  • FOAM SYSTEMS Design and Applications Manual

    Co

    ver

    No

    . F

    -20

    1120

    6

  • ANSUL®

    FOAM SYSTEMS DESIGN AND APPLICATIONS MANUAL

    ANSUL PART NO. 427448-05

    FEBRUARY 2, 2012

    © 2012 Tyco Fire Protection Products

    Marinette, WI 54143-2542

    Note: The converted metric values in this document are provided for dimensional reference only anddo not reflect an actual measurement.

  • REVISION RECORD2012-FEB-02 Page 1

    REV. 3

    Section 1

    6-1-07 F-93203 1

    6-1-07 F-93202 1

    6-1-07 F-9239 2

    6-1-07 F-83126 6

    6-1-07 F-8125 3

    6-1-07 F-83127 5

    6-1-07 F-9350 6

    6-1-07 F-81105 10

    6-1-07 F-2003282 1

    6-1-07 F-2005043 2

    6-1-07 F-2001072 2

    6-1-07 F-200208 1

    6-1-07 F-2004153 1

    6-1-07 F-2007003 New

    9-1-08 Page 1-3 2

    5-1-10 F-2009121 New

    5-1-10 F-93139 4

    5-1-10 F-9032-5 Out

    5-1-10 F-2009064 New/1

    2012-FEB-02 F-81297 6

    2012-FEB-02 F-83124 7

    2012-FEB-02 F-83125 7

    2012-FEB-02 F-2010265 New

    2012-FEB-02 F-2009161 New/1

    2012-FEB-02 F-2009162 New

    2012-FEB-02 F-2011240 New

    Section 2

    6-1-07 F-2005165 1

    6-1-07 F-85174 3

    6-1-07 F-9490 1

    6-1-07 F-2007066 New

    6-1-07 F-93133 1

    9-1-08 F-83178 3

    9-1-08 F-8649 4

    9-1-08 F-93215 3

    9-1-08 F-93132 3

    5-1-10 Page 2-2 2

    5-1-10 F-9197 3

    5-1-10 F-98236 3

    5-1-10 F-8739 3

    2012-FEB-02 F-83179 11

    2012-FEB-02 F-85144 9

    2012-FEB-02 F-8452 7

    2012-FEB-02 F-85143 6

    2012-FEB-02 F-94121 Out

    2012-FEB-02 F-9130 3

    Section 3

    6-1-07 F-85105 3

    6-1-07 F-99133 1

    6-1-07 F-8586 5

    6-1-07 F-99132 4

    6-1-07 F-85109 4

    6-1-07 F-86187 2

    DATE PAGE REV. NO. DATE PAGE REV. NO.

    Indicates revised information.

  • REVISION RECORD2012-FEB-02 Page 2REV. 3

    6-1-07 F-2004139 1

    9-1-08 F-8585 5

    9-1-08 F-86189 3

    9-1-08 F-8741 3

    5-1-10 F-85154 7

    5-1-10 F-87101 3

    5-1-10 F-200103 3

    2012-FEB-02 F-2002072 4

    2012-FEB-02 F-2002073 3

    2012-FEB-02 F-2002074 3

    2012-FEB-02 F-2002075 2

    2012-FEB-02 F-93137 9

    2012-FEB-02 F-2004133 2

    Section 3A

    6-1-07 F-92148 2

    6-1-07 F-93214 2

    6-1-07 F-8894 1

    6-1-07 F-2007071 1

    6-1-07 F-2001061 1

    6-1-07 F-91123 1

    2012-FEB-02 F-94116 Out

    2012-FEB-02 F-9226 Out

    2012-FEB-02 F-2002007 2

    Section 4

    6-1-07 F-2007011 New

    6-1-07 F-2007002 New

    2012-FEB-02 F-94118 Out

    Section 4A

    9-1-08 Page 4A-1 2

    Section 5

    5-1-10 Page 5F-1 3

    5-1-10 Page 5G-11 2

    5-1-10 Page 5G-12 New

    2012-FEB-02 F-2011070 1

    2012-FEB-02 F-2011071 1

    2012-FEB-02 F-2011072 1

    2012-FEB-02 F-2011073 1

    2012-FEB-02 Page 5C-3 3

    2012-FEB-02 Page 5C-4 2

    2012-FEB-02 Page 5C-5 2

    2012-FEB-02 Page 5C-10 2

    2012-FEB-02 Page 5C-11 2

    2012-FEB-02 F-2011074 1

    2012-FEB-02 F-2011075 1

    2012-FEB-02 F-2011076 1

    2012-FEB-02 F-2011077 1

    2012-FEB-02 Page 5G-1 2

    2012-FEB-02 Page 5G-2 2

    2012-FEB-02 Page 5G-3 2

    2012-FEB-02 Page 5G-4 2

    2012-FEB-02 Page 5G-5 2

    2012-FEB-02 Page 5G-6 3

    2012-FEB-02 Page 5G-7 3

    2012-FEB-02 Page 5G-8 3

    DATE PAGE REV. NO. DATE PAGE REV. NO.

    Indicates revised information.

  • REVISION RECORD2012-FEB-02          Page 3

    REV. 0

    2012-FEB-02 Page 5G-9 3

    2012-FEB-02 Page 5G-10 3

    2012-FEB-02 F-2011078 2

    Section 6

    5-1-10 Page 6-1 1

    2012-FEB-02 PN31274 7

    DATE PAGE REV. NO. DATE PAGE REV. NO.

    Indicates revised information.

  • Table of Contents2012-FEB-02        REV. 5

    Page 1

    Foam System Design and Application

    FORM/PAGESECTION NO.

    I. FOAM AGENTSFoam Vs. Combustion 1-1Classes of Fire 1-2 – 1-3Types of Foam 1-3 – 1-4Foam Quality and Testing 1-5 – 1-6Storing, Handling, and Inspecting ANSUL Foam Agents 1-6 – 1-7Testing and Approval of ANSUL Foam Agents 1-7ANSUL Foam Agent Data/Specifications Sheets

    3% Regular Protein Foam Concentrate Extinguishing Agent F-93203-13% Fluoroprotein Foam Concentrate Extinguishing Agent F-93202-1ANSULITE® 1% AFFF Concentrate F-81297-6ANSULITE 1% Freeze-Protected AFFF Concentrate –20 °F (–29 °C) F-9239-2ANSULITE 3% (AFC-3A) AFFF Concentrate F-83124-7ANSULITE Premium 3% (AFC-5A) AFFF Concentrate F-83126-6ANSULITE 3% Freeze-Protected AFFF Concentrate –20 °F (–29 °C) F-8125-3ANSULITE 6% (AFC-3) AFFF Concentrate F-83125-7ANSULITE Premium 6% (AFC-5) AFFF Concentrate F-83127-5ANSULITE 1x1 AR-AFFF Concentrate F-2010265ANSULITE 1x3 F-601A AR-AFFF Concentrate F-2009161-01ANSULITE 3x6 F-600A AR-AFFF Concentrate F-2009162ANSULITE 3x3 Low-Viscosity AR-AFFF Concentrate F-9350-6ANSULITE ARC 3% or 6% AR-AFFF Concentrate F-81105-10ANSULITE ARC 3% or 6% Freeze-Protected AR-AFFF Concentrate F-2003282-1JET-X 2% High-Expansion Foam Concentrate F-2009121JET-X 2 3/4% High-Expansion Foam Concentrate F-93139-4SILV-EX PLUS “Class A” Fire Control Concentrate F-2009064-1ANSUL-A Municipal “Class A” Fire Control Concentrate 30 °F (-1.1 °C) to 120 °F (49 °C) F-2005043-2TARGET-7 Vapor Mitigation and Neutralizing Agent F-2001072-2Training Foam Concentrate F-200208-1Foam Testing / Foam Test Kit F-2004153-1Proportioning Test Instruments F-2007003ANSUL Foam Concentrate Transfer Pump F-2011240

    II. PROPORTIONING EQUIPMENTProportioning 2-1Premix / Dump-In Method 2-1Balanced Pressure Proportioning Systems 2-1 – 2-3Line Proportioning Systems 2-4Around-The-Pump Proportioning Systems 2-5Proportioning Equipment Selection Criteria 2-6ANSUL Foam Proportioning Data/Specifications Sheets

    Vertical And Horizontal Bladder Tanks F-83179-11Bladder Tank Sight Gauge F-83178-3Threaded Proportioners (2 and 2 1/2 in.) F-85144-9Between Flange Proportioners (3, 4, 6, and 8 in.) F-8452-7Flanged Proportioners (3, 4, 6, and 8 in.) F-85143-6FLOWMAX CL Variable Range Proportioner F-2005165-1

  • Table of Contents2012-FEB-02        REV. 5

    Page 2

    FORM/PAGESECTION NO.

    II. PROPORTIONING EQUIPMENT (Continued)ANSUL Foam Data/Specifications Sheets (Continued)

    Hydraulic Concentrate Control Valve F-9197-3Pre-Piped Bladder Tanks With Proportioner F-98236-336 Gallon Bladder Tank/Foam Station F-8649-4Balanced Pressure Pump Proportioning System F-85174-3In-Line Balanced Pressure Proportioners Models IBP, IBP-M F-9130-3Atmospheric Poly Foam Concentrate Tanks F-93215-3Foam Systems Line Proportioners F-8739-3Around-The-Pump Proportioning Systems F-9490-1

    Foam Fire Fighting Systems SpecificationsBladder Tank Proportioning System F-93132-3Bladder Tank Proportioning System with FLOWMAX F-2007066In-Line Balanced Pressure Proportioning F-93133-1

    III. DISCHARGE DEVICESAspirated Vs. Nonaspirated Discharge Devices 3-1Discharge Device Classifications 3-2Nozzles 3-2Monitors 3-3Specialized Discharge Devices 3-3 – 3-4ANSUL Discharge Device Data/Specifications Sheets

    Manual Monitor MM-1000 Series F-85105-3Protector Station Monitor F-99133-1Automatic Water Oscillating Monitor Model WOM-3 F-8585-5Automatic Water Oscillating Monitor Model WOM-4 F-86189-3Master Stream Monitor Nozzles F-8586-5Self-Educting Master Foam Nozzle F-99132-4Air Aspirating Foam Nozzle Model AFN-1 F-85109-4Air Aspirating Foam Nozzle Model AFN-2 F-86187-2Manual Monitor/Nozzle High-Flow Series Model FJM-80 F-2002072-4Monitor/Nozzle High-Flow Series Model FJM-100 F-2002073-3Monitor/Nozzle High-Flow Series Model FJM-150 F-2002074-3Monitor/Nozzle High-Flow Series Model FJM-200 F-2002075-2Foam Chambers F-85154-7FLR and AFM Foam Makers F-87101-3FLR-30-FP/FLR-90-FP Rim Seal Foam Pourer F-200103-3High-Back-Pressure Foam Makers F-8741-3JET-X High-Expansion Foam Generators F-93137-9AHR Continuous Flow Hose Reels F-2004133-2AFS Foam Stations F-2004139-1

    III-3A. PORTABLE/MOBILE EQUIPMENTANSUL Portable/Mobile Data/Specifications Sheets

    Handline Nozzles and Eductors F-92148-2Foam Systems Mobilcart (36 Gallon) F-93214-2Air Aspirating Handline Nozzle F-8894-1Portable Monitor/Nozzle High-Flow Series – Model FJM-80P F-2002071-1JET-X PFG-7 and JET-X PFG-M Portable High Expansion Foam Generators F-2002007-2Master Foam Tote-Trailer F-2001061-1Proportioning Foam Trailers Models PFT-500, PFT-750, PFT-1000 F-91123-1

  • Table of Contents2012-FEB-02        REV. 3

    Page 3

    FORM/PAGESECTION NO.

    IV. SPRINKLER AND SPRAY NOZZLE SYSTEMSGeneral Description 4-1Types of Sprinkler Heads 4-1 – 4-2Types of Sprinkler Systems 4-3 – 4-6ANSUL Sprinkler Data Sheets

    Popular Sprinklers/Concentrates – Listings and Approvals F-2007011Model B-1 Foam-Water Sprinklers F-2007002

    IV-4A.SPRINKLER SYSTEM DESIGNLow-Expansion Foam Water Sprinkler Design – NFPA 16 and 30

    NFPA 16: Standard for the Installation of Foam-Water Sprinkler 4A-1and Foam-Water Spray Systems

    NFPA 30: Flammable and Combustible Liquids Code 4A-1 – 4A-2

    V. FOAM SYSTEM APPLICATIONSIntroduction 5-1Section 5A – Foam Agent Selection 5A-1 – 5A-2

    General Criteria 5A-1Foam Agent Limitations 5A-1Hydrocarbons and Polar Solvents 5A-1Flammable and Combustible Liquids 5A-2

    Section 5B – Storage Tank Protection 5B-1 – 5B-20Protection Options 5B-1Subsurface Injection 5B-1 – 5B-7

    Subsurface Flow Chart 5B-2Subsurface Design Parameters 5B-3 – 5B-7Example System – Subsurface Injection F-2011070-01

    Surface Application 5B-8 – 5B-21Surface Application 5B-8Cone Roof Flow Chart 5B-9Cone Roof Design Parameters 5B-10 – 5B-12Example System – Cone Roof F-2011071-01Floating Roof Flow Chart 5B-13Floating Roof Design Parameters 5B-14 – 5B-17Example System – Floating Roof F-2011072-01

    Dike Protection 5B-18 – 5B-20Overview 5B-18Dike Protection Flow Chart 5B-18Dike Protection Design Parameters 5B-19 – 5B-20Example System – Dike Protection F-2011073-01

  • Table of Contents2012-FEB-02        REV. 4

    Page 4

    FORM/PAGESECTION NO.

    V. FOAM SYSTEM APPLICATIONS (Continued)

    Section 5C – Aircraft Hangar Protection 5C-1 – 5C-11Protecting Aircraft 5C-1Aircraft Hangar Flow Chart 5C-2Aircraft Hangar Design Parameters 5C-3 – 5C-11Hangar High-Expansion System Calculation Form 5C-10Hangar High-Expansion System Calculation Form (Inside Air) 5C-11

    Example System – No. 1 (AFFF) F-2011074-01Example System – No. 2 (High-Expansion) F-2011075-01

    Section 5D – Truck Loading Rack Protection 5D-1 – 5D-4Protection Overview 5D-1Truck Loading Rack Flow Chart 5D-2Truck Loading Rack Design Parameters 5D-3 – 5D-4Example System – Truck Loading Rack F-2011076-01

    Section 5E – Heliport Protection 5E-1 – 5E-7Protection Overview 5E-1Heliport Flow Chart 5E-2Heliport Design Parameters 5E-3 – 5E-7Example System – Heliport F-2011077-01

    Section 5F – Spill Fire Protection 5F-1 – 5F-2Protection Overview 5F-1Protection Options 5F-1Determining Discharge Time and Application Rate 5F-1Typical System 5F-2

    Section 5G – High-Expansion Foam Systems 5G-1 – 5G-12Protection Overview 5G-1Protection Options 5G-1Total Flooding System Flow Chart 5G-2Total Flooding High-Expansion Foam Systems 5G-3 – 5G-8Local Application System Flow Chart 5G-9Local Application Systems 5G-10Medium-Expansion Foam Systems 5G-11 – 5G-12Example System – Total Flooding F-2011078-02

  • Table of Contents2012-FEB-02        REV. 3

    Page 5

    FORM/PAGESECTION NO.

    VI.  APPENDIXFoam Glossary 6-1 – 6-2

    References 6-2

    Typical Schematic Symbols 6-3

    Basic Hydraulic Calculations 6-4 – 6-5

    Equivalent Pipe Lengths 6-6

    Pipe Tables 6-7 – 6-9

    Friction Loss Table 6-10 – 6-11

    Darcy Formula 6-12

    Straight Bore Discharge Data 6-13

    Comparative Equivalents of Liquid Measures and Weights 6-14

    Metric Conversions 6-15

    Equivalent Values of Pressure 6-16

    Hose Friction Loss 6-17

    Friction Loss Data For ANSULITE ARC (Alcohol Resistant Concentrate) F-90128-1

    Understanding Fire Detection Devices, reprint from ELECTRICALCONSULTANT, May/June issue

    Technical Bulletin No. 52 – Environmental Impact of ANSULITE AFFF Products F-82289-3

    Technical Bulletin No. 54 – Shelf Life of ANSULITE AFFF Concentrates F-83114-2and Their Premixed Solutions

    Technical Bulletin No. 55 – Aspirated Versus Nonaspirated AFFF F-83115-2

    Technical Bulletin No. 59 – Acceptable Materials of Construction For F-90109-2Use With Ansul Foam Concentrates

    Technical Bulletin No. 60 – Foam: The Environment and Disposal Issues F-97136-3

    Technical Bulletin No. 64 – Compatibility of AFFF/Alcohol-Resistant F-2002179-1AFFF Concentrates

    Foam Concentrates and Foam Pre-Mix Solutions Field Inspection Manual P/N 31274-07

    Foam Systems Proposal lnformation Brochure F-94146

  • FOAM VS. COMBUSTION

    In order to understand how foam suppresses fire, it is firstnecessary to understand the process of com bustion.

    Combustion is a process where fuel undergoes a rapidexothermic chemical reaction (release of heat) with anoxidizing agent, usually air, resulting in the formation ofproducts of combustion and energy (fire).

    FUEL PRODUCTS OF COMBUSTION+ = +

    OXIDIZER ENERGY

    A fuel is any material that can be oxidized; it can be a solid,liquid, or gas and is generally organic in nature, i.e.,composed mostly of carbon, hydrogen, or oxygen. Theproducts of combustion of an organic fuel (assumingcomplete combustion) are carbon dioxide and water. Theenergy released may be in the form of heat or light, or thecombination of heat and light (fire).

    The chemical reaction is not a simple one-step reaction, butis a chain reaction resulting in a number of interdependentchemical reactions. Figure 1-1 depicts the four require-ments for combustion using the “fire tetrahedron.”

    FIGURE 1-1001141

    It follows that any method for extinguishing fire must involveone or more of the following techniques:

    1. Remove heat at a faster rate than it is released.

    2. Separate the fuel from the oxidizing agent.

    3. Dilute the vapor-phase concentration of the fuel and/oroxidizing agent below that necessary for combustion.

    4. Terminate the chemical chain-reaction sequence.

    Fire fighting foam is an aggregate of gas-filled bubbles(Figure 1-2) formed from aqueous solutions of speciallyformulated, liquid agent concentrates. The gas used isusually air, but certain applications use an inert gas.

    Since foam is lighter than flammable and combust ibleliquids, it floats on the fuel surface producing a continuousblanket that suppresses fire by separating flammablevapors and oxygen as shown in Figure 1-2. Because foamis a water-bearing mater ial, it also cools the fuel surface.

    FIGURE 1-2001142

    SECTION I6-1-07        REV. 1

    Page 1-1

    Foam System Design and Application Foam Agents

  • SECTION I6-1-07        REV. 1Page 1-2

    CLASSES OF FIRE

    There are four broad classes of fire as defined by theNational Fire Protection Association (NFPA). Three of theserepresent the fuel involved, while one, Class C, reflects thesource of ignition. In fact, all Class C fires involve Class A,Class B, or Class D combustibles. Each of these classesinvolves somewhat different modes of combustion.

    Class A Fires

    FIGURE 1-3001143

    Class A fires involve ordinary combustible materials (suchas wood, cloth, paper, rubber, and many plastics) requiringthe heat-absorbing (cooling) effects of water and watersolutions or the coating effects of certain dry chemicalswhich retard combustion.

    Class A fires can be further divided into two categories.Flaming combustion involves the volatile gases whichresult from the thermal decomposition of the fuel; itproduces rapid vapor-phase oxidation of the fuel and heattransfer back to the fuel. Glowing or deep-seated firesrepresent combustion within the mass of the fuel and arecharacterized by a slow rate of heat loss and a slow rate ofreaction between oxygen and fuel. While the two modes ofClass A fires usually occur concurrently, either type canprecede the other depending on the fuel type and configu-ration.

    Class B Fires

    FIGURE 1-4001144

    Class B fires involve flammable or combustible gases,liquids, greases, and similar materials where extinguish-ment is most readily accomplished by ex cluding oxygen,inhibiting the release of combustible vapors, or interruptingthe combustion of chain reaction. The combustion of theseliquids and gases involves rapid vapor-phase oxidation ofthe fuel and subsequent involvement of more fuel due toradiant heat feedback.

    Class B materials are either water soluble (mix with water)or water insoluble (will not mix with water). Water solublefuels require special alcohol-resistant foam agents that willresist breakdown by the fuel when applied correctly.

    Class C Fires

    FIGURE 1-5001145

    Class C fires involve energized electrical equipment whereoperator safety requires the use of electrically non-conduc-tive extinguishing agents. Foam agents are not recom-mended for Class C fires due to the conductivity of theagent resulting from the high water content. However, whenelectrical equipment is de-energized, foam agents may beused.

    Foam Agents

  • SECTION I9-1-08        REV. 2

    Page 1-3

    Classes of Fire  (Continued)

    Class D Fires

    FIGURE 1-6007914

    Class D fires involve certain combustible metals such asmagnesium, titanium, zirconium, sodium, potassium, etc.,and require a heat-absorbing extinguishing agent that doesnot react with the burning metal.

    The combustion of metals involves a rapid oxidation thatdepends upon the chemical and physical properties of themetal involved. Generally, metals burn at higher tempera-tures, but with relatively low flame intensity. In certainconfigurations, metal fires can become deep-seated (i.e.,magnesium dust) or if dispersed in the oxidizer, can beexplosive. However, the nature of the combustion processdepends on the properties of the metal (i.e., zirconiumburns explosively when dry, but when wetted with oil, burnsmore quietly).

    Foam agents are not recommended for Class D fires due tothe reactivity of some combustible metals with water.

    TYPES OF FOAM

    There are numerous types of foams that are selected forspecific applications according to their properties andperformance. Some foams are thick, viscous, and formtough, heat-resistant blankets over burning liquid surfaces;other foams are thinner and spread more rapidly. Somefoams are capable of producing a vapor sealing film ofsurface active water solution on a liquid surface. Others,such as medium and high expansion foams, are used aslarge volumes to flood surfaces and fill cavities.

    Chemical Foams

    Foams have been classified in different ways over theyears. The earliest foams were based upon a chemicalreaction occurring between aluminum sulfate (Al2 (SO4)3)and sodium bicarbonate (NaHCO3). The energy used tocreate the foam bubbles came from the chemical reaction.This type of foam is now largely obsolete.

    Mechanical Foams

    Mechanical foam is produced by mixing a foam concentratewith water at the appropriate concentration, and then aerat-ing and agitating the solution to form a bubble structure.Therefore, unlike chemical foams, the energy used tocreate the foam bubbles of a mechanical foam comes froman outside source.

    There are several types of mechanical foams:

    –  Protein

    –  Fluoroprotein

    –  Film-Forming Fluoroprotein (FFFP)

    –  Aqueous Film-Forming Foam (AFFF)

    –  Alcohol-Resistant Concentrate (ARC)

    –  Synthetic Detergent (High/Medium Expansion)

    The differences between these foam concentrates dependon:

    –  whether the concentrate is based upon naturally-occur-ring materials or synthetic chemicals.

    –  whether the synthetic chemicals are fluoronated ornonfluoronated.

    –  the type of fuel being protected.

    –  the expansion ratio (see Page 1-5).

    –  whether they will form an aqueous film on certain fuels.

    Protein Foam is derived from naturally-occurring sourcesof protein such as hoof and horn meal or feather meal. Theprotein meal is hydrolyzed in the presence of lime andconverted to a protein hydrolysate which is neutralized andto which other components are added such as foam stabi-lizers, corrosion inhibitors, antimicrobial agents, and freez-ing point depressants. Foams derived from protein foamconcentrates generally have very good heat stability andresist burnback, but are not as mobile or fluid on the fuelsurface as other types of low expansion foams. Proteinfoams are susceptible to fuel pickup; consequently, careshould be taken to minimize submergence.

    Fluoroprotein Foam is derived from protein foam concen-trates to which small amounts of fluoro chemical surfactantsare added. The fluorochemical surfactants are similar tothose developed for AFFF foam agents but used in muchlower concentrations. The addition of these chemicalsproduces an easier flowing foam. Because of these chemi-cals, fluoro protein foams are said to be oleophobic (oilshedding) and are well suited for sub-surface injection.

    Foam Agents

  • SECTION I6-1-07        REV. 1Page 1-4

    TYPES OF FOAM  (Continued)

    Film-Forming Fluoroprotein (FFFP) is a protein basefoam concentrate to which quantities of fluorochemicalsurfactants (similar to those used in AFFF foam agents) areadded. This improves the mobility of the foam to the pointwhere it begins to approach the quick extinguishment thatis characteristic of AFFF foam agents. On some fuels, italso forms an aqueous film like the AFFF foam agents.However, this reduces the burnback resistance that is char-acteristic of protein-based foams. Film-forming fluoroproteinfoams tend to be a compromise between AFFF and fluoro-protein foam agents.

    Aqueous Film-Forming Foam (AFFF) is a completelysynthetic foam. It consists of combinations of fluorochemi-cal and hydrocarbon surfactants combined with high boilingpoint solvents and water. Surfactants are chemicals thathave the ability to alter the surface properties of water.Fluorochemical surfactants alter these properties in such away that a thin film (Figure 1-7) can spread on a hydrocar-bon fuel (such as gasoline) even though the aqueous film ismore dense than the fuel.

    FIGURE 1-7001147

    Alcohol-Resistant Concentrate (ARC) produces a foamthat is effective on fuels such as methyl alcohol, ethylalcohol, and acetone which have appreciable water solubil-ity or miscibility.

    Standard foam agents are mixtures of chemicals (natural orsynthetic) whose bubbles collapse when applied to watersoluble fuels. These fuels are said to be foam destructive.The early alcohol-resistant foams were based on mixturesof protein foams and chemicals called metal soaps. Thesechemicals are hydrophobic or water repellent.

    The most current alcohol-resistant concentrates are basedon AFFF concentrates to which a water soluble polymer(polysaccharide) has been added. When these foamagents are applied to a water soluble fuel such as methylalcohol, a polymeric membrane (Fig ure 1-8) is formedbetween the foam and the water soluble fuel.

    When this foam agent is used on a conventional (waterinsoluble) hydrocarbon fuel, it functions as an AFFF foamby forming an aqueous film at the fuel/air interface.AR-AFFF exhibits the best cross-functional performance forflame knock-down, burnback resistance, extended vaporsuppression, manufacturing and proportioning consistency,and the longest potential shelf life.

    FIGURE 1-8001148

    Synthetic Detergent type foam agents are based onmixtures of non-fluorochemical, hydrocarbon type surfac-tants along with solvents and water. These foam agents donot form aqueous films or polymeric membranes. Instead,they function by forming an aggregate of foam bubbles onthe surface of the fuel. They are most frequently used withhigh expansion foam generators yielding expansion ratiosof 200 to 1000:1 (see Figure 1-9). The reduced watercontent of high expansion foams makes them suitable foruse in total flooding applications and on cyrogenic typefuels such as liquefied natural gas (LNG). Some of thesefoam agents are specially formulated to be used with low,medium, and high expansion foam hardware at differentproportioning ratios and are referred to as multiple expan-sion foam agents.

    FIGURE 1-9007629

    Foam Agents

  • SECTION I6-1-07        REV. 1

    Page 1-5

    FOAM QUALITY AND TESTING

    Depending on the authority having jurisdiction, varyingagencies require different qualification testing for foamconcentrates. Standard manufacturing tests for concen-trates include pH, density (or specific gravity), and viscosity.These are performed as quality control measures.

    Foam quality is a measure of the physical properties offoam expressed as expansion ratio and quarter drain time(or 25% drain time).

    Expansion Ratio

    Expansion ratio is the comparison of final foam volume tothe original foam solution before air is added.

    Volume of Container__________________EXPANSION RATIO =MassFull–MassEmpty

    Example: A 1000 ml graduated cylinder is filled withexpanded foam. The weight of the filled cylinder is 450 gwhile the tare weight of the cylinder is 250 g. The expan-sion ratio is calculated as follows:

    1000 ml___________EXPANSION RATIO =450 g – 250 g

    = 5.0

    NFPA classifies foam concentrates by expansion ratio asfollows:

    Low Expansion – Expansion ratio up to 20:1

    Medium Expansion – Expansion ratio from 20:1 to 200:1

    High Expansion – Expansion ratio above 200:1

    Typical values for expansion ratios are as follows:

    Low Expansion – 8:1

    Medium Expansion – 100:1

    High Expansion – 500:1

    Quarter Drain Time

    Quarter drain time is a test measure of the time required todrain the volume of liquid having a weight equal to 25% ofthe foam sample.

    Example: Continuing from the previous example, thequarter drain time is derived by timing from when the cylin-der was first filled until 25% by weight volume of liquid ismeasured as in the following calculation:

    25% (450 g – 250 g)  =  50 ml

    Note that 1 ml of foam solution is equal to 1 gram of weight.It is therefore simpler to use these units as compared tounits requiring conversion.

    Burnback Resistance

    Burnback resistance is the ability of the foam blanket toresist radiant heat after a fire is extinguished and to helpprevent reignition of the fuel. This test varies with specifica-tions and agents used.

    Compatibility

    The question of compatibility of different types and brandsof foams is important because there are a number of foamagent manufacturers throughout the world. “Compatibility”is a term which defines a situation where different manufac-turerʼs foam concentrates are mixed in the same storagevessel. Con cen trates are found to be compatible when,after mixing, the physical and chemical characteristics ofthe resulting mixture perform at least equal to that of eachindividual concentrate in the mixture.

    NFPA 11, Standard for Low, Medium, and High ExpansionFoam states that “different types and brands of concen-trates may be incompatible and shall not be mixed instorage.”

    United States Military Specifications O-F-555 for proteinfoam concentrate and MIL-F-24385 for AFFF concentratecompatibility require that: “concentrates of one manufac-turer shall be compatible in all proportions with the concen-trates furnished by other manufacturers listed on theQualified Products List (QPL).” This also includes compati-bility with concentrates from previous versions of therespective specification. Products which are on theQualified Products List for these specifications have beentested for compatibility.

    There are also non-qualified protein and AFFF concentratesalong with fluoroprotein and alcohol-resistant AFFF (AR-AFFF) for which there are no specifications or standardswhich address compatibility. These concentrates shouldonly be mixed in an emergency or if the manufacturer hassupporting data to substantiate that the mixture meets thesame requirements as the individual component concen-trates.

    Foam Agents

  • SECTION I6-1-07        REV. 1Page 1-6

    FOAM QUALITY AND TESTING  (Continued)

    Compatibility (Continued)

    Presently, all major U.S. manufacturers of polar solventAFFF concentrates are using the same type of polymer.Therefore, if the regular AFFF concentrates are compatible,then their polar solvent AFFF concentrates will be chemi-cally compatible. Physically, there may be a difference inthe density and static viscosity of any two manufacturerʼsproducts which may lead to layering of the two products.The fact that they donʼt intermix is not a concern. The prod-ucts may be left layered or, if desired, they may be mechan-ically mixed.

    Although compatibility is of concern in storage, NFPA 11states that “foams generated separately from protein, fluo-roprotein and AFFF concentrates may be applied to a fire insequence or simultaneously.”

    The only requirement still in effect for dry chemical compati-bility is for those protein and AFFF concentrates that are onthe Qualified Products List for the respective military speci-fications O-F-555 and MIL-F-24385. The U.S. Coast Guardand Under writers Laboratories no longer test or require drychemical agents to be foam compatible. Current ANSUL drychemical agents that may be applied with foam include:Purple-K, PLUS-FIFTY® C, and FORAY®.

    STORING, HANDLING, AND INSPECTING ANSUL FOAMAGENTS

    ANSUL foam concentrates will provide years of service ifproper handling and storage guidelines are followed. Ingeneral, all ANSUL synthetic concentrates have minimumshelf lives of 20 to 25 years. ANSUL protein base concen-trates have minimum shelf lives of 7 to 10 years. The shelflife of ANSUL foam concentrates is valid only when theagents are stored in accordance with the following recom-mendations.

    ANSUL Shipping/Storage Containers

    FIGURE 1-10001150

    Storage of ANSUL foam concentrates in their shippingcontainers is acceptable as long as certain precautions aretaken. Whenever possible, they should be stored within thetemperature limits specified on the container or containerlabel (see specific product data sheet or Technical BulletinNo. 54).

    ANSUL packages its concentrates in 5 gal. (19 L) pails and55 gal. (208 L) drums and 265 gal. (1000 L) intermediatebulk containers (totes). These containers are constructed ofmolded poly ethylene and meet the requirements of the U.S.Department of Transportation. At present, only UL Listedagents supplied in pails or drums can include the UL logoon the conainer label.

    STORING, HANDLING, AND INSPECTING ANSUL FOAMAGENTS

    Temperature ConsiderationsIf the minimum or maximum usable temperature isexceeded, inspection of the concentrate should beperformed. See Technical Bulletin No. 54 for details.

    If the product is frozen, it should be thawed and agitated byrolling on a level surface before inspection. In the case ofANSULITE alcohol-resistant concentrate, vigorous mechan-ical agitation may be necessary. It is important to note thatthe minimum usable temperature is not the freezing point ofthe product. It is the minimum temperature that the productwas tested for correct proportioning ability. Most ANSULfoam concentrates are not adversely affected byfreeze/thaw cycling; however, freezing of ANSULITEalcohol-resistant concentrates should be avoided.

    Foam Agents

  • SECTION I6-1-07        REV. 1

    Page 1-7

    STORING, HANDLING, AND INSPECTING ANSUL FOAMAGENTS (Continued)

    Temperature Considerations (Continued)

    Special freeze protected or low temperature ANSUL foamconcentrates are available with minimum use temperatures.Consult specific Agent Data Sheets for details.

    Inspection

    At least annually, an inspection shall be made of foamconcentrates and their tanks or storage containers forevidence of excessive sludging or deterioration. Samples ofconcentrates shall be sent to the manufacturer or a quali-fied laboratory for quality condition testing.

    Atmospheric Storage Tanks

    Atmospheric storage tanks, generally used with fixed ormobile equipment, should only be constructed of materialspecified by ANSUL. Materials of construction for the tankare normally polyethylene plastic, fiberglass reinforcedpolyester, fiberglass reinforced epoxy resin, mild steel, orstainless steel. These tanks should be closed to atmos-phere except for a pressure/vacuum vent mounted on topof the tank.

    Mild steel tanks should be designed with an expansiondome constructed of a heavier gauge material as comparedto the tank shell to allow for internal corrosion. These tanksshould always be filled half way into the expansion dome.In extremely corrosive environments, it may be desirable tofabricate these tanks from stainless steel or anothersynthetic material recommended by ANSUL.

    Alcohol-resistant concentrates are susceptible to polymercollapse due to dehydration. In order to protect from dehy-dration, it is desirable to always cap concentrates stored inatmospheric tanks with 1/4 in. mineral oil as a sealer.

    Under no circumstances should the interior of the tankbe painted or lined. The tank and lining have differentcoefficients of thermal expansion; as the ambient tempera-ture cycles, separation of the tank and lining will occur.Foam concentrates have good wetting characteristics, andif a crack develops, concentrate will quickly seep betweenthe tank wall and lining resulting in lining failure, corrosionproblems, and possible tank failure. In addition, smallpieces of the lining may break away resulting in cloggedstrainers or blocked proportioner orifices.

    TESTING AND APPROVAL OF ANSUL FOAM AGENTSThe ANSUL Fire Technology Center has the research,development and testing facilities to provide for all facets oftesting foam agents. These facilities include laboratories forformulation development, physiochemical property determi-nation, and complete fire test capabilities.

    ANSUL maintains a vigorous quality assurance programthrough complete quality control testing of all productionbatches. This includes physiochemical property testing ofboth incoming raw materials and finished productionbatches; and performance fire testing of all productionbatches to nationally recognized testing standards such asthose described in the latest Amendment of U.S. MilitarySpecification MIL-F-24385 and Underwriters LaboratoriesStandard 162.

    The qualification or listing of ANSUL foam concentrates asdetailed by product specific data sheets show that productshave met the rigid requirements of those standards andspecifications as tested by independent, third-party, testingauthorities. Most of the standards or specifications citedreflect end-user requirements as defined by a governmentagency, or independent laboratory requirements asaccepted by insurance underwriters. Government specifica-tions frequently detail the acceptable performance require-ments for the foam agent. Underwriters Laboratoriesspecifications reflects a combination of acceptable perfor-mance requirements for the agent in selected types of foamhardware.

    The United States Coast Guard (USCG) is the agency thatrepresents regulatory authority for commercial shipping aswell as offshore exploration and production facilities. USCGapproval is granted only on the basis of an approved foamsystem design for a defined hazard such as petroleum orchemical tanker involving a foam agent, a proportioningdevice, and a discharge device designed to produce foamat a given rate of application for a minimum period of time.It is for this reason that USCG approval only applies to acomplete system and never to individual components suchas the foam agent.

    Since specifications and standards cannot cover all possi-ble hazard characteristics, especially fuel type and configu-ration, it is necessary to have the facilities conduct testsand determine minimum rates of application as defined bythe National Fire Protection Association (NFPA) and invarious international standards. This then constitutes amanufacturerʼs approval or recommendation regarding theconditions under which the foam agent may be used. It isvery important that this recommendation be based upondocumented test data which supports the recommendation.

    Foam Agents

  • ANSUL® 3% Protein Foam Concentrate is formulated from hydrolyzedprotein, foam stabilizers (metal salts), bactericide, corrosion inhibitors,freezing point depressants and solvents. It is transported and stored asa concentrate to provide ease of use and considerable savings in weightand space.

    It is intended for use as a 3% proportioned solution either in fresh, saltor hard water. The correct proportioning ratio is 3 parts of concentrate to97 parts of water.

    Two fire extinguishing mechanisms are in effect when using ANSUL 3%Protein Foam. First, a foam blanket is formed which works to preventthe release of fuel vapor. Second, the water content of the foamprovides a cooling effect.

    ANSUL 3% Protein Foam Concentrate is intended for use on Class Bhydrocarbon fuels having low water solubility such as various crude oils,gasolines, diesel fuels, aviation fuels, etc. It is not suitable for use onfuels having appreciable water solubility (polar solvents), i.e., methyl andethyl alcohol, acetone and methyl ethyl ketone. This concentrate can beused only with air aspirating type discharge devices.

    Its wetting characteristics make it useful in combating Class A fires aswell. It can also be used with foam compatible dry chemical extinguish-ing agents without regard to the order of application, to provide evengreater fire protection capability.

    Fire Performance – The fire performance of ANSUL 3% Protein FoamConcentrate is measured against specifications and standards such asUnderwriters Laboratories Standard UL 162, latest edition.

    Foaming Properties – When used with fresh or salt water or water ofany hardness at the correct dilution and with most conventional foammaking equipment, the expansion ratio will vary depending on theperformance characteristics of the equipment. Air aspirating dischargedevices produce expansion ratios from 8 to 1 to 12 to 1 dependingprimarily on type and flow rate. In general, the higher the flow rate thehigher the expansion ratio. Thus, monitors and foam chambers normallyproduce higher expansion ratios than foam water sprinkler heads andhand held type nozzles.

    Typical expansion ratios for foam chambers are in the range of 5 to 1 to 7to 1, and for foam water sprinkler heads in the range of 3 to 1 to 6 to 1.

    Typical Physiochemical Properties at 77 °F (25 °C)

    Type 3%____ ___Appearance Dark brown liquidDensity 1.15 g/ml ± 0.03pH 6.0 – 8.0Viscosity 12 ± 4 centistokesFreezing Point 5 °F (–15 °C)Sediment Volume 0.20% maximum

    Proportioning – 3% Protein Foam Concentrate can be easily propor-tioned (at the correct dilution) using most conventional proportioningequipment such as:

    1. Balanced pressure and in-line balanced pressure pump proportioningequipment

    2. Balanced pressure bladder tank type proportioners

    3. Around the pump type proportioners

    4. Fixed or portable in-line venturi type proportioners

    5. Hand line nozzles with fixed induction/pick up tubes

    The minimum and maximum usable temperatures for ANSUL 3%Protein Foam Concentrate with this equipment is: 20 °F (–6.7 °C) to120 °F (49 °C) respectively.

    Storage/Shelf Life – When stored in the packaging supplied (polyethyl-ene drums or pails) within the temperature limits specified, or in equip-ment recommended by the manufacturer as part of the foam system, theshelf life of ANSUL 3% Protein Foam Concentrate is generally in excessof 10 years. If the product is frozen during storage or transportation,thawing will render the product completely usable.

    Compatibility – There are no specifications or standards which addressthe subject of compatibility of different manufacturer brands of proteinfoam concentrates. In an emergency or if the manufacturer has support-ing test data to substantiate that the mixture meets the same require-ments as the individual component concentrates, they may be mixedtogether in the same storage vessel.

    Different types of foam concentrates, i.e., AFFF and protein base shouldnot be mixed under any circumstances.

    Inspection – As with any fire extinguishing agent, ANSUL 3% ProteinFoam Concentrate should be inspected periodically.

    Please refer to the Field Inspection Manual for detailed procedures howto perform this inspection. An annual inspection is recommended unlessunusual conditions of exposure occur. In the latter case, ANSUL recom-mendation should be sought.

    PERFORMANCE

    APPLICATION

    DESCRIPTION

    3% REGULAR PROTEIN FOAM CONCENTRATEEXTINGUISHING AGENT

    Data/Specifications

  • ANSUL 3% Protein Foam Concentrate is approved, qualified under,listed or meets the requirements of the following specifications and stan-dards:

    Underwriters Laboratories, Inc. – UL Standard 162

    1. Foam Quality Test

    2. Class B Hydrocarbon Fuel Fire Tests

    3. Foam Identification Tests

    4. Test of shipping containers

    5. Class B Hydrocarbon fuel fire tests using foam water sprinkler (bothupright and pendent approvals)

    It is impractical for ANSUL to list its 3% Protein Foam Concentrate withevery piece of UL listed hardware. Moreover there are numerous foamhardware components without UL listings that cannot be listed for usewith any protein foam agent.

    Many unlisted pieces of foam hardware should be similar to those listed.However, on installations where ANSUL 3% foam concentrate may beused with hardware components of significantly different types thanthose tested, contact ANSUL for recommendations.

    Part No. Description______ _________73971 3% Protein Foam – 5 gallon73970 3% Protein Foam – 55 gallon

    Shipping Weight:5 gal (19 L) pail – 51 lb (23.1 kg)55 gal (208 L) drum – 555 lb (251.7 kg)

    Cube:5 gal (19 L) pail – 1.08 ft3 (0.0305 m3)55 gal (208 L) drum – 11.33 ft3 (0.3208 m3)

    ORDERING INFORMATION

    APPROVALS AND LISTINGS

    Copyright ©2007 Ansul IncorporatedForm No. F-93203-1

    ANSULis a trademark of Ansul Incorporated or its affiliates.

    Ansul IncorporatedMarinette, WI 54143-2542

    715-735-7411www.ansul.com

  • ANSUL® 3% Fluoroprotein Foam Concentrate is formulated fromhydrolyzed protein, fluorochemical surfactants, foam stabilizers (metalsalts), bactericide, corrosion inhibitors, freezing point depressants andsolvents. It is transported and stored as a concentrate to provide ease ofuse and considerable savings in weight and space.

    It is intended for use as a 3% proportioned solution either in fresh, saltor hard water. The correct proportioning ratio is 3 parts of concentrate to97 parts of water.

    Two fire extinguishing mechanisms are in effect when using ANSUL 3%Fluoroprotein Foam. First, a foam blanket is formed which works toprevent the release of fuel vapor. Second, the water content of the foamprovides a cooling effect.

    ANSUL 3% Fluoroprotein Foam Concentrate is intended for use onClass B hydrocarbon fuels having low water solubility such as variouscrude oils, gasolines, diesel fuels, aviation fuels, etc. It is not suitable foruse on fuels having appreciable water solubility (polar solvents), i.e.,methyl and ethyl alcohol, acetone and methyl ethyl ketone. This concen-trate can be used only with air aspirating type discharge devices.

    Its wetting characteristics make it useful in combating Class A fires aswell. It can also be used with foam compatible dry chemical extinguish-ing agents without regard to the order of application, to provide evengreater fire protection capability.

    Fire Performance – The fire performance of ANSUL 3% FluoroproteinFoam Concentrate is measured against specifications and standardssuch as Underwriters Laboratories Standard UL 162, latest edition.

    Foaming Properties – When used with fresh or salt water or water ofany hardness at the correct dilution and with most conventional foammaking equipment, the expansion ratio will vary depending on theperformance characteristics of the equipment. Air aspirating dischargedevices produce expansion ratios from 6 to 1 to 12 to 1 dependingprimarily on type and flow rate. In general, the higher the flow rate thehigher the expansion ratio. Thus, monitors and foam chambers normallyproduce higher expansion ratios than foam water sprinkler heads andhand held type nozzles.

    Typical expansion ratios for foam chambers are in the range of 5 to 1 to7 to 1, and for foam water sprinkler heads in the range of 3 to 1 to 6 to1. Subsurface injection is a special case where generally speaking,expansion ratios of 2 to 1 to 3 to 1 are preferred but up to 4 to 1 is alsoeffective.

    Typical Physiochemical Properties at 77 °F (25 °C)

    Type 3%____ ___Appearance Dark brown liquidDensity 1.15 g/ml ± 0.03pH 6.0 – 8.0Viscosity 10 ± 4 centistokesFreezing Point 5 °F (–15 °C)Sediment Volume 0.20% maximum

    Proportioning – 3% Fluoroprotein Foam Concentrate can be easilyproportioned (at the correct dilution) using most conventional proportion-ing equipment such as:

    1. Balanced pressure and in-line balanced pressure pump proportioningequipment

    2. Balanced pressure bladder tank type proportioners

    3. Around the pump type proportioners

    4. Fixed or portable in-line venturi type proportioners

    5. Hand line nozzles with fixed induction/pick up tubes

    The minimum and maximum usable temperatures for ANSUL 3%Fluoroprotein Foam Concentrate with this equipment is: 20 °F (–6.7 °C)to 120 °F (49 °C) respectively.

    Storage/Shelf Life – When stored in the packaging supplied (polyethyl-ene drums or pails) within the temperature limits specified, or in equip-ment recommended by the manufacturer as part of the foam system, theshelf life of ANSUL 3% Fluoroprotein Foam Concentrate is generally inexcess of 10 years. If the product is frozen during storage or transporta-tion, thawing will render the product completely usable.

    Compatibility – There are no specifications or standards which addressthe subject of compatibility of different manufacturer’s brands of fluoro-protein foam concentrates. In an emergency or if the manufacturer hassupporting test data to substantiate that the mixture meets the samerequirements as the individual component concentrates, they may bemixed together in the same storage vessel.

    Different types of foam concentrates, i.e., AFFF and fluoroprotein baseshould not be mixed under any circumstances.

    Inspection – As with any fire extinguishing agent, ANSUL 3%Fluoroprotein Foam Concentrate should be inspected periodically.Please refer to the Field Inspection Manual for detailed procedureshow to perform this inspection. An annual inspection is recommendedunless unusual conditions of exposure occur. In the latter case,ANSUL’s recommendation should be sought.

    PERFORMANCE

    APPLICATION

    DESCRIPTION

    3% FLUOROPROTEIN FOAM CONCENTRATEEXTINGUISHING AGENT

    Data/Specifications

  • ANSUL 3% Fluoroprotein Foam Concentrate is approved, qualifiedunder, listed or meets the requirements of the following specificationsand standards:

    Underwriters Laboratories, Inc. – UL Standard 162

    1. Foam Quality Test

    2. Class B Hydrocarbon Fuel Fire Tests

    3. Foam Identification Tests

    4. Test of shipping containers

    5. Class B Hydrocarbon fuel fire tests using foam water sprinkler (bothupright and pendent approvals)

    6. Subsurface Injection

    It is impractical for ANSUL to list its 3% Fluoroprotein Foam Concentratewith every piece of UL listed hardware. Moreover there are numerousfoam hardware components without UL listings that cannot be listed foruse with any fluoroprotein foam agent.

    Many unlisted pieces of foam hardware should be similar to those listed.However, on installations where ANSUL 3% foam concentrate may beused with hardware components of significantly different types thanthose tested, contact ANSUL for recommendations.

    Part No. Description______ _________73973 3% Fluoroprotein Foam – 5 gallon73972 3% Fluoroprotein Foam – 55 gallon

    Shipping Weight:5 gal (19 L) pail – 51 lb (23.1 kg)55 gal (208 L) drum – 555 lb (262.6 kg)

    Cube:5 gal (19 L) pail – 1.08 ft3 (0.0305 m3)55 gal (208 L) drum – 11.33 ft3 (0.3208 m3)

    ORDERING INFORMATION

    APPROVALS AND LISTINGS

    Copyright ©2007 Ansul IncorporatedForm No. F-93202-1

    ANSULis a trademark of Ansul Incorporated or its affiliates.

    Ansul IncorporatedMarinette, WI 54143-2542

    715-735-7411www.ansul.com

  • DESCRIPTION

    ANSULITE 1% AFFF (Aqueous Film-Forming Foam) Concentrate is formulated from specialty fluorochemical and hydrocarbon surfactants along with solvents. It is transported and stored as a concentrate to provide ease of use and considerable savings in weight and volume.It is intended for use as a 1% proportioned solution in fresh, salt or hard water. It may also be used and stored as a 1% premixed solution in fresh or potable water only. The correct proportioning or mixture ratio is 1 part concentrate to 99 parts of water.Three fire extinguishment mechanisms are in effect when using ANSULITE 1% AFFF Concentrate. First, an aqueous film is formed which works to help prevent the release of fuel vapor. Second, the foam blanket from which the film-forming liquid drains effectively excludes oxygen from the fuel surface. Third, the water content of the foam provides a cooling effect.

    TYPICAL PHYSIOCHEMICAL PROPERTIES AT 77 °F (25 °C)Appearance Colorless to Pale Yellow LiquidDensity 1.036 g/ml ± 0.01pH 7.0 – 8.5Refractive Index 1.3884 ± 0.0020Surface Tension (1% Solution) 18 ± 1 dynes/cmViscosity 7.5 ± 1 centistokes

    APPlICATION

    ANSULITE 1% AFFF Concentrate is intended for use on Class B hydrocarbon fuel fires having low water solubility such as various crude oils, gasolines, diesel fuels, aviation fuels, etc. It is not suitable for use on fuels having appreciable water solubility (polar solvents), i.e., methyl and ethyl alcohol, acetone, and methyl ethyl ketone. It can be used with both aspirating and non-aspirating discharge devices because of the low energy required to make it foam.

    Its excellent wetting characteristics make it useful in combating Class A fires as well. It can be used with dry chemical extinguishing agents without regard to the order of application to provide even greater fire protection capability.

    FIRE PERFORMANCE

    The fire performance of ANSULITE 1% AFFF Concentrate is measured against specifications and standards such as U.S. Military Specification MIL-F-24385 and Underwriters Laboratories Standard UL 162. Reports covering this fire performance are available on request since standards and specifications such as those cited are continuously being upgraded and changed.

    FOAMING PROPERTIES

    When used with fresh or salt water or water of any hardness, at the correct dilution with most conventional foam making equipment, the expansion will vary depending on the performance characteristics of the equipment. Aspirating discharge devices produce expansion ratios of from 6:1 to 10:1 depending primarily on type of aspirating device and flow rate. Subsurface injection generally produces expansion ratios of 2:1 to 3:1. Non-aspirating devices such as handline water fog/stream nozzles or standard sprinkler heads give expansion ratios of 2:1 to 4:1.

    PROPORTIONING

    ANSULITE 1% AFFF Concentrate can be proportioned (at the correct dilution) using most conventional proportioning equipment such as:

    1. Balanced pressure and in-line balanced pressure pumped propor-tioning equipment

    2. Balanced pressure bladder tank proportioner

    3. Fixed or portable (in-line) venturi type proportioners

    4. Handline nozzles with fixed induction/pickup tubes

    The minimum and maximum usable temperature for ANSULITE 1% AFFF Concentrate in this equipment is 35 °F (2 °C) to 120 °F (49 °C) respectively.

    STORAGE/SHElF lIFE

    When stored in the packaging supplied (polyethylene drums or pails) or in equipment recommended by the manufacturer as part of the foam system and within the temperature limits specified, the shelf life of ANSULITE AFFF 1% AFFF Concentrate is about 20-25 years. The factors affecting shelf life and stability for ANSULITE AFFF Agents are discussed in detail in ANSUL Technical Bulletin No. 54. If the product is frozen during storage or transportation, thawing will render the product completely usable.

    COMPATIBIlITY

    Tyco Fire Protection Products has conducted testing with admixtures of different manufacturers’ AFFF products in varying proportions and is satisfied that the ANSULITE 1% AFFF is compatible with these prod-ucts. Refer to ANSUL Technical Bulletin No. 48 for a more detailed discussion of compatibility.

    Different types of foam concentrates, i.e., AFFF, protein base, etc., should not be mixed under any circumstances.

    MATERIAlS OF CONSTRUCTION COMPATIBIlITY

    Tests have been performed with ANSULITE 1% AFFF Concentrate verifying its compatibility with standard carbon steel ‘‘black’’ pipe and pipe manufactured from various stainless steel or brass compounds. Alternative pipe, fittings, and valves may be used in some cases if acceptable to the customer and/or the authority having jurisdiction. Refer to ANSUL Technical Bulletin No. 59 addressing acceptable materials of construction for use with ANSUL foam concentrates.

    Galvanized pipe and fittings must not be used in areas where undiluted concentrate will contact them since corrosion will result.

    Please first consult Tyco Fire Protection Products for specific guidelines concerning materials of construction.

    ANSUlITE 1% AFFF CONCENTRATEData/Specifications

  • INSPECTION

    As with any fire extinguishing agent, ANSULITE 1% AFFF Concentrate, whether in the concentrate or pre-mixed form should be inspected peri-odically. Please refer to the Field Inspection Manual, Part No. 31274, for the detailed procedures to perform this inspection. An annual inspection is recommended unless unusual conditions of exposure occur such as are described in ANSUL Technical Bulletin No. 54. In such cases, Tyco Fire Protection Products’ recommendation should be sought.

    APPROVAlS AND lISTINGS

    ANSULITE 1% AFFF Concentrate is approved, qualified under, listed or meets the requirements of the following specifications and standards:Underwriters Laboratories Inc.

    UL Standard 162 (latest edition)

    1. Foam Quality Tests

    2. Class B Hydrocarbon Fuel Fire Tests

    3. Foam Identification Tests

    4. Tests of Shipping Containers

    5. Class B Hydrocarbon Fuel Sprinkler Tests (foam water and standard type both upright and pendent approvals)

    6. Subsurface Injection at 1% Proportioning

    It is impractical for Tyco Fire Protection Products to list its ANSULITE 1% agents with every piece of UL listed hardware. Moreover, there are numerous foam hardware components without UL listings that cannot be listed for use with any AFFF agent.

    Many unlisted pieces of foam hardware should be similar to those listed. However, on installations where ANSULITE 1% may be used with hardware components of significantly different types than those tested, contact Tyco Fire Protection Products for recommendations.

    ORDERING INFORMATION

    ANSULITE 1% AFFF is available in pails, drums, totes, or bulk shipment.Part No. Description Shipping Weight Cube_______ _________ _____________ _____55804 5 gal 45 lb 1.25 ft3 (19 L) Pail (20.4 kg) (0.0353 m3)55811 55 gal 495 lb 11.83 ft3 (208 L) Drum (224.5 kg) (0.335 m3)432160 265 gal 2465 lb 50.05 ft3 (1000 L) Tote (1118 kg) (1.42 m3)73595 Bulk Order Contact Technical Services

    Copyright ©2011 Tyco Fire Protection ProductsAll rights reserved.

    Form No. F-81297-06One Stanton StreetMarinette, WI 54143-2542

    +1-715-735-7411www.ansul.com

  • ANSULITE® 1% Freeze-Protected AFFF (Aqueous Film-Forming) FoamConcentrate is formulated from specialty fluorochemical and hydrocar-bon surfactants along with solvents. It is transported and stored as aconcentrate to provide ease of use and considerable savings in weightand volume.

    It is intended for use as a 1% proportioned solution in fresh, salt or hardwater. It may also be used and stored as a 1% premixed solution infresh or potable water only. The correct proportioning or mixture ratio is1 part concentrate to 99 parts of water.

    Three fire extinguishment mechanisms are in effect when usingANSULITE 1% Freeze-Protected AFFF Concentrate. First, an aqueousfilm is formed which works to help prevent the release of fuel vapor.Second, the foam blanket from which the film-forming liquid drains effec-tively excludes oxygen from the fuel surface. Third, the water content ofthe foam provides a cooling effect.

    Typical Physiochemical Properties at 77 °F (25 °C)

    Appearance Colorless to Pale Yellow Liquid

    Density 1.059 g/ml ± 0.020

    pH 7.0 – 8.5

    Refractive Index 1.4000 ± 0.0020

    Surface Tension (1% Solution) 18 ± 1 dynes/cm

    Viscosity 10.5 ± 1 centistokes

    ANSULITE 1% Freeze-Protected AFFF Concentrate is intended for useon Class B hydrocarbon fuel fires having low water solubility such asvarious crude oils, gasolines, diesel fuels, aviation fuels, etc. It is notsuitable for use on fuels having appreciable water solubility (polarsolvents), i.e., methyl and ethyl alcohol, acetone, and methyl ethylketone. It can be used with both aspirating and non-aspirating dischargedevices because of the low energy required to make it foam.

    Its excellent wetting characteristics make it useful in combating Class Afires as well. It can be used with dry chemical extinguishing agentswithout regard to the order of application to provide even greater fireprotection capability.

    Fire Performance – The fire performance of ANSULITE 1% Freeze-Protected AFFF Concentrate is measured primarily against UnderwritersLaboratories Standard UL 162.

    Foaming Properties – When used with fresh or salt water or water ofany hardness, at the correct dilution with most conventional foammaking equipment, the expansion will vary depending on the perform-ance characteristics of the equipment. Aspirating discharge devicesproduce expansion ratios of from 6:1 to 10:1 depending primarily ontype of aspirating device and flow rate. Subsurface injection is a specialcase where generally expansion ratios of 2:1 to 3:1 are preferred but upto 4:1 is allowed. Non-aspirating devices such as handline waterfog/stream nozzles or standard sprinkler heads give expansion ratios of2:1 to 4:1.

    Proportioning – ANSULITE 1% Freeze-Protected AFFF Concentratecan be easily proportioned (at the correct dilution) using most conven-tional proportioning equipment such as:

    1. Balanced pressure and in-line balanced pressure pumped proportion-ing equipment

    2. Balanced pressure bladder tank proportioner

    3. Around the pump type proportioners

    4. Fixed or portable (in-line) venturi type proportioners

    5. Handline nozzles with fixed induction/pickup tubes

    The minimum and maximum usable temperature for ANSULITE 1%Freeze-Protected AFFF Concentrate in this equipment is –20 °F(–29 °C) to 120 °F (49 °C) respectively.

    Storage/Shelf Life – When stored in the packaging supplied (polyethyl-ene drums or pails) or in equipment recommended by the manufactureras part of the foam system and within the temperature limits specified,the shelf life of ANSULITE 1% Freeze-Protected AFFF Concentrate isabout 20-25 years. The factors affecting shelf life and stability forANSULITE AFFF concentrates are discussed in detail in Ansul TechnicalBulletin No. 54. If the product is frozen during storage or transportation,thawing will render the product completely usable. Mixing after freezethaw cycle is recommended.

    Compatability – ANSUL has conducted testing with admixtures of differ-ent manufacturers’ AFFF products in varying proportions and is satisfiedthat the ANSULITE 1% Freeze-Protected AFFF Concentrate is compati-ble with these products. Refer to Ansul Technical Bulletin No. 48 for amore detailed discussion of compatibility.

    Different types of foam concentrates, i.e., AFFF, protein base, etc.,should not be mixed under any circumstances.

    Materials of Construction Compatibility – Tests have been performedwith ANSULITE AFFF concentrates verifying compatibility with standardcarbon steel “black” pipe and pipe manufactured from various stainlesssteel or brass compounds. Alternative pipe, fittings, and valves may beused in some cases if acceptable to the customer and/or the authorityhaving jurisdiction. Refer to Ansul Technical Bulletin No. 59 addressingacceptable materials of construction for use with ANSUL foam concen-trates.

    Galvanized pipe and fittings must not be used in areas where undilutedconcentrate will contact them since corrosion will result.

    Please first consult ANSUL Fire Protection for specific guidelinesconcerning materials of constructions.

    Inspection – As with any fire extinguishing agent, ANSULITE AFFFconcentrates, whether in the concentrate or pre-mixed form, should beinspected periodically. NFPA 11 “Standard for Low Expansion Foamand Combined Agent Systems” requires that foam concentrate samplesbe submitted to the manufacturer or other qualified laboratory for qualitycondition testing at least annually. Contact ANSUL for further informationon annual inspection.

    PERFORMANCE

    APPLICATION

    DESCRIPTION

    ANSULITE® 1% FREEZE-PROTECTED AFFFCONCENTRATE EXTINGUISHING AGENT —20 °F (—29 °C)

    Data/Specifications

  • ANSULITE 1% Freeze Protected AFFF Concentrate is approved, quali-fied under, listed or meets the requirements of the following specifica-tions and standards:

    Underwriters Laboratories Inc. – UL Standard 162

    1. Foam Quality Tests

    2. Class B Hydrocarbon Fuel Fire Tests

    3. Foam Identification Tests

    4. Tests of Shipping Containers

    It is impractical for ANSUL to list its ANSULITE 1% Freeze-ProtectedAFFF Concentrate with every piece of UL listed hardware. Moreover,there are numerous foam hardware components without UL listings thatcannot be listed for use with any AFFF concentrate.

    Many unlisted pieces of foam hardware should be similar to those listed.However, on installations where ANSULITE 1% Freeze-Protected AFFFConcentrate may be used with hardware components of significantlydifferent types than those tested, contact ANSUL for recommendations.

    ANSULITE 1% Freeze-Protected AFFF Concentrate is available in pails,drums, totes, or bulk shipment.

    Part No. 415301 5 gallon pailPart No. 415303 55 gallon drumPart No. 432156 265 gallon totePart No. 415305 Bulk (contact ANSUL about domestic truck-load

    delivery)

    Shipping Weight:5 gal (19 L) pail – 45 lb (20.4 kg)55 gal (208.1 L) drum – 495 lb (224.5 kg)265 gal (1000 L) tote – 2465 lb (1118 kg)

    Cube:5 gal (19 L) pail – 1.25 ft3 (0.0353 m3)55 gal (208.1 L) drum – 11.83 ft3 (0.3350 m3)265 gal (1000 L) tote – 50.05 ft3 (1.42 m3)

    ORDERING INFORMATION

    APPROVALS AND LISTINGS

    Copyright ©2007 Ansul IncorporatedForm No. F-9239-2

    ANSUL and ANSULITE are trademarks of Ansul Incorporated or its affiliates.

    Ansul IncorporatedMarinette, WI 54143-2542

    715-735-7411www.ansul.com

  • DESCRIPTION

    ANSULITE 3% (AFC-3A) AFFF (Aqueous Film-Forming Foam) Concentrate is formulated from specialty fluorochemical and hydrocar-bon type surfactants along with solvents. It is transported and stored as a concentrate to provide ease of use and considerable savings in weight and volume.

    It is intended for use as a 3% proportioned solution in fresh, salt or hard water. It may also be used and stored as a 3% premixed solution in fresh or potable water only. The correct proportioning or mixture ratio is 3 parts of concentrate to 97 parts of water.

    Three fire extinguishment mechanisms are in effect when using ANSULITE 3% (AFC-3A) AFFF Concentrate. First, an aqueous film is formed which works to help prevent the release of fuel vapor. Second, the foam blanket from which the film-forming liquid drains effectively excludes oxygen from the fuel surface. Third, the water content of the foam provides a cooling effect.

    Typical Physiochemical Properties at 77 °F (25 °C)Appearance Colorless to Pale Yellow LiquidDensity 1.026 g/ml ± 0.020pH 7.0 – 8.5Refractive Index 1.3490 ± 0.0025Surface Tension (3% Solution) 18 ± 1 dynes/cmViscosity 2.9 ± 1 centistokes

    APPLICATION

    ANSULITE 3% (AFC-3A) AFFF Concentrate is intended for use on Class B hydrocarbon fuel fires having low water solubility such as various crude oils, gasolines, diesel fuels, aviation fuels, etc. It is not suitable for use on fuels having appreciable water solubility (polar solvents), i.e., methyl and ethyl alcohol, acetone, and methyl ethyl ketone. It can be used with both aspirating and non-aspirating discharge devices because of the low energy required to make it foam.

    Its excellent wetting characteristics make it useful in combating Class A fires as well. It can be used with dry chemical extinguishing agents without regard to the order of application to provide even greater fire protection capability.

    PERFORMANCE

    Fire Performance – The fire performance of ANSULITE 3% (AFC-3A) AFFF Concentrate is measured against specifications and stan-dards such as U.S. Military Specification MIL-F-24385 but is not on the Qualified Product List (QPL). ANSULITE 3% (AFC-3A) AFFF Concentrate has also been tested to Underwriters Laboratories Standard 162. Reports covering this fire performance are available on request since standards and specifications such as those cited are continuously being upgraded and changed.

    Foaming Properties – When used with fresh or salt water or water of any hardness, at the correct dilution with most conventional foam making equipment, the expansion will vary depending on the perfor-mance characteristics of the equipment. Aspirating discharge devices produce expansion ratios of from 6:1 to 10:1 depending primarily on type of aspirating nozzle and flow rate. Sub surface injection is a special case where generally expansion ratios of 2:1 to 3:1 are preferred but up to 4:1 is allowed. Non-aspirating devices such as handline water fog/stream nozzles or standard sprinkler heads give expansion ratios of 2:1 to 4:1.

    Proportioning – ANSULITE 3% (AFC-3A) AFFF Concentrate can be easily proportioned (at the correct dilution) using most conventional proportioning equipment such as:1. Balanced pressure and in-line balanced pressure pumped proportion-

    ing equipment2. Balanced pressure bladder tank type proportioners3. Around the pump type proportioners4. Fixed or portable (in-line) venturi type proportioners5. Handline nozzles with fixed induction/pickup tubes

    The minimum and maximum usable temperatures for ANSULITE 3% (AFC-3A) AFFF Concentrate in this equipment is 35 °F (2 °C) to 120 °F (49 °C) respectively.

    Storage/Shelf Life – When stored in the packaging supplied (polyethyl-ene drums or pails) or in equipment recommended by the manufacturer as part of the foam system within the temperature limits specified, the shelf life of ANSULITE 3% (AFC-3A) AFFF Concentrate is about 20-25 years. The factors affecting shelf life and stability for ANSULITE AFFF Concentrates are discussed in detail in ANSUL Technical Bulletin No. 54. If the product is frozen during storage or transportation, thawing will render the product completely usable. Mixing after freeze thaw cycling is recommended.

    Compatibility – Certain specifications such as U.S. Military Specification MIL-F-24385 require that products placed on the Qualified Products List (QPL) for that specification demonstrate performance compatibility in all mixture proportions.

    With regard to non-qualified (QPL) AFFF type concentrates, they should only be mixed in an emergency, or if the manufacturer has supporting test data to substantiate that the mixture meets the same requirements as the individual component concentrates. Refer to ANSUL Technical Bulletin No. 48 for a more detailed discussion of compatibility.

    Different types of foam concentrates, i.e., AFFF, protein base, etc., should not be mixed under any circumstances.

    Materials of Construction Compatibility – Tests have been performed with ANSULITE 3% (AFC-3A) AFFF Concentrate verifying its compat-ibility with standard carbon steel “black” pipe and pipe manufactured from various stainless steel or brass compounds. Alternative pipe, plastic fittings, and valves may be used in some cases if acceptable to the customer and/or the authority having jurisdiction. Refer to ANSUL Technical Bulletin No. 59, Form No. F-90109, addressing acceptable materials of construction for use with ANSUL foam concentrates.

    Galvanized pipe and fittings must not be used in areas where undiluted concentrate will contact them since corrosion will result.

    Please first consult Tyco Fire Protection Products for specific guidelines concerning materials of construction.

    Inspection – As with any fire extinguishing agent, ANSULITE 3% (AFC-3A) AFFF Concentrate, whether in the concentrate or pre-mixed form should be inspected periodically. NFPA 11 “Standard for Low Expansion Foam and Combined Agent Systems” requires that foam concentrate samples be submitted to the manufacturer or other qualified laboratory for quality condition testing at least annually. Contact Tyco Fire Protection Products for further information on annual inspection.

    ANSULITE 3% (AFC-3A) AFFF CONCENTRATEData/Specifications

  • APPROVALS AND LISTING

    ANSULITE 3% (AFC-3A) AFFF Concentrate is approved, qualified under, listed or meets the requirements of the following specifications and standards:

    Underwriters Laboratories Inc. – UL Standard 1621. Foam Quality Tests2. Class B Hydrocarbon Fuel Fire Tests3. Foam Identification Tests4. Tests of Shipping Containers5. Class B Hydrocarbon Fuel Sprinkler Tests (Foam water and standard

    type both upright and pendent approvals)

    Factory Mutual Research Corporation – Approval Guide

    It is impractical for Tyco Fire Protection Products to list its ANSULITE 3% AFFF Concentrate with every piece of UL listed hardware. Moreover, there are numerous foam hardware components without UL listings that cannot be listed for use with any AFFF concentrate.

    Many unlisted pieces of foam hardware should be similar to those listed. However, on installations where ANSULITE 3% AFFF Concentrate may be used with hardware components of significantly different types than those tested, contact Tyco Fire Protection Products for recommendations.

    ORDERING INFORMATION

    ANSULITE 3% (AFC-3A) is available in pails, drums, totes, or bulk shipment.Part No. Description Shipping Weight Cube_______ _________ _____________ _____55800 5 gal 45 lb 1.25 ft3 (19 L) Pail (20.4 kg) (0.0353 m3)55809 55 gal 495 lb 11.83 ft3 (208 L) Drum (224.5 kg) (0.335 m3)431499 265 gal 2465 lb 50.05 ft3 (1000 L) Tote (1118 kg) (1.42 m3)26700 Bulk Order Contact Technical Services

    Copyright ©2011 Tyco Fire Protection ProductsAll rights reserved.

    Form No. F-83124-07One Stanton StreetMarinette, WI 54143-2542

    +1-715-735-7411www.ansul.com

  • ANSULITE® Premium 3% (AFC-5A) AFFF (Aqueous Film-FormingFoam) Concentrate is formulated from specialty fluorochemical andhydrocarbon type surfactants along with solvents. It is transported andstored as a concentrate to provide ease of use and considerablesavings in weight and space.

    It is intended for use as a 3% proportioned solution in fresh, salt, or hardwater. Water hardness should not exceed 500 ppm expressed ascalcium and magnesium. It may also be used and stored as a 3%premixed solution in fresh or potable water only. The correct proportion-ing or mixture ratio is 3 parts of concentrate to 97 parts of water.

    Three fire extinguishment mechanisms are in effect when usingANSULITE Premium 3% (AFC-5A) AFFF Concentrate. First, an aqueousfilm is formed which works to help prevent the release of fuel vapor.Second, the foam blanket from which the film-forming liquid drains effec-tively excludes oxygen from the fuel surface. Third, the water content ofthe foam provides a cooling effect.

    Typical Physiochemical Properties at 77 °F (25 °C)

    Appearance Colorless to Pale Yellow Liquid

    Density 1.023 g/ml ± 0.020

    pH 7.0 – 8.5

    Refractive Index 1.3640 ± 0.0020

    Surface Tension (3% Solution) 18 ±1 dynes/cm

    Viscosity 4.5 ± 1 centistokes

    ANSULITE Premium 3% (AFC-5A) AFFF Concentrate is intended foruse on Class B hydrocarbon fuel fires having low water solubility suchas various crude oils, gasolines, diesel fuels, aviation fuels, etc. It is notsuitable for use on fuels having appreciable water solubility (polarsolvents), i.e., methyl and ethyl alcohol, acetone, and methyl ethylketone. It can be used with both aspirating and non-aspirating dischargedevices because of the low energy required to make it foam.

    Its excellent wetting characteristics make it useful in combating Class Afires as well. It can be used with dry chemical extinguishing agentswithout regard to the order of application to provide even greater fireprotection capability.

    Fire Performance – The fire performance of ANSULITE Premium 3%(AFC-5A) AFFF Concentrate is measured against specifications andstandards such as U.S. Military Specification MIL-F-24385 and Under-writers Laboratories Standard UL 162. Reports covering this fireperformance are available on request since standards and specificationssuch as those cited are continuously being upgraded and changed.

    Foaming Properties – When used with fresh, salt or hard water at thecorrect dilution with most conventional foam making equipment, theexpansion will vary depending on the performance characteristics of theequipment. Aspirating discharge devices produce expansion ratios offrom 6:1 to 10:1 depending primarily on type of aspirating nozzle andflow rate. In general the higher the flow rate the higher the expansionratio. Thus monitors and foam chambers normally produce higherexpansion ratios than foam water sprinkler heads and hand held typenozzles. Subsurface injection is a special case where generally expan-sion ratios of 2:1 to 3:1 are preferred but up to 4:1 is allowed. Non-aspi-rating devices such as handline water fog/stream nozzles or standardsprinkler heads give expansion ratios of 2:1 to 4:1.

    Proportioning – ANSULITE Premium 3% (AFC-5A) AFFF Concentratecan be proportioned easily at the correct dilution using most conven-tional proportioning equipment such as:

    1. Balanced pressure and in-line balanced pressure pumped proportion-ing equipment

    2. Balanced pressure bladder tank type proportioners

    3. Around-the-pump type proportioners

    4. Fixed or portable (in-line) venturi type proportioners

    5. Handline nozzles with fixed induction/pickup tubes

    The minimum and maximum usable temperatures for ANSULITEPremium 3% (AFC-5A) AFFF Concentrate in this equipment is 35 °F(2 °C) to 120 °F (49 °C) respectively.

    Storage/Shelf Life – When stored in the packaging supplied (polyethyl-ene drums or pails) or in equipment recommended by the manufactureras part of the foam system and within the temperature limits specified,the shelf life of ANSULITE Premium 3% (AFC-5A) AFFF Concentrate isabout 20-25 years. The factors affecting shelf life and stability forANSULITE AFFF Agents are discussed in detail in Ansul TechnicalBulletin No. 54. If the product is frozen during storage or transportation,thawing will render the product completely usable. Upon thawing, gentlemixing to ensure a homogeneous solution is recommended.

    Compatibility – Certain specifications such as U.S. MilitarySpecification MIL-F-24385 require that products placed on the QualifiedProducts List (QPL) for that specification demonstrate performancecompatibility in all mixture proportions. ANSULITE Premium 3%(AFC-5A) AFFF Concentrate which is on the QPL for this specification istherefore compatible with any other product qualified under that specifi-cation or preceding versions of this specification.

    With regard to other non-qualified (QPL) AFFF type concentrates, theyshould only be mixed in an emergency, or if the manufacturer hassupporting test data to substantiate that the mixture meets the samerequirements as the individual component concentrates. Refer to AnsulTechnical Bulletin No. 48 for a more detailed discussion of compatibility.

    Different types of foam concentrates, i.e., AFFF, protein base, etc.,should not be mixed under any circumstances.

    Materials of Constructions Compatibility – Tests have beenperformed with ANSULITE Premium 3% (AFC-5A) AFFF Concentrateverifying its compatibility with standard carbon steel ‘‘black’’ pipe andpipe manufactured from various stainless steel or brass compounds.Alternative pipe, fittings, and valves may be used in some cases ifacceptable to the customer and/or the authority having jurisdiction. Referto Ansul Technical Bulletin No. 59, Form No. F-90109, addressingacceptable materials of construction for use with ANSUL foam concen-trates.

    Galvanized pipe and fittings must not be used in areas where undilutedconcentrate will contact them since corrosion will result.

    Please first consult Ansul Incorporated for specific guidelines concern-ing materials of construction.

    Inspection – As with any fire extinguishing agent, ANSULITE Premium3% (AFC-5A) AFFF Concentrate, whether in the concentrate or pre-mixed form should be inspected periodically. Please refer to the FieldInspection Manual, Ansul Part No. 31274, for the detailed procedures toperform this inspection. An annual inspection is recommended unlessunusual conditions of exposure occur, such as are described in AnsulTechnical Bulletin No. 54. In such cases, ANSUL’s recommendationshould be sought.

    PERFORMANCE

    APPLICATION

    DESCRIPTION

    ANSULITE® PREMIUM 3% (AFC-5A)AFFF CONCENTRATE

    Data/Specifications

  • ANSULITE Premium 3% (AFC-5A) AFFF Concentrate is approved, qual-ified under, listed or meets the requirements of the following specifica-tions and standards:

    U.S. Military Specification – MIL-F-24385 with latest amendments andlisted on QPL 24385 issued by U.S. Navy (NAVSEA).

    Underwriters Laboratories Inc. – UL Standard 162

    1. Foam Quality Tests

    2. Class B Hydrocarbon Fuel Fire Tests

    3. Foam Identification Tests

    4. Tests of Shipping Containers

    5. Class B Hydrocarbon Fuel Sprinkler Tests (Standard type bothupright and pendant approvals only).

    6. Subsurface Injection

    It is impractical for ANSUL to list its ANSULITE 3% agents with everypiece of UL listed hardware. Moreover, there are numerous foam hard-ware components without UL listings that can not be listed for use withany AFFF agent.

    Unlisted pieces of foam hardware should be similar to those listed.However, on installations where ANSULITE 3% may be used with hard-ware components of significantly different types than those tested,contact ANSUL for recommendations.

    ANSULITE Premium 3% (AFC-5A) AFFF Concentrate is available inpails, drums, totes, or bulk shipment.

    Part No. 68122 5 gallon pailPart No. 68123 55 gallon drumPart No. 432336 265 gallon totePart No. 68119 Bulk (contact ANSUL about domestic truckload

    delivery)

    Shipping Weight:5 gal (19 L) pail – 45 lb (20.4 kg)55 gal (208.1 L) drum – 495 lb (224.5 kg)

    265 gal (1000 L) tote – 2465 lb (1118 kg)

    Cube:5 gal (19 L) pail – 1.25 ft3 (0.0353 m3)55 gal (208.1 L) drum – 11.83 ft3 (0.3350 m3)265 gal (1000 L) tote – 50.05 ft3 (1.42 m3)

    ORDERING INFORMATION

    APPROVALS AND LISTING

    Copyright ©2007 Ansul IncorporatedForm No. F-83126-6

    ANSUL and ANSULITE are registered trademarks of Ansul Incorporated or its affiliates.

    Ansul IncorporatedMarinette, WI 54143-2542

    715-735-7411www.ansul.com

  • ANSULITE® 3% Freeze-Protected AFFF (Aqueous Film-Forming Foam)Concentrate is formulated from specialty fluorochemical and hydrocar-bon type surfactants along with solvents. It is transported and stored asa concentrate to provide ease of use and considerable savings in weightand volume.

    It is intended for use as a 3% proportioned solution in fresh, salt or hardwater. It may also be used and stored as a 3% premixed solution infresh or potable water only. However, the diluted solution will freeze at32 °F (0 °C). The correct proportioner mixture ratio is 3 parts concen-trate to 97 parts water.

    Three fire extinguishment mechanisms are in effect when usingANSULITE 3% Freeze-Protected AFFF Concentrate. First, an aqueousfilm is formed which works to help prevent the release of fuel vapor.Second, the foam blanket from which the film-forming liquid drains effec-tively excludes oxygen from the fuel surface. Third, the water content ofthe foam provides a cooling effect.

    Typical Physiochemical Properties at 77 °F (25 °C)of ANSULITE 3% Freeze-Protected AFFF Concentrate

    Appearance Colorless to Pale Yellow Liquid

    Density 1.050 g/ml ± 0.025

    pH 7.0 – 8.5

    Refractive Index 1.3910 ± 0.0030

    Surface Tension (3% Solution) 18 ± 1 dynes/cm

    Viscosity 7 ± 2 centistokes

    ANSULITE 3% Freeze-Protected AFFF Concentrate is intended for useon Class B hydrocarbon fuel fires having low water solubility such asvarious crude oils, gasolines, diesel fuels, aviation fuels, etc. It is notsuitable for use on fuels having appreciable water solubility (polarsolvents), i.e., methyl and ethyl alcohol, acetone, and methyl ethylketone. It can be used with both aspirating and non-aspirating dischargedevices because of the low energy required to make it foam.

    Its excellent wetting characteristics make it useful in combating Class Afires as well. It can be used with dry chemical extinguishing agentswithout regard to the order of application to provide even greater fireprotection capability.

    Fire Performance – The fire performance of ANSULITE 3% Freeze-Protected AFFF Concentrate is measured against specifications andstandards such as U.S. Military Specification MIL-F-24385 andUnderwriters Laboratories Standard UL 162. Reports covering this fireperformance are available on request since standards and specificationssuch as those cited are continuously being upgraded and changed.

    Foaming Properties – When used with fresh salt water or hard water atthe correct dilution with most conventional foam making equipment, theexpansion will vary depending on the performance characteristics of theequipment. Aspirating discharge devices produce expansion ratios offrom 6:1 to 10:1 depending primarily on type of aspirating device andflow rate. In general, the higher the flow rate the higher the expansionratio. Subsurface injection is a special case where generally expansionratios of 2:1 to 3:1 are preferred but up to 4:1 is allowed. Non-aspiratingdevices such as handline water fog/stream nozzles or standard sprinklerheads give expansion ratios of 2:1 to 4:1.

    Proportioning – ANSULITE 3% Freeze-Protected AFFF Concentratecan be proportioned easily at the correct dilution using most conven-tional proportioning equipment such as:

    1. Balanced pressure and in-line balanced pressure pumped proportion-ing equipment

    2. Balanced pressure bladder tank type proportioner

    3. Around-the-pump type proportioners

    4. Fixed or portable (in-line) venturi type proportioners

    5. Handline nozzles with fixed induction/pickup tubes

    The minimum and maximum usable temperatures for ANSULITE 3%Freeze-Protected AFFF Concentrate in this equipment is –20 °F(–29 °C) to 120 °F (49 °C) respectively.

    Storage/Shelf Life – When stored in the packaging supplied (polyethyl-ene drums or pails) or in equipment recommended by the manufactureras part of the foam system and within the temperature limits specified,the shelf life of ANSULITE 3% Freeze-Protected AFFF Concentrate isabout 20-25 years. The factors affecting shelf life and stability forANSULITE AFFF Agents are discussed in detail in Ansul® TechnicalBulletin No. 54. If the product is frozen during storage or transportation,thawing will render the product completely usable. Mixing after thawingis desirable so as to assure a homogenous solution.

    Compatibility – Although ANSULITE 3% Freeze-Protected AFFFConcentrate does not appear on the QPL for MIL-F-24385, ANSUL hasconducted testing with admixtures of different manufacturers products invarying proportions and is satisfied that the ANSULITE 3% Freeze-Protected AFFF Concentrate is compatible with these products. Refer toAnsul Technical Bulletin No. 48 for a more detailed discussion ofcompatibility.

    Different types of foam concentrates, i.e., AFFF, protein base etc.,should not be mixed under any circumstances. Refer to Ansul TechnicalBulletin No. 59 addressing acceptable materials of construction for usewith ANSUL foam concentrates.

    Inspection – As with any fire extinguishing agent, ANSULITE 3%Freeze-Protected AFFF Concentrate, whether in the concentrate or pre-mixed form, should be inspected periodically. Please refer to the FieldInspection Manual, Ansul Part No. 31274, for the detailed procedures toperform this inspection. An annual inspection is recommended unlessunusual conditions of exposure occur, such as are described in AnsulTechnical Bulletin No. 54. In such cases, ANSUL’s recommendationshould be sought.

    PERFORMANCE

    APPLICATION

    DESCRIPTION

    ANSULITE® 3% FREEZE-PROTECTEDAFFF CONCENTRATE –20 °F (–29 °C)

    Data/Specifications

  • ANSULITE 3% Freeze-Protected AFFF Concentrate is approved, quali-fied under, listed or meets the requirements of the following specifica-tions and standards:

    Underwriters Laboratories Inc. – UL Standard 162

    1. Foam Quality Tests

    2. Class B Hydrocarbon Fuel Fire Tests

    3. Foam Identification Tests

    4. Tests of Shipping Containers

    5. Class B Hydrocarbon Fuel Sprinkler Tests (Standard type bothupright and pendent approvals only)

    It is impractical for ANSUL to list its ANSULITE 3% agent with everypiece of UL listed hardware. Moreover, there are numerous foam hard-ware components without UL listings that cannot be listed for use withany AFFF agent.

    Many unlisted pieces of foam hardware should be similar to those listed.However, on installations where ANSULITE 3% may be used with signif-icantly different hardware components than those tested, contact ANSULfor recommendations.

    ANSULITE 3% Freeze-Protected AFFF Concentrate is available in pails,drums, totes, or bulk shipment.

    Part No. 54783 5 gallon pailPart No. 54892 55 gallon drumPart No. 432161 265 gallon totePart No. 54660 Bulk (contact ANSUL about domestic truck-load

    delivery)

    Shipping Weight:5 gal (19 L) pail – 45 lb (20.4 kg)55 gal (208.1 L) drum – 495 lb (224.5 kg)265 gal (1000 L) tote – 2465 lb (1118 kg)

    Cube:5 gal (19 L) pail – 1.25 ft3 (0.0353 m3)55 gal (208.1 L) drum – 11.83 ft3 (0.3350 m3)265 gal (1000 L) tote – 50.05 ft3 (1.42 m3)

    ORDERING INFORMATION

    APPROVALS AND LISTINGS

    Copyright ©2007 Ansul IncorporatedForm No. F-8125-3

    ANSUL and ANSULITE are trademarks of Ansul Incorporated or its affiliates.

    Ansul IncorporatedMarinette, WI 54143-2542

    715-735-7411www.ansul.com

  • DESCRIPTION

    ANSULITE 6% (AFC-3) AFFF (Aqueous Film-Forming Foam) Concentrate is formulated from specialty fluorochemical and hydrocar-bon surfactants along w