclamps

Input impedance 50kΩBandwidth >10kHz

Scaling 0.1,1,10,100,1000mV/A,variable,i5sandi430-flex

Nominal frequency 40Hzto70Hz

Sampling system

Resolution 16bitanalogtodigitalconverteron8channels

Maximum sampling speed 200kS/soneachchannelsimultaneously

RMS sampling 5000sampleson10/122cyclesaccordingIEC61000-4-30

PLL synchronization 4096sampleson10/122cyclesaccordingIEC61000-4-7

Display modesWaveform display AvailableinScopeandTransientmode

Captures8waveformssimultaneouslyDisplayupdaterate5xpersecondUpto10/122timeshorizontalzoomCursors:singleverticallineshowingmin,max,avgreadingatcursorposition

Phasor ShowsrealtimephasordiagramAvailableinScopeandUnbalancemodeDisplayupdaterate5xpersecond

Meter readings AvailableinVolts/Amps/Hertz,Harmonics,PowerandEnergy,Flicker,UnbalanceandLogger4mode

AutoTrend graph AvailableinVolts/Amps/Hertz,DipsandSwells,Harmonics,PowerandEnergy,Flicker,Unbalance,Inrush,MainsSignaling4Logger4andMonitormodeCursors:singleverticallineshowingwithmin,max,avgreadingatcursorposition

Bargraph AvailableinHarmonicsandMonitormode

Event list AvailableinDipsandSwells,MainsSignaling4,Logger4andMonitormode

7FlukeCorporationFluke430SeriesThree-PhasePowerQualityAnalyzers

Measurement modesScope Vrms,Arms,Vcursor,Acursor,Vfund,Afund,Hz,Vphaseangles,Aphaseangles

Volts/Amps/Hertz Vrms,Vpk,VCrestFactor,Arms,Apk,ACrestFactor,Hz

Dips and swells Vrms½,Arms½Capturesupto1000eventswithdate,time,duration,magnitudeandphaseidentificationwithprogrammablethresholds

Harmonics dc, 1 to 50 HarmonicVolts,THDVolt,HarmonicAmps,THDAmps,KAmps,HarmonicWatts,THDWatts,KWatts,InterharmonicVolts4,InterharmonicAmps4(relativetofundamentalortototalrms)

Power and energy Watts,VA,VAR,Powerfactor,Cosj/DPF,Arms,Vrms,kWh,kVAh,kVARh,peakdemandintervalusingtrend,KYZrevenuemeterverificationviaoptionalinput.

Flicker Pst(1min),Pst,Plt,PF5,Vrms½,Arms½,Dc,Dmax,TD

Unbalance Vneg,Vzero,Aneg,Azero,Vfund,Afund,Hz,Vphaseangles,Aphaseangles

Transients Vrms,Arms,Vcursor,Acursor

Inrush currents InrushCurrent,Inrushduration,Arms½,Vrms½

Mains signaling4 Relativesignalingvoltageandabsolutesignalingvoltageaveragedoverthreesecondsfortwoselectablefrequencies

Logger4 Measuresandrecordsupto100parametersonall4phasessimultaneouslywithselecableaveragingtimeCapturesupto10000eventswithdate,time,duration,magnitudeandphaseidentificationwithprogrammablethresholds

System monitor Vrms,Arms,HarmonicVolts,THDVolts,Plt,Vrms½,Arms½,Vneg,Hz,dipsandswells,unbalanceAllparametersaremeasuredsimultaneouslyinaccordancewithEN50160UsingFlaggingtoindicateunreliablereadingsaccordingIEC61000-4-30

Accuracy, resolution and rangeMeasurement range Resolution Accuracy

Volt/Amps/Hertz

Vrms (ac+dc) Fluke435 Fluke434

1Vrmsto600Vrms600Vrmsto1000Vrms1Vrmsto1000Vrms

0.01Vrms0.01Vrms0.1Vrms

±0.1%ofnominalvoltage±0.1%±0.5%ofnominalvoltage

Vpk 1Vpkto1400Vpk 1V 5%ofnominalvoltage

Voltage Crest Factor (CF) 1.0to>2.8 0.01 ±5%

Arms (ac+dc) Fluke435 Fluke434 Fluke434withi400s Fluke435withi430Flex

0kArmsto20.00kArms10kArmsto20.00kArms10Armsto40/400Arms30Armsto3000Arms

0,001Armsto10Arms10,001Armsto10Arms10.1and1Arms1Arms

±0.5%±5counts3±1%±5counts3±1%±5counts3±0.5%±20counts3

Apk using 1 mV/A scaling 0Apkto5500Apk 1A ±5%

A Crest Factor (CF) 1to10 0.01 ±5%

Hz5 Fluke435@50Hznominal Fluke435@60Hznominal Fluke434@50Hznominal Fluke434@60Hznominal

42.500Hzto57.500Hz51.000Hzto69.000Hz42.50Hzto57.50Hz51.00Hzto69.00Hz

0.001Hz0.001Hz0.01Hz0.01Hz

±0.01Hz±0.01Hz±0.01Hz±0.01Hz

Dips and swells

Vrms½ (ac+dc) Fluke435 Fluke434

0.0%to200%ofnominalvoltage0.0%to200%ofnominalvoltage

0.1Vrms0.1Vrms

±0.2%ofnominalvoltage±1%ofnominalvoltage

Arms½ (ac+dc) Fluke435 Fluke434 Fluke434withi400s Fluke435withi430Flex

0Armsto20,000Arms10Armsto20,000Arms10Armsto400Arms30Armsto3000Arms

0,001Armsto10Arms0,001Armsto10Arms0.1Armsand1Arms1Arms

±1%±10counts3±2%±10counts3±2%±10counts3±1%±20counts3

Threshold levels ProgrammablethresholdsinpercentofnominalvoltageEventdetectionbasedupon½cyclermsvoltagesCapturesdips,swells,interruptionsandrapidvoltagechanges

Duration hhh,mm,ss,mmm Halfcycle Onecycle

8FlukeCorporationFluke430SeriesThree-PhasePowerQualityAnalyzers

Measurement range Resolution Accuracy

Harmonics

Harmonic order (n) DC,1to50grouping:harmonicgroupsaccordingtoIEC61000-4-7

Inter-Harmonic order Off,1to49grouping:harmonicandinterharmonicsubgroupsaccordingtoIEC61000-4-7

Vrms Relative(%f): Fluke435Absolute: Fluke434Absolute:

0.0%to100.0%0.0Vrmsto1000Vrms0.0Vrmsto1000Vrms

0.1%0.1Vrms0.1Vrms

±0.1%±nx0.1%(±0.4%for%r)±0.05%ofnominalvoltageif<1%ofnominalvoltage±5%if≥1%ofnominalvoltage±5%±2counts

Arms Relative(%f): Absolute:

0.0%to100.0%0.0mVto4000mVxclampscaling

0.1%1mVrmsxclampscaling

±0.1%±nx0.1%(±0.4%for%r)±5%±5counts

Watts Relative:(Harmonicsonly) Absolute:

0.0%to100.0%dependsonclampandvoltagescaling

0.1% ±nx2%±5%±nx2%±10counts

DC Relative: Fluke435AbsoluteV: Fluke434AbsoluteV: AbsoluteA: AbsoluteW:

0.0%to100.0%0.0Vto1000V0.0Vto1000V0.0mVto4000mVxclampscalingdependsonclampandvoltagescaling

0.1%0.1V0.1V1mVrmsxclampscaling0.1Vdependsonscaling

±0.1%VandA(±2%Watt)±0.2%ofnominalvoltage±5%±10counts±5%±10counts±5%±10counts

THD(n=40) (relative%for%r) 0.0%to100.0% 0.1% ±2.5%VandA(±5%Watt)

Hz 0Hzto3500Hz 1Hz ±1Hz

Phase angle Fluke435 Fluke434

-360ºto+0º-360ºto+0º

1º1º

±n×1º(8)±n×1.5º(8)

Power and energy

Watt(VA,VAR) Fluke435 Fluke434

1.0MWto20.00MW11.0MWto20.00MW1

0.1kWto1kW10.1kWto1kW1

±1%±10counts3±1.5%±10counts3

kWh6 (kVA6,kVAR6) 00.00kWhrto200.0GWhr100.00kWhrto200.0GWhr1

0.01Xhrto100Whr10.01Whrto100Whr1

±1%±10counts3±1.5%±10counts3

Power Factor 0to1 0.01 ±0.033

Cos j/DPF 0to1 0.01 ±0.033

Flicker

Pst (1min), Pst, Plt, PF5 instantenous Flicker

0.00to20.00 0.01 Within±5%oftabulatedvaluesaccordingIEC61000-4-15

Dc%, Dmax% and Time d(t) exceeds limits as described per IEC 61000-3-3

0.0%to±100.0%forDc%andDmax%and0.000sto9.999sforTime

0.1%forDc%andDmax%and10msforTime

±1%forDc%andDmax%and20msforTime

Unbalance

Volts Fluke435(neg.andzeroseq.) Fluke434(neg.andzeroseq.)

0.0%to5.0%0.0%to5.0%

0.1%0.1%

±0.15%±0.5%

Current (neg.andzeroseq.) 0.0%to20% 0.1% ±1%

Phaseangle volts current

-360.0°to0.0°-360.0°to0.0°

0.1º0.1º

±2counts±5counts3

Transient capture

Volts cursorreading rmsreading

±6000Vpk10Vrmsto1000Vrms

1V1V

±15%ofcursorreading±2.5%ofVnominal

Minimum detect duration 5µs

Sampling rate 200kS/s

Inrush mode

Arms (ac+dc) 0.000kArmsto20.00kArms1 0.001Armsto10Arms1 ±1%ofmeas±5counts

Inrush Duration mm:ss:mmmbetween7.5sto30minutesselectable

10ms ±20ms(Fnominal=50Hz)

Mains Signaling4

Threshold levels Thresholds,limitsandsignalingdurationisprogramablefortwoindependentsignalingfrequencies

Signaling frequency 60Hzto3000Hz 0.1Hz

Relative V% 0%to100%ofVnominal 0.1% ±0.4%

Absolute V3s (3secondaverage) 0.0Vto1000V 0.1V ±5%ofnominalvoltage

Accuracy, resolution and range cont.

9FlukeCorporationFluke430SeriesThree-PhasePowerQualityAnalyzers

Trend recordingMethod AutoTrendautomaticallyrecordsmin,maxandaveragevaluesovertimeforallreadingsbeingdisplayedforthe3

phasesandneutralsimultaneously

Volts/Amps/Hertz, Harmonics, Power and Energy, Flicker, Unbalance and Mains Signaling4 mode

Sampling 5readings/seccontinuoussamplingperchannel

Recording time From30minwith1seconddisplayresolutionupto450dayswith6hourdisplayresolution.

Zoom Upto6xhorizontalzoom

Memory 1800min,maxandavgpointsforeachreading

Duration 30min. 2.5hrs 7.5hrs 15hrs 30hrs 150hrs 450hrs 900hrs 75d 225d 450d

Resolution 1s 5s 15s 30s 60s 5min. 15min. 30min. 1hr 3hrs 6hrs

Dips and Swells mode

Sampling 100/1202readings/seccontinuoussamplingperchannel

Recording time From90secwith25msecdisplayresolutionupto450dayswith3hrdisplayresolution

Zoom Upto12xhorizontalzoom

Memory 3600min,maxandavgpointsforeachreading

Duration 90s 180s 6min. 12min. 30min. 1hr 2.5hrs 7.5hrs 15hrs 30hrs

Resolution 25ms 50ms 100ms 200ms 500ms 1s 2.5s 7.5s 15s 30s

Inrush currents and flicker PF5 mode

Sampling 100/1202readings/seccontinuoussamplingperchannel

Recording time From7.5secwith25msecdisplayresolutionupto30minwith500msecdisplayresolutionforInrushmeasurementsandupto2hrwith2.5secdisplayresolutionforPF5recordings

Zoom Upto12xhorizontalzoom

Memory 3600min,maxandavgpointsforeachreading

Duration 7.5s 15s 30s 90s 180s 6min. 12min. 30min.

Resolution 25ms 25ms 25ms 25ms 50ms 100ms 200ms 500ms

Logger mode

Sampling Combinationof5readings/secand100/1202readings/seccontinuoussamplingperchanneldependingontheparametermeasured

Recording time Dependsonselectedreadingsandaveragingtime

Zoom Twozoompositions,displayallor1x

Memory Userconfigurablesharedmemory,upto15MBonFluke435,upto7MBonFluke4344

No.ofreadingson3phases+N 1 10 100

Averagingtime 0.5s 10min. 2hrs 0.5s 10min. 2hrs 0.5s 10min. 2hrs

Max7durationusing15MB 66hrs 9years 100years

6hrs 333days

10years

18min. 31days 1year

Monitor mode

Sampling Combinationof5readings/secand100/1202readings/seccontinuoussamplingperchanneldependingontheparametermeasured

Recording time Upto1weekwith10minresoluton

Memory 1008min,maxandavgpointsforeachreading,10minuteresolution

Limits AccordingEN50160orcustomerdefinable

Measurement methodVrms, Arms 10/122cyclecontiguousnonoverlappingintervalsusing500/4162samplespercycleinaccordancewith

IEC61000-4-30

Vpeak, Apeak Absolutehighestsamplevaluewithin10/122cycleintervalwith40µssampleresolution

V Crest Factor MeasuresratiobetweentheVpeakandVrms

A Crest Factor MeasuresratiobetweentheApeakandArms

Hz Measuredevery10secinaccordancewithIEC61000-4-30

Vrms½, Arms½ Valueismeasuredover1cycle,commencingatafundamentalzerocrossing,andrefreshedeachhalf-cycle.ThistechniqueisindependentforeachchannelinaccordancewithIEC61000-4-30.

Harmonics Calculatedfrom10/12-cyclegaplessharmonicgroupmeasurementsonVoltageandAmpsaccordingtoIEC61000-4-7

Watt SelectableTotalorFundamentalrealpowerdisplayCalculatesaveragevalueofinstantaneouspowerover10/12cycleperiodforeachphaseTotalActivePowerPT=P1+P2+P3

10FlukeCorporationFluke430SeriesThree-PhasePowerQualityAnalyzers

VA SelectabletotalorfundamentalapparentpowerdisplayCalculatesapparentpowerusingVrmsxArmsvalueover10/12cycleperiodTotalapparentpowerisrootmeansquareofrealandreactivepower

VAR SelectabletotaloffundamentalreactivepowerdisplayCalculatesreactivepowerasrootofVAsquaredminuswattsquaredover10/12cycleperiodCapacitiveandinductiveloadisindicatedwithcapacitorandinductoricons

Power Factor Calculatedwatt/VA

Cos j/DPF Cosofanglebetweenfundamentalvoltageandcurrent

Unbalance ThesupplyvoltageunbalanceisevaluatedusingthemethodofsymmetricalcomponentsaccordingtoIEC61000-4-30

Flicker AccordingtoIEC61000-4-15flickermeter—functionalanddesignspecificationIncludes230V50Hzlampand120V60Hzlampmodels

Transient capture CaptureswaveformtriggeredonsignalenvelopeAdditionallytriggersondips,swells,interruptionsandAmpslevelasspecifiedbyIEC61000-4-30

Inrush current TheinrushcurrentbeginswhentheArmshalfcyclerisesabovetheinrushthreshold,andendswhentheArmshalfcyclermsisequaltoorbelowtheinrushthresholdminusauser-selectedhysteresisvalue.ThemeasurementisthesquarerootofthemeanofthesquaredArmshalfcyclevaluesmeasuredduringtheinrushduration.Eachhalf-cycleintervaliscontiguousandnon-overlappingasrecommendedbyIEC61000-4-30.Markersindicateinrushduration.CursorsallowmeasurementofpeakArmshalfcycle.

Mains signaling Measurementsarebasedon:eitherthecorresponding10/12-cyclermsvalueinterharmonicbinorthermsofthefournearest10/12-cyclermsvalueinterharmonicbinsperIEC61000-4-30LimitsetupforMonitormodefollowsEN50160“Meistercurve”

Time synchronization OptionalGPS430timesyncmoduleprovidestimeuncertainty≤20msor≤16.7ms2fortimetaggingofeventsandtimeaggregatedmeasurements.Whensynchoronisationbecomesunavailable,timetoleranceis≤1-s/24h

Wiring configurations1Ø + NEUTRAL Singlephasewithneutral

1Ø SPLIT PHASE Splitphase

1Ø IT NO NEUTRAL Singlephasesystemwithtwophasevoltageswithoutneutral

3Ø WYE ThreephasefourwiresystemWYE

3Ø DELTA ThreephasethreewiresystemDelta

3Ø IT ThreephasesystemwithoutneutralWYE

3Ø HIGH LEG FourwirethreephaseDeltasystemwithcentertappedhighleg

3Ø OPEN LEG Opendeltathreewiresystemwith2transformerwindings

2-ELEMENT ThreephasethreewiresystemwithoutcurrentsensoronphaseL2/B(2wattmetermethod)

2½-ELEMENT ThreephasefourwiresystemwithoutvoltagesensoronphaseL2/B

Measurement method cont.

General specificationsCase

Design Rugged,shockproofwithintegratedprotectiveholster

Drip and dust proof IP51accordingtoIEC60529whenusedintiltstandposition

Shock and vibration Shock30g,vibration:3gsinusoid,random0.03g2/HzaccordingtoMIL-PRF-28800FClass2

Display

Type Brightfull-colorLCDwithCCFLbacklight,80cd/m2

Size 115.2mmx86.4mm(4.5inx3.4in)

Resolution 320x240pixels

Contrast and brightness User-adjustable,temperaturecompensated

Memory

Screens 50screenmemories

Data 10datamemoriesforstoringdataincludingrecordings

Logger Userconfigurablesharedmemory,upto15MBonFluke435,Upto7MBonFluke4344

Limit templates 2preprogrammed,2administrator(programmableviaFlukeView®),2userlocations

Real-time clock TimeanddatestampforAutoTrend,TransientdisplayandSystemMonitor

11FlukeCorporationFluke430SeriesThree-PhasePowerQualityAnalyzers

Mechanical

Size 256mmx169mmx64mm(10inx6.5inx2.5in)

Weight 2kg(4.5lb)

Power

Line power Switchable115V,230Vadapterwithcountryspecificplug

Power adapter output voltage 15Vdcto23Vdc;useonlypoweradapterBC430

Battery power RechargeableNiMHBP190(installed)

Battery operating time >7hours

Battery charging time 4hours,8hoursfor/006version(instrumentoff)

Power saving Adjustabletimefordimmedbacklightwithonscreenpowerindicator

Standards

Measurement methods used IEC61000-4-30Class-A

Measurement performance Fluke435IEC61000-4-30Class-A,Fluke434IEC61000-4-30Class-B

Power quality EN50160

Flicker IEC61000-4-15

Harmonics IEC61000-4-7

Cross talk

Between V inputs -60dB@nominalfrequency

Voltage to current input -95dB@nominalfrequency

Safety

Compliance IEC/EN61010-1-2001CAN/CSAC22.2No61010-1-04ULstdNo61010-1SafetyRequirementsforElectricalEquipmentforMeasurement,ControlandLaboratoryUse,Part1:GeneralrequirementsRated:600VCATIV/1000VCATIIIPollutionDegree2

Max voltage on banana input 1000VCATIII/600VCATIV

Max voltage on current BNC input 42Vpeak

Environmental

Operating temperature 0°Cto+50°C(32°Fto122°F)batteryonly,0°Cto+40°C(32°Fto104°F)withadapter,withinspec+15°Cto+35°C(59°Fto95°F)

Storage temperature -20°Cto+60°C(-4°Fto+140°F)

Humidity 10°Cto30°C:95%RHnon-condensing;30°Cto40°C:75%RHnon-condensing;40°Cto50°C:45%RHnon-condensingbatteryonly

Maximum operating altitude 3000m.Derateto1000VCATII/600VCATIII/300VCATIVabove2000m

Maximum storage altitude 12km

Warranty Three-yearsonmainframe,one-yearonincludedaccessories

Printers and Interface

Type Serial,opticallyisolated.CompatiblewithPM9080(RS-232)orOC4USB(USB)

Baud rate 1200,2400,9600to115kB

Print out facility (B&W only) ViaoptionaladapterPM9080orPAC91

Print protocol EpsonFX/LQ,Deskjet,LaserJet,DPU-414orPostScript

General specifications cont.

Electro Magnetic Compatibility (EMC)Emission and immunity EN61326-1 Fluke434/435,includingstandardaccessories,conformswiththeEEC

directive89/336forEMCimmunity,asdefinedbyEN61326,withtheadditionofthetablebelow

Frequency Disturbance < 0.5 % Disturbance < 10 %

80MHzto400MHz Allranges

400MHzto600MHz Allotherranges 125Vrange

600MHzto1GHz Allranges

TheAnalyzerissusceptibleforRFfieldswithafieldstrengthof10V/m,between400MHzand600MHz(PerformancecriteriaB).

1Dependingonclampscaling,voltscaling1:1250Hz/60HznominalfrequencyaccordingtoIEC61000-4-303Addclampaccuracyandphaseshift4TheloggerandmainssignalingfunctionareoptionalfortheFluke434andstandardontheFluke435

5MeasuredonreferencevoltageinputA/L16Maximumtime9999hours7Estimatedduration8Add±(n-1)x2.5°foramplitudewhenusingi430-flex-4pk

12FlukeCorporationFluke430SeriesThree-PhasePowerQualityAnalyzers

Power quality analyzer selection table

435 434*

Measuresvoltage,current,dips,swells,interruptions,harmonics,inter-harmonics,flicker,power,energy,transients,frequency,unbalance,inrush,EN50160overview

• •

Loggerfunctionwithmulti-parameterlogging • optional*

Mainssignaling • optional*

Memorysize 16MB 8MB

Currentprobes 3000Aflexible(4)

40A/400Aclamp(4)

Carryingcase water-tighthardcasewithrollers ruggedhardcase

Software FlukePowerLogandFlukeView®

FlukeView®

*Optionalfunctionalitycanbeaddedwithupgradekit.

Ordering informationFluke-435 Three-PhasePower QualityAnalyzerFluke-434 Three-PhasePower QualityAnalyzer

435 Includes:Hardcarryingcasewithrollers,fourflexiblecur-rentprobes(i430-flex),fivetestleadsandclips,batterycharger,FlukeViewsoftware,PowerLogsoftware,opticalUSBcable,colorlocalizationset,GettingStartedmanual,UsersmanualonCD-ROM.

434 Includes:Hardcarryingcase,fourcurrentprobes(i400s),fivetestleadsandclips,batterycharger,FlukeViewsoftware,opticalUSBcable,colorlocalizationset,GettingStartedmanual,UsersmanualonCD-ROM.

Optional accessoriesi400s 40A/400Aswitchablecurrent clamp(includedw/434)I5sPQ3 3packof5Aprecisioncurrent clampsi430-flex-4pk 4packof3000Aflexiblecurrent probes(includedw/435)C435 Water-tighthardcasewithrollers (includedw/435)GPS430 GPStimesynchronizationmodule forFluke430seriesFluke434/LOG Upgradekitfor434,includes PowerLogsoftwareandenables loggerandmainssignaling function(accuracyandmemory notupgradeable)