fume handling 400-409beckton.yolasite.com/resources/mech_lit/vent axia bif250...quality assurance to...
TRANSCRIPT
-
404
m3/s at Pa
B I F U R C A T E D A X I A L F L O W F U M E H A N D L I N GP E R F O R M A N C E C U R V E S
V E N T - A X I A B I F U R C A T E D A X I A L F L O W F U M E H A N D L I N G F A N S ( B I F )
B I F U R C A T E D A X I A L F U M E H A N D L I N G U N I T S (B
IF)
405
✔ Manufactured from UV stabilisedpolypropylene.
✔ Motor mounted outside the airstream.
✔ Suitable for extracting aggressivecorrosive air.
✔ Internal or external mounting.
✔ Quality Assurance to BS EN ISO 9001.
✔ Performance tested to BS 848 Part 1.
A X I A L F L O W F U M E H A N D L I N G B I F U R C A T E DF A N SA range of axial flow bifurcated fansdesigned to complement the centrifugalfume handling units we offer, andwithstand the rigours of fume extractionsystems. Features high performanceaxial flow fans and powerful highquality motors built to withstand hostileenvironments
S P E C I F I C A T I O NCasingsThe fan casing is constructed in heavygauge polypropylene UV stabilised withthe bore specially engineered to providea tight clearance fit. It is complete withdrilled flanges at each end to which,either ducting can be directlyconnected (adequately supported) or,matching flanges with flexibleconnectors.
M O T O R A N D I M P E L L E RA high performance aerofoil sectionaxial-flow impeller in durablepolypropylene statically and dynamicallybalanced. Driven through an extensionshaft by a totally enclosed, fan cooledsingle speed motor to BS 5000/99 outof the airstream and is wound to suitstandard UK voltages all complete withterminal box (and capacitor on singlephase types).
E L E C T R I C A LThe BIF range is available for either single phase 220-240V 50 Hz capacitor start and run or three phase380-415V 50Hz.
T E R M I N A L B O XAn IP54 terminal box is supplied withall models with 20mm and PGII entryoffering protection against dust andwater jets from any angle.
P E R F O R M A N C EThe fan performance, is in accordancewith tests to BS848 Part 1.
S O U N D L E V E L SFan sound levels, measured in areverberant chamber in accordancewith BS 848 Part 2. Published dB(A)figures are free field sound pressurelevels at 3m with spherical propagationat a reference level of 2 x 10–5Pa (20micro-Pascal). The sound power levelspectra figures are dB with a referencelevel of 10–12 Watts (1 pico-watt). Toensure minimum noise levels duringspeed control, an auto transformerspeed control is recommended.
A C C E S S O R I E SA full range of accessories is availablewith the Fume Handling BifurcatedFans:
D.O.L. Starters
Flexible Connections
Mounting Feet
Coupling Flanges
Anti-Vibration Mounts
Attenuators
Stock S.C F.L.C.
Ref. No. Motor r.p.m FID 25 50 75 100 150 200 kW Amps Amps dBA @ 3m
BIF250/4/1 1 phase 1400 0.235 0.172 - - - - - 0.18 7.0 1.35 49
BIF250/2/3 3 phase 2800 0.470 0.442 0.404 0.376 0.338 0.244 - 0.37 4.0 0.93 67
BIF315/4/1 1 phase 14000.635 0.545 0.432 - - - -
0.25 10.0 1.90 55
BIF315/4/3 3 phase 1400 0.37 4.73 1.20 55
BIF315/2/3 3 phase 2800 1.222 1.208 1.175 1.152 1.109 0.997 0.870 0.55 6.6 1.32 71
BIF400/4/1 1 phase 14001.363 1.269 1.157 1.015 0.804 - -
0.37 14.0 2.70 61
BIF400/4/3 3 phase 1400 0.37 4.73 1.20 61
N E W
Diameter 63 125 250 500 1k 2k 4k 8k
BIF250/4 66 67 66 65 65 62 58 54
BIF250/2 81 82 81 80 80 77 73 69
BIF315/4 72 74 73 72 71 68 64 61
BIF315/2 87 89 93 87 86 83 79 76
BIF400/4 76 77 80 75 75 72 68 64
S O U N D D A T ASound Power Level Spectra db (ref 10–12) Watts
Electrical Supply: Single phase motors are wound for 220-240V/50Hz/1ph AC supply and 3 phase motors are wound for 380-415V/50Hz/3ph
AC supply.
NB. Motors must have overload protection and 3 phase motors should also have single phasing prevention.
-
B I F U R C A T E D A X I A L F L O W F U M E H A N D L I N G F A N SD I M E N S I O N S ( mm )
406
B I F U R C A T E D A X I A L F U M E H A N D L I N G U N I T S (B
IF)
407
V E N T - A X I AB I F U R C A T E D A X I A L F L O W F U M E H A N D L I N G F A N SA C C E S S O R I E S
P E R F O R M A N C E C U R V E S
0
STAT
IC P
RES
SUR
E
Pa 250
0
AIR VOLUME
0.2 0.4 0.6 0.8 1.0 1.2 1.4 m3/s
25
50
75
100
125
150
175
200
225
1 2 3 45
Size 250/4 250/2 315/4 315/2 400/41 2 3 4 5
Size a b c d e f g
250 250 600 400 325 290 8 off 8
315 315 650 480 400 360 16 off 9
400 400 800 620 500 455 16 off 9
c o
utsi
de d
ia.
d d
ia
e p
cd
a d
ia.
b overall
f No. g dia. holes
AIRFLOW
Ancillaries: Flexible connectors, AV’s, mounting feet and silencers are available
Set ofD.O.L. Mounting Feet Matching Flexible Mounting
Starter & Coil (Pair) Flange Connections Feet & AV'sStock Ref. No. Stock Ref. No. Stock Ref. No. Stock Ref. No. Stock Ref. No. Stock Ref. No.
BIF250/4/1 103 11 240 + 103 12 018BIF250FT BIFMF250 BIF250FC AVM220
BIF250/2/3 103 11 415 + 103 12 018
BIF315/4/1 103 11 240 + 103 12 027
BIF315/4/3 103 11 415 + 103 12 018 BIF315FT BIFMF315 BIF315FC AVM220
BIF315/2/3 103 11 415 + 103 12 018
BIF400/4/1 103 11 240 + 103 12 040BIF400FT BIFMF400 BIF400FC AVM220
BIF400/4/3 103 11 415 + 103 12 018
-
118 119
B I F U R C A T E D C A S E A X I A L F A N S ( B I F )
B I F U R C A T E D C A S E A X I A L F A N W I R I N G D I A G R A M S
V E N T - A X I AB I F U R C A T E D C A S E A X I A L F A N W I R I N G D I A G R A M S
BIF 250/2/3/8-32˚BIF 315/2/3/8-32˚BIF 400/2/3/8-28˚
BIF 250/4/3/8-32˚BIF 315/4/3/8-32˚BIF 400/4/3/8-32˚BIF 500/4/3/8-30˚BIF 630/4/3/8-26˚
BIF 250/2/3/8-32˚BIF 315/2/3/8-32˚BIF 400/2/3/8-28˚
BIF 250/4/3/8-32˚BIF 315/4/3/8-32˚BIF 400/4/3/8-32˚BIF 500/4/3/8-30˚BIF 630/4/3/8-26˚
THREE PHASE FANCONNECTED TO A 415V COIL D.O.L. STARTER
THREE PHASE FANCONNECTED TO A 240V COIL D.O.L. STARTER
415 Volt D.O.L. StarterA suitable sized
overload relay must befitted to provide motor
protection.
N.B. Links betweenterminals 5 to 95 and 24
to 96 must be fitted.
V2
W1
FAN TERMINAL
W2
U1
U2
V1E
3 Phase Supply(380-415V 50Hz).
L3
1 3 5
2 4 6
L1 L2
95
96
E
A2
23
24
E
A1 E
240 Volt D.O.L. StarterA suitable sized
overload relay must befitted to provide motor
protection.
N.B. Links betweenterminals 5 to 95 and 24
to 96 must be fitted.
L2L1 L3
V2
W1
FAN TERMINAL
W2
U1
U2
V1
3 Phase Supply(380-415V 50Hz).
L3
51 3
2 64
L1 L2
95
96
E
A2
23
24
EN
A1 E
E
L2L1 L3
3 Phase Supply(380-415V 50Hz).STAR / DELTA Starter with current overload
protection and a 415 volt coil.
STAR / DELTASTARTER
N.B. Links between terminals 1 toA1, 5 to 95 must be fitted and thelink between terminals 24 to 96
must be FITTED.
415 Volt D.O.L. StarterA suitable sized
overload relay must befitted to provide motor
protection.
THREE PHASE FANCONNECTED TO A STAR / DELTA STARTER
THREE PHASE FANCONNECTED TO A 415V COIL D.O.L. STARTER & A 1.4, 4.0,
7.0 OR 11.0 AMP AUTO TRANSFORMER CONTROLLER
E
FAN TERMINAL
BIF500/2/3/18-26˚ BIF 800/4/3/8-18˚
W2
U2
V2
U1
V1
W1
2 4 6
24
A2
23
96
95
A1
E
4
3
2
1
6
5
L2L1 L3
E
NOTE: If a Auto Transformer is beingused to control the fan speed, the
manual reset facility must be disabled.Contact Vent-Axia's Technical
Support line for details.
TK
3 Phase AutoTransformer
Speed Controller.
103 14 311103 14 307103 14 304103 14 301
BIF 250/4/3/8-32˚BIF 315/4/3/8-32˚BIF 400/4/3/8-32˚BIF 500/4/3/8-30˚BIF 630/4/3/8-28˚
V2
W1
U1
FAN TERMINAL
W2
U1
U2
V1
W1TK V1
E
L3N L1L2
E
E E
A1
A2
23
242 4
1 3
6 96
5
95
3 Phase Supply(380-415V 50Hz).
N L1 L2 L3 E
E
-
120 121
B I F U R C A T E D C A S E A X I A L F A N S ( B I F )
B I F U R C A T E D C A S E A X I A L F A N W I R I N G D I A G R A M S
V E N T - A X I AB I F U R C A T E D C A S E A X I A L F A N W I R I N G D I A G R A M S
THREE PHASE FANSINGLE PHASE IN - THREE PHASE (240V) OUT
LC FAN CONNECTED TO AN INVERTER SPEED CONTROLLERKIT (103 20 101)
THREE PHASE FANSINGLE PHASE IN - THREE PHASE (240V) OUT
LC FAN CONNECTED TO AN INVERTER SPEED CONTROLLERKIT (103 20 102 OR 103 20 103)
E
FAN TERMINAL
U2 V2W2
U1 V1 W1
Shielding(WRAP WITH INSULATION TAPE).Connector
Shielding(WRAP WITH INSULATION TAPE DO NOTCONNECT TO THE EARTH TERMINAL).
Shielded Cable
RELAY
NE ~L
1 Phase Supply(220 - 240V).
E
Metal Enclosure &Wiring by others.
Inverter455552
User FanSpeed Controller
ILVC 1(103 20 601)
Ferrite Coil(Loop the fan supply cable around
the ferrite coil 3 times).
L2(N)
L1(L) P R
12VFW RE SP RS
T3(W)
T2(V)
T1(U)
Vi10V 0V FM10VFW 12V Vi 0V
3 PHASE SUPPLY(230 - 240 Volts)
FAN TERMINAL
U2 V2W2
U1 V1 W1
Shielding(WRAP WITH INSULATION TAPE).
Connector
Shielding(WRAP WITH INSULATION TAPE DO NOTCONNECT TO THE EARTH TERMINAL).
Shielded Cable
RELAY
NE ~L
1 Phase Supply(220 - 240V).
E
Metal Enclosure &Wiring by others.
Ferrite Coil(Loop the fan supply cable around
the ferrite coil 3 times).
L2L1(L) P R
12VFW RE SP RS
T3(W)
T2(V)
T1(U)
Vi10V 0V FM10VFW 12V Vi 0V
10 Volt D.C. (up to a maximum distance of 50mfrom the Inverter to the speed controller.
3 PHASE SUPPLY(230 - 240 Volts)
Inverter455553 or455554
L3(N)
User FanSpeed Controller
ILVC 1(103-20-601)
E
BIF 250/2/3/8-32˚BIF 315/2/3/8-30˚
BIF 250/4/3/8-32˚BIF 315/4/3/8-32˚BIF 400/4/3/8-32˚
BIF 500/4/3/8-32˚BIF 630/4/3/8-26˚
BIF 400/2/3/8-22˚
10 Volt D.C. (up to a maximum distance of 50mfrom the Inverter to the speed controller.
BIF 500/2/3/8-20˚
50m Maximum Distance
(shielded cable required).from the Inverter to the Fan
50m Maximum Distance
(shielded cable required).from the Inverter to the Fan
THREE PHASE FANTHREE PHASE IN - THREE PHASE OUT
BIFURCATED AXIAL FAN CONNECTED TO AN INVERTERSPEED CONTROLLER KIT
(103 20 301, 103 20 302, 103 20 303 OR 103 20 305)
THREE PHASE FANTHREE PHASE IN - THREE PHASE OUT
BIFURCATED AXIAL FAN CONNECTED TO ANINVERTER SPEED CONTROLLER KIT
(103 20 350)
E
FAN TERMINAL
BIF 250/2/3/8-32˚BIF 315/2/3/8-30˚BIF 400/2/3/8-22˚
BIF 250/4/3/8-32˚BIF 315/4/3/8-32˚BIF 400/4/3/8-32˚BIF 500/4/3/8-32˚BIF 630/4/3/8-26˚
U2 V2W2
U1 V1 W1
L3L2L1 E
Filter103 20 505103 20 512
3 Phase Supply(380-415V 50Hz)
L1 EL3L2
L1 L3L2 E
Connector
50m Maximum Distance fromthe Inverter to the Fan
(shielded cable required).
Shielding(WRAP WITH INSULATION TAPE DO NOT
CONNECT TO THE EARTH TERMINAL).
Shielded Cable
Shielding(WRAP WITH INSULATION TAPE).
Ferrite Coil(Loop the fan supply cable around
the ferrite coil 3 times).
+15V
VIN
Metal Enclosure &Wiring by others.
Inverter455556, 455557, 455558
or 103 20 303
E
3SC
E 2
1
64
5
8
7
User FanSpeed Controller
ILVC 2(103 20 602)
AO2
DOGGNDGND
AIN AUX
AO1
DO2DO1 A(+)IP12
E IG12
A(-)
S(+) S(-)
81 6 1110
R S T VB1/RB1/P- UB2 RAW RB RC
E
FAN TERMINAL
U2 V2W2
U1 V1 W1
L3L2L1 E
Filter103 20 512
3 Phase Supply(380-415V 50Hz)
L1 EL3L2
L1 L3L2 E
Connector
50m Maximum Distance fromthe Inverter to the Fan
(shielded cable required).
Shielding(WRAP WITH INSULATION TAPE DO NOT
CONNECT TO THE EARTH TERMINAL).
Shielded Cable
Shielding(WRAP WITH INSULATION TAPE).
Ferrite Coil(Loop the fan supply
cable around the ferritecoil 3 times).
+15V
VIN
Metal Enclosure &Wiring by others.
Inverter455559
E
3SC
E 2
1
64
5
8
7
User FanSpeed Controller
ILVC 2(103 20 602)
AO2
DOGGNDGND
AIN AUX
AO1
DO2DO1 A(+)IP12
E IG12
A(-)
S(+) S(-)
81 6 1110
10 Volt D.C. (up to a maximum distance of 50mfrom the Inverter to the speed controller.
R S T VB1/RB1/P- UB2 RAW RB RC
BIF 500/2/3/8-20˚
BIF 800/4/3/8-18˚
10 Volt D.C. (up to a maximum distance of 50mfrom the Inverter to the speed controller.
-
102
B I F U R C A T E D C A S E A X I A L F A N S ( B I F )
103
B I F U R C A T E D C A S E A X I A LF A N SThe Bifurcated Case Axial range hasbeen specifically developed to meet theneed for an axial fan which can handle atmospheres normallydetrimental to the life of the fan motor.
By isolating the motor from the systemairstream, the bifurcated fan can handle awide variety of saturated and dust-ladenatmospheres, heated air and hot gases.
The range has a split airway with adirect driven motor operating inambient air within the motorcompartment. They are suitable, asstandard, for handling air temperaturesup to +200˚C.
M O T O R SThe motors are specially selected tooperate within the motor compartmentwith the airstream in the duct system, atan elevated temperature.
Motors are of the B3 foot mountingtype, totally enclosed and fan cooled.
Being foot mounted the motors can, inthe event of a failure, be readilyinterchanged with a comparable framesize from a wide range of manufacturersto cover temperatures of up to 200˚C.
The motor is suitable for speed controlby either an inverter or a 5-step autotransformer speed controller when theambient air temperature is not higherthan 60˚C.
E L E C T R I C A LSingle phase 220-240V/50 Hz supplyare available in two sizes 250 and 315dia. in either 2 or 4 pole versions.Three phase 380-440V/50Hz supply areavailable in six sizes 250, 315, 400,500, 630 and 800 dia. in either 2 or 4pole versions (630 and 800 dia areavailable as 4 pole).
I M P E L L E R S A N DC A S I N GThe aluminium alloy impellers are diecast and have an adjustable pitch whichallows a wide range of air outputs to be selected. All the casings aremanufactured in steel and hot dippedgalvanised to BS EN ISO 1461 afterfabrication. Motor mountings andfixings used in the assembly of the fanare zinc plated and passivated.
F O R M O F R U N N I N G
Bifurcated fans have arrows showingthe direction of the impeller rotationand airflow. Ex-stock models are FormB running.
T E R M I N A L B O XTo IP55, protected against dust andwater jets from any angle, allowingoutside applications.
P E R F O R M A N C E Tested to BS 848 Part 1 & 2. PublisheddB(A) figures are free field soundpressure levels at 3m with sphericalpropagation at a reference level of 2 x10–5Pa (20 micro-Pascal). The inlet andoutlet sound power level spectra figuresare dB with a reference of 10–12 Watts (1 pico-watt).
C O O L I N GExternal cooling is provided by a fanmounted at the non-drive end of themotor, protected by a cover with a gridair intake. The airflow, guided by thefan cover, is directed longitudinally onthe entire periphery of the motor in thechannels formed by the frame ribs.
Adequate space is provided within themotor compartment to ensure a plentifulsupply of cooling air. The air within themotor compartment must not exceed40˚C. For ambients in excess of this,please consult our Technical ServicesDepartment for further information.
✔ Sizes 250 to 800 dia.
✔ Motors protected to IP55.
✔ Motor insulation Class ' F ' .
✔ Maximum ambient temperature 200˚C.
✔ Speed controllable via transformer orinverter (when the ambient airtemperature is not higher than 60˚C).
✔ IP55 terminal box.
✔ Suitable for relative humidity levels up to95% R.H.
✔ Manufactured to BS EN ISO 9001.
✔ Performance tested to BS 848 parts 1, 2and ISO 5801.
✔ 2 Year Guarantee.
V E N T - A X I A B I F U R C A T E D C A S E A X I A L F A N S ( B I F ) B I F U R C A T E D C A S E A X I A L F A N S
P E R F O R M A N C E G U I D E
Air Flow.(B Form).
2 POLEm3/s at Pa
Pitch dBA Dia. Phase Pole Angle 0 25 50 75 100 125 150 175 @ 3m
BIF 250 / 1 or 3 / 2 / 8˚ 0.27 0.25 0.23 0.22 0.21 0.19 0.17 0.16 58BIF 250 / 1 or 3 / 2 /10˚ 0.29 0.28 0.26 0.25 0.23 0.22 0.21 0.19 58BIF 250 / 1 or 3 / 2 /12˚ 0.32 0.31 0.29 0.28 0.26 0.25 0.23 0.20 58
BIF 250 / 1 or 3 / 2 /14˚ 0.35 0.33 0.32 0.30 0.29 0.28 0.26 0.23 58BIF 250 / 1 or 3 / 2 /16˚ 0.37 0.36 0.34 0.32 0.31 0.29 0.28 0.25 58BIF 250 / 1 or 3 / 2 /18˚ 0.40 0.38 0.37 0.35 0.34 0.32 0.31 0.28 58BIF 250 / 1 or 3 / 2 /20˚ 0.42 0.40 0.39 0.38 0.36 0.34 0.33 0.31 58BIF 250 / 1 or 3 / 2 /22˚ 0.44 0.43 0.41 0.40 0.38 0.37 0.35 0.33 58BIF 250 / 1 or 3 / 2 /24˚ 0.47 0.45 0.43 0.42 0.40 0.39 0.37 0.35 58BIF 250 / 1 or 3 / 2 /26˚ 0.49 0.47 0.46 0.44 0.42 0.40 0.39 0.37 58BIF 250 / 1 or 3 / 2 /28˚ 0.51 0.49 0.48 0.46 0.44 0.43 0.41 0.38 58BIF 250 / 1 or 3 / 2 /30˚ 0.54 0.52 0.50 0.48 0.47 0.45 0.43 0.40 58BIF 250 / 1 or 3 / 2 /32˚ 0.55 0.53 0.51 0.49 0.48 0.46 0.44 0.42 58
Pitch dBADia. Phase Pole Angle 0 50 100 150 200 250 300 @ 3m
BIF 315 / 1 or 3 / 2 / 8˚ 0.54 0.48 0.46 0.42 0.38 0.34 66BIF 315 / 1 or 3 / 2 / 10˚ 0.58 0.55 0.51 0.48 0.44 0.40 66BIF 315 / 1 or 3 / 2 / 12˚ 0.64 0.61 0.57 0.53 0.49 0.44 65BIF 315 / 1 or 3 / 2 / 14˚ 0.69 0.66 0.62 0.59 0.55 0.50 65BIF 315 / 1 or 3 / 2 / 16˚ 0.75 0.70 0.66 0.63 0.59 0.54 65BIF 315 / 1 or 3 / 2 / 18˚ 0.80 0.76 0.72 0.68 0.64 0.60 0.53 65BIF 315 / 1 or 3 / 2 / 20˚ 0.83 0.80 0.77 0.73 0.69 0.64 0.59 65BIF 315 / 1 or 3 / 2 /22˚ 0.88 0.84 0.80 0.77 0.73 0.69 0.64 65BIF 315 / 1 or 3 / 2 /24˚ 0.94 0.89 0.85 0.81 0.77 0.73 0.68 65BIF 315 / 1 or 3 / 2 / 26˚ 0.98 0.93 0.89 0.85 0.81 0.77 0.71 65BIF 315 / 1 or 3 / 2 / 28˚ 1.01 0.97 0.94 0.90 0.85 0.80 0.74 65BIF 315 / 1 or 3 / 2 / 30˚ 1.07 1.03 0.98 0.94 0.89 0.84 0.78 66
Pitch dBADia. Phase Pole Angle 0 100 200 300 400 450 @ 3m
BIF 400 / 3 / 2 / 8˚ 1.10 0.99 0.89 0.79 0.68 0.60 76BIF 400 / 3 / 2 / 10˚ 1.23 1.13 1.04 0.93 0.80 0.71 76BIF 400 / 3 / 2 / 12˚ 1.34 1.24 1.14 1.02 0.90 0.81 75BIF 400 / 3 / 2 / 14˚ 1.47 1.37 1.26 1.15 1.01 0.93 75BIF 400 / 3 / 2 / 16˚ 1.61 1.50 1.40 1.27 1.13 1.04 75BIF 400 / 3 / 2 / 18˚ 1.72 1.61 1.51 1.38 1.24 1.14 74BIF 400 / 3 / 2 / 20˚ 1.80 1.69 1.59 1.48 1.33 1.22 74BIF 400 / 3 / 2 / 22˚ 1.93 1.80 1.69 1.57 1.42 1.30 74
Pitch dBADia. Phase Pole Angle 0 100 200 300 400 500 600 700 @ 3m
BIF 500 / 3 / 2 / 8˚ 1.82 1.71 1.60 1.48 1.36 1.24 1.08 0.89 76BIF 500 / 3 / 2 / 10˚ 2.18 2.03 1.87 1.74 1.62 1.50 1.32 1.08 76BIF 500 / 3 / 2 / 12˚ 2.57 2.40 2.22 2.03 1.87 1.69 1.46 1.26 76BIF 500 / 3 / 2 / 14˚ 2.72 2.56 2.40 2.24 2.08 1.87 1.69 1.45 76BIF 500 / 3 / 2 / 16˚ 2.91 2.78 2.65 2.47 2.29 2.14 1.91 1.66 76BIF 500 / 3 / 2 / 18˚ 3.22 3.06 2.89 2.73 2.60 2.35 2.12 1.80 76BIF 500 / 3 / 2 / 20˚ 3.43 3.29 3.15 2.98 2.79 2.54 2.20 1.93 76
Red tabulations indicate a stock fan with a preset pitch angle. Black tabulations indicate the duty range of the preset fans in 2O
increment. The impellers will be factory set and dispatched within two days.
Rotation
-
104 105
B I F U R C A T E D C A S E A X I A L F A N S ( B I F )V E N T - A X I AB I F U R C A T E D C A S E A X I A L F A N SP E R F O R M A N C E G U I D E
B I F U R C A T E D C A S E A X I A L F A N SP E R F O R M A N C E G U I D E
4 POLEm3/s at Pa
Pitch dBADia. Phase Pole Angle 0 10 20 30 40 50 60 70 @ 3m
BIF 250 / 1 or 3 / 4 / 8˚ 0.14 0.12 0.11 0.10 0.08 42BIF 250 / 1 or 3 / 4 / 10˚ 0.15 0.13 0.12 0.11 0.10 42BIF 250 / 1 or 3 / 4 / 12˚ 0.16 0.15 0.14 0.13 0.11 42BIF 250 / 1 or 3 / 4 / 14˚ 0.17 0.16 0.15 0.15 0.12 42BIF 250 / 1 or 3 / 4 / 16˚ 0.19 0.17 0.16 0.15 0.13 42BIF 250 / 1 or 3 / 4 / 18˚ 0.20 0.19 0.17 0.16 0.15 42BIF 250 / 1 or 3 / 4 / 20˚ 0.21 0.20 0.19 0.17 0.16 42BIF 250 / 1 or 3 / 4 / 22˚ 0.22 0.21 0.20 0.18 0.17 42BIF 250 / 1 or 3 / 4 / 24˚ 0.23 0.22 0.21 0.19 0.18 42BIF 250 / 1 or 3 / 4 / 26˚ 0.24 0.23 0.22 0.20 0.19 42BIF 250 / 1 or 3 / 4 / 28˚ 0.25 0.24 0.23 0.21 0.20 42BIF 250 / 1 or 3 / 4 / 30˚ 0.27 0.25 0.24 0.22 0.21 42BIF 250 / 1 or 3 / 4 / 32˚ 0.28 0.26 0.25 0.23 0.22 42
Pitch dBADia. Phase Pole Angle 0 10 20 30 40 50 60 70 @ 3m
BIF 315 / 1 or 3 / 4 / 8˚ 0.27 0.25 0.23 0.22 0.21 0.19 0.17 0.15 50BIF 315 / 1 or 3 / 4 / 10˚ 0.29 0.28 0.26 0.25 0.23 0.22 0.20 0.19 50BIF 315 / 1 or 3 / 4 / 12˚ 0.32 0.31 0.29 0.28 0.26 0.25 0.23 0.20 49BIF 315/ 1 or 3 / 4 / 14˚ 0.35 0.33 0.32 0.30 0.29 0.28 0.26 0.23 49BIF 315 / 1 or 3 / 4 / 16˚ 0.37 0.36 0.34 0.32 0.31 0.29 0.28 0.25 49BIF 315 / 1 or 3 / 4 / 18˚ 0.40 0.38 0.37 0.35 0.34 0.32 0.31 0.28 49BIF 315 / 1 or 3 / 4 / 20˚ 0.42 0.40 0.39 0.38 0.36 0.34 0.33 0.30 49BIF 315 / 1 or 3 / 4 / 22˚ 0.44 0.43 0.41 0.39 0.38 0.37 0.35 0.33 49BIF 315 / 1 or 3 / 4 / 24˚ 0.47 0.45 0.43 0.42 0.40 0.39 0.37 0.35 49BIF 315 / 1 or 3 / 4 / 26˚ 0.49 0.47 0.45 0.44 0.42 0.40 0.39 0.37 49BIF 315 / 1 or 3 / 4 / 28˚ 0.51 0.49 0.48 0.46 0.44 0.43 0.41 0.38 49BIF 315 / 1 or 3 / 4 / 30˚ 0.54 0.52 0.50 0.48 0.47 0.45 0.43 0.40 50BIF 315 / 1 or 3 / 4 / 32˚ 0.55 0.53 0.51 0.49 0.48 0.46 0.44 0.41 50
Pitch dBADia. Phase Pole Angle 0 20 40 60 80 100 120 140 @ 3m
BIF 400 / 3 / 4 / 8˚ 0.55 0.50 0.46 0.43 0.38 0.34 0.27 61BIF 400 / 3 / 4 / 10˚ 0.62 0.58 0.54 0.50 0.45 0.40 0.33 60BIF 400 / 3 / 4 / 12˚ 0.67 0.63 0.59 0.55 0.50 0.45 0.38 60BIF 400 / 3 / 4 / 14˚ 0.74 0.70 0.65 0.61 0.56 0.50 0.44 59BIF 400 / 3 / 4 / 16˚ 0.80 0.76 0.72 0.68 0.62 0.56 0.50 59BIF 400 / 3 / 4 / 18˚ 0.86 0.81 0.77 0.73 0.68 0.62 0.54 59BIF 400 / 3 / 4 / 20˚ 0.90 0.86 0.81 0.77 0.73 0.66 0.57 58BIF 400 / 3 / 4 / 22˚ 0.97 0.91 0.87 0.82 0.77 0.71 0.62 58BIF 400 / 3 / 4 / 24˚ 1.01 0.96 0.92 0.87 0.82 0.75 0.65 58BIF 400 / 3 / 4 / 26˚ 1.05 1.00 0.95 0.90 0.85 0.78 0.70 58BIF 400 / 3 / 4 / 28˚ 1.09 1.04 0.99 0.94 0.89 0.83 0.74 58BIF 400 / 3 / 4 / 30˚ 1.12 1.07 1.02 0.98 0.93 0.86 0.76 58BIF 400 / 3 / 4 / 32˚ 1.14 1.10 1.06 1.01 0.95 0.89 0.79 58
Red tabulations indicate a stock fan with a preset pitch angle. Black tabulations indicate the duty range of the preset fans in 2O
increment. The impellers will be factory set and dispatched within two days.
4 POLEm3/s at Pa
Pitch dBADia. Phase Pole Angle 0 25 50 75 100 125 150 175 @ 3m
BIF 500 / 3 / 4 / 8˚ 0.91 0.86 0.80 0.74 0.68 0.62 0.54 0.45 60BIF 500 / 3 / 4 / 10˚ 1.09 1.01 0.94 0.87 0.81 0.75 0.66 0.54 60BIF 500 / 3 / 4 / 12˚ 1.29 1.20 1.11 1.01 0.94 0.84 0.73 0.63 60BIF 500 / 3 / 4 / 14˚ 1.36 1.28 1.20 1.12 1.04 0.93 0.84 0.73 60BIF 500 / 3 / 4 / 16˚ 1.46 1.39 1.33 1.23 1.14 1.07 0.95 0.83 60BIF 500 / 3 / 4 / 18˚ 1.61 1.53 1.45 1.37 1.30 1.17 1.06 0.90 60BIF 500 / 3 / 4 / 20˚ 1.72 1.65 1.58 1.49 1.39 1.27 1.10 0.97 60BIF 500 / 3 / 4 / 22˚ 1.82 1.75 1.68 1.60 1.50 1.37 1.18 1.02 61BIF 500 / 3 / 4 / 24˚ 1.94 1.87 1.78 1.69 1.59 1.45 58BIF 500 / 3 / 4 / 26˚ 2.11 1.99 1.89 1.79 1.68 1.55 58BIF 500 / 3 / 4 / 28˚ 2.21 2.11 2.02 1.89 1.76 1.62 58BIF 500 / 3 / 4 / 30˚ 2.27 2.18 2.08 1.96 1.81 1.63 58
Pitch dBADia. Phase Pole Angle 0 50 100 150 200 250 300 350 @ 3m
BIF 630 3 / 4 / 8˚ 1.82 1.68 1.54 1.39 1.23 1.04 0.76 77BIF 630 3 / 4 / 10˚ 2.18 1.99 1.80 1.64 1.49 1.25 0.95 77BIF 630 3 / 4 / 12˚ 2.57 2.35 2.12 1.91 1.68 1.39 1.17 77BIF 630 3 / 4 / 14˚ 2.72 2.52 2.31 2.12 1.86 1.64 1.29 77BIF 630 3 / 4 / 16˚ 2.91 2.75 2.56 2.32 2.13 1.84 1.48 77BIF 630 3 / 4 / 18˚ 3.22 3.03 2.81 2.63 2.34 2.04 1.61 77BIF 630 3 / 4 / 20˚ 3.43 3.26 3.07 2.83 2.53 2.12 1.78 77BIF 630 3 / 4 / 22˚ 3.64 3.48 3.28 3.06 2.70 2.27 1.87 78BIF 630 3 / 4 / 24˚ 3.87 3.69 3.47 3.23 2.88 75BIF 630 3 / 4 / 26˚ 4.21 3.92 3.67 3.41 3.09 75
Pitch dBADia. Phase Pole Angle 0 100 200 300 400 500 600 @ 3m
BIF 800 3 / 4 / 8˚ 3.82 3.43 2.95 2.58 1.99 1.31 80BIF 800 3 / 4 / 10˚ 4.42 4.06 3.55 3.05 2.48 1.69 80BIF 800 3 / 4 / 12˚ 5.13 4.58 4.13 3.57 2.95 2.21 80BIF 800 3 / 4 / 14˚ 5.57 5.02 4.55 4.03 3.33 2.42 80BIF 800 3 / 4 / 16˚ 6.06 5.57 5.03 4.48 3.77 2.69 80BIF 800 3 / 4 / 18˚ 6.55 6.10 5.61 5.05 4.02 3.19 80
Green tabulations indicate fans available on request. Please contact your local Sales Office for delivery information.
-
106 107
B I F U R C A T E D C A S E A X I A L F A N S ( B I F )V E N T - A X I AB I F U R C A T E D C A S E A X I A L F A N SD I M E N S I O N S (mm)
b
e No. OF HOLESC P.C.D.
CL
f Ø HOLES
Air Flow.(B Form).
hØ
Rotation
aØ In
side
dØ O
ver
Flan
ges
g
Stock Ref. No. a b c d e f g h Approx. Weight Kg
BIF250 / 2 & 4 / 1&3 / 8-32 250 535 302 328 8 10 200 452 30
BIF315 / 2 & 4 / 1&3 / 8-30 315 535 355 385 8 10 224 452 35
BIF400 / 2 & 4 / 3 / 8-22 400 625 450 480 8 10 280 585 49
BIF500 / 4 / 3 / 8-22 500 660 560 590 12 12 315 695 66
BIF500 / 2 / 3 / 8-20 500 710 560 590 12 12 315 695 87
B I F U R C A T E D C A S E A X I A L F A N SA C C E S S O R I E S D E T A I L S
Max. Load
Stock Ref. No. A B C D E F G H kg
105-23-033 37 26 27 67 54 7 3 M8 23
105-23-055 37 26 27 67 54 7 3 M8 35
105-23-133 57 46 35 95 76 10.5 4 M12 91
105-23-165 57 46 35 95 76 10.5 4 M12 215
AXIAL ANCILLARY PACKconsists of :
2 Matching flanges
2 Flexible connectors
2 Mounting feet
4 Anti vibration mounts
4 Worm drive clips
b
h ie Dia
fe Dia
e Dia
dg
c
a
MOUNTING FOOT
Stock Ref. No. a b c d e f g h i
105 03 250 232 24 180 200 10 14 115 146 130
105 03 315 275 24 224 224 10 14 115 177.5 167
105 03 400 348 24 280 280 12 14 135 225 213
105 03 500 425 24 315 315 12 14 135 280 268
105 03 630 520 24 400 400 12 14 175 345 333
105 03 800 800 40 700 450 12 22 262 430 405
A Ø
Insi
de
D Ø
Ove
r Fl
ange
s
B
G
E No OF HOLESC P.C.D.
CL
F Ø HOLES
Air Flow.(B Form).
Rotation
BIF250-BIF500 DIMENSIONS
BIF630-BIF800 DIMENSIONS
Stock Ref. No. A B C D E F G Approx. Weight Kg
BIF630 / 4 / 3 / 8-26 630 790 690 728 12 12 400 106
BIF800 / 4 / 3 / 8-18 800 880 860 890 16 12 450 155
INLET WIRE GUARD‘K’ factor loss 0.25Available for direct fixing to either side ofthe fan using flange sizing holes.Constructed to meet BS 848 Part 5.
COUPLING FLANGERolled from mild steel. Dimensionally matched to fan flangeand fixing holes.
Number of holes
Stock Ref. No. a b
105 05 250 245 3
105 05 315 380 3
105 05 400 475 3
105 05 500 595 3
105 05 630 725 3
105 05 800 870 10
overall spigot pcd ext dia hole dia No.Stock Ref. No. a b c d e holes
105 06 250 254 55 292 327 10 4
105 06 315 315 30 355 385 10 8
105 06 400 400 45 450 480 12 8
105 06 500 500 0 560 590 12 12
105 06 630 630 75 690 720 12 12
105 06 800A 800 40 860 884 12 13
150
a Ø
Flexible Connection
-
108 109
B I F U R C A T E D C A S E A X I A L F A N S ( B I F )V E N T - A X I AB I F U R C A T E D C A S E A X I A L F A N SA C C E S S O R I E SACCESSORIES
Model Mounting Feet Inlet Wire Guard Coupling Flange Ancillary Pack Attenuator Attenuator inc. Pod Anti-Vibration Mount
BIF250 105 03 250 105 05 250 105 06 315 105 13 250HT 105 14 250 105 00 250 105 23 033
BIF315 105 03 315 105 05 315 105 06 315 105 13 315HT 105 14 315 105 00 315 105 23 033
BIF400 105 03 400 105 05 400 105 06 400 105 13 400HT 105 14 400 105 00 400 105 23 033
BIF500 105 03 500 105 05 500 105 06 500 105 13 500HT 105 14 500 105 00 500 105 23 055
BIF630 105 03 630 105 05 630 105 06 630 105 13 630HT 105 14 630 105 00 630 105 23 055
BIF800 105 03 800A 105 05 800 105 06 800A 105 13 800HT 105 14 800A 105 00 800A 105 23 133
Model Stock Dia Dia Dia Length Dia No.Ref. No. a b c d e holes
BIF250 105 00 250 350 292 254 375 M8 4
BIF300 105 00 315 415 355 315 475 M8 8
BIF400 105 00 400 500 450 400 600 M10 8
BIF500 105 00 500 600 560 500 750 M10 12
BIF630 105 00 630 730 690 630 940 M10 12
BIF800 105 00 800A 900 860 796 1200 M10 16
No. ofholes.
1
RES
ISTA
NC
E (P
a)
40
0
10
20
30
0 2 3 4 5 6 7 8 9 10
Melinex lined attenuators are available on request
RESISTANCE GRAPH FOR AXIAL ATTENUATOR WITH POD
An attenuator without pod offers negligible resistance to air flow, and therefore the pressure loss can be considered to be thesame as that for the equivalent length of ducting.
Mean Duct Velocity m/s
B I F U R C A T E D C A S E A X I A L F A N A T T E N U A T O R SD I M E N S I O N S
B I F U R C A T E D C A S E A X I A L F A N SA T T E N U A T O R D E T A I L S
Diameter Stock Ref. No. 63 125 250 500 1k 2k 4k 8k kg approx
250 105 14 250 2 3 6 11 16 11 10 6 20
315 105 14 315 2 3 6 11 16 11 10 6 22
355 105 14 355 2 3 6 12 16 11 10 6 30
400 105 14 400 2 3 6 13 16 12 10 6 41
450 105 14 450 2 4 6 14 17 12 10 6 50
500 105 14 500 3 4 7 14 17 14 11 7 59
560 105 14 560 2 4 8 15 18 14 11 7 70
630 105 14 630 3 4 8 16 18 14 11 7 82
800 105 14 800A 1 2 6 9 12 10 6 2 100
CASE AXIAL ATTENUATOR FITTED WITH POD INSERTION LOSSES
Diameter Stock Ref. No. 63 125 250 500 1k 2k 4k 8k kg approx + POD
315 105 00 315 6 7 12 18 27 25 22 19 32
355 105 00 355 3 8 12 18 28 26 22 19 44
400 105 00 400 3 8 12 18 28 26 23 19 60
450 105 00 450 4 8 14 20 28 26 23 19 73
500 105 00 500 4 8 14 20 29 26 23 19 87
560 105 00 560 4 9 14 20 29 26 23 19 102
630 105 00 630 4 9 14 20 29 26 23 19 120
800 105 00 800A 6 10 20 30 35 28 25 22 149
ATTENUATOR INSERTION LOSS DATA
-
110 111
B I F U R C A T E D C A S E A X I A L F A N S ( B I F )V E N T - A X I AB I F U R C A T E D C A S E A X I A L F A N SE L E C T R I C A L D E T A I L S1 PHASE 2 POLE MOTORS
1 Phase 5 StepPitch Angle Nominal Motor Amps Amps Type of Starter 103-11-240 Auto-Transformer
Stock Ref. No. Range rpm kW F.L.C. S.C. Starter Overload 1 Phase
BIF250 / 2 / 1 / 32 8 TO 32 2900 0.25 3.8 8.0 D.O.L 103 12 070 N/A
BIF315 / 2 / 1 / 30 8 TO 30 2900 0.75 5.0 15.0 D.O.L 103 12 070 N/A
1 PHASE 4 POLE MOTORSPitch Angle Nominal Motor Amps Amps Type of Starter 103-11-240 Auto-Transformer
Stock Ref. No. Range rpm kW F.L.C. S.C. Starter Overload 1 PhaseBIF250 / 4 / 1 / 32 8 TO 32 1440 0.18 3.6 9.7 D.O.L 103 12 070 103 14 105
BIF315 / 4 / 1 / 32 8 TO 32 1440 0.18 3.6 9.7 D.O.L 103 12 070 103 14 105
3 PHASE 2 POLE MOTORS3 Phase
Starter 103 11 240 Coil 5 StepPitch Angle Nominal Motor Amps Amps Type of Starter 103 11 415 Coil Auto-Transformer
Stock Ref. No. Range rpm kW F.L.C. S.C. Starter Overload 3 Phase
BIF250 / 2 / 3 / 32 8 TO 32 2900 0.37 1.0 4.4 D.O.L 103 12 018 N/A
BIF315 / 2 / 3 / 30 8 TO 30 2900 0.75 1.6 8.8 D.O.L 103 12 027 N/A
BIF400 / 2 / 3 / 22 8 TO 22 2900 2.20 4.6 28.0 D.O.L 103 12 070 N/A
3 PHASE 2 POLE MOTORS1 Phase 5 Step
Pitch Angle Nominal Motor Amps Amps Type of Starter 103 15 415 Coil Auto-TransformerStock Ref. No. Range rpm kW F.L.C. S.C. Starter Overload 3 Phase
BIF500 / 2 / 3 / 20 8 TO 20 2900 4.00 7.5 50.0 STAR DELTA 103 12 070 N/A
3 PHASE 4 POLE MOTORS1 Phase
Starter 103 11 240 Coil 5 StepPitch Angle Nominal Motor Amps Amps Type of Starter 103 11 415 Coil Auto-Transformer
Stock Ref. No. Range rpm kW F.L.C. S.C. Starter Overload 3 Phase
BIF250 / 4 / 3 / 32 8 TO 32 1440 0.25 1.0 3.9 D.O.L 103 12 018 103 14 301
BIF315 / 4 / 3 / 32 8 TO 32 1440 0.25 1.0 3.9 D.O.L 103 12 018 103 14 301
BIF400 / 4 / 3 / 32 8 TO 32 1440 0.55 1.4 6.4 D.O.L 103 12 018 103 14 304
BIF500 / 4 / 3 / 32 8 TO 32 1440 1.10 2.6 11.5 D.O.L 103 12 040 103 14 304
BIF630 / 4 / 3 / 26 8 TO 26 1440 2.20 5.0 27.0 D.O.L 103 12 070 103 14 307
3 PHASE 4 POLE MOTORS1 Phase 5 Step
Pitch Angle Nominal Motor Amps Amps Type of Starter 103 15 415 Coil Auto-TransformerStock Ref. No. Range rpm kW F.L.C. S.C. Starter Overload 3 Phase
BIF800 / 4 / 3 / 18 8 TO 18 1440 4.00 8.4 50.0 STAR DELTA 103 12 070 -
The motor is suitable for speed control by either an inverteror a 5-step auto transformer speed controller when theambient air temperature is not higher than 60˚C.
S P E E D C O N T R O L L E RUsed in conjunction with speed controllable fans Vent-Axiaoffers a choice of speed controllers, the traditional Five-StepAuto Transformer or the Inverter Speed Controller.
The Five-Step-Auto Transformer provides five stepped speedsettings without the electronic motor harmonic noiseassociated with all electronic or solid state type SpeedControllers. Must be interlaced with a D.O.L. Starter.
The Inverter Speed Controller offers a more flexible solutionto speed control and is infinitely variable. The invertercontroller package, comprises of the inverter controller, abuilt in or separate filter where applicable and separateInverter Low Voltage Controller. The Inverter Controller isinstalled adjacent to the fan. The Low Voltage Controller canthen be installed up to a distance of 50m away from theInverter Controller and is wired using 5 core low voltagewire. This controller has a rotary speed control and separateOn/Off switch. The Inverter Controller package is factorymatched to the individual fan for ease of installation.
2 POLEPitch Angle Single Three
Stock Ref. No. Range Phase Supply Phase Supply
BIF250/2/3/32˚ 8 TO 32 103 20 101 08 103 20 301 08
BIF315/2/3/30˚ 8 TO 30 103 20 101 09 103 20 301 09
BIF400/2/3/22˚ 8 TO 22 103 20 103 02 103 20 303 05
BIF500/2/3/20˚ 8 TO 20 - 103 20 305 06
4 POLE
BIF250/4/3/32˚ 8 TO 32 103 20 101 10 103 20 301 10
BIF315/4/3/32˚ 8 TO 32 103 20 101 10 103 20 301 10
BIF400/4/3/32˚ 8 TO 32 103 20 101 11 103 20 301 11
BIF500/4/3/32˚ 8 TO 32 103 20 102 02 103 20 302 11
BIF630/4/3/26˚ 8 TO 26 103 20 103 04 103 20 305 07
BIF800/4/3/18˚ 8 TO 18 - 103 20 350 06
B I F U R C A T E D C A S E A X I A L F A N SI N V E R T E R D E T A I L S
I N V E R T E R C O N T R O L L E R SInverter (Variable speed drives) are suitable for allmodels of inverter controllable three phase fans.Offering complete user adaptability Vent-Axia Invertersoffer the following benefits: -
Frequency control setting resolution from 0-100% in0.1 increments (not only providing total speed control,but also enabling energy savings to be made throughthe fine tuning/optimisation of the fan)
Pre-settable minimum/maximum speed. Overloadprotection – 150% for 1 minute, therefore protectingthe fan from drawing excessive current.
Stall prevention during acceleration, deceleration andconstant speed, preventing nuisance tripping andproblems.
The versatility of the Inverter means that a single driveunit can be used to control the speed of multiple fans,provided that their combined loads do not exceed thedrive capacity.
Using an Inverter is by far the most effective andefficient way of controlling and optimising your fan orfans.
The Inverter controller, will include either a built in orseparate EMC filter, a ferrite coil and a low voltagevariable speed controller. The controls set will bematched to each individual fan and factory set, this willeliminate the need for any programming of the invertercontroller on site.
-
112
B I F U R C A T E D C A S E A X I A L F A N S ( B I F )
113
B I F U R C A T E D C A S E A X I A L F A N SP E R F O R M A N C E C U R V E S
IN DUCT OCTAVE BAND MID-FREQUENCY Hz (c/s)
SPECTRUM 63 125 250 500 1000 2000 4000 8000
CONSTANTS 5 6 8 7 11 17 20 22
IN DUCT OCTAVE BAND MID-FREQUENCY Hz (c/s)
SPECTRUM 63 125 250 500 1000 2000 4000 8000
CONSTANTS 7 9 5 9 10 15 19 21
0
0.1 0.50.0
80
70
60
30
0.3
40
10
50
0.2 0.4ST
ATIC
PR
ESSU
RE
AIR VOLUME0.6
28˚ 32˚
8˚ 12˚ 16˚ 20˚ 24˚ 28˚
71dbw61db
69dbw59db
67dbw57db
73dbw63db
20
71dbw61db
24˚20˚16˚12˚8˚
32˚m3/s
Pa
0
0.2 1.00.0
350
300
250
100
0.6
150
50
200
0.4 0.8
STAT
IC P
RES
SUR
E
AIR VOLUME1.2
8˚ 12˚ 16˚
20˚ 24˚ 28˚
8˚ 12˚ 16˚ 20˚ 24˚ 28˚
88dbw78db
86dbw76db
84dbw74db
90dbw80db
m3/s
Pa
315Ø Bifurcated 4 pole
315 Ø Bifurcated 2 pole
V E N T - A X I AB I F U R C A T E D C A S E A X I A L F A N SP E R F O R M A N C E C U R V E S
IN DUCT OCTAVE BAND MID-FREQUENCY Hz (c/s)
SPECTRUM 63 125 250 500 1000 2000 4000 8000
CONSTANTS 6 8 6 9 11 16 20 21
IN DUCT OCTAVE BAND MID-FREQUENCY Hz (c/s)
SPECTRUM 63 125 250 500 1000 2000 4000 8000
CONSTANTS 4 5 8 7 12 17 21 23
0
0.1 0.50.0
Pa 200
180
160
100
0.3
60
120
80
140
0.2 0.4
STAT
IC P
RES
SUR
E
AIR VOLUME
40
20
0.6
8˚ 12˚ 16˚ 20˚ 24˚ 28˚ 32˚
8˚ 12˚ 16˚ 20˚ 24˚ 28˚ 32˚
82dbw72db
80dbw70db
78dbw68db
m3/s
To obtain the sound spectrum in the octave bands 63 to 8000 Hz, subtract the constants shown under each performance chartfrom the dBW figure on the chart.
250 Ø Bifurcated 4 pole
250 Ø Bifurcated 2 pole
0
0.05 0.250.00
50
45
40
25
0.15
15
30
20
35
0.10 0.20
STAT
IC P
RES
SUR
E
AIR VOLUME
10
5
0.30
8˚ 12˚ 16˚ 20˚ 24˚ 28˚ 32˚
8˚ 12˚ 16˚ 20˚ 24˚ 28˚ 32˚
65dbw55db
63dbw53db
61dbw51db
m3/s
Pa
To obtain spectrum, subtract above constants from Sound Power Level etc
To obtain spectrum, subtract above constants from Sound Power Level etc
To obtain spectrum, subtract above constants from Sound Power Level etc
To obtain spectrum, subtract above constants from Sound Power Level etc
-
114
B I F U R C A T E D C A S E A X I A L F A N S ( B I F )
115
IN DUCT OCTAVE BAND MID-FREQUENCY Hz (c/s)
SPECTRUM 63 125 250 500 1000 2000 4000 8000
CONSTANTS 4 6 7 9 11 16 22 24
IN DUCT OCTAVE BAND MID-FREQUENCY Hz (c/s)
SPECTRUM 63 125 250 500 1000 2000 4000 8000
CONSTANTS 5 7 8 7 9 13 19 22
0
2.00.0
250
200
150
0.5
100
1.5ST
ATIC
PR
ESSU
RE
AIR VOLUME2.5
8˚ 12˚ 20˚
8˚ 12˚ 16˚ 20˚
88dbw74db
86dbw72db
84dbw70db
90dbw76db
50
16˚
1.0
24˚ 28˚
24˚ 28˚m3/s
Pa
0
3.00.0
800
700
600
1.0
300
500
2.0
STAT
IC P
RES
SUR
E
AIR VOLUME4.0
8˚ 12˚ 20˚
8˚ 12˚ 16˚ 20˚
105dbw91db
103dbw89db
101dbw87ad
107dbw93db
100
400
16˚
200
m3/s
Pa
500 Ø Bifurcated 4 pole
500 Ø Bifurcated 2 pole
B I F U R C A T E D C A S E A X I A L F A N SP E R F O R M A N C E C U R V E S
V E N T - A X I A B I F U R C A T E D C A S E A X I A L F A N P E R F O R M A N C E C U R V E S
IN DUCT OCTAVE BAND MID-FREQUENCY Hz (c/s)
SPECTRUM 63 125 250 500 1000 2000 4000 8000
CONSTANTS 5 6 8 10 12 17 20 22
IN DUCT OCTAVE BAND MID-FREQUENCY Hz (c/s)
SPECTRUM 63 125 250 500 1000 2000 4000 8000
CONSTANTS 6 7 7 9 11 16 21 23
0
1.00.0
140
120
100
0.6
40
80
0.2 0.8
STAT
IC P
RES
SUR
E
AIR VOLUME1.2
8˚ 12˚ 20˚
8˚ 12˚ 16˚ 20˚
81dbw69db
79dbw67db
77dbw65db
83dbw71db
20
60
16˚
0.4
24˚ 28˚ 32˚
24˚ 28˚ 32˚m3/s
Pa
0
2.00.0
500
450
400
150
1.0
250
50
350
0.5 1.5
STAT
IC P
RES
SUR
E
AIR VOLUME2.5
8˚ 12˚ 20˚
8˚ 12˚ 16˚ 20˚
98dbw86db
96dbw84db
94dbw82db
100dbw88db
100
200
300
16˚
m3/s
Pa
400 Ø Bifurcated 4 pole
400 Ø Bifurcated 2 pole
To obtain the sound spectrum in the octave bands 63 to 8000 Hz, subtract the constants shown under each performance chartfrom the dBW figure on the chart.
To obtain spectrum, subtract above constants from Sound Power Level etc
To obtain spectrum, subtract above constants from Sound Power Level etc
To obtain spectrum, subtract above constants from Sound Power Level etc
To obtain spectrum, subtract above constants from Sound Power Level etc
-
116
B I F U R C A T E D C A S E A X I A L F A N S ( B I F )
117
V E N T - A X I AB I F U R C A T E D C A S E A X I A L F A N P E R F O R M A N C E C U R V E S
IN DUCT OCTAVE BAND MID-FREQUENCY Hz (c/s)
SPECTRUM 63 125 250 500 1000 2000 4000 8000
CONSTANTS 6 9 8 10 12 14 19 21
IN DUCT OCTAVE BAND MID-FREQUENCY Hz (c/s)
SPECTRUM 63 125 250 500 1000 2000 4000 8000
CONSTANTS 7 9 8 10 11 15 20 22
0
4.00.0
350
300
250
1.0
150
3.0
STAT
IC P
RES
SUR
E
AIR VOLUME5.0
8˚ 12˚ 20˚
8˚ 12˚ 16˚ 20˚
90dbw74db
88dbw72db
86dbw70db
92dbw76db
50
16˚
2.024˚
100
200
84dbw68db
82dbw66db
24˚
m3/s
Pa
0
6.00.0
600
500
400
200
4.0
STAT
IC P
RES
SUR
E
AIR VOLUME8.0
8˚ 10˚ 14˚
8˚ 10˚ 12˚ 14˚
102dbw84db
100dbw82db
98dbw80db
104dbw86db
12˚
2.016˚
100
300
96dbw78db
94dbw76db
16˚ 18˚
18˚m3/s
Pa
630 Ø Bifurcated 4 pole
800 Ø Bifurcated 4 pole
To obtain the sound spectrum in the octave bands 63 to 8000 Hz, subtract the constants shown under each performance chartfrom the dBW figure on the chart.
To obtain spectrum, subtract above constants from Sound Power Level etc
To obtain spectrum, subtract above constants from Sound Power Level etc
SINGLE PHASE FANCONNECTED TO A D.O.L. STARTER
~
SINGLE PHASE FANCONNECTED TO A D.O.L. STARTER &
5.0 AMP AUTO TRANSFORMER
~
FAN TERMINAL
U1E
FAN TERMINAL
240 Volt D.O.L. StarterA suitable sized
overload relay must befitted to provide motor
protection.
42
N.B. Links betweenterminals 1 to A1, 3 to 6,
5 to 95 and 24 to 96must be fitted .
6
1 3 5
2395
96 24
A1
A2
E
N EL
1 Phase Supply(220-240V 50 Hz).
L
N
E
U2
1 Phase Supply(220-240V 50 Hz).
1 Phase AutoTransformer
Speed Controller.
103 14 105
N.B. Links betweenterminals 1 to A1, 3 to 6,
5 to 95 and 24 to 96must be fitted .
240 Volt D.O.L. StarterA suitable sized
overload relay must befitted to provide motor
protection.
U1E
L
N1L2
Fuse L1
N
U2
E
NE E
2 4
L
6
1 3
L N
5
E
E
24
23
N
96
95
A2
A1 E
BIF 250/4/1/8-32˚BIF 315/4/1/8-32˚
BIF 250/4/1/8-32˚BIF 315/4/1/8-32˚
BIF 250/2/1/8-32˚BIF 315/2/1/8-30˚
B I F U R C A T E D C A S E A X I A L F A N W I R I N G D I A G R A M S
-
READ INSTRUCTIONS IN CONJUNCTION WITH ILLUSTRATIONSPLEASE SAVE THESE INSTRUCTIONS
Installation and Wiring Instructions
Long Case Axial Fan
220-240V/1/50Hz & 380-415V/3/50Hz
-
2
Installation and Wiring Instructions for the Case Axial Fan.
IMPORTANT: READ THESE INSTRUCTIONS BEFORE COMMENCING THE INSTALLATION
DO NOT install this product in areas where the following may be present or occur:• Excessive oil or a grease laden atmosphere.• Corrosive or flammable gases, liquids or vapors.• Ambient temperatures less than –5°C or higher than 54°C.• Relative humidity above 95%• Possible obstructions which would hinder the access or removal of the fan.• Sudden ductwork bends or transformations close to the fan.
SAFETY AND GUIDANCE NOTES
Air moving equipment may present mechanical, electrical or noise hazards. To minimise the risks associated withthese potential hazards, it is essential that installation, operation and maintenance instructions are followed andcarried out by a suitably qualified person.
A. All wiring to be in accordance with the current I.E.E. Regulations, or the appropriate standards of your country.B. The Fan should be provided with a local 2/3 pole isolator switch having a contact separation of at least 3mm.C. Ensure that the mains supply (Voltage, Frequency, and Phase) complies with the rating label.D. The Fan should only be used in conjunction with the appropriate Vent-Axia products.E. It is recommended that the connection to the terminal box is made with flexible cable/conduit.F. The fan should not be sited within 600mm horizontally of/or 2250mm vertically of a bath/shower tray, in
accordance with the I.E.E. Regulations for bathrooms.G. When the Fan is used to remove air from a room containing a fuel-burning appliance, ensure that the air
replacement is adequate for both the fan and the fuel-burning appliance.H. If the fan is used to supply air into a room, the installer must ensure that the fan intake is located a minimum of
600mm from any flue outlet.I. This fan is designed as an inline ducted fan to be positioned between lengths of ducting. Short duct runs
terminating within 1.5m must incorporate suitable guards.J. Certain applications may require the installation of sound attenuation material, together with either an Auto
Transformer or Inverter Speed Controller to achieve the sound levels required.
DESCRIPTION.
The Long Case Axial range of fans incorporates factory adjustable pitch impellers, which provide a comprehensiverange of duties offering high performance and pressure characteristics. Available in twelve sizes ranging from315mm to 1250mm ø and performances from 0.24m3/s to 38m3/s with a pressure development up to 1250Pa. Thecasing is constructed from rolled steel plate and protected with a galvanised finish.
A. INSTALLATION.
1. Ensure the impeller rotates and is free from obstruction, prior to installation.
2. The fan is suitable for mounting at any angle.
3. Ensure that there is adequate clearance for accessing the fan.
4. Securely mount the fan using the holes in the end flanges and use the appropriate drop rods, bolts, anti-vibration mountings etc.
5. Ensure the Airflow Arrow is aligned with the direction of the airflow required.
6. The use of flexible connections and anti-vibration mountings is recommended to minimise noise and vibration.
7. Ensure that the flexible connections are taut and the fan and ductwork are aligned.
8. Flexible connections MUST be used in conjunction with anti-vibration mountings.
9. Anti-vibration mountings must be installed in compression.
-
3
FLEXIBLE CONNECTION
FLEXIBLE CONNECTION
AXIAL FAN
ANTI-VIBRATION MOUNTINGS
MOUNTINGFEET
LC56A4/1/8-26°LC63A4/1/8-22°
LC31A4/1/8-32°LC35A4/1/8-32°LC40A4/1/8-32°LC45A4/1/8-32°LC50A4/1/8-28°
N.B. Links between terminals 1 to A1, 3 to 6,
5 to 95 and 24 to 96 must be fitted .
240 Volt D.O.L. Starter A suitable sized
overload relay must be fitted to provide motor
protection.
LC40A2/1/8-28°LC35A2/1/8-32°LC31A2/1/8-32°
FAN TERMINAL
E
L
U1 U2
E
A2
A1
24
23
1 Phase Supply(220-240V 50 Hz).
N
3
42
1
L ~
6
N
5
96
95
E
E
1 Phase Supply(220-240V 50 Hz).
1 Phase Auto Transformer
Speed Controller.
LC56A4/1/8-26°LC63A4/1/8-22°
103 14 113103 14 107103 14 105103 14 103
LC31A4/1/8-32°LC35A4/1/8-32°LC40A4/1/8-32°LC45A4/1/8-32°LC50A4/1/8-28°
N.B. Links between terminals 1 to A1, 3 to 6,
5 to 95 and 24 to 96 must be fitted .
240 Volt D.O.L. Starter A suitable sized
overload relay must be fitted to provide motor
protection.
FAN TERMINAL
U1E
L
N1L2
Fuse L1
N
U2
E
N E E
2 4
L
6
1 3
~L N
5
E
E
24
23
N
96
95
A2
A1 E
Fig.1. TYPICAL INSTALLATION (Horizontal).
WIRING
WARNING: THE FAN AND ANCILLARY CONTROL EQUIPMENT MUST BE ISOLATED FROMTHE POWER SUPPLY DURING THE INSTALLATION / OR MAINTENANCE.THE EQUIPMENT MUST BE EARTHED
1. Select and follow the appropriate wiring diagram (Figs. 2-11).2. Check all connections have been made correctly and ensure that all terminal connections and cable clamps
are securely fastened.3. The cable entry must be made using a suitable grommet or cable gland.4. Switch the mains power supply on and check the fan is operating correctly.
Fig. 2. Single Phase Fan Connected Fig. 3. Single Phase Fan Connected to a 240V D.O.L. Starter. to a 240V D.O.L. Starter an Auto Transformer
Speed Controller.
-
4
N.B. Links between terminals 5 to 95 and 24
to 96 must be fitted.
415 Volt D.O.L. Starter A suitable sized
overload relay must be fitted to provide motor
protection.
FAN TERMINAL
U1
W2 U2
V1
V2
W1E
3 Phase Supply(380-415V 50Hz).
L1
2
1
L3L2
4
3
6
5
L1 L2 L3 E
E
E
24
23
A2
95
96
A1
LC31A2/3/8-32ºLC35A2/3/8-32ºLC40A2/3/8-28º LC45A2/3/8-24ºLC50A2/3/8-16º
LC31A4/3/8-32ºLC35A4/3/8-32ºLC40A4/3/8-32º LC45A4/3/8-32ºLC50A4/3/8-28ºLC56A4/3/8-26ºLC63A4/3/8-30ºLC71A4/3/8-18º
E
FAN TERMINAL
E
LC31A4/3/8-32ºLC35A4/3/8-32ºLC40A4/3/8-32º LC45A4/3/8-32ºLC50A4/3/8-28ºLC56A4/3/8-26ºLC63A4/3/8-30ºLC71A4/3/8-18º
3 Phase Auto Transformer
Speed Controller.103-14-301103-14-304103-14-307
V1TKTK W1 U1 N L3 L2E
L1
N.B. Links between terminals 1 to A1, 5 to 95 must be fitted and the link between terminals 24 to 96
must be FITTED.
415 Volt D.O.L. Starter A suitable sized
overload relay must be fitted to provide motor
protection.1 3 5
2 4 6 96 24
95 23
A2
3 Phase Supply(380-415V 50Hz).
EL1 L3L2
A1 E
N
E
U1 V1 W1
V2U2W2
E
FAN TERMINAL
LC50A2/3/18-26ºLC56A2/3/8-24ºLC63A2/3/8-16º
LC71A4/3/20-30ºLC80A4/3/8-28ºLC90A4/3/8-26ºLC100A4/3/8-28º LC125A4/3/8-24º
W2
U2
V2
U1
V1
W1
STAR / DELTA Starter with current overload protection and a 415 volt coil.
STAR / DELTA STARTER 2 4 6
24
A2
23
96
95
A1
E
3 Phase Supply(380-415V 50Hz).
4
3
2
1
6
5
L2L1 L3
E
Fig. 4.Three Phase Fan Connected Fig. 5. Three Phase Fan Connectedto a 415V D.O.L. Starter. to a Star / Delta Starter.
Fig. 6. Three Phase FanConnected to a 415V D.O.L. Starter and an Auto Transformer Speed Controller.
NOTE: If an Auto Transformer is being used to control theFan speed, the reset facility MUST be disabled.
Contact Vent-Axia’s Technical Support Line for details.
-
5
E
FAN TERMINAL
LC31A2/3/8-32ºLC35A2/3/8-32ºLC40A2/3/8-16º
LC31A4/3/8-32ºLC35A4/3/8-32ºLC40A4/3/8-32º LC45A4/3/8-32ºLC50A4/3/8-28ºLC56A4/3/8-20º
U2 V2W2
U1 V1 W1
Shielding.(WRAP WITH INSULATION TAPE).Connector
Shielding.(WRAP WITH INSULATION TAPE DO NOT
CONNECT TO THE EARTH TERMINAL).
Shielded Cable
NE ~L
1 Phase Supply(220 - 240V).
Metal Enclosure & Wiring by others.
Inverter 455552
User FanSpeed Controller
ILVC 1(103-20-601)
Ferrite Coil(Loop the fan supply
cable around the ferrite coil 3 times).
10 Volt D.C. (up to a maximum distance of 50m from the Inverter to the speed controller.
3 PHASE SUPPLY(230 - 240 Volts)
E
FAN TERMINAL
LC56A4/3/22-26ºLC63A4/3/8-22ºLC71A4/3/8-18º
U2 V2W2
U1 V1 W1
Shielding.(WRAP WITH INSULATION TAPE).Connector
Shielding.(WRAP WITH INSULATION TAPE DO NOT CONNECT TO THE EARTH TERMINAL).
Shielded Cable
NE ~L
1 Phase Supply(220 - 240V).
Metal Enclosure & Wiring by others.
Ferrite Coil(Loop the fan supply cable around
the ferrite coil 3 times).
10 Volt D.C. (up to a maximum distance of 50m from the Inverter to the speed controller.
3 PHASE SUPPLY(230 - 240 Volts)
Inverter455553 or
455554
LC40A2/3/18-28º
User FanSpeed Controller
ILVC 1(103-20-601)
10 Volt D.C. (up to a maximum distance of 50m from the Inverter to the speed controller.
Inverter455556, 455557, 455558
or 103 20 303
Filter103-20-505103-20-512
E
Metal Enclosure & Wiring by others.
LC31A 2/3/8-32ºLC35A 2/3/8-32ºLC40A 2/3/8-28ºLC45A 2/3/8-24ºLC50A 2/3/8-16º
LC31A 4/3/8-32ºLC35A 4/3/8-32ºLC40A 4/3/8-32º LC45A 4/3/8-32ºLC50A 4/3/8-28ºLC56A 4/3/8-26ºLC63A 4/3/8-30ºLC71A 4/3/8-18º
User FanSpeed Controller
ILVC 2 (103-20-602)
Fig. 7.Three Phase Fan Fig. 8.Three Phase FanSingle Phase in – Three Phase (240V) Out Single Phase in – Three Phase (240V) OutLC Fan connected to an Inverter Speed LC Fan connected to an Inverter SpeedController Kit (103 20 101). Controller Kit (103 20 102 or 103 20 103).
Fig. 9. Three Phase Fan.Three Phase In – Three Phase Out. LC Fan connected to an Inverter Speed Controller Kit(103 20 301, 103 20 302, 103 20 303 or 103 20 305).
-
6
Filter103-20-512103-20-524
Metal Enclosure & Wiring by others.
Inverter455559 or
455560
E
User FanSpeed Controller
ILVC 2 (103-20-602)
10 Volt D.C. (up to a maximum distance of 50m from the Inverter to the speed controller.
LC50A2/3/18-26ºLC56A2/3/8-24ºLC63A2/3/8-16º
LC71A4/3/20-30ºLC80A4/3/8-28ºLC90A4/3/8-18ºLC100A4/3/8-12º
Fig. 10. Three Phase Fan.Three Phase In – Three Phase Out. LC Fan connected to an Inverter Speed Controller Kit(103 20 350 or 103 20 310).
-
7
Filter103 20 524
Metal Enclosure & Wiring by others.
Inverter103 20 315
E
User FanSpeed Controller
ILVC 2 (103-20-602)
10 Volt D.C. (up to a maximum distance of 50m from the Inverter to the speed controller.
LC90A4/3/20-26ºLC100A4/3/14-16º
Fig. 11. Three Phase Fan.Three Phase In – Three Phase Out. LC Fan connected to an Inverter Speed Controller Kit (103 20 315).
ROUTINE INSPECTION AND MAINTENANCE
ISOLATE FROM THE POWER SUPPLY AND ENSURE THAT THE FAN CANNOT BE ACCIDENTALLY SWITCHED BACK ON.
1. At intervals appropriate to the installation, the fan should be inspected and cleaned to ensure there is no buildup of dirt or other deposits on the impeller or motor. If the fan is handling dust laden air, it is recommend that afilter is installed.
2. All Case Axial fans have sealed for life bearings and do not require lubrication.
3. Check the condition and security of all fixing bolts, rods, anti-vibration mountings, and flexible connections.
-
8
Head Office: Fleming Way, Crawley, West Sussex RH10 9YXTel: 01293 526062 Fax: 01293 551188
Internet site at: www.vent-axia.com
VENT-AXIA SALES CENTRES
ENGLAND & WALES NATIONAL CALL CENTER SCOTLANDNewton Road, CrawleyWest Sussex Telephone: 0141 429 1166RH10 9JA Fax: 01293 565169
Telephone: 01293 530202 REPUBLIC OF IRELANDFax: 01293 565169 Vent-Axia Ventilation Ltd.
921 Western Road Industrial EstateNORTHERN IRELAND Naas Road, Dublin 12.
Telephone: 02890 402220 Telephone: (01) 450 4133Fax: 01293 565169 Fax: (01) 450 4570
Did you find these instructions easy to use?
We value your comments, contact us via :
Email: [email protected]
The Vent-Axia GuaranteeApplicable only to products installed and used in the United Kingdom. For details of the Guarantee outside of the UnitedKingdom contact your local supplier.
Vent-Axia guarantees this product for two years from the date of purchase against faulty material or workmanship. In theevent of any part being found to be defective, the product will be repaired, or at the Company’s discretion the product willbe replaced without charge, provided that the product:
1). Has been installed and used in accordance with the instruction given with each unit.2). Has not been connected to an unsuitable electricity supply (The correct electricity supply voltage shown on the
product-rating label attached to the unit).3). Has not been misused, neglected or damaged.4). Has not been modified or repaired by any person not authorised to do so by Vent-Axia.
IF CLAIMING UNDER THE TERMS OF THE GUARANTEE
Please return the complete product, carriage paid to your original supplier by post or in person. Please ensure that it isadequately packed and accompanied by a letter clearly marked ‘Guarantee Claim’ stating the nature of the fault andproviding proof of the date and source of purchase.
As part of the policy of continuous product improvement Vent-Axia reserve the right to alter specifications without notice
454062 C 0403
-
9
DECLARATION OF CONFORMITYVent-Axia Ltd.Newton RoadCrawley,West Sussex,RH10 9JA
EC DECLARATION OF CONFORMITY.
Here with we declare that the air movement equipment designated below, on the basis of its design andconstruction in the form brought onto the market by us in accordance with the relevant safety and healthrequirements of the EC Directive on Machinery.
If alterations are made to the machinery without prior consultations with us, this declaration becomes invalid.
DESIGNATION OF EQUIPMENT: VENTILATION FAN.
SERIES TYPE: LONG CASE AXIAL FAN.
Applied Authorisation Standards (1) EN 292-1, EN 292-2, EN294in particular: EN 50081-2, EN 60204-1.
Applied National Standards and BS 848 Part 1,Technical Specifications (2) BS 848 Part 2,in particular: BS 848 Part 3.
Basis of self attestation Working toQuality Assurance: BS EN ISO 9001
Signatory:
R.D.A Spearman.Product Director.
Place / Date Crawley – April 2003
Notes: 1. For the complete list of applied standards and technical specifications see Vent- Axia Ltd. Documentation.2. Where no relevant harmonised standards exist.
425965 A 0403