foam plastics in building construction/media/6722c1b139ce4597a962c5696ceaf697.pdf• 45 min fire...
TRANSCRIPT
![Page 1: Foam Plastics in Building Construction/media/6722C1B139CE4597A962C5696CEAF697.pdf• 45 min fire engulfs 34.5 acre facility ... FTC Investigation (1972) ... (Plywood in IRC only, for](https://reader030.vdocument.in/reader030/viewer/2022011801/5af6ab737f8b9ae9488f15c3/html5/thumbnails/1.jpg)
Foam Plastics in Building Construction
Douglas H. Evans1 & Marcelo M. Hirschler2
1 Clark County (NV) Building Department2 GBH International
NFPA June 2014 – Session T44
2014 NFPA Conference & Expo
![Page 2: Foam Plastics in Building Construction/media/6722C1B139CE4597A962C5696CEAF697.pdf• 45 min fire engulfs 34.5 acre facility ... FTC Investigation (1972) ... (Plywood in IRC only, for](https://reader030.vdocument.in/reader030/viewer/2022011801/5af6ab737f8b9ae9488f15c3/html5/thumbnails/2.jpg)
NFPA 2014 World Congress and Exposition
Foam Plastics in Building Construction
Douglas H. Evans1 and Marcelo M Hirschler2
1Clark County Nevada Department of Buildings (Las Vegas, NV) 2GBH International (Mill Valley, CA)
ABSTRACT
Using foam plastics safely in building construction is a frequently misunderstood subject. This presentation will address many of the questions concerning fire safety of foam plastics and show how these materials can be used safely in building construction. This overview will cover what foam plastics are, associated fire losses, concerns associated with their fire-safe use, how they have been and are used in building construction, applicable code requirements, and fire testing, as well as their advantages and disadvantages.
![Page 3: Foam Plastics in Building Construction/media/6722C1B139CE4597A962C5696CEAF697.pdf• 45 min fire engulfs 34.5 acre facility ... FTC Investigation (1972) ... (Plywood in IRC only, for](https://reader030.vdocument.in/reader030/viewer/2022011801/5af6ab737f8b9ae9488f15c3/html5/thumbnails/3.jpg)
Structure of Talk Recent fire incidents Introduction: typical foam plastic insulations Building applications of foam plastic insulation Early fire tests Early fire incidents 1970s Federal Trade Commission decision Code revisions Modern fire testing Recent code proposals Summary and conclusions
![Page 4: Foam Plastics in Building Construction/media/6722C1B139CE4597A962C5696CEAF697.pdf• 45 min fire engulfs 34.5 acre facility ... FTC Investigation (1972) ... (Plywood in IRC only, for](https://reader030.vdocument.in/reader030/viewer/2022011801/5af6ab737f8b9ae9488f15c3/html5/thumbnails/4.jpg)
Recent Fire Incidents
![Page 5: Foam Plastics in Building Construction/media/6722C1B139CE4597A962C5696CEAF697.pdf• 45 min fire engulfs 34.5 acre facility ... FTC Investigation (1972) ... (Plywood in IRC only, for](https://reader030.vdocument.in/reader030/viewer/2022011801/5af6ab737f8b9ae9488f15c3/html5/thumbnails/5.jpg)
Why do we care?Notable Losses
Kiss Night Club, Brazil, January 2013˗ 242 fatalities
Station Night Club, RI, February 2003– 100 fatalities
Argentine Night Club fire, Dec. 2004– 194 fatalities
Monte Carlo Exterior Facade– January 2008
Palace Station Exterior Facade– July 1998
Eldorado Hotel, Reno, NV– September 1997
![Page 6: Foam Plastics in Building Construction/media/6722C1B139CE4597A962C5696CEAF697.pdf• 45 min fire engulfs 34.5 acre facility ... FTC Investigation (1972) ... (Plywood in IRC only, for](https://reader030.vdocument.in/reader030/viewer/2022011801/5af6ab737f8b9ae9488f15c3/html5/thumbnails/6.jpg)
2003 The Station Nightclub
West Warwick,
Rhode Island
(100 fatalities)
![Page 7: Foam Plastics in Building Construction/media/6722C1B139CE4597A962C5696CEAF697.pdf• 45 min fire engulfs 34.5 acre facility ... FTC Investigation (1972) ... (Plywood in IRC only, for](https://reader030.vdocument.in/reader030/viewer/2022011801/5af6ab737f8b9ae9488f15c3/html5/thumbnails/7.jpg)
2003 The Station Nightclub
![Page 8: Foam Plastics in Building Construction/media/6722C1B139CE4597A962C5696CEAF697.pdf• 45 min fire engulfs 34.5 acre facility ... FTC Investigation (1972) ... (Plywood in IRC only, for](https://reader030.vdocument.in/reader030/viewer/2022011801/5af6ab737f8b9ae9488f15c3/html5/thumbnails/8.jpg)
![Page 9: Foam Plastics in Building Construction/media/6722C1B139CE4597A962C5696CEAF697.pdf• 45 min fire engulfs 34.5 acre facility ... FTC Investigation (1972) ... (Plywood in IRC only, for](https://reader030.vdocument.in/reader030/viewer/2022011801/5af6ab737f8b9ae9488f15c3/html5/thumbnails/9.jpg)
The Station NightclubOFFICE
KITCHEN
SUNROOM
MAINBAR
BUILDING FRONT
BUILDING REAR
DANCEFLOOR
DRESSING ROOM
RAISED DINING AREA
RESTROOM
RESTROOM
STORAGE
RAISEDPLATFORM
Door 4
N
Door 1
Door 3
Door 2
Door 5
SIDE BAR
Main Entrance
![Page 10: Foam Plastics in Building Construction/media/6722C1B139CE4597A962C5696CEAF697.pdf• 45 min fire engulfs 34.5 acre facility ... FTC Investigation (1972) ... (Plywood in IRC only, for](https://reader030.vdocument.in/reader030/viewer/2022011801/5af6ab737f8b9ae9488f15c3/html5/thumbnails/10.jpg)
Buenos Aires, ArgentinaNightclub fire, 2004194 fatalities
![Page 11: Foam Plastics in Building Construction/media/6722C1B139CE4597A962C5696CEAF697.pdf• 45 min fire engulfs 34.5 acre facility ... FTC Investigation (1972) ... (Plywood in IRC only, for](https://reader030.vdocument.in/reader030/viewer/2022011801/5af6ab737f8b9ae9488f15c3/html5/thumbnails/11.jpg)
![Page 12: Foam Plastics in Building Construction/media/6722C1B139CE4597A962C5696CEAF697.pdf• 45 min fire engulfs 34.5 acre facility ... FTC Investigation (1972) ... (Plywood in IRC only, for](https://reader030.vdocument.in/reader030/viewer/2022011801/5af6ab737f8b9ae9488f15c3/html5/thumbnails/12.jpg)
![Page 13: Foam Plastics in Building Construction/media/6722C1B139CE4597A962C5696CEAF697.pdf• 45 min fire engulfs 34.5 acre facility ... FTC Investigation (1972) ... (Plywood in IRC only, for](https://reader030.vdocument.in/reader030/viewer/2022011801/5af6ab737f8b9ae9488f15c3/html5/thumbnails/13.jpg)
Kiss Night Club FireBrazil – 2013 – 242 fatalities
![Page 14: Foam Plastics in Building Construction/media/6722C1B139CE4597A962C5696CEAF697.pdf• 45 min fire engulfs 34.5 acre facility ... FTC Investigation (1972) ... (Plywood in IRC only, for](https://reader030.vdocument.in/reader030/viewer/2022011801/5af6ab737f8b9ae9488f15c3/html5/thumbnails/14.jpg)
Kiss Night Club FireBrazil – 2013 – 242 fatalities
![Page 15: Foam Plastics in Building Construction/media/6722C1B139CE4597A962C5696CEAF697.pdf• 45 min fire engulfs 34.5 acre facility ... FTC Investigation (1972) ... (Plywood in IRC only, for](https://reader030.vdocument.in/reader030/viewer/2022011801/5af6ab737f8b9ae9488f15c3/html5/thumbnails/15.jpg)
The Monte Carlo Façade FireJanuary 25, 2008
![Page 16: Foam Plastics in Building Construction/media/6722C1B139CE4597A962C5696CEAF697.pdf• 45 min fire engulfs 34.5 acre facility ... FTC Investigation (1972) ... (Plywood in IRC only, for](https://reader030.vdocument.in/reader030/viewer/2022011801/5af6ab737f8b9ae9488f15c3/html5/thumbnails/16.jpg)
![Page 17: Foam Plastics in Building Construction/media/6722C1B139CE4597A962C5696CEAF697.pdf• 45 min fire engulfs 34.5 acre facility ... FTC Investigation (1972) ... (Plywood in IRC only, for](https://reader030.vdocument.in/reader030/viewer/2022011801/5af6ab737f8b9ae9488f15c3/html5/thumbnails/17.jpg)
![Page 18: Foam Plastics in Building Construction/media/6722C1B139CE4597A962C5696CEAF697.pdf• 45 min fire engulfs 34.5 acre facility ... FTC Investigation (1972) ... (Plywood in IRC only, for](https://reader030.vdocument.in/reader030/viewer/2022011801/5af6ab737f8b9ae9488f15c3/html5/thumbnails/18.jpg)
Palace StationLas VegasJuly 20, 1998
![Page 19: Foam Plastics in Building Construction/media/6722C1B139CE4597A962C5696CEAF697.pdf• 45 min fire engulfs 34.5 acre facility ... FTC Investigation (1972) ... (Plywood in IRC only, for](https://reader030.vdocument.in/reader030/viewer/2022011801/5af6ab737f8b9ae9488f15c3/html5/thumbnails/19.jpg)
![Page 20: Foam Plastics in Building Construction/media/6722C1B139CE4597A962C5696CEAF697.pdf• 45 min fire engulfs 34.5 acre facility ... FTC Investigation (1972) ... (Plywood in IRC only, for](https://reader030.vdocument.in/reader030/viewer/2022011801/5af6ab737f8b9ae9488f15c3/html5/thumbnails/20.jpg)
12-21-99 “Don Belles” Letter to CCBD
![Page 21: Foam Plastics in Building Construction/media/6722C1B139CE4597A962C5696CEAF697.pdf• 45 min fire engulfs 34.5 acre facility ... FTC Investigation (1972) ... (Plywood in IRC only, for](https://reader030.vdocument.in/reader030/viewer/2022011801/5af6ab737f8b9ae9488f15c3/html5/thumbnails/21.jpg)
12-21-99 “Don Belles” Letter to CCBD
![Page 22: Foam Plastics in Building Construction/media/6722C1B139CE4597A962C5696CEAF697.pdf• 45 min fire engulfs 34.5 acre facility ... FTC Investigation (1972) ... (Plywood in IRC only, for](https://reader030.vdocument.in/reader030/viewer/2022011801/5af6ab737f8b9ae9488f15c3/html5/thumbnails/22.jpg)
Eldorado HotelReno, NevadaSeptember 30, 1997
![Page 23: Foam Plastics in Building Construction/media/6722C1B139CE4597A962C5696CEAF697.pdf• 45 min fire engulfs 34.5 acre facility ... FTC Investigation (1972) ... (Plywood in IRC only, for](https://reader030.vdocument.in/reader030/viewer/2022011801/5af6ab737f8b9ae9488f15c3/html5/thumbnails/23.jpg)
Fire incidents & Codes
• In every major fire incident in recent times, involving foam plastics, there was a code compliance failure
• Code compliant construction has had an excellent fire safety record recently
• Result of combination of code safeguards
![Page 24: Foam Plastics in Building Construction/media/6722C1B139CE4597A962C5696CEAF697.pdf• 45 min fire engulfs 34.5 acre facility ... FTC Investigation (1972) ... (Plywood in IRC only, for](https://reader030.vdocument.in/reader030/viewer/2022011801/5af6ab737f8b9ae9488f15c3/html5/thumbnails/24.jpg)
Introduction
![Page 25: Foam Plastics in Building Construction/media/6722C1B139CE4597A962C5696CEAF697.pdf• 45 min fire engulfs 34.5 acre facility ... FTC Investigation (1972) ... (Plywood in IRC only, for](https://reader030.vdocument.in/reader030/viewer/2022011801/5af6ab737f8b9ae9488f15c3/html5/thumbnails/25.jpg)
Definition of Foam Plastic Insulation
A plastic that is intentionally expanded bythe use of a foaming agent to produce areduced-density plastic containing voidsconsisting of open or closed cellsdistributed throughout the plastic forthermal insulating or acoustic purposesand that has a density less than 20 poundsper cubic foot (320 kg/m3).
![Page 26: Foam Plastics in Building Construction/media/6722C1B139CE4597A962C5696CEAF697.pdf• 45 min fire engulfs 34.5 acre facility ... FTC Investigation (1972) ... (Plywood in IRC only, for](https://reader030.vdocument.in/reader030/viewer/2022011801/5af6ab737f8b9ae9488f15c3/html5/thumbnails/26.jpg)
Typical Foam Insulations
Expanded polystyrene foam (EPS)
Extruded polystyrene foam (XPS)
Rigid polyurethane foam (RPU)
Polyisocyanurate foam (PIR)
Others
![Page 27: Foam Plastics in Building Construction/media/6722C1B139CE4597A962C5696CEAF697.pdf• 45 min fire engulfs 34.5 acre facility ... FTC Investigation (1972) ... (Plywood in IRC only, for](https://reader030.vdocument.in/reader030/viewer/2022011801/5af6ab737f8b9ae9488f15c3/html5/thumbnails/27.jpg)
EPS
EPS sheets are produced from solidpolystyrene beads. The beads areexpanded by injecting and dissolvinga small amount of pentane gas intothe base material during production.
![Page 28: Foam Plastics in Building Construction/media/6722C1B139CE4597A962C5696CEAF697.pdf• 45 min fire engulfs 34.5 acre facility ... FTC Investigation (1972) ... (Plywood in IRC only, for](https://reader030.vdocument.in/reader030/viewer/2022011801/5af6ab737f8b9ae9488f15c3/html5/thumbnails/28.jpg)
EPS (2)
Under heat, the gas expands the beads toform closed cells. These cells are roughly40 times the volume of the original bead,and can be molded to form insulationboards, blocks, or shapes. It has a lowerdensity and a lower R value than XPSfoam and is usually white.
![Page 29: Foam Plastics in Building Construction/media/6722C1B139CE4597A962C5696CEAF697.pdf• 45 min fire engulfs 34.5 acre facility ... FTC Investigation (1972) ... (Plywood in IRC only, for](https://reader030.vdocument.in/reader030/viewer/2022011801/5af6ab737f8b9ae9488f15c3/html5/thumbnails/29.jpg)
XPS
XPS foam is produced from solidpolystyrene crystals, which, togetherwith additives, are fed into anextruder. Within the extruder, highheat and pressure form the mixtureinto a plastic fluid.
![Page 30: Foam Plastics in Building Construction/media/6722C1B139CE4597A962C5696CEAF697.pdf• 45 min fire engulfs 34.5 acre facility ... FTC Investigation (1972) ... (Plywood in IRC only, for](https://reader030.vdocument.in/reader030/viewer/2022011801/5af6ab737f8b9ae9488f15c3/html5/thumbnails/30.jpg)
XPS (2)
This thick liquid plastic is forced intoa die where it emerges and expandsto a foam. This foam is then shaped,cooled, and cut. It has a higherdensity and a higher R value thanEPS foam and is usually not white.
![Page 31: Foam Plastics in Building Construction/media/6722C1B139CE4597A962C5696CEAF697.pdf• 45 min fire engulfs 34.5 acre facility ... FTC Investigation (1972) ... (Plywood in IRC only, for](https://reader030.vdocument.in/reader030/viewer/2022011801/5af6ab737f8b9ae9488f15c3/html5/thumbnails/31.jpg)
RPU
Polyurethanes are produced by a controlled reaction between a polyol and an isocyanate. Special recipes (with the polyol, isocyanate and other additives) are needed for each type of product.
![Page 32: Foam Plastics in Building Construction/media/6722C1B139CE4597A962C5696CEAF697.pdf• 45 min fire engulfs 34.5 acre facility ... FTC Investigation (1972) ... (Plywood in IRC only, for](https://reader030.vdocument.in/reader030/viewer/2022011801/5af6ab737f8b9ae9488f15c3/html5/thumbnails/32.jpg)
RPU (2)
The amount of polyol and isocyanate is matched according to a chemical equivalent weight. Typically the isocyanate used is 105% of the chemical equivalent of the polyol. Then the foam is said to have an index of 105.
![Page 33: Foam Plastics in Building Construction/media/6722C1B139CE4597A962C5696CEAF697.pdf• 45 min fire engulfs 34.5 acre facility ... FTC Investigation (1972) ... (Plywood in IRC only, for](https://reader030.vdocument.in/reader030/viewer/2022011801/5af6ab737f8b9ae9488f15c3/html5/thumbnails/33.jpg)
PIR
Polyisocyanurates can be produced without polyol, using only isocyanate and additives. Instead of reacting with the polyol, the isocyanate reacts with itself to form a highly crosslinked thermosetting polymer with a ring-like structure.
![Page 34: Foam Plastics in Building Construction/media/6722C1B139CE4597A962C5696CEAF697.pdf• 45 min fire engulfs 34.5 acre facility ... FTC Investigation (1972) ... (Plywood in IRC only, for](https://reader030.vdocument.in/reader030/viewer/2022011801/5af6ab737f8b9ae9488f15c3/html5/thumbnails/34.jpg)
PIR (2)
For commercial PIR foam, the polyurethane is modified with polyisocyanurate. PIR foam has a typical index about 250 (i.e. the isocyanate is 250% of the chemical equivalent of the polyol)
![Page 35: Foam Plastics in Building Construction/media/6722C1B139CE4597A962C5696CEAF697.pdf• 45 min fire engulfs 34.5 acre facility ... FTC Investigation (1972) ... (Plywood in IRC only, for](https://reader030.vdocument.in/reader030/viewer/2022011801/5af6ab737f8b9ae9488f15c3/html5/thumbnails/35.jpg)
Closed & Open Cell PU Foam
Both are spray appliedOpen cell foams have < density (and
< R value) and expand more easily to cover hard to reach locations.Closed cell foams are more resistant
to moisture and bacterial growth.
![Page 36: Foam Plastics in Building Construction/media/6722C1B139CE4597A962C5696CEAF697.pdf• 45 min fire engulfs 34.5 acre facility ... FTC Investigation (1972) ... (Plywood in IRC only, for](https://reader030.vdocument.in/reader030/viewer/2022011801/5af6ab737f8b9ae9488f15c3/html5/thumbnails/36.jpg)
Other Foam Insulations
Phenolic foam (Phen)Polyimide foam (PI)Polyolefin foam (Polef)Melamine foam (Mel)Flexible polymeric foam (Flex Pol)Reflective insulation/foam interior (Rfl)
![Page 37: Foam Plastics in Building Construction/media/6722C1B139CE4597A962C5696CEAF697.pdf• 45 min fire engulfs 34.5 acre facility ... FTC Investigation (1972) ... (Plywood in IRC only, for](https://reader030.vdocument.in/reader030/viewer/2022011801/5af6ab737f8b9ae9488f15c3/html5/thumbnails/37.jpg)
Foam Insulation R Factor
EPS: R/inch ≈ 4
XPS: R/inch ≈ 5
PU spray closed cell: R/inch: 5.8 – 6.4
PU spray open cell: R/inch ≈ 3.8
PIR: R/inch: 5.0 - 5.6
Based on Data from Manufacturers
![Page 38: Foam Plastics in Building Construction/media/6722C1B139CE4597A962C5696CEAF697.pdf• 45 min fire engulfs 34.5 acre facility ... FTC Investigation (1972) ... (Plywood in IRC only, for](https://reader030.vdocument.in/reader030/viewer/2022011801/5af6ab737f8b9ae9488f15c3/html5/thumbnails/38.jpg)
Some Other Insulations
Foam plastics: R/inch ≈ 3.7 – 6.4Fiberglass batt: R/inch: 3.1 – 3.7Fiberglass blown: R/inch: 2.2 – 4.3Cellulose loose-fill: R/inch: 3.0 – 3.3Mineral Wool batt: R/inch: 4.2Mineral Wool blown: R/inch: 3.3 – 3.8Straw bale: R/inch: 0.9 – 1.5Recycled Denim: R/inch: 3.7 – 4.0
Based on Data from Manufacturers
![Page 39: Foam Plastics in Building Construction/media/6722C1B139CE4597A962C5696CEAF697.pdf• 45 min fire engulfs 34.5 acre facility ... FTC Investigation (1972) ... (Plywood in IRC only, for](https://reader030.vdocument.in/reader030/viewer/2022011801/5af6ab737f8b9ae9488f15c3/html5/thumbnails/39.jpg)
![Page 40: Foam Plastics in Building Construction/media/6722C1B139CE4597A962C5696CEAF697.pdf• 45 min fire engulfs 34.5 acre facility ... FTC Investigation (1972) ... (Plywood in IRC only, for](https://reader030.vdocument.in/reader030/viewer/2022011801/5af6ab737f8b9ae9488f15c3/html5/thumbnails/40.jpg)
Foam Plastic Applications
• Cavity Insulation (Walls/Ceilings)• Roofing Systems• Coolers - Freezers – Doors• Floor Insulation• Backing for Siding• Exterior Systems• Insulation for Attics & Crawl Spaces
![Page 41: Foam Plastics in Building Construction/media/6722C1B139CE4597A962C5696CEAF697.pdf• 45 min fire engulfs 34.5 acre facility ... FTC Investigation (1972) ... (Plywood in IRC only, for](https://reader030.vdocument.in/reader030/viewer/2022011801/5af6ab737f8b9ae9488f15c3/html5/thumbnails/41.jpg)
Early Major Fire
![Page 42: Foam Plastics in Building Construction/media/6722C1B139CE4597A962C5696CEAF697.pdf• 45 min fire engulfs 34.5 acre facility ... FTC Investigation (1972) ... (Plywood in IRC only, for](https://reader030.vdocument.in/reader030/viewer/2022011801/5af6ab737f8b9ae9488f15c3/html5/thumbnails/42.jpg)
Livonia, MI, Fire, 8/12/1953 –General Motors
Largest Industrial Loss on Record at That Time$50 - $55 M in Property Damage$750 M in Business Interruption
32,000 Employees Laid Off
![Page 43: Foam Plastics in Building Construction/media/6722C1B139CE4597A962C5696CEAF697.pdf• 45 min fire engulfs 34.5 acre facility ... FTC Investigation (1972) ... (Plywood in IRC only, for](https://reader030.vdocument.in/reader030/viewer/2022011801/5af6ab737f8b9ae9488f15c3/html5/thumbnails/43.jpg)
Livonia Roofing Fire
• Welder’s torch sparks cause the fire• Roof covering burns and melts• Roof covering asphalt and layers• 45 min fire engulfs 34.5 acre facility• Resulted in “White House Roof” fire
test (100 ft. long) (1955-1957)• Then ended up in FM 4450 test
![Page 44: Foam Plastics in Building Construction/media/6722C1B139CE4597A962C5696CEAF697.pdf• 45 min fire engulfs 34.5 acre facility ... FTC Investigation (1972) ... (Plywood in IRC only, for](https://reader030.vdocument.in/reader030/viewer/2022011801/5af6ab737f8b9ae9488f15c3/html5/thumbnails/44.jpg)
Fire Testing
![Page 45: Foam Plastics in Building Construction/media/6722C1B139CE4597A962C5696CEAF697.pdf• 45 min fire engulfs 34.5 acre facility ... FTC Investigation (1972) ... (Plywood in IRC only, for](https://reader030.vdocument.in/reader030/viewer/2022011801/5af6ab737f8b9ae9488f15c3/html5/thumbnails/45.jpg)
Early Fire TestingASTM D1692, Standard Method of
Test for Flammability of Plastic Sheeting and Cellular Plastics (First issued 1959)Test: Horizontal Bunsen burner
flame, for 60 sTest specimen sits on a metallic grid
![Page 46: Foam Plastics in Building Construction/media/6722C1B139CE4597A962C5696CEAF697.pdf• 45 min fire engulfs 34.5 acre facility ... FTC Investigation (1972) ... (Plywood in IRC only, for](https://reader030.vdocument.in/reader030/viewer/2022011801/5af6ab737f8b9ae9488f15c3/html5/thumbnails/46.jpg)
Early Fire Testing (2)Specimen passed test if no ignition
or flame does not spread to end or flame spread rate is low If materials “passed” the test they
were labeled “self-extinguishing”Many foam plastics passed the testStandard withdrawn in 1976
![Page 47: Foam Plastics in Building Construction/media/6722C1B139CE4597A962C5696CEAF697.pdf• 45 min fire engulfs 34.5 acre facility ... FTC Investigation (1972) ... (Plywood in IRC only, for](https://reader030.vdocument.in/reader030/viewer/2022011801/5af6ab737f8b9ae9488f15c3/html5/thumbnails/47.jpg)
ASTM D1692
![Page 48: Foam Plastics in Building Construction/media/6722C1B139CE4597A962C5696CEAF697.pdf• 45 min fire engulfs 34.5 acre facility ... FTC Investigation (1972) ... (Plywood in IRC only, for](https://reader030.vdocument.in/reader030/viewer/2022011801/5af6ab737f8b9ae9488f15c3/html5/thumbnails/48.jpg)
Early Fire Testing (3)
ASTM E84, Standard Test Method for Surface Burning Characteristics of Building Materials [Steiner tunnel] (First issued 1950)Test: Horizontal massive burner
flame, for 10 min
![Page 49: Foam Plastics in Building Construction/media/6722C1B139CE4597A962C5696CEAF697.pdf• 45 min fire engulfs 34.5 acre facility ... FTC Investigation (1972) ... (Plywood in IRC only, for](https://reader030.vdocument.in/reader030/viewer/2022011801/5af6ab737f8b9ae9488f15c3/html5/thumbnails/49.jpg)
Early Fire Testing (4)
Test specimen under tunnel ceilingNo “pass” in the testTest measures flame spread index
and smoke developed indexCategories: A, B and C
![Page 50: Foam Plastics in Building Construction/media/6722C1B139CE4597A962C5696CEAF697.pdf• 45 min fire engulfs 34.5 acre facility ... FTC Investigation (1972) ... (Plywood in IRC only, for](https://reader030.vdocument.in/reader030/viewer/2022011801/5af6ab737f8b9ae9488f15c3/html5/thumbnails/50.jpg)
ASTM E84 Categories
• A: 25 FSI; 450 SDI• B: 75 FSI; 450 SDI• C: 200 FSI; 450 SDI• Categories/Requirements are not in the standard
![Page 51: Foam Plastics in Building Construction/media/6722C1B139CE4597A962C5696CEAF697.pdf• 45 min fire engulfs 34.5 acre facility ... FTC Investigation (1972) ... (Plywood in IRC only, for](https://reader030.vdocument.in/reader030/viewer/2022011801/5af6ab737f8b9ae9488f15c3/html5/thumbnails/51.jpg)
ASTM E 84 Test
![Page 52: Foam Plastics in Building Construction/media/6722C1B139CE4597A962C5696CEAF697.pdf• 45 min fire engulfs 34.5 acre facility ... FTC Investigation (1972) ... (Plywood in IRC only, for](https://reader030.vdocument.in/reader030/viewer/2022011801/5af6ab737f8b9ae9488f15c3/html5/thumbnails/52.jpg)
ASTM E 84 Burner
![Page 53: Foam Plastics in Building Construction/media/6722C1B139CE4597A962C5696CEAF697.pdf• 45 min fire engulfs 34.5 acre facility ... FTC Investigation (1972) ... (Plywood in IRC only, for](https://reader030.vdocument.in/reader030/viewer/2022011801/5af6ab737f8b9ae9488f15c3/html5/thumbnails/53.jpg)
![Page 54: Foam Plastics in Building Construction/media/6722C1B139CE4597A962C5696CEAF697.pdf• 45 min fire engulfs 34.5 acre facility ... FTC Investigation (1972) ... (Plywood in IRC only, for](https://reader030.vdocument.in/reader030/viewer/2022011801/5af6ab737f8b9ae9488f15c3/html5/thumbnails/54.jpg)
Foam Fire Childress
• Missouri polyurethane foam insulation fire killed 2 children of the Childress family
• Foam manufacturer had labeled the foam as “non burning and self extinguishing”, as a result of ASTM D1692 test results
• Lawsuit found manufacture liable• Manufacturer and testing lab were found to
be negligent because test was inadequate to assess the severe fire problem with the foam
![Page 55: Foam Plastics in Building Construction/media/6722C1B139CE4597A962C5696CEAF697.pdf• 45 min fire engulfs 34.5 acre facility ... FTC Investigation (1972) ... (Plywood in IRC only, for](https://reader030.vdocument.in/reader030/viewer/2022011801/5af6ab737f8b9ae9488f15c3/html5/thumbnails/55.jpg)
FTC Investigation (1972)
• Investigated fires involving cellular plastics• Same as foam plastics• FTC Determined there was “misuse” of small
scale test data in promotional materials• “Small scale tests are neither reliable nor
accurate tests for determining, evaluating, predicting or describing the burning characteristics of plastic products under actual fire conditions.”
![Page 56: Foam Plastics in Building Construction/media/6722C1B139CE4597A962C5696CEAF697.pdf• 45 min fire engulfs 34.5 acre facility ... FTC Investigation (1972) ... (Plywood in IRC only, for](https://reader030.vdocument.in/reader030/viewer/2022011801/5af6ab737f8b9ae9488f15c3/html5/thumbnails/56.jpg)
FTC Consent Order
• Determined that cellular (foam) plastics burn different than conventional materials
• Thermoplastics (like polystyrene) tend to melt and drip and contribute to fire spread
• FTC Consent Order Issued 11/4/1974• Cease using “non-burning”, “Self-extinguishing” or
non-combustible” when describing foam plastics• Any reference to numerical flame spread ratings
based on small scale tests, such as ASTM E84, must contain a disclaimer
![Page 57: Foam Plastics in Building Construction/media/6722C1B139CE4597A962C5696CEAF697.pdf• 45 min fire engulfs 34.5 acre facility ... FTC Investigation (1972) ... (Plywood in IRC only, for](https://reader030.vdocument.in/reader030/viewer/2022011801/5af6ab737f8b9ae9488f15c3/html5/thumbnails/57.jpg)
FTC Consent Order Terms
• Plastics manufacturers must conduct $5 million fire research program on safe means of using foams
• Develop guidelines for safe and effective use• Develop appropriate fire test methods, including
large scale test methods, to provide accurate and reliable means to assess burning characteristics under actual fire conditions
• Manufacturers must report to FTC for 5 years• FTC Consent Order withdrawn in 1980
![Page 58: Foam Plastics in Building Construction/media/6722C1B139CE4597A962C5696CEAF697.pdf• 45 min fire engulfs 34.5 acre facility ... FTC Investigation (1972) ... (Plywood in IRC only, for](https://reader030.vdocument.in/reader030/viewer/2022011801/5af6ab737f8b9ae9488f15c3/html5/thumbnails/58.jpg)
FTC Consequences
• Industry conducted research with NBS (now NIST)• Developed large scale wall tests• Developed large scale corner tests• Developed correlations with ASTM E84• Developed validation studies• Developed combustion toxicity studies• This resulted in modern fire test requirements• Incorporated into codes in 1970s• Have been slightly modified since then
![Page 59: Foam Plastics in Building Construction/media/6722C1B139CE4597A962C5696CEAF697.pdf• 45 min fire engulfs 34.5 acre facility ... FTC Investigation (1972) ... (Plywood in IRC only, for](https://reader030.vdocument.in/reader030/viewer/2022011801/5af6ab737f8b9ae9488f15c3/html5/thumbnails/59.jpg)
Code Requirements Now
International Building Code (IBC): Chapter 26 and section 2603NFPA 5000: Chapter 48 and section
48.4Very similar in both
![Page 60: Foam Plastics in Building Construction/media/6722C1B139CE4597A962C5696CEAF697.pdf• 45 min fire engulfs 34.5 acre facility ... FTC Investigation (1972) ... (Plywood in IRC only, for](https://reader030.vdocument.in/reader030/viewer/2022011801/5af6ab737f8b9ae9488f15c3/html5/thumbnails/60.jpg)
Code Fire Testing Now
Either: Testing Foam Plastic to NFPA 286 Or: Testing Foam Plastic to ASTM E84 If tested to ASTM E84 Foam Plastic Must be
Covered by Thermal Barrier for all Occupiable Spaces
Foam Plastic Also Always Needs to Meet ASTM E84 Class B (75/450)
![Page 61: Foam Plastics in Building Construction/media/6722C1B139CE4597A962C5696CEAF697.pdf• 45 min fire engulfs 34.5 acre facility ... FTC Investigation (1972) ... (Plywood in IRC only, for](https://reader030.vdocument.in/reader030/viewer/2022011801/5af6ab737f8b9ae9488f15c3/html5/thumbnails/61.jpg)
NFPA 286Basic Test Apparatus
![Page 62: Foam Plastics in Building Construction/media/6722C1B139CE4597A962C5696CEAF697.pdf• 45 min fire engulfs 34.5 acre facility ... FTC Investigation (1972) ... (Plywood in IRC only, for](https://reader030.vdocument.in/reader030/viewer/2022011801/5af6ab737f8b9ae9488f15c3/html5/thumbnails/62.jpg)
Fire Requirements for NFPA 286
• Requirements are not in the standard
• No Flashover• Peak HRR ≤ 800 kW• Peak TSR ≤ 1000 m2
![Page 63: Foam Plastics in Building Construction/media/6722C1B139CE4597A962C5696CEAF697.pdf• 45 min fire engulfs 34.5 acre facility ... FTC Investigation (1972) ... (Plywood in IRC only, for](https://reader030.vdocument.in/reader030/viewer/2022011801/5af6ab737f8b9ae9488f15c3/html5/thumbnails/63.jpg)
![Page 64: Foam Plastics in Building Construction/media/6722C1B139CE4597A962C5696CEAF697.pdf• 45 min fire engulfs 34.5 acre facility ... FTC Investigation (1972) ... (Plywood in IRC only, for](https://reader030.vdocument.in/reader030/viewer/2022011801/5af6ab737f8b9ae9488f15c3/html5/thumbnails/64.jpg)
![Page 65: Foam Plastics in Building Construction/media/6722C1B139CE4597A962C5696CEAF697.pdf• 45 min fire engulfs 34.5 acre facility ... FTC Investigation (1972) ... (Plywood in IRC only, for](https://reader030.vdocument.in/reader030/viewer/2022011801/5af6ab737f8b9ae9488f15c3/html5/thumbnails/65.jpg)
![Page 66: Foam Plastics in Building Construction/media/6722C1B139CE4597A962C5696CEAF697.pdf• 45 min fire engulfs 34.5 acre facility ... FTC Investigation (1972) ... (Plywood in IRC only, for](https://reader030.vdocument.in/reader030/viewer/2022011801/5af6ab737f8b9ae9488f15c3/html5/thumbnails/66.jpg)
Interior Wall & Ceiling FinishFire Requirements (2015)
• Foam Plastic Finish Permitted Only If:
• (a) Meets NFPA 286-based requirements
• (b) Meets FM 4880/UL 1715/UL 1040 (all large scale tests)
• (c) Covered by Thermal Barrier
• and meets ASTM E84 75/450
![Page 67: Foam Plastics in Building Construction/media/6722C1B139CE4597A962C5696CEAF697.pdf• 45 min fire engulfs 34.5 acre facility ... FTC Investigation (1972) ... (Plywood in IRC only, for](https://reader030.vdocument.in/reader030/viewer/2022011801/5af6ab737f8b9ae9488f15c3/html5/thumbnails/67.jpg)
FM 4880 25 ft. Corner Test
![Page 68: Foam Plastics in Building Construction/media/6722C1B139CE4597A962C5696CEAF697.pdf• 45 min fire engulfs 34.5 acre facility ... FTC Investigation (1972) ... (Plywood in IRC only, for](https://reader030.vdocument.in/reader030/viewer/2022011801/5af6ab737f8b9ae9488f15c3/html5/thumbnails/68.jpg)
Thermal Barrier
![Page 69: Foam Plastics in Building Construction/media/6722C1B139CE4597A962C5696CEAF697.pdf• 45 min fire engulfs 34.5 acre facility ... FTC Investigation (1972) ... (Plywood in IRC only, for](https://reader030.vdocument.in/reader030/viewer/2022011801/5af6ab737f8b9ae9488f15c3/html5/thumbnails/69.jpg)
Thermal Barrier
• Must meet NFPA 275, which has NFPA 286 & ASTM E119 tests
• Also thermal barriers named as:• Alternative: ½” gypsum board• New alternative: ¾” plywood• (Plywood in IRC only, for now)
![Page 70: Foam Plastics in Building Construction/media/6722C1B139CE4597A962C5696CEAF697.pdf• 45 min fire engulfs 34.5 acre facility ... FTC Investigation (1972) ... (Plywood in IRC only, for](https://reader030.vdocument.in/reader030/viewer/2022011801/5af6ab737f8b9ae9488f15c3/html5/thumbnails/70.jpg)
NFPA 275:
ASTM E119 (small scale)
and NFPA 286
![Page 71: Foam Plastics in Building Construction/media/6722C1B139CE4597A962C5696CEAF697.pdf• 45 min fire engulfs 34.5 acre facility ... FTC Investigation (1972) ... (Plywood in IRC only, for](https://reader030.vdocument.in/reader030/viewer/2022011801/5af6ab737f8b9ae9488f15c3/html5/thumbnails/71.jpg)
Exceptions to Thermal Barrier Requirements (1) Behind 1 inch of masonry or concrete Cooler & freezer walls Walk-in coolers Exterior walls in one-story buildings Roofing Attics & crawl spaces (non occupiable) Doors not required to have fire protection
rating
![Page 72: Foam Plastics in Building Construction/media/6722C1B139CE4597A962C5696CEAF697.pdf• 45 min fire engulfs 34.5 acre facility ... FTC Investigation (1972) ... (Plywood in IRC only, for](https://reader030.vdocument.in/reader030/viewer/2022011801/5af6ab737f8b9ae9488f15c3/html5/thumbnails/72.jpg)
Exceptions to Thermal Barrier Requirements (2) Exterior doors in Group R-2/R-3 buildings Garage doors Siding backer board Interior trim Interior signs Type V (combustible) construction Walking surfaces of structural floors
![Page 73: Foam Plastics in Building Construction/media/6722C1B139CE4597A962C5696CEAF697.pdf• 45 min fire engulfs 34.5 acre facility ... FTC Investigation (1972) ... (Plywood in IRC only, for](https://reader030.vdocument.in/reader030/viewer/2022011801/5af6ab737f8b9ae9488f15c3/html5/thumbnails/73.jpg)
Non Occupiable SpacesAttics & Crawl Spaces
Foam Plastic Needs to Meet ASTM E84 Class B (75/450)Normally Spray FoamFoam Plastic Must be Covered by
an Ignition BarrierIgnition Barrier: Named Products
![Page 74: Foam Plastics in Building Construction/media/6722C1B139CE4597A962C5696CEAF697.pdf• 45 min fire engulfs 34.5 acre facility ... FTC Investigation (1972) ... (Plywood in IRC only, for](https://reader030.vdocument.in/reader030/viewer/2022011801/5af6ab737f8b9ae9488f15c3/html5/thumbnails/74.jpg)
Ignition Barrier
![Page 75: Foam Plastics in Building Construction/media/6722C1B139CE4597A962C5696CEAF697.pdf• 45 min fire engulfs 34.5 acre facility ... FTC Investigation (1972) ... (Plywood in IRC only, for](https://reader030.vdocument.in/reader030/viewer/2022011801/5af6ab737f8b9ae9488f15c3/html5/thumbnails/75.jpg)
Ignition Barrier
• 1.5” Mineral Fiber Insulation• 0.25” Wood Structural Panel• 3/8” Gypsum Wallboard• 0.25” Hardboard• 0.016” Corrosion Resistant Steel • 1.5” Cellulose Insulation• Another Approved Material
![Page 76: Foam Plastics in Building Construction/media/6722C1B139CE4597A962C5696CEAF697.pdf• 45 min fire engulfs 34.5 acre facility ... FTC Investigation (1972) ... (Plywood in IRC only, for](https://reader030.vdocument.in/reader030/viewer/2022011801/5af6ab737f8b9ae9488f15c3/html5/thumbnails/76.jpg)
Exterior Walls
![Page 77: Foam Plastics in Building Construction/media/6722C1B139CE4597A962C5696CEAF697.pdf• 45 min fire engulfs 34.5 acre facility ... FTC Investigation (1972) ... (Plywood in IRC only, for](https://reader030.vdocument.in/reader030/viewer/2022011801/5af6ab737f8b9ae9488f15c3/html5/thumbnails/77.jpg)
Exterior Walls: 1 story
• Foam plastic without thermal barrier if it complies with all the following:
• ASTM E84 25/450 &• Maximum 4 inches thick &• Al (0.032”) or steel (0.016”) covering &• Building fully sprinklered
![Page 78: Foam Plastics in Building Construction/media/6722C1B139CE4597A962C5696CEAF697.pdf• 45 min fire engulfs 34.5 acre facility ... FTC Investigation (1972) ... (Plywood in IRC only, for](https://reader030.vdocument.in/reader030/viewer/2022011801/5af6ab737f8b9ae9488f15c3/html5/thumbnails/78.jpg)
Exterior Walls: > 1 storyType I-IV Construction
• Fire resistance rating• Thermal barrier over foam• Foam must meet NFPA 259 Pot. Heat• ASTM E84 25/450• Pass NFPA 285 multistory test• Pass NFPA 268 ignition test
![Page 79: Foam Plastics in Building Construction/media/6722C1B139CE4597A962C5696CEAF697.pdf• 45 min fire engulfs 34.5 acre facility ... FTC Investigation (1972) ... (Plywood in IRC only, for](https://reader030.vdocument.in/reader030/viewer/2022011801/5af6ab737f8b9ae9488f15c3/html5/thumbnails/79.jpg)
![Page 80: Foam Plastics in Building Construction/media/6722C1B139CE4597A962C5696CEAF697.pdf• 45 min fire engulfs 34.5 acre facility ... FTC Investigation (1972) ... (Plywood in IRC only, for](https://reader030.vdocument.in/reader030/viewer/2022011801/5af6ab737f8b9ae9488f15c3/html5/thumbnails/80.jpg)
![Page 81: Foam Plastics in Building Construction/media/6722C1B139CE4597A962C5696CEAF697.pdf• 45 min fire engulfs 34.5 acre facility ... FTC Investigation (1972) ... (Plywood in IRC only, for](https://reader030.vdocument.in/reader030/viewer/2022011801/5af6ab737f8b9ae9488f15c3/html5/thumbnails/81.jpg)
![Page 82: Foam Plastics in Building Construction/media/6722C1B139CE4597A962C5696CEAF697.pdf• 45 min fire engulfs 34.5 acre facility ... FTC Investigation (1972) ... (Plywood in IRC only, for](https://reader030.vdocument.in/reader030/viewer/2022011801/5af6ab737f8b9ae9488f15c3/html5/thumbnails/82.jpg)
NFPA 268 Test
Requirements: No ignition @ 12.5 kW/m2
![Page 83: Foam Plastics in Building Construction/media/6722C1B139CE4597A962C5696CEAF697.pdf• 45 min fire engulfs 34.5 acre facility ... FTC Investigation (1972) ... (Plywood in IRC only, for](https://reader030.vdocument.in/reader030/viewer/2022011801/5af6ab737f8b9ae9488f15c3/html5/thumbnails/83.jpg)
Exterior Walls: > 1 storyType I-IV Construction
• Tested to NFPA 268 (ignition)• Exceptions:• Thermal Barrier• 1” Concrete• 3/8” Glass Fiber Reinfor. Concrete• Steel or Aluminum Panels• 7/8” Stucco
![Page 84: Foam Plastics in Building Construction/media/6722C1B139CE4597A962C5696CEAF697.pdf• 45 min fire engulfs 34.5 acre facility ... FTC Investigation (1972) ... (Plywood in IRC only, for](https://reader030.vdocument.in/reader030/viewer/2022011801/5af6ab737f8b9ae9488f15c3/html5/thumbnails/84.jpg)
Exterior Walls: > 1 storyType V Construction
• Thermal barrier over foam• ASTM E84: 75/450
![Page 85: Foam Plastics in Building Construction/media/6722C1B139CE4597A962C5696CEAF697.pdf• 45 min fire engulfs 34.5 acre facility ... FTC Investigation (1972) ... (Plywood in IRC only, for](https://reader030.vdocument.in/reader030/viewer/2022011801/5af6ab737f8b9ae9488f15c3/html5/thumbnails/85.jpg)
Cooler/Freezer Walls
![Page 86: Foam Plastics in Building Construction/media/6722C1B139CE4597A962C5696CEAF697.pdf• 45 min fire engulfs 34.5 acre facility ... FTC Investigation (1972) ... (Plywood in IRC only, for](https://reader030.vdocument.in/reader030/viewer/2022011801/5af6ab737f8b9ae9488f15c3/html5/thumbnails/86.jpg)
Cooler/Freezer Walls
• Foam plastic without thermal barrier if it complies with all the following:
• ASTM E84 25/450 &• Maximum 10 inches thick &• Al (0.032”) or steel (0.016”) covering &• Ignition temperature 600/800F (flash/self) &• Building fully sprinklered
![Page 87: Foam Plastics in Building Construction/media/6722C1B139CE4597A962C5696CEAF697.pdf• 45 min fire engulfs 34.5 acre facility ... FTC Investigation (1972) ... (Plywood in IRC only, for](https://reader030.vdocument.in/reader030/viewer/2022011801/5af6ab737f8b9ae9488f15c3/html5/thumbnails/87.jpg)
Walk-in Coolers
![Page 88: Foam Plastics in Building Construction/media/6722C1B139CE4597A962C5696CEAF697.pdf• 45 min fire engulfs 34.5 acre facility ... FTC Investigation (1972) ... (Plywood in IRC only, for](https://reader030.vdocument.in/reader030/viewer/2022011801/5af6ab737f8b9ae9488f15c3/html5/thumbnails/88.jpg)
Walk-in Coolers
• Foam plastic without thermal barrier if it complies with all the following:
• ASTM E84 75/450 &• Maximum 4 inches thick &• Al (0.032”) or steel (0.016”) covering &• Aggregate floor area ≤ 400 ft2
![Page 89: Foam Plastics in Building Construction/media/6722C1B139CE4597A962C5696CEAF697.pdf• 45 min fire engulfs 34.5 acre facility ... FTC Investigation (1972) ... (Plywood in IRC only, for](https://reader030.vdocument.in/reader030/viewer/2022011801/5af6ab737f8b9ae9488f15c3/html5/thumbnails/89.jpg)
Roofing
![Page 90: Foam Plastics in Building Construction/media/6722C1B139CE4597A962C5696CEAF697.pdf• 45 min fire engulfs 34.5 acre facility ... FTC Investigation (1972) ... (Plywood in IRC only, for](https://reader030.vdocument.in/reader030/viewer/2022011801/5af6ab737f8b9ae9488f15c3/html5/thumbnails/90.jpg)
Roofing
• Foam plastic without thermal barrier if it complies with all the following:
• ASTM E84 75/450 &• Wood structural panel 0.47” & exterior glue• Roof assembly meets FM 4450 or UL 1256
(including foam)• Foam plastic with thermal barrier, roof
assembly (with foam) must meet ASTM E108 Class A, B or C
![Page 91: Foam Plastics in Building Construction/media/6722C1B139CE4597A962C5696CEAF697.pdf• 45 min fire engulfs 34.5 acre facility ... FTC Investigation (1972) ... (Plywood in IRC only, for](https://reader030.vdocument.in/reader030/viewer/2022011801/5af6ab737f8b9ae9488f15c3/html5/thumbnails/91.jpg)
FM 4450Heat Release Roofing Test
Heptane & propane burners – 30 minute test
![Page 92: Foam Plastics in Building Construction/media/6722C1B139CE4597A962C5696CEAF697.pdf• 45 min fire engulfs 34.5 acre facility ... FTC Investigation (1972) ... (Plywood in IRC only, for](https://reader030.vdocument.in/reader030/viewer/2022011801/5af6ab737f8b9ae9488f15c3/html5/thumbnails/92.jpg)
Structural Floors
![Page 93: Foam Plastics in Building Construction/media/6722C1B139CE4597A962C5696CEAF697.pdf• 45 min fire engulfs 34.5 acre facility ... FTC Investigation (1972) ... (Plywood in IRC only, for](https://reader030.vdocument.in/reader030/viewer/2022011801/5af6ab737f8b9ae9488f15c3/html5/thumbnails/93.jpg)
Structural Floors
• Foam plastic without thermal barrier if it complies with all the following:
• ASTM E84 75/450 &• Wood structural panel 0.5” &• Thermal barrier on underside if the
underside is exposed to building interior
![Page 94: Foam Plastics in Building Construction/media/6722C1B139CE4597A962C5696CEAF697.pdf• 45 min fire engulfs 34.5 acre facility ... FTC Investigation (1972) ... (Plywood in IRC only, for](https://reader030.vdocument.in/reader030/viewer/2022011801/5af6ab737f8b9ae9488f15c3/html5/thumbnails/94.jpg)
Siding Backer Board
![Page 95: Foam Plastics in Building Construction/media/6722C1B139CE4597A962C5696CEAF697.pdf• 45 min fire engulfs 34.5 acre facility ... FTC Investigation (1972) ... (Plywood in IRC only, for](https://reader030.vdocument.in/reader030/viewer/2022011801/5af6ab737f8b9ae9488f15c3/html5/thumbnails/95.jpg)
Siding Backer Board
• Foam plastic without thermal barrier if it complies with all the following:
• ASTM E84 75/450 &• NFPA 259 ≤ 2000 BTU/ft2 &• Maximum thickness 0.5” &• Separated from building interior by 2” of
mineral fiber insulation or equivalent• Does not include “insulated vinyl siding”
![Page 96: Foam Plastics in Building Construction/media/6722C1B139CE4597A962C5696CEAF697.pdf• 45 min fire engulfs 34.5 acre facility ... FTC Investigation (1972) ... (Plywood in IRC only, for](https://reader030.vdocument.in/reader030/viewer/2022011801/5af6ab737f8b9ae9488f15c3/html5/thumbnails/96.jpg)
Interior Trim
![Page 97: Foam Plastics in Building Construction/media/6722C1B139CE4597A962C5696CEAF697.pdf• 45 min fire engulfs 34.5 acre facility ... FTC Investigation (1972) ... (Plywood in IRC only, for](https://reader030.vdocument.in/reader030/viewer/2022011801/5af6ab737f8b9ae9488f15c3/html5/thumbnails/97.jpg)
Interior Trim
• Needs to comply with all the following to avoid thermal barrier:
• ASTM E84 75 (no SDI) &• Surface ≤ 10% of wall or ceiling &• Density ≥ 20 lb./ft3
• Thickness ≤ 0.5”• Width ≤ 8”
![Page 98: Foam Plastics in Building Construction/media/6722C1B139CE4597A962C5696CEAF697.pdf• 45 min fire engulfs 34.5 acre facility ... FTC Investigation (1972) ... (Plywood in IRC only, for](https://reader030.vdocument.in/reader030/viewer/2022011801/5af6ab737f8b9ae9488f15c3/html5/thumbnails/98.jpg)
Interior Signs
![Page 99: Foam Plastics in Building Construction/media/6722C1B139CE4597A962C5696CEAF697.pdf• 45 min fire engulfs 34.5 acre facility ... FTC Investigation (1972) ... (Plywood in IRC only, for](https://reader030.vdocument.in/reader030/viewer/2022011801/5af6ab737f8b9ae9488f15c3/html5/thumbnails/99.jpg)
Interior Signs in Covered Malls
• Needs to comply with all the following to avoid thermal barrier:
• UL 1975 or NFPA 289, 20 kW source, HRR ≤ 150 kW &
• Height ≤ 36” (or 96” x 36” if vertical) &• Surface ≤ 20% of wall• No ASTM E84 requirements
![Page 100: Foam Plastics in Building Construction/media/6722C1B139CE4597A962C5696CEAF697.pdf• 45 min fire engulfs 34.5 acre facility ... FTC Investigation (1972) ... (Plywood in IRC only, for](https://reader030.vdocument.in/reader030/viewer/2022011801/5af6ab737f8b9ae9488f15c3/html5/thumbnails/100.jpg)
Plenums
![Page 101: Foam Plastics in Building Construction/media/6722C1B139CE4597A962C5696CEAF697.pdf• 45 min fire engulfs 34.5 acre facility ... FTC Investigation (1972) ... (Plywood in IRC only, for](https://reader030.vdocument.in/reader030/viewer/2022011801/5af6ab737f8b9ae9488f15c3/html5/thumbnails/101.jpg)
Foam Plastic In Plenums
• Foam Plastic Interior Finish Must Have Thermal Barrier or NFPA 286
• Also: ASTM E84 75/50
• Or NFPA 286 (as above)
• Or Al or Steel coverings
![Page 102: Foam Plastics in Building Construction/media/6722C1B139CE4597A962C5696CEAF697.pdf• 45 min fire engulfs 34.5 acre facility ... FTC Investigation (1972) ... (Plywood in IRC only, for](https://reader030.vdocument.in/reader030/viewer/2022011801/5af6ab737f8b9ae9488f15c3/html5/thumbnails/102.jpg)
Plenum Pipe/Duct Insulation
• ASTM E84 with FSI 25/SDI 50
• Mounting by ASTM E2231
• Included in IMC (& IBC)
• Included in UMC
• Included in NFPA 5000 and 90A
![Page 103: Foam Plastics in Building Construction/media/6722C1B139CE4597A962C5696CEAF697.pdf• 45 min fire engulfs 34.5 acre facility ... FTC Investigation (1972) ... (Plywood in IRC only, for](https://reader030.vdocument.in/reader030/viewer/2022011801/5af6ab737f8b9ae9488f15c3/html5/thumbnails/103.jpg)
Recent Developments
![Page 104: Foam Plastics in Building Construction/media/6722C1B139CE4597A962C5696CEAF697.pdf• 45 min fire engulfs 34.5 acre facility ... FTC Investigation (1972) ... (Plywood in IRC only, for](https://reader030.vdocument.in/reader030/viewer/2022011801/5af6ab737f8b9ae9488f15c3/html5/thumbnails/104.jpg)
Code ProposalsInternational Residential Code
• RB 163: Allows foam plastic without fire test in wall cavities
• RB 164: Allows foam plastic without fire test under floors
• Both proposals were disapproved• RB 167: Allows ¾” plywood as thermal
barrier: proposal approved
![Page 105: Foam Plastics in Building Construction/media/6722C1B139CE4597A962C5696CEAF697.pdf• 45 min fire engulfs 34.5 acre facility ... FTC Investigation (1972) ... (Plywood in IRC only, for](https://reader030.vdocument.in/reader030/viewer/2022011801/5af6ab737f8b9ae9488f15c3/html5/thumbnails/105.jpg)
Code ProposalsInternational Green Code
• GG 221: Requires foam plastic to disclose contents or comply with GreenScreen label
• GG 222: Allows foam plastic without fire test under floors
• GG 242: Requires 50% of foam plastic insulation to have no halogens
![Page 106: Foam Plastics in Building Construction/media/6722C1B139CE4597A962C5696CEAF697.pdf• 45 min fire engulfs 34.5 acre facility ... FTC Investigation (1972) ... (Plywood in IRC only, for](https://reader030.vdocument.in/reader030/viewer/2022011801/5af6ab737f8b9ae9488f15c3/html5/thumbnails/106.jpg)
California LawCA AB 127
• Requires California State Fire Marshal to develop new fire test or options for using foam plastic insulation without meeting a fire test
• Working group formed in California• Much debate centers on allegations of
toxicity of flame retardants
![Page 107: Foam Plastics in Building Construction/media/6722C1B139CE4597A962C5696CEAF697.pdf• 45 min fire engulfs 34.5 acre facility ... FTC Investigation (1972) ... (Plywood in IRC only, for](https://reader030.vdocument.in/reader030/viewer/2022011801/5af6ab737f8b9ae9488f15c3/html5/thumbnails/107.jpg)
Flame Retardants in Foams
• Typical foams do not pass needed fire tests as such (polyurethane, polystyrene, polyisocyanurate)
• Need FR to meet fire test requirements• New flame retardants are being used• Many other insulation materials also
need flame retardants
![Page 108: Foam Plastics in Building Construction/media/6722C1B139CE4597A962C5696CEAF697.pdf• 45 min fire engulfs 34.5 acre facility ... FTC Investigation (1972) ... (Plywood in IRC only, for](https://reader030.vdocument.in/reader030/viewer/2022011801/5af6ab737f8b9ae9488f15c3/html5/thumbnails/108.jpg)
Toxicity of Flame Retardants (1)
• Issue is “measurable vs meaningful”• Decomposition products of flame
retardants are found in fire effluents• Studies have shown that toxicity of
normal smoke effluents (such as CO and polynuclear aromatics are 1,000 times more toxic than FR derivatives
![Page 109: Foam Plastics in Building Construction/media/6722C1B139CE4597A962C5696CEAF697.pdf• 45 min fire engulfs 34.5 acre facility ... FTC Investigation (1972) ... (Plywood in IRC only, for](https://reader030.vdocument.in/reader030/viewer/2022011801/5af6ab737f8b9ae9488f15c3/html5/thumbnails/109.jpg)
Toxicity of Flame Retardants (2)
• More fire safe materials lower emissions• Firefighters have higher cancer rates• All fire effluents affect firefighters, both
during fires and during overhaul• SCBA use is essential for firefighters• Rapid cleaning of fire gear is essential• The key issue is personal protection
![Page 110: Foam Plastics in Building Construction/media/6722C1B139CE4597A962C5696CEAF697.pdf• 45 min fire engulfs 34.5 acre facility ... FTC Investigation (1972) ... (Plywood in IRC only, for](https://reader030.vdocument.in/reader030/viewer/2022011801/5af6ab737f8b9ae9488f15c3/html5/thumbnails/110.jpg)
Conclusions
• Foam plastic insulation materials are needed for energy efficiency
• They have high insulation (R values)• They can be used safely• Fire incidents have involved code non
compliance
![Page 111: Foam Plastics in Building Construction/media/6722C1B139CE4597A962C5696CEAF697.pdf• 45 min fire engulfs 34.5 acre facility ... FTC Investigation (1972) ... (Plywood in IRC only, for](https://reader030.vdocument.in/reader030/viewer/2022011801/5af6ab737f8b9ae9488f15c3/html5/thumbnails/111.jpg)
NFPA 2014 Conference & Expo
Thank You• CEUs: To receive CEUs for this session, scan your badge
at the back of the room before leaving• Evaluation: Complete the session evaluation on the
mobile app. (To download, search your app store for ‘NFPA 2014 C&E.’)
• Handouts: Handouts will be available via the mobile app or at nfpa.org/conference
• Recordings: Audio recordings will be available. To order, see Fleetwood Media Productions (at Breakers Registration desk) or visit nfpa.org/conference