fork truck hazard
TRANSCRIPT
-
8/12/2019 Fork Truck Hazard
1/18
INDUSTRIAL HEALTH
A GUIDE TO
FORK TRUCK
HAZARD PROTECTION
Published by the DEPARTMENT OF LABOUR - New Zealand
SAFET
Y
WELFARE
ARCHIVE
DIESEL FORK TRUCKS OPERATING WITHINDEFINED HAZARDOUS ZONES
-
8/12/2019 Fork Truck Hazard
2/18
2
ARCHIVE
Published by Explosives and Dangerous Goods
Occupational Safety & Health Service
Department of Labour
Wellington
New Zealand
www.osh.dol.govt.nz
ISBN 0-477-03462-4
Second Edition:1989
Important Note:
All the publications in the Publications Archive
contain the best guidance available at the time of
publishing. However, you should consider the
effect of any changes to the law since then. You
should also check that the Standards referred to
are still current.
-
8/12/2019 Fork Truck Hazard
3/18
3
ARCHIVE
CONTENTS
Section 1 Introduction 4
Section 2 Legislative Requirement 6
Section 3 Approval Procedures 7
Section 4 Modifications 9
Appendix I Maintenance Requirements 12
Appendix II Hazardous Zone Classification 13
Section III T Temperature Rating Testing 14
Section IV List of Approved Units 16
Section V Related Documents 18
-
8/12/2019 Fork Truck Hazard
4/18
4
ARCHIVEFLAME PROOF DIESEL POWERED FORK LIFTS FOR USE IN
HAZARDOUS AREAS
SECTION 1
INTRODUCTION
1.1 The mistaken belief that diesel engines, having no electrical spark ignition
system, could be safely used in areas where flammable vapours might be
present, provided that suitable spark arrestors were fitted to the exhaust
system, has been firmly dispelled by various incidents which have
occurred in the petroleum, petrochemical and allied industries.
For instance, an explosion which occurred in recent times in the UnitedKingdom was directly attributable to cyclohexane being ingested by a
diesel engine resulting in wild over-revving, disintegration of the engine
and ignition of the surrounding inflammable gas cloud, which caused
millions of pounds worth of damage.
This, plus a number of similar incidents elsewhere in the world, has
provided some valuable lessons on the behaviour of diesel engines
operating in hazardous zones.
1.2 By drawing in flammable gas through its air intake, a diesel engine cancontinue to run even with its normal fuel supply cut off.
Should such a diesel engine take in sufficient combustible gas to
supplement the normal fuel supply, overspeed can occur to a point where
the engine disintegrates.
1.3 Another risk is that entrained flammable gas in the induction system can
be ignited by a flash over from one or more cylinders at the moment the
inlet valve opens.
Also, after-burning in the exhaust system can cause spark or flame
emission from the exhaust tail pipe, as well as surface temperature rise.
1.4 Diesel exhaust systems frequently operate with surface temperatures of
300C or higher, depending on engine loads. Temperatures of that order
can ignite many inflammable liquids or vapours (auto-ignition
temperature). Standard electrical equipment must also be regarded as a
potential ignition source. Should any form of electrical equipment be
required, it must be of a properly certified flame-proof nature.
1.5 The recommendations in this guide are related to the modifications and
equipment fitted to the vehicle only and are supplementary to existing
-
8/12/2019 Fork Truck Hazard
5/18
5
ARCHIVEsafety practices. Training in the use of diesel-powered forklifts in
hazardous zones is outside the scope of this guide.
While it is considered that the implementation of these requirements will
help to reduce to a minimum the risk of accidents associated with the use
of such machines in defined hazardous zones, the modifications as listed
must be regarded as the minimum required to eliminate all possible
sources of ignition associated with standard machines.
Consideration must be given that apart from design aspects, safety in use
is dependent upon the machinery being in a good state of maintenance.
Recommendations relating to maintenance requirements are given in
Appendix I.
-
8/12/2019 Fork Truck Hazard
6/18
6
ARCHIVESECTION 2
LEGISLATIVE REQUIREMENT
2.1 The Dangerous Goods Act and associated Regulations prohibit theintroduction of sources of ignition into certain areas where dangerous
goods may be present, or within certain specified distances associated with
such areas.
2.2 Where in the relevant regulations there is any requirement limiting the
presence of sources of ignition, that requirement may be modified in
respect of electrical equipment or machinery liable to be an ignition source
by applying the principle of zoning into regions of differing degrees of
hazard in accordance with such standard specification or code as may be
approved by the Chief Inspector of Explosives, and using within any such
zone equipment, such as modified fork lifts, as may be approved by the
Chief Inspector as being acceptable for the particular zone.
Refer to Appendix II for details relating to hazardous zone classification.
2.3 All suitably modified diesel-powered forklifts intended to be used within
defined hazardous zones are to be approved for such use by the Chief
Inspector of Explosives.
Additionally, the user of any such machine must ensure that it has a formalT temperature rating relevant to the auto-ignition temperature of any
flammable agents that it is likely to come into contact with within a
defined hazardous zone.
-
8/12/2019 Fork Truck Hazard
7/18
7
ARCHIVESECTION 3
APPROVAL PROCEDURES
3.1 If it is determined by the user that it may be necessary to operate a diesel-powered forklift unit in a suspected hazardous zone, the first course of
action is to correctly determine the class and extent of the hazardous zone.
The body responsible for determining such an area is the relevant
Dangerous Goods licencing authority for the particular locality.
3.2 Upon confirmation of the existence of an hazardous zone, action may be
taken to modify an existing forklift or to acquire a suitably modified
approved unit for use in such an area.
A list of approved units to date can be found in Appendix IV.
3.3 Any supplier or agent conducting the modification of an existing unit must
comply with the list of minimum requirements as detailed in section 4.
3.4 A further requirement is that such forklifts must have a formal T
temperature rating equal to or less than the auto-ignition temperature of
any dangerous goods that are located within the defined hazardous zone
and which the forklift unit may possibly come into contact with.
3.5 It will be necessary for any such machine to be suitably tested and certified
as to its formal T temperature rating. Such testing is to be carried out by
an approved independent test authority. The rating relates to the maximum
surface temperature during the course of normal operation of any
component subject to heating.
Appendix III details information relating to such testing.
3.6 Upon completion of the relevant testing, a copy of the test report is to be
made available to the Technical Services Officer, Department of Labour,
Dangerous Goods Division. An inspection of the relevant machine will be
conducted for confirmation that the necessary modifications have been
satisfactorily completed.
3.7 Upon the satisfactory completion of the relevant testing and inspection of
the unit concerned, a letter of approval will be issued by the Chief
Inspector of Dangerous Goods.
3.8 Such a letter of approval will detail the particular hazardous zone
classification that the particular machine may operate within. Furthermore,
it will detail the specific T temperature rating of the unit and any
associated operating restrictions that may be imposed upon it.
-
8/12/2019 Fork Truck Hazard
8/18
8
ARCHIVE3.9 It has been determined that any similarly modified units of the same make,
model and type, will not require a temperature rating test to be carried out,
on the specific condition that any such similar units are identical in every
respect and in particular have identical modifications and components
fitted as the previously tested and approved unit.
An inspection of such a unit is carried out prior to the issue of a letter of
approval to ensure compliance with the required modifications.
3.10 Should such a unit have any material changes or modifications
incorporated which are a departure from the originally approved unit, then
it may be necessary for a temperature test to be conducted. This aspect will
be determined by the actual changes involved, in particular any changes
which may involve the exhaust system.
-
8/12/2019 Fork Truck Hazard
9/18
9
ARCHIVESECTION 4
MODIFICATIONS
4.1 Various modifications are incorporated into approved flame-proof dieselforklifts to eliminate potential sources of ignition which exist on standard
units.
4.2 The various hazards which such modifications are designed to control are
listed below:
(1) Discharge of sparks from electrical equipment.
(2) Discharge of sparks from mechanical causes.
(3) Generation and discharge of static from belt drives.
(4) Discharge of sparks or flames from the exhaust system.
(5) Flash back through the induction system.
(6) Excessive temperature of exhaust gases and excessive surface
temperature of engine and exhaust systems.
(7) Overspeeding and possible destruction of the engine due to induction
of flammable gas or vapour.
(8) Explosion in engine crank case; discharge from crank case and
cylinder head relief valves and breathers.
(9) Explosions in intake or exhaust systems.
(10) Flame transmission to atmosphere by opening of decompression ports.
(11) Reverse running of engine.
4.3 The following list of modifications is considered as the minimum required
to allow use in hazardous zones. Explanatory notes are included.
1. All electrical equipment and apparatus must be removed. See note
3(a).
2. The starter system shall be a non-electric type, either pneumatic.
hydraulic, spring recoil, inertia or manual.
3. All electrically actuated gauges are removed. They may be replaced
by alternative mechanical types such as mechanical load indicators,
capillary tube dash board gauges etc.
(a) Note that if any electrical equipment is required though operational
necessity, than such equipment is to be of a suitably certified
flameproof type approved for use in the relevant hazardous zone.
-
8/12/2019 Fork Truck Hazard
10/18
10
ARCHIVE4. The unit shall comply with the maximum surface temperature
requirements as laid down in Australian Standard 1915:1976.
The temperature class of the unit shall be at or below the ignition
temperature of the gases or vapours to which the unit is liable to be
exposed in actual operation. See Appendix III for further information.
5. Light alloy metals, and paints based on light alloy powders, shall not be
used unless the components concerned are suitably protected against
possible mechanical impact or rubbing that could produce incendive
sparking.
6. Blades of the cooling fan shall be made from non-metallic materials.
7. All driving belts shall be of anti-static type.
8. Static discharge. All wheels shall be tyred with rubber or non-metallic
material. At least two tyres and wheels shall be constructed of antistaticmaterial in accordance with B.S. 2050, or some other approved effective
static discharge device shall be provided.
9. Adequate flame paths to be provided on all inlet and exhaust connections.
All such joints, including the attachment of the inlet and exhaust manifold
to the block, shall have a flame path of not less than 13 mm through or
across the joint. This may require spiggotting into the block and manifold
to obtain the required distance. In any case, all such joints shall generally
comply with the requirements for appropriate group enclosures in
accordance with A.S. C98.
10. Suitable metal-clad or other acceptable jointing material gaskets shall be
interposed between all joint faces to ensure that leakage does not occur.
11. Where valve spindles pass through the walls of any component of the
induction system, the diametrical clearance shall not exceed 0.13 mm for
an axial length of not less than 25 mm, unless end caps are fitted. No
screw, stud or bolt hole shall pass through the wall of any component of
the exhaust or induction system.
12. An approved flame arrestor is to be fitted on the air intake between the air
cleaner and intake manifold. This is to counteract flashback through the
induction system.
It is preferable that such a unit is manufactured from stainless steel.
13. An overspeed shutdown device is to be fitted. This may take the form of
(i) a strangler valve unit fitted to the induction system to close the air
intake; or (ii) a system to inject an inert gas into the air intake. Such a
device, which is designed to stop the engine in the event of flammable gasor vapour in the atmosphere causing the engine to overspeed, may be
operated either manually or automatically. It is desirable that any
-
8/12/2019 Fork Truck Hazard
11/18
11
ARCHIVEautomatic system has, in addition, provision for manual operation. This
manual facility must be readily accessible.
14 Relative to the pre-determined T temperature rating requirement of any
particular machine, it may prove necessary to provide a water-cooled
exhaust manifold. Many standard machines may meet the necessary limit,
but may require additional cooling when operated under full load
conditions. The relevant testing will determine this aspect. It is preferable
that such manifolds are manufactured from stainless steel.
Appendix III relates to T temperature rating requirements and testing.
15. A suitable exhaust flame trap and spark arrestor unit is to be fitted. This is
to consist of a water scrubber unit, preferably fabricated from non-
corrodible materials, in which the exhaust gases are passed through water.
The unit is to be fitted with baffles to prevent water carry over and should
be designed to minimise back pressure on the engine.
The unit shall contain sufficient water to allow 8 hours of normal
operation without refilling.
Under certain conditions, consideration may possibly be given for the use
of a suitably certified spark arrestor unit (Dry Cyclone Type) combined
with a flame trap (Spaced Plate Type). Such an arrangement would
probably require the use of an exhaust aftercooler unit.
16. An air-operated (may be aerosol) horn unit to be fitted as an audible
warning device.
17. The fuel tank shall be constructed of metal at least 1.6 mm thick and shall
be fitted with a drain plug and a non-spill vent to maintain atmospheric
internal pressure.
18. An engine having a crankcase volume of over 0.5m3shall be provided
with relief devices. Relief valves or breather units on engines shall be
suitable explosion proof types or else fitted with flame traps.
Alternatively, they may discharge into the induction system downstream ofthe flame trap and upstream of the shut off valve.
Dipsticks and/or filler caps should be screwed or effectively secured by
other means.
19. The fuel injection pump and governor where fitted shall be so designed
that reverse running of the engine is not possible.
20. All fuel or lubricating oil lines are to be routed clear of any likely hot
spots, in particular the exhaust system. All such lines are to be well
supported and clear of any possible chafe points.
-
8/12/2019 Fork Truck Hazard
12/18
12
ARCHIVEAPPENDIX I
MAINTENANCE REQUIREMENTS
As indicated in Section 1, continued safety in use of an approved unit is dependent
upon the unit being in a good state of maintenance at all times that it is utilised in a
hazardous zone.
In association with ongoing maintenance of such units, any replacement parts fitted
to such units which may affect flame-proofing of the unit must be suitably
approved items, manufactured in accordance with the requirements to which the
machine has been originally approved.
The following aspects should be checked at intervals of not longer than three
months, or as indicated by the manufacturer, and a maintenance record kept
covering these items. It should be noted that local conditions and operationalrequirements may require shorter intervals to be considered for such servicing.
This servicing is required in addition to normal mechanical service checks.
(1) Exhaust system including muffler unit and spark arrestor unit if fitted
for carbon build-up, corrosion and damage.
(2) Rotating mechanical equipment
for security and freedom from contact with stationary parts.
(3) Antistatic fan belts for condition and tightness.
(4) Certified electrical equipment (if fitted)
for damage or deterioration, correct operation.
(5) Pressure/temperature alarms and other shutdown devices
for operability at set conditions.
(6) Overspeed shutdown devices
for freedom of operation, correctly filled cylinder for inert gas system if
fitted.
(7) Relief valves and breathers
or operability and cleanliness.
(8) Fasteners and Joints
for tightness and security particularly on induction, exhaust and fuel
systems.
It should be noted that specific maintenance schedules as specified by the relevant
manufacturers should be adhered to. In particular, this will relate to the care and
correct usage of water baffled exhaust scrubber systems, and spark arrestor
elements.
-
8/12/2019 Fork Truck Hazard
13/18
13
ARCHIVEAPPENDIX II
HAZARDOUS ZONE CLASSIFICATION
Hazardous areas may be regarded as those areas where dangerous goods of aflammable nature are present, or may be expected to be present in quantities such
as to require special precautions with respect to the use of items of equipment
liable to be a source of ignition. Within such areas where by regulation there is any
requirement limiting the presence of sources of ignition, that requirement may be
modified in respect of mechanical equipment utilised in the area by applying the
principle of zoning into regions of hazard in accordance with such standard
specifications or codes as may be approved by the Chief Inspector of Explosives.
The classification and delineation of hazardous areas requires, in each case, a
careful review of all the relevant factors. The quantity of flammable substance that
may possibly be liberated, its physical characteristics, the natural tendency of
vapours to disperse into the atmosphere, the location and general ventilation of the
area, and the standards of maintenance or housekeeping that may affect the nature
and extent of the hazard, are factors that must be recognised in determining the
degree and extent of danger.
In all instances, the local dangerous goods licencing authority is responsible for
determining the existence and extent of any hazardous zone.
-
8/12/2019 Fork Truck Hazard
14/18
14
ARCHIVEAPPENDIX III
T TEMPERATURE RATING TESTING
The normal operating temperature of any vehicle component, either electrical or
mechanical to which surrounding atmosphere has access shall not exceed that
stated in Table 1, according to the temperature class for which the vehicle is
intended.
Compliance with the specified temperature limits shall be determined by the
temperature test based upon the requirements of A.S. 1915-1976. The specific
temperature class required for any particular machine is determined by the ignition
temperature of the gas or vapour that the machine is liable to come into contact
with, as determined by A.S. 1896.
TABLE 1
Operating Temperature Limits
Class Max. Surface Temp. oC
T1 450
T2 300
T3 200
T4 135
T5 100
T6 85
A distinction should be drawn between flashpoint and ignition temperature. The
former is the lowest temperature at which an explosive gas/air mixture can exist
under normal atmospheric conditions, whereas the latter is a higher temperature at
which the most ignitable mixture will ignite spontaneously on account of the
environmental temperature.
Test Procedure
(1) The test course shall be 60m long and shall include a gradient of 5 percentwith a total rise of l m.
(2) The test course shall be negotiated at a rate of not less than six complete
cycles per hour and the test shall be conducted in such a manner that the
vehicle is in operation for not less than 50 percent of the total time.
(3) The vehicle shall be operated at normal speed over this course, hauling
full-rated load. Mast tilt should be fully to the rear against the stops with
the relief valve in full operation.
(4) At the end of the course the vehicle shall be stopped and the load moved
through the full lifting cycle.
-
8/12/2019 Fork Truck Hazard
15/18
15
ARCHIVE(5) The vehicle with the load shall then return to the starting point where the
load is again moved through the full lifting cycle and then deposited
beside the test course.
(6) The vehicle shall then be operated with no load over the same course, at
the end of which the forks shall be raised to full height and lowered.
(7) The vehicle shall then be returned to the starting point and the load picked
up.
(8) These runs shall be repeated, laden and unladen trips alternating.
(9) The test shall be continued until constant surface temperatures have been
reached.
(10) During the test, the temperature of any surface exposed to the surrounding
atmosphere shall not exceed the value specified in Table 1 for the
temperature class assigned to the unit.
Brake Temperature Test
(1) Immediately following the above temperature test, the unit, while carrying
its rated load at maximum possible speed, shall be operated over the
course and shall be brought to a complete stop every 15m by application of
the brakes.
(2) The test shall be continued until constant surface temperatures are reached
on the brakes
(3) During the test, the brake temperature shall not exceed the value specified
in Table 1 for the temperature class assigned to the unit.
The relevant testing is to be carried out by an independent testing agency approved
by the Chief Inspector of Explosives. A report of the test is to be provided to the
dangerous goods division.
-
8/12/2019 Fork Truck Hazard
16/18
16
ARCHIVEAPPENDIX IV
LIST OF APPROVED UNITS
The list on the following page details the various diesel powered forklifts whichhave been approved to date as being suitably modified for use as flameproof units
for use in designated hazardous zones.
-
8/12/2019 Fork Truck Hazard
17/18
17
ARCHIVE
APPRO
VEDFLAMEPROOFDIESEL
POWEREDFORKLIFTS
Manufa
cturer
Supplier
Model
SerialNo.
TestingAuthority
T
emp.Class
HazardZone
DateApproved
Hyster/
Baldwin
Gough,Gough
H50H
ED72/009
Exp.Div.NSW
-
C1.1ZN1
10.6.1910
&Hammer
BelcherEquip./
Belcher
2115E
WakefieldLab.
T6
C1.1ZN11
0.1.1984
FordSp
ecial
Equipment
TowTruck
Clark
Andrews&
C500-Y560
11212-30
Materials&Testing
T2
C1.1ZN1
24.4.1981
Beavan
11213-30
Lab.Ltd
11194-29
Datsun
LoadLift
QF02A2FU
5345
Materials&Testing
T3
C1.1ZN-l
23.1.1980
Datsun
LoadLift
QF02A25U
25315
LabLtd.
T3
C1.1ZN1
21.12.1983
Datsun
LoadLift
QF02A25U
22815
T3
C1.1ZN1
17.10.1983
Datsun
LoadLift
QF02A2FU
22125
S.G.S.NZLtd
T3
C1.1ZN1
1.5.1984
Nissan
LoadLift
QF02A25U
25325
S.G.S.NZLtd
T3
C1.1ZN1
7.1.1985
Nissan
LoadLift
QF02A25U
25925
T3
C1.1ZN1
24.9.1985
Toyota
Andrews&
F025
11993/19
DSIRCH.CH
T4
C1.1ZN1
5.1984
Beavan
-
8/12/2019 Fork Truck Hazard
18/18
ARCHIVEAPPENDIX V
RELATED DOCUMENTS
Dangerous Goods Act 1974.
The Dangerous Goods (Class 2 - Gases) Regulations 1980
The Dangerous Goods (Class 3 - Flammable Liquids) Regulations 1985
Dangerous Goods (Labelling) Regulations 1978.
M.P. 6105: 1976 Electrical Wiring in Hazardous Locations.
Australian Standard 1896:1976 Method of Test for Ignition Temperature of Gases
and Vapours.
Australian Standard 1915:1976 Electrical Equipment for Explosive Atmospheres.Battery Operated Vehicles.
Australian Standard C98:1970 Electrical Equipment for Explosive Atmospheres.
Flameproof Enclosure.
British Standard 2050:1978 Electrical Resistance of Conducting and Antistatic
Products made from Flexible Polymeric Material.
NFPA 505 Fire Safety Standard for Powered Industrial Trucks.
Exploded view of a typical modification of a diesel engine for use in defined
hazardous zones.
(not included)