7/29/2019 Fpro Data Sheet(Latest) http://slidepdf.com/reader/full/fpro-data-sheetlatest 1/4 ERL The F-PRO range of multifunction relays provide cost effective, integrated Numerical Protection, Control, Monitoring, Measuring and Communication functionality. The relay has state-of-the-art technology which ensures superior performance. The multifunction capability of F-PRO finds application as main or backup protection in almost every area of power system protection. Applications F-PRO provides comprehensive protection for distribution feeders, and back-up protection for Transformers, Transmission lines and Generators. Functions & Features Protection F-PRO e 3     E     l   e    g    a    n     t Easy to Use Multifunction Protection The relay has ProLogic & GroupLogic functions, which allows user to build or implement their own logic depending upon the scheme requirement for various interlock applications and activation of relevant setting groups Monitoring Broken Conductor Detection (46BC) Current Transformer Supervision (60CTS) Voltage Transformer Supervision (60VTS) and functions inhibit feature Trip Circuit Supervision (74TCS) Displays Distance to Fault value (21FL) CB Monitoring (I² t) Total Harmonic Distortion current detection Alarm (THD) Thermal Over Load Alarm (49AL) 2nd Harmonic based Inrush Detection and functions blocking feature Stores upto 1024 Sequence Of Events / Faults in non-volatile memory with date and time stamp Stores upto 20 disturbance records in non-volatile memory Stores 30 to 360 days of Trend data with maximum of 16 parameters Dir/Non-Dir Over current Protection (67/51/50) Dir/Non-Dir Measured ground fault Protection (67G/51G/50G) or/and Derived ground fault Protection (67N/51N/50N) Restricted/Sensitive (Dir./Non Dir.) ground fault protection (64REF/67SEF/51SEF/50SEF) Voltage Controlled/Retrained Over Current (51V) Over/Under Voltage Protection (59/27) Neutral Voltage Displacement Protection (59N/59G) Negative Sequence Over Current Protection (46) Negative Sequence Over Voltage Protection (47) Thermal Over Load Protection (49) Directional Real/Reactive Power Protection (32P/32Q) Over/Under Frequency Protection (81O/81U) Rate Of Change of Frequency Protection (81R) Cold Load Pick-up (67C/51C) Switch-On-To-Fault Protection (SOTF) Circuit Breaker Failure Protection (50BF) Control Four-shot Auto-Reclose function (79) Synchro check (25) Flexible number of programmable digital Inputs, Virtual inputs and digital outputs Fully Programmable Protection Control Logic-ProLogic Group control logic-GroupLogic

Upload: ajitkalel

Post on 14-Apr-2018

222 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Fpro Data Sheet(Latest)

7/29/2019 Fpro Data Sheet(Latest)

http://slidepdf.com/reader/full/fpro-data-sheetlatest 1/4

ERL

The F-PRO range of multifunction relays provide cost effective,integrated Numerical Protection, Control, Monitoring, Measuring

and Communication functionality. The relay has state-of-the-art

technology which ensures superior performance. The multifunction

capability of F-PRO finds application as main or backup protection

in almost every area of power system protection.

Applications

F-PRO provides comprehensive protection for distribution feeders,

and back-up protection for Transformers, Transmission lines and

Generators.

Functions & FeaturesProtection

F-PRO

e3

    E    l  e

   g    a   n    t

Easy to Use

E    f     f     i    c   

i    e   n   t    

Multifunction Protection

The relay has ProLogic & GroupLogic functions, which allows userto build or implement their own logic depending upon the scheme

requirement for various interlock applications and activation of

relevant setting groups

Monitoring• Broken Conductor Detection (46BC)

• Current Transformer Supervision (60CTS)

• Voltage Transformer Supervision (60VTS) and functions

inhibit feature

• Trip Circuit Supervision (74TCS)

• Displays Distance to Fault value (21FL)

• CB Monitoring (I² t)

• Total Harmonic Distortion current detection Alarm (THD)

• Thermal Over Load Alarm (49AL)

• 2nd Harmonic based Inrush Detection and functions

blocking feature• Stores upto 1024 Sequence Of Events / Faults in non-volatile

memory with date and time stamp

• Stores upto 20 disturbance records in non-volatile memory

• Stores 30 to 360 days of Trend data with maximum of 16

parameters

• Dir/Non-Dir Over current Protection (67/51/50)

• Dir/Non-Dir Measured ground fault Protection (67G/51G/50G)

or/and Derived ground fault Protection (67N/51N/50N)

• Restricted/Sensitive (Dir./Non Dir.) ground fault protection

(64REF/67SEF/51SEF/50SEF)

• Voltage Controlled/Retrained Over Current (51V)

• Over/Under Voltage Protection (59/27)

• Neutral Voltage Displacement Protection (59N/59G)

• Negative Sequence Over Current Protection (46)• Negative Sequence Over Voltage Protection (47)

• Thermal Over Load Protection (49)

• Directional Real/Reactive Power Protection (32P/32Q)

• Over/Under Frequency Protection (81O/81U)

• Rate Of Change of Frequency Protection (81R)

• Cold Load Pick-up (67C/51C)

• Switch-On-To-Fault Protection (SOTF)

• Circuit Breaker Failure Protection (50BF)

Control• Four-shot Auto-Reclose function (79)• Synchro check (25)

• Flexible number of programmable digital Inputs, Virtual

inputs and digital outputs

• Fully Programmable Protection Control Logic-ProLogic

• Group control logic-GroupLogic

Page 2: Fpro Data Sheet(Latest)

7/29/2019 Fpro Data Sheet(Latest)

http://slidepdf.com/reader/full/fpro-data-sheetlatest 2/4

Measurements• Voltage, Current magnitude and phase angle

• Residual Voltage, Current magnitude and phase angle• Sequence Voltage and Current Magnitude

• Real and Reactive Power (P & Q)

• Frequency

• 3Ph Real and Reactive Energy In / Out (MWh / MVARh)

• THD Current value

• Demand value of Phase Voltage, Current, Real / 

Reactive Power, Frequency and THD.

• I² t accumulated

• I² t for last operation

• All the protection, monitoring function, binary input and

output status

Other Features:• Self monitoring

• 1A & 5A CT inputs in same relay

• Wide range of site selectable universal operating time

curve or user defined curve

• Wide range of Auxiliary supply

• Expandable Input / Output Modules

• IRIG-B port for time synchronization

• Outputs configurable to Self / Manual reset

• Multi level password protection

• User friendly setting and disturbance record analysis

software

• Eight independent setting groups

• Graphic LCD (128 * 64 dots / 8 lines * 21 Characters) to

view/change setting, view events and analog information

• Programmable alarm / trip indication LEDs with text legend

Communication Features:

• Front USB port for local communication

• Rear ports:

One Standard RS485 serial port for remote communicationOne Standard fiber optic ST connector serial port for

remote communication

• Two optional RJ45 / Fiber optic Ethernet ports for remote

networking

• The relay supports open protocols of IEC 61850, DNP or

MODBUS RTU & ASCII

Technical Data:Auxiliary Power Supply:

Nominal Operating range

24V,30V,48V DC 18V – 60V DC

110V,125V,220V,250V DC 88V – 350V DC, 80V – 260V AC

Analog Inputs:

Standard : 5 CT inputs or 5 VT inputsOptional : Maximum of 5 CT and 4 VT inputs

Rated current : In = 1A & 5A AC (Dual rated)

Rated Voltage : Un = 63.5 / 110V AC (VT secondary settable

from 40V to 160V AC)

Rated Frequency : 50Hz / 60Hz (Site selectable)

Burden

CT circuit : <0.3VA @ 1A & <0.5VA @ 5A

VT circuit : <0.15 VA @ 67V AC & <0.3VA @ 120V AC

Continuous Rating:

CT circuit : 3 * In AC

VT circuit : 230 V AC

Short time Thermal Rating:

CT circuit : 30 * In for 3 seconds, 100A for 1second

VT circuit : 450V AC for 10 seconds

Binary Inputs:

Standard – 8 programmable binary inputs. Extendable up to 24

Nominal Operating range

24V/30V DC 18 to 37.5V DC

48V/50V DC 37.5 to 60V DC

110V/125V DC 87.5 to 137.5V DC

220V/250V DC 175 to 280V DC

Output Relays:Standard – 8 programmable output relays. Extendable upto 16

Contact Rating:

Carry Continuous : 8A AC or DC

Make & Carry : 30A AC or DC for 0.2 seconds.

Break : 250 VA @ p.f <0.4

Resistive 75W DC, Inductive 50W DC@

L/R < 40msec, with maximum 300V DC.

Dimensions:E6 case : 17.7cm High x 15.5cm Wide x 28cm Deep

E8 case : 17.7cm High x 20.7cm Wide x 28cm Deep

For cut-out and detailed dimensions, refer F-PRO datasheet

Page 3: Fpro Data Sheet(Latest)

7/29/2019 Fpro Data Sheet(Latest)

http://slidepdf.com/reader/full/fpro-data-sheetlatest 3/4

Functional OverviewThe figure below gives a functional overview of a multifunction F-PRO with 5CT inputs and 4 VT inputs

Environmental withstand:

1. Ambient Environment

Temperature – IEC 60255-6

Operating : -10°C to + 55°C

Storage & Transit : -25°C to + 70°C

Cold – IEC 60068-2-1

Dry Heat – IEC 60068-2-2

Humidity – IEC 60068-2-3

Damp Heat Cyclic Test – IEC 60068-2-30

2. Electrical Environment

Di-Electric Test – IEC 60255-5, Clause 6.1.4

Be

ac for 1 min.

Across normally open contacts: 1.0kVac for 1min.

 

Di-Electric Test - IEEE C37.90

Across open contact of change over output type

1.0kV ac for 1 min.

Across open contact of normally open output type

1.5kV ac for 1 min.

Transient Overvoltage – IEC 60255-5, Class III, Clause

6.1.3

Between all terminals and earth or between any twoindependent circuits without damage or flashover –

5kV 1.2/50 μsec; 0.5j; 5 positive & negative shots at theinterval of 10 Sec. 

Insulation Resistance Test – IEC 60255-5

Between all terminals and earth – 500V applied for more than

1minute – 10 mega ohm to 100 mega ohm

 

tween all terminals and earth: 2.0kVac for 1 min.

Between independent circuit : 2.0kV

3. Electromagnetic Environment – Immunity

  High Frequency disturbance – IEC 60255-22-1 Class III

2.5kV Common (Longitudinal) mode : < 5% variation

1.0 kV series (Transverse) mode : < 5% variation

Electrostatic discharge – IEC 60255-22-2 Class IV;

IEC 61000-4-2 Class IV; IEEE C37.90.3

8kV contact discharge: < 5% variation

15kV air discharge: < 5% variation

Power Frequency Magnetic Field Interference

- EN 61000-4-8, Class V

100 A/m Continuous

1000 A/m for 3 Sec.

Radio Frequency Interference – IEC 60255-22-3

ENV 50140; IEC61000-4-3

20MHz to 1000MHz, 10V/m; < 5% variation

 

Radio Frequency Electro Magnetic Field Pulse Modulated

ENV 50140 / ENV 50204

900 MHz, repetition freq: 200Hz;

Duty cycle 50%; 10V/m: < 5% variation

Radio Frequency Interference - IEEE C37.90.2

25MHz to 1000MHz, 35V/m:<5% variation

 

Fast Transient – IEC 60255-22-4 Class IV, IEC61000-4-4

Conducted freq: Interference – IEC 60255-26;

IEC61000-4-6; ENV50141; EN61000-6-3

0.15MHz to 1000MHz, 10V/m: < 5% variation

 

Surge Immunity – IEC61000-4-5, Level 4

 

Page 4: Fpro Data Sheet(Latest)

7/29/2019 Fpro Data Sheet(Latest)

http://slidepdf.com/reader/full/fpro-data-sheetlatest 4/4

The policy of EASUN REYROLLE is one of continuous improvement and development. The company therefore reserves the right to supply equipment which may differ slightly 

from that described and illustrated in the publication.

ERL

ERL Group Corporate Office

#389, “Rasukumaki”, Hulimavu, Begur Hobli, Bannerghatta Road, Bangalore – 560 076, India

Tel: +91 80 6717 7000 Fax: +91 80 6717 7002 Email: [email protected]

Global Marketing Offices

Germany, Canada, Hong Kong, Thailand, South Africa, UAE, Brazil, Peru & USA

Global Manufacturing CentersIndia, Canada & Germany

Global Technology Centers

India, Canada & Germany

Marketing Offices in IndiaBangaloreTel: +91 80 6717 7000/01

Fax: +91 80 6717 7002

Email: [email protected]

BhopalFax: +91 755 2684221

Email: [email protected]

ChennaiTel: +91 44 2434 6425/7608

Fax: +91 44 2434 6435

Email: [email protected]

KolkataTel: +91 33 2284 8320

Fax: +91 33 2284 8326

Email: [email protected]

MumbaiTel: +91 22 2285 54415/ 2202 2270

Fax: +91 22 2285 5703

Email: [email protected]

NoidaTel: +91 120 2405 741/42/43

Fax: +91 120 2405 744

Email: [email protected]

SecunderabadTel: +91 40 2781 7847

Email: [email protected]

      F      A      C      T      /      F   -      P      R      O      /      0      9   -      1      0      /      R      E      V      1 .

      0

Surge withstand capability – IEEE/ANSI C37.90.1

5kV fast transient and 3kV oscillatory applied direct across

each output contact, optically isolated input and power

supply circuit.

4. Electromagnetic Environment – Emission

Radiated Radio Frequency – IEC 60255-25;

ENV 55011 – Group 1; Class A Limits

Conducted Radio Frequency – IEC 60255-25;

ENV 55011 – Group 1 Class A Limits

5. Mechanical Environment

Vibration (Sinusoidal) – IEC 60255-21-1 Class I

IEC 60068-2-6

Shock and bump – IEC 60255-21-2 Class IIEC 60068-2-27

Seismic - IEC 60255-21-3 Class I

Mechanical Classification6

Durability in excess of 10 operations

www easunreyrolle com

Ordering Information: 

Please refer F-PRO datasheet for ordering information.

Qualification

ISO 9001:2008

CE Compliant to relevant EU Directives