Frequency Response Analysis: Failure Mode Analysis
Dinesh Chhajer, PE Volney Naranjo
Applications Engineers
2
Introduction
FRA: • Sensitive diagnostic test to detect damage in the
electrical/mechanical configuration of a transformer – Windings, core, leads, insulation, tap changer, etc.
• Measures the response to a signal of variable frequency injected at one terminal and measured at another
• Results are compared with a reference response – “fingerprint” to make a diagnostic
• Has the potential to detect minor damage not evident in other electrical tests
3
Introduction
• Results are compared with a reference response – “fingerprint” expecting a perfect match
• No match = change in configuration = problem
4
Introduction
Standardization • IEEE C57.149-2012
– “Guide for the Application and Interpretation of Frequency Response Analysis for Oil-Immersed Transformers”
• IEC60076-18 Ed. 1 – 2012 • Std. DL/T911-2004 • Cigré Technical Brochure No. 342, April 2008
5
Introduction
Review of IEEE C57.149-2012 Recommendations from other Standards C57.149-2012 Failure Modes Real Life Failure Mode Analysis FRA Case Studies Conclusion Summary
7
Test Instrument • Minimum 200 points per decade, XML format • Three lead configuration (signal, reference, and test),
– coaxial cables and with length up to 30m • Frequency range wide enough to diagnose problems in the
core, clamping structure and winding/interconnections.
Specimen Scope • Explicit for oil-immersed transformers – No limits on V or MVA • Test after any situation that can cause mechanical movement
or electrical damage – Short circuit: factory test or through fault – Installation, relocation or catastrophic event – Routine diagnostic measurement protocol – After a transformer alarm, change in electrical test
conditions (i.e., a change in winding capacitance)
8
Test Conditions
Image from: www.TAW.com
All terminals disconnected
Tank should be grounded
Close to in-service condition: - bushings installed - filled with oil (preferred)
CT’s connected for in-service conditions
If possible, all test leads connections should go directly to the bushing terminal.
LTC: - Test in extreme raise
position - Neutral: preferred to
arrive from raise position
DETC - determined by in-service
conditions - Operation up to the
decision of the owner
9
Test Voltage • Use the same voltage for every test to guarantee repeatability
below 10 KHz • Avoid applying excessive voltages to
transformers without oil
Frequency Range • IEEE has no specific recommendation or requirement for the
frequency range setting • It analyzes different failures in a frequency range from 20 Hz to
1 MHz • A response greater than 1 MHz is irregular and complex, it may
contain important information from the leads of taps but it is also affected by the grounding leads.
10Vpp
0.1 Vpp
10
Measurement Types
• Minimum requirement: all open circuit tests • Recommended: all end-to-end open and short circuit tests • LTC should be set in extreme position to include all tap
windings in the circuit
Instrument and Tests Verification • Run a self-check of the instrument on a standard test object
with a known response
11
Test Lead Connections • Sequence of connections:
– The purpose is to test all windings – Measurements should be done from head-to-tail, following
winding configuration (vector group) – Variations on sequence or polarity are accepted
• Shield grounding: - Run an extension of the grounding
cable from the top of the bushing (lead connection) to the flange of the bushing.
- Grounding techniques, conductors, routing and any other aspect related to it should be precise, repeatable and documented.
12
Test Result Analysis • Main purpose is to determine if the physical condition has
changed • Secondary purpose is to determine the type of mechanical
failure, e.g., radial deformation, axial elongation, core defects and turn-to-turn short circuit, among others
• The two basic analysis tools are: Trace comparison and Identification of trace characteristics
13
Trace Comparison • Primary tool for analysis • Compares to a previous measurement, similar units or the other
phases on the same unit as a reference • A comparison to a previous measurement should overlay almost
perfectly • Method 1: Plot inspection
– It is the method used to determine the different failure modes – Evaluate trace resonances and magnitude and phase deviations
as well as the general patterns – Any deviation may be an indication of a mechanical change
• Method 2: Difference Plotting – Any deviation from zero requires a detailed evaluation
• Method 3: Correlation coefficients – Determines how random or similar two traces are
14
Trace Characteristics • There is a general characteristic response for each type of test and
frequency region • Knowing the characteristics helps in identifying problems and
narrowing them to a specific component of the transformer • There are significant indicators for two general problems:
1. Winding deformation/Insulation degradation: – New resonances or loss of resonances – Shift in frequency for an existing resonance
2. Winding looseness: – Continuous increment of magnitude compared to the
reference trace with a similar shape as frequency increases above 500 KHz.
• Each type of test has its own general expected characteristic
16
CIGRE Technical Brochure No. 342 Chinese Standard DL/T911-2004 IEC Standard 60076-18 Ed.1
Frequency Range • Cigré: shows the typical ranges response for high voltage (HV), low
voltage (LV), and regulating windings of large and medium MVA rating
17
Frequency Range (cont.) • IEC recommends using at least 2 MHz in all tests for compatibility and
simplicity
Sequence of Connections • IEC:
– Yn Windings: Source to the line terminal, measurement on the neutral
– Delta Windings and Y (w/o neutral): Follow the terminal numbering or labeling in ascending order
– It also defines the connections for zigzag windings, autotransformers, phase shifting transformers and reactors
Standard Range DL/T911-2004 1 KHz to 1 MHz
IEC 60076-18 Ed.1 ≤20 Hz to 1 MHz for test objects >72.5 KV ≤20 Hz to 2 MHz for test objects ≤72.5 KV
18
Sequence of Connections • IEC (cont):
– Provides a table to specify additional measurements if required. connection terminals for each test: signal/reference, response, grounded, floating, shorted; tap position and previous position.
• Chinese Standard – Follows the same criteria as IEC but swaps the location of the
leads; it states to connect the source to the tail and the measurement to the head.
19
Shield Grounding • IEC:
– 1st Method (Preferred): o Allows interpretation up to 2
MHz
– 2nd Method: o Use a fixed length wire or
braid o May affect amplitude (dB)
measurements above 500 kHz and resonant frequencies above 1 MHz
21
Instrument and Tests Verification • Cigré
– Run an integrity verification: oObject of a known response oBy means of connecting the test leads together: 0 dB response
– Run a repeatability check, especially across bushings rated 400 kV and higher: oTo determine the maximum usable frequency for results
analysis oConsists of repeating a test after removing the test leads and
reconnecting them oMaximum usable frequency: the point where the two results
start to deviate significantly. o For bushings of lower voltages, the issues of repeatability are
above 1 MHz
22
Instrument and Tests Verification • IEC:
– Instrument performance: This is same as the integrity verification of Cigré
– Repeatability: It recommends repeating the first test after completion of the measurements
– Zero check: oOptional oPurpose: To determine the highest frequency usable for
interpretation on each side of the transformer. oConsists of making two measurements. First with all the test
leads connected to one of the HV terminals and then to one of the LV terminals.
24
Radial Deformation
It is a radial (inward) compressive failure. The result
is a buckling along the winding.
Deformation can occur in two
forms, free and forced, and forces are concentrated on the
inner windings.
Frequency Range
Open Circuit
Short Circuit
20 Hz - 10 kHz Generally unaffected
Slight attenuation
5 kHz - 100 kHz Minimal shifts or new resonances
50 kHz - 1 MHz Obvious shifts or new resonances
> 1 MHz Unaffected
Radial Deformation Case 2
25
Axial Deformation
The winding will be stretched and its radius will be
reduced.
The response might show multiple resonances shifting in a broad frequency range.
Frequency Range
Open Circuit
Short Circuit
20 Hz - 10 kHz Generally unaffected
Change in magnitude
5 kHz - 100 kHz Obvious shifts or new resonances
50 kHz - 1 MHz Possible shifts or new resonances
> 1 MHz Unpredictable
Axial Deformation Case Study 2
26
Bulk Winding Deformation
Corresponds to the movement of coils due to high currents,
shocks during transportation or natural disasters.
Frequency Range
Open Circuit
Short Circuit
20 Hz - 10 kHz Generally unaffected
Generally unaffected
5 kHz - 100 kHz Obvious new resonances Possible shifting
50 kHz - 1 MHz Possible shifting at the higher frequencies
> 1 MHz Possible shifting
27
Core Defects
A physical change in the transformer core: shorted or burnt
laminations, disconnected core
ground or unintentional core grounds, and joint
movements.
Frequency Range
Open Circuit
Short Circuit
20 Hz - 10 kHz
Changes in the primary resonance.
Discard magnetization
effects.
Generally unaffected
5 kHz - 100 kHz Possible shifts or new resonances
50 kHz - 1 MHz Possible shifting at the higher frequencies
> 1 MHz Possible shifting
28
Contact Resistance
More than a failure mode it is an indication of poor contact on the bushing to winding connection,
LTC or DETC that can cause changes in low and high
frequencies.
Frequency Range
Open Circuit
Short Circuit
20 Hz - 10 kHz Generally unaffected
Affected winding
will show offset
5 kHz - 100 kHz Possible shifts or new resonances
50 kHz - 1 MHz Possible shifts or new resonances
> 1 MHz Possible shifts or new resonances
29
Turn-to-turn short circuit
Low or high impedance shorts between turns
easily detected with a FRA test.
The open circuit diagnose response will look like a
short circuit test.
Frequency Range
Open Circuit
Short Circuit
20 Hz - 10 kHz
Response similar to a short circuit
test
Obvious differences.
Affected winding shows offset
5 kHz - 100 kHz Possible shifts or new resonances
50 kHz - 1 MHz Possible shifts or new resonances
> 1 MHz Possible shifts or new resonances
30
Open Winding
High impedance due to loose connections or burned through coils from thermal
failure.
Complete open circuits will show
results close to the noise floor.
Frequency Range
Open Circuit
Short Circuit
20 Hz - 10 kHz Changes in the primary resonance.
Discard magnetization
effects
Obvious differences.
Affected winding shows
offset 5 kHz - 100 kHz Obvious new resonances.
Possible shifting 50 kHz - 1 MHz Possible shifts
or new resonances > 1 MHz Possible shifts
or new resonances
31
Winding Looseness It is a spreading of the disk-to-disk or turn-to-
turn axial distances caused by the
loosening of a clamping structure.
Commonly caused by transportation.
Frequency Range
Open Circuit
20 Hz - 500 kHz Generally unaffected
500 kHz – 2 MHz Some detectable increasing differences
1 MHz – 5 MHz Largest increasing differences.
Floating Static Shield with Carbonization
Loose electric contact of the copper bonding braid on the
aluminum shield strips
Frequency Range
Open Circuit
<100 kHz Some differences 100 kHz – 500
kHz Possible large differences in
magnitude of resonances
1 MHz – 3 MHz Largest differences in magnitude of resonances
Winding Looseness Case 1
33
Case 1 History
Four single-phase regulating autotransformers, 130/130/16.5 MVA, 230/√3 / 161/√3 / 69 kV, in process of installation and commissioning experienced a major earthquake of very high intensity.
Fingerprints taken at the delivery of the autotransformers were compared to test performed after the earthquake and significant deviations were detected on three out of the four autotransformers.
The deviations were noticeable on the short circuit test H1-H0X0 [with shorted X1-H0X0].
37
Analysis
On evaluating the short circuit results, significant differences were observed in the following high frequency ranges: • Autotransformer 1: 150 KHz to 2 MHz • Autotransformer 2: 200 KHz to 1 MHz • Autotransformer 3: 700 KHz to 2 MHz
A common characteristic for each comparison is an increasing magnitude difference in the high frequencies area. This is a typical indicator of winding looseness as described in the failure modes section of IEEE guide.
38
Conclusion
It was decided to inspect the transformers on site.
Visual inspection was performed and it was found that the three autotransformers were longitudinally displaced.
There was a bigger separation between the turns of the winding due to the loosening of the blocking structure.
The FRA diagnosis was able to detect the internal winding movement and issue was resolved at site by transformer manufacturer before the commissioning of the auto transformers.
39
Case 2 History
A 40 MVA, 115/13.8 kV wye-wye transformer installed in 1991, showed an increase in PF and LV side capacitance readings after maintenance was performed as a result of reported oil leaks
Under scheduled maintenance the next year, LV side capacitance showed a further increase in readings.
FRA test was performed as a part of advanced diagnosis. There were no baseline curves available for the transformer.
41
Analysis
All three phases were compared to determine any mechanical changes within the transformer
The three LV windings showed a lot of asymmetry in the frequency range of 20 kHz- 1 MHz
Possible LV main winding movement was suspected based upon the FRA curves
Results were further analyzed to compare A (X1-X0) and C (X3-X0) phase traces that should have similar resemblance.
44
Analysis
Traces were compared in the frequency range of 30- 500 kHz that corresponds to the main winding section.
Two traces showed extensive asymmetry; suspected winding movement was further strengthened.
As per IEEE guide, radial winding deformation or hoop buckling is most visible in FRA trace in the 50 kHz – 1MHz frequency range
45
In Service Trip
Transformer was placed under watch list. It was put back in service.
In the same year, a few months later the transformer tripped out due to a fault.
It was decided not to put this transformer back in service based upon a further increase in LV side capacitance (PF test) after the fault.
Transformer was sent for inspection and repair.
48
Conclusion
Upon de-tanking and tear down, it was found that all three low side windings were severely deformed showing signs of radial buckling due to lack of strength to withstand through fault conditions.
After diagnosing the problem, the transformer was rebuilt and put back in service at a different location.
A new FRA fingerprint was taken before putting it back in service for any future investigation and analysis.
50
Case Study 1 History
A 22 kV/4160 V delta wye transformer showed questionable readings on routine electrical tests.
Winding resistance readings on low side B phase showed a difference of more than 17% as compared to A & C phase.
The excitation current showed very high values on B phase when compared against A and C phase excitation currents.
Because of such high excitation current, it was only possible to perform the test at 5 kV to avoid test instrument tripping out.
51
Advanced Diagnostics
FRA test was performed to do advanced diagnostics.
No baseline results or similar transformer traces were available to compare the traces.
The three phases were compared against each other to perform the diagnosis.
54
Analysis
IEEE guide recommendation for comparing FRA short circuit results with DC winding resistance tests states that if the short-circuit test produces a horizontal response at frequencies, less than 30 Hz, then the FRA results can be compared to the DC winding resistance results.
Any differences between phases at these low frequencies should be checked with a DC winding resistance test.
This analysis supports the questionable readings obtained in winding resistance test.
56
Analysis
B phase trace which usually have a distinct pattern and offset throughout the low frequency region up to 1 kHz showed a cross over point where it crossed A and C phase traces. This kind of response is unusual and typically not expected.
58
Analysis
The IEEE guide explains that Delta connected windings will usually show two further resonances spaced apart in frequency range from 20Hz to 5 kHz. In the HV winding open circuit test results for A and C phases, the two resonances as described in guide were missing.
When analyzing the minima (anti resonance) in low frequency region, A phase minima was attenuated, smoothing the sharpness of parallel LC resonance.
On analyzing the low side open circuit traces, A and C phases matched very closely in low frequency region, however the B phase showed great amount of resonance shift and attenuation.
59
Conclusion
FRA Short circuit results confirmed the problem identified with the winding resistance test.
In the absence of baseline measurements, when the three phases open circuit results were compared, a lot of anomalies were found that indicated problem related to core and windings.
FRA trace characteristics analysis helped in confirming the questionable readings obtained from other electrical tests.
Transformer was in service for more than 50 years therefore it was decided to retire the transformer to avoid any possible future catastrophic failure.
60
Case Study 2 History
A 66 MVA 115/34.5 kV Autotransformer without tertiary showed an increase in winding capacitance to ground of 7% in scheduled maintenance test. DGA analysis showed high levels of hydrogen gas and ethane.
It was informed that transformer saw a full short circuit fault because of B phase explosion of three phase station service transformer connected to the low side bus of the auto transformer.
It was decided to perform FRA tests as per IEEE guidelines
61
FRA Test on Similar Transformer
In the absence of baseline measurements, the three phases were analyzed together.
The comparison between the phases was inconclusive.
It was decided to perform the FRA test on sister autotransformer 2 in the same substation. Both the auto transformers had similar nameplate information and serial numbers were consecutive.
65
Analysis
FRA trace comparisons between respective phases of two auto transformers showed a lot of symmetry for A and C phases with some curve mismatch in mid to high frequencies
Phase B comparison showed shift in resonance, change in magnitude and loss of resonances in frequency range from 200 Hz to 600 kHz
Phase B traces from two transformers were further compared in narrow frequency bands of 20 Hz -10 kHz and 5 kHz -100 kHz
66
FRA Low Frequency Region Analysis (20 Hz -10 kHz)
Comparison of B phase of autotransformers 1 and 2, low frequency area of 20 Hz – 10 kHz
67
FRA Low Frequency Region Analysis (20 Hz -10 kHz)
Core magnetization can affect the results in this region. However, no shift and change in magnitude (in lower portion of this frequency range), which rules out a core magnetization problem.
It is easy to see change in primary resonance between the two traces. This shift could indicate problems associated with core defects like shorted or burnt laminations, disconnected core ground or unintentional core grounds and joint dislocations.
68
FRA Low-Mid Frequency Region Analysis (5 kHz -100 kHz)
Comparison of B phase of autotransformers 1 and 2, low frequency area of 5 kHz – 100 kHz
69
FRA Low-Mid Frequency Region Analysis (5 kHz -100 kHz)
In this frequency band, multiple resonance shifts in broad frequency range can be observed. Additionally, some change in magnitude and loss of resonances were noticed as well.
Traces exhibiting these symptoms could indicate problems associated with winding movement and in particular axial deformation.
70
Conclusion
Based upon the FRA comparison of two auto transformers, it was determined that there has been some winding deterioration and movement in B phase of auto transformer 1. Other components of the transformer may have been affected as well.
FRA analysis strengthened the conclusion drawn by other electrical tests performed on the transformer.
Based upon the analysis, the transformer has been put under watch list with oil samples taken every 3 months and scheduled maintenance testing reduced from eight years to one year.
Decision on when to replace the transformer would be taken based upon DGA analysis and scheduled maintenance test results in coming time.
72
Recommendation on Best Field Practices
Instrument Validation • The test equipment should always be checked for its
performance and validity using the supplied test leads before initiating the FRA test on a specimen.
• Cigré recommends running integrity verification with an object
of a known response . A standard test object is usually offered by the test equipment manufacturer.
• In the absence of that, as an alternative, self check can be performed by shorting the test leads together, the user should expect a zero dB response.
74
Core Residual Magnetism
Core’s residual magnetism can affect the FRA response in lower frequency region up to 2 kHz.
It is advisable to demagnetize the transformer before performing the FRA test.
In the field, if resources are not available to demagnetize the transformer, it is recommended to perform FRA test before the dc winding resistance to minimize the effect of residual magnetism on FRA results.
75
Test Voltage
Applied test voltage can affect the FRA response in the lower frequency region up to 10 kHz.
It is recommended to use same test voltage used for obtaining baseline results or when comparing traces between similar transformers.
76
Connections
Transformer configuration will vary
from one specimen to the other.
Placement of source and measuring leads need to be consistent and follow a set procedure.
IEEE guide recommends to connect from head (source) to tail (measuring) of the vector for any phase measurement.
77
Connections and Documentation
It is recommended to connect leads directly to the bushing
terminals. In the FRA tests where shorting leads are used it is advisable to use shortest possible shorting leads and they should be isolated from ground.
It is advisable to document as much as information as possible like manufacturer and serial number of transformer, vector configuration, test instrument used, operator, tap position, pictures of transformer, testing, shorting and grounding leads and other relevant information
78
Measurement Settings
It is advisable to have less measurement points (50 per decade) in lower frequency region and as frequency increases, more measurement points per decade are added (200 per decade in highest frequencies).
It provides the desired resolution and accuracy both in low and high frequency regions.
79
Tap Changer Position
To obtain repeatable results, use the same tap position for each comparison test. It is recommended to use in service tap for DETC and extreme raise position for LTC
If nominal tap is to be used for
LTC, it is recommended to note down the previous tap position before nominal.
80
Grounding Technique It is very important to apply the same grounding practices each time to
obtain consistent and repeatable results.
“Shortest possible ground” technique provides the source and measuring leads the closest ground (reference) point with shortest length of ground braid.
Inconsistent grounding practice can greatly affect the high frequency region of the FRA trace.
Effective use of flat braid ground wire
83
Summary of IEEE FRA guide and recommendations from other
standards provide the tools to perform the measurements correctly and interpret the FRA results to detect any defects in mechanical integrity associated with windings, core and other components of a transformer.
FRA failure mode analysis assists in narrowing down the type of problem and related faulty section of the transformer.
The case studies and its analysis based upon failure mode characteristics provide techniques and process to identify issues and utilize FRA measurements for advanced diagnosis.