freescalesemiconductorpresentation.pdf

Upload: muoi2002

Post on 04-Jun-2018

218 views

Category:

Documents


0 download

TRANSCRIPT

  • 8/14/2019 FreescaleSemiconductorPresentation.pdf

    1/24

    Energy Optimization of a LargeCentral Plant Chilled Water System

    Riyaz Papar, PE, CEMHudson Technologies Company

    Harold Myart, PE, CEMMark Krawczyk, PE, CEM

    Freescale Semiconductor, Inc.

    Texas Chemical Council Seminar

    June 09, 2009

  • 8/14/2019 FreescaleSemiconductorPresentation.pdf

    2/24

    Agenda Objectives

    System Description

    Data Collection & Models

    System Optimization Opportunities

    System Optimization Results

    Conclusions

  • 8/14/2019 FreescaleSemiconductorPresentation.pdf

    3/24

    Objectives Conduct a chilled water system Energy

    Savings Assessment (ESA) using a Systems

    Approach at the Oak Hill Plant site

    Identify (and quantify) chilled water plant

    energy savings opportunities

    Assist plant personnel to gain familiarity with

    certain bestpractices and to continue toidentify energy efficiency improvementopportunities at the site

  • 8/14/2019 FreescaleSemiconductorPresentation.pdf

    4/24

  • 8/14/2019 FreescaleSemiconductorPresentation.pdf

    5/24

    System PFD

    1 62 3 4 5

    1 2 3

    Water Chillers (42F)

    Glycol Chillers (32F)

    Air Coils

    Air Coils

  • 8/14/2019 FreescaleSemiconductorPresentation.pdf

    6/24

    Identified Chiller Plant BestPractices Site-level integrated chilled water and glycol loops

    High efficiency two-stage centrifugal chillers for base load and screwmachines to provide for swing capacity

    Use of variable speed drives on the secondary pumping loop

    Use of variable speed drives on the condenser water pumps

    Use of two-speed fans on the cooling towers

    Significant instrumentation, data monitoring and controls

    Use of real-time data for tracking efficiency metrics (kW/ton) and aHistorian for analysis

    Good periodic maintenance practices for equipment (oil analysis,cleaning of heat exchanger tubes, eddy current testing, etc.)

    Periodic calibration of all critical instrumentation

  • 8/14/2019 FreescaleSemiconductorPresentation.pdf

    7/24

  • 8/14/2019 FreescaleSemiconductorPresentation.pdf

    8/24

    Load Profile

    -

    2,000

    4,000

    6,000

    8,000

    10,000

    9/5/07 10/25/07 12/14/07 2/2/08 3/23/08 5/12/08 7/1/08 8/20/08 10/9/08

    42FChillerPlantLoad(RT)

    1

    2

    3

    4

    5

    6

    NumberofOperatingChillers

  • 8/14/2019 FreescaleSemiconductorPresentation.pdf

    9/24

    Chilled Water Plant Efficiency

    0.400

    0.450

    0.500

    0.550

    0.600

    0.650

    0.700

    0.750

    0.800

    9/5/07 10/25/07 12/14/07 2/2/08 3/23/08 5/12/08 7/1/08 8/20/08 10/9/08

    OverallPlant

    Efficiency(kW/RT)

  • 8/14/2019 FreescaleSemiconductorPresentation.pdf

    10/24

    Chilled Water Plant Efficiency

    0.6230.7040.6500.6770.7050.5410.597Efficiency (kW/RT)

    2,144591561599610511553Power (kW)

    3,428846863887868944924Load (RT)

    8,7502,5916,3366,8772,6337,4587,469Operating hours

    OverallPlant

    654321Chiller #

  • 8/14/2019 FreescaleSemiconductorPresentation.pdf

    11/24

    Chiller Efficiency

    0.50

    0.55

    0.60

    0.65

    0.70

    0.75

    0.80

    0.85

    0.90

    68 70 72 74 76 78 80 82

    Condenser Water Temperature (F)

    ChillerEffi

    ciency(kW/RT)

  • 8/14/2019 FreescaleSemiconductorPresentation.pdf

    12/24

    Chiller Efficiency

    0.40

    0.45

    0.50

    0.55

    0.60

    0.65

    0.70

    0.75

    0.80

    39.0 40.0 41.0 42.0 43.0 44.0 45.0 46.0 47.0

    Chilled Water Supply Temperature (F)

    ChillerEffi

    ciency(kW/RT)

  • 8/14/2019 FreescaleSemiconductorPresentation.pdf

    13/24

    Energy Savings Opportunity Reduce condenser water temperature

    Condenser water maintained currently at 75F

    Controlled by two-speed fans

    Typically, 10% energy used by fans, 20% bypumps and 70% by compressor

    Compressor kW/RT increases with highercondenser water temperature

    Float condenser pressure for maximum savings

    Implementation to lower condenser water to 70F Potential savings ~7%

  • 8/14/2019 FreescaleSemiconductorPresentation.pdf

    14/24

    Energy Savings Opportunity Constraints / Precautions - Reduce condenser

    water temperature

    Check manufacturers recommendations 65Fminimum condenser water temperature

    Refrigerant Stacking issues

    Concerns about leaks in low pressure (R123)chillers

  • 8/14/2019 FreescaleSemiconductorPresentation.pdf

    15/24

    Energy Savings Opportunity Reduce number of operating chillers

    -

    1,000

    2,000

    3,000

    4,000

    5,000

    6,000

    7,000

    8,000

    09/05/07 10/25/07 12/14/07 02/02/08 03/23/08 05/12/08 07/01/08 08/20/08 10/09/08

    ChillerTons

    (RT)

    Actual P lant Load

    Operating Capacity

    Ex cess Ca pacity

    \

  • 8/14/2019 FreescaleSemiconductorPresentation.pdf

    16/24

  • 8/14/2019 FreescaleSemiconductorPresentation.pdf

    17/24

    Energy Savings Opportunity Increase primary chilled water flow through chillers

    Design rating is based on 42F chilled water, 85Fcondenser water and 100% load (Tons)

    But this happens for 1-3% of the operating hours

    Chiller has a lot more capacity at off-design conditions

    Implement Variable Primary Flow and increase chilledwater flow

    Chiller moves to full-load conditions and kW/RT reduces

    Preliminary estimates ~5-10% energy savings Constraints / Precautions

    Pumping power capability

    Compressor horsepower limitation

  • 8/14/2019 FreescaleSemiconductorPresentation.pdf

    18/24

  • 8/14/2019 FreescaleSemiconductorPresentation.pdf

    19/24

    Energy Savings Opportunity Implement SMART algorithm to reset chilled water

    supply temperature

    1F increase in chilled water supply temperature leadsto a reduction of 0.015 kW/RT

    DAS has information on chilled water flow control valve

    positions of almost all the air-handling units Automatically increase chilled water supply temperature

    till a control valve reaches 80% open

    Currently, done on a manual basis

    Constraints / Precautions

    Dynamic flow issues

    Will have to ensure no hunting

  • 8/14/2019 FreescaleSemiconductorPresentation.pdf

    20/24

    BestPractices Implement real-time calculation of chiller

    efficiencies and trending

    Will provide information for further optimization All the data is already available

    Implement a Chiller Chemistry program Fluids Refrigerant, Oil and Water should be tested

    every six months

    An engineering analysis combining all these results

    Root-cause analysis

    Best Predictive Maintenance can be done online

  • 8/14/2019 FreescaleSemiconductorPresentation.pdf

    21/24

    Energy Savings Opportunities

    N5,000NC0NCImplement a Chiller Chemistry PM program

    N25,000NANANAImplement real time monitoring and add trendingof efficiency

    MNCNC0NCImplement SMART algorithm to reset chilledwater supply temperature

    M25,00020,0000315,000Transfer load from the 32F glycol loop to the42F chilled water loop

    N10,00060,0000930,000Increase primary chilled water flow through thechillers

    N25,00091,00001,400,000Reduce number of operating chillers

    N40,00053,0000815,000Reduce condenser water temperature

    ThermskWhPB

    ProjectCost ($)

    CostSavings ($)

    Energy Savings

    Opportunity

    *NA Not Applicable**NC Not Calculated (See write up for details)

  • 8/14/2019 FreescaleSemiconductorPresentation.pdf

    22/24

    Conclusions Instrumentation & monitoring of critical

    parameters was key for optimization of thechilled water plant

    A Systems Approach is needed for optimizing

    any energy system

    Typically, chilled water and refrigeration

    systems are neglected in plants but they offersignificant energy savings potential

  • 8/14/2019 FreescaleSemiconductorPresentation.pdf

    23/24

    Acknowledgments Kathey Ferland

    TX Industries of the Future

    Paul Lloyd & Dean BlackmanFreescale Semiconductor, Inc.

  • 8/14/2019 FreescaleSemiconductorPresentation.pdf

    24/24

    Discussion & Questions