Fundamentals of Making Energy-Saving
and Cost-Efficient Boiler Exhaust Systems
– Design Solutions and Applications
ASHRAE Qatar Oryx Chapter – 10th November 2012
Presenter: Steen Hagensen
![Page 2: Fundamentals of Making Energy-Saving and Cost-Efficient ... · Chimney Design 1996 Edition Chimney Equation Default Values: 8.5% CO 2, 60o F Ambient, 360o F Flue Gas, & Sea Level](https://reader033.vdocument.in/reader033/viewer/2022050518/5fa21d17dda75147ff7326ed/html5/thumbnails/2.jpg)
Make the unimaginable and impossible POSSIBLE!
A guide for using the ASHRAE’s chimney design
equation to design boiler exhaust systems that
save space, reduce installation cost and energy -
and allow the designer to design systems that
normally would be deemed impossible
![Page 3: Fundamentals of Making Energy-Saving and Cost-Efficient ... · Chimney Design 1996 Edition Chimney Equation Default Values: 8.5% CO 2, 60o F Ambient, 360o F Flue Gas, & Sea Level](https://reader033.vdocument.in/reader033/viewer/2022050518/5fa21d17dda75147ff7326ed/html5/thumbnails/3.jpg)
Z223.1-NFPA54 / International Fuel
Gas Code (Venting of equipment)
Minimum Safe Performance
A venting system shall be designed and constructed so as to
develop a positive flow adequate to remove flue or vent gases
to the outside atmosphere.
Equipment Draft Requirement
A venting system shall satisfy the draft requirement of the
equipment in accordance with the manufacturer’s instructions.
![Page 4: Fundamentals of Making Energy-Saving and Cost-Efficient ... · Chimney Design 1996 Edition Chimney Equation Default Values: 8.5% CO 2, 60o F Ambient, 360o F Flue Gas, & Sea Level](https://reader033.vdocument.in/reader033/viewer/2022050518/5fa21d17dda75147ff7326ed/html5/thumbnails/4.jpg)
ASHRAE 90.1 – Boiler Efficiency
• Current average boiler use:
6570 hours per year
• Current average operating
efficiency: 77%
• Efficiency threshold: 85%
![Page 5: Fundamentals of Making Energy-Saving and Cost-Efficient ... · Chimney Design 1996 Edition Chimney Equation Default Values: 8.5% CO 2, 60o F Ambient, 360o F Flue Gas, & Sea Level](https://reader033.vdocument.in/reader033/viewer/2022050518/5fa21d17dda75147ff7326ed/html5/thumbnails/5.jpg)
Boiler Draft vs Efficiency
![Page 6: Fundamentals of Making Energy-Saving and Cost-Efficient ... · Chimney Design 1996 Edition Chimney Equation Default Values: 8.5% CO 2, 60o F Ambient, 360o F Flue Gas, & Sea Level](https://reader033.vdocument.in/reader033/viewer/2022050518/5fa21d17dda75147ff7326ed/html5/thumbnails/6.jpg)
ASHRAE Chimney Design Equation
INPUTS:
• Appliance Type
• Fuel Type
• kW Input
• CO2% in Flue Gases
• Flue Gas Temperature
• Ambient Temperature
• Altitude
• Flue Layout
RESULTS:
• Flue Gas Volume
• Flue Gas Velocity
• Theoretical Draft
• Total Pressure Losses
• Appliance Outlet Pressure
Outlet Pressure
Theoretical Draft (-)
+ Pressure Losses (+)
![Page 7: Fundamentals of Making Energy-Saving and Cost-Efficient ... · Chimney Design 1996 Edition Chimney Equation Default Values: 8.5% CO 2, 60o F Ambient, 360o F Flue Gas, & Sea Level](https://reader033.vdocument.in/reader033/viewer/2022050518/5fa21d17dda75147ff7326ed/html5/thumbnails/7.jpg)
10’
Theoretical Draft: • Chimney Height
• Flue Gas Temperature
• Surrounding Temperature
• Barometric Pressure
Pressure Loss: • Flue Gas Volume
• Total Resistance
- 7 Pa
1,000 MBH Forced Draft
10” Flue
Difference at Outlet: • Specified by Equipment
• Efficiencies
• Safety
+ 8 Pa
- 15 Pa
Chimney Design
![Page 8: Fundamentals of Making Energy-Saving and Cost-Efficient ... · Chimney Design 1996 Edition Chimney Equation Default Values: 8.5% CO 2, 60o F Ambient, 360o F Flue Gas, & Sea Level](https://reader033.vdocument.in/reader033/viewer/2022050518/5fa21d17dda75147ff7326ed/html5/thumbnails/8.jpg)
10’
Theoretical Draft: • Chimney Height
• Flue Gas Temperature
• Surrounding Temperature
• Barometric Pressure
Pressure Loss: • Flue Gas Volume
• Total Resistance
+ 7 Pa
1,000 MBH Forced Draft
10” Flue
5’
Difference at Outlet: • Specified by Equipment
• Efficiencies
• Safety
+ 22 Pa
- 15 Pa
Chimney Design
![Page 9: Fundamentals of Making Energy-Saving and Cost-Efficient ... · Chimney Design 1996 Edition Chimney Equation Default Values: 8.5% CO 2, 60o F Ambient, 360o F Flue Gas, & Sea Level](https://reader033.vdocument.in/reader033/viewer/2022050518/5fa21d17dda75147ff7326ed/html5/thumbnails/9.jpg)
30’
Theoretical Draft: • Chimney Height
• Flue Gas Temperature
• Surrounding Temperature
• Barometric Pressure
Pressure Loss: • Flue Gas Volume
• Total Resistance
- 34 Pa
1,000 MBH Forced Draft
10” Flue
11 Pa
- 45 Pa
Difference at Outlet: • Specified by Equipment
• Efficiencies
• Safety
Chimney Design
![Page 10: Fundamentals of Making Energy-Saving and Cost-Efficient ... · Chimney Design 1996 Edition Chimney Equation Default Values: 8.5% CO 2, 60o F Ambient, 360o F Flue Gas, & Sea Level](https://reader033.vdocument.in/reader033/viewer/2022050518/5fa21d17dda75147ff7326ed/html5/thumbnails/10.jpg)
1996 Edition Chimney Equation Default Values: 8.5% CO2, 60o F Ambient, 360o F Flue Gas, & Sea Level
Appliance Values: 1,000 MBH Input with 8” Diameter Flue Outlet
Flue or Chimney Layout: • 8” Diameter
• 20’ Vertical
• 0’ Lateral
• No Fittings
Results: - 27 Pa Natural Draft
+ 26 Pa Pressure Loss
- 1 Pa at Flue Outlet
Chimney Design
![Page 11: Fundamentals of Making Energy-Saving and Cost-Efficient ... · Chimney Design 1996 Edition Chimney Equation Default Values: 8.5% CO 2, 60o F Ambient, 360o F Flue Gas, & Sea Level](https://reader033.vdocument.in/reader033/viewer/2022050518/5fa21d17dda75147ff7326ed/html5/thumbnails/11.jpg)
Chimney Design 1996 Edition
Chimney Equation Default Values: 8.5% CO2, 60o F Ambient, 360o F Flue Gas, & Sea Level
Appliance Values: 1,000 MBH Input with 8” Diameter Flue Outlet
Flue or Chimney Layout: • 8” Diameter
• 20’ Vertical
• 5’ Lateral
• (2) Fittings
Results: - 27 Pa Natural Draft
+ 48 Pa Pressure Loss
+ 21 Pa at Flue Outlet
![Page 12: Fundamentals of Making Energy-Saving and Cost-Efficient ... · Chimney Design 1996 Edition Chimney Equation Default Values: 8.5% CO 2, 60o F Ambient, 360o F Flue Gas, & Sea Level](https://reader033.vdocument.in/reader033/viewer/2022050518/5fa21d17dda75147ff7326ed/html5/thumbnails/12.jpg)
Chimney Design 1996 Edition
Chimney Equation Default Values: 8.5% CO2, 60o F Ambient, 360o F Flue Gas, & Sea Level
Appliance Values: 1,000 MBH Input with 8” Diameter Flue Outlet
Flue or Chimney Layout: • 10” Diameter
• 20’ Vertical
• 5’ Lateral
• (2) Fittings
Results: - 27 Pa Natural Draft
+ 19 Pa Pressure Loss
- 8 Pa at Flue Outlet
![Page 13: Fundamentals of Making Energy-Saving and Cost-Efficient ... · Chimney Design 1996 Edition Chimney Equation Default Values: 8.5% CO 2, 60o F Ambient, 360o F Flue Gas, & Sea Level](https://reader033.vdocument.in/reader033/viewer/2022050518/5fa21d17dda75147ff7326ed/html5/thumbnails/13.jpg)
Chimney Design 1996 Edition
Chimney Equation Default Values: 8.5% CO2, 60o F Ambient, 360o F Flue Gas, & Sea Level
Appliance Values: 1,000 MBH Input with 8” Diameter Flue Outlet
Flue or Chimney Layout: • 10” Diameter
• 10’ Vertical
• 5’ Lateral
• (2) Fittings
Results: - 13 Pa Natural Draft
+ 18 Pa Pressure Loss
+ 5 Pa at Flue Outlet
![Page 14: Fundamentals of Making Energy-Saving and Cost-Efficient ... · Chimney Design 1996 Edition Chimney Equation Default Values: 8.5% CO 2, 60o F Ambient, 360o F Flue Gas, & Sea Level](https://reader033.vdocument.in/reader033/viewer/2022050518/5fa21d17dda75147ff7326ed/html5/thumbnails/14.jpg)
1996 Edition
Chimney Design Chimney Equation Default Values: 8.5% CO2, 60o F Ambient, 360o F Flue Gas, & Sea Level
Appliance Values: 1,000 MBH Input with 8” Diameter Flue Outlet
Flue or Chimney Layout: • 12” Diameter
• 10’ Vertical
• 5’ Lateral
• (2) Fittings
Results: - 13 Pa Natural Draft
+ 8 Pa Pressure Loss
- 5 Pa at Flue Outlet
![Page 15: Fundamentals of Making Energy-Saving and Cost-Efficient ... · Chimney Design 1996 Edition Chimney Equation Default Values: 8.5% CO 2, 60o F Ambient, 360o F Flue Gas, & Sea Level](https://reader033.vdocument.in/reader033/viewer/2022050518/5fa21d17dda75147ff7326ed/html5/thumbnails/15.jpg)
Natural Draft Boiler Exhaust System
![Page 16: Fundamentals of Making Energy-Saving and Cost-Efficient ... · Chimney Design 1996 Edition Chimney Equation Default Values: 8.5% CO 2, 60o F Ambient, 360o F Flue Gas, & Sea Level](https://reader033.vdocument.in/reader033/viewer/2022050518/5fa21d17dda75147ff7326ed/html5/thumbnails/16.jpg)
Modulating Boiler Exhaust System
![Page 17: Fundamentals of Making Energy-Saving and Cost-Efficient ... · Chimney Design 1996 Edition Chimney Equation Default Values: 8.5% CO 2, 60o F Ambient, 360o F Flue Gas, & Sea Level](https://reader033.vdocument.in/reader033/viewer/2022050518/5fa21d17dda75147ff7326ed/html5/thumbnails/17.jpg)
NFPA 54
IAS (A.G.A.)
ANSI Z
223.1
Appliance Categories
NFPA 54 / International Fuel Gas Code
• Category I
• Category II
• Category III
• Category IV
![Page 18: Fundamentals of Making Energy-Saving and Cost-Efficient ... · Chimney Design 1996 Edition Chimney Equation Default Values: 8.5% CO 2, 60o F Ambient, 360o F Flue Gas, & Sea Level](https://reader033.vdocument.in/reader033/viewer/2022050518/5fa21d17dda75147ff7326ed/html5/thumbnails/18.jpg)
IV
III
II
I
Appliance Categories
Atmospheric Forced Draft – non-condensing
Fan-Assisted Forced Draft – condensing
![Page 19: Fundamentals of Making Energy-Saving and Cost-Efficient ... · Chimney Design 1996 Edition Chimney Equation Default Values: 8.5% CO 2, 60o F Ambient, 360o F Flue Gas, & Sea Level](https://reader033.vdocument.in/reader033/viewer/2022050518/5fa21d17dda75147ff7326ed/html5/thumbnails/19.jpg)
IV
III
II
I
Chimney Flue/ Vent Material
Aluminium Liner Stainless Steel 316 inner, 304 outer
Stainless Steel 316 inner, 304 outer Stainless Steel 316 inner, 304 outer
+ -
![Page 20: Fundamentals of Making Energy-Saving and Cost-Efficient ... · Chimney Design 1996 Edition Chimney Equation Default Values: 8.5% CO 2, 60o F Ambient, 360o F Flue Gas, & Sea Level](https://reader033.vdocument.in/reader033/viewer/2022050518/5fa21d17dda75147ff7326ed/html5/thumbnails/20.jpg)
Modern System Design
• Design Software
• Vent type application
• Operating temperature
• Resistance factors
• Ambient temperature
variations
• Code violations
Demand-Controlled Boiler Exhaust Systems
![Page 21: Fundamentals of Making Energy-Saving and Cost-Efficient ... · Chimney Design 1996 Edition Chimney Equation Default Values: 8.5% CO 2, 60o F Ambient, 360o F Flue Gas, & Sea Level](https://reader033.vdocument.in/reader033/viewer/2022050518/5fa21d17dda75147ff7326ed/html5/thumbnails/21.jpg)
Example – Over-draft Application
100 m
Draft
Control
Damper
![Page 22: Fundamentals of Making Energy-Saving and Cost-Efficient ... · Chimney Design 1996 Edition Chimney Equation Default Values: 8.5% CO 2, 60o F Ambient, 360o F Flue Gas, & Sea Level](https://reader033.vdocument.in/reader033/viewer/2022050518/5fa21d17dda75147ff7326ed/html5/thumbnails/22.jpg)
Example – Over-draft Application
![Page 23: Fundamentals of Making Energy-Saving and Cost-Efficient ... · Chimney Design 1996 Edition Chimney Equation Default Values: 8.5% CO 2, 60o F Ambient, 360o F Flue Gas, & Sea Level](https://reader033.vdocument.in/reader033/viewer/2022050518/5fa21d17dda75147ff7326ed/html5/thumbnails/23.jpg)
Example – Downsize
![Page 24: Fundamentals of Making Energy-Saving and Cost-Efficient ... · Chimney Design 1996 Edition Chimney Equation Default Values: 8.5% CO 2, 60o F Ambient, 360o F Flue Gas, & Sea Level](https://reader033.vdocument.in/reader033/viewer/2022050518/5fa21d17dda75147ff7326ed/html5/thumbnails/24.jpg)
Example – Downsize
![Page 25: Fundamentals of Making Energy-Saving and Cost-Efficient ... · Chimney Design 1996 Edition Chimney Equation Default Values: 8.5% CO 2, 60o F Ambient, 360o F Flue Gas, & Sea Level](https://reader033.vdocument.in/reader033/viewer/2022050518/5fa21d17dda75147ff7326ed/html5/thumbnails/25.jpg)
Example – Downsize 24 inch (610 mm) boiler exhaust
18 inch (450 mm) boiler exhaust
![Page 26: Fundamentals of Making Energy-Saving and Cost-Efficient ... · Chimney Design 1996 Edition Chimney Equation Default Values: 8.5% CO 2, 60o F Ambient, 360o F Flue Gas, & Sea Level](https://reader033.vdocument.in/reader033/viewer/2022050518/5fa21d17dda75147ff7326ed/html5/thumbnails/26.jpg)
Why Packaged Boiler Exhaust
Systems?
![Page 27: Fundamentals of Making Energy-Saving and Cost-Efficient ... · Chimney Design 1996 Edition Chimney Equation Default Values: 8.5% CO 2, 60o F Ambient, 360o F Flue Gas, & Sea Level](https://reader033.vdocument.in/reader033/viewer/2022050518/5fa21d17dda75147ff7326ed/html5/thumbnails/27.jpg)
Benefits of Packaged
Boiler Exhaust Systems Where
• Hotels / Resorts / Apartment Buildings
• Hospitals
What
• Steam boilers
• Calorifiers / Water Heaters
Why
• Save space, Save material – use smaller chimney
• Reduce number of chimneys
• Avoid “over-crowded” boiler-rooms
• Aesthetics
• Safety and redundancy
• Single supplier responsibility
![Page 28: Fundamentals of Making Energy-Saving and Cost-Efficient ... · Chimney Design 1996 Edition Chimney Equation Default Values: 8.5% CO 2, 60o F Ambient, 360o F Flue Gas, & Sea Level](https://reader033.vdocument.in/reader033/viewer/2022050518/5fa21d17dda75147ff7326ed/html5/thumbnails/28.jpg)
Boiler Exhaust System And Over-draft Control Or Fan-Powered Chimney
Stainless steel boiler exhaust (316/304), 25 mm insulation
Modulating fan control with boiler interlock
Boiler exhaust fan (variable speed)
Modulating Over-Draft Damper
Packaged Boiler Exhaust Systems
![Page 29: Fundamentals of Making Energy-Saving and Cost-Efficient ... · Chimney Design 1996 Edition Chimney Equation Default Values: 8.5% CO 2, 60o F Ambient, 360o F Flue Gas, & Sea Level](https://reader033.vdocument.in/reader033/viewer/2022050518/5fa21d17dda75147ff7326ed/html5/thumbnails/29.jpg)
Packaged Boiler Exhaust Systems
Boiler exhaust
with safety
controls
Boiler exhaust
with over-draft
control
Boiler exhaust with
over-draft control and
modulating draft
control
![Page 30: Fundamentals of Making Energy-Saving and Cost-Efficient ... · Chimney Design 1996 Edition Chimney Equation Default Values: 8.5% CO 2, 60o F Ambient, 360o F Flue Gas, & Sea Level](https://reader033.vdocument.in/reader033/viewer/2022050518/5fa21d17dda75147ff7326ed/html5/thumbnails/30.jpg)
IPVB 300 - 685 – Inline Power Venter
• SS316L construction
• Direct drive, TEFC variable
speed motor
• Maintenance free
• 575ºF Continuous
• All gas-fired or oil-fired
boilers
• Simple design with few
components reduces the
risk of failure and simplifies
service
• UL 378 – Draft Equipment
![Page 31: Fundamentals of Making Energy-Saving and Cost-Efficient ... · Chimney Design 1996 Edition Chimney Equation Default Values: 8.5% CO 2, 60o F Ambient, 360o F Flue Gas, & Sea Level](https://reader033.vdocument.in/reader033/viewer/2022050518/5fa21d17dda75147ff7326ed/html5/thumbnails/31.jpg)
IPVB 300 - 685 – Inline Power Venter
Motor and impeller drive
unit can be removed
without removing the fan
from the stack system
![Page 32: Fundamentals of Making Energy-Saving and Cost-Efficient ... · Chimney Design 1996 Edition Chimney Equation Default Values: 8.5% CO 2, 60o F Ambient, 360o F Flue Gas, & Sea Level](https://reader033.vdocument.in/reader033/viewer/2022050518/5fa21d17dda75147ff7326ed/html5/thumbnails/32.jpg)
Modulating Over-Draft Damper System MDF Damper
• Sizes – 12 in. to 48 in. diameters
• Multiple opposed blades made of 16 gauge type 316 stainless
• Pressure stack flange connections
• Rated to 700°F
EBC30
• Prime function
• Additional over-pressure protection for Forced-draft boilers
![Page 33: Fundamentals of Making Energy-Saving and Cost-Efficient ... · Chimney Design 1996 Edition Chimney Equation Default Values: 8.5% CO 2, 60o F Ambient, 360o F Flue Gas, & Sea Level](https://reader033.vdocument.in/reader033/viewer/2022050518/5fa21d17dda75147ff7326ed/html5/thumbnails/33.jpg)
IPVB 300 - 500 – Power Venter
Anywhere You Want It
![Page 34: Fundamentals of Making Energy-Saving and Cost-Efficient ... · Chimney Design 1996 Edition Chimney Equation Default Values: 8.5% CO 2, 60o F Ambient, 360o F Flue Gas, & Sea Level](https://reader033.vdocument.in/reader033/viewer/2022050518/5fa21d17dda75147ff7326ed/html5/thumbnails/34.jpg)
ENERVEX Chimney Flue
EPS
High Pressure Twin-Wall
Stainless Steel Multi-Purpose
Exhaust Duct and Chimney
System
![Page 35: Fundamentals of Making Energy-Saving and Cost-Efficient ... · Chimney Design 1996 Edition Chimney Equation Default Values: 8.5% CO 2, 60o F Ambient, 360o F Flue Gas, & Sea Level](https://reader033.vdocument.in/reader033/viewer/2022050518/5fa21d17dda75147ff7326ed/html5/thumbnails/35.jpg)
One Chimney Flue – EPS Multi-Purpose
• Building Heating
Chimney – condensing
and non-condensing
• Engine/Generator
Exhaust
• Grease Duct / Kitchen
Exhaust
![Page 36: Fundamentals of Making Energy-Saving and Cost-Efficient ... · Chimney Design 1996 Edition Chimney Equation Default Values: 8.5% CO 2, 60o F Ambient, 360o F Flue Gas, & Sea Level](https://reader033.vdocument.in/reader033/viewer/2022050518/5fa21d17dda75147ff7326ed/html5/thumbnails/36.jpg)
Chimney Flue - EPS
• Inner Liner:
316L stainless steel, 1mm
thick (1.2mm for diameters
of 1000mm and above)
• Outer wall:
304 stainless steel, 0.6mm
thick (0.8mm for diameters
of 700mm and above)
• Insulation
25-100mm thick fiber
insulation
![Page 37: Fundamentals of Making Energy-Saving and Cost-Efficient ... · Chimney Design 1996 Edition Chimney Equation Default Values: 8.5% CO 2, 60o F Ambient, 360o F Flue Gas, & Sea Level](https://reader033.vdocument.in/reader033/viewer/2022050518/5fa21d17dda75147ff7326ed/html5/thumbnails/37.jpg)
Chimney Flue - EPS
• Welded continuous
construction
• Integral flange at each end
• Male insert for easy
centering and assembly
• Graphite seal (no messy
silicone sealant)
![Page 38: Fundamentals of Making Energy-Saving and Cost-Efficient ... · Chimney Design 1996 Edition Chimney Equation Default Values: 8.5% CO 2, 60o F Ambient, 360o F Flue Gas, & Sea Level](https://reader033.vdocument.in/reader033/viewer/2022050518/5fa21d17dda75147ff7326ed/html5/thumbnails/38.jpg)
Chimney Flue - EPS
• Easy and accurate
assembly
• Hinged v-band
![Page 39: Fundamentals of Making Energy-Saving and Cost-Efficient ... · Chimney Design 1996 Edition Chimney Equation Default Values: 8.5% CO 2, 60o F Ambient, 360o F Flue Gas, & Sea Level](https://reader033.vdocument.in/reader033/viewer/2022050518/5fa21d17dda75147ff7326ed/html5/thumbnails/39.jpg)
Generator & Engine Exhaust
• NFPA37, Standard for
Emergency Generators
• 60” (1500mm) W.C.
pressure capability
• 1400°F (760°C)
• 2-4” (25-100mm) insulation
![Page 40: Fundamentals of Making Energy-Saving and Cost-Efficient ... · Chimney Design 1996 Edition Chimney Equation Default Values: 8.5% CO 2, 60o F Ambient, 360o F Flue Gas, & Sea Level](https://reader033.vdocument.in/reader033/viewer/2022050518/5fa21d17dda75147ff7326ed/html5/thumbnails/40.jpg)
Boiler Exhaust
• UL103 Building Heating
Chimney
• UL1738 Chimney for
Condensing Heating
Appliances
• 60” (1500mm) W.C.
pressure capability
• 1400°F (760°C)
![Page 41: Fundamentals of Making Energy-Saving and Cost-Efficient ... · Chimney Design 1996 Edition Chimney Equation Default Values: 8.5% CO 2, 60o F Ambient, 360o F Flue Gas, & Sea Level](https://reader033.vdocument.in/reader033/viewer/2022050518/5fa21d17dda75147ff7326ed/html5/thumbnails/41.jpg)
Kitchen Exhaust
• UL 1978 Grease Duct
Exhaust System
• Thermal expansion
compensation
• Clean-out access
• No welding
• Easy hood and fan
connection
![Page 42: Fundamentals of Making Energy-Saving and Cost-Efficient ... · Chimney Design 1996 Edition Chimney Equation Default Values: 8.5% CO 2, 60o F Ambient, 360o F Flue Gas, & Sea Level](https://reader033.vdocument.in/reader033/viewer/2022050518/5fa21d17dda75147ff7326ed/html5/thumbnails/42.jpg)
Space Saving & Aesthetics
![Page 43: Fundamentals of Making Energy-Saving and Cost-Efficient ... · Chimney Design 1996 Edition Chimney Equation Default Values: 8.5% CO 2, 60o F Ambient, 360o F Flue Gas, & Sea Level](https://reader033.vdocument.in/reader033/viewer/2022050518/5fa21d17dda75147ff7326ed/html5/thumbnails/43.jpg)
Space Saving
![Page 44: Fundamentals of Making Energy-Saving and Cost-Efficient ... · Chimney Design 1996 Edition Chimney Equation Default Values: 8.5% CO 2, 60o F Ambient, 360o F Flue Gas, & Sea Level](https://reader033.vdocument.in/reader033/viewer/2022050518/5fa21d17dda75147ff7326ed/html5/thumbnails/44.jpg)
Space Saving
![Page 45: Fundamentals of Making Energy-Saving and Cost-Efficient ... · Chimney Design 1996 Edition Chimney Equation Default Values: 8.5% CO 2, 60o F Ambient, 360o F Flue Gas, & Sea Level](https://reader033.vdocument.in/reader033/viewer/2022050518/5fa21d17dda75147ff7326ed/html5/thumbnails/45.jpg)
Aesthetics
![Page 46: Fundamentals of Making Energy-Saving and Cost-Efficient ... · Chimney Design 1996 Edition Chimney Equation Default Values: 8.5% CO 2, 60o F Ambient, 360o F Flue Gas, & Sea Level](https://reader033.vdocument.in/reader033/viewer/2022050518/5fa21d17dda75147ff7326ed/html5/thumbnails/46.jpg)
Design Freedom
![Page 47: Fundamentals of Making Energy-Saving and Cost-Efficient ... · Chimney Design 1996 Edition Chimney Equation Default Values: 8.5% CO 2, 60o F Ambient, 360o F Flue Gas, & Sea Level](https://reader033.vdocument.in/reader033/viewer/2022050518/5fa21d17dda75147ff7326ed/html5/thumbnails/47.jpg)
Crowded Boiler Rooms
![Page 48: Fundamentals of Making Energy-Saving and Cost-Efficient ... · Chimney Design 1996 Edition Chimney Equation Default Values: 8.5% CO 2, 60o F Ambient, 360o F Flue Gas, & Sea Level](https://reader033.vdocument.in/reader033/viewer/2022050518/5fa21d17dda75147ff7326ed/html5/thumbnails/48.jpg)
Redundancy for Critical Installations
![Page 49: Fundamentals of Making Energy-Saving and Cost-Efficient ... · Chimney Design 1996 Edition Chimney Equation Default Values: 8.5% CO 2, 60o F Ambient, 360o F Flue Gas, & Sea Level](https://reader033.vdocument.in/reader033/viewer/2022050518/5fa21d17dda75147ff7326ed/html5/thumbnails/49.jpg)
Energy Savings
Demand-Controlled boiler exhaust system
Demand-Controlled boiler exhaust System with Heat Recovery
![Page 50: Fundamentals of Making Energy-Saving and Cost-Efficient ... · Chimney Design 1996 Edition Chimney Equation Default Values: 8.5% CO 2, 60o F Ambient, 360o F Flue Gas, & Sea Level](https://reader033.vdocument.in/reader033/viewer/2022050518/5fa21d17dda75147ff7326ed/html5/thumbnails/50.jpg)
Case Studies/Design Examples
How to get the most out of a creative design ……
![Page 51: Fundamentals of Making Energy-Saving and Cost-Efficient ... · Chimney Design 1996 Edition Chimney Equation Default Values: 8.5% CO 2, 60o F Ambient, 360o F Flue Gas, & Sea Level](https://reader033.vdocument.in/reader033/viewer/2022050518/5fa21d17dda75147ff7326ed/html5/thumbnails/51.jpg)
Burj KhalifaTower / Armani Hotel,
Dubai
Six Demand Controlled Boiler Exhaust
Systems servicing horizontal venting for side
wall termination providing the
engineers full
flexibility in the
design
![Page 52: Fundamentals of Making Energy-Saving and Cost-Efficient ... · Chimney Design 1996 Edition Chimney Equation Default Values: 8.5% CO 2, 60o F Ambient, 360o F Flue Gas, & Sea Level](https://reader033.vdocument.in/reader033/viewer/2022050518/5fa21d17dda75147ff7326ed/html5/thumbnails/52.jpg)
Khalidiya Palace, Abu Dhabi
Three boilers common vented with a
Demand Controlled Boiler Exhaust
System using an inline boiler exhaust
fan. Savings on material cost over $
30,000
![Page 53: Fundamentals of Making Energy-Saving and Cost-Efficient ... · Chimney Design 1996 Edition Chimney Equation Default Values: 8.5% CO 2, 60o F Ambient, 360o F Flue Gas, & Sea Level](https://reader033.vdocument.in/reader033/viewer/2022050518/5fa21d17dda75147ff7326ed/html5/thumbnails/53.jpg)
Capital Plaza (Sofitel Hotel), Abu
Dhabi Four boilers common vented with a Demand
Controlled Boiler Exhaust System using an
inline boiler exhaust fan. Savings on material
cost over $ 60,000
![Page 54: Fundamentals of Making Energy-Saving and Cost-Efficient ... · Chimney Design 1996 Edition Chimney Equation Default Values: 8.5% CO 2, 60o F Ambient, 360o F Flue Gas, & Sea Level](https://reader033.vdocument.in/reader033/viewer/2022050518/5fa21d17dda75147ff7326ed/html5/thumbnails/54.jpg)
Jumeirah Creekside Hotel, Dubai
Four boilers common vented with a
Demand Controlled Boiler Exhaust
System using an inline boiler exhaust
fan. Savings on material cost over $
60,000.
![Page 55: Fundamentals of Making Energy-Saving and Cost-Efficient ... · Chimney Design 1996 Edition Chimney Equation Default Values: 8.5% CO 2, 60o F Ambient, 360o F Flue Gas, & Sea Level](https://reader033.vdocument.in/reader033/viewer/2022050518/5fa21d17dda75147ff7326ed/html5/thumbnails/55.jpg)
Why is This Attractive?
• Single supplier responsibility.
• Space savings = cost savings
• Small footprint = less space required
• Save energy and reduce emissions
• Improve boiler room safety
• Enhance aesthetics
Make the unimaginable and impossible
POSSIBLE.
![Page 56: Fundamentals of Making Energy-Saving and Cost-Efficient ... · Chimney Design 1996 Edition Chimney Equation Default Values: 8.5% CO 2, 60o F Ambient, 360o F Flue Gas, & Sea Level](https://reader033.vdocument.in/reader033/viewer/2022050518/5fa21d17dda75147ff7326ed/html5/thumbnails/56.jpg)
A Final Note
“Chimney system must be designed/approved/supplied by boiler
manufacturer”
Let boiler experts deal with the boiler design
Let chimney design experts deal with the chimney design
![Page 57: Fundamentals of Making Energy-Saving and Cost-Efficient ... · Chimney Design 1996 Edition Chimney Equation Default Values: 8.5% CO 2, 60o F Ambient, 360o F Flue Gas, & Sea Level](https://reader033.vdocument.in/reader033/viewer/2022050518/5fa21d17dda75147ff7326ed/html5/thumbnails/57.jpg)
Questions?