full service - electric fire pump controllers · 2016.dec.01 14:09:55 cut-in cut-out 150 100 monday...

4
Standard Features ViZiTouch V2 operator interface NEMA 2 assembly Pressure and event recorder Voltage and amperage display Single operator for both isolating switch and circuit breaker Surge arrestor Lifting lugs Run test push button Available with automatic power transfer switch Emergency start handle Start and stop pushbuttons Locked rotor protector Phase reversal indication Remote start / deluge valve start provision Pressure transducer and run test solenoid valve externally mounted Gland plate Audible alarm Alarm contacts for remote indication Available with full voltage and reduced voltage starting GPx Series Full Service - Electric Fire Pump Controllers LISTEN DEVELOP LEAD 2018-2019 OPTIONAL

Upload: others

Post on 15-May-2020

2 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Full Service - Electric Fire Pump Controllers · 2016.Dec.01 14:09:55 Cut-in Cut-out 150 100 Monday Week. Test Auto. Shutdown (m) Date and time RUN TEST User login Duration (min)

Tornatech Inc, Montreal, Quebec, Canada

LISTEN DEVELOP LEAD

Standard Features• ViZiTouch V2 operator interface• NEMA 2 assembly• Pressure and event recorder• Voltage and amperage display• Single operator for both isolating switch and circuit breaker• Surge arrestor• Lifting lugs• Run test push button• Available with automatic power transfer switch• Emergency start handle• Start and stop pushbuttons• Locked rotor protector• Phase reversal indication• Remote start / deluge valve start provision• Pressure transducer and run test solenoid

valve externally mounted• Gland plate• Audible alarm• Alarm contacts for remote indication• Available with full voltage and reduced

voltage starting

GPx SeriesFull Service - Electric Fire Pump Controllers

LISTEN DEVELOP LEAD

2018-2019 OPTIONAL

Page 2: Full Service - Electric Fire Pump Controllers · 2016.Dec.01 14:09:55 Cut-in Cut-out 150 100 Monday Week. Test Auto. Shutdown (m) Date and time RUN TEST User login Duration (min)

— G

PX

GPA MODEL SHOWN

1. Alarm bell2. Externally mounted pressure transducer

and run test solenoid valve with protective cover

3. Lifting Lugs4. ViZiTouch V2 operator interface5. Exterior USB Port

(Interior USB port also supplied)6. Custom designed Isolation switch /

Circuit breaker operator handle

GPW + GPU MODEL SHOWN

1

2

4

6

5

7

3

8

9

10

11

7. Key lock8. Remote alarm contacts with removable

terminals9. Surge arrestor10. Custom designed emergency start

mechanism with integrated limit switch11. Gland plate12. Automatic power transfer switch

Page 3: Full Service - Electric Fire Pump Controllers · 2016.Dec.01 14:09:55 Cut-in Cut-out 150 100 Monday Week. Test Auto. Shutdown (m) Date and time RUN TEST User login Duration (min)

— G

PX

ViZiTouch V2 Operator Interface

HOME SCREEN

Electric Fire Pump Controller

Home 53C06:45:342016.Dec.01

Non pressure actuated Automatic controller Automatic shutdown

N2

N3

N1

A2

A3

A1

480 V 480 V

480 V

0 V0 V

0 V

480 V 480 V

480 V

23.4A

23.4A

23.4A

MANUAL

0

300

System

70PSI

90110

0

300

System

Home 26C13:34:102016.Dec.01

Pressure actuated Non automatic controller Automatic shutdown

L2

L3

L1480 V 480 V

480 V

23.4A

23.4A

23.4A

90

150

70PSI

Electric Fire Pump Controllerwith Automatic Transfer Switch

0

300

System

Home 26C13:34:102016.Dec.01

Pressure actuated Non automatic controller Automatic shutdown

L2

L3

L1480 V 480 V

480 V

23.4A

23.4A

23.4A

90

150

70PSI

VIZITOUCH V2 MAJOR FEATURES INCLUDE:

• Touch screen operation with 7” color display and intuitive graphics

• Multi-language• Upgradable software• Password protected

ConfigHome 26C14:34:282016.Dec.01

Pressure

Periodic test

Advanced

PSI

PT1

Duration (min)

14:09:552016.Dec.01

Cut-in

Cut-out 150

100

Monday

Week. Test

Auto. Shutdown (m)

Date and time

RUN TEST

User login

Duration (min) 10

Duration (min) 10

30

5

7

Max. Pres. 300

2

EventsHistory 26°C14:34:282016.Dec.01

2016.12.01

2016.12.01 Under Voltage: ACTIVE

Under Voltage INACTIVE

2016.12.01 Alarms Reset

2016.12.01

2016.12.01

2016.12.01

2016.12.01

2016.12.01

2016.12.01

2016.12.01

14:28:23

14:28:52

14:28:09

14:09:55

14:11:22

14:03:11

14:08:46

14:03:03

14:12:06

14:28:08 ACB in OFF or Tripped: INACTIVE

Alternate is Tripped/Open: INACTIVE

Control Voltage not Healthy: ACTIVE

Generator: Started

Motor: Started in Automatic

Loss of Power: ACTIVE

Pump On Demand: INACTIVE

ServiceHome 26C14:33:062016.Dec.01

Last service date

Commissionning date

Service interval

Nameplate Information

Jockey pump cut-in

Live view

Jockey pump cut-out

Complete service

Next service due

2016.12.01 14:28:52

2016.12.01 14:28:52

1 year

130

2016.12.01 14:28:52

110

[email protected]

+ 65 6795 8114+ 65 6795 7823

ASIA

+ 32 (0) 1084 4001EUROPE

+ 1 800 363 8448+ 514 334 0523

AMERICAS

+ 971 (0)4 887 0615MIDDLE EAST

Pressure CurvesHistory 26°C14:37:172016.Dec.01

150

120

90

60

30

0

2016.02.2314:24:05

2016.02.2314:25:05

1m 5m 20m 1h 2h 3h 4h 5h 6h 12h 1d 2d 3d 4d 5d 6d 1w 2w

StatisticsFirst Service StatisticsStatistics 26C14:34:282016.Dec.01

First Service Statistics

From

2016.12.01Since

2016.12.01

14:28:09

20

0-00-08-57

14:08:46

99.1 PSI

61-04-08-27On Time

Motor

Start Count

Last Started On

Pressure

Minimum

On Time

SETTINGS

HISTORY/STATISTICS

EVENTS

SERVICE

PUMP CURVES PRESSURE CURVES

ON-SCREEN MENU

Home

Alarm

Configuration

History

Service

Manual

Languages

Pump CurvesHistory 26°C14:37:172016.Dec.01

P

90

68

45

23

01075538 1613 2150 Q 2016.02.23

14:25:05

PMS 295 PMS 361 Noir

®

Page 4: Full Service - Electric Fire Pump Controllers · 2016.Dec.01 14:09:55 Cut-in Cut-out 150 100 Monday Week. Test Auto. Shutdown (m) Date and time RUN TEST User login Duration (min)

Model Voltage HP Short Circuit Withstand Rating

Seismic Certified

GPA GPA+GPU

GPP GPP+GPU

GPY GPY+GPU

200V - 208V5-150 100kA Yes

200 50kA No

220V - 240V5-200 100kA Yes

250 50kA No

380V - 416V5-300 100kA Yes

350-450 50kA No

440V - 480V

5-400100kA

Yes

450No

50050kA

575V - 600V 5-500 Yes

GPR

GPR+GPU

GPW

GPW+GPU

200V - 208V5-150 100kA Yes

200 50kA No

220V - 240V5-200 100kA Yes

250 50kA No

380V - 416V5-300 100kA Yes

350-450 50kA No

440V - 480V

5-400100kA

Yes

450No

50050kA

575V - 600V 5-500 Yes

Model Voltage HP Short Circuit Withstand Rating

Seismic Certified

GPS GPS+GPU

200V - 208V

5-100100kA

Yes

150No

200 50kA

220V - 240V

5-150100kA

Yes

200No

250 50kA

380V - 416V

5-250100kA

Yes

300

No350-450 50kA

440V - 480V

5-300

100kA

Yes

350

No400

450

500

50kA575V - 600V

5-400 Yes

450No

500

GPX SERIES / VOLTAGE / HP / SHORT CIRCUIT WITHSTAND RATING / SEISMIC CERTIFICATION

GPx-SBRO-004-E Rev.0.1

AMERICAS

Tornatech Inc.

Head Office

Laval, Quebec, Canada

Tel: + 1 514 334 0523

Toll free: + 1 800 363 8448

MIDDLE EAST

Tornatech FZE

Dubai, United Arab Emirates

Tel: + 971 (0)4 887 0615

ASIA

Tornatech Pte Ltd.

Singapore

Tel: + 65 6795 8114

Tel: + 65 6795 7823

EUROPE

Tornatech Europe SPRL

Wavre, Belgium

Tel: + 32 (0) 10 84 40 01

HOW TO ORDER: GPx - V / HP / Ph / Hz / Options

Ex.: GPA - 208 / 30 / 3 / 60 / Options