freescalesemiconductorpresentation.pdf
TRANSCRIPT
-
8/14/2019 FreescaleSemiconductorPresentation.pdf
1/24
Energy Optimization of a LargeCentral Plant Chilled Water System
Riyaz Papar, PE, CEMHudson Technologies Company
Harold Myart, PE, CEMMark Krawczyk, PE, CEM
Freescale Semiconductor, Inc.
Texas Chemical Council Seminar
June 09, 2009
-
8/14/2019 FreescaleSemiconductorPresentation.pdf
2/24
Agenda Objectives
System Description
Data Collection & Models
System Optimization Opportunities
System Optimization Results
Conclusions
-
8/14/2019 FreescaleSemiconductorPresentation.pdf
3/24
Objectives Conduct a chilled water system Energy
Savings Assessment (ESA) using a Systems
Approach at the Oak Hill Plant site
Identify (and quantify) chilled water plant
energy savings opportunities
Assist plant personnel to gain familiarity with
certain bestpractices and to continue toidentify energy efficiency improvementopportunities at the site
-
8/14/2019 FreescaleSemiconductorPresentation.pdf
4/24
-
8/14/2019 FreescaleSemiconductorPresentation.pdf
5/24
System PFD
1 62 3 4 5
1 2 3
Water Chillers (42F)
Glycol Chillers (32F)
Air Coils
Air Coils
-
8/14/2019 FreescaleSemiconductorPresentation.pdf
6/24
Identified Chiller Plant BestPractices Site-level integrated chilled water and glycol loops
High efficiency two-stage centrifugal chillers for base load and screwmachines to provide for swing capacity
Use of variable speed drives on the secondary pumping loop
Use of variable speed drives on the condenser water pumps
Use of two-speed fans on the cooling towers
Significant instrumentation, data monitoring and controls
Use of real-time data for tracking efficiency metrics (kW/ton) and aHistorian for analysis
Good periodic maintenance practices for equipment (oil analysis,cleaning of heat exchanger tubes, eddy current testing, etc.)
Periodic calibration of all critical instrumentation
-
8/14/2019 FreescaleSemiconductorPresentation.pdf
7/24
-
8/14/2019 FreescaleSemiconductorPresentation.pdf
8/24
Load Profile
-
2,000
4,000
6,000
8,000
10,000
9/5/07 10/25/07 12/14/07 2/2/08 3/23/08 5/12/08 7/1/08 8/20/08 10/9/08
42FChillerPlantLoad(RT)
1
2
3
4
5
6
NumberofOperatingChillers
-
8/14/2019 FreescaleSemiconductorPresentation.pdf
9/24
Chilled Water Plant Efficiency
0.400
0.450
0.500
0.550
0.600
0.650
0.700
0.750
0.800
9/5/07 10/25/07 12/14/07 2/2/08 3/23/08 5/12/08 7/1/08 8/20/08 10/9/08
OverallPlant
Efficiency(kW/RT)
-
8/14/2019 FreescaleSemiconductorPresentation.pdf
10/24
Chilled Water Plant Efficiency
0.6230.7040.6500.6770.7050.5410.597Efficiency (kW/RT)
2,144591561599610511553Power (kW)
3,428846863887868944924Load (RT)
8,7502,5916,3366,8772,6337,4587,469Operating hours
OverallPlant
654321Chiller #
-
8/14/2019 FreescaleSemiconductorPresentation.pdf
11/24
Chiller Efficiency
0.50
0.55
0.60
0.65
0.70
0.75
0.80
0.85
0.90
68 70 72 74 76 78 80 82
Condenser Water Temperature (F)
ChillerEffi
ciency(kW/RT)
-
8/14/2019 FreescaleSemiconductorPresentation.pdf
12/24
Chiller Efficiency
0.40
0.45
0.50
0.55
0.60
0.65
0.70
0.75
0.80
39.0 40.0 41.0 42.0 43.0 44.0 45.0 46.0 47.0
Chilled Water Supply Temperature (F)
ChillerEffi
ciency(kW/RT)
-
8/14/2019 FreescaleSemiconductorPresentation.pdf
13/24
Energy Savings Opportunity Reduce condenser water temperature
Condenser water maintained currently at 75F
Controlled by two-speed fans
Typically, 10% energy used by fans, 20% bypumps and 70% by compressor
Compressor kW/RT increases with highercondenser water temperature
Float condenser pressure for maximum savings
Implementation to lower condenser water to 70F Potential savings ~7%
-
8/14/2019 FreescaleSemiconductorPresentation.pdf
14/24
Energy Savings Opportunity Constraints / Precautions - Reduce condenser
water temperature
Check manufacturers recommendations 65Fminimum condenser water temperature
Refrigerant Stacking issues
Concerns about leaks in low pressure (R123)chillers
-
8/14/2019 FreescaleSemiconductorPresentation.pdf
15/24
Energy Savings Opportunity Reduce number of operating chillers
-
1,000
2,000
3,000
4,000
5,000
6,000
7,000
8,000
09/05/07 10/25/07 12/14/07 02/02/08 03/23/08 05/12/08 07/01/08 08/20/08 10/09/08
ChillerTons
(RT)
Actual P lant Load
Operating Capacity
Ex cess Ca pacity
\
-
8/14/2019 FreescaleSemiconductorPresentation.pdf
16/24
-
8/14/2019 FreescaleSemiconductorPresentation.pdf
17/24
Energy Savings Opportunity Increase primary chilled water flow through chillers
Design rating is based on 42F chilled water, 85Fcondenser water and 100% load (Tons)
But this happens for 1-3% of the operating hours
Chiller has a lot more capacity at off-design conditions
Implement Variable Primary Flow and increase chilledwater flow
Chiller moves to full-load conditions and kW/RT reduces
Preliminary estimates ~5-10% energy savings Constraints / Precautions
Pumping power capability
Compressor horsepower limitation
-
8/14/2019 FreescaleSemiconductorPresentation.pdf
18/24
-
8/14/2019 FreescaleSemiconductorPresentation.pdf
19/24
Energy Savings Opportunity Implement SMART algorithm to reset chilled water
supply temperature
1F increase in chilled water supply temperature leadsto a reduction of 0.015 kW/RT
DAS has information on chilled water flow control valve
positions of almost all the air-handling units Automatically increase chilled water supply temperature
till a control valve reaches 80% open
Currently, done on a manual basis
Constraints / Precautions
Dynamic flow issues
Will have to ensure no hunting
-
8/14/2019 FreescaleSemiconductorPresentation.pdf
20/24
BestPractices Implement real-time calculation of chiller
efficiencies and trending
Will provide information for further optimization All the data is already available
Implement a Chiller Chemistry program Fluids Refrigerant, Oil and Water should be tested
every six months
An engineering analysis combining all these results
Root-cause analysis
Best Predictive Maintenance can be done online
-
8/14/2019 FreescaleSemiconductorPresentation.pdf
21/24
Energy Savings Opportunities
N5,000NC0NCImplement a Chiller Chemistry PM program
N25,000NANANAImplement real time monitoring and add trendingof efficiency
MNCNC0NCImplement SMART algorithm to reset chilledwater supply temperature
M25,00020,0000315,000Transfer load from the 32F glycol loop to the42F chilled water loop
N10,00060,0000930,000Increase primary chilled water flow through thechillers
N25,00091,00001,400,000Reduce number of operating chillers
N40,00053,0000815,000Reduce condenser water temperature
ThermskWhPB
ProjectCost ($)
CostSavings ($)
Energy Savings
Opportunity
*NA Not Applicable**NC Not Calculated (See write up for details)
-
8/14/2019 FreescaleSemiconductorPresentation.pdf
22/24
Conclusions Instrumentation & monitoring of critical
parameters was key for optimization of thechilled water plant
A Systems Approach is needed for optimizing
any energy system
Typically, chilled water and refrigeration
systems are neglected in plants but they offersignificant energy savings potential
-
8/14/2019 FreescaleSemiconductorPresentation.pdf
23/24
Acknowledgments Kathey Ferland
TX Industries of the Future
Paul Lloyd & Dean BlackmanFreescale Semiconductor, Inc.
-
8/14/2019 FreescaleSemiconductorPresentation.pdf
24/24
Discussion & Questions