MCEER: Earthquake Engineering to Extreme Events by Shoma Kitayama and Michael C. Constantinou Technical Report MCEER-20-0002 June 30, 2020 Further Results on the Assessment of Performance of Seismically Isolated Electrical Transformers

Upload: others

Post on 30-Oct-2020

0 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

MCEER: Earthquake Engineering to Extreme Events

byShoma Kitayama and Michael C. Constantinou

Technical Report MCEER-20-0002

June 30, 2020

Further Results on the Assessment of Performance of Seismically Isolated

Electrical Transformers

Page 2: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

NOTICEThis report was prepared by the University at Buff alo, The State University of New York, as a result of research sponsored by MCEER. Neither MCEER, associates of MCEER, its sponsors, University at Buff alo, The State University of New York, nor any person acting on their behalf:

a. makes any warranty, express or implied, with respect to the use of any information, apparatus, method, or process disclosed in this report or that such use may not infringe upon privately owned rights; or

b. assumes any liabilities of whatsoever kind with respect to the use of, or the damage resulting from the use of, any information, apparatus, method, or process disclosed in this report.

Any opinions, fi ndings, and conclusions or recommendations expressed in this publication are those of the author(s) and do not necessarily refl ect the views of MCEER, the National Science Foundation or other sponsors.

Page 3: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

  

Further Results on the Assessment of Performance of Seismically Isolated

Electrical Transformers

by

Shoma Kitayama1 and Michael C. Constantinou2

Publication Date: June 30, 2020 Submittal Date: October 16, 2019

Technical Report MCEER-20-0002

1. Postdoctoral Associate, Department of Civil, Structural and Environmental Engineering, University at Buffalo, The State University of New York

2 Samuel P. Capen Professor, SUNY Distinguished Professor, Department of Civil, Structural and Environmental Engineering, University at Buffalo, The State University of New York

MCEER: Earthquake Engineering to Extreme Events University at Buffalo, The State University of New York

212 Ketter Hall, Buffalo, NY 14260 [email protected]; buffalo.edu/mceer

Page 4: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on
Page 5: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

iii  

Preface MCEER is a national center of excellence dedicated to the discovery and development of new knowledge, tools and technologies that equip communities to become more disaster resilient in the face of earthquakes and other extreme events. MCEER accomplishes this through a system of multidisciplinary, multi-hazard research, in tandem with complimentary education and outreach initiatives. Headquartered at the University at Buffalo, The State University of New York, MCEER was originally established by the National Science Foundation in 1986, as the first National Center for Earthquake Engineering Research (NCEER). In 1998, it became known as the Multidisciplinary Center for Earthquake Engineering Research (MCEER), from which the current name, MCEER, evolved. Comprising a consortium of researchers and industry partners from numerous disciplines and institutions throughout the United States, MCEER’s mission has expanded from its original focus on earthquake engineering to one which addresses the technical and socio-economic impacts of a variety of hazards, both natural and man-made, on critical infrastructure, facilities, and society. The Center derives support from several Federal agencies, including the National Science Foundation, Federal Highway Administration, Department of Energy, Nuclear Regulatory Commission, and the State of New York, foreign governments and private industry.

This report presents results on the probability of failure in a lifetime of 50 years of non‐isolated and seismically isolated transformers at ten locations in the Western US. This study considers: (a) scaling the ground motions for use in the incremental dynamic analysis by adjusting the spectral acceleration at the fundamental period (or effective period for isolated transformers) instead of the peak ground acceleration (PGA) in the earlier studies, (b) correcting for the spectral shape effects, which were ignored in the earlier studies, and (c) accounting for uncertainties, which were neglected in earlier studies. Moreover, the report presents sample results for near‐field motions, which do not differ much from the results obtained for far‐field motions. The results of this report, documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on the location of the transformer and the form and properties of the seismic isolation system. The benefit is assessed on the basis of the probability of failure in a lifetime of 50 years. The information may also be used to assess the seismic performance of electric transmission networks under scenarios of component failures.

Page 6: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on
Page 7: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

iii

PREFACE

MCEER is a national center of excellence dedicated to the discovery and development of 

new knowledge, tools and technologies that equip communities to become more disaster 

resilient in the face of earthquakes and other extreme events. MCEER accomplishes this 

through  a  system  of  multidisciplinary,  multi‐hazard  research,  in  tandem  with 

complimentary education and outreach initiatives. 

Headquartered at the University at Buffalo, The State University of New York, MCEER 

was  originally  established  by  the National  Science  Foundation  in  1986,  as  the  fi  rst 

National  Center  for  Earthquake  Engineering  Research  (NCEER).  In  1998,  it  became 

known as the Multidisciplinary Center for Earthquake Engineering Research (MCEER), 

from which the current name, MCEER, evolved. 

Comprising  a  consortium  of  researchers  and  industry  partners  from  numerous 

disciplines  and  institutions  throughout  the  United  States,  MCEER’s  mission  has 

expanded from its original focus on earthquake engineering to one which addresses the 

technical and socioeconomic impacts of a variety of hazards, both natural and man‐made, 

on critical infrastructure, facilities, and society. 

The Center derives support from several Federal agencies, including the National Science 

Foundation,  Federal  Highway  Administration,  National  Institute  of  Standards  and 

Technology,  Department  of  Homeland  Security/Federal  Emergency  Management 

Agency,  and  the  State  of New York,  other  state  governments,  academic  institutions, 

foreign governments and private industry. 

This report presents results on the probability of failure in a lifetime of 50 years of non‐

isolated and seismically  isolated  transformers at  ten  locations  in  the Western US. This 

study  considers:  (a)  scaling  the  ground motions  for  use  in  the  incremental  dynamic 

analysis by adjusting  the  spectral acceleration at  the  fundamental period  (or effective 

period for  isolated transformers)  instead of the peak ground acceleration (PGA)  in the 

earlier studies,  (b) correcting  for  the spectral shape effects, which were  ignored  in  the 

earlier  studies,  and  (c)  accounting  for  uncertainties, which were  neglected  in  earlier 

studies. Moreover, the report presents sample results for near‐field motions, which do 

not much differ from the results obtained for far‐field motions. The results of this report, 

documented  in numerous  tables, may be used  to decide on  the benefits offered by a 

seismic isolation system depending on the location of the transformer and the form and 

properties of  the seismic  isolation system.   The benefit  is assessed on  the basis of  the 

probability of failure in 50 years of lifetime.  The information may also be used to assess 

Page 8: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on
Page 9: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

v

ABSTRACT

This report presents results on the probability of failure in a lifetime of 50 years of non-isolated and

seismically isolated transformers at ten locations in the Western US. This report presents an investigation

of the limitations of past studies by considering: (a) scaling the ground motions for use in the incremental

dynamic analysis by adjusting the spectral acceleration at the fundamental period (or effective period for

isolated transformers) instead of the peak ground acceleration (PGA) in the earlier studies, (b) correcting

for the spectral shape effects, which were ignored in the earlier studies, and (c) accounting for uncertainties,

which were neglected in earlier studies. Moreover, the report presents sample results for near-field motions,

which however, could not be corrected for spectral shape effects.

Results obtained for far-field motions show that, in general, scaling of the ground motions based on the

spectral acceleration at the fundamental period or the effective period results in significant increases in the

probability of failure for the isolated transformers, which are significantly moderated by corrections for the

spectral shape effects. By comparison, the changes in the probability of failure of the studied non-isolated

transformers were small due to the fact that the fundamental period was very small so that the spectral

acceleration at the fundamental period was very close to the PGA which was used in the earlier studies for

the scaling.

Based on the new results in this report, combined horizontal-vertical seismic isolation systems offer the

lowest probabilities of failure for all cases of transformer and isolation system parameters, and for all

considered sites. Horizontal only isolation offers no or offers insignificant advantages over non-isolation

when the bushing transverse acceleration limit is 2g. However, horizontal only isolation offers important

advantages over non-isolation when the bushing transverse acceleration limit is 1g.

The results of this report, documented in numerous tables, may be used to decide on the benefits offered by

a seismic isolation system depending on the location of the transformer and the form and properties of the

seismic isolation system. The benefit is assessed on the basis of the probability of failure in 50 years of

lifetime. The information may also be used to assess the seismic performance of electric transmission

networks under scenarios of component failures.

Page 10: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on
Page 11: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

vii

ACKNOWLEDGEMENTS

This work was made possible with financial support by the Bonneville Power Administration (BPA) with

Dr. Leon Kempner, Jr. as the responsible technical officer. This support is gratefully acknowledged.

Page 12: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on
Page 13: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

ix

TABLE OF CONTENTS

SECTION 1  INTRODUCTION ............................................................................................................ 1 

SECTION 2  EVALUATING THE EFFECT OF SEISMIC GROUND MOTION INTENSITY

MEASURES ON FRAGILITY ................................................................................................................ 13 

SECTION 3  EFFECT OF SPECTRAL SHAPE ON THE FRAGILITY OF ELECTRICAL

TRANSFORMERS ......................................................................................................... 37 

SECTION 4  CONSIDERATIONS FOR UNCERTAINTIES .......................................................... 71 

SECTION 5  SUMMARY OF RESULTS FOR FAR-FIELD MOTIONS ....................................... 77 

SECTION 6  RESULTS FOR NEAR-FIELD MOTIONS ............................................................... 139 

SECTION 7  SUMMARY AND CONCLUSIONS ........................................................................... 147 

SECTION 8  REFERENCES .............................................................................................................. 149 

APPENDIX A  PROCEDURE FOR CONSIDERATION OF SPECTRAL SHAPE EFFECTS AND

RESULTS ........................................................................................................................................ 153 

A.1 Introduction ..................................................................................................................... 153 

A.2 Procedure for Correction for Spectral Shape Effects ...................................................... 155 

Page 14: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on
Page 15: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

xi

LIST OF FIGURES

Figure 1-1 Section of smallest isolator with displacement capacity DCapacity=17.7inch ........................... 4 

Figure 1-2 Section of largest isolator with displacement capacity DCapacity=31.3inch ............................. 4 

Figure 1-3 Location of transformers considered in this study ...................................................................... 5 

Figure 1-4 Seismic hazard curves for zero, 0.1, 0.2, 2 and 3sec period at Vancouver, WA ......................... 6 

Figure 1-5 Seismic hazard curves for zero, 0.1, 0.2, 2 and 3sec period at Saranap, CA .............................. 6 

Figure 1-6 Seismic hazard curves for zero, 0.1, 0.2, 2 and 3sec period at Loma Linda, CA ........................ 7 

Figure 1-7 Seismic hazard curves for zero, 0.1, 0.2, 2 and 3sec period at Aberdeen, WA ........................... 7 

Figure 1-8 Seismic hazard curves for zero, 0.1, 0.2, 2 and 3sec period at Chehalis, WA ............................ 8 

Figure 1-9 Seismic hazard curves for zero, 0.1, 0.2, 2 and 3sec period at Hillsboro, OR ............................ 8 

Figure 1-10 Seismic hazard curves for zero, 0.1, 0.2, 2 and 3sec period at Eugene, OR ............................. 9 

Figure 1-11 Seismic hazard curves for zero, 0.1, 0.2, 2 and 3sec period at Wilsonville, OR ....................... 9 

Figure 1-12 Seismic hazard curves for zero, 0.1, 0.2, 2 and 3sec period at Curry County, OR ................. 10 

Figure 1-13 Seismic hazard curves for zero, 0.1, 0.2, 2 and 3sec period at Troutdale, OR ........................ 10

Figure 2-1 Scaling of ground motions so that the spectral acceleration values of the horizontal components

are the same at zero period (left) and at period Ti (right) .......................................................... 13 

Figure 2-2 Probability of failure in lifetime of 50 years of non-isolated transformer (W=420kip, fAI=7.7Hz,

inclined bushing) located at Chehalis, WA as function of period used for scaling the ground

motions ...................................................................................................................................... 18 

Figure 2-3 Probability of failure in lifetime of 50 years of horizontally isolated transformer (W=420kip,

fAI=7.7Hz, inclined bushing, DCapacity=17.7inch, lower bound) located at Chehalis, WA as

function of period used for scaling the ground motions ........................................................... 18 

Figure 2-4 Probability of failure in lifetime of 50 years of horizontally-vertically isolated transformer

without rocking (W=420kip, fAI=7.7Hz, inclined bushing, DCapacity=17.7inch, lower bound)

located at Chehalis, WA as function of period used for scaling the ground motions ................ 19 

Figure 2-5 Probability of failure in lifetime of 50 years of horizontally-vertically isolated transformer with

rocking (W=420kip, fAI=7.7Hz, inclined bushing, DCapacity=17.7inch, lower bound) located at

Chehalis, WA as function of period used for scaling the ground motions ................................ 19 

Figure 2-6 Probability of failure in lifetime of 50 years of non-isolated transformer (W=420kip, fAI=7.7Hz,

inclined bushing) located at Loma Linda, CA as function of period used for scaling the ground

motions ...................................................................................................................................... 20 

Page 16: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

xii

LIST OF FIGURES (CONT'D)

Figure 2-7 Probability of failure in lifetime of 50 years of horizontally isolated transformer (W=420kip,

fAI=7.7Hz, inclined bushing, DCapacity=17.7inch, lower bound) located at Loma Linda, CA as

function of period used for scaling the ground motion ............................................................ 20 

Figure 2-8 Probability of failure in lifetime of 50 years of horizontally-vertically isolated transformer

without rocking (W=420kip, fAI=7.7Hz, inclined bushing, DCapacity=17.7inch, lower bound)

located at Loma Linda, CA as function of period used for scaling the ground motions ........... 21 

Figure 2-9 Probability of failure in lifetime of 50 years of horizontally-vertically isolated transformer with

rocking (W=420kip, fAI=7.7Hz, inclined bushing, DCapacity=17.7inch, lower bound) located at

Loma Linda, CA as function of period used for scaling the ground motions ........................... 21 

Figure 2-10 Probability of failure in lifetime of 50 years of non-isolated transformer (W=420kip, fAI=7.7Hz,

inclined bushing) located at Troutdale, OR as function of period used for scaling the ground

motions .................................................................................................................................... 22 

Figure 2-11 Probability of failure in lifetime of 50 years of horizontally isolated transformer (W=420kip,

fAI=7.7Hz, inclined bushing, DCapacity=17.7inch, lower bound) located at Troutdale, OR as

function of period used for scaling the ground motions .......................................................... 22 

Figure 2-12 Probability of failure in lifetime of 50 years of horizontally-vertically isolated transformer

without rocking (W=420kip, fAI=7.7Hz, inclined bushing, DCapacity=17.7inch, lower bound)

located at Troutdale, OR as function of period used for scaling the ground motions ............. 23 

Figure 2-13 Probability of failure in lifetime of 50 years of horizontally-vertically isolated transformer with

rocking (W=420kip, fAI=7.7Hz, inclined bushing, DCapacity=17.7inch, lower bound) located at

Troutdale, OR as function of period used for scaling the ground motions ............................. 23 

Figure 2-14 Probability of failure in lifetime of 50 years of non-isolated transformer (W=420kip, fAI=4.3Hz,

inclined bushing) located at Chehalis, WA as function of period used for scaling the ground

motions .................................................................................................................................... 24 

Figure 2-15 Probability of failure in lifetime of 50 years of horizontally isolated transformer (W=420kip,

fAI=4.3Hz, inclined bushing, DCapacity=17.7inch, lower bound) located at Chehalis, WA as

function of period used for scaling the ground motions ......................................................... 24 

Figure 2-16 Probability of failure in lifetime of 50 years of horizontally-vertically isolated transformer

without rocking (W=420kip, fAI=4.3Hz, inclined bushing, DCapacity=17.7inch, lower bound)

located at Chehalis, WA as function of period used for scaling the ground motions ............. 25 

Figure 2-17 Probability of failure in lifetime of 50 years of horizontally-vertically isolated transformer with

rocking (W=420kip, fAI=4.3Hz, inclined bushing, DCapacity=17.7inch, lower bound) located at

Page 17: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

xiii

LIST OF FIGURES (CONT'D)

Chehalis, WA as function of period used for scaling the ground motions.............................. 25 

Figure 2-18 Probability of failure in lifetime of 50 years of non-isolated transformer (W=420kip, fAI=4.3Hz,

inclined bushing) located at Loma Linda, CA as function of period used for scaling the ground

motions .................................................................................................................................... 26 

Figure 2-19 Probability of failure in lifetime of 50 years of horizontally isolated transformer (W=420kip,

fAI=4.3Hz, inclined bushing, DCapacity=17.7inch, lower bound) located at Loma Linda, CA as

function of period used for scaling the ground motions ......................................................... 26 

Figure 2-20 Probability of failure in lifetime of 50 years of horizontally-vertically isolated transformer

without rocking (W=420kip, fAI=4.3Hz, inclined bushing, DCapacity=17.7inch, lower bound)

located at Loma Linda, CA as function of period used for scaling the ground motions ......... 27 

Figure 2-21 Probability of failure in lifetime of 50 years of horizontally-vertically isolated transformer with

rocking (W=420kip, fAI=4.3Hz, inclined bushing, DCapacity=17.7inch, lower bound) located at

Loma Linda, CA as function of period used for scaling the ground motions ......................... 27 

Figure 2-22 Probability of failure in lifetime of 50 years of non-isolated transformer (W=420kip, fAI=4.3Hz,

inclined bushing) located at Troutdale, OR as function of period used for scaling the ground

motions .................................................................................................................................... 28 

Figure 2-23 Probability of failure in lifetime of 50 years of horizontally isolated transformer (W=420kip,

fAI=4.3Hz, inclined bushing, DCapacity=17.7inch, lower bound) located at Troutdale, OR as

function of period used for scaling the ground motions .......................................................... 28 

Figure 2-24 Probability of failure in lifetime of 50 years of horizontay-vertically isolated transformer

without rocking (W=420kip, fAI=4.3Hz, inclined bushing, DCapacity=17.7inch, lower bound)

located at Troutdale, OR as function of period used for scaling the ground motions ............. 29 

Figure 2-25 Probability of failure in lifetime of 50 years of horizontally-vertically isolated transformer with

rocking (W=420kip, fAI=4.3Hz, inclined bushing, DCapacity=17.7inch, lower bound) located at

Troutdale, OR as function of period used for scaling the ground motions ............................. 29 

Figure 2-26 Probability of failure in lifetime of 50 years of non-isolated transformer (W=420kip,

fAI=11.3Hz, inclined bushing) located at Chehalis, WA as function of period used for scaling

the ground motions ................................................................................................................. 30 

Figure 2-27 Probability of failure in lifetime of 50 years of horizontally isolated transformer (W=420kip,

fAI=11.3Hz, inclined bushing, DCapacity=17.7inch, lower bound) located at Chehalis, WA as

function of period used for scaling the ground motions ......................................................... 30 

Figure 2-28 Probability of failure in lifetime of 50 years of horizontally-vertically isolated transformer

Page 18: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

xiv

LIST OF FIGURES (CONT'D)

without rocking (W=420kip, fAI=11.3Hz, inclined bushing, DCapacity=17.7inch, lower bound)

located at Chehalis, WA as function of period used for scaling the ground motions ............. 31 

Figure 2-29 Probability of failure in lifetime of 50 years of horizontally-vertically isolated transformer with

rocking (W=420kip, fAI=11.3Hz, inclined bushing, DCapacity=17.7inch, lower bound) located at

Chehalis, WA as function of period used for scaling the ground motions.............................. 31 

Figure 2-30 Probability of failure in lifetime of 50 years of non-isolated transformer (W=420kip,

fAI=11.3Hz, inclined bushing) located at Loma Linda, CA as function of period used for scaling

the ground motion ................................................................................................................... 32 

Figure 2-31 Probability of failure in lifetime of 50 years of horizontally isolated transformer (W=420kip,

fAI=11.3Hz, inclined bushing, DCapacity=17.7inch, lower bound) located at Loma Linda, CA as

function of period used for scaling the ground motions ......................................................... 32 

Figure 2-32 Probability of failure in lifetime of 50 years of horizontally-vertically isolated transformer

without rocking (W=420kip, fAI=11.3Hz, inclined bushing, DCapacity=17.7inch, lower bound)

located at Loma Linda, CA as function of period used for scaling the ground motions ......... 33 

Figure 2-33 Probability of failure in lifetime of 50 years of horizontally-vertically isolated transformer with

rocking (W=420kip, fAI=11.3Hz, inclined bushing, DCapacity=17.7inch, lower bound) located at

Loma Linda, CA as function of period used for scaling the ground motions .......................... 33 

Figure 2-34 Probability of failure in lifetime of 50 years of non-isolated transformer (W=420kip,

fAI=11.3Hz, inclined bushing) located at Troutdale, OR as function of period used for scaling

the ground motions .................................................................................................................. 34 

Figure 2-35 Probability of failure in lifetime of 50 years of horizontally isolated transformer (W=420kip,

fAI=11.3Hz, inclined bushing, DCapacity=17.7inch, lower bound) located at Troutdale, OR as

function of period used for scaling the ground motions ......................................................... 34 

Figure 2-36 Probability of failure in lifetime of 50 years of horizontally-vertically isolated transformer

without rocking (W=420kip, fAI=11.3Hz, inclined bushing, DCapacity=17.7inch, lower bound)

located at Troutdale, OR as function of period used for scaling the ground motions .............. 35 

Figure 2-37 Probability of failure in lifetime of 50 years of horizontally-vertically isolated transformer with

rocking (W=420kip, fAI=11.3Hz, inclined bushing, DCapacity=17.7inch, lower bound) located at

Troutdale, OR as function of period used for scaling the ground motions ............................. 35

Figure 5-1 Probabilities of failure in 50 years for non-isolated and horizontally isolated transformers with

transverse bushing acceleration limit of 1g (case of RTR≤0.4) for ten sites ........................... 138

Page 19: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

xv

LIST OF FIGURES (CONT'D)

Figure 6-1 Horizontal acceleration response spectra of selected 25 near-field ground motions (total of 50

components) ............................................................................................................................ 141 

Figure 6-2 Vertical acceleration response spectra of selected 25 near-field ground motions (total of 25

components) ............................................................................................................................ 141 

Figure 6-3 Vertical to horizontal average spectral (V/H) ratio of 50 sets of near-field motions .............. 142 

Figure A-1 Comparison of observed and predicted response spectra (from FEMA, 2009 and Haselton and

Baker, 2006) ............................................................................................................................ 154 

Figure A-2 Response spectra of FEMA far-field motions and predicted median spectra at Chehalis, WA

location .................................................................................................................................... 157 

Figure A-3 Response spectra of FEMA far-field motions and predicted median spectra at Loma Linda, CA

location .................................................................................................................................... 157 

Figure A-4 Response spectra of FEMA far-field motions and predicted median spectra at Troutdale, OR

location .................................................................................................................................... 158 

Figure A-5 Standard deviation of natural logarithm of spectral acceleration at Chehalis, WA ............... 158 

Figure A-6 Standard deviation of natural logarithm of spectral acceleration at Loma Linda, CA ........... 158 

Figure A-7 Standard deviation of natural logarithm of spectral acceleration at Troutdale, OR ............... 159 

Figure A-8 Calculated values of j(T1) for the 40 ground motions used in analysis for Chehalis, WA location

............................................................................................................................................... 159 

Figure A-9 Calculated values of j(T1) for the 40 ground motions used in analysis for Loma Linda, CA

location .................................................................................................................................... 159 

Figure A-10 Calculated values of j(T1) for the 40 ground motions used in analysis for Troutdale, OR

location .................................................................................................................................... 160 

Figure A-11 Relationship between ln[SaCol,j(T1)] and j(T1) of non-isolated transformer with bushing of

7.7Hz as-installed frequency at Chehalis, WA ....................................................................... 160 

Figure A-12 Relationship between ln[SaCol,j(T1)] and j(T1) of horizontally isolated transformer

(DCapacity=17.7inch, lower bound) with as-installed bushing frequency of 7.7Hz at Chehalis,

WA ........................................................................................................................................ 161 

Figure A-13 Relationship between ln[SaCol,j(T1)] and j(T1) of horizontally-vertically isolated without

rocking transformer (DCapacity=17.7inch, lower bound) with as-installed bushing frequency of

7.7Hz at Chehalis, WA ........................................................................................................ 161 

Page 20: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

xvi

LIST OF FIGURES (CONT'D)

Figure A-14 Relationship between ln[SaCol,j(T1)] and j(T1) of non-isolated transformer with bushing of

4.3Hz as-installed frequency at Chehalis, WA .................................................................... 162 

Figure A-15 Relationship between ln[SaCol,j(T1)] and j(T1) of non-isolated transformer with bushing of

4.3Hz as-installed frequency at Chehalis, WA ..................................................................... 162 

Figure A-16 Relationship between ln[SaCol,j(T1)] and j(T1) of horizontally isolated transformer

(DCapacity=17.7inch, lower bound) with as-installed bushing frequency of 4.3Hz at Chehalis,

WA ........................................................................................................................................ 163 

Figure A-17 Relationship between ln[SaCol,j(T1)] and j(T1) of horizontally-vertically isolated without

rocking transformer (DCapacity=17.7inch, lower bound) with as-installed bushing frequency of

4.3Hz at Chehalis, WA ........................................................................................................ 163 

Figure A-18 Relationship between ln[SaCol,j(T1)] and j(T1) of horizontally-vertically isolated with rocking

transformer (DCapacity=17.7inch, lower bound) with as-installed bushing frequency of 4.3Hz at

Chehalis, WA ...................................................................................................................... 164 

Figure A-19 Relationship between ln[SaCol,j(T1)] and j(T1) of non-isolated transformer with bushing of

11.3Hz as-installed frequency at Chehalis, WA .................................................................. 164 

Figure A-20 Relationship between ln[SaCol,j(T1)] and j(T1) of horizontally isolated transformer

(DCapacity=17.7inch, lower bound) with as-installed bushing frequency of 11.3Hz at Chehalis,

WA ....................................................................................................................................... 165 

Figure A-21 Relationship between ln[SaCol,j(T1)] and j(T1) of horizontally-vertically isolated without

rocking transformer (DCapacity=17.7inch, lower bound) with as-installed bushing frequency of

11.3Hz at Chehalis, WA ...................................................................................................... 165 

Figure A-22 Relationship between ln[SaCol,j(T1)] and j(T1) of horizontally-vertically isolated with rocking

transformer (DCapacity=17.7inch, lower bound) with as-installed bushing frequency of 11.3Hz

at Chehalis, WA ................................................................................................................... 166 

Figure A-23 Relationship between ln[SaCol,j(T1)] and j(T1) of non-isolated transformer with bushing of

7.7Hz as-installed frequency at Loma Linda, CA ................................................................. 166 

Figure A-24 Relationship between ln[SaCol,j(T1)] and j(T1) of horizontally isolated transformer

(DCapacity=17.7inch, lower bound) with as-installed bushing frequency of 7.7Hz at Loma Linda,

CA ........................................................................................................................................ 167 

Figure A-25 Relationship between ln[SaCol,j(T1)] and j(T1) of horizontally-vertically isolated without

rocking transformer (DCapacity=17.7inch, lower bound) with as-installed bushing frequency of

Page 21: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

xvii

LIST OF FIGURES (CONT'D)

7.7Hz at Loma Linda, CA .................................................................................................... 167 

Figure A-26 Relationship between ln[SaCol,j(T1)] and j(T1) of horizontally-vertically isolated with rocking

transformer (DCapacity=17.7inch, lower bound) with as-installed bushing frequency of 7.7Hz at

Loma Linda, CA .................................................................................................................. 168 

Figure A-27 Relationship between ln[SaCol,j(T1)] and j(T1) of non-isolated transformer with bushing of

4.3Hz as-installed frequency at Loma Linda, CA ................................................................ 168 

Figure A-28 Relationship between ln[SaCol,j(T1)] and j(T1) of horizontally isolated transformer

(DCapacity=17.7inch, lower bound) with as-installed bushing frequency of 4.3Hz at Loma Linda,

CA ......................................................................................................................................... 169 

Figure A-29 Relationship between ln[SaCol,j(T1)] and j(T1) of horizontally-vertically isolated without

rocking transformer (DCapacity=17.7inch, lower bound) with as-installed bushing frequency of

4.3Hz at Loma Linda, CA .................................................................................................... 169 

Figure A-30 Relationship between ln[SaCol,j(T1)] and j(T1) of horizontally-vertically isolated with rocking

transformer (DCapacity=17.7inch, lower bound) with as-installed bushing frequency of 4.3Hz at

Loma Linda, CA .................................................................................................................. 170 

Figure A-31 Relationship between ln[SaCol,j(T1)] and j(T1) of non-isolated transformer with bushing of

11.3Hz as-installed frequency at Loma Linda, CA .............................................................. 170 

Figure A-32 Relationship between ln[SaCol,j(T1)] and j(T1) of horizontally isolated transformer

(DCapacity=17.7inch, lower bound) with as-installed bushing frequency of 11.3Hz at Loma

Linda, CA ............................................................................................................................. 171 

Figure A-33 Relationship between ln[SaCol,j(T1)] and j(T1) of horizontally-vertically isolated without

rocking transformer (DCapacity=17.7inch, lower bound) with as-installed bushing frequency of

11.3Hz at Loma Linda, CA .................................................................................................. 171 

Figure A-34 Relationship between ln[SaCol,j(T1)] and j(T1) of horizontally-vertically isolated with rocking

transformer (DCapacity=17.7inch, lower bound) with as-installed bushing frequency of 11.3Hz

at Loma Linda, CA .............................................................................................................. 172 

Figure A-35 Relationship between ln[SaCol,j(T1)] and j(T1) of non-isolated transformer with bushing of

7.7Hz as-installed frequency at Troutdale, OR .................................................................... 172 

Figure A-36 Relationship between ln[SaCol,j(T1)] and j(T1) of horizontally isolated transformer

(DCapacity=17.7inch, lower bound) with as-installed bushing frequency of 7.7Hz at Troutdale,

OR ........................................................................................................................................ 173 

Page 22: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

xviii

LIST OF FIGURES (CONT'D)

Figure A-37 Relationship between ln[SaCol,j(T1)] and j(T1) of horizontally-vertically isolated without

rocking transformer (DCapacity=17.7inch, lower bound) with as-installed bushing frequency of

7.7Hz at Troutdale, OR ........................................................................................................ 173 

Figure A-38 Relationship between ln[SaCol,j(T1)] and j(T1) of horizontally-vertically isolated with rocking

transformer (DCapacity=17.7inch, lower bound) with as-installed bushing frequency of 7.7Hz at

Troutdale, OR ...................................................................................................................... 174 

Figure A-39 Relationship between ln[SaCol,j(T1)] and j(T1) of non-isolated transformer with bushing of

4.3Hz as-installed frequency at Troutdale, OR .................................................................... 174 

Figure A-40 Relationship between ln[SaCol,j(T1)] and j(T1) of horizontally isolated transformer

(DCapacity=17.7inch, lower bound) with as-installed bushing frequency of 4.3Hz at Troutdale,

OR ........................................................................................................................................ 175 

Figure A-41 Relationship between ln[SaCol,j(T1)] and j(T1) of horizontally-vertically isolated without

rocking transformer (DCapacity=17.7inch, lower bound) with as-installed bushing frequency of

4.3Hz at Troutdale, OR ........................................................................................................ 175 

Figure A-42 Relationship between ln[SaCol,j(T1)] and j(T1) of horizontally-vertically isolated with rocking

transformer (DCapacity=17.7inch, lower bound) with as-installed bushing frequency of 4.3Hz at

Troutdale, OR ...................................................................................................................... 176 

Figure A-43 Relationship between ln[SaCol,j(T1)] and j(T1) of non-isolated transformer with bushing of

11.3Hz as-installed frequency at Troutdale, OR .................................................................. 176 

Figure A-44 Relationship between ln[SaCol,j(T1)] and j(T1) of horizontally isolated transformer

(DCapacity=17.7inch, lower bound) with as-installed bushing frequency of 11.3Hz at Troutdale,

OR ........................................................................................................................................ 177 

Figure A-45 Relationship between ln[SaCol,j(T1)] and j(T1) of horizontally-vertically isolated without

rocking transformer (DCapacity=17.7inch, lower bound) with as-installed bushing frequency of

11.3Hz at Troutdale, OR ...................................................................................................... 177 

Figure A-46 Relationship between ln[SaCol,j(T1)] and j(T1) of horizontally-vertically isolated with rocking

transformer (DCapacity=17.7inch, lower bound) with as-installed bushing frequency of 11.3Hz

at Troutdale, OR ................................................................................................................... 178 

Page 23: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

xix

LIST OF TABLES

Table 1-1 Properties of bushings used in study (after Kitayama et al., 2016) .............................................. 2 

Table 3-1 Summary of results for probability of failure for isolated and non-isolated transformer with

W=420kip, fAI=7.7Hz and inclined bushing. When isolated, DCapacity=17.7inch and lower bound

friction properties. Location: Vancouver, WA .......................................................................... 40 

Table 3-2 Summary of results for probability of failure for isolated and non-isolated transformer with

W=420kip, fAI=7.7Hz and inclined bushing. When isolated, DCapacity=17.7inch and lower bound

friction properties. Location: Saranap, CA ................................................................................ 40 

Table 3-3 Summary of results for probability of failure for isolated and non-isolated transformer with

W=420kip, fAI=7.7Hz and inclined bushing. When isolated, DCapacity=17.7inch and lower bound

friction properties. Location: Loma Linda, CA ......................................................................... 41 

Table 3-4 Summary of results for probability of failure for isolated and non-isolated transformer with

W=420kip, fAI=7.7Hz and inclined bushing. When isolated, DCapacity=17.7inch and lower bound

friction properties. Location: Aberdeen, WA ............................................................................ 41 

Table 3-5 Summary of results for probability of failure for isolated and non-isolated transformer with

W=420kip, fAI=7.7Hz and inclined bushing. When isolated, DCapacity=17.7inch and lower bound

friction properties. Location: Chehalis, WA .............................................................................. 42 

Table 3-6 Summary of results for probability of failure for isolated and non-isolated transformer with

W=420kip, fAI=7.7Hz and inclined bushing. When isolated, DCapacity=17.7inch and lower bound

friction properties. Location: Hillsboro, OR .............................................................................. 42 

Table 3-7 Summary of results for probability of failure for isolated and non-isolated transformer with

W=420kip, fAI=7.7Hz and inclined bushing. When isolated, DCapacity=17.7inch and lower bound

friction properties. Location: Eugene, OR ................................................................................. 43 

Table 3-8 Summary of results for probability of failure for isolated and non-isolated transformer with

W=420kip, fAI=7.7Hz and inclined bushing. When isolated, DCapacity=17.7inch and lower bound

friction properties. Location: Wilsonville, OR .......................................................................... 43 

Table 3-9 Summary of results for probability of failure for isolated and non-isolated transformer with

W=420kip, fAI=7.7Hz and inclined bushing. When isolated, DCapacity=17.7inch and lower bound

friction properties. Location: Curry County, OR ....................................................................... 44 

Page 24: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

xx

LIST OF TABLES (CONT'D)

Table 3-10 Summary of results for probability of failure for isolated and non-isolated transformer with

W=420kip, fAI=7.7Hz and inclined bushing. When isolated, DCapacity=17.7inch and lower bound

friction properties. Location: Troutdale, OR ............................................................................ 44 

Table 3-11 Summary of results for probability of failure for isolated and non-isolated transformer with

W=420kip, fAI=4.3Hz and inclined bushing. When isolated, DCapacity=17.7inch and lower bound

friction properties. Location: Vancouver, WA ........................................................................ 45 

Table 3-12 Summary of results for probability of failure for isolated and non-isolated transformer with

W=420kip, fAI=4.3Hz and inclined bushing. When isolated, DCapacity=17.7inch and lower bound

friction properties. Location: Saranap, CA .............................................................................. 45 

Table 3-13 Summary of results for probability of failure for isolated and non-isolated transformer with

W=420kip, fAI=4.3Hz and inclined bushing. When isolated, DCapacity=17.7inch and lower bound

friction properties. Location: Chehalis, WA ............................................................................ 46 

Table 3-14 Summary of results for probability of failure for isolated and non-isolated transformer with

W=420kip, fAI=4.3Hz and inclined bushing. When isolated, DCapacity=17.7inch and lower bound

friction properties. Location: Aberdeen, WA .......................................................................... 46 

Table 3-15 Summary of results for probability of failure for isolated and non-isolated transformer with

W=420kip, fAI=4.3Hz and inclined bushing. When isolated, DCapacity=17.7inch and lower bound

friction properties. Location: Loma Linda, CA ....................................................................... 47 

Table 3-16 Summary of results for probability of failure for isolated and non-isolated transformer with

W=420kip, fAI=4.3Hz and inclined bushing. When isolated, DCapacity=17.7inch and lower bound

friction properties. Location: Hillsboro, OR ............................................................................ 47 

Table 3-17 Summary of results for probability of failure for isolated and non-isolated transformer with

W=420kip, fAI=4.3Hz and inclined bushing. When isolated, DCapacity=17.7inch and lower bound

friction properties. Location: Eugene, OR ............................................................................... 48 

Table 3-18 Summary of results for probability of failure for isolated and non-isolated transformer with

W=420kip, fAI=4.3Hz and inclined bushing. When isolated, DCapacity=17.7inch and lower bound

friction properties. Location: Wilsonville, OR ........................................................................ 48 

Table 3-19 Summary of results for probability of failure for isolated and non-isolated transformer with

W=420kip, fAI=4.3Hz and inclined bushing. When isolated, DCapacity=17.7inch and lower bound

friction properties. Location: Curry County, OR ..................................................................... 49 

Page 25: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

xxi

LIST OF TABLES (CONT'D)

Table 3-20 Summary of results for probability of failure for isolated and non-isolated transformer with

W=420kip, fAI=4.3Hz and inclined bushing. When isolated, DCapacity=17.7inch and lower bound

friction properties. Location: Troutdale, OR ............................................................................ 49 

Table 3-21 Summary of results for probability of failure for isolated and non-isolated transformer with

W=420kip, fAI=11.3Hz and inclined bushing. When isolated, DCapacity=17.7inch and lower

bound friction properties. Location: Vancouver, WA.............................................................. 50 

Table 3-22 Summary of results for probability of failure for isolated and non-isolated transformer with

W=420kip, fAI=11.3Hz and inclined bushing. When isolated, DCapacity=17.7inch and lower

bound friction properties. Location: Saranap, CA ................................................................... 50 

Table 3-23 Summary of results for probability of failure for isolated and non-isolated transformer with

W=420kip, fAI=11.3Hz and inclined bushing. When isolated, DCapacity=17.7inch and lower

bound friction properties. Location: Chehalis, WA ................................................................. 51 

Table 3-24 Summary of results for probability of failure for isolated and non-isolated transformer with

W=420kip, fAI=11.3Hz and inclined bushing. When isolated, DCapacity=17.7inch and lower

bound friction properties. Location: Aberdeen, WA ............................................................... 51 

Table 3-25 Summary of results for probability of failure for isolated and non-isolated transformer with

W=420kip, fAI=11.3Hz and inclined bushing. When isolated, DCapacity=17.7inch and lower

bound friction properties. Location: Loma Linda, CA ............................................................ 52 

Table 3-26 Summary of results for probability of failure for isolated and non-isolated transformer with

W=420kip, fAI=11.3Hz and inclined bushing. When isolated, DCapacity=17.7inch and lower

bound friction properties. Location: Hillsboro, OR ................................................................. 52 

Table 3-27 Summary of results for probability of failure for isolated and non-isolated transformer with

W=420kip, fAI=11.3Hz and inclined bushing. When isolated, DCapacity=17.7inch and lower

bound friction properties. Location: Eugene, OR .................................................................... 53 

Table 3-28 Summary of results for probability of failure for isolated and non-isolated transformer with

W=420kip, fAI=11.3Hz and inclined bushing. When isolated, DCapacity=17.7inch and lower

bound friction properties. Location: Wilsonville, OR ............................................................. 53 

Table 3-29 Summary of results for probability of failure for isolated and non-isolated transformer with

W=420kip, fAI=11.3Hz and inclined bushing. When isolated, DCapacity=17.7inch and lower

bound friction properties. Location: Curry County, OR .......................................................... 54 

Page 26: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

xxii

LIST OF TABLES (CONT'D)

Table 3-30 Summary of results for probability of failure for isolated and non-isolated transformer with

W=420kip, fAI=11.3Hz and inclined bushing. When isolated, DCapacity=17.7inch and lower

bound friction properties. Location: Troutdale, OR ................................................................. 54 

Table 3-31 Summary of results for probability of failure for isolated and non-isolated transformer with

W=420kip, fAI=7.7Hz and inclined bushing. When isolated, DCapacity=31.3inch and lower bound

friction properties. Location: Vancouver, WA ........................................................................ 55 

Table 3-32 Summary of results for probability of failure for isolated and non-isolated transformer with

W=420kip, fAI=7.7Hz and inclined bushing. When isolated, DCapacity=31.3inch and lower bound

friction properties. Location: Saranap, CA .............................................................................. 55 

Table 3-33 Summary of results for probability of failure for isolated and non-isolated transformer with

W=420kip, fAI=7.7Hz and inclined bushing. When isolated, DCapacity=31.3inch and lower bound

friction properties. Location: Loma Linda, CA ....................................................................... 56 

Table 3-34 Summary of results for probability of failure for isolated and non-isolated transformer with

W=420kip, fAI=7.7Hz and inclined bushing. When isolated, DCapacity=31.3inch and lower bound

friction properties. Location: Aberdeen, WA .......................................................................... 56 

Table 3-35 Summary of results for probability of failure for isolated and non-isolated transformer with

W=420kip, fAI=7.7Hz and inclined bushing. When isolated, DCapacity=31.3inch and lower bound

friction properties. Location: Chehalis, WA ............................................................................ 57 

Table 3-36 Summary of results for probability of failure for isolated and non-isolated transformer with

W=420kip, fAI=7.7Hz and inclined bushing. When isolated, DCapacity=31.3inch and lower bound

friction properties. Location: Hillsboro, OR ............................................................................ 57 

Table 3-37 Summary of results for probability of failure for isolated and non-isolated transformer with

W=420kip, fAI=7.7Hz and inclined bushing. When isolated, DCapacity=31.3inch and lower bound

friction properties. Location: Eugene, OR ............................................................................... 58 

Table 3-38 Summary of results for probability of failure for isolated and non-isolated transformer with

W=420kip, fAI=7.7Hz and inclined bushing. When isolated, DCapacity=31.3inch and lower bound

friction properties. Location: Wilsonville, OR ........................................................................ 58 

Table 3-39 Summary of results for probability of failure for isolated and non-isolated transformer with

W=420kip, fAI=7.7Hz and inclined bushing. When isolated, DCapacity=31.3inch and lower bound

friction properties. Location: Curry County, OR ..................................................................... 59 

Page 27: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

xxiii

LIST OF TABLES (CONT'D)

Table 3-40 Summary of results for probability of failure for isolated and non-isolated transformer with

W=420kip, fAI=7.7Hz and inclined bushing. When isolated, DCapacity=31.3inch and lower bound

friction properties. Location: Troutdale, OR ............................................................................ 59 

Table 3-41 Summary of results for probability of failure for isolated and non-isolated transformer with

W=420kip, fAI=4.3Hz and inclined bushing. When isolated, DCapacity=31.3inch and lower bound

friction properties. Location: Vancouver, WA ........................................................................ 60 

Table 3-42 Summary of results for probability of failure for isolated and non-isolated transformer with

W=420kip, fAI=4.3Hz and inclined bushing. When isolated, DCapacity=31.3inch and lower bound

friction properties. Location: Saranap, CA .............................................................................. 60 

Table 3-43 Summary of results for probability of failure for isolated and non-isolated transformer with

W=420kip, fAI=4.3Hz and inclined bushing. When isolated, DCapacity=31.3inch and lower bound

friction properties. Location: Chehalis, WA ............................................................................ 61 

Table 3-44 Summary of results for probability of failure for isolated and non-isolated transformer with

W=420kip, fAI=4.3Hz and inclined bushing. When isolated, DCapacity=31.3inch and lower bound

friction properties. Location: Aberdeen, WA .......................................................................... 61 

Table 3-45 Summary of results for probability of failure for isolated and non-isolated transformer with

W=420kip, fAI=4.3Hz and inclined bushing. When isolated, DCapacity=31.3inch and lower bound

friction properties. Location: Loma Linda, CA ....................................................................... 62 

Table 3-46 Summary of results for probability of failure for isolated and non-isolated transformer with

W=420kip, fAI=4.3Hz and inclined bushing. When isolated, DCapacity=31.3inch and lower bound

friction properties. Location: Hillsboro, OR ............................................................................ 62 

Table 3-47 Summary of results for probability of failure for isolated and non-isolated transformer with

W=420kip, fAI=4.3Hz and inclined bushing. When isolated, DCapacity=31.3inch and lower bound

friction properties. Location: Eugene, OR ............................................................................... 63 

Table 3-48 Summary of results for probability of failure for isolated and non-isolated transformer with

W=420kip, fAI=4.3Hz and inclined bushing. When isolated, DCapacity=31.3inch and lower bound

friction properties. Location: Wilsonville, OR ........................................................................ 63 

Table 3-49 Summary of results for probability of failure for isolated and non-isolated transformer with

W=420kip, fAI=4.3Hz and inclined bushing. When isolated, DCapacity=31.3inch and lower bound

friction properties. Location: Curry County, OR ..................................................................... 64 

Page 28: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

xxiv

LIST OF TABLES (CONT'D)

Table 3-50 Summary of results for probability of failure for isolated and non-isolated transformer with

W=420kip, fAI=4.3Hz and inclined bushing. When isolated, DCapacity=31.3inch and lower bound

friction properties. Location: Troutdale, OR ............................................................................ 64 

Table 3-51 Summary of results for probability of failure for isolated and non-isolated transformer with

W=420kip, fAI=11.3Hz and inclined bushing. When isolated, DCapacity=31.3inch and lower

bound friction properties. Location: Vancouver, WA.............................................................. 65 

Table 3-52 Summary of results for probability of failure for isolated and non-isolated transformer with

W=420kip, fAI=11.3Hz and inclined bushing. When isolated, DCapacity=31.3inch and lower

bound friction properties. Location: Saranap, CA ................................................................... 65 

Table 3-53 Summary of results for probability of failure for isolated and non-isolated transformer with

W=420kip, fAI=11.3Hz and inclined bushing. When isolated, DCapacity=31.3inch and lower

bound friction properties. Location: Chehalis, WA ................................................................. 66 

Table 3-54 Summary of results for probability of failure for isolated and non-isolated transformer with

W=420kip, fAI=11.3Hz and inclined bushing. When isolated, DCapacity=31.3inch and lower

bound friction properties. Location: Aberdeen, WA ............................................................... 66 

Table 3-55 Summary of results for probability of failure for isolated and non-isolated transformer with

W=420kip, fAI=11.3Hz and inclined bushing. When isolated, DCapacity=31.3inch and lower

bound friction properties. Location: Loma Linda, CA ............................................................ 67 

Table 3-56 Summary of results for probability of failure for isolated and non-isolated transformer with

W=420kip, fAI=11.3Hz and inclined bushing. When isolated, DCapacity=31.3inch and lower

bound friction properties. Location: Hillsboro, OR ................................................................. 67 

Table 3-57 Summary of results for probability of failure for isolated and non-isolated transformer with

W=420kip, fAI=11.3Hz and inclined bushing. When isolated, DCapacity=31.3inch and lower

bound friction properties. Location: Eugene, OR .................................................................... 68 

Table 3-58 Summary of results for probability of failure for isolated and non-isolated transformer with

W=420kip, fAI=11.3Hz and inclined bushing. When isolated, DCapacity=31.3inch and lower

bound friction properties. Location: Wilsonville, OR ............................................................. 68 

Table 3-59 Summary of results for probability of failure for isolated and non-isolated transformer with

W=420kip, fAI=11.3Hz and inclined bushing. When isolated, DCapacity=31.3inch and lower

bound friction properties. Location: Curry County, OR .......................................................... 69 

Page 29: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

xxv

LIST OF TABLES (CONT'D)

Table 3-60 Summary of results for probability of failure for isolated and non-isolated transformer with

W=420kip, fAI=11.3Hz and inclined bushing. When isolated, DCapacity=31.3inch and lower

bound friction properties. Location: Troutdale, OR .................................................................... 69 

Table 5-1 Summary of results for probability of failure when considering uncertainties for isolated and non-

isolated transformer with W=420kip, fAI=7.7Hz and inclined bushing. When isolated,

DCapacity=17.7inch and lower bound friction properties. Location: Vancouver, WA. Far-field

motions .............................................................................................................................................. 77 

Table 5-2 Summary of results for probability of failure when considering uncertainties for isolated and non-

isolated transformer with W=420kip, fAI=7.7Hz and inclined bushing. When isolated,

DCapacity=17.7inch and lower bound friction properties. Location: Saranap, CA. Far-field motions

............................................................................................................................................................ 78 

Table 5-3 Summary of results for probability of failure when considering uncertainties for isolated and non-

isolated transformer with W=420kip, fAI=7.7Hz and inclined bushing. When isolated,

DCapacity=17.7inch and lower bound friction properties. Location: Loma Linda, CA. Far-field

motions .............................................................................................................................................. 79 

Table 5-4 Summary of results for probability of failure when considering uncertainties for isolated and non-

isolated transformer with W=420kip, fAI=7.7Hz and inclined bushing. When isolated,

DCapacity=17.7inch and lower bound friction properties. Location: Aberdeen, WA. Far-field

motions .............................................................................................................................................. 80 

Table 5-5 Summary of results for probability of failure when considering uncertainties for isolated and non-

isolated transformer with W=420kip, fAI=7.7Hz and inclined bushing. When isolated,

DCapacity=17.7inch and lower bound friction properties. Location: Chehalis, WA. Far-field motions

............................................................................................................................................................ 81 

Table 5-6 Summary of results for probability of failure when considering uncertainties for isolated and non-

isolated transformer with W=420kip, fAI=7.7Hz and inclined bushing. When isolated,

DCapacity=17.7inch and lower bound friction properties. Location: Hillsboro, OR. Far-field motions

............................................................................................................................................................ 82 

Table 5-7 Summary of results for probability of failure when considering uncertainties for isolated and non-

isolated transformer with W=420kip, fAI=7.7Hz and inclined bushing. When isolated,

DCapacity=17.7inch and lower bound friction properties. Location: Eugene, OR. Far-field motions

............................................................................................................................................................ 83 

Page 30: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

xxvi

LIST OF TABLES (CONT'D)

Table 5-8 Summary of results for probability of failure when considering uncertainties for isolated and non-

isolated transformer with W=420kip, fAI=7.7Hz and inclined bushing. When isolated,

DCapacity=17.7inch and lower bound friction properties. Location: Wilsonville, OR. Far-field

motions ........................................................................................................................................ 84 

Table 5-9 Summary of results for probability of failure when considering uncertainties for isolated and non-

isolated transformer with W=420kip, fAI=7.7Hz and inclined bushing. When isolated,

DCapacity=17.7inch and lower bound friction properties. Location: Curry County, OR. Far-field

motions ........................................................................................................................................ 85 

Table 5-10 Summary of results for probability of failure when considering uncertainties for isolated and

non-isolated transformer with W=420kip, fAI=7.7Hz and inclined bushing. When isolated,

DCapacity=17.7inch and lower bound friction properties. Location: Troutdale, OR. Far-field

motions ........................................................................................................................................ 86 

Table 5-11 Summary of results for probability of failure when considering uncertainties for isolated and

non-isolated transformer with W=420kip, fAI=4.3Hz and inclined bushing. When isolated,

DCapacity=17.7inch and lower bound friction properties. Location: Vancouver, WA. Far-field

motions ........................................................................................................................................ 87 

Table 5-12 Summary of results for probability of failure when considering uncertainties for isolated and

non-isolated transformer with W=420kip, fAI=4.3Hz and inclined bushing. When isolated,

DCapacity=17.7inch and lower bound friction properties. Location: Saranap, CA. Far-field

motions ..................................................................................................................................... 88 

Table 5-13 Summary of results for probability of failure when considering uncertainties for isolated and

non-isolated transformer with W=420kip, fAI=4.3Hz and inclined bushing. When isolated,

DCapacity=17.7inch and lower bound friction properties. Location: Chehalis, WA. Far-field

motions ..................................................................................................................................... 89 

Table 5-14 Summary of results for probability of failure when considering uncertainties for isolated and

non-isolated transformer with W=420kip, fAI=4.3Hz and inclined bushing. When isolated,

DCapacity=17.7inch and lower bound friction properties. Location: Aberdeen, WA. Far-field

motions ..................................................................................................................................... 90 

Table 5-15 Summary of results for probability of failure when considering uncertainties for isolated and

non-isolated transformer with W=420kip, fAI=4.3Hz and inclined bushing. When isolated,

DCapacity=17.7inch and lower bound friction properties. Location: Loma Linda, CA. Far-field

motions ..................................................................................................................................... 91 

Page 31: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

xxvii

LIST OF TABLES (CONT'D)

Table 5-16 Summary of results for probability of failure when considering uncertainties for isolated and

non-isolated transformer with W=420kip, fAI=4.3Hz and inclined bushing. When isolated,

DCapacity=17.7inch and lower bound friction properties. Location: Hillsboro, OR. Far-field

motions ..................................................................................................................................... 92 

Table 5-17 Summary of results for probability of failure when considering uncertainties for isolated and

non-isolated transformer with W=420kip, fAI=4.3Hz and inclined bushing. When isolated,

DCapacity=17.7inch and lower bound friction properties. Location: Eugene, OR. Far-field motions

................................................................................................................................................. 93 

Table 5-18 Summary of results for probability of failure when considering uncertainties for isolated and

non-isolated transformer with W=420kip, fAI=4.3Hz and inclined bushing. When isolated,

DCapacity=17.7inch and lower bound friction properties. Location: Wilsonville, OR. Far-field

motions ..................................................................................................................................... 94 

Table 5-19 Summary of results for probability of failure when considering uncertainties for isolated and

non-isolated transformer with W=420kip, fAI=4.3Hz and inclined bushing. When isolated,

DCapacity=17.7inch and lower bound friction properties. Location: Curry County, OR. Far-field

motions ..................................................................................................................................... 95 

Table 5-20 Summary of results for probability of failure when considering uncertainties for isolated and

non-isolated transformer with W=420kip, fAI=4.3Hz and inclined bushing. When isolated,

DCapacity=17.7inch and lower bound friction properties. Location: Troutdale, OR. Far-field

motions ..................................................................................................................................... 96 

Table 5-21 Summary of results for probability of failure when considering uncertainties for isolated and

non-isolated transformer with W=420kip, fAI=11.3Hz and inclined bushing. When isolated,

DCapacity=17.7inch and lower bound friction properties. Location: Vancouver, WA. Far-field

motions ..................................................................................................................................... 97 

Table 5-22 Summary of results for probability of failure when considering uncertainties for isolated and

non-isolated transformer with W=420kip, fAI=11.3Hz and inclined bushing. When isolated,

DCapacity=17.7inch and lower bound friction properties. Location: Saranap, CA. Far-field

motions ..................................................................................................................................... 98 

Table 5-23 Summary of results for probability of failure when considering uncertainties for isolated and

non-isolated transformer with W=420kip, fAI=11.3Hz and inclined bushing. When isolated,

DCapacity=17.7inch and lower bound friction properties. Location: Chehalis, WA. Far-field

motions ..................................................................................................................................... 99 

Page 32: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

xxviii

LIST OF TABLES (CONT'D)

Table 5-24 Summary of results for probability of failure when considering uncertainties for isolated and

non-isolated transformer with W=420kip, fAI=11.3Hz and inclined bushing. When isolated,

DCapacity=17.7inch and lower bound friction properties. Location: Aberdeen, WA. Far-field

motions ................................................................................................................................... 100 

Table 5-25 Summary of results for probability of failure when considering uncertainties for isolated and

non-isolated transformer with W=420kip, fAI=11.3Hz and inclined bushing. When isolated,

DCapacity=17.7inch and lower bound friction properties. Location: Loma Linda, CA. Far-field

motions ................................................................................................................................... 101 

Table 5-26 Summary of results for probability of failure when considering uncertainties for isolated and

non-isolated transformer with W=420kip, fAI=11.3Hz and inclined bushing. When isolated,

DCapacity=17.7inch and lower bound friction properties. Location: Hillsboro, OR. Far-field

motions ................................................................................................................................... 102 

Table 5-27 Summary of results for probability of failure when considering uncertainties for isolated and

non-isolated transformer with W=420kip, fAI=11.3Hz and inclined bushing. When isolated,

DCapacity=17.7inch and lower bound friction properties. Location: Eugene, OR. Far-field motions

............................................................................................................................................... 103 

Table 5-28 Summary of results for probability of failure when considering uncertainties for isolated and

non-isolated transformer with W=420kip, fAI=11.3Hz and inclined bushing. When isolated,

DCapacity=17.7inch and lower bound friction properties. Location: Wilsonville, OR. Far-field

motions ................................................................................................................................... 104 

Table 5-29 Summary of results for probability of failure when considering uncertainties for isolated and

non-isolated transformer with W=420kip, fAI=11.3Hz and inclined bushing. When isolated,

DCapacity=17.7inch and lower bound friction properties. Location: Curry County, OR. Far-field

motions ................................................................................................................................... 105 

Table 5-30 Summary of results for probability of failure when considering uncertainties for isolated and

non-isolated transformer with W=420kip, fAI=11.3Hz and inclined bushing. When isolated,

DCapacity=17.7inch and lower bound friction properties. Location: Troutdale, OR. Far-field

motions ................................................................................................................................... 106 

Table 5-31 Summary of results for probability of failure when considering uncertainties for isolated and

non-isolated transformer with W=420kip, fAI=7.7Hz and inclined bushing. When isolated,

DCapacity=31.3inch and lower bound friction properties. Location: Vancouver, WA. Far-field

motions ................................................................................................................................... 107 

Page 33: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

xxix

LIST OF TABLES (CONT'D)

Table 5-32 Summary of results for probability of failure when considering uncertainties for isolated and

non-isolated transformer with W=420kip, fAI=7.7Hz and inclined bushing. When isolated,

DCapacity=31.3inch and lower bound friction properties. Location: Saranap, CA. Far-field

motions ................................................................................................................................... 108 

Table 5-33 Summary of results for probability of failure when considering uncertainties for isolated and

non-isolated transformer with W=420kip, fAI=7.7Hz and inclined bushing. When isolated,

DCapacity=31.3inch and lower bound friction properties. Location: Loma Linda, CA. Far-field

motions ................................................................................................................................... 109 

Table 5-34 Summary of results for probability of failure when considering uncertainties for isolated and

non-isolated transformer with W=420kip, fAI=7.7Hz and inclined bushing. When isolated,

DCapacity=31.3inch and lower bound friction properties. Location: Aberdeen, WA. .Far-field

motions ................................................................................................................................... 110 

Table 5-35 Summary of results for probability of failure when considering uncertainties for isolated and

non-isolated transformer with W=420kip, fAI=7.7Hz and inclined bushing. When isolated,

DCapacity=31.3inch and lower bound friction properties. Location: Chehalis, WA. Far-field

motions ................................................................................................................................... 111 

Table 5-36 Summary of results for probability of failure when considering uncertainties for isolated and

non-isolated transformer with W=420kip, fAI=7.7Hz and inclined bushing. When isolated,

DCapacity=31.3inch and lower bound friction properties. Location: Hillsboro, OR. Far-field

motions ................................................................................................................................... 112 

Table 5-37 Summary of results for probability of failure when considering uncertainties for isolated and

non-isolated transformer with W=420kip, fAI=7.7Hz and inclined bushing. When isolated,

DCapacity=31.3inch and lower bound friction properties. Location: Eugene, OR. Far-field motions

............................................................................................................................................... 113 

Table 5-38 Summary of results for probability of failure when considering uncertainties for isolated and

non-isolated transformer with W=420kip, fAI=7.7Hz and inclined bushing. When isolated,

DCapacity=31.3inch and lower bound friction properties. Location: Wilsonville, OR. Far-field

motions ................................................................................................................................... 114 

Table 5-39 Summary of results for probability of failure when considering uncertainties for isolated and

non-isolated transformer with W=420kip, fAI=7.7Hz and inclined bushing. When isolated,

DCapacity=31.3inch and lower bound friction properties. Location: Curry County, OR. Far-field

motions ................................................................................................................................... 115 

Page 34: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

xxx

LIST OF TABLES (CONT'D)

Table 5-40 Summary of results for probability of failure when considering uncertainties for isolated and

non-isolated transformer with W=420kip, fAI=7.7Hz and inclined bushing. When isolated,

DCapacity=31.3inch and lower bound friction properties. Location: Troutdale, OR. Far-field

motions ................................................................................................................................... 116 

Table 5-41 Summary of results for probability of failure when considering uncertainties for isolated and

non-isolated transformer with W=420kip, fAI=4.3Hz and inclined bushing. When isolated,

DCapacity=31.3inch and lower bound friction properties. Location: Vancouver, WA. Far-field

motions ................................................................................................................................... 117 

Table 5-42 Summary of results for probability of failure when considering uncertainties for isolated and

non-isolated transformer with W=420kip, fAI=4.3Hz and inclined bushing. When isolated,

DCapacity=31.3inch and lower bound friction properties. Location: Saranap, CA. Far-field

motions ................................................................................................................................... 118 

Table 5-43 Summary of results for probability of failure when considering uncertainties for isolated and

non-isolated transformer with W=420kip, fAI=4.3Hz and inclined bushing. When isolated,

DCapacity=31.3inch and lower bound friction properties. Location: Chehalis, WA. Far-field

motions ................................................................................................................................... 119 

Table 5-44 Summary of results for probability of failure when considering uncertainties for isolated and

non-isolated transformer with W=420kip, fAI=4.3Hz and inclined bushing. When isolated,

DCapacity=31.3inch and lower bound friction properties. Location: Aberdeen, WA. Far-field

motions ................................................................................................................................... 120 

Table 5-45 Summary of results for probability of failure when considering uncertainties for isolated and

non-isolated transformer with W=420kip, fAI=4.3Hz and inclined bushing. When isolated,

DCapacity=31.3inch and lower bound friction properties. Location: Loma Linda, CA. Far-field

motions ................................................................................................................................... 121 

Table 5-46 Summary of results for probability of failure when considering uncertainties for isolated and

non-isolated transformer with W=420kip, fAI=4.3Hz and inclined bushing. When isolated,

DCapacity=31.3inch and lower bound friction properties. Location: Hillsboro, OR. Far-field

motions ................................................................................................................................... 122 

Table 5-47 Summary of results for probability of failure when considering uncertainties for isolated and

non-isolated transformer with W=420kip, fAI=4.3Hz and inclined bushing. When isolated,

DCapacity=31.3inch and lower bound friction properties. Location: Eugene, OR. Far-field motions

............................................................................................................................................... 123 

Page 35: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

xxxi

LIST OF TABLES (CONT'D)

Table 5-48 Summary of results for probability of failure when considering uncertainties for isolated and

non-isolated transformer with W=420kip, fAI=4.3Hz and inclined bushing. When isolated,

DCapacity=31.3inch and lower bound friction properties. Location: Wilsonville, OR. Far-field

motions ................................................................................................................................... 124 

Table 5-49 Summary of results for probability of failure when considering uncertainties for isolated and

non-isolated transformer with W=420kip, fAI=4.3Hz and inclined bushing. When isolated,

DCapacity=31.3inch and lower bound friction properties. Location: Curry County, OR. Far-field

motions ................................................................................................................................... 125 

Table 5-50 Summary of results for probability of failure when considering uncertainties for isolated and

non-isolated transformer with W=420kip, fAI=4.3Hz and inclined bushing. When isolated,

DCapacity=31.3inch and lower bound friction properties. Location: Troutdale, OR. Far-field

motions ................................................................................................................................... 126 

Table 5-51 Summary of results for probability of failure when considering uncertainties for isolated and

non-isolated transformer with W=420kip, fAI=11.3Hz and inclined bushing. When isolated,

DCapacity=31.3inch and lower bound friction properties. Location: Vancouver, WA. Far-field

motions ................................................................................................................................... 127 

Table 5-52 Summary of results for probability of failure when considering uncertainties for isolated and

non-isolated transformer with W=420kip, fAI=11.3Hz and inclined bushing. When isolated,

DCapacity=31.3inch and lower bound friction properties. Location: Saranap, CA. Far-field

motions ................................................................................................................................... 128 

Table 5-53 Summary of results for probability of failure when considering uncertainties for isolated and

non-isolated transformer with W=420kip, fAI=11.3Hz and inclined bushing. When isolated,

DCapacity=31.3inch and lower bound friction properties. Location: Chehalis, WA. Far-field

motions ................................................................................................................................... 129 

Table 5-54 Summary of results for probability of failure when considering uncertainties for isolated and

non-isolated transformer with W=420kip, fAI=11.3Hz and inclined bushing. When isolated,

DCapacity=31.3inch and lower bound friction properties. Location: Aberdeen, WA. Far-field

motions ................................................................................................................................... 130 

Table 5-55 Summary of results for probability of failure when considering uncertainties for isolated and

non-isolated transformer with W=420kip, fAI=11.3Hz and inclined bushing. When isolated,

DCapacity=31.3inch and lower bound friction properties. Location: Loma Linda, CA. Far-field

motions ................................................................................................................................... 131 

Page 36: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

xxxii

LIST OF TABLES (CONT'D)

Table 5-56 Summary of results for probability of failure when considering uncertainties for isolated and

non-isolated transformer with W=420kip, fAI=11.3Hz and inclined bushing. When isolated,

DCapacity=31.3inch and lower bound friction properties. Location: Hillsboro, OR. Far-field

motions ................................................................................................................................... 132 

Table 5-57 Summary of results for probability of failure when considering uncertainties for isolated and

non-isolated transformer with W=420kip, fAI=11.3Hz and inclined bushing. When isolated,

DCapacity=31.3inch and lower bound friction properties. Location: Eugene, OR. Far-field motions

............................................................................................................................................... 133 

Table 5-58 Summary of results for probability of failure when considering uncertainties for isolated and

non-isolated transformer with W=420kip, fAI=11.3Hz and inclined bushing. When isolated,

DCapacity=31.3inch and lower bound friction properties. Location: Wilsonville, OR. Far-field

motions ................................................................................................................................... 134 

Table 5-59 Summary of results for probability of failure when considering uncertainties for isolated and

non-isolated transformer with W=420kip, fAI=11.3Hz and inclined bushing. When isolated,

DCapacity=31.3inch and lower bound friction properties. Location: Curry County, OR. Far-field

motions ................................................................................................................................... 135 

Table 5-60 Summary of results for probability of failure when considering uncertainties for isolated and

non-isolated transformer with W=420kip, fAI=11.3Hz and inclined bushing. When isolated,

DCapacity=31.3inch and lower bound friction properties. Location: Troutdale, OR. Far-field

motions ................................................................................................................................... 136 

Table 5-61 Probabilities of failure in 50 years for non-isolated and horizontally isolated transformers with

transverse bushing acceleration limit of 1g (case of RTR≤0.4) .............................................. 137 

Table 6-1 Near-field ground motions used in dynamic analysis ............................................................... 140 

Table 6-2 Summary of results for probability of failure for isolated and non-isolated transformer with

W=420kip, fAI=4.3Hz and inclined bushing. When isolated, DCapacity=31.3inch and lower bound

friction properties. Location: Saranap, CA. Near-field motions .............................................. 143 

Table 6-3 Summary of results for probability of failure for isolated and non-isolated transformer with

W=420kip, fAI=4.3Hz and inclined bushing. When isolated, DCapacity=31.3inch and lower bound

friction properties. Location: Loma Linda, CA. Near-field motions ....................................... 144 

Page 37: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

xxxiii

LIST OF TABLES (CONT'D)

Table 6-4 Summary of results for probability of failure for isolated and non-isolated transformer with

W=420kip, fAI=7.7Hz and inclined bushing. When isolated, DCapacity=31.3inch and lower bound

friction properties. Location: Saranap, CA. Near-field motions ............................................. 144 

Table 6-5 Summary of results for probability of failure for isolated and non-isolated transformer with

W=420kip, fAI=7.7Hz and inclined bushing. When isolated, DCapacity=31.3inch and lower bound

friction properties. Location: Loma Linda, CA. Near-field motions ....................................... 145 

Table 6-6 Summary of results for probability of failure for isolated and non-isolated transformer with

W=420kip, fAI=11.3Hz and inclined bushing. When isolated, DCapacity=31.3inch and lower bound

friction properties. Location: Saranap, CA. Near-field motions .............................................. 145 

Table 6-7 Summary of results for probability of failure for isolated and non-isolated transformer with

W=420kip, fAI=11.3Hz and inclined bushing. When isolated, DCapacity=31.3inch and lower bound

friction properties. Location: Loma Linda, CA. Near-field motions ....................................... 146 

Table A-1 Values of , M and R at three representative sites for 2475 years return period earthquake

................................................................................................................................................ 156 

Page 38: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on
Page 39: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

1

SECTION 1

INTRODUCTION

Earlier studies on the assessment of seismic performance of seismically isolated electrical power

transformers (Kitayama et al., 2016, 2017) utilized FEMA P695 procedures (FEMA, 2009) with

the following limitations:

1) The peak ground acceleration (PGA) was selected as the measure of seismic intensity in

the scaling of ground motions used in the incremental dynamic analysis for constructing

fragility curves. While many studies of seismic assessment of electrical transformers used

the PGA as a measure of seismic intensity (Shinozuka et al., 2007; Shumuta, 2007), the

spectral acceleration at the fundamental period Sa(T1) of the analyzed structure is thought

to be a more appropriate measure of intensity and has been used in building performance

studies. FEMA (2009), Masroor and Mosqueda (2015) and Kitayama and Constantinou

(2018a, 2018b, 2019a, 2019b) used the spectral acceleration at the fundamental period as

the measure of ground motion intensity for seismically isolated structures. The selection of

the measure of seismic intensity affects the scaling of the motions for analysis and

accordingly affects the results. An example in Section 2 demonstrates the effect.

2) The fragility analysis did not account for spectral shape effects. The analysis used a large

sample of actual ground motions and increased their intensity until failure was detected in

an approach that only accounted for the ground-motion intensity in the assessment of

failure. The approach did not account for the changing spectral shape of the motions as

intensity is increased. Appendix A presents more details of the spectral shape effects and

the procedure used to account for them in this study.

3) The fragility analysis results and the calculated probabilities of failure did not account for

uncertainties other than the record-to-record variability (aleatory uncertainty) and only

considered modeling uncertainties (epistemic uncertainty) through a limited bounding

analysis by considering a range of model parameters. The analysis did not consider

uncertainties related to the quality of the analysis model and the quality of construction of

the transformer. Kitayama and Constantinou (2018a, 2018b, 2019a, 2019b) demonstrated

the effects of uncertainties on the calculated probabilities of collapse of isolated buildings.

4) The study only considered far-field motions. Two of the ten considered sites in the

transformer performance evaluation are in close proximity to active faults so that near-fault

Page 40: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

2

motions (see Section 11.4.1 of ASCE/SEI 7-16 standard for identification; ASCE, 2017)

should have been considered. Such motions often result in larger isolator displacement

demands and thus may affect the failure performance.

This report presents an investigation of the limitations of past studies by considering other

measures of seismic intensity, including spectral shape effects, incorporating uncertainties and

performing representative analyses with near-field ground motions. The studies are performed

with a representative transformer model out of those studied in Kitayama et al. (2016). The reader

should first read the report of Kitayama et al. (2016) to be able to follow the work in this report.

The selected transformer is the one with 420kip weight and an inclined (20 degrees) bushing of

4.3Hz or 7.7Hz or 11.3Hz frequency (W=420kip, fAI=4.3 or 7.7 or 11.3Hz). Table 1-1 lists the

properties of the three considered bushings. In its non-isolated version, the transformer model has

an inherent damping of 3% of critical in all its modes. Inherent damping was realized in the

analysis model by adding translational and rotational viscous damping elements at selected

locations as described in Kitayama et al. (2016). When isolated, the transformer model was placed

on top of the seismic isolation model and interconnected without any specification for global

damping in order to avoid affecting the behavior of the isolation system.

Table 1-1 Properties of bushings used in study (after Kitayama et al., 2016)

Unit Bushing 3 Bushing 6 Bushing 8

Voltage capacity kV 550 196/230 550

Total height meter 6.22 3.85 6.48

Length over mounting flange: HUB meter 4.95 2.32 4.83

Length below mounting flange: HLB meter 1.27 1.52 1.65

Total weight kN 12.5 3.74 9.70

Upper bushing weight: mUB∙g kN 9.59 1.99 6.98

Location of upper bushing center of gravity: HCM_UB meter 2.23 0.86 2.16

Lower bushing weight: mLB∙g kN 2.46 1.30 2.27

Location of lower bushing center of gravity: HCM_LB meter 1.50 0.71 0.99

Connection housing weight: mCH∙g kN 0.44 0.44 0.44

Weight per unit length kN/m 1.94 0.86 1.43

Distance to the flange (half of center pocket): HF meter 0.29 0.34 0.29

Fixed frequency: fFix Hz 9.36 21.00 9.35

As-installed frequency: fAI Hz 4.25 11.25 7.70

Material of insulator - Porcelain Porcelain Porcelain

Page 41: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

3

When seismically isolated, the horizontal isolators considered in the study were Triple FP isolators

with ultimate displacement capacity of 17.7inch or 31.3inch without an inner restrainer. The

fiction properties considered were for the lower bound conditions as those always resulted in the

largest probabilities of failure (W=420kip, fAI=4.3 or 7.7 or 11.3Hz, 20 degree inclined bushing,

DCapacity=17.7inch or 31.3inch, lower bound conditions with μ1=μ4=0.12 and μ2=μ3=0.08) (the

values of the friction coefficient μ1 and μ4 apply for the outer sliding interfaces 1 and 4 and the

values of the friction coefficient μ2 and μ3 apply for the inner sliding interfaces 2 and 3 as shown

in Figure 1-1). The intermediate size isolator with DCapacity=27.7inch considered in Kitayama et al.

(2016) was not considered as its displacement capacity was close to the one with capacity of

31.3inch. When vertically isolated, the vertical isolation system consisted of four isolators, each

with stiffness K=44kip/in, damping constant C=3.4kip-sec/in and a stroke capacity of 5inch. The

system in the vertical direction had a frequency of 2.0Hz and a damping ratio of 0.50. Vertical

isolation systems with either complete restraint against rocking (using a second very stiff base)

(results identified as “without rocking”) or free to rock (results identified as “with rocking”) were

analyzed.

Figures 1-1 and 1-2 present sections of the two isolators. Note that the two isolators differ in the

displacement capacity and in the radius of curvature of the two main concave plates. This is

important in understanding some of the results of this study.

The bushing failure acceleration limits considered were (a) 1g or 2g in the bushing transverse

direction, and (b) 5g in the bushing longitudinal direction. Other transformer failure criteria used

in the fragility analysis were (a) exceedance of isolator horizontal displacement capacity DCapacity,

(b) isolator uplift exceeding 2inch, and (c) numerical instability in the analysis. The interested

reader is referred to the report of Kitayama et al. (2016) for details on the selection of and

justification for the acceleration limits of the bushings. In general, the failure criteria of the

bushings are based on comparisons of predicted fragility curves of analyzed non-isolated

transformers to empirical fragility curves based on observations of damage to electrical equipment

in earthquakes.

Page 42: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

4

Figure 1-1 Section of smallest isolator with displacement capacity DCapacity=17.7inch

Figure 1-2 Section of largest isolator with displacement capacity DCapacity=31.3inch

The locations considered for the transformer were the ten sites considered in the Kitayama et al.

(2016) study (Vancouver, WA; Saranap, CA; Loma Linda, CA; Aberdeen, WA; Chehalis, WA;

Hillsboro, OR; Eugene, OR; Wilsonville, OR; Curry County, OR; Troutdale, OR) (see Table 2-1

in Kitayama et al., 2016). Figure 1-3 shows these locations. These locations have different seismic

hazard curves, which should result in different probabilities of failure in 50 years. For example,

Chehalis, WA is a moderate seismicity site, Loma Linda, CA is a high seismicity site, and

Sliding Interfaces 1 and 4 Sliding Interfaces 2 and 3

Page 43: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

5

Troutdale, OR is a low seismicity site. Figures 1-4 to 1-13 presents seismic hazard curves for the

10 locations at periods of zero, 0.1, 0.2, 2 and 3second. These periods are relevant to the analysis

in this report. The seismic hazard curves were obtained from the United States Geological Survey

(http://geohazards.usgs.gov/hazardtool/application.php) in the form of the annual frequency of

exceedance as function of the spectral acceleration at selected values of period for the site locations

and soil conditions.

Figure 1-3 Location of transformers considered in this study

Page 44: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

6

Figure 1-4 Seismic hazard curves for zero, 0.1, 0.2, 2 and 3sec period at Vancouver, WA

Figure 1-5 Seismic hazard curves for zero, 0.1, 0.2, 2 and 3sec period at Saranap, CA

Page 45: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

7

Figure 1-6 Seismic hazard curves for zero, 0.1, 0.2, 2 and 3sec period at Loma Linda, CA

Figure 1-7 Seismic hazard curves for zero, 0.1, 0.2, 2 and 3sec period at Aberdeen, WA

Page 46: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

8

Figure 1-8 Seismic hazard curves for zero, 0.1, 0.2, 2 and 3sec period at Chehalis, WA

Figure 1-9 Seismic hazard curves for zero, 0.1, 0.2, 2 and 3sec period at Hillsboro, OR

Page 47: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

9

Figure 1-10 Seismic hazard curves for zero, 0.1, 0.2, 2 and 3sec period at Eugene, OR

Figure 1-11 Seismic hazard curves for zero, 0.1, 0.2, 2 and 3sec period at Wilsonville, OR

Page 48: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

10

Figure 1-12 Seismic hazard curves for zero, 0.1, 0.2, 2 and 3sec period at Curry County, OR

Figure 1-13 Seismic hazard curves for zero, 0.1, 0.2, 2 and 3sec period at Troutdale, OR

Page 49: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

11

Results obtained for near-field and far-field motions, both without correction for spectral shape

effects, reveal that for the studied isolated transformers there is a small difference between the

results of the two sets of motions. We suggest that the considered isolators of low stiffness and

large displacement capacity for near-field applications did not experience failure and did not cause

any significant increase in the bushing acceleration as the isolator displacement demand increased

due to the effects of the near-field motions. It was concluded that near-field motions do not

appreciably change the results obtained for the far-field motions when isolators of appropriately

larger displacement capacity and low stiffness are used.

Results obtained for far-field motions show that, in general, scaling of the ground motions based

on the spectral acceleration at the fundamental period or the effective period results in significant

increases in the probability of failure for the isolated transformers, which are then significantly

moderated by corrections for the spectral shape effects. By comparison, the changes in the

probability of failure of the studied non-isolated transformers were small due to the fact that the

fundamental period was very small so that the spectral acceleration at the fundamental period was

very close to the PGA which was used in the earlier studies for the scaling.

Based on the new results in this report, combined horizontal-vertical seismic isolation systems

offer the lowest probabilities of failure for all cases of transformer and isolation system parameters,

and for all considered sites. Horizontal only isolation offers no or offers insignificant advantages

over non-isolation when the bushing transverse acceleration limit is 2g. However, horizontal

only isolation offers important advantages over non-isolation when the bushing transverse

acceleration limit is 1g.

The results of this report, documented in numerous tables, may be used to decide on the benefits

offered by a seismic isolation system depending on the location of the transformer and the form

and properties of the seismic isolation system. The benefit is assessed on the basis of the

probability of failure in 50 years of lifetime. The information may also be used to assess the

seismic performance of electric transmission networks under scenarios of component failures.

Page 50: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on
Page 51: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

13

SECTION 2

EVALUATING THE EFFECT OF SEISMIC GROUND MOTION INTENSITY

MEASURES ON FRAGILITY

Figure 2-1 illustrates how the selection of the measure of the ground motion intensity affects the

calculation of the probability of failure (fragility curve) and by extension the mean annual

frequency of failure F and the probability of failure over a specified time. The figure shows the

5%-damped response spectra of ground motions used in Incremental Dynamic Analysis (IDA) for

constructing the fragility curves. The ground motions are first scaled so that their 5%-damped

spectral acceleration values are the same at a selected period. Figure 2-1 shows the result of the

scaling when the selected period is (near) zero (so that the intensity measure is the PGA) and

another period Ti (so that the intensity measure is Sa (Ti)). Response history analysis is then

performed by increasing the ground motion intensity in small steps while detecting failure in each

step. Conceptually, the results should be relatively insensitive to the conditioning period provided

that the records are representative of the site in consideration and the number of records is large

enough. However, in this study the same set of records is used for several sites and, therefore, it is

expected that the scaling procedure should have some effect.

Figure 2-1 Scaling of ground motions so that the spectral acceleration values of the horizontal

components are the same at zero period (left) and at period Ti (right)

Studies reported in Kitayama et al. (2016, 2017) presented results on the mean annual frequency

of failure F and the probability of failure in a lifetime of 50 years of several isolated and non-

isolated electrical transformers at the ten locations shown in Figure 1-3. These results of F were

Page 52: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

14

obtained by using the PGA as the measure of ground motion intensity. A procedure is described

below for converting the results acquired on the basis of PGA scaling to new results based on

scaling of the ground motions using the spectral acceleration at an arbitrary period Ti, which is

now considered a variable. The information used from the results of the earlier studies is the peak

ground acceleration at failure of the transformer in each conducted IDA with the scaling of the

ground motions based on the PGA as the measure of seismic intensity.

Consider the case of the far-field motions studied in Kitayama et al. (2016, 2017). There are 40

pairs of horizontal-vertical components of ground motions. The following analysis steps are

followed to convert the results:

1. Start with a period Ti. We considered 300 different values of period, that is, i=1 to 300, with

the minimum value of Ti being 0.02second, the maximum value being 6.0second and the

increment being 0.02second.

2. From the jth un-scaled acceleration response spectrum of each of 40 horizontal ground

motions (j=1 to 40), obtain ratio of PGAj to Saj(Ti):

𝑅𝑎𝑡𝑖𝑜𝑆𝑎/𝑃𝐺𝐴𝑗=

𝑆𝑎𝑗(𝑇𝑖)

𝑃𝐺𝐴𝑗(2-1)

Note that the value of RatioSa/PGA remains constant as the motions are scaled for conducting

the IDA.

3. The value of the peak ground acceleration at failure of a particular transformer PGAF,j for the

jth ground motion is known from Kitayama et al. (2016, 2017). Obtain the spectral

acceleration at period Ti that causes failure of transformer or SaF,j(Ti) as follows:

𝑆𝑎𝐹,𝑗(𝑇𝑖) = 𝑃𝐺𝐴𝐹,𝑗 ∙ 𝑅𝑎𝑡𝑖𝑜𝑆𝑎/𝑃𝐺𝐴𝑗(2-2)

4. Calculate the median of the natural logarithm of SaF,j(Ti):

𝑆�̂�𝐹(𝑇𝑖) = Median⟨𝑆𝑎𝐹,1(𝑇𝑖), 𝑆𝑎𝐹,2(𝑇𝑖), 𝑆𝑎𝐹,3(𝑇𝑖), … , 𝑆𝑎𝐹,40(𝑇𝑖)⟩ (2-3)

Page 53: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

15

Quantity 𝑆�̂�𝐹(𝑇𝑖) is the measure of intensity (spectral acceleration at period Ti) that

results in a 50% probability of failure of the transformer (that is, 20 of 40 analyses

result in failure).

5. Calculate the standard deviation of the natural logarithm of SaF,j(Ti):

𝛽𝑅𝑇𝑅𝑖 = std⟨ln[𝑆𝑎𝐹,1(𝑇𝑖)] , ln[𝑆𝑎𝐹,2(𝑇𝑖)] , ln[𝑆𝑎𝐹,3(𝑇𝑖)] , … , ln[𝑆𝑎𝐹,40(𝑇𝑖)]⟩ (2-4)

Quantity RTRi is the dispersion coefficient that accounts for the record-to-record

variability in the ground motions. Note that “std” is the operation for calculating the

standard deviation.

Parameters 𝑆�̂�𝐹(𝑇𝑖) and RTRi describe the fragility curve as a lognormal distribution given

by Equation (2-5) in the form of the cumulative distribution function:

( )( )

2

F

20

ˆln ln ( )1| ( ) exp

22

x i

F i

RTRiRTRi

s Sa TP Sa T x ds

s

− = −

(2-5)

In Equation (2-5), PF|Sa(Ti) is the fragility curve (probability of failure given the value of

Sa(Ti)) (variable x representing the spectral acceleration at period Ti).

6. For the location of the transformer, construct the seismic hazard curve for period Ti (see figure

2-3 in Kitayama et al., 2016).

7. Calculate the mean annual frequency of failure, F,i, for ith period Ti, by using information on

the fragility curve (from steps 3 and 4) and the seismic hazard curve (from step 5). Quantity

F,i is given by Equation (2-6) (Krawinkler et al., 2006) in which (𝑃𝐹|𝑆𝑎) is the fragility

curve (probability of failure given the value of Sa) and 𝑑𝜆𝑆𝑎

𝑑(𝑆𝑎) is the slope of the seismic hazard

curve.

𝜆𝐹,𝑖 = ∫ (𝑃𝐹|𝑆𝑎)∞

0|

𝑑𝜆𝑆𝑎

𝑑(𝑆𝑎)| ∙ 𝑑(𝑆𝑎) (2-6)

Page 54: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

16

Note that in the calculation of Equation (2-6) the seismic hazard curve is obtained from

the curves shown in Figures 1-4 to 1-14 by interpolation at the value of the period used

for the scaling of the records.

8. The probability of failure over the lifetime of the transformer, n years, can be calculated by

assuming that the earthquake occurrence follows a Poisson distribution:

𝑃F,𝑖(𝑛 ∙ years) = 1 − exp(−𝜆F ∙ 𝑛) (2-7)

9. Repeat for different period (Ti where i=1 to 300) and calculate PF,i for each value of period.

Note that in this process of converting the available results based on scaling using the PGA as the

measure of intensity to one based on the spectral acceleration at another value of the period for the

intensity measure, every pair of horizontal-vertical ground motion used in the analysis maintained

its original as-recorded characteristics. That is, while all horizontal components used in the

analysis have the same value of their spectral acceleration at the selected period, the vertical

components have different spectral acceleration values at the same period. Guidelines for the

scaling of the vertical ground motions for seismic performance evaluation do not exist in FEMA

(2009). Some guidance provided for design practice in NIST (2011) implies that is appropriate to

use horizontal and vertical ground motions scaled to represent conditional horizontal and vertical

spectra where the conditioning periods in the horizontal and vertical directions are related to modal

properties in those two directions. That is for the horizontally only isolated transformer the vertical

conditioning period should be zero and for the horizontally-vertically isolated transformer should

be 0.5sec. The procedure then to perform a failure performance evaluation would be to generate

suites of such pairs of motions, each for several seismic intensities starting from very low to very

high (say return periods of 50 to 10000 years) and perform dynamic analysis. Kitayama and

Constantinou (2018a, 2019a) applied this approach to the seismic performance of isolated

buildings but without the vertical ground motion.

Figures 2-2 to 2-37 present results for the case of isolators with DCapacity=17.7inch for three out of

the ten studied sites: Chehalis, WA, Loma Linda, CA and Troutdale, OR. Each of these figures

presents graphs of the calculated probability of failure in a lifetime of 50 years PF (50 years) as

function of the selected period Ti used in the scaling of the motions. Vertical lines in these figures

show the value of the fundamental period of the analyzed system. For the non-isolated transformer

this period is T1=0.24sec (=1/4.3Hz) or 0.13sec (=1/7.7Hz) or 0.088sec (=1/11.3Hz). For the

isolated transformers, the period used is average effective isolation period in the horizontal

Page 55: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

17

direction at the displacement of 13.0inch (a displacement just prior to initiation of stiffening in the

smallest isolator) and in the lower bound conditions. This period was calculated as 2.1sec for the

smallest isolator and as 2.7sec for the largest isolator. The difference is due to differences in the

radii of curvature of the two isolators. The average value Teff=T1=2.4sec was used for all isolated

transformers. When isolated in the vertical direction, the system has linear elastic and linear

viscous behavior with vertical frequency of 2.0Hz and a corresponding damping ratio of 0.50. The

corresponding vertical period is 0.5sec.

The results demonstrate that the selection of the period for scaling the ground motions has an effect

on the probability of failure, which is significant in the case of the isolated transformers. When the

scaling of ground motions is based on the short periods of 0.088sec to 0.23sec, which is appropriate

for the case of the non-isolated transformers, there is a small reduction of the probability of failure

by comparison to when using the zero period for scaling. When the scaling is based on the effective

period of 2.4sec, which is appropriate for the case of the horizontally isolated transformers, there

is an increase of the probability of failure by comparison to when using the zero period for scaling.

As an example, consider the Loma Linda, CA location in Figures 2-6 and 2-7 for the non-isolated

and the horizontally isolated transformers, respectively. Consider the case of 1g limit for the

bushing transverse acceleration. For the non-isolated transformer, the probability of failure in 50

years is 0.398 when scaling is based on the PGA (as reported in Kitayama et al., 2016) and is 0.343

when scaling is based on the spectral acceleration at the fundamental period of 0.13sec. For the

isolated transformer, the probability of failure in 50 years is 0.102 when scaling is based on the

PGA (as reported in Kitayama et al., 2016) and is 0.301 when scaling is based on the spectral

acceleration at the fundamental period of 2.4sec. Based on these results, one would conclude that

horizontal isolation does not offer any important advantage (probability of failure of 0.301 versus

0.343 when non-isolated). However, the data in Figures 2-2 to 2-37 have not been corrected for

the effects of spectral shape. When the correction is made, as described in Section 3, the results

change drastically. The probability of failure for the non-isolated transformer changes from 0.343

to 0.297 and for the isolated transformer from 0.301 to 0.100. The adjusted probabilities of failure

now justify the use of horizontal isolation.

Page 56: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

18

As-installed bushing of 7.7Hz

Isolator DCapacity=17.7inch, Lower Bound Conditions with μ1=μ4=0.12 and μ2=μ3=0.08

Location Chehalis, WA

Figure 2-2 Probability of failure in lifetime of 50 years of non-isolated transformer (W=420kip,

fAI=7.7Hz, inclined bushing) located at Chehalis, WA as function of period used for scaling the

ground motions

Figure 2-3 Probability of failure in lifetime of 50 years of horizontally isolated transformer

(W=420kip, fAI=7.7Hz, inclined bushing, DCapacity=17.7inch, lower bound) located at Chehalis,

WA as function of period used for scaling the ground motions

0.00

0.02

0.04

0.06

0.08

0.10

0.12

0.14

0.16

0.18

0.20

0.0 0.5 1.0 1.5 2.0 2.5 3.0 3.5 4.0 4.5 5.0

0.00

0.01

0.02

0.03

0.04

0.05

0.06

0.0 0.5 1.0 1.5 2.0 2.5 3.0 3.5 4.0 4.5 5.0

Period for Scaling Ti (second)

PF

(5

0 y

ears

)

1g Bushing Transverse Acceleration Limit

2g Bushing Transverse Acceleration Limit

0.128

0.028

0.108

0.022

T1=0.13 sec

Period for Scaling Ti (second)

PF

(50 y

ears

)

1g Bushing Transverse Acceleration Limit

2g Bushing Transverse

Acceleration Limit

0.026

0.012 T1=Teff=2.4sec

0.036

0.020

Page 57: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

19

Figure 2-4 Probability of failure in lifetime of 50 years of horizontally-vertically isolated

transformer without rocking (W=420kip, fAI=7.7Hz, inclined bushing, DCapacity=17.7inch, lower

bound) located at Chehalis, WA as function of period used for scaling the ground motions

Figure 2-5 Probability of failure in lifetime of 50 years of horizontally-vertically isolated

transformer with rocking (W=420kip, fAI=7.7Hz, inclined bushing, DCapacity=17.7inch, lower

bound) located at Chehalis, WA as function of period used for scaling the ground motions

0.000

0.005

0.010

0.015

0.020

0.025

0.030

0.0 0.5 1.0 1.5 2.0 2.5 3.0 3.5 4.0 4.5 5.0

0.000

0.005

0.010

0.015

0.020

0.025

0.030

0.0 0.5 1.0 1.5 2.0 2.5 3.0 3.5 4.0 4.5 5.0

Period for Scaling Ti (second)

PF

(5

0 y

ears

) 1g Bushing Transverse Acceleration Limit

2g Bushing Transverse Acceleration Limit

0.013

0.008

T1=Teff=2.4sec

0.015

0.012

Period for Scaling Ti (second)

PF

(50 y

ears

)

1g Bushing Transverse

Acceleration Limit

2g Bushing Transverse

Acceleration Limit

0.010

0.006 T1=Teff=2.4sec

0.016

0.009

Page 58: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

20

As-installed bushing of 7.7Hz

Isolator DCapacity=17.7inch, Lower Bound Conditions with μ1=μ4=0.12 and μ2=μ3=0.08

Location Loma Linda, CA

Figure 2-6 Probability of failure in lifetime of 50 years of non-isolated transformer (W=420kip,

fAI=7.7Hz, inclined bushing) located at Loma Linda, CA as function of period used for scaling

the ground motions

Figure 2-7 Probability of failure in lifetime of 50 years of horizontally isolated transformer

(W=420kip, fAI=7.7Hz, inclined bushing, DCapacity=17.7inch, lower bound) located at Loma

Linda, CA as function of period used for scaling the ground motion

0.00

0.10

0.20

0.30

0.40

0.50

0.60

0.70

0.80

0.0 0.5 1.0 1.5 2.0 2.5 3.0 3.5 4.0 4.5 5.0

0.00

0.05

0.10

0.15

0.20

0.25

0.30

0.35

0.40

0.45

0.50

0.0 0.5 1.0 1.5 2.0 2.5 3.0 3.5 4.0 4.5 5.0

Period for Scaling Ti (second)

PF

(5

0 y

ears

)

1g Bushing Transverse Acceleration Limit

2g Bushing Transverse Acceleration Limit

0.398

0.108

0.343

0.075

T1=0.13 sec

Period for Scaling Ti (second)

PF

(5

0 y

ears

)

1g Bushing Transverse Acceleration Limit

2g Bushing Transverse

Acceleration Limit

0.102

0.049 T1=Teff=2.4sec

0.301

0.206

Page 59: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

21

Figure 2-8 Probability of failure in lifetime of 50 years of horizontally-vertically isolated

transformer without rocking (W=420kip, fAI=7.7Hz, inclined bushing, DCapacity=17.7inch, lower

bound) located at Loma Linda, CA as function of period used for scaling the ground motions

Figure 2-9 Probability of failure in lifetime of 50 years of horizontally-vertically isolated

transformer with rocking (W=420kip, fAI=7.7Hz, inclined bushing, DCapacity=17.7inch, lower

bound) located at Loma Linda, CA as function of period used for scaling the ground motions

0.00

0.05

0.10

0.15

0.20

0.25

0.30

0.35

0.40

0.0 0.5 1.0 1.5 2.0 2.5 3.0 3.5 4.0 4.5 5.0

0.00

0.05

0.10

0.15

0.20

0.25

0.30

0.35

0.0 0.5 1.0 1.5 2.0 2.5 3.0 3.5 4.0 4.5 5.0

Period for Scaling Ti (second)

PF

(5

0 y

ears

) 1g Bushing Transverse

Acceleration Limit

2g Bushing Transverse

Acceleration Limit

0.053

0.033 T1=Teff=2.4sec

0.175

0.151

Period for Scaling Ti (second)

PF

(50 y

ears

)

1g Bushing Transverse Acceleration Limit

2g Bushing Transverse

Acceleration Limit

0.041

0.024 T1=Teff=2.4sec

0.177

0.123

Page 60: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

22

As-installed bushing of 7.7Hz

Isolator DCapacity=17.7inch, Lower Bound Conditions with μ1=μ4=0.12 and μ2=μ3=0.08

Location Troutdale, OR

Figure 2-10 Probability of failure in lifetime of 50 years of non-isolated transformer (W=420kip,

fAI=7.7Hz, inclined bushing) located at Troutdale, OR as function of period used for scaling the

ground motions

Figure 2-11 Probability of failure in lifetime of 50 years of horizontally isolated transformer

(W=420kip, fAI=7.7Hz, inclined bushing, DCapacity=17.7inch, lower bound) located at Troutdale,

OR as function of period used for scaling the ground motions

0.00

0.02

0.04

0.06

0.08

0.10

0.12

0.14

0.0 0.5 1.0 1.5 2.0 2.5 3.0 3.5 4.0 4.5 5.0

0.00

0.01

0.02

0.03

0.04

0.05

0.0 0.5 1.0 1.5 2.0 2.5 3.0 3.5 4.0 4.5 5.0

Period for Scaling Ti (second)

PF

(5

0 y

ears

)

2g Bushing Transverse Acceleration Limit

0.071

0.014

0.056

0.009

T1=0.13 sec

Period for Scaling Ti (second)

PF

(5

0 y

ears

)

1g Bushing Transverse Acceleration Limit

2g Bushing Transverse

Acceleration Limit

0.013

0.006 T1=Teff=2.4sec

0.025

0.013

1g Bushing Transverse Acceleration Limit

Page 61: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

23

Figure 2-12 Probability of failure in lifetime of 50 years of horizontally-vertically isolated

transformer without rocking (W=420kip, fAI=7.7Hz, inclined bushing, DCapacity=17.7inch, lower

bound) located at Troutdale, OR as function of period used for scaling the ground motions

Figure 2-13 Probability of failure in lifetime of 50 years of horizontally-vertically isolated

transformer with rocking (W=420kip, fAI=7.7Hz, inclined bushing, DCapacity=17.7inch, lower

bound) located at Troutdale, OR as function of period used for scaling the ground motions

0.000

0.005

0.010

0.015

0.020

0.0 0.5 1.0 1.5 2.0 2.5 3.0 3.5 4.0 4.5 5.0

0.000

0.005

0.010

0.015

0.020

0.0 0.5 1.0 1.5 2.0 2.5 3.0 3.5 4.0 4.5 5.0

Period for Scaling Ti (second)

PF

(5

0 y

ears

) 1g Bushing Transverse Acceleration Limit

2g Bushing Transverse

Acceleration Limit

0.006

0.004 T1=Teff=2.4sec

0.009

0.007

Period for Scaling Ti (second)

PF

(50 y

ears

)

1g Bushing Transverse Acceleration Limit

2g Bushing Transverse

Acceleration Limit

0.005

0.003 T1=Teff=2.4sec

0.009

0.005

Page 62: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

24

As-installed bushing of 4.3Hz

Isolator DCapacity=17.7inch, Lower Bound Conditions with μ1=μ4=0.12 and μ2=μ3=0.08

Location Chehalis, WA

Figure 2-14 Probability of failure in lifetime of 50 years of non-isolated transformer (W=420kip,

fAI=4.3Hz, inclined bushing) located at Chehalis, WA as function of period used for scaling the

ground motions

Figure 2-15 Probability of failure in lifetime of 50 years of horizontally isolated transformer

(W=420kip, fAI=4.3Hz, inclined bushing, DCapacity=17.7inch, lower bound) located at Chehalis,

WA as function of period used for scaling the ground motions

0.00

0.02

0.04

0.06

0.08

0.10

0.12

0.14

0.16

0.18

0.20

0.0 0.5 1.0 1.5 2.0 2.5 3.0 3.5 4.0 4.5 5.0

0.00

0.01

0.02

0.03

0.04

0.05

0.0 0.5 1.0 1.5 2.0 2.5 3.0 3.5 4.0 4.5 5.0

Period for Scaling Ti (second)

PF

(5

0 y

ears

)

1g Bushing Transverse Acceleration Limit

2g Bushing Transverse Acceleration Limit

0.074

0.012

0.070

0.012

T1=0.24 sec

Period for Scaling Ti (second)

PF

(50 y

ears

)

1g Bushing Transverse Acceleration Limit

2g Bushing Transverse Acceleration Limit

0.013

0.010

T1=Teff=2.4sec

0.021

0.018

Page 63: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

25

Figure 2-16 Probability of failure in lifetime of 50 years of horizontally-vertically isolated

transformer without rocking (W=420kip, fAI=4.3Hz, inclined bushing, DCapacity=17.7inch, lower

bound) located at Chehalis, WA as function of period used for scaling the ground motions

Figure 2-17 Probability of failure in lifetime of 50 years of horizontally-vertically isolated

transformer with rocking (W=420kip, fAI=4.3Hz, inclined bushing, DCapacity=17.7inch, lower

bound) located at Chehalis, WA as function of period used for scaling the ground motions

0.000

0.005

0.010

0.015

0.020

0.025

0.030

0.0 0.5 1.0 1.5 2.0 2.5 3.0 3.5 4.0 4.5 5.0

0.00

0.01

0.02

0.03

0.04

0.05

0.0 0.5 1.0 1.5 2.0 2.5 3.0 3.5 4.0 4.5 5.0

Period for Scaling Ti (second)

PF

(5

0 y

ears

)

1g Bushing Transverse Acceleration Limit

2g Bushing Transverse

Acceleration Limit

0.010

0.008 T1=Teff=2.4sec

0.013

0.012

Period for Scaling Ti (second)

PF

(50 y

ears

)

1g Bushing Transverse

Acceleration Limit

2g Bushing Transverse

Acceleration Limit

0.018

0.007 T1=Teff=2.4sec

0.025

0.009

Page 64: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

26

As-installed bushing of 4.3Hz

Isolator DCapacity=17.7inch, Lower Bound Conditions with μ1=μ4=0.12 and μ2=μ3=0.08

Location Loma Linda, CA

Figure 2-18 Probability of failure in lifetime of 50 years of non-isolated transformer (W=420kip,

fAI=4.3Hz, inclined bushing) located at Loma Linda, CA as function of period used for scaling

the ground motions

Figure 2-19 Probability of failure in lifetime of 50 years of horizontally isolated transformer

(W=420kip, fAI=4.3Hz, inclined bushing, DCapacity=17.7inch, lower bound) located at Loma

Linda, CA as function of period used for scaling the ground motions

0.00

0.10

0.20

0.30

0.40

0.50

0.60

0.70

0.80

0.0 0.5 1.0 1.5 2.0 2.5 3.0 3.5 4.0 4.5 5.0

0.00

0.05

0.10

0.15

0.20

0.25

0.30

0.35

0.0 0.5 1.0 1.5 2.0 2.5 3.0 3.5 4.0 4.5 5.0

Period for Scaling Ti (second)

PF

(5

0 y

ears

)

1g Bushing Transverse Acceleration Limit

2g Bushing Transverse Acceleration Limit

0.261

0.047

0.234

0.038

T1=0.24 sec

Period for Scaling Ti (second)

PF

(5

0 y

ears

)

1g Bushing Transverse Acceleration Limit

2g Bushing Transverse

Acceleration Limit

0.051

0.042 T1=Teff=2.4sec

0.212

0.197

Page 65: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

27

Figure 2-20 Probability of failure in lifetime of 50 years of horizontally-vertically isolated

transformer without rocking (W=420kip, fAI=4.3Hz, inclined bushing, DCapacity=17.7inch, lower

bound) located at Loma Linda, CA as function of period used for scaling the ground motions

Figure 2-21 Probability of failure in lifetime of 50 years of horizontally-vertically isolated

transformer with rocking (W=420kip, fAI=4.3Hz, inclined bushing, DCapacity=17.7inch, lower

bound) located at Loma Linda, CA as function of period used for scaling the ground motions

0.00

0.05

0.10

0.15

0.20

0.25

0.30

0.0 0.5 1.0 1.5 2.0 2.5 3.0 3.5 4.0 4.5 5.0

0.00

0.05

0.10

0.15

0.20

0.25

0.30

0.35

0.40

0.0 0.5 1.0 1.5 2.0 2.5 3.0 3.5 4.0 4.5 5.0

Period for Scaling Ti (second)

PF

(5

0 y

ears

) 1g Bushing Transverse Acceleration Limit

2g Bushing Transverse

Acceleration Limit

0.041

0.032

T1=Teff=2.4sec

0.161

0.149

Period for Scaling Ti (second)

PF

(50 y

ears

)

1g Bushing Transverse

Acceleration Limit

2g Bushing Transverse

Acceleration Limit

0.072

0.029

T1=Teff=2.4sec

0.240

0.120

Page 66: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

28

As-installed bushing of 4.3Hz

Isolator DCapacity=17.7inch, Lower Bound Conditions with μ1=μ4=0.12 and μ2=μ3=0.08

Location Troutdale, OR

Figure 2-22 Probability of failure in lifetime of 50 years of non-isolated transformer (W=420kip,

fAI=4.3Hz, inclined bushing) located at Troutdale, OR as function of period used for scaling the

ground motions

Figure 2-23 Probability of failure in lifetime of 50 years of horizontally isolated transformer

(W=420kip, fAI=4.3Hz, inclined bushing, DCapacity=17.7inch, lower bound) located at Troutdale,

OR as function of period used for scaling the ground motions

0.00

0.01

0.02

0.03

0.04

0.05

0.06

0.07

0.08

0.09

0.10

0.0 0.5 1.0 1.5 2.0 2.5 3.0 3.5 4.0 4.5 5.0

0.000

0.005

0.010

0.015

0.020

0.025

0.030

0.0 0.5 1.0 1.5 2.0 2.5 3.0 3.5 4.0 4.5 5.0

Period for Scaling Ti (second)

PF

(5

0 y

ears

)

1g Bushing Transverse Acceleration Limit

2g Bushing Transverse Acceleration Limit

0.038

0.005

0.037

0.005

T1=0.24 sec

Period for Scaling Ti (second)

PF

(50 y

ears

)

1g Bushing Transverse Acceleration Limit

2g Bushing Transverse Acceleration Limit

0.006

0.005 T1=Teff=2.4sec

0.014

0.011

Page 67: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

29

Figure 2-24 Probability of failure in lifetime of 50 years of horizontay-vertically isolated

transformer without rocking (W=420kip, fAI=4.3Hz, inclined bushing, DCapacity=17.7inch, lower

bound) located at Troutdale, OR as function of period used for scaling the ground motions

Figure 2-25 Probability of failure in lifetime of 50 years of horizontally-vertically isolated

transformer with rocking (W=420kip, fAI=4.3Hz, inclined bushing, DCapacity=17.7inch, lower

bound) located at Troutdale, OR as function of period used for scaling the ground motions

0.000

0.005

0.010

0.015

0.0 0.5 1.0 1.5 2.0 2.5 3.0 3.5 4.0 4.5 5.0

0.00

0.01

0.02

0.03

0.04

0.0 0.5 1.0 1.5 2.0 2.5 3.0 3.5 4.0 4.5 5.0

Period for Scaling Ti (second)

PF

(5

0 y

ears

) 1g Bushing Transverse Acceleration Limit

2g Bushing Transverse

Acceleration Limit

0.005

0.004

T1=Teff=2.4sec

0.008

0.007

Period for Scaling Ti (second)

PF

(50 y

ears

)

1g Bushing Transverse Acceleration Limit

2g Bushing Transverse Acceleration Limit

0.009

0.003

T1=Teff=2.4sec

0.017

0.005

Page 68: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

30

As-installed bushing of 11.3Hz

Isolator DCapacity=17.7inch, Lower Bound Conditions with μ1=μ4=0.12 and μ2=μ3=0.08

Location Chehalis, WA

Figure 2-26 Probability of failure in lifetime of 50 years of non-isolated transformer (W=420kip,

fAI=11.3Hz, inclined bushing) located at Chehalis, WA as function of period used for scaling the

ground motions

Figure 2-27 Probability of failure in lifetime of 50 years of horizontally isolated transformer

(W=420kip, fAI=11.3Hz, inclined bushing, DCapacity=17.7inch, lower bound) located at Chehalis,

WA as function of period used for scaling the ground motions

0.00

0.01

0.02

0.03

0.04

0.05

0.06

0.07

0.08

0.0 0.5 1.0 1.5 2.0 2.5 3.0 3.5 4.0 4.5 5.0

0.00

0.01

0.02

0.03

0.04

0.05

0.06

0.0 0.5 1.0 1.5 2.0 2.5 3.0 3.5 4.0 4.5 5.0

Period for Scaling Ti (second)

PF

(5

0 y

ears

)

1g Bushing Transverse Acceleration Limit

2g Bushing Transverse Acceleration Limit

0.029

0.003

0.041

0.006

T1=0.09 sec

Period for Scaling Ti (second)

PF

(50 y

ears

)

1g Bushing Transverse Acceleration Limit

2g Bushing Transverse Acceleration Limit

0.024

0.014

T1=Teff=2.4sec

0.030

0.021

Page 69: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

31

Figure 2-28 Probability of failure in lifetime of 50 years of horizontally-vertically isolated

transformer without rocking (W=420kip, fAI=11.3Hz, inclined bushing, DCapacity=17.7inch, lower

bound) located at Chehalis, WA as function of period used for scaling the ground motions

Figure 2-29 Probability of failure in lifetime of 50 years of horizontally-vertically isolated

transformer with rocking (W=420kip, fAI=11.3Hz, inclined bushing, DCapacity=17.7inch, lower

bound) located at Chehalis, WA as function of period used for scaling the ground motions

0.000

0.005

0.010

0.015

0.020

0.025

0.030

0.0 0.5 1.0 1.5 2.0 2.5 3.0 3.5 4.0 4.5 5.0

0.000

0.005

0.010

0.015

0.020

0.0 0.5 1.0 1.5 2.0 2.5 3.0 3.5 4.0 4.5 5.0

Period for Scaling Ti (second)

PF

(5

0 y

ears

) 1g Bushing Transverse Acceleration Limit

2g Bushing Transverse

Acceleration Limit

0.011

0.010

T1=Teff=2.4sec

0.015

0.013

Period for Scaling Ti (second)

PF

(50 y

ears

)

1g Bushing Transverse Acceleration Limit

2g Bushing Transverse

Acceleration Limit

0.006

0.005 T1=Teff=2.4sec

0.010

0.008

Page 70: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

32

As-installed bushing of 11.3Hz

Isolator DCapacity=17.7inch, Lower Bound Conditions with μ1=μ4=0.12 and μ2=μ3=0.08

Location Loma Linda, CA

Figure 2-30 Probability of failure in lifetime of 50 years of non-isolated transformer (W=420kip,

fAI=11.3Hz, inclined bushing) located at Loma Linda, CA as function of period used for scaling

the ground motions

Figure 2-31 Probability of failure in lifetime of 50 years of horizontally isolated transformer

(W=420kip, fAI=11.3Hz, inclined bushing, DCapacity=17.7inch, lower bound) located at Loma

Linda, CA as function of period used for scaling the ground motions

0.00

0.10

0.20

0.30

0.40

0.50

0.60

0.0 0.5 1.0 1.5 2.0 2.5 3.0 3.5 4.0 4.5 5.0

0.00

0.05

0.10

0.15

0.20

0.25

0.30

0.35

0.40

0.45

0.0 0.5 1.0 1.5 2.0 2.5 3.0 3.5 4.0 4.5 5.0

Period for Scaling Ti (second)

PF

(5

0 y

ears

)

1g Bushing Transverse Acceleration Limit

2g Bushing Transverse Acceleration Limit

0.113

0.013

0.143

0.019

T1=0.09 sec

Period for Scaling Ti (second)

PF

(50 y

ears

)

1g Bushing Transverse Acceleration Limit

2g Bushing Transverse

Acceleration Limit

0.094

0.055 T1=Teff=2.4sec

0.267

0.221

Page 71: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

33

Figure 2-32 Probability of failure in lifetime of 50 years of horizontally-vertically isolated

transformer without rocking (W=420kip, fAI=11.3Hz, inclined bushing, DCapacity=17.7inch, lower

bound) located at Loma Linda, CA as function of period used for scaling the ground motions

Figure 2-33 Probability of failure in lifetime of 50 years of horizontally-vertically isolated

transformer with rocking (W=420kip, fAI=11.3Hz, inclined bushing, DCapacity=17.7inch, lower

bound) located at Loma Linda, CA as function of period used for scaling the ground motions

0.00

0.05

0.10

0.15

0.20

0.25

0.30

0.0 0.5 1.0 1.5 2.0 2.5 3.0 3.5 4.0 4.5 5.0

0.00

0.05

0.10

0.15

0.20

0.25

0.0 0.5 1.0 1.5 2.0 2.5 3.0 3.5 4.0 4.5 5.0

Period for Scaling Ti (second)

PF

(5

0 y

ears

) 1g Bushing Transverse Acceleration Limit

2g Bushing Transverse

Acceleration Limit

0.043

0.039 T1=Teff=2.4sec

0.176

0.156

Period for Scaling Ti (second)

PF

(50 y

ears

)

1g Bushing Transverse Acceleration Limit

2g Bushing Transverse

Acceleration Limit

0.024

0.021 T1=Teff=2.4sec

0.135

0.115

Page 72: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

34

As-installed bushing of 11.3Hz

Isolator DCapacity=17.7inch, Lower Bound Conditions with μ1=μ4=0.12 and μ2=μ3=0.08

Location Troutdale, OR

Figure 2-34 Probability of failure in lifetime of 50 years of non-isolated transformer (W=420kip,

fAI=11.3Hz, inclined bushing) located at Troutdale, OR as function of period used for scaling the

ground motions

Figure 2-35 Probability of failure in lifetime of 50 years of horizontally isolated transformer

(W=420kip, fAI=11.3Hz, inclined bushing, DCapacity=17.7inch, lower bound) located at Troutdale,

OR as function of period used for scaling the ground motions

0.00

0.01

0.02

0.03

0.04

0.05

0.06

0.0 0.5 1.0 1.5 2.0 2.5 3.0 3.5 4.0 4.5 5.0

0.00

0.01

0.02

0.03

0.04

0.05

0.0 0.5 1.0 1.5 2.0 2.5 3.0 3.5 4.0 4.5 5.0

Period for Scaling Ti (second)

PF

(5

0 y

ears

)

1g Bushing Transverse Acceleration Limit

2g Bushing Transverse Acceleration Limit

0.014

0.013

0.017

0.002

T1=0.09 sec

Period for Scaling Ti (second)

PF

(50 y

ears

)

1g Bushing Transverse Acceleration Limit

2g Bushing Transverse

Acceleration Limit

0.012

0.006 T1=Teff=2.4sec

0.021

0.014

Page 73: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

35

Figure 2-36 Probability of failure in lifetime of 50 years of horizontally-vertically isolated

transformer without rocking (W=420kip, fAI=11.3Hz, inclined bushing, DCapacity=17.7inch, lower

bound) located at Troutdale, OR as function of period used for scaling the ground motions

Figure 2-37 Probability of failure in lifetime of 50 years of horizontally-vertically isolated

transformer with rocking (W=420kip, fAI=11.3Hz, inclined bushing, DCapacity=17.7inch, lower

bound) located at Troutdale, OR as function of period used for scaling the ground motions

0.000

0.004

0.008

0.012

0.016

0.0 0.5 1.0 1.5 2.0 2.5 3.0 3.5 4.0 4.5 5.0

0.000

0.002

0.004

0.006

0.008

0.010

0.0 0.5 1.0 1.5 2.0 2.5 3.0 3.5 4.0 4.5 5.0

Period for Scaling Ti (second)

PF

(5

0 y

ears

) 1g Bushing Transverse Acceleration Limit

2g Bushing Transverse

Acceleration Limit

0.005

0.004 T1=Teff=2.4sec

0.009

0.007

Period for Scaling Ti (second)

PF

(50 y

ears

)

1g Bushing Transverse Acceleration Limit

2g Bushing Transverse

Acceleration Limit

0.003

0.002 T1=Teff=2.4sec

0.006

0.004

Page 74: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on
Page 75: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

37

SECTION 3

EFFECT OF SPECTRAL SHAPE ON THE FRAGILITY OF ELECTRICAL

TRANSFORMERS

The results in Figures 2-2 to 2-37 are based on analyses in which the original as-recorded motions

have been scaled without any consideration of the spectral shape effects. These effects are the

subject of this section. In general, these effects are dependent on the value of the target expected

“epsilon” (see Appendix A) which differs between the ten considered sites and is also dependent

on the period.

In general, consideration of the spectral shape effects results in a change in the median spectral

acceleration at failure at the fundamental period Ti (quantity 𝑆�̂�𝐹(𝑇𝑖) obtained by use of Equation

2-3). In addition, consideration of uncertainties results in increases of the dispersion coefficient

(quantity RTR calculated using Equation 2-4).

We corrected for the spectral shape effects for the non-isolated and the isolated transformers

studied when the scaling is based on the spectral acceleration at the fundamental period Sa(Ti)

where Ti is either 0.13sec or 2.3sec. Tables 3-1 to 3-60 present the results on the probability of

failure in 50 years of lifetime for all considered cases (10 locations, 3 bushing frequencies and 2

isolator displacement capacities for the 420 kip transformer). Appendix A describes the method

for adjusting the results for spectral shape effects, and presents details of the method for

representative cases.

Tables 3-1 to 3-60 also include the value of the probability of failure reported in report MCEER-

16-0010 (Kitayama et al, 2016) for which the scaling of ground motions was based on the PGA

(spectral acceleration at zero period) and the spectral shape effects were not considered. We

considered only the record-to-record uncertainty in the calculation of all values of the probability

of failure in these tables, without any adjustment of the results for additional uncertainties. Section

4 addresses uncertainties.

The results in Tables 3-1 to 3-60 demonstrate that scaling of the ground motions at the fundamental

period and consideration of spectral shape effects change the probabilities of failure which

generally increase for the isolated transformers and slightly decrease for the non-isolated

transformers. Note that there is a significant increase in the probability of failure for the isolated

transformers due to the scaling using as measure of intensity the spectral acceleration at the

fundamental period of 2.4sec instead of the PGA. This increase is then modified due to the effects

Page 76: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

38

of the spectral shape in some cases by a minor amount, whereas in others (e.g., Loma Linda site)

the probabilities of failure are reduced by significant amounts. Nevertheless, the probabilities of

failure for seismically isolated transformers are smaller than those of non-isolated transformers,

particularly for the case of the bushing acceleration limit of 1g. The benefits of seismic isolation

further improve when the larger displacement capacity isolator is considered although, as it will

be discussed later this is due, in some cases, to the increased displacement capacity, whereas in

other cases is due to the lower stiffness of the isolator.

Note that the values of the median spectral acceleration at the fundamental period 𝑆�̂�𝐹(𝑇1) and of

the dispersion coefficient βRTR that describe the fragility curve without the correction for the

spectral shape effects are independent of the location of the transformer. However, the median

spectral acceleration value changes when the correction for the spectral shape effects is applied

and then it depends on the location. The dependence on the location results from the dependence

of the correction for the spectral shape effects on the expected value of epsilon at the location of

the transformer (see details in Appendix A).

Moreover, note that the values of the dispersion coefficient are generally in the range of about 0.2

to about 0.4 except for the case of the horizontally only isolated transformers where the values are

larger and about 0.5 to 0.7. (In addition, one case of the horizontally-vertically isolated transformer

with rocking, 4.3Hz frequency bushing of 1g acceleration limit resulted in a large value of the

dispersion coefficient). Values of the dispersion coefficient beyond 0.4 have not been computed

in any of the FEMA (2009) studies or any of those of Kitayama and Constantinou (2018a, 2018b;

2019a, 2019b) for seismically isolated buildings, all of which utilized the same set of ground

motions. We believe this difference results in from the use of vertical ground motion. The

vertical ground motion has important effects on the horizontally isolated transformer (as a result

of uplift and impact-see Kitayama et al., 2016 for modeling details) but has lesser effects on the

horizontally-vertically isolated transformer (uplift and impact are essentially eliminated), and has

practically no effect on the non-isolated transformer. The origin of the problem is related to the

methodology used to carry out the incremental dynamic analysis in which the scaling of the

horizontal components of the ground motions was based on the horizontal spectral acceleration

value at the fundamental period, whereas the vertical component maintained its original as-

recorded characteristics as discussed in more detail in Section 2.

FEMA (2009) recommends the use of an upper bound value of 0.4 for the record-to-record

dispersion coefficient. This has not been done in the results presented in Tables 30-1 to 3-60 that

follow. Accordingly, the computed probabilities of failure for the horizontally only isolated

Page 77: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

39

transformers may have been overestimated. Section 4 further addresses this issue and presents

summary results on the probability of failure including adjusted results for the effects of additional

uncertainties.

Page 78: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

40

Table 3-1 Summary of results for probability of failure for isolated and non-isolated transformer with W=420kip, fAI=7.7Hz and inclined bushing. When isolated, DCapacity=17.7inch and lower

bound friction properties. Location: Vancouver, WA

System

Transverse

Bushing

Acceleration

Limit (g)

Without Spectral Shape

Effects With Spectral Shape Effects

Reported in

MCEER-16-0010

Median

𝑆�̂�𝐹(𝑇1)(g)

RTR PF (50

years)

Median

𝑆�̂�𝐹(𝑇1)(g)

RTR PF (50

years) PF (50 years)

Non-isolated

T1=0.13sec

1g 0.735 0.276 0.063 0.704 0.276 0.069 0.089

2g 1.470 0.276 0.012 1.408 0.276 0.013 0.016

Horizontally

isolated

T1=2.4sec

1g 0.331 0.656 0.028 0.284 0.656 0.036 0.015

2g 0.410 0.492 0.014 0.369 0.492 0.018 0.007

Horizontally-

vertically

isolated

without

rocking

T1=2.4sec

1g 0.442 0.393 0.010 0.415 0.393 0.012 0.008

2g 0.466 0.296 0.008 0.462 0.296 0.008 0.005

Horizontally-

vertically

isolated with

rocking

T1=2.4sec

1g 0.439 0.411 0.011 0.411 0.411 0.013 0.006

2g 0.525 0.293 0.006 0.512 0.293 0.006 0.003

Table 3-2 Summary of results for probability of failure for isolated and non-isolated transformer with W=420kip, fAI=7.7Hz and inclined bushing. When isolated, DCapacity=17.7inch and lower

bound friction properties. Location: Saranap, CA

System

Transverse

Bushing

Acceleration

Limit (g)

Without Spectral Shape

Effects With Spectral Shape Effects

Reported in

MCEER-16-0010

Median

𝑆�̂�𝐹(𝑇1)(g)

RTR PF (50

years)

Median

𝑆�̂�𝐹(𝑇1)(g)

RTR PF (50

years) PF (50 years)

Non-isolated

T1=0.13sec

1g 0.735 0.276 0.300 0.782 0.276 0.266 0.359

2g 1.470 0.276 0.047 1.564 0.276 0.038 0.077

Horizontally

isolated

T1=2.4sec

1g 0.331 0.656 0.197 0.588 0.656 0.067 0.072

2g 0.410 0.492 0.100 0.644 0.492 0.033 0.029

Horizontally-

vertically

isolated

without

rocking

T1=2.4sec

1g 0.442 0.393 0.068 0.620 0.393 0.027 0.033

2g 0.466 0.296 0.048 0.639 0.296 0.018 0.019

Horizontally-

vertically

isolated with

rocking T1=2.4sec

1g 0.439 0.411 0.072 0.646 0.411 0.025 0.024

2g 0.525 0.293 0.034 0.704 0.293 0.013 0.013

Page 79: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

41

Table 3-3 Summary of results for probability of failure for isolated and non-isolated transformer with W=420kip, fAI=7.7Hz and inclined bushing. When isolated, DCapacity=17.7inch and lower

bound friction properties. Location: Loma Linda, CA

System

Transverse

Bushing

Acceleration

Limit (g)

Without Spectral Shape

Effects With Spectral Shape Effects

Reported in

MCEER-16-0010

Median

𝑆�̂�𝐹(𝑇1)(g)

RTR PF (50

years)

Median

𝑆�̂�𝐹(𝑇1)(g)

RTR PF (50

years) PF (50 years)

Non-isolated

T1=0.13sec

1g 0.735 0.276 0.108 0.782 0.276 0.309 0.398

2g 1.470 0.276 0.075 1.565 0.276 0.063 0.108

Horizontally

isolated

T1=2.4sec

1g 0.331 0.656 0.301 0.744 0.656 0.103 0.102

2g 0.410 0.492 0.206 0.770 0.492 0.078 0.049

Horizontally-

vertically

isolated

without

rocking

T1=2.4sec

1g 0.442 0.393 0.175 0.706 0.393 0.081 0.053

2g 0.466 0.296 0.151 0.709 0.296 0.073 0.033

Horizontally-

vertically

isolated with

rocking

T1=2.4sec

1g 0.439 0.411 0.177 0.748 0.411 0.074 0.041

2g 0.525 0.293 0.123 0.780 0.293 0.059 0.024

Table 3-4 Summary of results for probability of failure for isolated and non-isolated transformer with W=420kip, fAI=7.7Hz and inclined bushing. When isolated, DCapacity=17.7inch and lower

bound friction properties. Location: Aberdeen, WA

System

Transverse

Bushing

Acceleration

Limit (g)

Without Spectral Shape

Effects With Spectral Shape Effects

Reported in

MCEER-16-0010

Median

𝑆�̂�𝐹(𝑇1)(g)

RTR PF (50

years)

Median

𝑆�̂�𝐹(𝑇1)(g)

RTR PF (50

years) PF (50 years)

Non-isolated

T1=0.13sec

1g 0.735 0.276 0.129 0.737 0.276 0.128 0.145

2g 1.470 0.276 0.038 1.473 0.276 0.038 0.044

Horizontally

isolated

T1=2.4sec

1g 0.331 0.656 0.051 0.359 0.656 0.047 0.042

2g 0.410 0.492 0.036 0.441 0.492 0.033 0.025

Horizontally-

vertically

isolated without

rocking

T1=2.4sec

1g 0.442 0.393 0.031 0.472 0.393 0.028 0.025

2g 0.466 0.296 0.027 0.513 0.296 0.024 0.018

Horizontally-

vertically

isolated with

rocking

T1=2.4sec

1g 0.439 0.411 0.031 0.475 0.411 0.028 0.022

2g 0.525 0.293 0.023 0.567 0.293 0.021 0.014

Page 80: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

42

Table 3-5 Summary of results for probability of failure for isolated and non-isolated transformer with W=420kip, fAI=7.7Hz and inclined bushing. When isolated, DCapacity=17.7inch and lower

bound friction properties. Location: Chehalis, WA

System

Transverse

Bushing

Acceleration

Limit (g)

Without Spectral Shape

Effects With Spectral Shape Effects

Reported in

MCEER-16-0010

Median

𝑆�̂�𝐹(𝑇1)(g)

RTR PF (50

years)

Median

𝑆�̂�𝐹(𝑇1)(g)

RTR PF (50

years) PF (50 years)

Non-isolated

T1=0.13sec

1g 0.735 0.276 0.108 0.717 0.276 0.113 0.128

2g 1.470 0.276 0.022 1.434 0.276 0.024 0.028

Horizontally

isolated

T1=2.4sec

1g 0.331 0.656 0.036 0.286 0.656 0.045 0.026

2g 0.410 0.492 0.020 0.372 0.492 0.024 0.012

Horizontally-

vertically

isolated

without

rocking

T1=2.4sec

1g 0.442 0.393 0.015 0.415 0.393 0.017 0.013

2g 0.466 0.296 0.012 0.462 0.296 0.012 0.008

Horizontally-

vertically

isolated with

rocking

T1=2.4sec

1g 0.439 0.411 0.016 0.411 0.411 0.018 0.010

2g 0.525 0.293 0.009 0.513 0.293 0.010 0.006

Table 3-6 Summary of results for probability of failure for isolated and non-isolated transformer with W=420kip, fAI=7.7Hz and inclined bushing. When isolated, DCapacity=17.7inch and lower

bound friction properties. Location: Hillsboro, OR

System

Transverse

Bushing

Acceleration

Limit (g)

Without Spectral Shape

Effects With Spectral Shape Effects

Reported in

MCEER-16-0010

Median

𝑆�̂�𝐹(𝑇1)(g)

RTR PF (50

years)

Median

𝑆�̂�𝐹(𝑇1)(g)

RTR PF (50

years) PF (50 years)

Non-isolated

T1=0.13sec

1g 0.735 0.276 0.071 0.711 0.276 0.076 0.094

2g 1.470 0.276 0.015 1.422 0.276 0.017 0.021

Horizontally

isolated

T1=2.4sec

1g 0.331 0.656 0.032 0.284 0.656 0.040 0.020

2g 0.410 0.492 0.018 0.369 0.492 0.022 0.009

Horizontally-

vertically

isolated without

rocking

T1=2.4sec

1g 0.442 0.393 0.014 0.415 0.393 0.016 0.010

2g 0.466 0.296 0.011 0.462 0.296 0.011 0.006

Horizontally-

vertically

isolated with

rocking

T1=2.4sec

1g 0.439 0.411 0.014 0.411 0.411 0.016 0.008

2g 0.525 0.293 0.008 0.512 0.293 0.009 0.005

Page 81: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

43

Table 3-7 Summary of results for probability of failure for isolated and non-isolated transformer with W=420kip, fAI=7.7Hz and inclined bushing. When isolated, DCapacity=17.7inch and lower

bound friction properties. Location: Eugene, OR

System

Transverse

Bushing

Acceleration

Limit (g)

Without Spectral Shape

Effects With Spectral Shape Effects

Reported in

MCEER-16-0010

Median

𝑆�̂�𝐹(𝑇1)(g)

RTR PF (50

years)

Median

𝑆�̂�𝐹(𝑇1)(g)

RTR PF (50

years) PF (50 years)

Non-isolated

T1=0.13sec

1g 0.735 0.276 0.049 0.704 0.276 0.052 0.038

2g 1.470 0.276 0.014 1.407 0.276 0.015 0.007

Horizontally

isolated

T1=2.4sec

1g 0.331 0.656 0.030 0.279 0.656 0.038 0.007

2g 0.410 0.492 0.019 0.364 0.492 0.023 0.004

Horizontally-

vertically

isolated

without

rocking

T1=2.4sec

1g 0.442 0.393 0.015 0.411 0.393 0.017 0.004

2g 0.466 0.296 0.013 0.458 0.296 0.013 0.003

Horizontally-

vertically

isolated with

rocking

T1=2.4sec

1g 0.439 0.411 0.016 0.406 0.411 0.018 0.003

2g 0.525 0.293 0.010 0.508 0.293 0.011 0.002

Table 3-8 Summary of results for probability of failure for isolated and non-isolated transformer with W=420kip, fAI=7.7Hz and inclined bushing. When isolated, DCapacity=17.7inch and lower

bound friction properties. Location: Wilsonville, OR

System

Transverse

Bushing

Acceleration

Limit (g)

Without Spectral Shape

Effects With Spectral Shape Effects

Reported in

MCEER-16-0010

Median

𝑆�̂�𝐹(𝑇1)(g)

RTR PF (50

years)

Median

𝑆�̂�𝐹(𝑇1)(g)

RTR PF (50

years) PF (50 years)

Non-isolated

T1=0.13sec

1g 0.735 0.276 0.064 0.705 0.276 0.069 0.087

2g 1.470 0.276 0.012 1.410 0.276 0.014 0.018

Horizontally

isolated

T1=2.4sec

1g 0.331 0.656 0.028 0.285 0.656 0.036 0.017

2g 0.410 0.492 0.015 0.370 0.492 0.018 0.008

Horizontally-

vertically

isolated without

rocking

T1=2.4sec

1g 0.442 0.393 0.011 0.416 0.393 0.013 0.008

2g 0.466 0.296 0.009 0.463 0.296 0.009 0.005

Horizontally-

vertically

isolated with

rocking

T1=2.4sec

1g 0.439 0.411 0.012 0.412 0.411 0.013 0.006

2g 0.525 0.293 0.006 0.513 0.293 0.007 0.004

Page 82: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

44

Table 3-9 Summary of results for probability of failure for isolated and non-isolated transformer with W=420kip, fAI=7.7Hz and inclined bushing. When isolated, DCapacity=17.7inch and lower

bound friction properties. Location: Curry County, OR

System

Transverse

Bushing

Acceleration

Limit (g)

Without Spectral Shape

Effects With Spectral Shape Effects

Reported in

MCEER-16-0010

Median

𝑆�̂�𝐹(𝑇1)(g)

RTR PF (50

years)

Median

𝑆�̂�𝐹(𝑇1)(g)

RTR PF (50

years) PF (50 years)

Non-isolated

T1=0.24sec

1g 0.735 0.276 0.111 0.778 0.276 0.103 0.123

2g 1.470 0.276 0.038 1.556 0.276 0.034 0.047

Horizontally

isolated

T1=2.4sec

1g 0.331 0.656 0.085 0.571 0.656 0.046 0.046

2g 0.410 0.492 0.062 0.629 0.492 0.036 0.029

Horizontally-

vertically

isolated without

rocking

T1=2.4sec

1g 0.441 0.393 0.055 0.610 0.393 0.035 0.030

2g 0.466 0.296 0.049 0.630 0.296 0.031 0.022

Horizontally-

vertically

isolated with

rocking

T1=2.4sec

1g 0.439 0.411 0.055 0.634 0.411 0.033 0.026

2g 0.525 0.293 0.041 0.695 0.293 0.027 0.017

Table 3-10 Summary of results for probability of failure for isolated and non-isolated transformer with W=420kip, fAI=7.7Hz and inclined bushing. When isolated, DCapacity=17.7inch

and lower bound friction properties. Location: Troutdale, OR

System

Transverse

Bushing

Acceleration

Limit (g)

Without Spectral Shape

Effects With Spectral Shape Effects

Reported in

MCEER-16-0010

Median

𝑆�̂�𝐹(𝑇1)(g)

RTR PF (50

years)

Median

𝑆�̂�𝐹(𝑇1)(g)

RTR PF (50

years) PF (50 years)

Non-isolated

T1=0.13sec

1g 0.735 0.276 0.056 0.702 0.276 0.061 0.071

2g 1.470 0.276 0.009 1.403 0.276 0.011 0.014

Horizontally

isolated

T1=2.4sec

1g 0.331 0.656 0.025 0.277 0.656 0.035 0.013

2g 0.410 0.492 0.013 0.362 0.492 0.017 0.006

Horizontally-

vertically

isolated without

rocking

T1=2.4sec

1g 0.442 0.393 0.009 0.410 0.393 0.011 0.006

2g 0.466 0.296 0.007 0.457 0.296 0.007 0.004

Horizontally-

vertically

isolated with

rocking

T1=2.4sec

1g 0.439 0.411 0.009 0.405 0.411 0.012 0.005

2g 0.525 0.293 0.005 0.507 0.293 0.005 0.003

Page 83: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

45

Table 3-11 Summary of results for probability of failure for isolated and non-isolated transformer with W=420kip, fAI=4.3Hz and inclined bushing. When isolated, DCapacity=17.7inch

and lower bound friction properties. Location: Vancouver, WA

System

Transverse

Bushing

Acceleration

Limit (g)

Without Spectral Shape

Effects With Spectral Shape Effects

Reported in

MCEER-16-0010

Median

𝑆�̂�𝐹(𝑇1)(g)

RTR PF (50

years)

Median

𝑆�̂�𝐹(𝑇1)(g)

RTR PF (50

years) PF (50 years)

Non-isolated

T1=0.24sec

1g 1.033 0.173 0.043 1.019 0.173 0.045 0.045

2g 2.066 0.173 0.006 2.038 0.173 0.006 0.007

Horizontally

isolated

T1=2.4sec

1g 0.418 0.551 0.015 0.378 0.551 0.019 0.007

2g 0.425 0.477 0.013 0.414 0.477 0.014 0.006

Horizontally-

vertically

isolated without

rocking

T1=2.4sec

1g 0.457 0.322 0.009 0.464 0.322 0.008 0.006

2g 0.471 0.278 0.008 0.502 0.278 0.006 0.005

Horizontally-

vertically

isolated with

rocking

T1=2.4sec

1g 0.395 0.620 0.019 0.355 0.620 0.023 0.011

2g 0.520 0.289 0.006 0.529 0.289 0.006 0.004

Table 3-12 Summary of results for probability of failure for isolated and non-isolated transformer with W=420kip, fAI=4.3Hz and inclined bushing. When isolated, DCapacity=17.7inch

and lower bound friction properties. Location: Saranap, CA

System

Transverse

Bushing

Acceleration

Limit (g)

Without Spectral Shape

Effects With Spectral Shape Effects

Reported in

MCEER-16-0010

Median

𝑆�̂�𝐹(𝑇1)(g)

RTR PF (50

years)

Median

𝑆�̂�𝐹(𝑇1)(g)

RTR PF (50

years) PF (50 years)

Non-isolated

T1=0.24sec

1g 1.033 0.173 0.182 1.105 0.173 0.153 0.211

2g 2.066 0.173 0.016 2.211 0.173 0.012 0.027

Horizontally

isolated

T1=2.4sec

1g 0.418 0.551 0.108 0.696 0.551 0.032 0.031

2g 0.425 0.477 0.089 0.702 0.477 0.024 0.024

Horizontally-

vertically

isolated without

rocking

T1=2.4sec

1g 0.457 0.322 0.054 0.644 0.322 0.019 0.025

2g 0.471 0.278 0.045 0.662 0.278 0.015 0.019

Horizontally-

vertically

isolated with

rocking

T1=2.4sec

1g 0.395 0.620 0.137 0.724 0.620 0.037 0.048

2g 0.520 0.289 0.034 0.706 0.289 0.012 0.016

Page 84: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

46

Table 3-13 Summary of results for probability of failure for isolated and non-isolated transformer with W=420kip, fAI=4.3Hz and inclined bushing. When isolated, DCapacity=17.7inch

and lower bound friction properties. Location: Chehalis, WA

System

Transverse

Bushing

Acceleration

Limit (g)

Without Spectral Shape

Effects With Spectral Shape Effects

Reported in

MCEER-16-0010

Median

𝑆�̂�𝐹(𝑇1)(g)

RTR PF (50

years)

Median

𝑆�̂�𝐹(𝑇1)(g)

RTR PF (50

years) PF (50 years)

Non-isolated

T1=0.24sec

1g 1.033 0.173 0.070 1.042 0.173 0.069 0.074

2g 2.066 0.173 0.012 2.085 0.173 0.011 0.012

Horizontally

isolated

T1=2.4sec

1g 0.418 0.551 0.021 0.354 0.551 0.028 0.013

2g 0.425 0.477 0.018 0.391 0.477 0.021 0.010

Horizontally-

vertically

isolated without

rocking

T1=2.4sec

1g 0.457 0.322 0.013 0.448 0.322 0.014 0.010

2g 0.471 0.278 0.012 0.487 0.278 0.011 0.008

Horizontally-

vertically

isolated with

rocking

T1=2.4sec

1g 0.395 0.620 0.025 0.328 0.620 0.035 0.018

2g 0.520 0.289 0.009 0.512 0.289 0.010 0.007

Table 3-14 Summary of results for probability of failure for isolated and non-isolated transformer with W=420kip, fAI=4.3Hz and inclined bushing. When isolated, DCapacity=17.7inch

and lower bound friction properties. Location: Aberdeen, WA

System

Transverse

Bushing

Acceleration

Limit (g)

Without Spectral Shape

Effects With Spectral Shape Effects

Reported in

MCEER-16-0010

Median

𝑆�̂�𝐹(𝑇1)(g)

RTR PF (50

years)

Median

𝑆�̂�𝐹(𝑇1)(g)

RTR PF (50

years) PF (50 years)

Non-isolated

T1=0.24sec

1g 1.033 0.173 0.095 1.064 0.173 0.091 0.095

2g 2.066 0.173 0.027 2.130 0.173 0.026 0.025

Horizontally

isolated

T1=2.4sec

1g 0.418 0.551 0.036 0.439 0.551 0.034 0.026

2g 0.425 0.477 0.034 0.471 0.477 0.030 0.022

Horizontally-

vertically

isolated without

rocking

T1=2.4sec

1g 0.457 0.322 0.029 0.503 0.322 0.025 0.021

2g 0.471 0.278 0.027 0.537 0.278 0.022 0.018

Horizontally-

vertically

isolated with

rocking

T1=2.4sec

1g 0.395 0.620 0.041 0.423 0.620 0.038 0.032

2g 0.520 0.289 0.024 0.568 0.289 0.021 0.016

Page 85: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

47

Table 3-15 Summary of results for probability of failure for isolated and non-isolated transformer with W=420kip, fAI=4.3Hz and inclined bushing. When isolated, DCapacity=17.7inch

and lower bound friction properties. Location: Loma Linda, CA

System

Transverse

Bushing

Acceleration

Limit (g)

Without Spectral Shape

Effects With Spectral Shape Effects

Reported in

MCEER-16-0010

Median

𝑆�̂�𝐹(𝑇1)(g)

RTR PF (50

years)

Median

𝑆�̂�𝐹(𝑇1)(g)

RTR PF (50

years) PF (50 years)

Non-isolated

T1=0.24sec

1g 1.033 0.173 0.234 1.109 0.173 0.203 0.261

2g 2.066 0.173 0.038 2.220 0.173 0.029 0.047

Horizontally

isolated

T1=2.4sec

1g 0.418 0.551 0.212 0.865 0.551 0.068 0.051

2g 0.425 0.477 0.197 0.847 0.477 0.064 0.042

Horizontally-

vertically

isolated

without rocking

T1=2.4sec

1g 0.457 0.322 0.161 0.724 0.322 0.071 0.041

2g 0.471 0.278 0.149 0.730 0.278 0.067 0.032

Horizontally-

vertically

isolated with

rocking

T1=2.4sec

1g 0.395 0.620 0.024 0.935 0.620 0.066 0.072

2g 0.520 0.289 0.012 0.782 0.289 0.059 0.029

Table 3-16 Summary of results for probability of failure for isolated and non-isolated transformer with W=420kip, fAI=4.3Hz and inclined bushing. When isolated, DCapacity=17.7inch

and lower bound friction properties. Location: Hillsboro, OR

System

Transverse

Bushing

Acceleration

Limit (g)

Without Spectral Shape

Effects With Spectral Shape Effects

Reported in

MCEER-16-0010

Median

𝑆�̂�𝐹(𝑇1)(g)

RTR PF (50

years)

Median

𝑆�̂�𝐹(𝑇1)(g)

RTR PF (50

years) PF (50 years)

Non-isolated

T1=0.24sec

1g 1.033 0.173 0.052 1.037 0.173 0.051 0.055

2g 2.066 0.173 0.009 2.074 0.173 0.009 0.009

Horizontally

isolated

T1=2.4sec

1g 0.418 0.551 0.019 0.352 0.551 0.025 0.010

2g 0.425 0.477 0.016 0.390 0.477 0.019 0.008

Horizontally-

vertically isolated

without rocking

T1=2.4sec

1g 0.457 0.322 0.012 0.447 0.322 0.012 0.008

2g 0.471 0.278 0.010 0.487 0.278 0.010 0.006

Horizontally-

vertically isolated

with rocking

T1=2.4sec

1g 0.395 0.620 0.023 0.328 0.620 0.031 0.014

2g 0.520 0.289 0.008 0.512 0.289 0.009 0.006

Page 86: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

48

Table 3-17 Summary of results for probability of failure for isolated and non-isolated transformer with W=420kip, fAI=4.3Hz and inclined bushing. When isolated, DCapacity=17.7inch

and lower bound friction properties. Location: Eugene, OR

System

Transverse

Bushing

Acceleration

Limit (g)

Without Spectral Shape

Effects With Spectral Shape Effects

Reported in

MCEER-16-0010

Median

𝑆�̂�𝐹(𝑇1)(g)

RTR PF (50

years)

Median

𝑆�̂�𝐹(𝑇1)(g)

RTR PF (50

years) PF (50 years)

Non-isolated

T1=0.24sec

1g 1.033 0.173 0.042 1.030 0.173 0.043 0.019

2g 2.066 0.173 0.010 2.062 0.173 0.010 0.004

Horizontally

isolated

T1=2.4sec

1g 0.418 0.551 0.019 0.347 0.551 0.026 0.004

2g 0.425 0.477 0.018 0.385 0.477 0.021 0.003

Horizontally-

vertically

isolated without

rocking

T1=2.4sec

1g 0.457 0.322 0.013 0.443 0.322 0.012 0.003

2g 0.471 0.278 0.012 0.483 0.278 0.010 0.003

Horizontally-

vertically

isolated with

rocking

T1=2.4sec

1g 0.395 0.620 0.023 0.321 0.620 0.030 0.005

2g 0.520 0.289 0.010 0.508 0.289 0.011 0.003

Table 3-18 Summary of results for probability of failure for isolated and non-isolated transformer with W=420kip, fAI=4.3Hz and inclined bushing. When isolated, DCapacity=17.7inch

and lower bound friction properties. Location: Wilsonville, OR

System

Transverse

Bushing

Acceleration

Limit (g)

Without Spectral Shape

Effects With Spectral Shape Effects

Reported in

MCEER-16-0010

Median

𝑆�̂�𝐹(𝑇1)(g)

RTR PF (50

years)

Median

𝑆�̂�𝐹(𝑇1)(g)

RTR PF (50

years) PF (50 years)

Non-isolated

T1=0.24sec

1g 1.033 0.173 0.045 1.030 0.173 0.045 0.050

2g 2.066 0.173 0.007 2.061 0.173 0.007 0.007

Horizontally

isolated

T1=2.4sec

1g 0.418 0.551 0.016 0.354 0.551 0.022 0.008

2g 0.425 0.477 0.014 0.392 0.477 0.016 0.006

Horizontally-

vertically isolated

without rocking

T1=2.4sec

1g 0.457 0.322 0.009 0.448 0.322 0.010 0.006

2g 0.471 0.278 0.008 0.488 0.278 0.008 0.005

Horizontally-

vertically isolated

with rocking

T1=2.4sec

1g 0.395 0.620 0.020 0.329 0.620 0.029 0.012

2g 0.520 0.289 0.006 0.513 0.289 0.011 0.004

Page 87: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

49

Table 3-19 Summary of results for probability of failure for isolated and non-isolated transformer with W=420kip, fAI=4.3Hz and inclined bushing. When isolated, DCapacity=17.7inch

and lower bound friction properties. Location: Curry County, OR

System

Transverse

Bushing

Acceleration

Limit (g)

Without Spectral Shape

Effects With Spectral Shape Effects

Reported in

MCEER-16-0010

Median

𝑆�̂�𝐹(𝑇1)(g)

RTR PF (50

years)

Median

𝑆�̂�𝐹(𝑇1)(g)

RTR PF (50

years) PF (50 years)

Non-isolated

T1=0.24sec

1g 1.033 0.173 0.095 1.107 0.173 0.087 0.092

2g 2.066 0.173 0.031 2.215 0.173 0.027 0.029

Horizontally

isolated

T1=2.4sec

1g 0.418 0.551 0.063 0.676 0.551 0.034 0.031

2g 0.425 0.477 0.059 0.685 0.477 0.031 0.026

Horizontally-

vertically

isolated without

rocking

T1=2.4sec

1g 0.457 0.322 0.051 0.634 0.322 0.032 0.025

2g 0.471 0.278 0.048 0.653 0.278 0.029 0.021

Horizontally-

vertically

isolated with

rocking

T1=2.4sec

1g 0.395 0.620 0.069 0.701 0.620 0.034 0.036

2g 0.520 0.289 0.042 0.696 0.289 0.027 0.020

Table 3-20 Summary of results for probability of failure for isolated and non-isolated transformer with W=420kip, fAI=4.3Hz and inclined bushing. When isolated, DCapacity=17.7inch

and lower bound friction properties. Location: Troutdale, OR

System

Transverse

Bushing

Acceleration

Limit (g)

Without Spectral Shape

Effects With Spectral Shape Effects

Reported in

MCEER-16-0010

Median

𝑆�̂�𝐹(𝑇1)(g)

RTR PF (50

years)

Median

𝑆�̂�𝐹(𝑇1)(g)

RTR PF (50

years) PF (50 years)

Non-isolated

T1=0.24sec

1g 1.033 0.173 0.037 1.023 0.173 0.038 0.038

2g 2.066 0.173 0.005 2.047 0.173 0.005 0.005

Horizontally

isolated

T1=2.4sec

1g 0.418 0.551 0.014 0.345 0.551 0.020 0.006

2g 0.425 0.477 0.011 0.383 0.477 0.015 0.005

Horizontally-

vertically

isolated

without rocking

T1=2.4sec

1g 0.457 0.322 0.008 0.442 0.322 0.008 0.005

2g 0.471 0.278 0.007 0.482 0.278 0.006 0.004

Horizontally-

vertically

isolated with

rocking

T1=2.4sec

1g 0.395 0.620 0.017 0.320 0.620 0.026 0.009

2g 0.520 0.289 0.005 0.507 0.289 0.005 0.003

Page 88: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

50

Table 3-21 Summary of results for probability of failure for isolated and non-isolated transformer with W=420kip, fAI=11.3Hz and inclined bushing. When isolated, DCapacity=17.7inch

and lower bound friction properties. Location: Vancouver, WA

System

Transverse

Bushing

Acceleration

Limit (g)

Without Spectral Shape

Effects With Spectral Shape Effects

Reported in

MCEER-16-0010

Median

𝑆�̂�𝐹(𝑇1)(g)

RTR PF (50

years)

Median

𝑆�̂�𝐹(𝑇1)(g)

RTR PF (50

years) PF (50 years)

Non-isolated

T1=0.09sec

1g 1.031 0.303 0.020 0.955 0.303 0.024 0.017

2g 2.063 0.303 0.002 1.909 0.303 0.003 0.002

Horizontally

isolated

T1=2.4sec

1g 0.352 0.600 0.023 0.302 0.600 0.030 0.014

2g 0.406 0.548 0.016 0.344 0.548 0.022 0.008

Horizontally-

vertically

isolated without

rocking

T1=2.4sec

1g 0.430 0.323 0.010 0.420 0.323 0.011 0.006

2g 0.462 0.316 0.008 0.442 0.316 0.009 0.006

Horizontally-

vertically

isolated with

rocking

T1=2.4sec

1g 0.497 0.291 0.007 0.500 0.291 0.007 0.003

2g 0.541 0.271 0.005 0.526 0.271 0.006 0.003

Table 3-22 Summary of results for probability of failure for isolated and non-isolated transformer with W=420kip, fAI=11.3Hz and inclined bushing. When isolated, DCapacity=17.7inch

and lower bound friction properties. Location: Saranap, CA

System

Transverse

Bushing

Acceleration

Limit (g)

Without Spectral Shape

Effects With Spectral Shape Effects

Reported in

MCEER-16-0010

Median

𝑆�̂�𝐹(𝑇1)(g)

RTR PF (50

years)

Median

𝑆�̂�𝐹(𝑇1)(g)

RTR PF (50

years) PF (50 years)

Non-isolated

T1=0.09sec

1g 1.031 0.303 0.105 1.140 0.303 0.078 0.079

2g 2.063 0.303 0.008 2.281 0.303 0.005 0.006

Horizontally

isolated

T1=2.4sec

1g 0.352 0.600 0.163 0.677 0.600 0.041 0.064

2g 0.406 0.548 0.114 0.717 0.548 0.029 0.034

Horizontally-

vertically

isolated without

rocking

T1=2.4sec

1g 0.430 0.323 0.064 0.616 0.323 0.022 0.026

2g 0.462 0.316 0.051 0.637 0.316 0.019 0.024

Horizontally-

vertically

isolated with

rocking

T1=2.4sec

1g 0.497 0.291 0.040 0.702 0.291 0.013 0.013

2g 0.541 0.271 0.029 0.715 0.271 0.011 0.011

Page 89: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

51

Table 3-23 Summary of results for probability of failure for isolated and non-isolated transformer with W=420kip, fAI=11.3Hz and inclined bushing. When isolated,

DCapacity=17.7inch and lower bound friction properties. Location: Chehalis, WA

System

Transverse

Bushing

Acceleration

Limit (g)

Without Spectral Shape

Effects With Spectral Shape Effects

Reported in

MCEER-16-0010

Median

𝑆�̂�𝐹(𝑇1)(g)

RTR PF (50

years)

Median

𝑆�̂�𝐹(𝑇1)(g)

RTR PF (50

years) PF (50 years)

Non-isolated

T1=0.09sec

1g 1.031 0.303 0.041 0.959 0.303 0.048 0.029

2g 2.063 0.303 0.006 1.918 0.303 0.007 0.003

Horizontally

isolated

T1=2.4sec

1g 0.352 0.600 0.030 0.315 0.600 0.036 0.024

2g 0.406 0.548 0.021 0.358 0.548 0.028 0.014

Horizontally-

vertically

isolated without

rocking

T1=2.4sec

1g 0.430 0.323 0.015 0.428 0.323 0.015 0.011

2g 0.462 0.316 0.013 0.451 0.316 0.013 0.010

Horizontally-

vertically

isolated with

rocking

T1=2.4sec

1g 0.497 0.291 0.010 0.509 0.291 0.010 0.006

2g 0.541 0.271 0.008 0.534 0.271 0.009 0.005

Table 3-24 Summary of results for probability of failure for isolated and non-isolated transformer with W=420kip, fAI=11.3Hz and inclined bushing. When isolated, DCapacity=17.7inch

and lower bound friction properties. Location: Aberdeen, WA

System

Transverse

Bushing

Acceleration

Limit (g)

Without Spectral Shape

Effects With Spectral Shape Effects

Reported in

MCEER-16-0010

Median

𝑆�̂�𝐹(𝑇1)(g)

RTR PF (50

years)

Median

𝑆�̂�𝐹(𝑇1)(g)

RTR PF (50

years) PF (50 years)

Non-isolated

T1=0.09sec

1g 1.031 0.303 0.059 1.025 0.303 0.060 0.047

2g 2.063 0.303 0.014 2.049 0.303 0.014 0.010

Horizontally

isolated

T1=2.4sec

1g 0.352 0.600 0.046 0.402 0.600 0.039 0.040

2g 0.406 0.548 0.038 0.447 0.548 0.033 0.027

Horizontally-

vertically

isolated without

rocking

T1=2.4sec

1g 0.430 0.323 0.031 0.481 0.323 0.027 0.022

2g 0.462 0.316 0.028 0.503 0.316 0.025 0.021

Horizontally-

vertically

isolated with

rocking

T1=2.4sec

1g 0.497 0.291 0.025 0.564 0.291 0.021 0.014

2g 0.541 0.271 0.022 0.587 0.271 0.020 0.013

Page 90: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

52

Table 3-25 Summary of results for probability of failure for isolated and non-isolated transformer with W=420kip, fAI=11.3Hz and inclined bushing. When isolated,

DCapacity=17.7inch and lower bound friction properties. Location: Loma Linda, CA

System

Transverse

Bushing

Acceleration

Limit (g)

Without Spectral Shape

Effects With Spectral Shape Effects

Reported in

MCEER-16-0010

Median

𝑆�̂�𝐹(𝑇1)(g)

RTR PF (50

years)

Median

𝑆�̂�𝐹(𝑇1)(g)

RTR PF (50

years) PF (50 years)

Non-isolated

T1=0.09sec

1g 1.031 0.303 0.143 1.135 0.303 0.114 0.113

2g 2.063 0.303 0.019 2.271 0.303 0.013 0.013

Horizontally

isolated

T1=2.4sec

1g 0.352 0.600 0.267 0.866 0.600 0.074 0.094

2g 0.406 0.548 0.221 0.897 0.548 0.064 0.055

Horizontally-

vertically

isolated without

rocking

T1=2.4sec

1g 0.430 0.323 0.176 0.693 0.323 0.078 0.043

2g 0.462 0.316 0.156 0.712 0.316 0.073 0.039

Horizontally-

vertically

isolated with

rocking

T1=2.4sec

1g 0.497 0.291 0.135 0.779 0.291 0.060 0.024

2g 0.541 0.271 0.115 0.786 0.271 0.057 0.021

Table 3-26 Summary of results for probability of failure for isolated and non-isolated transformer with W=420kip, fAI=11.3Hz and inclined bushing. When isolated, DCapacity=17.7inch

and lower bound friction properties. Location: Hillsboro, OR

System

Transverse

Bushing

Acceleration

Limit (g)

Without Spectral Shape

Effects With Spectral Shape Effects

Reported in

MCEER-16-0010

Median

𝑆�̂�𝐹(𝑇1)(g)

RTR PF (50

years)

Median

𝑆�̂�𝐹(𝑇1)(g)

RTR PF (50

years) PF (50 years)

Non-isolated

T1=0.09sec

1g 1.031 0.303 0.024 0.967 0.303 0.028 0.022

2g 2.063 0.303 0.004 1.934 0.303 0.005 0.003

Horizontally

isolated

T1=2.4sec

1g 0.352 0.600 0.027 0.314 0.600 0.032 0.018

2g 0.406 0.548 0.020 0.357 0.548 0.025 0.010

Horizontally-

vertically

isolated without

rocking

T1=2.4sec

1g 0.430 0.323 0.013 0.428 0.323 0.013 0.008

2g 0.462 0.316 0.011 0.450 0.316 0.012 0.008

Horizontally-

vertically

isolated with

rocking

T1=2.4sec

1g 0.497 0.291 0.009 0.508 0.291 0.009 0.005

2g 0.541 0.271 0.007 0.534 0.271 0.008 0.004

Page 91: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

53

Table 3-27 Summary of results for probability of failure for isolated and non-isolated transformer with W=420kip, fAI=11.3Hz and inclined bushing. When isolated, DCapacity=17.7inch

and lower bound friction properties. Location: Eugene, OR

System

Transverse

Bushing

Acceleration

Limit (g)

Without Spectral Shape

Effects With Spectral Shape Effects

Reported in

MCEER-16-0010

Median

𝑆�̂�𝐹(𝑇1)(g)

RTR PF (50

years)

Median

𝑆�̂�𝐹(𝑇1)(g)

RTR PF (50

years) PF (50 years)

Non-isolated

T1=0.09sec

1g 1.031 0.303 0.019 0.949 0.303 0.023 0.007

2g 2.063 0.303 0.004 1.898 0.303 0.005 0.002

Horizontally

isolated

T1=2.4sec

1g 0.352 0.600 0.026 0.308 0.600 0.032 0.006

2g 0.406 0.548 0.020 0.351 0.548 0.025 0.004

Horizontally-

vertically

isolated without

rocking

T1=2.4sec

1g 0.430 0.323 0.015 0.424 0.323 0.015 0.003

2g 0.462 0.316 0.013 0.446 0.316 0.014 0.003

Horizontally-

vertically

isolated with

rocking

T1=2.4sec

1g 0.497 0.291 0.011 0.504 0.291 0.011 0.002

2g 0.541 0.271 0.009 0.530 0.271 0.010 0.002

Table 3-28 Summary of results for probability of failure for isolated and non-isolated transformer with W=420kip, fAI=11.3Hz and inclined bushing. When isolated, DCapacity=17.7inch

and lower bound friction properties. Location: Wilsonville, OR

System

Transverse

Bushing

Acceleration

Limit (g)

Without Spectral Shape

Effects With Spectral Shape Effects

Reported in

MCEER-16-0010

Median

𝑆�̂�𝐹(𝑇1)(g)

RTR PF (50

years)

Median

𝑆�̂�𝐹(𝑇1)(g)

RTR PF (50

years) PF (50 years)

Non-isolated

T1=0.09sec

1g 1.031 0.303 0.021 0.953 0.303 0.025 0.019

2g 2.063 0.303 0.003 1.907 0.303 0.004 0.002

Horizontally

isolated

T1=2.4sec

1g 0.352 0.600 0.023 0.316 0.600 0.028 0.015

2g 0.406 0.548 0.017 0.359 0.548 0.021 0.009

Horizontally-

vertically

isolated without

rocking

T1=2.4sec

1g 0.430 0.323 0.011 0.429 0.323 0.011 0.007

2g 0.462 0.316 0.009 0.451 0.316 0.010 0.006

Horizontally-

vertically

isolated with

rocking

T1=2.4sec

1g 0.497 0.291 0.007 0.509 0.291 0.007 0.004

2g 0.541 0.271 0.006 0.535 0.271 0.006 0.003

Page 92: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

54

Table 3-29 Summary of results for probability of failure for isolated and non-isolated transformer with W=420kip, fAI=11.3Hz and inclined bushing. When isolated, DCapacity=17.7inch

and lower bound friction properties. Location: Curry County, OR

System

Transverse

Bushing

Acceleration

Limit (g)

Without Spectral Shape

Effects With Spectral Shape Effects

Reported in

MCEER-16-0010

Median

𝑆�̂�𝐹(𝑇1)(g)

RTR PF (50

years)

Median

𝑆�̂�𝐹(𝑇1)(g)

RTR PF (50

years) PF (50 years)

Non-isolated

T1=0.09sec

1g 1.031 0.303 0.055 1.123 0.303 0.048 0.052

2g 2.063 0.303 0.015 2.247 0.303 0.012 0.013

Horizontally

isolated

T1=2.4sec

1g 0.352 0.600 0.077 0.656 0.600 0.037 0.045

2g 0.406 0.548 0.065 0.697 0.548 0.032 0.032

Horizontally-

vertically

isolated without

rocking

T1=2.4sec

1g 0.430 0.323 0.055 0.607 0.323 0.034 0.026

2g 0.462 0.316 0.050 0.628 0.316 0.032 0.024

Horizontally-

vertically

isolated with

rocking

T1=2.4sec

1g 0.497 0.291 0.045 0.693 0.291 0.027 0.017

2g 0.541 0.271 0.039 0.707 0.271 0.026 0.016

Table 3-30 Summary of results for probability of failure for isolated and non-isolated transformer with W=420kip, fAI=11.3Hz and inclined bushing. When isolated, DCapacity=17.7inch and lower bound friction properties. Location: Troutdale, OR

System

Transverse

Bushing

Acceleration

Limit (g)

Without Spectral Shape

Effects With Spectral Shape Effects

Reported in

MCEER-16-0010

Median

𝑆�̂�𝐹(𝑇1)(g)

RTR PF (50

years)

Median

𝑆�̂�𝐹(𝑇1)(g)

RTR PF (50

years) PF (50 years)

Non-isolated

T1=0.09sec

1g 1.031 0.303 0.014 0.948 0.303 0.021 0.014

2g 2.063 0.303 0.002 1.895 0.303 0.003 0.013

Horizontally

isolated

T1=2.4sec

1g 0.352 0.600 0.021 0.307 0.600 0.027 0.012

2g 0.406 0.548 0.014 0.349 0.548 0.020 0.006

Horizontally-

vertically

isolated without

rocking

T1=2.4sec

1g 0.430 0.323 0.009 0.423 0.323 0.009 0.005

2g 0.462 0.316 0.007 0.445 0.316 0.008 0.004

Horizontally-

vertically

isolated with

rocking

T1=2.4sec

1g 0.497 0.291 0.006 0.503 0.291 0.006 0.003

2g 0.541 0.271 0.004 0.529 0.271 0.005 0.002

Page 93: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

55

Table 3-31 Summary of results for probability of failure for isolated and non-isolated transformer with W=420kip, fAI=7.7Hz and inclined bushing. When isolated, DCapacity=31.3inch

and lower bound friction properties. Location: Vancouver, WA

System

Transverse

Bushing

Acceleration

Limit (g)

Without Spectral Shape

Effects With Spectral Shape Effects

Reported in

MCEER-16-0010

Median

𝑆�̂�𝐹(𝑇1)(g)

RTR PF (50

years)

Median

𝑆�̂�𝐹(𝑇1)(g)

RTR PF (50

years) PF (50 years)

Non-isolated

T1=0.13sec

1g 0.735 0.276 0.063 0.706 0.276 0.069 0.089

2g 1.470 0.276 0.012 1.411 0.276 0.013 0.016

Horizontally

isolated

T1=2.4sec

1g 0.345 0.744 0.030 0.304 0.744 0.037 0.014

2g 0.512 0.611 0.012 0.430 0.611 0.016 0.004

Horizontally-

vertically

isolated

without

rocking

T1=2.4sec

1g 0.459 0.405 0.010 0.414 0.405 0.012 0.003

2g 0.483 0.319 0.008 0.451 0.319 0.009 0.002

Horizontally-

vertically

isolated with

rocking

T1=2.4sec

1g 0.458 0.404 0.010 0.423 0.404 0.012 0.002

2g 0.523 0.302 0.006 0.481 0.302 0.008 0.001

Table 3-32 Summary of results for probability of failure for isolated and non-isolated transformer with W=420kip, fAI=7.7Hz and inclined bushing. When isolated, DCapacity=31.3inch

and lower bound friction properties. Location: Saranap, CA

System

Transverse

Bushing

Acceleration

Limit (g)

Without Spectral Shape

Effects With Spectral Shape Effects

Reported in

MCEER-16-0010

Median

𝑆�̂�𝐹(𝑇1)(g)

RTR PF (50

years)

Median

𝑆�̂�𝐹(𝑇1)(g)

RTR PF (50

years) PF (50 years)

Non-isolated

T1=0.13sec

1g 0.735 0.276 0.300 0.782 0.276 0.266 0.359

2g 1.470 0.276 0.047 1.564 0.276 0.038 0.077

Horizontally

isolated

T1=2.4sec

1g 0.345 0.744 0.210 0.700 0.744 0.058 0.067

2g 0.512 0.611 0.080 0.911 0.611 0.019 0.015

Horizontally-

vertically

isolated without

rocking

T1=2.4sec

1g 0.459 0.405 0.064 0.653 0.405 0.024 0.010

2g 0.483 0.319 0.046 0.665 0.319 0.017 0.006

Horizontally-

vertically

isolated with

rocking

T1=2.4sec

1g 0.458 0.404 0.064 0.676 0.404 0.021 0.006

2g 0.523 0.302 0.035 0.699 0.302 0.013 0.003

Page 94: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

56

Table 3-33 Summary of results for probability of failure for isolated and non-isolated transformer with W=420kip, fAI=7.7Hz and inclined bushing. When isolated, DCapacity=31.3inch

and lower bound friction properties. Location: Loma Linda, CA

System

Transverse

Bushing

Acceleration

Limit (g)

Without Spectral Shape

Effects With Spectral Shape Effects

Reported in

MCEER-16-0010

Median

𝑆�̂�𝐹(𝑇1)(g)

RTR PF (50

years)

Median

𝑆�̂�𝐹(𝑇1)(g)

RTR PF (50

years) PF (50 years)

Non-isolated

T1=0.13sec

1g 0.735 0.276 0.108 0.782 0.276 0.297 0.398

2g 1.470 0.276 0.075 1.565 0.276 0.059 0.108

Horizontally

isolated

T1=2.4sec

1g 0.345 0.744 0.307 0.902 0.744 0.087 0.093

2g 0.512 0.611 0.170 1.146 0.611 0.044 0.026

Horizontally-

vertically

isolated

without

rocking

T1=2.4sec

1g 0.459 0.405 0.167 0.751 0.405 0.073 0.019

2g 0.483 0.319 0.146 0.749 0.319 0.066 0.012

Horizontally-

vertically

isolated with

rocking

T1=2.4sec

1g 0.458 0.404 0.168 0.780 0.404 0.068 0.012

2g 0.523 0.302 0.127 0.783 0.302 0.060 0.006

Table 3-34 Summary of results for probability of failure for isolated and non-isolated transformer with W=420kip, fAI=7.7Hz and inclined bushing. When isolated, DCapacity=31.3inch

and lower bound friction properties. Location: Aberdeen, WA

System

Transverse

Bushing

Acceleration

Limit (g)

Without Spectral Shape

Effects With Spectral Shape Effects

Reported in

MCEER-16-0010

Median

𝑆�̂�𝐹(𝑇1)(g)

RTR PF (50

years)

Median

𝑆�̂�𝐹(𝑇1)(g)

RTR PF (50

years) PF (50 years)

Non-isolated

T1=0.13sec

1g 0.735 0.276 0.129 0.737 0.276 0.135 0.145

2g 1.470 0.276 0.038 1.473 0.276 0.040 0.044

Horizontally

isolated

T1=2.4sec

1g 0.345 0.744 0.053 0.409 0.744 0.043 0.038

2g 0.512 0.611 0.029 0.562 0.611 0.026 0.015

Horizontally-

vertically

isolated without

rocking

T1=2.4sec

1g 0.459 0.405 0.030 0.487 0.405 0.027 0.012

2g 0.483 0.319 0.026 0.518 0.319 0.024 0.009

Horizontally-

vertically

isolated with

rocking

T1=2.4sec

1g 0.458 0.404 0.030 0.500 0.404 0.026 0.009

2g 0.523 0.302 0.024 0.550 0.302 0.022 0.006

Page 95: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

57

Table 3-35 Summary of results for probability of failure for isolated and non-isolated transformer with W=420kip, fAI=7.7Hz and inclined bushing. When isolated, DCapacity=31.3inch

and lower bound friction properties. Location: Chehalis, WA

System

Transverse

Bushing

Acceleration

Limit (g)

Without Spectral Shape

Effects With Spectral Shape Effects

Reported in

MCEER-16-0010

Median

𝑆�̂�𝐹(𝑇1)

(g)

RTR PF (50

years)

Median

𝑆�̂�𝐹(𝑇1)

(g)

RTR PF (50

years) PF (50 years)

Non-isolated

T1=0.13sec

1g 0.735 0.276 0.108 0.717 0.276 0.113 0.128

2g 1.470 0.276 0.022 1.434 0.276 0.024 0.028

Horizontally

isolated

T1=2.4sec

1g 0.345 0.744 0.039 0.318 0.744 0.044 0.024

2g 0.512 0.611 0.016 0.448 0.611 0.021 0.007

Horizontally-

vertically

isolated

without

rocking

T1=2.4sec

1g 0.459 0.405 0.014 0.424 0.405 0.017 0.005

2g 0.483 0.319 0.012 0.460 0.319 0.013 0.003

Horizontally-

vertically

isolated with

rocking

T1=2.4sec

1g 0.458 0.404 0.014 0.433 0.404 0.016 0.003

2g 0.523 0.302 0.010 0.491 0.302 0.011 0.002

Table 3-36 Summary of results for probability of failure for isolated and non-isolated transformer with W=420kip, fAI=7.7Hz and inclined bushing. When isolated, DCapacity=31.3inch

and lower bound friction properties. Location: Hillsboro, OR

System

Transverse

Bushing

Acceleration

Limit (g)

Without Spectral Shape

Effects With Spectral Shape Effects

Reported in

MCEER-16-0010

Median

𝑆�̂�𝐹(𝑇1)

(g)

RTR PF (50

years)

Median

𝑆�̂�𝐹(𝑇1)

(g)

RTR PF (50

years) PF (50 years)

Non-isolated

T1=0.13sec

1g 0.735 0.276 0.071 0.711 0.276 0.076 0.094

2g 1.470 0.276 0.015 1.422 0.276 0.017 0.021

Horizontally

isolated

T1=2.4sec

1g 0.345 0.744 0.034 0.317 0.744 0.038 0.018

2g 0.512 0.611 0.014 0.447 0.611 0.018 0.005

Horizontally-

vertically

isolated without

rocking

T1=2.4sec

1g 0.459 0.405 0.013 0.423 0.405 0.015 0.004

2g 0.483 0.319 0.010 0.460 0.319 0.011 0.002

Horizontally-

vertically

isolated with

rocking

T1=2.4sec

1g 0.458 0.404 0.013 0.433 0.404 0.014 0.002

2g 0.523 0.302 0.008 0.490 0.302 0.010 0.001

Page 96: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

58

Table 3-37 Summary of results for probability of failure for isolated and non-isolated transformer with W=420kip, fAI=7.7Hz and inclined bushing. When isolated, DCapacity=31.3inch

and lower bound friction properties. Location: Eugene, OR

System

Transverse

Bushing

Acceleration

Limit (g)

Without Spectral Shape

Effects With Spectral Shape Effects

Reported in

MCEER-16-0010

Median

𝑆�̂�𝐹(𝑇1)(g)

RTR PF (50

years)

Median

𝑆�̂�𝐹(𝑇1)(g)

RTR PF (50

years) PF (50 years)

Non-isolated

T1=0.13sec

1g 0.735 0.276 0.049 0.704 0.276 0.052 0.038

2g 1.470 0.276 0.014 1.407 0.276 0.015 0.007

Horizontally

isolated

T1=2.4sec

1g 0.345 0.744 0.031 0.311 0.744 0.035 0.007

2g 0.512 0.611 0.015 0.439 0.611 0.019 0.002

Horizontally-

vertically

isolated

without

rocking

T1=2.4sec

1g 0.459 0.405 0.014 0.419 0.405 0.017 0.002

2g 0.483 0.319 0.012 0.456 0.319 0.014 0.001

Horizontally-

vertically

isolated with

rocking

T1=2.4sec

1g 0.458 0.404 0.014 0.428 0.404 0.016 0.001

2g 0.523 0.302 0.010 0.486 0.302 0.012 0.001

Table 3-38 Summary of results for probability of failure for isolated and non-isolated transformer with W=420kip, fAI=7.7Hz and inclined bushing. When isolated, DCapacity=31.3inch

and lower bound friction properties. Location: Wilsonville, OR

System

Transverse

Bushing

Acceleration

Limit (g)

Without Spectral Shape

Effects With Spectral Shape Effects

Reported in

MCEER-16-0010

Median

𝑆�̂�𝐹(𝑇1)(g)

RTR PF (50

years)

Median

𝑆�̂�𝐹(𝑇1)(g)

RTR PF (50

years) PF (50 years)

Non-isolated

T1=0.13sec

1g 0.735 0.276 0.064 0.705 0.276 0.069 0.087

2g 1.470 0.276 0.012 1.410 0.276 0.014 0.018

Horizontally

isolated

T1=2.4sec

1g 0.345 0.744 0.030 0.319 0.744 0.034 0.002

2g 0.512 0.611 0.012 0.449 0.611 0.015 0.004

Horizontally-

vertically

isolated without

rocking

T1=2.4sec

1g 0.459 0.405 0.010 0.425 0.405 0.012 0.003

2g 0.483 0.319 0.008 0.461 0.319 0.009 0.002

Horizontally-

vertically

isolated with

rocking

T1=2.4sec

1g 0.458 0.404 0.010 0.434 0.404 0.012 0.002

2g 0.523 0.302 0.007 0.492 0.302 0.008 0.001

Page 97: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

59

Table 3-39 Summary of results for probability of failure for isolated and non-isolated transformer with W=420kip, fAI=7.7Hz and inclined bushing. When isolated, DCapacity=31.3inch

and lower bound friction properties. Location: Curry County, OR

System

Transverse

Bushing

Acceleration

Limit (g)

Without Spectral Shape

Effects With Spectral Shape Effects

Reported in

MCEER-16-0010

Median

𝑆�̂�𝐹(𝑇1)(g)

RTR PF (50

years)

Median

𝑆�̂�𝐹(𝑇1)(g)

RTR PF (50

years) PF (50 years)

Non-isolated

T1=0.24sec

1g 0.735 0.276 0.111 0.778 0.276 0.107 0.123

2g 1.470 0.276 0.038 1.556 0.276 0.036 0.047

Horizontally

isolated

T1=2.4sec

1g 0.345 0.744 0.085 0.677 0.744 0.040 0.042

2g 0.512 0.611 0.051 0.885 0.611 0.024 0.019

Horizontally-

vertically

isolated without

rocking

T1=2.4sec

1g 0.459 0.405 0.052 0.642 0.405 0.033 0.015

2g 0.483 0.319 0.047 0.655 0.319 0.030 0.011

Horizontally-

vertically

isolated with

rocking

T1=2.4sec

1g 0.458 0.404 0.052 0.664 0.404 0.030 0.011

2g 0.523 0.302 0.042 0.689 0.302 0.027 0.007

Table 3-40 Summary of results for probability of failure for isolated and non-isolated transformer with W=420kip, fAI=7.7Hz and inclined bushing. When isolated, DCapacity=31.3inch

and lower bound friction properties. Location: Troutdale, OR

System

Transverse

Bushing

Acceleration

Limit (g)

Without Spectral Shape

Effects With Spectral Shape Effects

Reported in

MCEER-16-0010

Median

𝑆�̂�𝐹(𝑇1)(g)

RTR PF (50

years)

Median

𝑆�̂�𝐹(𝑇1)(g)

RTR PF (50

years) PF (50 years)

Non-isolated

T1=0.13sec

1g 0.735 0.276 0.056 0.702 0.276 0.061 0.071

2g 1.470 0.276 0.009 1.403 0.276 0.011 0.014

Horizontally

isolated

T1=2.4sec

1g 0.345 0.744 0.028 0.310 0.744 0.033 0.012

2g 0.512 0.611 0.010 0.437 0.611 0.014 0.003

Horizontally-

vertically

isolated without

rocking

T1=2.4sec

1g 0.459 0.405 0.009 0.418 0.405 0.011 0.002

2g 0.483 0.319 0.007 0.454 0.319 0.008 0.001

Horizontally-

vertically

isolated with

rocking

T1=2.4sec

1g 0.458 0.404 0.009 0.427 0.404 0.010 0.001

2g 0.523 0.302 0.005 0.485 0.302 0.006 0.001

Page 98: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

60

Table 3-41 Summary of results for probability of failure for isolated and non-isolated transformer with W=420kip, fAI=4.3Hz and inclined bushing. When isolated, DCapacity=31.3inch

and lower bound friction properties. Location: Vancouver, WA

System

Transverse

Bushing

Acceleration

Limit (g)

Without Spectral Shape

Effects With Spectral Shape Effects

Reported in

MCEER-16-0010

Median

𝑆�̂�𝐹(𝑇1)(g)

RTR PF (50

years)

Median

𝑆�̂�𝐹(𝑇1)(g)

RTR PF (50

years) PF (50 years)

Non-isolated

T1=0.24sec

1g 1.033 0.173 0.043 1.030 0.173 0.045 0.045

2g 2.066 0.173 0.006 2.061 0.173 0.006 0.007

Horizontally

isolated

T1=2.4sec

1g 0.472 0.672 0.015 0.408 0.672 0.020 NA

2g 0.592 0.607 0.009 0.470 0.607 0.014 NA

Horizontally-

vertically

isolated without

rocking

T1=2.4sec

1g 0.676 0.423 0.004 0.563 0.423 0.006 NA

2g 0.718 0.341 0.003 0.647 0.341 0.004 NA

Horizontally-

vertically

isolated with

rocking

T1=2.4sec

1g 0.454 0.746 0.019 0.370 0.746 0.027 NA

2g 0.738 0.388 0.003 0.664 0.388 0.004 NA

Table 3-42 Summary of results for probability of failure for isolated and non-isolated transformer with W=420kip, fAI=4.3Hz and inclined bushing. When isolated, DCapacity=31.3inch

and lower bound friction properties. Location: Saranap, CA

System

Transverse

Bushing

Acceleration

Limit (g)

Without Spectral Shape

Effects With Spectral Shape Effects

Reported in

MCEER-16-0010

Median

𝑆�̂�𝐹(𝑇1)(g)

RTR PF (50

years)

Median

𝑆�̂�𝐹(𝑇1)(g)

RTR PF (50

years) PF (50 years)

Non-isolated

T1=0.24sec

1g 1.033 0.173 0.182 1.105 0.173 0.153 0.211

2g 2.066 0.173 0.016 2.211 0.173 0.012 0.027

Horizontally

isolated

T1=2.4sec

1g 0.472 0.672 0.109 0.920 0.672 0.024 NA

2g 0.592 0.607 0.057 1.014 0.607 0.014 NA

Horizontally-

vertically isolated

without rocking

T1=2.4sec

1g 0.676 0.423 0.023 0.928 0.423 0.008 NA

2g 0.718 0.341 0.014 0.973 0.341 0.004 NA

Horizontally-

vertically isolated

with rocking

T1=2.4sec

1g 0.454 0.746 0.135 0.959 0.746 0.029 NA

2g 0.738 0.388 0.015 1.037 0.388 0.004 NA

Page 99: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

61

Table 3-43 Summary of results for probability of failure for isolated and non-isolated transformer with W=420kip, fAI=4.3Hz and inclined bushing. When isolated, DCapacity=31.3inch

and lower bound friction properties. Location: Chehalis, WA

System

Transverse

Bushing

Acceleration

Limit (g)

Without Spectral Shape

Effects With Spectral Shape Effects

Reported in

MCEER-16-0010

Median

𝑆�̂�𝐹(𝑇1)

(g)

RTR PF (50

years)

Median

𝑆�̂�𝐹(𝑇1)

(g)

RTR PF (50

years) PF (50 years)

Non-isolated

T1=0.24sec

1g 1.033 0.173 0.070 1.043 0.173 0.069 0.074

2g 2.066 0.173 0.012 2.087 0.173 0.011 0.012

Horizontally

isolated

T1=2.4sec

1g 0.472 0.672 0.021 0.426 0.672 0.025 NA

2g 0.592 0.607 0.012 0.489 0.607 0.017 NA

Horizontally-

vertically

isolated without

rocking

T1=2.4sec

1g 0.676 0.423 0.007 0.579 0.423 0.009 NA

2g 0.718 0.341 0.005 0.661 0.341 0.006 NA

Horizontally-

vertically

isolated with

rocking

T1=2.4sec

1g 0.454 0.746 0.025 0.389 0.746 0.032 NA

2g 0.738 0.388 0.005 0.680 0.388 0.006 NA

Table 3-44 Summary of results for probability of failure for isolated and non-isolated transformer with W=420kip, fAI=4.3Hz and inclined bushing. When isolated, DCapacity=31.3inch

and lower bound friction properties. Location: Aberdeen, WA

System

Transverse

Bushing

Acceleration

Limit (g)

Without Spectral Shape

Effects With Spectral Shape Effects

Reported in

MCEER-16-0010

Median

𝑆�̂�𝐹(𝑇1)

(g)

RTR PF (50

years)

Median

𝑆�̂�𝐹(𝑇1)

(g)

RTR PF (50

years) PF (50 years)

Non-isolated

T1=0.24sec

1g 1.033 0.173 0.095 1.064 0.173 0.091 0.095

2g 2.066 0.173 0.027 2.130 0.173 0.026 0.025

Horizontally

isolated

T1=2.4sec

1g 0.472 0.672 0.034 0.545 0.672 0.029 NA

2g 0.592 0.607 0.024 0.618 0.607 0.023 NA

Horizontally-

vertically

isolated without

rocking

T1=2.4sec

1g 0.676 0.423 0.017 0.673 0.423 0.017 NA

2g 0.718 0.341 0.015 0.748 0.341 0.014 NA

Horizontally-

vertically

isolated with

rocking

T1=2.4sec

1g 0.454 0.746 0.038 0.519 0.746 0.033 NA

2g 0.738 0.388 0.015 0.778 0.388 0.013 NA

Page 100: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

62

Table 3-45 Summary of results for probability of failure for isolated and non-isolated transformer with W=420kip, fAI=4.3Hz and inclined bushing. When isolated, DCapacity=31.3inch and lower bound friction properties. Location: Loma Linda, CA

System

Transverse

Bushing

Acceleration

Limit (g)

Without Spectral Shape

Effects With Spectral Shape Effects

Reported in

MCEER-16-0010

Median

𝑆�̂�𝐹(𝑇1)(g)

RTR PF (50

years)

Median

𝑆�̂�𝐹(𝑇1)(g)

RTR PF (50

years) PF (50 years)

Non-isolated

T1=0.24sec

1g 1.033 0.173 0.234 1.119 0.173 0.203 0.261

2g 2.066 0.173 0.038 2.241 0.173 0.029 0.047

Horizontally

isolated

T1=2.4sec

1g 0.472 0.672 0.201 0.925 0.672 0.074 NA

2g 0.592 0.607 0.138 1.019 0.607 0.055 NA

Horizontally-

vertically

isolated

without rocking

T1=2.4sec

1g 0.676 0.423 0.090 0.931 0.423 0.048 NA

2g 0.718 0.341 0.074 0.976 0.341 0.039 NA

Horizontally-

vertically

isolated with

rocking

T1=2.4sec

1g 0.454 0.746 0.226 0.965 0.746 0.078 NA

2g 0.738 0.388 0.074 1.040 0.388 0.036 NA

Table 3-46 Summary of results for probability of failure for isolated and non-isolated transformer with W=420kip, fAI=4.3Hz and inclined bushing. When isolated, DCapacity=31.3inch

and lower bound friction properties. Location: Hillsboro, OR

System

Transverse

Bushing

Acceleration

Limit (g)

Without Spectral Shape

Effects With Spectral Shape Effects

Reported in

MCEER-16-0010

Median

𝑆�̂�𝐹(𝑇1)(g)

RTR PF (50

years)

Median

𝑆�̂�𝐹(𝑇1)(g)

RTR PF (50

years) PF (50 years)

Non-isolated

T1=0.24sec

1g 1.033 0.173 0.052 1.037 0.173 0.051 0.055

2g 2.066 0.173 0.009 2.074 0.173 0.009 0.009

Horizontally

isolated

T1=2.4sec

1g 0.472 0.672 0.018 0.425 0.672 0.022 NA

2g 0.592 0.607 0.011 0.488 0.607 0.016 NA

Horizontally-

vertically isolated

without rocking

T1=2.4sec

1g 0.676 0.423 0.006 0.578 0.423 0.008 NA

2g 0.718 0.341 0.004 0.660 0.341 0.005 NA

Horizontally-

vertically isolated

with rocking

T1=2.4sec

1g 0.454 0.746 0.022 0.388 0.746 0.028 NA

2g 0.738 0.388 0.004 0.679 0.388 0.005 NA

Page 101: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

63

Table 3-47 Summary of results for probability of failure for isolated and non-isolated transformer with W=420kip, fAI=4.3Hz and inclined bushing. When isolated, DCapacity=31.3inch

and lower bound friction properties. Location: Eugene, OR

System

Transverse

Bushing

Acceleration

Limit (g)

Without Spectral Shape

Effects With Spectral Shape Effects

Reported in

MCEER-16-0010

Median

𝑆�̂�𝐹(𝑇1)(g)

RTR PF (50

years)

Median

𝑆�̂�𝐹(𝑇1)(g)

RTR PF (50

years) PF (50 years)

Non-isolated

T1=0.24sec

1g 1.033 0.173 0.042 1.030 0.173 0.043 0.019

2g 2.066 0.173 0.010 2.062 0.173 0.010 0.004

Horizontally

isolated

T1=2.4sec

1g 0.472 0.672 0.018 0.417 0.672 0.022 NA

2g 0.592 0.607 0.012 0.479 0.607 0.017 NA

Horizontally-

vertically

isolated without

rocking

T1=2.4sec

1g 0.676 0.423 0.007 0.571 0.423 0.010 NA

2g 0.718 0.341 0.006 0.654 0.341 0.007 NA

Horizontally-

vertically

isolated with

rocking

T1=2.4sec

1g 0.454 0.746 0.021 0.380 0.746 0.027 NA

2g 0.738 0.388 0.006 0.672 0.388 0.007 NA

Table 3-48 Summary of results for probability of failure for isolated and non-isolated transformer with W=420kip, fAI=4.3Hz and inclined bushing. When isolated, DCapacity=31.3inch

and lower bound friction properties. Location: Wilsonville, OR

System

Transverse

Bushing

Acceleration

Limit (g)

Without Spectral Shape

Effects With Spectral Shape Effects

Reported in

MCEER-16-0010

Median

𝑆�̂�𝐹(𝑇1)(g)

RTR PF (50

years)

Median

𝑆�̂�𝐹(𝑇1)(g)

RTR PF (50

years) PF (50 years)

Non-isolated

T1=0.24sec

1g 1.033 0.173 0.045 1.030 0.173 0.045 0.050

2g 2.066 0.173 0.007 2.061 0.173 0.007 0.007

Horizontally

isolated

T1=2.4sec

1g 0.472 0.672 0.016 0.427 0.672 0.019 NA

2g 0.592 0.607 0.009 0.491 0.607 0.013 NA

Horizontally-

vertically

isolated without

rocking

T1=2.4sec

1g 0.676 0.423 0.004 0.580 0.423 0.006 NA

2g 0.718 0.341 0.003 0.662 0.341 0.004 NA

Horizontally-

vertically

isolated with

rocking

T1=2.4sec

1g 0.454 0.746 0.019 0.391 0.746 0.025 NA

2g 0.738 0.388 0.003 0.681 0.388 0.004 NA

Page 102: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

64

Table 3-49 Summary of results for probability of failure for isolated and non-isolated transformer with W=420kip, fAI=4.3Hz and inclined bushing. When isolated, DCapacity=31.3inch

and lower bound friction properties. Location: Curry County, OR

System

Transverse

Bushing

Acceleration

Limit (g)

Without Spectral Shape

Effects With Spectral Shape Effects

Reported in

MCEER-16-0010

Median

𝑆�̂�𝐹(𝑇1)(g)

RTR PF (50

years)

Median

𝑆�̂�𝐹(𝑇1)(g)

RTR PF (50

years) PF (50 years)

Non-isolated

T1=0.24sec

1g 1.033 0.173 0.095 1.107 0.173 0.087 0.092

2g 2.066 0.173 0.031 2.215 0.173 0.027 0.029

Horizontally

isolated

T1=2.4sec

1g 0.472 0.672 0.058 0.891 0.672 0.025 NA

2g 0.592 0.607 0.042 0.984 0.607 0.020 NA

Horizontally-

vertically

isolated without

rocking

T1=2.4sec

1g 0.676 0.423 0.031 0.910 0.423 0.019 NA

2g 0.718 0.341 0.026 0.958 0.341 0.016 NA

Horizontally-

vertically

isolated with

rocking

T1=2.4sec

1g 0.454 0.746 0.064 0.924 0.746 0.026 NA

2g 0.738 0.388 0.026 1.019 0.388 0.015 NA

Table 3-50 Summary of results for probability of failure for isolated and non-isolated transformer with W=420kip, fAI=4.3Hz and inclined bushing. When isolated, DCapacity=31.3inch

and lower bound friction properties. Location: Troutdale, OR

System

Transverse

Bushing

Acceleration

Limit (g)

Without Spectral Shape

Effects With Spectral Shape Effects

Reported in

MCEER-16-0010

Median

𝑆�̂�𝐹(𝑇1)(g)

RTR PF (50

years)

Median

𝑆�̂�𝐹(𝑇1)(g)

RTR PF (50

years) PF (50 years)

Non-isolated

T1=0.24sec

1g 1.033 0.173 0.037 1.023 0.173 0.038 0.038

2g 2.066 0.173 0.005 2.047 0.173 0.005 0.005

Horizontally

isolated

T1=2.4sec

1g 0.472 0.672 0.014 0.415 0.672 0.018 NA

2g 0.592 0.607 0.008 0.477 0.607 0.012 NA

Horizontally-

vertically

isolated

without rocking

T1=2.4sec

1g 0.676 0.423 0.003 0.569 0.423 0.005 NA

2g 0.718 0.341 0.002 0.653 0.341 0.003 NA

Horizontally-

vertically

isolated with

rocking

T1=2.4sec

1g 0.454 0.746 0.017 0.377 0.746 0.024 NA

2g 0.738 0.388 0.002 0.670 0.388 0.003 NA

Page 103: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

65

Table 3-51 Summary of results for probability of failure for isolated and non-isolated transformer with W=420kip, fAI=11.3Hz and inclined bushing. When isolated, DCapacity=31.3inch

and lower bound friction properties. Location: Vancouver, WA

System

Transverse

Bushing

Acceleration

Limit (g)

Without Spectral Shape

Effects With Spectral Shape Effects

Reported in

MCEER-16-0010

Median

𝑆�̂�𝐹(𝑇1)(g)

RTR PF (50

years)

Median

𝑆�̂�𝐹(𝑇1)(g)

RTR PF (50

years) PF (50 years)

Non-isolated

T1=0.09sec

1g 1.031 0.303 0.020 0.955 0.303 0.024 0.017

2g 2.063 0.303 0.002 1.909 0.303 0.003 0.002

Horizontally

isolated

T1=2.4sec

1g 0.439 0.714 0.019 0.350 0.714 0.028 NA

2g 0.583 0.672 0.010 0.425 0.672 0.019 NA

Horizontally-

vertically

isolated without

rocking

T1=2.4sec

1g 0.636 0.437 0.005 0.546 0.437 0.007 NA

2g 0.657 0.415 0.004 0.572 0.415 0.006 NA

Horizontally-

vertically

isolated with

rocking

T1=2.4sec

1g 0.729 0.381 0.003 0.648 0.381 0.004 NA

2g 0.763 0.346 0.002 0.692 0.346 0.003 NA

Table 3-52 Summary of results for probability of failure for isolated and non-isolated transformer with W=420kip, fAI=11.3Hz and inclined bushing. When isolated, DCapacity=31.3inch

and lower bound friction properties. Location: Saranap, CA

System

Transverse

Bushing

Acceleration

Limit (g)

Without Spectral Shape

Effects With Spectral Shape Effects

Reported in

MCEER-16-0010

Median

𝑆�̂�𝐹(𝑇1)(g)

RTR PF (50

years)

Median

𝑆�̂�𝐹(𝑇1)(g)

RTR PF (50

years) PF (50 years)

Non-isolated

T1=0.09sec

1g 1.031 0.303 0.105 1.139 0.303 0.079 0.079

2g 2.063 0.303 0.008 2.277 0.303 0.005 0.006

Horizontally

isolated

T1=2.4sec

1g 0.439 0.714 0.135 0.656 0.714 0.062 NA

2g 0.583 0.672 0.071 0.767 0.672 0.038 NA

Horizontally-

vertically

isolated without

rocking

T1=2.4sec

1g 0.636 0.437 0.028 0.771 0.437 0.016 NA

2g 0.657 0.415 0.024 0.795 0.415 0.013 NA

Horizontally-

vertically

isolated with

rocking

T1=2.4sec

1g 0.729 0.381 0.015 0.875 0.381 0.008 NA

2g 0.763 0.346 0.011 0.914 0.346 0.006 NA

Page 104: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

66

Table 3-53 Summary of results for probability of failure for isolated and non-isolated transformer with W=420kip, fAI=11.3Hz and inclined bushing. When isolated, DCapacity=31.3inch

and lower bound friction properties. Location: Chehalis, WA

System

Transverse

Bushing

Acceleration

Limit (g)

Without Spectral Shape

Effects With Spectral Shape Effects

Reported in

MCEER-16-0010

Median

𝑆�̂�𝐹(𝑇1)(g)

RTR PF (50

years)

Median

𝑆�̂�𝐹(𝑇1)(g)

RTR PF (50

years) PF (50 years)

Non-isolated

T1=0.09sec

1g 1.031 0.303 0.041 0.959 0.303 0.048 0.029

2g 2.063 0.303 0.006 1.918 0.303 0.007 0.003

Horizontally

isolated

T1=2.4sec

1g 0.439 0.714 0.025 0.367 0.714 0.034 NA

2g 0.583 0.672 0.014 0.445 0.672 0.023 NA

Horizontally-

vertically

isolated without

rocking

T1=2.4sec

1g 0.636 0.437 0.008 0.561 0.437 0.010 NA

2g 0.657 0.415 0.007 0.587 0.415 0.009 NA

Horizontally-

vertically

isolated with

rocking

T1=2.4sec

1g 0.729 0.381 0.005 0.663 0.381 0.006 NA

2g 0.763 0.346 0.004 0.707 0.346 0.005 NA

Table 3-54 Summary of results for probability of failure for isolated and non-isolated transformer with W=420kip, fAI=11.3Hz and inclined bushing. When isolated, DCapacity=31.3inch

and lower bound friction properties. Location: Aberdeen, WA

System

Transverse

Bushing

Acceleration

Limit (g)

Without Spectral Shape

Effects With Spectral Shape Effects

Reported in

MCEER-16-0010

Median

𝑆�̂�𝐹(𝑇1)(g)

RTR PF (50

years)

Median

𝑆�̂�𝐹(𝑇1)(g)

RTR PF (50

years) PF (50 years)

Non-isolated

T1=0.09sec

\ 1.031 0.303 0.059 1.025 0.303 0.060 0.047

2g 2.063 0.303 0.014 2.049 0.303 0.014 0.010

Horizontally

isolated

T1=2.4sec

1g 0.439 0.714 0.039 0.487 0.714 0.034 NA

2g 0.583 0.672 0.026 0.580 0.672 0.026 NA

Horizontally-

vertically

isolated without

rocking

T1=2.4sec

1g 0.636 0.437 0.019 0.655 0.437 0.018 NA

2g 0.657 0.415 0.018 0.681 0.415 0.017 NA

Horizontally-

vertically

isolated with

rocking

T1=2.4sec

1g 0.729 0.381 0.015 0.759 0.381 0.014 NA

2g 0.763 0.346 0.014 0.801 0.346 0.013 NA

Page 105: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

67

Table 3-55 Summary of results for probability of failure for isolated and non-isolated transformer with W=420kip, fAI=11.3Hz and inclined bushing. When isolated, DCapacity=31.3inch

and lower bound friction properties. Location: Loma Linda, CA

System

Transverse

Bushing

Acceleration

Limit (g)

Without Spectral Shape

Effects With Spectral Shape Effects

Reported in

MCEER-16-0010

Median

𝑆�̂�𝐹(𝑇1)(g)

RTR PF (50

years)

Median

𝑆�̂�𝐹(𝑇1)(g)

RTR PF (50

years) PF (50 years)

Non-isolated

T1=0.09sec

1g 1.031 0.303 0.143 1.135 0.303 0.114 0.113

2g 2.063 0.303 0.019 2.271 0.303 0.013 0.013

Horizontally

isolated

T1=2.4sec

1g 0.439 0.714 0.229 1.183 0.714 0.051 NA

2g 0.583 0.672 0.152 1.333 0.672 0.037 NA

Horizontally-

vertically

isolated without

rocking

T1=2.4sec

1g 0.636 0.437 0.102 1.065 0.437 0.037 NA

2g 0.657 0.415 0.094 1.083 0.415 0.034 NA

Horizontally-

vertically

isolated with

rocking

T1=2.4sec

1g 0.729 0.381 0.075 1.160 0.381 0.027 NA

2g 0.763 0.346 0.066 1.186 0.346 0.024 NA

Table 3-56 Summary of results for probability of failure for isolated and non-isolated transformer with W=420kip, fAI=11.3Hz and inclined bushing. When isolated, DCapacity=31.3inch

and lower bound friction properties. Location: Hillsboro, OR

System

Transverse

Bushing

Acceleration

Limit (g)

Without Spectral Shape

Effects With Spectral Shape Effects

Reported in

MCEER-16-0010

Median

𝑆�̂�𝐹(𝑇1)(g)

RTR PF (50

years)

Median

𝑆�̂�𝐹(𝑇1)(g)

RTR PF (50

years) PF (50 years)

Non-isolated

T1=0.09sec

1g 1.031 0.303 0.024 0.967 0.303 0.028 0.022

2g 2.063 0.303 0.004 1.934 0.303 0.005 0.003

Horizontally

isolated

T1=2.4sec

1g 0.439 0.714 0.022 0.365 0.714 0.030 NA

2g 0.583 0.672 0.013 0.443 0.672 0.020 NA

Horizontally-

vertically

isolated without

rocking

T1=2.4sec

1g 0.636 0.437 0.007 0.560 0.437 0.009 NA

2g 0.657 0.415 0.006 0.586 0.415 0.008 NA

Horizontally-

vertically

isolated with

rocking

T1=2.4sec

1g 0.729 0.381 0.004 0.662 0.381 0.006 NA

2g 0.763 0.346 0.004 0.706 0.346 0.004 NA

Page 106: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

68

Table 3-57 Summary of results for probability of failure for isolated and non-isolated transformer with W=420kip, fAI=11.3Hz and inclined bushing. When isolated, DCapacity=31.3inch

and lower bound friction properties. Location: Eugene, OR

System

Transverse

Bushing

Acceleration

Limit (g)

Without Spectral Shape

Effects With Spectral Shape Effects

Reported in

MCEER-16-0010

Median

𝑆�̂�𝐹(𝑇1)(g)

RTR PF (50

years)

Median

𝑆�̂�𝐹(𝑇1)(g)

RTR PF (50

years) PF (50 years)

Non-isolated

T1=0.09sec

1g 1.031 0.303 0.019 0.949 0.303 0.023 0.007

2g 2.063 0.303 0.004 1.898 0.303 0.005 0.002

Horizontally

isolated

T1=2.4sec

1g 0.439 0.714 0.022 0.358 0.714 0.029 NA

2g 0.583 0.672 0.013 0.434 0.672 0.021 NA

Horizontally-

vertically

isolated without

rocking

T1=2.4sec

1g 0.636 0.437 0.008 0.553 0.437 0.011 NA

2g 0.657 0.415 0.007 0.579 0.415 0.010 NA

Horizontally-

vertically

isolated with

rocking

T1=2.4sec

1g 0.729 0.381 0.006 0.655 0.381 0.007 NA

2g 0.763 0.346 0.005 0.699 0.346 0.006 NA

Table 3-58 Summary of results for probability of failure for isolated and non-isolated transformer with W=420kip, fAI=11.3Hz and inclined bushing. When isolated, DCapacity=31.3inch

and lower bound friction properties. Location: Wilsonville, OR

System

Transverse

Bushing

Acceleration

Limit (g)

Without Spectral Shape

Effects With Spectral Shape Effects

Reported in

MCEER-16-0010

Median

𝑆�̂�𝐹(𝑇1)(g)

RTR PF (50

years)

Median

𝑆�̂�𝐹(𝑇1)(g)

RTR PF (50

years) PF (50 years)

Non-isolated

T1=0.09sec

1g 1.031 0.303 0.021 0.953 0.303 0.025 0.019

2g 2.063 0.303 0.003 1.906 0.303 0.004 0.002

Horizontally

isolated

T1=2.4sec

1g 0.439 0.714 0.019 0.369 0.714 0.026 NA

2g 0.583 0.672 0.011 0.447 0.672 0.017 NA

Horizontally-

vertically

isolated without

rocking

T1=2.4sec

1g 0.636 0.437 0.005 0.562 0.437 0.007 NA

2g 0.657 0.415 0.005 0.588 0.415 0.006 NA

Horizontally-

vertically

isolated with

rocking

T1=2.4sec

1g 0.729 0.381 0.003 0.665 0.381 0.004 NA

2g 0.763 0.346 0.003 0.708 0.346 0.003 NA

Page 107: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

69

Table 3-59 Summary of results for probability of failure for isolated and non-isolated transformer with W=420kip, fAI=11.3Hz and inclined bushing. When isolated, DCapacity=31.3inch

and lower bound friction properties. Location: Curry County, OR

System

Transverse

Bushing

Acceleration

Limit (g)

Without Spectral Shape

Effects With Spectral Shape Effects

Reported in

MCEER-16-0010

Median

𝑆�̂�𝐹(𝑇1)(g)

RTR PF (50

years)

Median

𝑆�̂�𝐹(𝑇1)(g)

RTR PF (50

years) PF (50 years)

Non-isolated

T1=0.09sec

1g 1.031 0.303 0.055 1.123 0.303 0.048 0.052

2g 2.063 0.303 0.015 2.247 0.303 0.012 0.013

Horizontally

isolated

T1=2.4sec

1g 0.439 0.714 0.065 0.857 0.714 0.028 NA

2g 0.583 0.672 0.045 0.986 0.672 0.022 NA

Horizontally-

vertically

isolated without

rocking

T1=2.4sec

1g 0.636 0.437 0.034 0.893 0.437 0.020 NA

2g 0.657 0.415 0.032 0.915 0.415 0.018 NA

Horizontally-

vertically

isolated with

rocking

T1=2.4sec

1g 0.729 0.381 0.026 0.995 0.381 0.015 NA

2g 0.763 0.346 0.024 1.029 0.346 0.014 NA

Table 3-60 Summary of results for probability of failure for isolated and non-isolated transformer with W=420kip, fAI=11.3Hz and inclined bushing. When isolated, DCapacity=31.3inch and lower bound friction properties. Location: Troutdale, OR

System

Transverse

Bushing

Acceleration

Limit (g)

Without Spectral Shape

Effects With Spectral Shape Effects

Reported in

MCEER-16-0010

Median

𝑆�̂�𝐹(𝑇1)(g)

RTR PF (50

years)

Median

𝑆�̂�𝐹(𝑇1)(g)

RTR PF (50

years) PF (50 years)

Non-isolated

T1=0.09sec

1g 1.031 0.303 0.014 0.948 0.303 0.021 0.014

2g 2.063 0.303 0.002 1.895 0.303 0.003 0.013

Horizontally

isolated

T1=2.4sec

1g 0.439 0.714 0.017 0.356 0.714 0.025 NA

2g 0.583 0.672 0.009 0.432 0.672 0.016 NA

Horizontally-

vertically

isolated without

rocking

T1=2.4sec

1g 0.636 0.437 0.004 0.551 0.437 0.006 NA

2g 0.657 0.415 0.004 0.577 0.415 0.005 NA

Horizontally-

vertically

isolated with

rocking

T1=2.4sec

1g 0.729 0.381 0.002 0.653 0.381 0.003 NA

2g 0.763 0.346 0.002 0.697 0.346 0.003 NA

Page 108: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on
Page 109: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

71

SECTION 4

CONSIDERATIONS FOR UNCERTAINTIES

Many sources of uncertainties contribute to variability in the calculated probability of failure.

These uncertainties include the record-to-record variability, which is accounted for by the use of a

large number of actual ground motions in the incremental dynamic analysis, and by correcting the

results for the spectral shape effects as discussed in Section 3. It may be seen in the results of

Tables 3-1 to 3-60 that the record-to-record variability is reflected in the value of the dispersion

coefficient βRTR whereas the correction for the spectral shape effects is reflected in an adjusted

value of the median of the spectral acceleration at the fundamental period 𝑆�̂�𝐹(𝑇1). These two

parameters describe the fragility curve in the form of the lognormal distribution in Equation (2-5)

which is presented again below in the form of a cumulative distribution function with a slightly

different interpretation of parameters:

( )( )

2

F 1

1 20

ˆln ln ( )1| ( ) exp

22

x

F

s Sa TP Sa T x ds

s

− = −

(4-1)

In Equation (4-1), PF|Sa(T1) is the fragility curve (probability of failure given the value of Sa(T1))

(variable x representing the spectral acceleration at the fundamental period). Parameter β is the

total value of the dispersion coefficient that includes all uncertainties. Note that the values of

probabilities reported in Tables 3-1 to 3-60 are based on the use of Equations (2-6) and (2-7) for

computing the probability of failure in the lifetime of the equipment with due consideration for

only the record-to-record variability.

In general, uncertainties should affect the fragility curve, thus both the median value 𝑆�̂�𝐹(𝑇1) and

the dispersion coefficient. Uncertainties exist in the transformer model for analysis, the isolation

system mechanical properties, the isolation system force and displacement capacities, the bushing

failure limits and the ground motions used in the analysis. In addition, uncertainties should affect

the seismic hazard curve used in Equation (2-6) to compute the mean annual frequency of failure,

from which the probability of failure over a specific time period is calculated (Equation 2-7). The

approach followed in this study is to adjust the dispersion coefficient to account for uncertainties

in the transformer model whereas all other uncertainties are accounted for by limited deterministic

analyses using bounding values of properties of the isolation system and bushings. Specifically:

Page 110: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

72

1) A simple model of a representative generic transformer is used with the understanding that

uncertainties in the model can be accounted for by adjustments of the dispersion coefficient

obtained in the IDA and reported in Tables 3-1 to 3-60. Moreover, the results presented in

this report are meant to be representative results for ten locations in the Western United

States for use by responsible officials to aid in their decision to implement seismic

isolation. This decision needs to be made on the basis of the potential benefit to be provided

by seismic isolation by comparing probabilities of failure of non-isolated and isolated

models of transformers of identical parameters, which are parametrically varied.

2) The transformer model utilizes a typical weight of 420kip. Studies in Kitayama et al. (2016)

(see Figure 8-7 of the Kitayama reference) have demonstrated insignificant difference in

the fragilities curves as the weight varied from 320 to 520kip while the same isolators were

used (however, the isolator properties were adjusted to reflect the effect of changes of

weight on the friction coefficient). Accordingly, weight does not have any important effect

to warrant additional studies.

3) The damping ratio of the transformer model was set at 3% of critical for all modes. It is an

appropriate value based on field studies (Villaverde et al., 2001). Higher values certainly

result in reduction of the probabilities of failure. Accordingly, the results based on the 3%

value are representative of real conditions.

4) The plan dimension of the planar transformer model had a single value of 110inch between

supports. While this dimension does not affect the results of the non-isolated model, it does

for the isolated model through uplift of the isolators. The 110-inch value represents the

smaller plan dimension of some actual transformers (see examples in Oikonomou et al.,

2016 and Lee and Constantinou, 2017). Placing isolators at a distance equal to the smaller

dimension is neither necessary, nor recommended (in Lee and Constantinou, 2017 the

isolators were placed further away under a concrete base). Accordingly, the results for the

horizontally isolated transformers may be slightly conservative, particularly for the cases

of the smallest displacement capacity isolator and the largest bushing acceleration limit

where impact on the displacement restraint and uplift were more likely to occur.

5) A single inclined bushing having an as-installed frequency of either 4.3 or 7.7 or 11.3Hz

(three cases) was used to represent the transformer. This represents a realistic range of

frequencies for most bushings (Kitayama et al., 2016). The as-installed frequency has an

important effect on the probability of failure as seen in the results of Tables 3-1 to 3-60.

Page 111: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

73

Given that there is uncertainty on the as-installed frequency of a bushing, and that

transformers have many bushings of different as-installed frequencies, it is appropriate to

consider the results of all three cases in this report in assessing the benefits of isolation for

a transformer.

6) The bushing failure acceleration limits considered were 1g and 2g in the transverse

direction at its upper part center of mass (see Kitayama et al., 2016 for details). These two

limits were established by comparing analytically constructed fragility curves of non-

isolated transformers to empirical fragility curves of seven different types of transformers

with two different bushing voltages (230 or 500kV) (Kitayama et al., 2016). It was

observed that the 2g limit was representative of failures not attributed to bushing failure

but rather of some other component, whereas the 1g limit appeared as an appropriate lower

bound limit. We believe that an assessment of performance based on the data presented

in this report should be based on the 1g bushing acceleration limit as it results in

conservative estimates of the probability of failure. Any consideration of uncertainties

on the value of the acceleration would have caused a further increase of a conservatively

estimated probability of failure.

7) The isolation system frictional properties considered are the lower bound values as studies

in Kitayama et al. (2016) demonstrated generally small differences between the two cases

of upper and lower bound friction, with the lower bound resulting in slightly larger

probabilities of failure. For the case of 1g bushing acceleration limit in the study of

Kitayama et al. (2016), the two cases of bounds for friction produced very close fragility

curves.

8) Two FP isolator sizes in terms of their displacement capacity were considered, one small

(DCapacity=17.7inch) and one large (DCapacity=31.3inch). These two isolators can be readily

produced, with the small one having been used in some applications in the Western United

States. The larger isolator has a different radius of curvature (R=61inch) than the small

isolator (R=39inch) and is intended for use in areas of higher seismic hazard. These two

cases should provide sufficient information for deciding on the use of seismic isolation.

We note that larger displacement capacity isolators can be produced, but their use will

likely be very special due primarily to the requirement to detail the electrical connections

of the isolated transformer for accommodating large displacements.

Page 112: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

74

9) A single set of vertical isolator properties has been considered with parameters identical to

those of a tested system in Lee and Constantinou (2017, 2018). The results show some

benefits with the use of the vertical isolation system for some locations but the decision to

use it should consider the complexities in its construction (for example the system “without

rocking” requires a massive base-see example in Lee and Constantinou, 2017).

Realistically only the system “with rocking” is practical but should be reserved for very

special cases where the vertical ground acceleration of a horizontally-only isolated

transformer causes global uplift and bouncing. Recognizing that there are additional

uncertainties in the model of analysis for the horizontally-vertically isolated transformer

by comparison to the horizontally only transformer, we will propose different parameters

when computing the probabilities of collapse in the two cases.

Based on the considerations discussed above, it is assumed that the results on the probability of

failure presented in this report in Section 3 encompass a range of possible properties of

transformers and are useful in assessing performance and in deciding on the utility of seismic

isolation. The only remaining consideration is to adjust the results for additional uncertainties

related to the transformer model, which are perceived different for the various considered

configurations. Following the paradigm of FEMA P695 (FEMA, 2009), we define the value of the

dispersion coefficient in Equation (4-1) as

𝛽 = √𝛽RTR2 + 𝛽MDL

2 (4-2)

In this equation, βRTR is the dispersion coefficient due to the record-to-record variability (or record-

to-record failure uncertainty) as reported in Tables 3-1 to 3-60, and βMDL is the modeling

uncertainty to account for how well the model of analysis represents the actual transformer,

isolated or non-isolated. We use of the following values based on FEMA (2009) and the following

considerations:

1) For non-isolated transformers βMDL=0.3 as the model captures a wide range of the

transformer properties space but the model accuracy and robustness is fair.

2) For horizontally-vertically isolated transformers βMDL=0.2 as the model captures a wide

range of the transformer properties space and the model accuracy and robustness is

medium.

Page 113: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

75

3) For horizontally isolated transformers βMDL=0.1 as the model captures a wide range of the

transformer properties space and the model accuracy and robustness is superior.

Moreover, we recognize that the selection and scaling of the pairs of horizontal-vertical ground

motions may have not been appropriate for incremental dynamic analysis and this affected the

calculated record-to-record dispersion for the horizontally only transformer models. Accordingly,

calculations will be performed for the values of βRTR and then again using an upper bound of 0.4

for βRTR. This will better inform the user of the results in deciding which probabilities of failure

are relevant in the decision process.

Page 114: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on
Page 115: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

77

SECTION 5

SUMMARY OF RESULTS FOR FAR-FIELD MOTIONS

Tables 5-1 to 5-60 present a summary of the fragility analysis results and the probabilities of failure

in a lifetime of 50 years for all analyzed cases using the far-field motions. The presented fragility

analysis results (values of 𝑆�̂�𝐹(𝑇1) and βRTR) include the spectral shape effects. The probabilities

of failure are presented for two cases, one using the computed value of βRTR and one based on an

upper bound of 0.4 for βRTR. All probabilities of collapse have been computed using the total value

of the dispersion coefficient per Equation (4-2) and using the values of βMDL in Section 4.

Table 5-1 Summary of results for probability of failure when considering uncertainties for isolated and non-isolated transformer with W=420kip, fAI=7.7Hz and inclined bushing. When isolated, DCapacity=17.7inch and lower bound friction properties. Location: Vancouver, WA.

Far-field motions

System

Transverse

Bushing

Acceleration

Limit (g)

Fragility Parameters with

Spectral Shape Effects

RTR as computed. βMDL as defined in

Section 4

RTR bound by 0.4. βMDL as defined in

Section 4 Median

𝑆�̂�𝐹(𝑇1)(g)

RTR PF (50

years) β

PF (50

years) β

PF (50

years)

Non-isolated

T1=0.13sec

1g 0.704 0.276 0.069 0.408 0.080 0.408 0.080

2g 1.408 0.276 0.013 0.408 0.017 0.408 0.017

Horizontally

isolated

T1=2.4sec

1g 0.284 0.656 0.036 0.664 0.036 0.412 0.026

2g 0.369 0.492 0.018 0.502 0.018 0.412 0.016

Horizontally-

vertically

isolated

without

rocking

T1=2.4sec

1g 0.415 0.393 0.012 0.441 0.013 0.441 0.013

2g 0.462 0.296 0.008 0.357 0.009 0.357 0.009

Horizontally-

vertically

isolated with

rocking

T1=2.4sec

1g 0.411 0.411 0.013 0.457 0.014 0.447 0.013

2g 0.512 0.293 0.006 0.355 0.007 0.355 0.007

Page 116: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

78

Table 5-2 Summary of results for probability of failure when considering uncertainties for isolated and non-isolated transformer with W=420kip, fAI=7.7Hz and inclined bushing. When

isolated, DCapacity=17.7inch and lower bound friction properties. Location: Saranap, CA. Far-field motions

System

Transverse

Bushing

Acceleration

Limit (g)

Fragility Parameters with

Spectral Shape Effects

RTR as computed. βMDL as defined in

Section 4

RTR bound by 0.4. βMDL as defined in

Section 4 Median

𝑆�̂�𝐹(𝑇1)(g)

RTR PF (50

years) β

PF (50

years) β

PF (50

years)

Non-isolated

T1=0.13sec

1g 0.782 0.276 0.266 0.408 0.307 0.408 0.307

2g 1.564 0.276 0.038 0.408 0.058 0.408 0.058

Horizontally

isolated

T1=2.4sec

1g 0.588 0.656 0.067 0.664 0.068 0.412 0.033

2g 0.644 0.492 0.033 0.502 0.034 0.412 0.025

Horizontally-

vertically

isolated

without

rocking

T1=2.4sec

1g 0.620 0.393 0.027 0.441 0.031 0.441 0.031

2g 0.639 0.296 0.018 0.357 0.022 0.357 0.022

Horizontally-

vertically

isolated with

rocking

T1=2.4sec

1g 0.646 0.411 0.025 0.457 0.029 0.447 0.028

2g 0.704 0.293 0.013 0.355 0.016 0.355 0.016

Page 117: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

79

Table 5-3 Summary of results for probability of failure when considering uncertainties for isolated and non-isolated transformer with W=420kip, fAI=7.7Hz and inclined bushing. When isolated, DCapacity=17.7inch and lower bound friction properties. Location: Loma Linda, CA.

Far-field motions

System

Transverse

Bushing

Acceleration

Limit (g)

Fragility Parameters with

Spectral Shape Effects

RTR as computed. βMDL as defined in

Section 4

RTR bound by 0.4. βMDL as defined in

Section 4 Median

𝑆�̂�𝐹(𝑇1)(g)

RTR PF (50

years) β

PF (50

years) β

PF (50

years)

Non-isolated

T1=0.13sec

1g 0.782 0.276 0.309 0.408 0.346 0.408 0.346

2g 1.565 0.276 0.063 0.408 0.084 0.408 0.084

Horizontally

isolated

T1=2.4sec

1g 0.744 0.656 0.103 0.664 0.104 0.412 0.075

2g 0.770 0.492 0.078 0.502 0.079 0.412 0.070

Horizontally-

vertically

isolated

without

rocking

T1=2.4sec

1g 0.706 0.393 0.081 0.441 0.085 0.441 0.085

2g 0.709 0.296 0.073 0.357 0.077 0.357 0.077

Horizontally-

vertically

isolated with

rocking

T1=2.4sec

1g 0.748 0.411 0.074 0.457 0.078 0.447 0.077

2g 0.780 0.293 0.059 0.355 0.064 0.355 0.064

Page 118: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

80

Table 5-4 Summary of results for probability of failure when considering uncertainties for isolated and non-isolated transformer with W=420kip, fAI=7.7Hz and inclined bushing. When isolated, DCapacity=17.7inch and lower bound friction properties. Location: Aberdeen, WA.

Far-field motions

System

Transverse

Bushing

Acceleration

Limit (g)

Fragility Parameters with

Spectral Shape Effects

RTR as computed. βMDL as defined in

Section 4

RTR bound by 0.4. βMDL as defined in

Section 4 Median

𝑆�̂�𝐹(𝑇1)(g)

RTR PF (50

years) β

PF (50

years) β

PF (50

years)

Non-isolated

T1=0.13sec

1g 0.737 0.276 0.128 0.408 0.141 0.408 0.141

2g 1.473 0.276 0.038 0.408 0.044 0.408 0.044

Horizontally

isolated

T1=2.4sec

1g 0.359 0.656 0.047 0.664 0.047 0.412 0.040

2g 0.441 0.492 0.033 0.502 0.033 0.412 0.031

Horizontally-

vertically

isolated

without

rocking

T1=2.4sec

1g 0.472 0.393 0.028 0.441 0.029 0.441 0.029

2g 0.513 0.296 0.024 0.357 0.025 0.357 0.025

Horizontally-

vertically

isolated with

rocking

T1=2.4sec

1g 0.475 0.411 0.028 0.457 0.029 0.447 0.029

2g 0.567 0.293 0.021 0.355 0.021 0.355 0.021

Page 119: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

81

Table 5-5 Summary of results for probability of failure when considering uncertainties for isolated and non-isolated transformer with W=420kip, fAI=7.7Hz and inclined bushing. When

isolated, DCapacity=17.7inch and lower bound friction properties. Location: Chehalis, WA. Far-field motions

System

Transverse

Bushing

Acceleration

Limit (g)

Fragility Parameters with

Spectral Shape Effects

RTR as computed. βMDL as defined in

Section 4

RTR bound by 0.4. βMDL as defined in

Section 4 Median

𝑆�̂�𝐹(𝑇1)(g)

RTR PF (50

years) β

PF (50

years) β

PF (50

years)

Non-isolated

T1=0.13sec

1g 0.717 0.276 0.113 0.408 0.129 0.408 0.129

2g 1.434 0.276 0.024 0.408 0.030 0.408 0.030

Horizontally

isolated

T1=2.4sec

1g 0.286 0.656 0.045 0.664 0.046 0.412 0.034

2g 0.372 0.492 0.024 0.502 0.024 0.412 0.022

Horizontally-

vertically

isolated

without

rocking

T1=2.4sec

1g 0.415 0.393 0.017 0.441 0.018 0.441 0.018

2g 0.462 0.296 0.012 0.357 0.013 0.357 0.013

Horizontally-

vertically

isolated with

rocking

T1=2.4sec

1g 0.411 0.411 0.018 0.457 0.019 0.447 0.019

2g 0.513 0.293 0.010 0.355 0.011 0.355 0.011

Page 120: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

82

Table 5-6 Summary of results for probability of failure when considering uncertainties for isolated and non-isolated transformer with W=420kip, fAI=7.7Hz and inclined bushing. When

isolated, DCapacity=17.7inch and lower bound friction properties. Location: Hillsboro, OR. Far-field motions

System

Transverse

Bushing

Acceleration

Limit (g)

Fragility Parameters with

Spectral Shape Effects

RTR as computed. βMDL as defined in

Section 4

RTR bound by 0.4. βMDL as defined in

Section 4 Median

𝑆�̂�𝐹(𝑇1)(g)

RTR PF (50

years) β

PF (50

years) β

PF (50

years)

Non-isolated

T1=0.13sec

1g 0.711 0.276 0.076 0.408 0.085 0.408 0.085

2g 1.422 0.276 0.017 0.408 0.021 0.408 0.021

Horizontally

isolated

T1=2.4sec

1g 0.284 0.656 0.040 0.664 0.041 0.412 0.031

2g 0.369 0.492 0.022 0.502 0.022 0.412 0.020

Horizontally-

vertically

isolated

without

rocking

T1=2.4sec

1g 0.415 0.393 0.016 0.441 0.016 0.441 0.016

2g 0.462 0.296 0.011 0.357 0.012 0.357 0.012

Horizontally-

vertically

isolated with

rocking

T1=2.4sec

1g 0.411 0.411 0.016 0.457 0.017 0.447 0.017

2g 0.512 0.293 0.009 0.355 0.010 0.355 0.010

Page 121: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

83

Table 5-7 Summary of results for probability of failure when considering uncertainties for isolated and non-isolated transformer with W=420kip, fAI=7.7Hz and inclined bushing. When

isolated, DCapacity=17.7inch and lower bound friction properties. Location: Eugene, OR. Far-field motions.

System

Transverse

Bushing

Acceleration

Limit (g)

Fragility Parameters with

Spectral Shape Effects

RTR as computed. βMDL as defined in

Section 4

RTR bound by 0.4. βMDL as defined in

Section 4 Median

𝑆�̂�𝐹(𝑇1)(g)

RTR PF (50

years) β

PF (50

years) β

PF (50

years)

Non-isolated

T1=0.13sec

1g 0.704 0.276 0.052 0.408 0.056 0.408 0.056

2g 1.407 0.276 0.015 0.408 0.017 0.408 0.017

Horizontally

isolated

T1=2.4sec

1g 0.279 0.656 0.038 0.664 0.038 0.412 0.032

2g 0.364 0.492 0.023 0.502 0.023 0.412 0.021

Horizontally-

vertically

isolated

without

rocking

T1=2.4sec

1g 0.411 0.393 0.017 0.441 0.018 0.441 0.018

2g 0.458 0.296 0.013 0.357 0.014 0.357 0.014

Horizontally-

vertically

isolated with

rocking

T1=2.4sec

1g 0.406 0.411 0.018 0.457 0.019 0.447 0.018

2g 0.508 0.293 0.011 0.355 0.011 0.355 0.011

Page 122: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

84

Table 5-8 Summary of results for probability of failure when considering uncertainties for isolated and non-isolated transformer with W=420kip, fAI=7.7Hz and inclined bushing. When isolated, DCapacity=17.7inch and lower bound friction properties. Location: Wilsonville, OR.

Far-field motions

System

Transverse

Bushing

Acceleration

Limit (g)

Fragility Parameters with

Spectral Shape Effects

RTR as computed. βMDL as defined in

Section 4

RTR bound by 0.4. βMDL as defined in

Section 4 Median

𝑆�̂�𝐹(𝑇1)(g)

RTR PF (50

years) β

PF (50

years) β

PF (50

years)

Non-isolated

T1=0.13sec

1g 0.705 0.276 0.069 0.408 0.079 0.408 0.079

2g 1.410 0.276 0.014 0.408 0.018 0.408 0.018

Horizontally

isolated

T1=2.4sec

1g 0.285 0.656 0.036 0.664 0.036 0.412 0.027

2g 0.370 0.492 0.018 0.502 0.019 0.412 0.017

Horizontally-

vertically

isolated

without

rocking

T1=2.4sec

1g 0.416 0.393 0.013 0.441 0.014 0.441 0.014

2g 0.463 0.296 0.009 0.357 0.010 0.357 0.010

Horizontally-

vertically

isolated with

rocking

T1=2.4sec

1g 0.412 0.411 0.013 0.457 0.014 0.447 0.014

2g 0.513 0.293 0.007 0.355 0.007 0.355 0.007

Page 123: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

85

Table 5-9 Summary of results for probability of failure when considering uncertainties for isolated and non-isolated transformer with W=420kip, fAI=7.7Hz and inclined bushing. When

isolated, DCapacity=17.7inch and lower bound friction properties. Location: Curry County, OR. Far-field motions

System

Transverse

Bushing

Acceleration

Limit (g)

Fragility Parameters with

Spectral Shape Effects

RTR as computed. βMDL as defined in

Section 4

RTR bound by 0.4. βMDL as defined in

Section 4 Median

𝑆�̂�𝐹(𝑇1)(g)

RTR PF (50

years) β

PF (50

years) β

PF (50

years)

Non-isolated

T1=0.13sec

1g 0.778 0.276 0.103 0.408 0.108 0.408 0.108

2g 1.556 0.276 0.034 0.408 0.039 0.408 0.039

Horizontally

isolated

T1=2.4sec

1g 0.571 0.656 0.046 0.664 0.046 0.412 0.039

2g 0.629 0.492 0.036 0.502 0.036 0.412 0.034

Horizontally-

vertically

isolated

without

rocking

T1=2.4sec

1g 0.610 0.393 0.035 0.441 0.036 0.441 0.036

2g 0.630 0.296 0.031 0.357 0.033 0.357 0.033

Horizontally-

vertically

isolated with

rocking

T1=2.4sec

1g 0.634 0.411 0.033 0.457 0.035 0.447 0.034

2g 0.695 0.293 0.027 0.355 0.028 0.355 0.028

Page 124: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

86

Table 5-10 Summary of results for probability of failure when considering uncertainties for isolated and non-isolated transformer with W=420kip, fAI=7.7Hz and inclined bushing. When

isolated, DCapacity=17.7inch and lower bound friction properties. Location: Troutdale, OR. Far-field motions

System

Transverse

Bushing

Acceleration

Limit (g)

Fragility Parameters with

Spectral Shape Effects

RTR as computed. βMDL as defined in

Section 4

RTR bound by 0.4. βMDL as defined in

Section 4 Median

𝑆�̂�𝐹(𝑇1)(g)

RTR PF (50

years) β

PF (50

years) β

PF (50

years)

Non-isolated

T1=0.13sec

1g 0.702 0.276 0.061 0.408 0.071 0.408 0.071

2g 1.403 0.276 0.011 0.408 0.015 0.408 0.015

Horizontally

isolated

T1=2.4sec

1g 0.277 0.656 0.035 0.664 0.035 0.412 0.025

2g 0.362 0.492 0.017 0.502 0.017 0.412 0.015

Horizontally-

vertically

isolated

without

rocking

T1=2.4sec

1g 0.410 0.393 0.011 0.441 0.012 0.441 0.012

2g 0.457 0.296 0.007 0.357 0.008 0.357 0.008

Horizontally-

vertically

isolated with

rocking

T1=2.4sec

1g 0.405 0.411 0.012 0.457 0.013 0.447 0.012

2g 0.507 0.293 0.005 0.355 0.006 0.355 0.006

Page 125: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

87

Table 5-11 Summary of results for probability of failure when considering uncertainties for isolated and non-isolated transformer with W=420kip, fAI=4.3Hz and inclined bushing. When isolated, DCapacity=17.7inch and lower bound friction properties. Location: Vancouver, WA.

Far-field motions

System

Transverse

Bushing

Acceleration

Limit (g)

Fragility Parameters with

Spectral Shape Effects

RTR as computed. βMDL as defined in

Section 4

RTR bound by 0.4. βMDL as defined in

Section 4 Median

𝑆�̂�𝐹(𝑇1)(g)

RTR PF (50

years) β

PF (50

years) β

PF (50

years)

Non-isolated

T1=0.24sec

1g 1.019 0.173 0.045 0.346 0.053 0.346 0.053

2g 2.038 0.173 0.006 0.346 0.009 0.346 0.009

Horizontally

isolated

T1=2.4sec

1g 0.378 0.551 0.019 0.560 0.019 0.412 0.015

2g 0.414 0.477 0.014 0.487 0.014 0.412 0.013

Horizontally-

vertically

isolated

without

rocking

T1=2.4sec

1g 0.464 0.322 0.008 0.379 0.009 0.379 0.009

2g 0.502 0.278 0.006 0.342 0.007 0.342 0.007

Horizontally-

vertically

isolated with

rocking

T1=2.4sec

1g 0.355 0.620 0.023 0.651 0.025 0.447 0.018

2g 0.529 0.289 0.006 0.351 0.006 0.351 0.006

Page 126: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

88

Table 5-12 Summary of results for probability of failure when considering uncertainties for isolated and non-isolated transformer with W=420kip, fAI=4.3Hz and inclined bushing. When

isolated, DCapacity=17.7inch and lower bound friction properties. Location: Saranap, CA. Far-field motions

System

Transverse

Bushing

Acceleration

Limit (g)

Fragility Parameters with

Spectral Shape Effects

RTR as computed. βMDL as defined in

Section 4

RTR bound by 0.4. βMDL as defined in

Section 4 Median

𝑆�̂�𝐹(𝑇1)(g)

RTR PF (50

years) β

PF (50

years) β

PF (50

years)

Non-isolated

T1=0.24sec

1g 1.105 0.173 0.153 0.346 0.192 0.346 0.192

2g 2.211 0.173 0.012 0.346 0.023 0.346 0.023

Horizontally

isolated

T1=2.4sec

1g 0.696 0.551 0.032 0.560 0.033 0.412 0.020

2g 0.702 0.477 0.024 0.487 0.025 0.412 0.019

Horizontally-

vertically

isolated

without

rocking

T1=2.4sec

1g 0.644 0.322 0.019 0.379 0.023 0.379 0.023

2g 0.662 0.278 0.015 0.342 0.018 0.342 0.018

Horizontally-

vertically

isolated with

rocking

T1=2.4sec

1g 0.724 0.620 0.037 0.651 0.041 0.447 0.020

2g 0.706 0.289 0.012 0.351 0.015 0.351 0.015

Page 127: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

89

Table 5-13 Summary of results for probability of failure when considering uncertainties for isolated and non-isolated transformer with W=420kip, fAI=4.3Hz and inclined bushing. When

isolated, DCapacity=17.7inch and lower bound friction properties. Location: Chehalis, WA. Far-field motions

System

Transverse

Bushing

Acceleration

Limit (g)

Fragility Parameters with

Spectral Shape Effects

RTR as computed. βMDL as defined in

Section 4

RTR bound by 0.4. βMDL as defined in

Section 4 Median

𝑆�̂�𝐹(𝑇1)(g)

RTR PF (50

years) β

PF (50

years) β

PF (50

years)

Non-isolated

T1=0.24sec

1g 1.042 0.173 0.069 0.346 0.081 0.346 0.081

2g 2.085 0.173 0.011 0.346 0.016 0.346 0.016

Horizontally

isolated

T1=2.4sec

1g 0.354 0.551 0.028 0.560 0.029 0.412 0.024

2g 0.391 0.477 0.021 0.487 0.022 0.412 0.020

Horizontally-

vertically

isolated

without

rocking

T1=2.4sec

1g 0.448 0.322 0.014 0.379 0.015 0.379 0.015

2g 0.487 0.278 0.011 0.342 0.012 0.342 0.012

Horizontally-

vertically

isolated with

rocking

T1=2.4sec

1g 0.328 0.620 0.035 0.651 0.037 0.447 0.028

2g 0.512 0.289 0.010 0.351 0.011 0.351 0.011

Page 128: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

90

Table 5-14 Summary of results for probability of failure when considering uncertainties for isolated and non-isolated transformer with W=420kip, fAI=4.3Hz and inclined bushing. When isolated, DCapacity=17.7inch and lower bound friction properties. Location: Aberdeen, WA.

Far-field motions

System

Transverse

Bushing

Acceleration

Limit (g)

Fragility Parameters with

Spectral Shape Effects

RTR as computed. βMDL as defined in

Section 4

RTR bound by 0.4. βMDL as defined in

Section 4 Median

𝑆�̂�𝐹(𝑇1)(g)

RTR PF (50

years) β

PF (50

years) β

PF (50

years)

Non-isolated

T1=0.24sec

1g 1.064 0.173 0.091 0.346 0.100 0.346 0.100

2g 2.130 0.173 0.026 0.346 0.030 0.346 0.030

Horizontally

isolated

T1=2.4sec

1g 0.439 0.551 0.034 0.560 0.034 0.412 0.031

2g 0.471 0.477 0.030 0.487 0.030 0.412 0.029

Horizontally-

vertically

isolated

without

rocking

T1=2.4sec

1g 0.503 0.322 0.025 0.379 0.026 0.379 0.026

2g 0.537 0.278 0.022 0.342 0.023 0.342 0.023

Horizontally-

vertically

isolated with

rocking

T1=2.4sec

1g 0.423 0.620 0.038 0.651 0.038 0.447 0.034

2g 0.568 0.289 0.021 0.351 0.021 0.351 0.021

Page 129: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

91

Table 5-15 Summary of results for probability of failure when considering uncertainties for isolated and non-isolated transformer with W=420kip, fAI=4.3Hz and inclined bushing. When isolated, DCapacity=17.7inch and lower bound friction properties. Location: Loma Linda, CA.

Far-field motions

System

Transverse

Bushing

Acceleration

Limit (g)

Fragility Parameters with

Spectral Shape Effects

RTR as computed. βMDL as defined in

Section 4

RTR bound by 0.4. βMDL as defined in

Section 4 Median

𝑆�̂�𝐹(𝑇1)(g)

RTR PF (50

years) β

PF (50

years) β

PF (50

years)

Non-isolated

T1=0.24sec

1g 1.109 0.173 0.203 0.346 0.236 0.346 0.236

2g 2.220 0.173 0.029 0.346 0.043 0.346 0.043

Horizontally

isolated

T1=2.4sec

1g 0.865 0.551 0.068 0.560 0.069 0.412 0.056

2g 0.847 0.477 0.064 0.487 0.065 0.412 0.058

Horizontally-

vertically

isolated

without

rocking

T1=2.4sec

1g 0.724 0.322 0.071 0.379 0.076 0.379 0.076

2g 0.730 0.278 0.067 0.342 0.072 0.342 0.072

Horizontally-

vertically

isolated with

rocking

T1=2.4sec

1g 0.935 0.620 0.066 0.651 0.070 0.447 0.050

2g 0.782 0.289 0.059 0.351 0.063 0.351 0.063

Page 130: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

92

Table 5-16 Summary of results for probability of failure when considering uncertainties for isolated and non-isolated transformer with W=420kip, fAI=4.3Hz and inclined bushing. When

isolated, DCapacity=17.7inch and lower bound friction properties. Location: Hillsboro, OR. Far-field motions

System

Transverse

Bushing

Acceleration

Limit (g)

Fragility Parameters with

Spectral Shape Effects

RTR as computed. βMDL as defined in

Section 4

RTR bound by 0.4. βMDL as defined in

Section 4 Median

𝑆�̂�𝐹(𝑇1)(g)

RTR PF (50

years) β

PF (50

years) β

PF (50

years)

Non-isolated

T1=0.24sec

1g 1.037 0.173 0.051 0.346 0.059 0.346 0.059

2g 2.074 0.173 0.009 0.346 0.012 0.346 0.012

Horizontally

isolated

T1=2.4sec

1g 0.352 0.551 0.025 0.560 0.026 0.412 0.022

2g 0.390 0.477 0.019 0.487 0.020 0.412 0.018

Horizontally-

vertically

isolated

without

rocking

T1=2.4sec

1g 0.447 0.322 0.012 0.379 0.013 0.379 0.013

2g 0.487 0.278 0.010 0.342 0.010 0.342 0.010

Horizontally-

vertically

isolated with

rocking

T1=2.4sec

1g 0.328 0.620 0.031 0.651 0.032 0.447 0.025

2g 0.512 0.289 0.009 0.351 0.009 0.351 0.009

Page 131: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

93

Table 5-17 Summary of results for probability of failure when considering uncertainties for isolated and non-isolated transformer with W=420kip, fAI=4.3Hz and inclined bushing. When

isolated, DCapacity=17.7inch and lower bound friction properties. Location: Eugene, OR. Far-field motions

System

Transverse

Bushing

Acceleration

Limit (g)

Fragility Parameters with

Spectral Shape Effects

RTR as computed. βMDL as defined in

Section 4

RTR bound by 0.4. βMDL as defined in

Section 4 Median

𝑆�̂�𝐹(𝑇1)(g)

RTR PF (50

years) β

PF (50

years) β

PF (50

years)

Non-isolated

T1=0.24sec

1g 1.030 0.173 0.043 0.346 0.046 0.346 0.046

2g 2.062 0.173 0.010 0.346 0.012 0.346 0.012

Horizontally

isolated

T1=2.4sec

1g 0.347 0.551 0.026 0.560 0.026 0.412 0.023

2g 0.385 0.477 0.021 0.487 0.021 0.412 0.020

Horizontally-

vertically

isolated

without

rocking

T1=2.4sec

1g 0.443 0.322 0.012 0.379 0.015 0.379 0.015

2g 0.483 0.278 0.010 0.342 0.012 0.342 0.012

Horizontally-

vertically

isolated with

rocking

T1=2.4sec

1g 0.321 0.620 0.030 0.651 0.031 0.447 0.027

2g 0.508 0.289 0.011 0.351 0.011 0.351 0.011

Page 132: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

94

Table 5-18 Summary of results for probability of failure when considering uncertainties for isolated and non-isolated transformer with W=420kip, fAI=4.3Hz and inclined bushing. When isolated, DCapacity=17.7inch and lower bound friction properties. Location: Wilsonville, OR.

Far-field motions

System

Transverse

Bushing

Acceleration

Limit (g)

Fragility Parameters with

Spectral Shape Effects

RTR as computed. βMDL as defined in

Section 4

RTR bound by 0.4. βMDL as defined in

Section 4 Median

𝑆�̂�𝐹(𝑇1)(g)

RTR PF (50

years) β

PF (50

years) β

PF (50

years)

Non-isolated

T1=0.24sec

1g 1.030 0.173 0.045 0.346 0.053 0.346 0.053

2g 2.061 0.173 0.007 0.346 0.010 0.346 0.010

Horizontally

isolated

T1=2.4sec

1g 0.354 0.551 0.022 0.560 0.022 0.412 0.018

2g 0.392 0.477 0.016 0.487 0.016 0.412 0.015

Horizontally-

vertically

isolated

without

rocking

T1=2.4sec

1g 0.448 0.322 0.010 0.379 0.011 0.379 0.011

2g 0.488 0.278 0.008 0.342 0.008 0.342 0.008

Horizontally-

vertically

isolated with

rocking

T1=2.4sec

1g 0.329 0.620 0.029 0.651 0.029 0.447 0.022

2g 0.513 0.289 0.007 0.351 0.007 0.351 0.007

Page 133: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

95

Table 5-19 Summary of results for probability of failure when considering uncertainties for isolated and non-isolated transformer with W=420kip, fAI=4.3Hz and inclined bushing. When

isolated, DCapacity=17.7inch and lower bound friction properties. Location: Curry County, OR. Far-field motions

System

Transverse

Bushing

Acceleration

Limit (g)

Fragility Parameters with

Spectral Shape Effects

RTR as computed. βMDL as defined in

Section 4

RTR bound by 0.4. βMDL as defined in

Section 4 Median

𝑆�̂�𝐹(𝑇1)(g)

RTR PF (50

years) β

PF (50

years) β

PF (50

years)

Non-isolated

T1=0.24sec

1g 1.107 0.173 0.087 0.346 0.092 0.346 0.092

2g 2.215 0.173 0.027 0.346 0.031 0.346 0.031

Horizontally

isolated

T1=2.4sec

1g 0.676 0.551 0.034 0.560 0.034 0.412 0.030

2g 0.685 0.477 0.031 0.487 0.031 0.412 0.030

Horizontally-

vertically

isolated

without

rocking

T1=2.4sec

1g 0.634 0.322 0.032 0.379 0.033 0.379 0.033

2g 0.653 0.278 0.029 0.342 0.031 0.342 0.031

Horizontally-

vertically

isolated with

rocking

T1=2.4sec

1g 0.701 0.620 0.034 0.651 0.035 0.447 0.029

2g 0.696 0.289 0.027 0.351 0.028 0.351 0.028

Page 134: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

96

Table 5-20 Summary of results for probability of failure when considering uncertainties for isolated and non-isolated transformer with W=420kip, fAI=4.3Hz and inclined bushing. When

isolated, DCapacity=17.7inch and lower bound friction properties. Location: Troutdale, OR. Far-field motions

System

Transverse

Bushing

Acceleration

Limit (g)

Fragility Parameters with

Spectral Shape Effects

RTR as computed. βMDL as defined in

Section 4

RTR bound by 0.4. βMDL as defined in

Section 4 Median

𝑆�̂�𝐹(𝑇1)(g)

RTR PF (50

years) β

PF (50

years) β

PF (50

years)

Non-isolated

T1=0.24sec

1g 1.023 0.173 0.038 0.346 0.046 0.346 0.046

2g 2.047 0.173 0.005 0.346 0.007 0.346 0.007

Horizontally

isolated

T1=2.4sec

1g 0.345 0.551 0.020 0.560 0.021 0.412 0.016

2g 0.383 0.477 0.015 0.487 0.015 0.412 0.013

Horizontally-

vertically

isolated

without

rocking

T1=2.4sec

1g 0.442 0.322 0.008 0.379 0.009 0.379 0.009

2g 0.482 0.278 0.006 0.342 0.007 0.342 0.007

Horizontally-

vertically

isolated with

rocking

T1=2.4sec

1g 0.320 0.620 0.026 0.651 0.027 0.447 0.020

2g 0.507 0.289 0.005 0.351 0.006 0.351 0.006

Page 135: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

97

Table 5-21 Summary of results for probability of failure when considering uncertainties for isolated and non-isolated transformer with W=420kip, fAI=11.3Hz and inclined bushing. When isolated, DCapacity=17.7inch and lower bound friction properties. Location: Vancouver, WA.

Far-field motions

System

Transverse

Bushing

Acceleration

Limit (g)

Fragility Parameters with

Spectral Shape Effects

RTR as computed. βMDL as defined in

Section 4

RTR bound by 0.4. βMDL as defined in

Section 4 Median

𝑆�̂�𝐹(𝑇1)(g)

RTR PF (50

years) β

PF (50

years) β

PF (50

years)

Non-isolated

T1=0.09sec

1g 0.955 0.303 0.024 0.426 0.030 0.426 0.030

2g 1.909 0.303 0.003 0.426 0.005 0.426 0.005

Horizontally

isolated

T1=2.4sec

1g 0.302 0.600 0.030 0.608 0.030 0.412 0.024

2g 0.344 0.548 0.022 0.557 0.022 0.412 0.018

Horizontally-

vertically

isolated

without

rocking

T1=2.4sec

1g 0.420 0.323 0.011 0.380 0.012 0.380 0.012

2g 0.442 0.316 0.009 0.374 0.010 0.374 0.010

Horizontally-

vertically

isolated with

rocking

T1=2.4sec

1g 0.500 0.291 0.007 0.353 0.007 0.353 0.007

2g 0.526 0.271 0.006 0.337 0.006 0.337 0.006

Page 136: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

98

Table 5-22 Summary of results for probability of failure when considering uncertainties for isolated and non-isolated transformer with W=420kip, fAI=11.3Hz and inclined bushing. When

isolated, DCapacity=17.7inch and lower bound friction properties. Location: Saranap, CA. Far-field motions

System

Transverse

Bushing

Acceleration

Limit (g)

Fragility Parameters with

Spectral Shape Effects

RTR as computed. βMDL as defined in

Section 4

RTR bound by 0.4. βMDL as defined in

Section 4 Median

𝑆�̂�𝐹(𝑇1)(g)

RTR PF (50

years) β

PF (50

years) β

PF (50

years)

Non-isolated

T1=0.13sec

1g 1.140 0.303 0.078 0.426 0.106 0.426 0.106

2g 2.281 0.303 0.005 0.426 0.011 0.426 0.011

Horizontally

isolated

T1=2.4sec

1g 0.677 0.600 0.041 0.608 0.042 0.412 0.022

2g 0.717 0.548 0.029 0.557 0.030 0.412 0.018

Horizontally-

vertically

isolated

without

rocking

T1=2.4sec

1g 0.616 0.323 0.022 0.380 0.026 0.380 0.026

2g 0.637 0.316 0.019 0.374 0.023 0.374 0.023

Horizontally-

vertically

isolated with

rocking

T1=2.4sec

1g 0.702 0.291 0.013 0.353 0.016 0.353 0.016

2g 0.715 0.271 0.011 0.337 0.014 0.337 0.014

Page 137: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

99

Table 5-23 Summary of results for probability of failure when considering uncertainties for isolated and non-isolated transformer with W=420kip, fAI=11.3Hz and inclined bushing. When

isolated, DCapacity=17.7inch and lower bound friction properties. Location: Chehalis, WA. Far-field motions

System

Transverse

Bushing

Acceleration

Limit (g)

Fragility Parameters with

Spectral Shape Effects

RTR as computed. βMDL as defined in

Section 4

RTR bound by 0.4. βMDL as defined in

Section 4 Median

𝑆�̂�𝐹(𝑇1)(g)

RTR PF (50

years) β

PF (50

years) β

PF (50

years)

Non-isolated

T1=0.13sec

1g 0.959 0.303 0.048 0.426 0.058 0.426 0.058

2g 1.918 0.303 0.007 0.426 0.011 0.426 0.011

Horizontally

isolated

T1=2.4sec

1g 0.315 0.600 0.036 0.608 0.037 0.412 0.029

2g 0.358 0.548 0.028 0.557 0.028 0.412 0.023

Horizontally-

vertically

isolated

without

rocking

T1=2.4sec

1g 0.428 0.323 0.015 0.380 0.016 0.380 0.016

2g 0.451 0.316 0.013 0.374 0.014 0.374 0.014

Horizontally-

vertically

isolated with

rocking

T1=2.4sec

1g 0.509 0.291 0.010 0.353 0.011 0.353 0.011

2g 0.534 0.271 0.009 0.337 0.010 0.337 0.010

Page 138: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

100

Table 5-24 Summary of results for probability of failure when considering uncertainties for isolated and non-isolated transformer with W=420kip, fAI=11.3Hz and inclined bushing. When

isolated, DCapacity=17.7inch and lower bound friction properties. Location: Aberdeen, WA. Far-field motions

System

Transverse

Bushing

Acceleration

Limit (g)

Fragility Parameters with

Spectral Shape Effects

RTR as computed. βMDL as defined in

Section 4

RTR bound by 0.4. βMDL as defined in

Section 4 Median

𝑆�̂�𝐹(𝑇1)(g)

RTR PF (50

years) β

PF (50

years) β

PF (50

years)

Non-isolated

T1=0.13sec

1g 1.025 0.303 0.060 0.426 0.068 0.426 0.068

2g 2.049 0.303 0.014 0.426 0.017 0.426 0.017

Horizontally

isolated

T1=2.4sec

1g 0.402 0.600 0.039 0.608 0.040 0.412 0.035

2g 0.447 0.548 0.033 0.557 0.034 0.412 0.031

Horizontally-

vertically

isolated

without

rocking

T1=2.4sec

1g 0.481 0.323 0.027 0.380 0.027 0.380 0.027

2g 0.503 0.316 0.025 0.374 0.026 0.374 0.026

Horizontally-

vertically

isolated with

rocking

T1=2.4sec

1g 0.564 0.291 0.021 0.353 0.022 0.353 0.022

2g 0.587 0.271 0.020 0.337 0.020 0.337 0.020

Page 139: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

101

Table 5-25 Summary of results for probability of failure when considering uncertainties for isolated and non-isolated transformer with W=420kip, fAI=11.3Hz and inclined bushing. When isolated, DCapacity=17.7inch and lower bound friction properties. Location: Loma Linda, CA.

Far-field motions

System

Transverse

Bushing

Acceleration

Limit (g)

Fragility Parameters with

Spectral Shape Effects

RTR as computed. βMDL as defined in

Section 4

RTR bound by 0.4. βMDL as defined in

Section 4 Median

𝑆�̂�𝐹(𝑇1)(g)

RTR PF (50

years) β

PF (50

years) β

PF (50

years)

Non-isolated

T1=0.09sec

1g 1.135 0.303 0.114 0.426 0.140 0.426 0.140

2g 2.271 0.303 0.013 0.426 0.021 0.426 0.021

Horizontally

isolated

T1=2.4sec

1g 0.866 0.600 0.074 0.608 0.075 0.412 0.055

2g 0.897 0.548 0.064 0.557 0.064 0.412 0.052

Horizontally-

vertically

isolated

without

rocking

T1=2.4sec

1g 0.693 0.323 0.078 0.380 0.082 0.380 0.082

2g 0.712 0.316 0.073 0.374 0.078 0.374 0.078

Horizontally-

vertically

isolated with

rocking

T1=2.4sec

1g 0.779 0.291 0.060 0.353 0.064 0.353 0.064

2g 0.786 0.271 0.057 0.337 0.061 0.337 0.061

Page 140: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

102

Table 5-26 Summary of results for probability of failure when considering uncertainties for isolated and non-isolated transformer with W=420kip, fAI=11.3Hz and inclined bushing. When

isolated, DCapacity=17.7inch and lower bound friction properties. Location: Hillsboro, OR. Far-field motions

System

Transverse

Bushing

Acceleration

Limit (g)

Fragility Parameters with

Spectral Shape Effects

RTR as computed. βMDL as defined in

Section 4

RTR bound by 0.4. βMDL as defined in

Section 4 Median

𝑆�̂�𝐹(𝑇1)(g)

RTR PF (50

years) β

PF (50

years) β

PF (50

years)

Non-isolated

T1=0.09sec

1g 0.967 0.303 0.028 0.426 0.034 0.426 0.034

2g 1.934 0.303 0.005 0.426 0.006 0.426 0.006

Horizontally

isolated

T1=2.4sec

1g 0.314 0.600 0.032 0.608 0.033 0.412 0.026

2g 0.357 0.548 0.025 0.557 0.258 0.412 0.236

Horizontally-

vertically

isolated

without

rocking

T1=2.4sec

1g 0.428 0.323 0.013 0.380 0.014 0.380 0.014

2g 0.450 0.316 0.012 0.374 0.013 0.374 0.013

Horizontally-

vertically

isolated with

rocking

T1=2.4sec

1g 0.508 0.291 0.009 0.353 0.010 0.353 0.010

2g 0.534 0.271 0.008 0.337 0.008 0.337 0.008

Page 141: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

103

Table 5-27 Summary of results for probability of failure when considering uncertainties for isolated and non-isolated transformer with W=420kip, fAI=11.3Hz and inclined bushing. When

isolated, DCapacity=17.7inch and lower bound friction properties. Location: Eugene, OR. Far-field motions

System

Transverse

Bushing

Acceleration

Limit (g)

Fragility Parameters with

Spectral Shape Effects

RTR as computed. βMDL as defined in

Section 4

RTR bound by 0.4. βMDL as defined in

Section 4 Median

𝑆�̂�𝐹(𝑇1)(g)

RTR PF (50

years) β

PF (50

years) β

PF (50

years)

Non-isolated

T1=0.09sec

1g 0.949 0.303 0.023 0.426 0.026 0.426 0.026

2g 1.898 0.303 0.005 0.426 0.006 0.426 0.006

Horizontally

isolated

T1=2.4sec

1g 0.308 0.600 0.032 0.608 0.032 0.412 0.028

2g 0.351 0.548 0.025 0.557 0.025 0.412 0.023

Horizontally-

vertically

isolated

without

rocking

T1=2.4sec

1g 0.424 0.323 0.015 0.380 0.016 0.380 0.016

2g 0.446 0.316 0.014 0.374 0.015 0.374 0.015

Horizontally-

vertically

isolated with

rocking

T1=2.4sec

1g 0.504 0.291 0.011 0.353 0.012 0.353 0.012

2g 0.530 0.271 0.010 0.337 0.010 0.337 0.010

Page 142: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

104

Table 5-28 Summary of results for probability of failure when considering uncertainties for isolated and non-isolated transformer with W=420kip, fAI=11.3Hz and inclined bushing. When

isolated, DCapacity=17.7inch and lower bound friction properties. Location: Wilsonville, OR. Far-field motions

System

Transverse

Bushing

Acceleration

Limit (g)

Fragility Parameters with

Spectral Shape Effects

RTR as computed. βMDL as defined in

Section 4

RTR bound by 0.4. βMDL as defined in

Section 4 Median

𝑆�̂�𝐹(𝑇1)(g)

RTR PF (50

years) β

PF (50

years) β

PF (50

years)

Non-isolated

T1=0.09sec

1g 0.953 0.303 0.025 0.426 0.030 0.426 0.030

2g 1.907 0.303 0.004 0.426 0.005 0.426 0.005

Horizontally

isolated

T1=2.4sec

1g 0.316 0.600 0.028 0.608 0.029 0.412 0.022

2g 0.359 0.548 0.021 0.557 0.021 0.412 0.018

Horizontally-

vertically

isolated

without

rocking

T1=2.4sec

1g 0.429 0.323 0.011 0.380 0.012 0.380 0.012

2g 0.451 0.316 0.010 0.374 0.010 0.374 0.010

Horizontally-

vertically

isolated with

rocking

T1=2.4sec

1g 0.509 0.291 0.007 0.353 0.008 0.353 0.008

2g 0.535 0.271 0.006 0.337 0.007 0.337 0.007

Page 143: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

105

Table 5-29 Summary of results for probability of failure when considering uncertainties for isolated and non-isolated transformer with W=420kip, fAI=11.3Hz and inclined bushing. When isolated, DCapacity=17.7inch and lower bound friction properties. Location: Curry County, OR.

Far-field motions

System

Transverse

Bushing

Acceleration

Limit (g)

Fragility Parameters with

Spectral Shape Effects

RTR as computed. βMDL as defined in

Section 4

RTR bound by 0.4. βMDL as defined in

Section 4 Median

𝑆�̂�𝐹(𝑇1)(g)

RTR PF (50

years) β

PF (50

years) β

PF (50

years)

Non-isolated

T1=0.13sec

1g 1.123 0.303 0.048 0.426 0.053 0.426 0.053

2g 2.247 0.303 0.012 0.426 0.015 0.426 0.015

Horizontally

isolated

T1=2.4sec

1g 0.656 0.600 0.037 0.608 0.037 0.412 0.032

2g 0.697 0.548 0.032 0.557 0.033 0.412 0.029

Horizontally-

vertically

isolated

without

rocking

T1=2.4sec

1g 0.607 0.323 0.034 0.380 0.035 0.380 0.035

2g 0.628 0.316 0.032 0.374 0.033 0.374 0.033

Horizontally-

vertically

isolated with

rocking

T1=2.4sec

1g 0.693 0.291 0.027 0.353 0.028 0.353 0.028

2g 0.707 0.271 0.026 0.337 0.027 0.337 0.027

Page 144: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

106

Table 5-30 Summary of results for probability of failure when considering uncertainties for isolated and non-isolated transformer with W=420kip, fAI=11.3Hz and inclined bushing. When

isolated, DCapacity=17.7inch and lower bound friction properties. Location: Troutdale, OR. Far-field motions

System

Transverse

Bushing

Acceleration

Limit (g)

Fragility Parameters with

Spectral Shape Effects

RTR as computed. βMDL as defined in

Section 4

RTR bound by 0.4. βMDL as defined in

Section 4 Median

𝑆�̂�𝐹(𝑇1)(g)

RTR PF (50

years) β

PF (50

years) β

PF (50

years)

Non-isolated

T1=0.13sec

1g 0.948 0.303 0.021 0.426 0.027 0.426 0.027

2g 1.895 0.303 0.003 0.426 0.004 0.426 0.004

Horizontally

isolated

T1=2.4sec

1g 0.307 0.600 0.027 0.608 0.027 0.412 0.021

2g 0.349 0.548 0.020 0.557 0.020 0.412 0.016

Horizontally-

vertically

isolated

without

rocking

T1=2.4sec

1g 0.423 0.323 0.009 0.380 0.010 0.380 0.010

2g 0.445 0.316 0.008 0.374 0.009 0.374 0.009

Horizontally-

vertically

isolated with

rocking

T1=2.4sec

1g 0.503 0.291 0.006 0.353 0.006 0.353 0.006

2g 0.529 0.271 0.005 0.337 0.005 0.337 0.005

Page 145: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

107

Table 5-31 Summary of results for probability of failure when considering uncertainties for isolated and non-isolated transformer with W=420kip, fAI=7.7Hz and inclined bushing. When isolated, DCapacity=31.3inch and lower bound friction properties. Location: Vancouver, WA.

Far-field motions

System

Transverse

Bushing

Acceleration

Limit (g)

Fragility Parameters with

Spectral Shape Effects

RTR as computed. βMDL as defined in

Section 4

RTR bound by 0.4. βMDL as defined in

Section 4 Median

𝑆�̂�𝐹(𝑇1)(g)

RTR PF (50

years) β

PF (50

years) β

PF (50

years)

Non-isolated

T1=0.13sec

1g 0.706 0.276 0.069 0.408 0.080 0.408 0.080

2g 1.411 0.276 0.013 0.408 0.017 0.408 0.017

Horizontally

isolated

T1=2.4sec

1g 0.304 0.744 0.037 0.751 0.037 0.412 0.023

2g 0.430 0.611 0.016 0.619 0.017 0.412 0.012

Horizontally-

vertically

isolated

without

rocking

T1=2.4sec

1g 0.414 0.405 0.012 0.452 0.013 0.447 0.013

2g 0.451 0.319 0.009 0.377 0.010 0.377 0.010

Horizontally-

vertically

isolated with

rocking

T1=2.4sec

1g 0.423 0.404 0.012 0.451 0.013 0.447 0.013

2g 0.481 0.302 0.008 0.362 0.008 0.362 0.008

Page 146: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

108

Table 5-32 Summary of results for probability of failure when considering uncertainties for isolated and non-isolated transformer with W=420kip, fAI=7.7Hz and inclined bushing. When

isolated, DCapacity=31.3inch and lower bound friction properties. Location: Saranap, CA. Far-field motions

System

Transverse

Bushing

Acceleration

Limit (g)

Fragility Parameters with

Spectral Shape Effects

RTR as computed. βMDL as defined in

Section 4

RTR bound by 0.4. βMDL as defined in

Section 4 Median

𝑆�̂�𝐹(𝑇1)(g)

RTR PF (50

years) β

PF (50

years) β

PF (50

years)

Non-isolated

T1=0.13sec

1g 0.782 0.276 0.266 0.408 0.307 0.408 0.307

2g 1.564 0.276 0.038 0.408 0.058 0.408 0.058

Horizontally

isolated

T1=2.4sec

1g 0.700 0.744 0.058 0.751 0.060 0.412 0.019

2g 0.911 0.611 0.019 0.619 0.020 0.412 0.008

Horizontally-

vertically

isolated

without

rocking

T1=2.4sec

1g 0.653 0.405 0.024 0.452 0.028 0.447 0.027

2g 0.665 0.319 0.017 0.377 0.020 0.377 0.020

Horizontally-

vertically

isolated with

rocking

T1=2.4sec

1g 0.676 0.404 0.021 0.451 0.025 0.447 0.025

2g 0.699 0.302 0.013 0.362 0.016 0.362 0.016

Page 147: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

109

Table 5-33 Summary of results for probability of failure when considering uncertainties for isolated and non-isolated transformer with W=420kip, fAI=7.7Hz and inclined bushing. When isolated, DCapacity=31.3inch and lower bound friction properties. Location: Loma Linda, CA.

Far-field motions

System

Transverse

Bushing

Acceleration

Limit (g)

Fragility Parameters with

Spectral Shape Effects

RTR as computed. βMDL as defined in

Section 4

RTR bound by 0.4. βMDL as defined in

Section 4 Median

𝑆�̂�𝐹(𝑇1)(g)

RTR PF (50

years) β

PF (50

years) β

PF (50

years)

Non-isolated

T1=0.13sec

1g 0.782 0.276 0.297 0.408 0.346 0.408 0.346

2g 1.565 0.276 0.059 0.408 0.084 0.408 0.084

Horizontally

isolated

T1=2.4sec

1g 0.902 0.744 0.087 0.751 0.088 0.412 0.051

2g 1.146 0.611 0.044 0.619 0.045 0.412 0.030

Horizontally-

vertically

isolated

without

rocking

T1=2.4sec

1g 0.751 0.405 0.073 0.452 0.077 0.447 0.077

2g 0.749 0.319 0.066 0.377 0.071 0.377 0.071

Horizontally-

vertically

isolated with

rocking

T1=2.4sec

1g 0.780 0.404 0.068 0.451 0.072 0.447 0.071

2g 0.783 0.302 0.060 0.362 0.064 0.362 0.064

Page 148: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

110

Table 5-34 Summary of results for probability of failure when considering uncertainties for isolated and non-isolated transformer with W=420kip, fAI=7.7Hz and inclined bushing. When

isolated, DCapacity=31.3inch and lower bound friction properties. Location: Aberdeen, WA. .Far-field motions

System

Transverse

Bushing

Acceleration

Limit (g)

Fragility Parameters with

Spectral Shape Effects

RTR as computed. βMDL as defined in

Section 4

RTR bound by 0.4. βMDL as defined in

Section 4 Median

𝑆�̂�𝐹(𝑇1)(g)

RTR PF (50

years) β

PF (50

years) β

PF (50

years)

Non-isolated

T1=0.13sec

1g 0.737 0.276 0.135 0.408 0.141 0.408 0.141

2g 1.473 0.276 0.040 0.408 0.044 0.408 0.044

Horizontally

isolated

T1=2.4sec

1g 0.409 0.744 0.043 0.751 0.044 0.412 0.034

2g 0.562 0.611 0.026 0.619 0.026 0.412 0.022

Horizontally-

vertically

isolated

without

rocking

T1=2.4sec

1g 0.487 0.405 0.027 0.452 0.028 0.447 0.028

2g 0.518 0.319 0.024 0.377 0.025 0.377 0.025

Horizontally-

vertically

isolated with

rocking

T1=2.4sec

1g 0.500 0.404 0.026 0.451 0.027 0.447 0.027

2g 0.550 0.302 0.022 0.362 0.023 0.362 0.023

Page 149: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

111

Table 5-35 Summary of results for probability of failure when considering uncertainties for isolated and non-isolated transformer with W=420kip, fAI=7.7Hz and inclined bushing. When

isolated, DCapacity=31.3inch and lower bound friction properties. Location: Chehalis, WA. Far-field motions

System

Transverse

Bushing

Acceleration

Limit (g)

Fragility Parameters with

Spectral Shape Effects

RTR as computed. βMDL as defined in

Section 4

RTR bound by 0.4. βMDL as defined in

Section 4 Median

𝑆�̂�𝐹(𝑇1)(g)

RTR PF (50

years) β

PF (50

years) β

PF (50

years)

Non-isolated

T1=0.13sec

1g 0.717 0.276 0.113 0.408 0.129 0.408 0.129

2g 1.434 0.276 0.024 0.408 0.030 0.408 0.030

Horizontally

isolated

T1=2.4sec

1g 0.318 0.744 0.044 0.751 0.044 0.412 0.029

2g 0.448 0.611 0.021 0.619 0.021 0.412 0.015

Horizontally-

vertically

isolated

without

rocking

T1=2.4sec

1g 0.424 0.405 0.017 0.452 0.018 0.447 0.018

2g 0.460 0.319 0.013 0.377 0.014 0.377 0.014

Horizontally-

vertically

isolated with

rocking

T1=2.4sec

1g 0.433 0.404 0.016 0.451 0.017 0.447 0.017

2g 0.491 0.302 0.011 0.362 0.012 0.362 0.012

Page 150: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

112

Table 5-36 Summary of results for probability of failure when considering uncertainties for isolated and non-isolated transformer with W=420kip, fAI=7.7Hz and inclined bushing. When

isolated, DCapacity=31.3inch and lower bound friction properties. Location: Hillsboro, OR. Far-field motions

System

Transverse

Bushing

Acceleration

Limit (g)

Fragility Parameters with

Spectral Shape Effects

RTR as computed. βMDL as defined in

Section 4

RTR bound by 0.4. βMDL as defined in

Section 4 Median

𝑆�̂�𝐹(𝑇1)(g)

RTR PF (50

years) β

PF (50

years) β

PF (50

years)

Non-isolated

T1=0.13sec

1g 0.711 0.276 0.076 0.408 0.085 0.408 0.085

2g 1.422 0.276 0.017 0.408 0.021 0.408 0.021

Horizontally

isolated

T1=2.4sec

1g 0.317 0.744 0.038 0.751 0.039 0.412 0.026

2g 0.447 0.611 0.018 0.619 0.019 0.412 0.014

Horizontally-

vertically

isolated

without

rocking

T1=2.4sec

1g 0.423 0.405 0.015 0.452 0.016 0.447 0.016

2g 0.460 0.319 0.011 0.377 0.012 0.377 0.012

Horizontally-

vertically

isolated with

rocking

T1=2.4sec

1g 0.433 0.404 0.014 0.451 0.015 0.447 0.015

2g 0.490 0.302 0.010 0.362 0.011 0.362 0.011

Page 151: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

113

Table 5-37 Summary of results for probability of failure when considering uncertainties for isolated and non-isolated transformer with W=420kip, fAI=7.7Hz and inclined bushing. When

isolated, DCapacity=31.3inch and lower bound friction properties. Location: Eugene, OR. Far-field motions

System

Transverse

Bushing

Acceleration

Limit (g)

Fragility Parameters with

Spectral Shape Effects

RTR as computed. βMDL as defined in

Section 4

RTR bound by 0.4. βMDL as defined in

Section 4 Median

𝑆�̂�𝐹(𝑇1)(g)

RTR PF (50

years) β

PF (50

years) β

PF (50

years)

Non-isolated

T1=0.13sec

1g 0.704 0.276 0.052 0.408 0.056 0.408 0.056

2g 1.407 0.276 0.015 0.408 0.017 0.408 0.017

Horizontally

isolated

T1=2.4sec

1g 0.311 0.744 0.035 0.751 0.036 0.412 0.027

2g 0.439 0.611 0.019 0.619 0.019 0.412 0.016

Horizontally-

vertically

isolated

without

rocking

T1=2.4sec

1g 0.419 0.405 0.017 0.452 0.018 0.447 0.018

2g 0.456 0.319 0.014 0.377 0.014 0.377 0.014

Horizontally-

vertically

isolated with

rocking

T1=2.4sec

1g 0.428 0.404 0.016 0.451 0.017 0.447 0.017

2g 0.486 0.302 0.012 0.362 0.012 0.362 0.012

Page 152: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

114

Table 5-38 Summary of results for probability of failure when considering uncertainties for isolated and non-isolated transformer with W=420kip, fAI=7.7Hz and inclined bushing. When isolated, DCapacity=31.3inch and lower bound friction properties. Location: Wilsonville, OR.

Far-field motions

System

Transverse

Bushing

Acceleration

Limit (g)

Fragility Parameters with

Spectral Shape Effects

RTR as computed. βMDL as defined in

Section 4

RTR bound by 0.4. βMDL as defined in

Section 4 Median

𝑆�̂�𝐹(𝑇1)(g)

RTR PF (50

years) β

PF (50

years) β

PF (50

years)

Non-isolated

T1=0.13sec

1g 0.705 0.276 0.069 0.408 0.079 0.408 0.079

2g 1.410 0.276 0.014 0.408 0.018 0.408 0.018

Horizontally

isolated

T1=2.4sec

1g 0.319 0.744 0.034 0.751 0.034 0.412 0.022

2g 0.449 0.611 0.015 0.619 0.016 0.412 0.011

Horizontally-

vertically

isolated

without

rocking

T1=2.4sec

1g 0.425 0.405 0.012 0.452 0.013 0.447 0.013

2g 0.461 0.319 0.009 0.377 0.010 0.377 0.010

Horizontally-

vertically

isolated with

rocking

T1=2.4sec

1g 0.434 0.404 0.012 0.451 0.013 0.447 0.013

2g 0.492 0.302 0.008 0.362 0.008 0.362 0.008

Page 153: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

115

Table 5-39 Summary of results for probability of failure when considering uncertainties for isolated and non-isolated transformer with W=420kip, fAI=7.7Hz and inclined bushing. When

isolated, DCapacity=31.3inch and lower bound friction properties. Location: Curry County, OR. Far-field motions

System

Transverse

Bushing

Acceleration

Limit (g)

Fragility Parameters with

Spectral Shape Effects

RTR as computed. βMDL as defined in

Section 4

RTR bound by 0.4. βMDL as defined in

Section 4 Median

𝑆�̂�𝐹(𝑇1)(g)

RTR PF (50

years) β

PF (50

years) β

PF (50

years)

Non-isolated

T1=0.13sec

1g 0.778 0.276 0.107 0.408 0.108 0.408 0.108

2g 1.556 0.276 0.036 0.408 0.039 0.408 0.039

Horizontally

isolated

T1=2.4sec

1g 0.677 0.744 0.040 0.751 0.040 0.412 0.030

2g 0.885 0.611 0.024 0.619 0.024 0.412 0.019

Horizontally-

vertically

isolated

without

rocking

T1=2.4sec

1g 0.642 0.405 0.033 0.452 0.034 0.447 0.034

2g 0.655 0.319 0.030 0.377 0.031 0.377 0.031

Horizontally-

vertically

isolated with

rocking

T1=2.4sec

1g 0.664 0.404 0.030 0.451 0.032 0.447 0.032

2g 0.689 0.302 0.027 0.362 0.028 0.362 0.028

Page 154: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

116

Table 5-40 Summary of results for probability of failure when considering uncertainties for isolated and non-isolated transformer with W=420kip, fAI=7.7Hz and inclined bushing. When

isolated, DCapacity=31.3inch and lower bound friction properties. Location: Troutdale, OR. Far-field motions

System

Transverse

Bushing

Acceleration

Limit (g)

Fragility Parameters with

Spectral Shape Effects

RTR as computed. βMDL as defined in

Section 4

RTR bound by 0.4. βMDL as defined in

Section 4 Median

𝑆�̂�𝐹(𝑇1)(g)

RTR PF (50

years) β

PF (50

years) β

PF (50

years)

Non-isolated

T1=0.13sec

1g 0.702 0.276 0.061 0.408 0.071 0.408 0.071

2g 1.403 0.276 0.011 0.408 0.015 0.408 0.015

Horizontally

isolated

T1=2.4sec

1g 0.310 0.744 0.033 0.751 0.033 0.412 0.020

2g 0.437 0.611 0.014 0.619 0.014 0.412 0.010

Horizontally-

vertically

isolated

without

rocking

T1=2.4sec

1g 0.418 0.405 0.011 0.452 0.012 0.447 0.011

2g 0.454 0.319 0.008 0.377 0.008 0.377 0.008

Horizontally-

vertically

isolated with

rocking

T1=2.4sec

1g 0.427 0.404 0.010 0.451 0.011 0.447 0.010

2g 0.485 0.302 0.006 0.362 0.007 0.362 0.007

Page 155: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

117

Table 5-41 Summary of results for probability of failure when considering uncertainties for isolated and non-isolated transformer with W=420kip, fAI=4.3Hz and inclined bushing. When isolated, DCapacity=31.3inch and lower bound friction properties. Location: Vancouver, WA.

Far-field motions

System

Transverse

Bushing

Acceleration

Limit (g)

Fragility Parameters with

Spectral Shape Effects

RTR as computed. βMDL as defined in

Section 4

RTR bound by 0.4. βMDL as defined in

Section 4 Median

𝑆�̂�𝐹(𝑇1)(g)

RTR PF (50

years) β

PF (50

years) β

PF (50

years)

Non-isolated

T1=0.24sec

1g 1.030 0.173 0.045 0.346 0.053 0.346 0.053

2g 2.061 0.173 0.006 0.346 0.009 0.346 0.009

Horizontally

isolated

T1=2.4sec

1g 0.408 0.672 0.020 0.679 0.020 0.412 0.013

2g 0.470 0.607 0.014 0.615 0.014 0.412 0.009

Horizontally-

vertically

isolated

without

rocking

T1=2.4sec

1g 0.563 0.423 0.006 0.468 0.007 0.447 0.007

2g 0.647 0.341 0.004 0.395 0.004 0.395 0.004

Horizontally-

vertically

isolated with

rocking

T1=2.4sec

1g 0.370 0.746 0.027 0.772 0.028 0.447 0.017

2g 0.664 0.388 0.004 0.437 0.004 0.437 0.004

Page 156: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

118

Table 5-42 Summary of results for probability of failure when considering uncertainties for isolated and non-isolated transformer with W=420kip, fAI=4.3Hz and inclined bushing. When

isolated, DCapacity=31.3inch and lower bound friction properties. Location: Saranap, CA. Far-field motions

System

Transverse

Bushing

Acceleration

Limit (g)

Fragility Parameters with

Spectral Shape Effects

RTR as computed. βMDL as defined in

Section 4

RTR bound by 0.4. βMDL as defined in

Section 4 Median

𝑆�̂�𝐹(𝑇1)(g)

RTR PF (50

years) β

PF (50

years) β

PF (50

years)

Non-isolated

T1=0.24sec

1g 1.105 0.173 0.153 0.346 0.192 0.346 0.192

2g 2.211 0.173 0.012 0.346 0.023 0.346 0.023

Horizontally

isolated

T1=2.4sec

1g 0.920 0.672 0.024 0.679 0.025 0.412 0.008

2g 1.014 0.607 0.014 0.615 0.015 0.412 0.005

Horizontally-

vertically

isolated

without

rocking

T1=2.4sec

1g 0.928 0.423 0.008 0.468 0.010 0.447 0.009

2g 0.973 0.341 0.004 0.395 0.006 0.395 0.006

Horizontally-

vertically

isolated with

rocking

T1=2.4sec

1g 0.959 0.746 0.029 0.772 0.032 0.447 0.008

2g 1.037 0.388 0.004 0.437 0.006 0.437 0.006

Page 157: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

119

Table 5-43 Summary of results for probability of failure when considering uncertainties for isolated and non-isolated transformer with W=420kip, fAI=4.3Hz and inclined bushing. When

isolated, DCapacity=31.3inch and lower bound friction properties. Location: Chehalis, WA. Far-field motions

System

Transverse

Bushing

Acceleration

Limit (g)

Fragility Parameters with

Spectral Shape Effects

RTR as computed. βMDL as defined in

Section 4

RTR bound by 0.4. βMDL as defined in

Section 4 Median

𝑆�̂�𝐹(𝑇1)(g)

RTR PF (50

years) β

PF (50

years) β

PF (50

years)

Non-isolated

T1=0.24sec

1g 1.043 0.173 0.069 0.346 0.081 0.346 0.081

2g 2.087 0.173 0.011 0.346 0.016 0.346 0.016

Horizontally

isolated

T1=2.4sec

1g 0.426 0.672 0.025 0.679 0.025 0.412 0.017

2g 0.489 0.607 0.017 0.615 0.018 0.412 0.013

Horizontally-

vertically

isolated

without

rocking

T1=2.4sec

1g 0.579 0.423 0.009 0.468 0.010 0.447 0.010

2g 0.661 0.341 0.006 0.395 0.007 0.395 0.007

Horizontally-

vertically

isolated with

rocking

T1=2.4sec

1g 0.389 0.746 0.032 0.772 0.034 0.447 0.021

2g 0.680 0.388 0.006 0.437 0.007 0.437 0.007

Page 158: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

120

Table 5-44 Summary of results for probability of failure when considering uncertainties for isolated and non-isolated transformer with W=420kip, fAI=4.3Hz and inclined bushing. When

isolated, DCapacity=31.3inch and lower bound friction properties. Location: Aberdeen, WA. Far-field motions

System

Transverse

Bushing

Acceleration

Limit (g)

Fragility Parameters with

Spectral Shape Effects

RTR as computed. βMDL as defined in

Section 4

RTR bound by 0.4. βMDL as defined in

Section 4 Median

𝑆�̂�𝐹(𝑇1)(g)

RTR PF (50

years) β

PF (50

years) β

PF (50

years)

Non-isolated

T1=0.24sec

1g 1.064 0.173 0.091 0.346 0.100 0.346 0.100

2g 2.130 0.173 0.026 0.346 0.030 0.346 0.030

Horizontally

isolated

T1=2.4sec

1g 0.545 0.672 0.029 0.679 0.029 0.412 0.023

2g 0.618 0.607 0.023 0.615 0.023 0.412 0.020

Horizontally-

vertically

isolated

without

rocking

T1=2.4sec

1g 0.673 0.423 0.017 0.468 0.018 0.447 0.018

2g 0.748 0.341 0.014 0.395 0.014 0.395 0.014

Horizontally-

vertically

isolated with

rocking

T1=2.4sec

1g 0.519 0.746 0.033 0.772 0.033 0.447 0.026

2g 0.778 0.388 0.013 0.437 0.014 0.437 0.014

Page 159: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

121

Table 5-45 Summary of results for probability of failure when considering uncertainties for isolated and non-isolated transformer with W=420kip, fAI=4.3Hz and inclined bushing. When isolated, DCapacity=31.3inch and lower bound friction properties. Location: Loma Linda, CA.

Far-field motions

System

Transverse

Bushing

Acceleration

Limit (g)

Fragility Parameters with

Spectral Shape Effects

RTR as computed. βMDL as defined in

Section 4

RTR bound by 0.4. βMDL as defined in

Section 4 Median

𝑆�̂�𝐹(𝑇1)(g)

RTR PF (50

years) β

PF (50

years) β

PF (50

years)

Non-isolated

T1=0.24sec

1g 1.119 0.173 0.203 0.346 0.236 0.346 0.236

2g 2.241 0.173 0.029 0.346 0.043 0.346 0.043

Horizontally

isolated

T1=2.4sec

1g 0.925 0.672 0.074 0.679 0.075 0.412 0.048

2g 1.019 0.607 0.055 0.615 0.056 0.412 0.039

Horizontally-

vertically

isolated

without

rocking

T1=2.4sec

1g 0.931 0.423 0.048 0.468 0.052 0.447 0.050

2g 0.976 0.341 0.039 0.395 0.042 0.395 0.042

Horizontally-

vertically

isolated with

rocking

T1=2.4sec

1g 0.965 0.746 0.078 0.772 0.081 0.447 0.047

2g 1.040 0.388 0.036 0.437 0.039 0.437 0.039

Page 160: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

122

Table 5-46 Summary of results for probability of failure when considering uncertainties for isolated and non-isolated transformer with W=420kip, fAI=4.3Hz and inclined bushing. When

isolated, DCapacity=31.3inch and lower bound friction properties. Location: Hillsboro, OR. Far-field motions

System

Transverse

Bushing

Acceleration

Limit (g)

Fragility Parameters with

Spectral Shape Effects

RTR as computed. βMDL as defined in

Section 4

RTR bound by 0.4. βMDL as defined in

Section 4 Median

𝑆�̂�𝐹(𝑇1)(g)

RTR PF (50

years) β

PF (50

years) β

PF (50

years)

Non-isolated

T1=0.24sec

1g 1.037 0.173 0.051 0.059 0.346 0.059 0.059

2g 2.074 0.173 0.009 0.012 0.346 0.012 0.012

Horizontally

isolated

T1=2.4sec

1g 0.425 0.672 0.022 0.679 0.022 0.412 0.015

2g 0.488 0.607 0.016 0.615 0.016 0.412 0.011

Horizontally-

vertically

isolated

without

rocking

T1=2.4sec

1g 0.578 0.423 0.008 0.468 0.009 0.447 0.008

2g 0.660 0.341 0.005 0.395 0.006 0.395 0.006

Horizontally-

vertically

isolated with

rocking

T1=2.4sec

1g 0.388 0.746 0.028 0.772 0.029 0.447 0.019

2g 0.679 0.388 0.005 0.437 0.006 0.437 0.006

Page 161: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

123

Table 5-47 Summary of results for probability of failure when considering uncertainties for isolated and non-isolated transformer with W=420kip, fAI=4.3Hz and inclined bushing. When

isolated, DCapacity=31.3inch and lower bound friction properties. Location: Eugene, OR. Far-field motions.

System

Transverse

Bushing

Acceleration

Limit (g)

Fragility Parameters with

Spectral Shape Effects

RTR as computed. βMDL as defined in

Section 4

RTR bound by 0.4. βMDL as defined in

Section 4 Median

𝑆�̂�𝐹(𝑇1)(g)

RTR PF (50

years) β

PF (50

years) β

PF (50

years)

Non-isolated

T1=0.24sec

1g 1.030 0.173 0.043 0.346 0.046 0.346 0.046

2g 2.062 0.173 0.010 0.346 0.012 0.346 0.012

Horizontally

isolated

T1=2.4sec

1g 0.417 0.672 0.022 0.679 0.022 0.412 0.017

2g 0.479 0.607 0.016 0.615 0.017 0.412 0.013

Horizontally-

vertically

isolated

without

rocking

T1=2.4sec

1g 0.571 0.423 0.010 0.468 0.010 0.447 0.010

2g 0.654 0.341 0.007 0.395 0.007 0.395 0.007

Horizontally-

vertically

isolated with

rocking

T1=2.4sec

1g 0.380 0.746 0.027 0.772 0.028 0.447 0.021

2g 0.672 0.388 0.007 0.437 0.007 0.437 0.007

Page 162: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

124

Table 5-48 Summary of results for probability of failure when considering uncertainties for isolated and non-isolated transformer with W=420kip, fAI=4.3Hz and inclined bushing. When isolated, DCapacity=31.3inch and lower bound friction properties. Location: Wilsonville, OR.

Far-field motions

System

Transverse

Bushing

Acceleration

Limit (g)

Fragility Parameters with

Spectral Shape Effects

RTR as computed. βMDL as defined in

Section 4

RTR bound by 0.4. βMDL as defined in

Section 4 Median

𝑆�̂�𝐹(𝑇1)(g)

RTR PF (50

years) β

PF (50

years) β

PF (50

years)

Non-isolated

T1=0.24sec

1g 1.030 0.173 0.045 0.346 0.053 0.346 0.053

2g 2.061 0.173 0.007 0.346 0.010 0.346 0.010

Horizontally

isolated

T1=2.4sec

1g 0.427 0.672 0.019 0.679 0.019 0.412 0.012

2g 0.491 0.607 0.013 0.615 0.013 0.412 0.009

Horizontally-

vertically

isolated

without

rocking

T1=2.4sec

1g 0.580 0.423 0.006 0.468 0.007 0.447 0.007

2g 0.662 0.341 0.004 0.395 0.004 0.395 0.004

Horizontally-

vertically

isolated with

rocking

T1=2.4sec

1g 0.391 0.746 0.025 0.772 0.026 0.447 0.016

2g 0.681 0.388 0.004 0.437 0.004 0.437 0.004

Page 163: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

125

Table 5-49 Summary of results for probability of failure when considering uncertainties for isolated and non-isolated transformer with W=420kip, fAI=4.3Hz and inclined bushing. When

isolated, DCapacity=31.3inch and lower bound friction properties. Location: Curry County, OR. Far-field motions

System

Transverse

Bushing

Acceleration

Limit (g)

Fragility Parameters with

Spectral Shape Effects

RTR as computed. βMDL as defined in

Section 4

RTR bound by 0.4. βMDL as defined in

Section 4 Median

𝑆�̂�𝐹(𝑇1)(g)

RTR PF (50

years) β

PF (50

years) β

PF (50

years)

Non-isolated

T1=0.24sec

1g 1.107 0.173 0.087 0.346 0.092 0.346 0.092

2g 2.215 0.173 0.027 0.346 0.031 0.346 0.031

Horizontally

isolated

T1=2.4sec

1g 0.891 0.672 0.025 0.679 0.026 0.412 0.019

2g 0.984 0.607 0.020 0.615 0.020 0.412 0.016

Horizontally-

vertically

isolated

without

rocking

T1=2.4sec

1g 0.910 0.423 0.019 0.468 0.020 0.447 0.019

2g 0.958 0.341 0.016 0.395 0.017 0.395 0.017

Horizontally-

vertically

isolated with

rocking

T1=2.4sec

1g 0.924 0.746 0.026 0.772 0.027 0.447 0.019

2g 1.019 0.388 0.015 0.437 0.016 0.437 0.016

Page 164: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

126

Table 5-50 Summary of results for probability of failure when considering uncertainties for isolated and non-isolated transformer with W=420kip, fAI=4.3Hz and inclined bushing. When

isolated, DCapacity=31.3inch and lower bound friction properties. Location: Troutdale, OR. Far-field motions

System

Transverse

Bushing

Acceleration

Limit (g)

Fragility Parameters with

Spectral Shape Effects

RTR as computed. βMDL as defined in

Section 4

RTR bound by 0.4. βMDL as defined in

Section 4 Median

𝑆�̂�𝐹(𝑇1)(g)

RTR PF (50

years) β

PF (50

years) β

PF (50

years)

Non-isolated

T1=0.24sec

1g 1.023 0.173 0.038 0.346 0.046 0.346 0.046

2g 2.047 0.173 0.005 0.346 0.007 0.346 0.007

Horizontally

isolated

T1=2.4sec

1g 0.415 0.672 0.018 0.679 0.018 0.412 0.011

2g 0.477 0.607 0.012 0.615 0.012 0.412 0.008

Horizontally-

vertically

isolated

without

rocking

T1=2.4sec

1g 0.569 0.423 0.005 0.468 0.006 0.447 0.006

2g 0.653 0.341 0.003 0.395 0.003 0.395 0.003

Horizontally-

vertically

isolated with

rocking

T1=2.4sec

1g 0.377 0.746 0.024 0.772 0.025 0.447 0.014

2g 0.670 0.388 0.003 0.437 0.004 0.437 0.004

Page 165: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

127

Table 5-51 Summary of results for probability of failure when considering uncertainties for isolated and non-isolated transformer with W=420kip, fAI=11.3Hz and inclined bushing. When

isolated, DCapacity=31.3inch and lower bound friction properties. Location: Vancouver, WA. Far-field motions

System

Transverse

Bushing

Acceleration

Limit (g)

Fragility Parameters with

Spectral Shape Effects

RTR as computed. βMDL as defined in

Section 4

RTR bound by 0.4. βMDL as defined in

Section 4 Median

𝑆�̂�𝐹(𝑇1)(g)

RTR PF (50

years) β

PF (50

years) β

PF (50

years)

Non-isolated

T1=0.09sec

1g 0.955 0.303 0.024 0.426 0.030 0.426 0.030

2g 1.909 0.303 0.003 0.426 0.005 0.426 0.005

Horizontally

isolated

T1=2.4sec

1g 0.350 0.714 0.028 0.721 0.028 0.412 0.018

2g 0.425 0.672 0.019 0.679 0.019 0.412 0.012

Horizontally-

vertically

isolated

without

rocking

T1=2.4sec

1g 0.546 0.437 0.007 0.481 0.008 0.447 0.007

2g 0.572 0.415 0.006 0.461 0.007 0.447 0.006

Horizontally-

vertically

isolated with

rocking

T1=2.4sec

1g 0.648 0.381 0.004 0.430 0.005 0.430 0.005

2g 0.692 0.346 0.003 0.400 0.004 0.400 0.004

Page 166: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

128

Table 5-52 Summary of results for probability of failure when considering uncertainties for isolated and non-isolated transformer with W=420kip, fAI=11.3Hz and inclined bushing. When

isolated, DCapacity=31.3inch and lower bound friction properties. Location: Saranap, CA. Far-field motions

System

Transverse

Bushing

Acceleration

Limit (g)

Fragility Parameters with

Spectral Shape Effects

RTR as computed. βMDL as defined in

Section 4

RTR bound by 0.4. βMDL as defined in

Section 4 Median

𝑆�̂�𝐹(𝑇1)(g)

RTR PF (50

years) β

PF (50

years) β

PF (50

years)

Non-isolated

T1=0.09sec

1g 1.139 0.303 0.079 0.426 0.106 0.426 0.106

2g 2.277 0.303 0.005 0.426 0.011 0.426 0.011

Horizontally

isolated

T1=2.4sec

1g 0.656 0.714 0.062 0.721 0.063 0.412 0.024

2g 0.767 0.672 0.038 0.679 0.039 0.412 0.015

Horizontally-

vertically

isolated

without

rocking

T1=2.4sec

1g 0.771 0.437 0.016 0.481 0.019 0.447 0.016

2g 0.795 0.415 0.013 0.461 0.016 0.447 0.015

Horizontally-

vertically

isolated with

rocking

T1=2.4sec

1g 0.875 0.381 0.008 0.430 0.010 0.430 0.010

2g 0.914 0.346 0.006 0.400 0.008 0.400 0.008

Page 167: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

129

Table 5-53 Summary of results for probability of failure when considering uncertainties for isolated and non-isolated transformer with W=420kip, fAI=11.3Hz and inclined bushing. When

isolated, DCapacity=31.3inch and lower bound friction properties. Location: Chehalis, WA. Far-field motions

System

Transverse

Bushing

Acceleration

Limit (g)

Fragility Parameters with

Spectral Shape Effects

RTR as computed. βMDL as defined in

Section 4

RTR bound by 0.4. βMDL as defined in

Section 4 Median

𝑆�̂�𝐹(𝑇1)(g)

RTR PF (50

years) β

PF (50

years) β

PF (50

years)

Non-isolated

T1=0.09sec

1g 0.959 0.303 0.048 0.426 0.058 0.426 0.058

2g 1.918 0.303 0.007 0.426 0.011 0.426 0.011

Horizontally

isolated

T1=2.4sec

1g 0.367 0.714 0.034 0.721 0.034 0.412 0.022

2g 0.445 0.672 0.023 0.679 0.023 0.412 0.015

Horizontally-

vertically

isolated

without

rocking

T1=2.4sec

1g 0.561 0.437 0.010 0.481 0.011 0.447 0.010

2g 0.587 0.415 0.009 0.461 0.009 0.447 0.009

Horizontally-

vertically

isolated with

rocking

T1=2.4sec

1g 0.663 0.381 0.006 0.430 0.007 0.430 0.007

2g 0.707 0.346 0.005 0.400 0.006 0.400 0.006

Page 168: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

130

Table 5-54 Summary of results for probability of failure when considering uncertainties for isolated and non-isolated transformer with W=420kip, fAI=11.3Hz and inclined bushing. When

isolated, DCapacity=31.3inch and lower bound friction properties. Location: Aberdeen, WA. Far-field motions

System

Transverse

Bushing

Acceleration

Limit (g)

Fragility Parameters with

Spectral Shape Effects

RTR as computed. βMDL as defined in

Section 4

RTR bound by 0.4. βMDL as defined in

Section 4 Median

𝑆�̂�𝐹(𝑇1)(g)

RTR PF (50

years) β

PF (50

years) β

PF (50

years)

Non-isolated

T1=0.09sec

1g 1.025 0.303 0.060 0.426 0.068 0.426 0.068

2g 2.049 0.303 0.014 0.426 0.017 0.426 0.017

Horizontally

isolated

T1=2.4sec

1g 0.487 0.714 0.034 0.721 0.034 0.412 0.027

2g 0.580 0.672 0.026 0.679 0.027 0.412 0.022

Horizontally-

vertically

isolated

without

rocking

T1=2.4sec

1g 0.655 0.437 0.018 0.481 0.019 0.447 0.018

2g 0.681 0.415 0.017 0.461 0.018 0.447 0.017

Horizontally-

vertically

isolated with

rocking

T1=2.4sec

1g 0.759 0.381 0.014 0.430 0.014 0.430 0.014

2g 0.801 0.346 0.013 0.400 0.013 0.400 0.013

Page 169: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

131

Table 5-55 Summary of results for probability of failure when considering uncertainties for isolated and non-isolated transformer with W=420kip, fAI=11.3Hz and inclined bushing. When isolated, DCapacity=31.3inch and lower bound friction properties. Location: Loma Linda, CA.

Far-field motions

System

Transverse

Bushing

Acceleration

Limit (g)

Fragility Parameters with

Spectral Shape Effects

RTR as computed. βMDL as defined in

Section 4

RTR bound by 0.4. βMDL as defined in

Section 4 Median

𝑆�̂�𝐹(𝑇1)(g)

RTR PF (50

years) β

PF (50

years) β

PF (50

years)

Non-isolated

T1=0.09sec

1g 1.135 0.303 0.114 0.426 0.140 0.426 0.140

2g 2.271 0.303 0.013 0.426 0.021 0.426 0.021

Horizontally

isolated

T1=2.4sec

1g 1.183 0.714 0.051 0.721 0.052 0.412 0.028

2g 1.333 0.672 0.037 0.679 0.038 0.412 0.021

Horizontally-

vertically

isolated

without

rocking

T1=2.4sec

1g 1.065 0.437 0.037 0.481 0.040 0.447 0.038

2g 1.083 0.415 0.034 0.461 0.037 0.447 0.036

Horizontally-

vertically

isolated with

rocking

T1=2.4sec

1g 1.160 0.381 0.027 0.430 0.030 0.430 0.030

2g 1.186 0.346 0.024 0.400 0.027 0.400 0.027

Page 170: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

132

Table 5-56 Summary of results for probability of failure when considering uncertainties for isolated and non-isolated transformer with W=420kip, fAI=11.3Hz and inclined bushing. When

isolated, DCapacity=31.3inch and lower bound friction properties. Location: Hillsboro, OR. Far-field motions

System

Transverse

Bushing

Acceleration

Limit (g)

Fragility Parameters with

Spectral Shape Effects

RTR as computed. βMDL as defined in

Section 4

RTR bound by 0.4. βMDL as defined in

Section 4 Median

𝑆�̂�𝐹(𝑇1)(g)

RTR PF (50

years) β

PF (50

years) β

PF (50

years)

Non-isolated

T1=0.09sec

1g 0.967 0.303 0.028 0.426 0.034 0.426 0.034

2g 1.934 0.303 0.005 0.426 0.006 0.426 0.006

Horizontally

isolated

T1=2.4sec

1g 0.365 0.714 0.030 0.721 0.030 0.412 0.020

2g 0.443 0.672 0.020 0.679 0.021 0.412 0.014

Horizontally-

vertically

isolated

without

rocking

T1=2.4sec

1g 0.560 0.437 0.009 0.481 0.010 0.447 0.009

2g 0.586 0.415 0.008 0.461 0.008 0.447 0.008

Horizontally-

vertically

isolated with

rocking

T1=2.4sec

1g 0.662 0.381 0.006 0.430 0.006 0.430 0.006

2g 0.706 0.346 0.004 0.400 0.005 0.400 0.005

Page 171: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

133

Table 5-57 Summary of results for probability of failure when considering uncertainties for isolated and non-isolated transformer with W=420kip, fAI=11.3Hz and inclined bushing. When

isolated, DCapacity=31.3inch and lower bound friction properties. Location: Eugene, OR. Far-field motions

System

Transverse

Bushing

Acceleration

Limit (g)

Fragility Parameters with

Spectral Shape Effects

RTR as computed. βMDL as defined in

Section 4

RTR bound by 0.4. βMDL as defined in

Section 4 Median

𝑆�̂�𝐹(𝑇1)(g)

RTR PF (50

years) β

PF (50

years) β

PF (50

years)

Non-isolated

T1=0.09sec

1g 0.949 0.303 0.023 0.426 0.026 0.426 0.026

2g 1.898 0.303 0.005 0.426 0.006 0.426 0.006

Horizontally

isolated

T1=2.4sec

1g 0.358 0.714 0.029 0.721 0.029 0.412 0.022

2g 0.434 0.672 0.021 0.679 0.021 0.412 0.016

Horizontally-

vertically

isolated

without

rocking

T1=2.4sec

1g 0.553 0.437 0.011 0.481 0.011 0.447 0.011

2g 0.579 0.415 0.010 0.461 0.010 0.447 0.010

Horizontally-

vertically

isolated with

rocking

T1=2.4sec

1g 0.655 0.381 0.007 0.430 0.008 0.430 0.008

2g 0.699 0.346 0.006 0.400 0.006 0.400 0.006

Page 172: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

134

Table 5-58 Summary of results for probability of failure when considering uncertainties for isolated and non-isolated transformer with W=420kip, fAI=11.3Hz and inclined bushing. When

isolated, DCapacity=31.3inch and lower bound friction properties. Location: Wilsonville, OR. Far-field motions

System

Transverse

Bushing

Acceleration

Limit (g)

Fragility Parameters with

Spectral Shape Effects

RTR as computed. βMDL as defined in

Section 4

RTR bound by 0.4. βMDL as defined in

Section 4 Median

𝑆�̂�𝐹(𝑇1)(g)

RTR PF (50

years) β

PF (50

years) β

PF (50

years)

Non-isolated

T1=0.09sec

1g 0.953 0.303 0.025 0.426 0.030 0.426 0.030

2g 1.906 0.303 0.004 0.426 0.005 0.426 0.005

Horizontally

isolated

T1=2.4sec

1g 0.369 0.714 0.026 0.721 0.026 0.412 0.017

2g 0.447 0.672 0.017 0.679 0.018 0.412 0.011

Horizontally-

vertically

isolated

without

rocking

T1=2.4sec

1g 0.562 0.437 0.007 0.481 0.008 0.447 0.007

2g 0.588 0.415 0.006 0.461 0.007 0.447 0.006

Horizontally-

vertically

isolated with

rocking

T1=2.4sec

1g 0.665 0.381 0.004 0.430 0.005 0.430 0.005

2g 0.708 0.346 0.003 0.400 0.004 0.400 0.004

Page 173: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

135

Table 5-59 Summary of results for probability of failure when considering uncertainties for isolated and non-isolated transformer with W=420kip, fAI=11.3Hz and inclined bushing. When isolated, DCapacity=31.3inch and lower bound friction properties. Location: Curry County, OR.

Far-field motions

System

Transverse

Bushing

Acceleration

Limit (g)

Fragility Parameters with

Spectral Shape Effects

RTR as computed. βMDL as defined in

Section 4

RTR bound by 0.4. βMDL as defined in

Section 4 Median

𝑆�̂�𝐹(𝑇1)(g)

RTR PF (50

years) β

PF (50

years) β

PF (50

years)

Non-isolated

T1=0.09sec

1g 1.123 0.303 0.048 0.426 0.053 0.426 0.053

2g 2.247 0.303 0.012 0.426 0.015 0.426 0.015

Horizontally

isolated

T1=2.4sec

1g 0.857 0.714 0.028 0.721 0.028 0.412 0.021

2g 0.986 0.672 0.022 0.679 0.022 0.412 0.016

Horizontally-

vertically

isolated

without

rocking

T1=2.4sec

1g 0.893 0.437 0.020 0.481 0.021 0.447 0.020

2g 0.915 0.415 0.018 0.461 0.019 0.447 0.019

Horizontally-

vertically

isolated with

rocking

T1=2.4sec

1g 0.995 0.381 0.015 0.430 0.016 0.430 0.016

2g 1.029 0.346 0.014 0.400 0.015 0.400 0.015

Page 174: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

136

Table 5-60 Summary of results for probability of failure when considering uncertainties for isolated and non-isolated transformer with W=420kip, fAI=11.3Hz and inclined bushing. When

isolated, DCapacity=31.3inch and lower bound friction properties. Location: Troutdale, OR. Far-field motions

System

Transverse

Bushing

Acceleration

Limit (g)

Fragility Parameters with

Spectral Shape Effects

RTR as computed. βMDL as defined in

Section 4

RTR bound by 0.4. βMDL as defined in

Section 4 Median

𝑆�̂�𝐹(𝑇1)(g)

RTR PF (50

years) β

PF (50

years) β

PF (50

years)

Non-isolated

T1=0.09sec

1g 0.948 0.303 0.021 0.426 0.027 0.426 0.027

2g 1.895 0.303 0.003 0.426 0.004 0.426 0.004

Horizontally

isolated

T1=2.4sec

1g 0.356 0.714 0.025 0.721 0.025 0.412 0.015

2g 0.432 0.672 0.016 0.679 0.017 0.412 0.010

Horizontally-

vertically

isolated

without

rocking

T1=2.4sec

1g 0.551 0.437 0.006 0.481 0.007 0.447 0.006

2g 0.577 0.415 0.005 0.461 0.006 0.447 0.005

Horizontally-

vertically

isolated with

rocking

T1=2.4sec

1g 0.653 0.381 0.003 0.430 0.004 0.430 0.004

2g 0.697 0.346 0.003 0.400 0.003 0.400 0.003

The results presented in Tables 5-1 to 5-60 show that there is no or there is insignificant benefit in

isolating the considered transformers in any of the ten sites when the transverse acceleration

bushing limit is 2g. There are benefits in isolating the considered transformers when the

transverse acceleration bushing limit is 1g. Table 5-61 presents a summary of results for the

probability of failure in 50 years at the 10 considered sites in the case of the 1g transverse

acceleration bushing limit and for horizontal isolation only. The results are for the case RTR≤0.4

(last column in each of Tables 5-1 to 5-60). Note that when the transformers are horizontally-vertically

isolated, the calculated probabilities of failure are lower than those of the horizontally isolated transformers.

The results in Table 5-61 clearly show the benefits of seismic isolation in the reduction of the probabilities

of failure. Figure 5-1 presents the results of Table 5-61 in graphical form where the benefits can be better

viewed.

The results in Figure 5-1 show that the probability of failure generally improves when the largest

displacement capacity isolator is used. The improvement is partially due to the increased

displacement capacity (particularly for the locations of the highest seismic hazard-Loma Linda and

Saranac, CA) but primarily is due to the difference in the radius of curvature of the largest

Page 175: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

137

displacement capacity isolator. Due to the larger radius of curvature (see Figures 1-1 and 1-2)

the stiffness is smaller, which results in a reduction in peak acceleration.

Table 5-61 Probabilities of failure in 50 years for non-isolated and horizontally isolated transformers with transverse bushing acceleration limit of 1g (case of RTR≤0.4)

Site Non-isolated Horizontally isolated

DCapacity=17.7in Horizontally isolated

DCapacity=31.3in Bushing

Frequency (Hz)

4.3 7.7 11.3 4.3 7.7 11.3 4.3 7.7 11.3

Vancouver,

WA: 1 0.053 0.080 0.030 0.015 0.026 0.024 0.013 0.023 0.018

Saranap,

CA: 2 0.192 0.307 0.106 0.020 0.033 0.022 0.008 0.019 0.024

Loma Linda,

CA: 3 0.236 0.346 0.140 0.056 0.075 0.055 0.048 0.051 0.028

Aberdeen,

WA: 4 0.100 0.141 0.068 0.031 0.040 0.035 0.023 0.034 0.027

Chehalis,

WA: 5 0.081 0.129 0.058 0.024 0.034 0.029 0.017 0.029 0.022

Hillsboro,

OR: 6 0.059 0.085 0.034 0.022 0.031 0.026 0.015 0.026 0.020

Eugene,

OR: 7 0.046 0.056 0.026 0.023 0.032 0.028 0.017 0.027 0.022

Wilsonville,

OR: 8 0.053 0.079 0.030 0.018 0.027 0.022 0.012 0.022 0.017

Curry County,

OR: 9 0.092 0.108 0.053 0.030 0.039 0.032 0.019 0.030 0.021

Trousdale,

OR: 10 0.046 0.071 0.027 0.016 0.025 0.021 0.011 0.020 0.015

Page 176: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

138

Figure 5-1 Probabilities of failure in 50 years for non-isolated and horizontally isolated

transformers with transverse bushing acceleration limit of 1g (case of RTR≤0.4) for ten sites

0.001

0.010

0.100

1.000

1 2 3 4 5 6 7 8 9 10

SITE (per Table 5-61) P

rob

ab

ilit

y o

f fa

ilu

re i

n 5

0

: Non-isolated, 4.3Hz

: Non-isolated, 7.7Hz

: Non-isolated, 11.3Hz

: Isolated, DCap=17.7”, 4.3Hz

: Isolated, DCap=17.7”, 7.7Hz

: Isolated, DCap=17.7”, 11.3Hz

: Isolated, DCap=31.3”, 4.3Hz

: Isolated, DCap=31.3”, 7.7Hz

: Isolated, DCap=31.3”, 11.3Hz

Bushing acceleration limit=1g, RTR≤0.4

Page 177: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

139

SECTION 6

RESULTS FOR NEAR-FIELD MOTIONS

Two of the ten considered sites, the Loma Linda and the Saranap, CA sites, qualify for

classification as being in the proximity of active faults, with the closest fault being within 1km to

4km. For these locations, the fragility analysis results presented in Sections 2 to 5 need to be re-

assessed by conducting the incremental dynamic analysis using motions with near-field

characteristics. FEMA (2009) provided a set of such motions consisting of 28 records of bi-

directional components (56 individual horizontal components) for use in these cases. Table 6-1

presents a subset of 25 of these records for which the vertical ground motion component was

available. In total 50 pairs of horizontal-vertical were available for use in the incremental dynamic

analysis.

Figures 6-1 and 6-2 present the 5%-damped acceleration response spectra for the horizontal and

vertical ground motions, respectively. The horizontal spectra consist of the 50 spectra of fault

normal and fault parallel components, and the vertical spectra consist of the 25 spectra of the

vertical components. The average spectra are also shown for each direction. Figure 6-3 presents

the ratio of the average vertical spectrum to the average horizontal spectrum of the motions (V/H

ratio).

Page 178: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

140

Tab

le 6

-1 N

ear-

fiel

d g

rou

nd m

oti

ons

use

d i

n d

ynam

ic a

nal

ysi

s

Ear

thq

uak

eR

eco

rdin

g S

tati

on

Sit

e D

ata

Val

ues

sh

ow

n a

re i

n t

wo

ho

rizo

nta

l d

irec

tio

ns,

th

en

ver

tica

l; u

nit

s g

, in

/sec

, in

ch

M

Yea

rN

ame

Nam

eN

EH

RP

Cla

ss

Vs_

30

(m/s

ec)

PG

AP

GV

PG

D

Pu

lse

Rec

ord

s S

ub

set

6.5

19

79

Imp

eria

l V

alle

y-0

6E

l C

entr

o A

rray

#6

D2

03

0.4

4, 0

.40

, 1

.89

44

.0, 2

5.5

, 25

.02

6.2

, 9

.8, 9

.3

6.5

19

79

Imp

eria

l V

alle

y-0

6E

l C

entr

o A

rray

#7

D2

11

0.4

6, 0

.34

, 0

.58

42

.8, 1

7.5

, 10

.71

7.9

, 9

.4, 3

.9

6.9

19

80

Irp

inia

, It

aly

-01

Stu

rno

B1

00

00

.23

, 0

.31

, 0

.23

16

.3, 1

7.9

, 9

.58

.7,

9.2

, 4

.1

6.9

19

89

Lo

ma

Pri

eta

Sar

ato

ga

- A

loh

aC

37

10

.36

, 0

.38

, 0

.40

21

.9, 1

7.0

, 11

.01

1.6

, 6

.2, 6

.8

6.7

19

92

Erz

ican

, T

urk

eyE

rzin

can

D2

75

0.4

9, 0

.42

, 0

.23

37

.4, 1

7.8

, 6

.51

2.6

, 6

.5, 4

.1

7

19

92

Cap

e M

end

oci

no

Pet

roli

aC

71

30

.61

, 0

.63

, 0

.17

32

.2, 2

3.8

, 8

.01

0.0

, 1

0.2

, 7

.9

7.3

19

92

Lan

der

sL

uce

rne

C6

85

0.7

1, 0

.79

, 0

.82

55

.1, 2

0.8

, 16

.29

5.7

, 4

7.1

, 11

.7

6.7

19

94

No

rth

rid

ge-

01

Rin

ald

i R

ecei

vin

g S

taD

28

20

.87

, 0

.42

, 0

.96

65

.7, 2

4.6

, 16

.61

1.3

, 8

.4, 1

.5

6.7

19

94

No

rth

rid

ge-

01

Sy

lmar

- O

liv

e V

iew

C4

41

0.7

3, 0

.60

, 0

.54

48

.3, 2

1.4

, 7

.31

2.5

, 4

.2, 3

.1

7.5

19

99

Ko

cael

i, T

urk

eyIz

mit

B8

11

0.1

5, 0

.22

, 0

.14

8.9

, 11

.7, 4

.93

.9,

6.7

, 4

.5

7.6

19

99

Ch

i-C

hi,

Tai

wan

TC

U0

65

D3

06

0.8

2, 0

.59

, 0

.26

50

.2, 3

1.6

, 27

.33

6.7

, 2

3.0

, 22

.6

7.6

19

99

Ch

i-C

hi,

Tai

wan

TC

U1

02

C7

14

0.2

9, 0

.17

, 0

.18

41

.9, 3

0.5

, 26

.93

4.6

, 2

1.6

, 20

.3

7.1

19

99

Du

zce,

Tu

rkey

Du

zce

D2

76

0.3

6, 0

.52

, 0

.35

24

.5, 3

1.2

, 7

.91

8.3

, 1

8.9

, 8

.2

No

Pu

lse

Rec

ord

s S

ub

set

6.8

6.8

Gaz

li,

US

SR

Kar

aky

rC

66

00

.60

, 0

.71

, 1

.70

25

.6, 2

8.0

, 22

.29

.5,

9.7

, 3

.5

6.5

19

79

Imp

eria

l V

alle

y-0

6B

on

ds

Co

rner

D2

23

0.7

6, 0

.59

, 0

.53

17

.4, 1

7.2

, 4

.86

.1,

6.5

, 1

.3

6.5

19

79

Imp

eria

l V

alle

y-0

6C

hih

uah

ua

D2

75

0.2

8, 0

.27

, 0

.22

12

.0, 1

0.6

, 2

.04

.2,

3.1

, 1

.0

6.8

19

85

Nah

ann

i, C

anad

aS

ite

1C

66

00

.85

, 1

.18

, 2

.28

17

.2, 1

4.4

, 16

.16

.3,

1.7

, 4

.0

6.9

19

89

Lo

ma

Pri

eta

BR

AN

C3

76

0.6

4, 0

.41

, 0

.51

22

.0, 1

5.2

, 7

.15

.2,

3.6

, 1

.7

6.9

19

89

Lo

ma

Pri

eta

Co

rral

ito

sC

46

20

.48

, 0

.51

, 0

.46

17

.9, 1

6.4

, 7

.75

.5,

2.8

, 5

.1

71

99

2C

ape

Men

do

cin

oC

ape

Men

do

cin

oC

51

41

.27

, 1

.43

, 0

.74

22

.7, 4

6.6

, 22

.95

.4,

15

.0, 2

2.8

6.7

19

94

No

rth

rid

ge-

01

LA

- S

epu

lved

a V

AC

38

00

.73

, 0

.71

, 0

.32

24

.9, 2

7.5

, 9

.87

.4,

5.7

, 4

.4

7.5

19

99

Ko

cael

i, T

urk

eyY

arim

caD

29

70

.28

, 0

.31

, 0

.24

19

.0,

28

.7,

12

.11

7.0

, 2

2.1

, 11

.6

7.6

19

99

Ch

i-C

hi,

Tai

wan

TC

U0

67

C4

34

0.5

6, 0

.31

, 0

.24

36

.1, 1

8.7

, 19

.63

8.7

, 1

4.4

, 13

.7

7.6

19

99

Ch

i-C

hi,

Tai

wan

TC

U0

84

C5

53

1.1

6, 0

.42

, 0

.32

45

.3, 1

7.2

, 10

.11

2.5

, 8

.2, 5

.2

7.9

20

02

Den

ali,

Ala

ska

TA

PS

Pu

mp

Sta

. #

10

C5

53

0.3

3, 0

.28

, 0

.24

34

.5, 4

9.7

, 20

.13

5.2

, 4

7.1

, 7

.8

Page 179: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

141

Figure 6-1 Horizontal acceleration response spectra of selected 25 near-field ground motions

(total of 50 components)

Figure 6-2 Vertical acceleration response spectra of selected 25 near-field ground motions (total

of 25 components)

0.0

0.5

1.0

1.5

2.0

2.5

3.0

3.5

4.0

0.1 1 10

0

1

2

3

4

5

6

7

8

9

0.1 1 10 100

Frequency (Hz)

Acc

eler

atio

n (

g)

Frequency (Hz)

Acc

eler

atio

n (

g)

: Spectra of 50 components

: Average spectrum

5% damped

: Spectra of 25 components

: Average spectrum

5% damped VERTICAL

HORIZONTAL

Page 180: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

142

Figure 6-3 Vertical to horizontal average spectral (V/H) ratio of 50 sets of near-field motions

Incremental dynamic analysis was performed using the near-field motions for the three cases of

bushing as-installed frequencies (4.3, 7.7 and 11.3Hz) of the 420kip transformer without and with

isolators of displacement capacity DCapacity=31.3inch. When vertically isolated, the vertical

isolation frequency and damping were 2Hz and 0.50, respectively. The isolator friction properties

had the lower bound values. The scaling of the motions was based on the use of the spectral

acceleration at the fundamental period as the measure of seismic intensity (period equal to 2.4sec

for the isolated transformers and equal to the inverse of the as-installed bushing frequency for the

non-isolated transformers). The fragility parameters were determined but not adjusted for spectral

shape effects based on the procedures of Appendix A. Based on Haselton et al. (2011), the

approach of Appendix A is inapplicable to near-field motions with large forward-directivity pulses.

Many of the records (see Table 6-1) do contain such pulses. The only way to correctly account for

the spectral shape effects is to follow the approach of Lin et al. (2013), which was applied in the

study of Kitayama and Constantinou (2019a). However, the approach requires a seismic hazard

analysis for each site, construction of conditional spectra for increasing earthquake intensities, and

selection and scaling of motions to represent each of these spectra. In the study of Kitayama and

Constantinou (2019a), 400 motions were used in the analysis for earthquake intensities

representing spectra with 43 years to 10000 return periods. Such study is beyond the scope of this

work.

0

0.2

0.4

0.6

0.8

1

1.2

1.4

1.6

1.8

0.1 1 10

5% damped : Average V/H Ratio of 50 motions

Frequency (Hz)

V/H

Rat

io

Page 181: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

143

Probabilities of failure in 50 years were calculated based on Equations (2-6) and (2-7) using the

same seismic hazard curves used earlier for the results of Section 3. Tables 6-2 to 6-7 present the

results where they are compared to those obtained using the far-field motions in Section 3. To be

able to better assess the significance of the near-field results, results for the far-field motions

without and with the spectral shape effects correction are included in Tables 6-2 to 6-7. As seen in

these tables and in the results of Section 3, the correction for spectral shape effects for the far-field

motions may result in significant reduction of the probability of failure for isolated transformers

at the Saranac and Lima Linda, CA locations, whereas there was increase in the probability of

failure for the non-isolated transformers at the same locations.

Table 6-2 Summary of results for probability of failure for isolated and non-isolated transformer

with W=420kip, fAI=4.3Hz and inclined bushing. When isolated, DCapacity=31.3inch and lower

bound friction properties. Location: Saranap, CA. Near-field motions

System

Transverse

Bushing

Acceleration

Limit (g)

Without Spectral Shape

Effects

Value reported in

Section 3 for Far-

field Motions

(without spectral

shape effects)

Value reported in

Section 3 for Far-

field Motions (with

spectral shape

effects)

Median

𝑆�̂�𝐹(𝑇1)(g)

RTR PF (50

years) PF (50 years) PF (50 years)

Non-isolated

T1=0.24sec

1g 1.029 0.157 0.181 0.182 0.153

2g 2.030 0.214 0.019 0.016 0.012

Horizontally

isolated

T1=2.4sec

1g 0.497 0.696 0.103 0.109 0.024

2g 0.563 0.692 0.080 0.057 0.014

Horizontally-

vertically

isolated

without

rocking

T1=2.4sec

1g 0.684 0.416 0.021 0.023 0.008

2g 0.710 0.308 0.012 0.014 0.004

Horizontally-

vertically

isolated with

rocking

T1=2.4sec

1g 0.644 0.598 0.046 0.135 0.029

2g 0.753 0.317 0.011 0.015 0.004

Page 182: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

144

Table 6-3 Summary of results for probability of failure for isolated and non-isolated transformer with W=420kip, fAI=4.3Hz and inclined bushing. When isolated, DCapacity=31.3inch and lower

bound friction properties. Location: Loma Linda, CA. Near-field motions

System

Transverse

Bushing

Acceleration

Limit (g)

Without Spectral Shape

Effects

Value reported in

Section 3 for Far-

field Motions

(without spectral

shape effects)

Value reported in

Section 3 for Far-

field Motions (with

spectral shape

effects)

Median

𝑆�̂�𝐹(𝑇1)(g)

RTR PF (50

years) PF (50 years) PF (50 years)

Non-isolated

T1=0.24sec

1g 1.029 0.157 0.234 0.234 0.203

2g 2.030 0.214 0.042 0.038 0.029

Horizontally

isolated

T1=2.4sec

1g 0.497 0.696 0.193 0.201 0.074

2g 0.563 0.692 0.163 0.138 0.055

Horizontally-

vertically isolated

without rocking

T1=2.4sec

1g 0.684 0.416 0.088 0.090 0.048

2g 0.710 0.308 0.073 0.074 0.039

Horizontally-

vertically isolated

with rocking

T1=2.4sec

1g 0.644 0.598 0.120 0.226 0.078

2g 0.753 0.317 0.066 0.074 0.036

Table 6-4 Summary of results for probability of failure for isolated and non-isolated transformer with W=420kip, fAI=7.7Hz and inclined bushing. When isolated, DCapacity=31.3inch and lower

bound friction properties. Location: Saranap, CA. Near-field motions

System

Transverse

Bushing

Acceleration

Limit (g)

Without Spectral Shape

Effects

Value reported in

Section 3 for Far-

field Motions

(without spectral

shape effects)

Value reported in

Section 3 for Far-

field Motions (with

spectral shape

effects)

Median

𝑆�̂�𝐹(𝑇1)(g)

RTR PF (50

years) PF (50 years) PF (50 years)

Non-isolated

T1=0.13sec

1g 0.681 0.305 0.353 0.300 0.266

2g 1.365 0.303 0.065 0.047 0.038

Horizontally

isolated

T1=2.4sec

1g 0.324 0.822 0.255 0.210 0.058

2g 0.511 0.707 0.100 0.080 0.019

Horizontally-

vertically isolated

without rocking

T1=2.4sec

1g 0.483 0.357 0.050 0.064 0.024

2g 0.492 0.296 0.041 0.046 0.017

Horizontally-

vertically isolated

with rocking T1=2.4sec

1g 0.488 0.465 0.063 0.064 0.021

2g 0.503 0.282 0.037 0.035 0.013

Page 183: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

145

Table 6-5 Summary of results for probability of failure for isolated and non-isolated transformer with W=420kip, fAI=7.7Hz and inclined bushing. When isolated, DCapacity=31.3inch and lower

bound friction properties. Location: Loma Linda, CA. Near-field motions

System

Transverse

Bushing

Acceleration

Limit (g)

Without Spectral Shape

Effects

Value reported in

Section 3 for Far-

field Motions

(without spectral

shape effects)

Value reported in

Section 3 for Far-

field Motions (with

spectral shape

effects)

Median

𝑆�̂�𝐹(𝑇1)(g)

RTR PF (50

years) PF (50 years) PF (50 years)

Non-isolated

T1=0.13sec

1g 0.681 0.305 0.393 0.108 0.297

2g 1.365 0.303 0.096 0.075 0.059

Horizontally isolated

T1=2.4sec

1g 0.324 0.822 0.348 0.307 0.087

2g 0.511 0.707 0.188 0.170 0.044

Horizontally-

vertically isolated

without rocking

T1=2.4sec

1g 0.483 0.357 0.150 0.167 0.073

2g 0.492 0.296 0.140 0.146 0.066

Horizontally-

vertically isolated

with rocking

T1=2.4sec

1g 0.488 0.465 0.160 0.168 0.068

2g 0.503 0.282 0.134 0.127 0.060

Table 6-6 Summary of results for probability of failure for isolated and non-isolated transformer with W=420kip, fAI=11.3Hz and inclined bushing. When isolated, DCapacity=31.3inch and lower bound friction properties. Location: Saranap, CA. Near-field motions

System

Transverse

Bushing

Acceleration

Limit (g)

Without Spectral Shape

Effects

Value reported in

Section 3 for Far-

field Motions

(without spectral

shape effects)

Value reported in

Section 3 for Far-

field Motions (with

spectral shape

effects)

Median

𝑆�̂�𝐹(𝑇1)(g)

RTR PF (50

years) PF (50 years) PF (50 years)

Non-isolated

T1=0.09sec

1g 0.956 0.332 0.136 0.105 0.079

2g 1.910 0.337 0.014 0.008 0.005

Horizontally isolated

T1=2.4sec

1g 0.385 0.852 0.210 0.135 0.062

2g 0.515 0.713 0.100 0.071 0.038

Horizontally-

vertically isolated

without rocking

T1=2.4sec

1g 0.669 0.429 0.024 0.028 0.016

2g 0.693 0.374 0.018 0.024 0.013

Horizontally-

vertically isolated

with rocking T1=2.4sec

1g 0.734 0.406 0.016 0.015 0.008

2g 0.769 0.315 0.010 0.011 0.006

Page 184: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

146

Table 6-7 Summary of results for probability of failure for isolated and non-isolated transformer with W=420kip, fAI=11.3Hz and inclined bushing. When isolated, DCapacity=31.3inch and lower

bound friction properties. Location: Loma Linda, CA. Near-field motions

System

Transverse

Bushing

Acceleration

Limit (g)

Without Spectral Shape

Effects

Value reported in

Section 3 for Far-

field Motions

(without spectral

shape effects)

Value reported in

Section 3 for Far-

field Motions (with

spectral shape

effects)

Median

𝑆�̂�𝐹(𝑇1)(g)

RTR PF (50

years) PF (50 years) PF (50 years)

Non-isolated

T1=0.09sec

1g 0.956 0.332 0.176 0.143 0.114

2g 1.910 0.337 0.027 0.019 0.013

Horizontally

isolated

T1=2.4sec

1g 0.385 0.852 0.300 0.229 0.051

2g 0.515 0.713 0.187 0.152 0.037

Horizontally-

vertically isolated

without rocking

T1=2.4sec

1g 0.669 0.429 0.093 0.102 0.037

2g 0.693 0.374 0.082 0.094 0.034

Horizontally-

vertically isolated

with rocking

T1=2.4sec

1g 0.734 0.406 0.076 0.075 0.027

2g 0.769 0.315 0.063 0.066 0.024

The results in Tables 6-2 to 6-7 demonstrate relatively small changes, particularly for the isolated

transformers, in the probability of failure in 50 years of lifetime obtained for near-field motions by

comparison to far-field motions without the correction for the spectral shape effects. This

result may appear surprising given the significant differences between the two sets of motions.

However, it should be noted that for the isolated transformers, the isolation system allows for small

increases in the bushing acceleration as the isolator displacement increases given the fact that the

isolators are of large radius of curvature. Also, the isolators considered are of large displacement

capacity so that failure of the isolators does not occur in the more demanding near-field motions.

That is, the results are valid but limited to the isolator studied (radius of curvature of 61inch for

each concave plate and displacement capacity at failure equal to 31.3inch) and cannot be

generalized to the other studied isolator of different properties.

Assuming that a correction for the spectral shape effects would produce similar results in the two

cases of ground motions, we conclude that consideration of near-field motions did not produce any

significant change in the results obtained using the set of far-field motions.

Page 185: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

147

SECTION 7

SUMMARY AND CONCLUSIONS

This report presents results on the probability of failure in a lifetime of 50 years of non-isolated

and seismically isolated transformers at ten locations in the Western US. The transformer and

isolation system models are the same as those used in the earlier studies of Kitayama et al. (2016,

2017). However, this study deviated from the earlier studies of Kitayama et al. (2016, 2017) by (a)

scaling the ground motions for use in the incremental dynamic analysis by adjusting the spectral

acceleration at the fundamental period (or effective period for isolated transformers) instead of

the peak ground acceleration (PGA) in the earlier studies, (b) correcting for the spectral shape

effects, which were ignored in the earlier studies, and (c) accounting for uncertainties, which were

neglected in earlier studies.

Moreover, the report presents sample results for near-field motions, which however, could not be

corrected for spectral shape effects. A comparison of results obtained for near-field and far-field

motions, both without correction for spectral shape effects, revealed that for the isolated

transformers there is a small difference between the results of the two sets of motions. This was

explained by the fact that the considered isolators were of large radius of curvature (so low

stiffness) and large displacement capacity so that any increases in isolator displacement demand

caused by near-field motions did not cause failure of the isolators or any significant increase in the

bushing acceleration. Accordingly, it was concluded that near-field motions do not appreciably

change the results obtained by the use of far-field motions, provided that for the two locations

considered (Saranap and Loma Linda in California, which are in close proximity to active faults),

isolators of the larger displacement capacity and low stiffness are used.

Results obtained for far-field motions show that, in general, scaling of the ground motions based

on the spectral acceleration at the fundamental period or the effective period results in significant

increases in the probability of failure for the isolated transformers, which are significantly

moderated by corrections for the spectral shape effects. By comparison, the changes in the

probability of failure of the studied non-isolated transformers were small due to the fact that the

fundamental period was very small so that the spectral acceleration at the fundamental period was

very close to the PGA which was used in the earlier studies for the scaling.

Page 186: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

148

Based on the new results in this report, combined horizontal-vertical seismic isolation systems

offer the lowest probabilities of failure for all cases of transformer and isolation system parameters,

and for all considered sites. Horizontal only isolation offers no or offers insignificant advantages

over non-isolation when the bushing transverse acceleration limit is 2g. However, horizontal only

isolation offers important advantages over non-isolation when the bushing transverse acceleration

limit is 1g.

The results of this report, documented in numerous tables, may be used to decide on the benefits

offered by a seismic isolation system depending on the location of the transformer and the form

and properties of the seismic isolation system. The benefit is assessed on the basis of the

probability of failure in 50 years of lifetime. The information may also be used to assess the seismic

performance of electric transmission networks under scenarios of component failures.

Page 187: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

149

SECTION 8

REFERENCES

Abrahamson NA and Silva WJ. Empirical response spectral attenuation relations for shallow

crustal earthquakes, Seismological Research Letters, 1997; 68(1), 94-127.

American Society of Civil Engineers (ASCE) (2017). Standard ASCE/SEI 7-16, Minimum design

loads for buildings and other structures, Reston, VA.

Baker JW. (2011). Conditional mean spectrum: Tool for ground-motion selection. Journal of

Structural Engineering, ASCE, 137(3), 332-344.

Haselton, CB and Baker JW. (2006). Ground motion intensity measures for collapse capacity

prediction: Choice of optimal spectral period and effect of spectral shape. Eighth National

Conference on Earthquake Engineering, pp. 18-22.

Haselton CB, Baker JW, Liel AB and Deierlein GG. (2011). Accounting for ground-motion

spectral shape characteristics in structural collapse assessment through an adjustment for epsilon.

Journal of Structural Engineering, ASCE, 137(3), 332-344.

FEMA. (2009). Quantification of building seismic performance factors. Report FEMA P695,

Federal Emergency Management Agency, Washington, DC.

Field EH, Jordan TH and Cornell CA. (2003). OpenSHA: A developing community-model-ling

environment for seismic hazard analysis. Seismological Research Letters, 74 (4), 406-419.

Kitayama S, Constantinou MC, Lee D. (2016). Procedures and results of assessment of seismic

performance of seismically isolated electrical transformers with due consideration for vertical

isolation and vertical ground motion effects. Report MCEER-16-0010. Multidisciplinary Center

for Earthquake Engineering Research, Buffalo, NY.

Kitayama S, Lee D, Constantinou MC and Kempner L. (2017). Probabilistic seismic assessment

of seismically isolated electrical transformers considering vertical isolation and vertical ground

motion. Engineering Structures, 152 (1), pp. 888-900.

Page 188: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

150

Kitayama S and Constantinou MC. (2018a). Seismic Performance assessment of seismically

isolated buildings designed by the procedures of ASCE/SEI 7. Report MCEER-18-0004,

Multidisciplinary Center for Earthquake Engineering Research, Buffalo, NY.

Kitayama S and Constantinou MC. (2018b). Collapse performance of seismically isolated

buildings designed by the procedures of ASCE/SEI 7. Engineering Structures, 164, pp. 243-258.

Kitayama, S and Constantinou, MC. (2019a). Probabilistic seismic performance assessment of

seismically isolated buildings designed by the procedures of ASCE/SEI 7 and other enhanced

criteria. Engineering Structures, 179, pp. 566-582.

Kitayama, S and Constantinou, MC. (2019b). Effect of displacement restraint on the collapse

performance of seismically isolated buildings. Bulletin of Earthquake Engineering,

https://doi.org/10.1007/s10518-019-00626-z .

Krawinkler H, Zarein F, Medina RA and Ibarra LF. (2006). Decision support for conceptual

performance-based design. Earthquake Engineering and Structural Dynamics, 35 (1), pp. 115-

133.

Lee D and Constantinou MC. (2017). Development and validation of a combined horizontal-

vertical seismic isolation system for high-voltage power transformers. Report MCEER-17-0007,

Multidisciplinary Center for Earthquake Engineering Research, University at Buffalo, Buffalo,

NY.

Lee D and Constantinou MC. (2018). Combined horizontal-vertical seismic isolation system for

high-voltage power transformers: development, testing and validation. Bulletin of Earthquake

Engineering, 16, pp. 4273–4296.

Liel B, Haselton CB, Deierlein GG and Baker JW. (2009). Incorporating modeling uncertainties

in the assessment of seismic collapse risk of buildings. Structural Safety, 31, pp. 197-211.

Lin T, Haselton CB and Baker JW. (2013). Conditional spectrum-based ground motion selection.

Part-I: Hazard consistency for risk-based assessments. Earthquake Engineering and Structural

Dynamics, 42 (12), pp. 1847-1865.

Page 189: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

151

Masroor A and Mosqueda G. (2015). Assessing the collapse probability of base-isolated

buildings considering pounding to moat walls using the FEMA P695 methodology. Earthquake

Spectra, 31(4), pp. 2069-2086.

NIST. (2011). Selecting and scaling earthquake ground motions for performing response-history

analysis, Report NIST GCR 11-917-15. Technical Report, prepared by the NEHRP Consultants

Joint Venture for the National Institute of Standards and Technology: Gaithersburg, Maryland.

Oikonomou K, Constantinou MC, Reinhorn AM and Kempner Jr. L. (2016). “Seismic Isolation of

High Voltage Electrical Power Transformers.” Report MCEER-16-0006, Multidisciplinary Center

for Earthquake Engineering Research, University at Buffalo, Buffalo, NY.

Shinozuka M, Dong X, Chen TC and Jin X. (2007). Seismic performance of electric transmission

network under component failures. Earthquake Engineering and Structural Dynamics, 36 (2), pp.

227-244.

Shumuta Y. (2007). Practical seismic upgrade of electric transmission network under component

failures. Earthquake Engineering and Structural Dynamics, 27(2), pp. 209-226.

Vamvatsikos D and Cornell CA. (2002). Incremental dynamic analysis. Earthquake Engineering

and Structural Dynamics, 31(3), pp. 491–514.

Villaverde R, Pardoen GC and Carnalla S. (2001). Ground motion amplification at flange level of

bushings mounted on electric substation transformers. Earthquake Engineering and Structural

Dynamics, 30(5), pp. 621–32.

Page 190: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on
Page 191: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

153

APPENDIX A

PROCEDURE FOR CONSIDERATION OF SPECTRAL SHAPE EFFECTS AND

RESULTS

A.1 Introduction

The construction of fragility curves is based on incremental dynamic analysis (IDA) in which a

large sample of actual ground motions is used by increasing their intensity until collapse (or

failure by exceeding a certain acceleration level at the bushing) is detected in the analysis model.

This approach accounts only for ground-motion intensity in the assessment of collapse or failure.

It does not account for the spectral shape of the motions. The shape of the uniform hazard

response spectrum for which a design is performed (for example, design of the seismic isolation

system for an electrical transformer; one described by a ground-motion hazard of 2% chance of

exceedance in 50 years or a return period of 2475 years) can be significantly different than the

response spectrum of a real ground motion that is scaled to an equal spectral amplitude at the

period of interest.

The following example from FEMA (2009) and Haselton and Baker (2006) demonstrates the

issue. Figure A-1 shows the acceleration spectrum of a ground motion recorded in the Loma

Prieta earthquake. The Loma Prieta spectrum has a spectral value of 0.9g at 1.0sec period, which

has a 2% chance of exceedance in 50 years. The figure also shows the mean expected spectrum

predicted by an attenuation prediction model (BJF for Boore, Joyner and Fuma) that is consistent

with the event magnitude, distance, and site characteristics associated with this ground motion.

Figure A-1 shows that this ground motion has a much different shape than the mean predicted

spectrum.

Page 192: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

154

Figure A-1. Comparison of observed and predicted response spectra (from FEMA, 2009 and

Haselton and Baker, 2006)

At the1.0sec period, the spectral value of the Loma Prieta record is 1.9 standard deviations above

the predicted mean spectral value from the attenuation relationship so this record is said to have

an “epsilon” ε=1.9 at the 1.0sec period. “Epsilon” is defined as the number of logarithmic

standard deviations between the observed spectral value and the mean spectral acceleration

predicted by a ground-motion prediction model. Parameter epsilon is used to characterize the

spectral shape.

The approach developed by Haselton et al. (2011) for seismic performance evaluation is based

on the use of a general ground-motion set for analysis (the motions in FEMA, 2009) that are

selected independently of the ε values for the particular site of the analyzed structure. The

results on the failure fragility are then corrected to account for the spectral shape. The correction

adjustment is calculated by using values of ε at the considered period (fundamental or effective

period T1 in this study) which are computed for the site of the transformer and the considered

hazard level (2475 year return period) through the disaggregation of the seismic hazard for the

site.

Page 193: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

155

A.2 Procedure for Correction for Spectral Shape Effects

The procedure involves the following steps:

1. Obtain the target epsilon 𝜀0̅(𝑇1), magnitude M, and distance R from de-aggregation of

the ground motion hazard (probabilistic seismic hazard analysis) for the specific location

of the structure (longitude and latitude), site class (average shear-wave velocity Vs30=259

m/sec for class D), spectral period and return period. The return period of 2475 years

(corresponding to a probability of exceedance of 2% in 50 years) is used because the

primary purpose of collapse or failure evaluation is to compute the conditional collapse

or failure probability for a 2% in 50 years ground motion. Information was obtained from

the USGS website (https://earthquake.usgs.gov/hazards/interactive/ accessed on

September 25, 2018) where results of de-aggregation for period of 0.2, 1.0 and 2.0

second were available. Linear interpolation and extrapolation in logarithmic space of the

seismic hazard curves (annual frequency of exceedance vs spectral acceleration) was

used for other values of period (T1=0.13sec for non-isolated transformer, and T1=2.40sec

for isolated transformer).

2. Perform incremental dynamic analysis (IDA) (Vamvatsikos and Cornell, 2002) (for this

study the 40 far-field ground motions of FEMA P695) to obtain the collapse capacity in

terms of the spectral acceleration at fundamental period T1 at failure for each ground

motion, SaCol,j(T1) (j is the identification number for the ground motions; j = 1 to 40).

3. Calculate epsilon at T1, j(T1) for the jth ground motion (j=1 to 40), defined as the number

of standard deviations by which the natural logarithm of Saj(T1), ln[Saj(T1)], differs from

the mean predicted ln[Sa(T1)] for a given magnitude and distance (Baker, 2011):

𝜀𝑗(𝑇1) =ln[𝑆𝑎𝑗(𝑇1)]−𝜇ln 𝑆𝑎(𝑀,𝑅,𝑇1)

𝜎ln 𝑆𝑎(𝑇1)(A-1)

In Equation A-1, lnSa(M,R,T1) is the predicted mean of ln[Sa(T1)] at a given magnitude M,

distance R and period T1, and lnSa(T1) is the predicted standard deviation of ln[Sa(T1)] at

a given M, R and T1. Note that lnSa(M,R,T1) and lnSa(T1) are obtained from any ground

motion prediction model (herein the model of Abrahamson and Silva, 1997 was used,

which was also used by Haselton et al., 2011). Quantity ln[Saj(T1)] in Equation A-1 is the

natural logarithm of the spectral acceleration at T1 of each of 40 original (before scaling)

Page 194: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

156

ground motions.

4. Perform a linear regression analysis between ln[SaCol,j(T1)] and j(T1) and determine

parameters c0 and c1 based on the following equation:

ln[𝑆𝑎Col(𝑇1)] = 𝑐0 + 𝑐1 ∙ 𝜀(𝑇1) (A-2)

5. Replace (T1) with 𝜀0̅(𝑇1) in Equation A-2 and solve to obtain the adjusted mean

collapse capacity, 𝑆�̂�Col,adj(𝑇1):

𝑆�̂�Col,adj(𝑇1) (𝑢𝑛𝑖𝑡𝑠 𝑔) = exp[𝑐0 + 𝑐1 ∙ 𝜀0̅(𝑇1)] (A-3)

The record-to-record dispersion coefficient, RTR, is calculated as the standard deviation

of the natural logarithm of SaColj(T1) of the 40 motions without any further adjustment.

Note that Haselton et al. (2011) described a procedure for further reduction of the

dispersion using the residuals of the regression analysis but the effect was found to be

insignificant in this study and was not included in the presented results.

Values of the target epsilon 𝜀0̅(𝑇1), magnitude M and distance R for return period of 2475 years

obtained by de-aggregation of the seismic hazard are presented in Table A-1 at three

representative sites out of the ten studied.

Table A-1 Values of 𝜀0̅(𝑇1), M and R at three representative sites for 2475 years return period

earthquake

Site Structure 𝜀0̅(𝑇1) M R (km)

Chehalis, WA Non-isolated

4.3 Hz 1.27 7.75 53.92

7.7 Hz 1.22 7.78 53.24

11.3 Hz 1.19 7.82 53.01

Isolated 0.72 8.78 66.48

Loma Linda, CA Non-isolated

4.3 Hz 0.74 7.38 6.88

7.7 Hz 0.63 7.43 6.65

11.3 Hz 0.58 7.48 6.43

Isolated 1.10 8.01 3.61

Troutdale, OR Non-isolated

4.3 Hz 1.11 7.03 47.74

7.7 Hz 1.07 7.02 46.98

11.3 Hz 1.05 7.04 47.25

Isolated 0.94 8.43 100.45

Page 195: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

157

The ground motion prediction model of Abrahamson and Silva (1997) was used to construct the

median 5%-damped response spectra for the isolated and non-isolated transformers. The

spectra are presented in Figures A-2 to A-4 together with the spectra of the 44 ground motions

used in the IDA for three of the considered sites. We used program OpenSHA (Field et al., 2003)

to construct the spectra based on the Abrahamson and Silva prediction model. The same model

also predicted the standard deviation of the 5%-damped response spectrum. It is presented in

Figures A-5 to A-7. Isolated and non-isolated transformers have the same standard deviation at

each of the three locations.

Figure A-2 Response spectra of FEMA far-field motions and predicted median spectra at

Chehalis, WA location

Figure A-3 Response spectra of FEMA far-field motions and predicted median spectra at Loma

Linda, CA location

0.0

0.5

1.0

1.5

2.0

2.5

3.0

0.0 0.5 1.0 1.5 2.0 2.5 3.0 3.5 4.0 4.5 5.0

0.0

0.5

1.0

1.5

2.0

2.5

3.0

0.0 0.5 1.0 1.5 2.0 2.5 3.0 3.5 4.0 4.5 5.0

Period (second)

Predicted median spectrum for non-isolated transformer (fAI=7.7Hz)

5%-damped spectra of 40 far-field ground motions in FEMA (2009)

Sp

ectr

al

acc

eler

ati

on

(g

)

Predicted median spectrum for isolated transformer

Predicted median spectrum for non-isolated transformer (fAI=4.3Hz)

Predicted median spectrum for non-isolated transformer (fAI=11.3Hz)

Period (second)

Predicted median spectrum for non-isolated transformer (fAI=7.7Hz)

5%-damped spectra of 40 far-field ground motions in FEMA (2009)

Sp

ectr

al

acc

eler

ati

on

(g)

Predicted median spectrum for isolated transformer

Predicted median spectrum for non-isolated transformer (fAI=4.3Hz)

Predicted median spectrum for non-isolated transformer (fAI=11.3Hz)

Page 196: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

158

Figure A-4 Response spectra of FEMA far-field motions and predicted median spectra at

Troutdale, OR location

Figure A-5 Standard deviation of natural logarithm of spectral acceleration at Chehalis, WA

Figure A-6 Standard deviation of natural logarithm of spectral acceleration at Loma Linda, CA

0.0

0.5

1.0

1.5

2.0

2.5

3.0

0.0 0.5 1.0 1.5 2.0 2.5 3.0 3.5 4.0 4.5 5.0

0

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

0.0 0.5 1.0 1.5 2.0 2.5 3.0 3.5 4.0 4.5 5.0

0

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

0.0 0.5 1.0 1.5 2.0 2.5 3.0 3.5 4.0 4.5 5.0

Predicted median spectrum for non-isolated transformer (fAI=7.7Hz)

Predicted median spectrum for isolated transformer

Predicted median spectrum for non-isolated transformer (fAI=4.3Hz)

Predicted median spectrum for non-isolated transformer (fAI=11.3Hz)

Predicted median spectrum for non-isolated transformer (fAI=7.7Hz)

Predicted median spectrum for isolated transformer

Predicted median spectrum for non-isolated transformer (fAI=4.3Hz)

Predicted median spectrum for non-isolated transformer (fAI=11.3Hz)

lnSa

(T1

)

Period (second)

Period (second)

Predicted median spectrum for non-isolated transformer (fAI=7.7Hz)

5%-damped spectra of 40 far-field ground motions in FEMA (2009)

Sp

ectr

al

acc

eler

ati

on

(g

)

Predicted median spectrum for isolated transformer

Predicted median spectrum for non-isolated transformer (fAI=4.3Hz)

Predicted median spectrum for non-isolated transformer (fAI=11.3Hz)

lnSa

(T1

)

Period (second)

Page 197: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

159

Figure A-7 Standard deviation of natural logarithm of spectral acceleration at Troutdale, OR

The values of j(T1) for each of the 40 ground motions (j=1 to 40) for the isolated and

non-isolated structures were then calculated by use of Equation A-1 and are presented in Figures

A-8 to A-10 for the case of the isolated and non-isolated transformers at the three sites. Values

of epsilon are higher for the non-isolated transformer.

Figure A-8 Calculated values of j(T1) for the 40 ground motions used in analysis for Chehalis,

WA location

Figure A-9 Calculated values of j(T1) for the 40 ground motions used in analysis for Loma

Linda, CA location

0

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

0.0 0.5 1.0 1.5 2.0 2.5 3.0 3.5 4.0 4.5 5.0

-2

-1

0

1

2

3

4

5

6

0 5 10 15 20 25 30 35 40

-4

-3

-2

-1

0

1

2

0 5 10 15 20 25 30 35 40

Ground motion

j(T

1)

Predicted median spectrum for non-isolated transformer (fAI=7.7Hz)

Predicted median spectrum for isolated transformer

Predicted median spectrum for non-isolated transformer (fAI=4.3Hz)

Predicted median spectrum for non-isolated transformer (fAI=11.3Hz)

non-isolated transformer (fAI=7.7Hz) non-isolated transformer (fAI=4.3Hz)

non-isolated transformer (fAI=11.3Hz) Isolated transformer

lnSa

(T1

)

Period (second)

Ground motion

j(T

1)

non-isolated transformer (fAI=7.7Hz) non-isolated transformer (fAI=4.3Hz)

non-isolated transformer (fAI=11.3Hz) Isolated transformer

Page 198: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

160

Figure A-10 Calculated values of j(T1) for the 40 ground motions used in analysis for Troutdale,

OR location

Based on the results of IDA and the information on j(T1) in Figures A-8 to A-10, linear

regression analysis was performed to establish the relationship between the ln[SaCol,j(T1)] and

j(T1). Figures A-11 to A-46 present the relationship between ln[SaCol,j(T1)] and j(T1) for the

non-isolated transformer and the isolated transformers at the three representative sites. The

figures also present the fitted linear regression model of Equation A-2.

(a) 1g limit (c0=-0.372, c1=0.032) (b) 2g limit (c0=-0.322, c1=0.032)

Figure A-11 Relationship between ln[SaCol,j(T1)] and j(T1) of non-isolated transformer with

bushing of 7.7Hz as-installed frequency at Chehalis, WA

-2

-1

0

1

2

3

4

5

6

0 5 10 15 20 25 30 35 40

-0.8

-0.6

-0.4

-0.2

0

0.2

0.4

0.6

0 1 2 3 4 5

-0.2

0

0.2

0.4

0.6

0.8

1

1.2

1.4

0 1 2 3 4 5

ln[Sa

CO

L(T

1)]

(T1)

ln[Sa

CO

L(T

1)]

(T1)

j(T

1)

Ground motion

non-isolated transformer (fAI=7.7Hz) non-isolated transformer (fAI=4.3Hz)

non-isolated transformer (fAI=11.3Hz) Isolated transformer

Page 199: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

161

(a) 1g limit (c0=-0.3716, c1=0.0318) (b) 2g limit (c0=-1.230, c1=0.336)

Figure A-12 Relationship between ln[SaCol,j(T1)] and j(T1) of horizontally isolated transformer

(DCapacity=17.7inch, lower bound) with as-installed bushing frequency of 7.7Hz at Chehalis, WA

(a) 1g limit (c0=-1.053, c1=0.2427) (b) 2g limit (c0=-0.912, c1=0.196)

Figure A-13 Relationship between ln[SaCol,j(T1)] and j(T1) of horizontally-vertically isolated

without rocking transformer (DCapacity=17.7inch, lower bound) with as-installed bushing

frequency of 7.7Hz at Chehalis, WA

-3.5

-3.0

-2.5

-2.0

-1.5

-1.0

-0.5

0.0

-2 -1 0 1 2 3

-3

-2.5

-2

-1.5

-1

-0.5

0

-2 -1 0 1 2 3

-2.5

-2.0

-1.5

-1.0

-0.5

0.0

-2 -1 0 1 2 3

-1.8

-1.6

-1.4

-1.2

-1

-0.8

-0.6

-0.4

-0.2

0

-2 -1 0 1 2 3

ln[Sa

CO

L(T

1)]

(T1)

ln[Sa

CO

L(T

1)]

(T1)

ln[Sa

CO

L(T

1)]

(T1)

ln[Sa

CO

L(T

1)]

(T1)

Page 200: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

162

(a) 1g limit (c0=-1.085, c1=0.273) (b) 2g limit (c0=-0.806, c1=0.192)

Figure A-14 Relationship between ln[SaCol,j(T1)] and j(T1) of horizontally-vertically isolated

with rocking transformer (DCapacity=17.7inch, lower bound) with as-installed bushing frequency

of 7.7Hz at Chehalis, WA

(a) 1g limit (c0=-0.010, c1=0.025) (b) 2g limit (c0=0.704, c1=0.025)

Figure A-15 Relationship between ln[SaCol,j(T1)] and j(T1) of non-isolated transformer with

bushing of 4.3Hz as-installed frequency at Chehalis, WA

-2.5

-2

-1.5

-1

-0.5

0

-2 -1 0 1 2 3

-1.6

-1.4

-1.2

-1

-0.8

-0.6

-0.4

-0.2

0

-2 -1 0 1 2 3

-0.2

-0.1

0

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0 1 2 3 4 5

0

0.2

0.4

0.6

0.8

1

1.2

1.4

1.6

0 1 2 3 4 5

ln[Sa

CO

L(T

1)]

(T1)

ln[Sa

CO

L(T

1)]

(T1)

ln[Sa

CO

L(T

1)]

(T1)

ln[Sa

CO

L(T

1)]

(T1)

Page 201: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

163

(a) 1g limit (c0=-1.331, c1=0.409) (b) 2g limit (c0=-1.193, c1=0.353)

Figure A-16 Relationship between ln[SaCol,j(T1)] and j(T1) of horizontally isolated transformer

(DCapacity=17.7inch, lower bound) with as-installed bushing frequency of 4.3Hz at Chehalis, WA

(a) 1g limit (c0=-0.962, c1=0.220) (b) 2g limit (c0=-0.852, c1=0.185)

Figure A-17 Relationship between ln[SaCol,j(T1)] and j(T1) of horizontally-vertically isolated

without rocking transformer (DCapacity=17.7inch, lower bound) with as-installed bushing

frequency of 4.3Hz at Chehalis, WA

-3

-2.5

-2

-1.5

-1

-0.5

0

-2 -1 0 1 2 3

-3

-2.5

-2

-1.5

-1

-0.5

0

-2 -1 0 1 2 3

-2

-1.8

-1.6

-1.4

-1.2

-1

-0.8

-0.6

-0.4

-0.2

0

-2 -1 0 1 2 3

-1.8

-1.6

-1.4

-1.2

-1

-0.8

-0.6

-0.4

-0.2

0

-2 -1 0 1 2 3

ln[Sa

CO

L(T

1)]

(T1)

ln[Sa

CO

L(T

1)]

(T1)

ln[Sa

CO

L(T

1)]

(T1) ln

[Sa

CO

L(T

1)]

(T1)

Page 202: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

164

(a) 1g limit (c0=-1.457, c1=0.478) (b) 2g limit (c0=-0.807, c1=0.194)

Figure A-18 Relationship between ln[SaCol,j(T1)] and j(T1) of horizontally-vertically isolated

with rocking transformer (DCapacity=17.7inch, lower bound) with as-installed bushing frequency

of 4.3Hz at Chehalis, WA

(a) 1g limit (c0=-0.136, c1=0.079) (b) 2g limit (c0=0.557, c1=0.079)

Figure A-19 Relationship between ln[SaCol,j(T1)] and j(T1) of non-isolated transformer with

bushing of 11.3Hz as-installed frequency at Chehalis, WA

-3.5

-3

-2.5

-2

-1.5

-1

-0.5

0

-2 -1 0 1 2 3

-1.8

-1.6

-1.4

-1.2

-1

-0.8

-0.6

-0.4

-0.2

0

-2 -1 0 1 2 3

-0.8

-0.6

-0.4

-0.2

0

0.2

0.4

0.6

0.8

1

0 2 4 6

0

0.2

0.4

0.6

0.8

1

1.2

1.4

1.6

1.8

0 2 4 6

ln[Sa

CO

L(T

1)]

(T1)

ln[Sa

CO

L(T

1)]

(T1)

ln[Sa

CO

L(T

1)]

(T1)

ln[Sa

CO

L(T

1)]

(T1)

Page 203: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

165

(a) 1g limit (c0=-1.486, c1=0.461) (b) 2g limit (c0=-1.330, c1=0.420)

Figure A-20 Relationship between ln[SaCol,j(T1)] and j(T1) of horizontally isolated transformer

(DCapacity=17.7inch, lower bound) with as-installed bushing frequency of 11.3Hz at Chehalis, WA

(a) 1g limit (c0=-1.006, c1=0.220) (b) 2g limit (c0=-0.947, c1=0.209)

Figure A-21 Relationship between ln[SaCol,j(T1)] and j(T1) of horizontally-vertically isolated

without rocking transformer (DCapacity=17.7inch, lower bound) with as-installed bushing

frequency of 11.3Hz at Chehalis, WA

-3.5

-3

-2.5

-2

-1.5

-1

-0.5

0

-2 -1 0 1 2 3

-3

-2.5

-2

-1.5

-1

-0.5

0

-2 -1 0 1 2 3

-2

-1.8

-1.6

-1.4

-1.2

-1

-0.8

-0.6

-0.4

-0.2

0

-2 -1 0 1 2 3

-1.8

-1.6

-1.4

-1.2

-1

-0.8

-0.6

-0.4

-0.2

0

-2 -1 0 1 2 3

ln[Sa

CO

L(T

1)]

(T1)

ln[Sa

CO

L(T

1)]

(T1)

ln[Sa

CO

L(T

1)]

(T1)

ln[Sa

CO

L(T

1)]

(T1)

Page 204: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

166

(a) 1g limit (c0=-0.816, c1=0.195) (b) 2g limit (c0=-0.754, c1=0.177)

Figure A-22 Relationship between ln[SaCol,j(T1)] and j(T1) of horizontally-vertically isolated

with rocking transformer (DCapacity=17.7inch, lower bound) with as-installed bushing frequency

of 11.3Hz at Chehalis, WA

(a) 1g limit (c0=-0.265, c1=0.032) (b) 2g limit (c0=0.428, c1=0.032)

Figure A-23 Relationship between ln[SaCol,j(T1)] and j(T1) of non-isolated transformer with

bushing of 7.7Hz as-installed frequency at Loma Linda, CA

-1.6

-1.4

-1.2

-1

-0.8

-0.6

-0.4

-0.2

0

-2 -1 0 1 2 3

-1.6

-1.4

-1.2

-1

-0.8

-0.6

-0.4

-0.2

0

-2 -1 0 1 2 3

-1.0

-0.8

-0.6

-0.4

-0.2

0.0

0.2

0.4

0.6

0.8

-3 -2 -1 0 1 2

-0.2

0.0

0.2

0.4

0.6

0.8

1.0

1.2

1.4

-3 -2 -1 0 1 2

ln[Sa

CO

L(T

1)]

(T1)

ln[Sa

CO

L(T

1)]

(T1)

ln[Sa

CO

L(T

1)]

(T1)

ln[Sa

CO

L(T

1)]

(T1)

Page 205: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

167

(a) 1g limit (c0=-0.781, c1=0.440) (b) 2g limit (c0=-0.632, c1=0.337)

Figure A-24 Relationship between ln[SaCol,j(T1)] and j(T1) of horizontally isolated transformer

(DCapacity=17.7inch, lower bound) with as-installed bushing frequency of 7.7Hz at Loma Linda,

CA

(a) 1g limit (c0=-0.616, c1=0.243) (b) 2g limit (c0=-0.560, c1=0.196)

Figure A-25 Relationship between ln[SaCol,j(T1)] and j(T1) of horizontally-vertically isolated

without rocking transformer (DCapacity=17.7inch, lower bound) with as-installed bushing

frequency of 7.7Hz at Loma Linda, CA

-4.0

-3.5

-3.0

-2.5

-2.0

-1.5

-1.0

-0.5

0.0

-4 -3 -2 -1 0 1 2

-3.0

-2.5

-2.0

-1.5

-1.0

-0.5

0.0

-4 -3 -2 -1 0 1 2

-2.5

-2.0

-1.5

-1.0

-0.5

0.0

-4 -3 -2 -1 0 1 2

-1.8

-1.6

-1.4

-1.2

-1.0

-0.8

-0.6

-0.4

-0.2

0.0

-4 -3 -2 -1 0 1 2

ln[Sa

CO

L(T

1)]

(T1)

ln[Sa

CO

L(T

1)]

(T1)

ln[Sa

CO

L(T

1)]

(T1)

ln[Sa

CO

L(T

1)]

(T1)

Page 206: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

168

(a) 1g limit (c0=-0.593, c1=0.274) (b) 2g limit (c0=-0.461, c1=0.192)

Figure A-26 Relationship between ln[SaCol,j(T1)] and j(T1) of horizontally-vertically isolated

with rocking transformer (DCapacity=17.7inch, lower bound) with as-installed bushing frequency

of 7.7Hz at Loma Linda, CA

(a) 1g limit (c0=-0.085, c1=0.025) (b) 2g limit (c0=0.779, c1=0.025)

Figure A-27 Relationship between ln[SaCol,j(T1)] and j(T1) of non-isolated transformer with

bushing of 4.3Hz as-installed frequency at Loma Linda, CA

-2.5

-2.0

-1.5

-1.0

-0.5

0.0

-4 -3 -2 -1 0 1 2

-1.6

-1.4

-1.2

-1.0

-0.8

-0.6

-0.4

-0.2

0.0

-4 -3 -2 -1 0 1 2

-0.2

-0.1

0.0

0.1

0.2

0.3

0.4

0.5

0.6

0.7

-3 -2 -1 0 1 2

0.0

0.2

0.4

0.6

0.8

1.0

1.2

1.4

1.6

-3 -2 -1 0 1 2

ln[Sa

CO

L(T

1)]

(T1)

ln[Sa

CO

L(T

1)]

(T1)

ln[Sa

CO

L(T

1)]

(T1)

ln[Sa

CO

L(T

1)]

(T1)

Page 207: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

169

(a) 1g limit (c0=-0.597, c1=0.410) (b) 2g limit (c0=-0.556, c1=0.354)

Figure A-28 Relationship between ln[SaCol,j(T1)] and j(T1) of horizontally isolated transformer

(DCapacity=17.7inch, lower bound) with as-installed bushing frequency of 4.3Hz at Loma Linda,

CA

(a) 1g limit (c0=-0.566, c1=0.221) (b) 2g limit (c0=-0.519, c1=0.185)

Figure A-29 Relationship between ln[SaCol,j(T1)] and j(T1) of horizontally-vertically isolated

without rocking transformer (DCapacity=17.7inch, lower bound) with as-installed bushing

frequency of 4.3Hz at Loma Linda, CA

-3.0

-2.5

-2.0

-1.5

-1.0

-0.5

0.0

-4 -3 -2 -1 0 1 2

-3.0

-2.5

-2.0

-1.5

-1.0

-0.5

0.0

-4 -3 -2 -1 0 1 2

-2.0

-1.8

-1.6

-1.4

-1.2

-1.0

-0.8

-0.6

-0.4

-0.2

0.0

-4 -3 -2 -1 0 1 2

-1.8

-1.6

-1.4

-1.2

-1.0

-0.8

-0.6

-0.4

-0.2

0.0

-4 -3 -2 -1 0 1 2

ln[Sa

CO

L(T

1)]

(T1)

ln[Sa

CO

L(T

1)]

(T1)

ln[Sa

CO

L(T

1)]

(T1)

ln[Sa

CO

L(T

1)]

(T1)

Page 208: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

170

(a) 1g limit (c0=-0.596, c1=0.479) (b) 2g limit (c0=-0.459, c1=0.194)

Figure A-30 Relationship between ln[SaCol,j(T1)] and j(T1) of horizontally-vertically isolated

with rocking transformer (DCapacity=17.7inch, lower bound) with as-installed bushing frequency

of 4.3Hz at Loma Linda, CA

(a) 1g limit (c0=0.097, c1=0.052) (b) 2g limit (c0=0.790, c1=0.052)

Figure A-31 Relationship between ln[SaCol,j(T1)] and j(T1) of non-isolated transformer with

bushing of 11.3Hz as-installed frequency at Loma Linda, CA

-3.5

-3.0

-2.5

-2.0

-1.5

-1.0

-0.5

0.0

-4 -3 -2 -1 0 1 2

-1.8

-1.6

-1.4

-1.2

-1.0

-0.8

-0.6

-0.4

-0.2

0.0

-4 -3 -2 -1 0 1 2

-0.8

-0.6

-0.4

-0.2

0.0

0.2

0.4

0.6

0.8

1.0

-4 -3 -2 -1 0 1 2

0.0

0.2

0.4

0.6

0.8

1.0

1.2

1.4

1.6

1.8

-4 -3 -2 -1 0 1 2

ln[Sa

CO

L(T

1)]

(T1)

ln[Sa

CO

L(T

1)]

(T1)

ln[Sa

CO

L(T

1)]

(T1)

ln[Sa

CO

L(T

1)]

(T1)

Page 209: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

171

(a) 1g limit (c0=-0.655, c1=0.463) (b) 2g limit (c0=-0.573, c1=0.422)

Figure A-32 Relationship between ln[SaCol,j(T1)] and j(T1) of horizontally isolated transformer

(DCapacity=17.7inch, lower bound) with as-installed bushing frequency of 11.3Hz at Loma Linda,

CA

(a) 1g limit (c0=-0.610, c1=0.220) (b) 2g limit (c0=-0.571, c1=0.209)

Figure A-33 Relationship between ln[SaCol,j(T1)] and j(T1) of horizontally-vertically isolated

without rocking transformer (DCapacity=17.7inch, lower bound) with as-installed bushing

frequency of 11.3Hz at Loma Linda, CA

-3.5

-3.0

-2.5

-2.0

-1.5

-1.0

-0.5

0.0

-4 -3 -2 -1 0 1 2

-3.0

-2.5

-2.0

-1.5

-1.0

-0.5

0.0

-4 -3 -2 -1 0 1 2

-2.0

-1.8

-1.6

-1.4

-1.2

-1.0

-0.8

-0.6

-0.4

-0.2

0.0

-4 -3 -2 -1 0 1 2

-1.8

-1.6

-1.4

-1.2

-1.0

-0.8

-0.6

-0.4

-0.2

0.0

-4 -3 -2 -1 0 1 2

ln[Sa

CO

L(T

1)]

(T1)

ln[Sa

CO

L(T

1)]

(T1)

ln[Sa

CO

L(T

1)]

(T1)

ln[Sa

CO

L(T

1)]

(T1)

Page 210: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

172

(a) 1g limit (c0=-0.465, c1=0.196) (b) 2g limit (c0=-0.436, c1=0.177)

Figure A-34 Relationship between ln[SaCol,j(T1)] and j(T1) of horizontally-vertically isolated

with rocking transformer (DCapacity=17.7inch, lower bound) with as-installed bushing frequency

of 11.3Hz at Loma Linda, CA

(a) 1g limit (c0=-0.389, c1=0.032) (b) 2g limit (c0=0.305, c1=0.032)

Figure A-35 Relationship between ln[SaCol,j(T1)] and j(T1) of non-isolated transformer with

bushing of 7.7Hz as-installed frequency at Troutdale, OR

-1.6

-1.4

-1.2

-1.0

-0.8

-0.6

-0.4

-0.2

0.0

-4 -3 -2 -1 0 1 2

-1.6

-1.4

-1.2

-1.0

-0.8

-0.6

-0.4

-0.2

0.0

-4 -3 -2 -1 0 1 2

-1

-0.8

-0.6

-0.4

-0.2

0

0.2

0.4

0.6

0.8

0 2 4 6

-0.2

0

0.2

0.4

0.6

0.8

1

1.2

1.4

0 2 4 6

ln[Sa

CO

L(T

1)]

(T1)

ln[Sa

CO

L(T

1)]

(T1)

ln[Sa

CO

L(T

1)]

(T1)

ln[Sa

CO

L(T

1)]

(T1)

Page 211: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

173

(a) 1g limit (c0=-1.695, c1=0.440) (b) 2g limit (c0=-1.330, c1=0.337)

Figure A-36 Relationship between ln[SaCol,j(T1)] and j(T1) of horizontally isolated transformer

(DCapacity=17.7inch, lower bound) with as-installed bushing frequency of 7.7Hz at Troutdale, OR

(a) 1g limit (c0=-1.120, c1=0.243) (b) 2g limit (c0=-0.966, c1=0.196)

Figure A-37 Relationship between ln[SaCol,j(T1)] and j(T1) of horizontally-vertically isolated

without rocking transformer (DCapacity=17.7inch, lower bound) with as-installed bushing

frequency of 7.7Hz at Troutdale, OR

-4

-3.5

-3

-2.5

-2

-1.5

-1

-0.5

0

-2 -1 0 1 2 3 4

-3

-2.5

-2

-1.5

-1

-0.5

0

-2 -1 0 1 2 3 4

-2.5

-2

-1.5

-1

-0.5

0

-2 -1 0 1 2 3 4

-1.8

-1.6

-1.4

-1.2

-1

-0.8

-0.6

-0.4

-0.2

0

-2 -1 0 1 2 3 4

ln[Sa

CO

L(T

1)]

(T1)

ln[Sa

CO

L(T

1)]

(T1)

ln[Sa

CO

L(T

1)]

(T1)

ln[Sa

CO

L(T

1)]

(T1)

Page 212: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

174

(a) 1g limit (c0=-1.161, c1=0.274) (b) 2g limit (c0=-0.859, c1=0.192)

Figure A-38 Relationship between ln[SaCol,j(T1)] and j(T1) of horizontally-vertically isolated

with rocking transformer (DCapacity=17.7inch, lower bound) with as-installed bushing frequency

of 7.7Hz at Troutdale, OR

(a) 1g limit (c0=-0.005, c1=0.025) (b) 2g limit (c0=0.688, c1=0.025)

Figure A-39 Relationship between ln[SaCol,j(T1)] and j(T1) of non-isolated transformer with

bushing of 4.3Hz as-installed frequency at Troutdale, OR

-2.5

-2

-1.5

-1

-0.5

0

-2 -1 0 1 2 3 4

-1.6

-1.4

-1.2

-1

-0.8

-0.6

-0.4

-0.2

0

-2 -1 0 1 2 3 4

-0.2

-0.1

0

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0 1 2 3 4 5

0

0.2

0.4

0.6

0.8

1

1.2

1.4

1.6

0 1 2 3 4 5

ln[Sa

CO

L(T

1)]

(T1)

ln[Sa

CO

L(T

1)]

(T1)

ln[Sa

CO

L(T

1)]

(T1)

ln[Sa

CO

L(T

1)]

(T1)

Page 213: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

175

(a) 1g limit (c0=-1.448, c1=0.410) (b) 2g limit (c0=-1.291, c1=0.354)

Figure A-40 Relationship between ln[SaCol,j(T1)] and j(T1) of horizontally isolated transformer

(DCapacity=17.7inch, lower bound) with as-installed bushing frequency of 4.3Hz at Troutdale, OR

(a) 1g limit (c0=-1.023, c1=0.221) (b) 2g limit (c0=-0.903, c1=0.185)

Figure A-41 Relationship between ln[SaCol,j(T1)] and j(T1) of horizontally-vertically isolated

without rocking transformer (DCapacity=17.7inch, lower bound) with as-installed bushing

frequency of 4.3Hz at Troutdale, OR

-3

-2.5

-2

-1.5

-1

-0.5

0

-2 -1 0 1 2 3 4

-3

-2.5

-2

-1.5

-1

-0.5

0

-2 -1 0 1 2 3 4

-2

-1.8

-1.6

-1.4

-1.2

-1

-0.8

-0.6

-0.4

-0.2

0

-2 -1 0 1 2 3 4

-1.8

-1.6

-1.4

-1.2

-1

-0.8

-0.6

-0.4

-0.2

0

-2 -1 0 1 2 3 4

ln[Sa

CO

L(T

1)]

(T1)

ln[Sa

CO

L(T

1)]

(T1)

ln[Sa

CO

L(T

1)]

(T1)

ln[Sa

CO

L(T

1)]

(T1)

Page 214: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

176

(a) 1g limit (c0=-1.589, c1=0.479) (b) 2g limit (c0=-0.861, c1=0.194)

Figure A-42 Relationship between ln[SaCol,j(T1)] and j(T1) of horizontally-vertically isolated

with rocking transformer (DCapacity=17.7inch, lower bound) with as-installed bushing frequency

of 4.3Hz at Troutdale, OR

(a) 1g limit (c0=-0.109, c1=0.052) (b) 2g limit (c0=0.584, c1=0.052)

Figure A-43 Relationship between ln[SaCol,j(T1)] and j(T1) of non-isolated transformer with

bushing of 11.3Hz as-installed frequency at Troutdale, OR

-3.5

-3

-2.5

-2

-1.5

-1

-0.5

0

-2 -1 0 1 2 3 4

-1.8

-1.6

-1.4

-1.2

-1

-0.8

-0.6

-0.4

-0.2

0

-2 -1 0 1 2 3 4

-0.8

-0.6

-0.4

-0.2

0

0.2

0.4

0.6

0.8

1

0 2 4 6

0

0.2

0.4

0.6

0.8

1

1.2

1.4

1.6

1.8

0 2 4 6

ln[Sa

CO

L(T

1)]

(T1)

ln[Sa

CO

L(T

1)]

(T1)

ln[Sa

CO

L(T

1)]

(T1)

ln[Sa

CO

L(T

1)]

(T1)

Page 215: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

177

(a) 1g limit (c0=-1.615, c1=0.463) (b) 2g limit (c0=-1.447, c1=0.422)

Figure A-44 Relationship between ln[SaCol,j(T1)] and j(T1) of horizontally isolated transformer

(DCapacity=17.7inch, lower bound) with as-installed bushing frequency of 11.3Hz at Troutdale, OR

(a) 1g limit (c0=-1.067, c1=0.220) (b) 2g limit (c0=-1.005, c1=0.209)

Figure A-45 Relationship between ln[SaCol,j(T1)] and j(T1) of horizontally-vertically isolated

without rocking transformer (DCapacity=17.7inch, lower bound) with as-installed bushing

frequency of 11.3Hz at Troutdale, OR

-3.5

-3

-2.5

-2

-1.5

-1

-0.5

0

-2 -1 0 1 2 3 4

-3

-2.5

-2

-1.5

-1

-0.5

0

-2 -1 0 1 2 3 4

-2

-1.8

-1.6

-1.4

-1.2

-1

-0.8

-0.6

-0.4

-0.2

0

-2 -1 0 1 2 3 4

-1.8

-1.6

-1.4

-1.2

-1

-0.8

-0.6

-0.4

-0.2

0

-2 -1 0 1 2 3 4

ln[Sa

CO

L(T

1)]

(T1)

ln[Sa

CO

L(T

1)]

(T1)

ln[Sa

CO

L(T

1)]

(T1)

ln[Sa

CO

L(T

1)]

(T1)

Page 216: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

178

(a) 1g limit (c0=-0.870, c1=0.196) (b) 2g limit (c0=-0.803, c1=0.177)

Figure A-46 Relationship between ln[SaCol,j(T1)] and j(T1) of horizontally-vertically isolated

with rocking transformer (DCapacity=17.7inch, lower bound) with as-installed bushing frequency

of 11.3Hz at Troutdale, OR

-1.6

-1.4

-1.2

-1

-0.8

-0.6

-0.4

-0.2

0

-2 -1 0 1 2 3 4

-1.6

-1.4

-1.2

-1

-0.8

-0.6

-0.4

-0.2

0

-2 -1 0 1 2 3 4

ln[Sa

CO

L(T

1)]

(T1)

ln[Sa

CO

L(T

1)]

(T1)

Page 217: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

179

MCEER Technical Reports

MCEER publishes technical reports on a variety of subjects written by authors funded through MCEER. These reports can be downloaded from the MCEER website at http://www.buffalo.edu/mceer. They can also be requested through NTIS, P.O. Box 1425, Springfield, Virginia 22151. NTIS accession numbers are shown in parenthesis, if available.

NCEER-87-0001 "First-Year Program in Research, Education and Technology Transfer," 3/5/87, (PB88-134275, A04, MF-A01).

NCEER-87-0002 "Experimental Evaluation of Instantaneous Optimal Algorithms for Structural Control," by R.C. Lin, T.T. Soong and A.M. Reinhorn, 4/20/87, (PB88-134341, A04, MF-A01).

NCEER-87-0003 "Experimentation Using the Earthquake Simulation Facilities at University at Buffalo," by A.M. Reinhorn and R.L. Ketter, not available.

NCEER-87-0004 "The System Characteristics and Performance of a Shaking Table," by J.S. Hwang, K.C. Chang and G.C. Lee, 6/1/87, (PB88-134259, A03, MF-A01). This report is available only through NTIS (see address given above).

NCEER-87-0005 "A Finite Element Formulation for Nonlinear Viscoplastic Material Using a Q Model," by O. Gyebi and G. Dasgupta, 11/2/87, (PB88-213764, A08, MF-A01).

NCEER-87-0006 "Symbolic Manipulation Program (SMP) - Algebraic Codes for Two and Three Dimensional Finite Element Formulations," by X. Lee and G. Dasgupta, 11/9/87, (PB88-218522, A05, MF-A01).

NCEER-87-0007 "Instantaneous Optimal Control Laws for Tall Buildings Under Seismic Excitations," by J.N. Yang, A. Akbarpour and P. Ghaemmaghami, 6/10/87, (PB88-134333, A06, MF-A01). This report is only available through NTIS (see address given above).

NCEER-87-0008 "IDARC: Inelastic Damage Analysis of Reinforced Concrete Frame - Shear-Wall Structures," by Y.J. Park, A.M. Reinhorn and S.K. Kunnath, 7/20/87, (PB88-134325, A09, MF-A01). This report is only availablethrough NTIS (see address given above).

NCEER-87-0009 "Liquefaction Potential for New York State: A Preliminary Report on Sites in Manhattan and Buffalo," by M. Budhu, V. Vijayakumar, R.F. Giese and L. Baumgras, 8/31/87, (PB88-163704, A03, MF-A01). Thisreport is available only through NTIS (see address given above).

NCEER-87-0010 "Vertical and Torsional Vibration of Foundations in Inhomogeneous Media," by A.S. Veletsos and K.W. Dotson, 6/1/87, (PB88-134291, A03, MF-A01). This report is only available through NTIS (see address given above).

NCEER-87-0011 "Seismic Probabilistic Risk Assessment and Seismic Margins Studies for Nuclear Power Plants," by Howard H.M. Hwang, 6/15/87, (PB88-134267, A03, MF-A01). This report is only available through NTIS (seeaddress given above).

NCEER-87-0012 "Parametric Studies of Frequency Response of Secondary Systems Under Ground-Acceleration Excitations," by Y. Yong and Y.K. Lin, 6/10/87, (PB88-134309, A03, MF-A01). This report is only available through NTIS (see address given above).

NCEER-87-0013 "Frequency Response of Secondary Systems Under Seismic Excitation," by J.A. HoLung, J. Cai and Y.K. Lin, 7/31/87, (PB88-134317, A05, MF-A01). This report is only available through NTIS (see address given above).

NCEER-87-0014 "Modelling Earthquake Ground Motions in Seismically Active Regions Using Parametric Time Series Methods," by G.W. Ellis and A.S. Cakmak, 8/25/87, (PB88-134283, A08, MF-A01). This report is only available through NTIS (see address given above).

NCEER-87-0015 "Detection and Assessment of Seismic Structural Damage," by E. DiPasquale and A.S. Cakmak, 8/25/87, (PB88-163712, A05, MF-A01). This report is only available through NTIS (see address given above).

Page 218: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

180

NCEER-87-0016 "Pipeline Experiment at Parkfield, California," by J. Isenberg and E. Richardson, 9/15/87, (PB88-163720, A03, MF-A01). This report is available only through NTIS (see address given above).

NCEER-87-0017 "Digital Simulation of Seismic Ground Motion," by M. Shinozuka, G. Deodatis and T. Harada, 8/31/87, (PB88-155197, A04, MF-A01). This report is available only through NTIS (see address given above).

NCEER-87-0018 "Practical Considerations for Structural Control: System Uncertainty, System Time Delay and Truncation of Small Control Forces," J.N. Yang and A. Akbarpour, 8/10/87, (PB88-163738, A08, MF-A01). This report is only available through NTIS (see address given above).

NCEER-87-0019 "Modal Analysis of Nonclassically Damped Structural Systems Using Canonical Transformation," by J.N. Yang, S. Sarkani and F.X. Long, 9/27/87, (PB88-187851, A04, MF-A01).

NCEER-87-0020 "A Nonstationary Solution in Random Vibration Theory," by J.R. Red-Horse and P.D. Spanos, 11/3/87, (PB88-163746, A03, MF-A01).

NCEER-87-0021 "Horizontal Impedances for Radially Inhomogeneous Viscoelastic Soil Layers," by A.S. Veletsos and K.W. Dotson, 10/15/87, (PB88-150859, A04, MF-A01).

NCEER-87-0022 "Seismic Damage Assessment of Reinforced Concrete Members," by Y.S. Chung, C. Meyer and M. Shinozuka, 10/9/87, (PB88-150867, A05, MF-A01). This report is available only through NTIS (see address given above).

NCEER-87-0023 "Active Structural Control in Civil Engineering," by T.T. Soong, 11/11/87, (PB88-187778, A03, MF-A01).

NCEER-87-0024 "Vertical and Torsional Impedances for Radially Inhomogeneous Viscoelastic Soil Layers," by K.W. Dotson and A.S. Veletsos, 12/87, (PB88-187786, A03, MF-A01).

NCEER-87-0025 "Proceedings from the Symposium on Seismic Hazards, Ground Motions, Soil-Liquefaction and Engineering Practice in Eastern North America," October 20-22, 1987, edited by K.H. Jacob, 12/87, (PB88-188115, A23, MF-A01). This report is available only through NTIS (see address given above).

NCEER-87-0026 "Report on the Whittier-Narrows, California, Earthquake of October 1, 1987," by J. Pantelic and A. Reinhorn, 11/87, (PB88-187752, A03, MF-A01). This report is available only through NTIS (see address given above).

NCEER-87-0027 "Design of a Modular Program for Transient Nonlinear Analysis of Large 3-D Building Structures," by S. Srivastav and J.F. Abel, 12/30/87, (PB88-187950, A05, MF-A01). This report is only available through NTIS (see address given above).

NCEER-87-0028 "Second-Year Program in Research, Education and Technology Transfer," 3/8/88, (PB88-219480, A04, MF-A01).

NCEER-88-0001 "Workshop on Seismic Computer Analysis and Design of Buildings With Interactive Graphics," by W. McGuire, J.F. Abel and C.H. Conley, 1/18/88, (PB88-187760, A03, MF-A01). This report is only available through NTIS (see address given above).

NCEER-88-0002 "Optimal Control of Nonlinear Flexible Structures," by J.N. Yang, F.X. Long and D. Wong, 1/22/88, (PB88-213772, A06, MF-A01).

NCEER-88-0003 "Substructuring Techniques in the Time Domain for Primary-Secondary Structural Systems," by G.D. Manolis and G. Juhn, 2/10/88, (PB88-213780, A04, MF-A01).

NCEER-88-0004 "Iterative Seismic Analysis of Primary-Secondary Systems," by A. Singhal, L.D. Lutes and P.D. Spanos, 2/23/88, (PB88-213798, A04, MF-A01).

NCEER-88-0005 "Stochastic Finite Element Expansion for Random Media," by P.D. Spanos and R. Ghanem, 3/14/88, (PB88-213806, A03, MF-A01).

NCEER-88-0006 "Combining Structural Optimization and Structural Control," by F.Y. Cheng and C.P. Pantelides, 1/10/88, (PB88-213814, A05, MF-A01).

Page 219: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

181

NCEER-88-0007 "Seismic Performance Assessment of Code-Designed Structures," by H.H-M. Hwang, J-W. Jaw and H-J.

Shau, 3/20/88, (PB88-219423, A04, MF-A01). This report is only available through NTIS (see address given above).

NCEER-88-0008 "Reliability Analysis of Code-Designed Structures Under Natural Hazards," by H.H-M. Hwang, H. Ushiba

and M. Shinozuka, 2/29/88, (PB88-229471, A07, MF-A01). This report is only available through NTIS (see address given above).

NCEER-88-0009 "Seismic Fragility Analysis of Shear Wall Structures," by J-W Jaw and H.H-M. Hwang, 4/30/88, (PB89-

102867, A04, MF-A01). NCEER-88-0010 "Base Isolation of a Multi-Story Building Under a Harmonic Ground Motion - A Comparison of

Performances of Various Systems," by F-G Fan, G. Ahmadi and I.G. Tadjbakhsh, 5/18/88, (PB89-122238, A06, MF-A01). This report is only available through NTIS (see address given above).

NCEER-88-0011 "Seismic Floor Response Spectra for a Combined System by Green's Functions," by F.M. Lavelle, L.A.

Bergman and P.D. Spanos, 5/1/88, (PB89-102875, A03, MF-A01). NCEER-88-0012 "A New Solution Technique for Randomly Excited Hysteretic Structures," by G.Q. Cai and Y.K. Lin,

5/16/88, (PB89-102883, A03, MF-A01). NCEER-88-0013 "A Study of Radiation Damping and Soil-Structure Interaction Effects in the Centrifuge," by K. Weissman,

supervised by J.H. Prevost, 5/24/88, (PB89-144703, A06, MF-A01). NCEER-88-0014 "Parameter Identification and Implementation of a Kinematic Plasticity Model for Frictional Soils," by J.H.

Prevost and D.V. Griffiths, not available. NCEER-88-0015 "Two- and Three- Dimensional Dynamic Finite Element Analyses of the Long Valley Dam," by D.V.

Griffiths and J.H. Prevost, 6/17/88, (PB89-144711, A04, MF-A01). NCEER-88-0016 "Damage Assessment of Reinforced Concrete Structures in Eastern United States," by A.M. Reinhorn, M.J.

Seidel, S.K. Kunnath and Y.J. Park, 6/15/88, (PB89-122220, A04, MF-A01). This report is only available through NTIS (see address given above).

NCEER-88-0017 "Dynamic Compliance of Vertically Loaded Strip Foundations in Multilayered Viscoelastic Soils," by S.

Ahmad and A.S.M. Israil, 6/17/88, (PB89-102891, A04, MF-A01). NCEER-88-0018 "An Experimental Study of Seismic Structural Response With Added Viscoelastic Dampers," by R.C. Lin, Z.

Liang, T.T. Soong and R.H. Zhang, 6/30/88, (PB89-122212, A05, MF-A01). This report is available only through NTIS (see address given above).

NCEER-88-0019 "Experimental Investigation of Primary - Secondary System Interaction," by G.D. Manolis, G. Juhn and

A.M. Reinhorn, 5/27/88, (PB89-122204, A04, MF-A01). NCEER-88-0020 "A Response Spectrum Approach For Analysis of Nonclassically Damped Structures," by J.N. Yang, S.

Sarkani and F.X. Long, 4/22/88, (PB89-102909, A04, MF-A01). NCEER-88-0021 "Seismic Interaction of Structures and Soils: Stochastic Approach," by A.S. Veletsos and A.M. Prasad,

7/21/88, (PB89-122196, A04, MF-A01). This report is only available through NTIS (see address given above).

NCEER-88-0022 "Identification of the Serviceability Limit State and Detection of Seismic Structural Damage," by E.

DiPasquale and A.S. Cakmak, 6/15/88, (PB89-122188, A05, MF-A01). This report is available only through NTIS (see address given above).

NCEER-88-0023 "Multi-Hazard Risk Analysis: Case of a Simple Offshore Structure," by B.K. Bhartia and E.H. Vanmarcke,

7/21/88, (PB89-145213, A05, MF-A01).

Page 220: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

182

NCEER-88-0024 "Automated Seismic Design of Reinforced Concrete Buildings," by Y.S. Chung, C. Meyer and M. Shinozuka, 7/5/88, (PB89-122170, A06, MF-A01). This report is available only through NTIS (see address given above).

NCEER-88-0025 "Experimental Study of Active Control of MDOF Structures Under Seismic Excitations," by L.L. Chung,

R.C. Lin, T.T. Soong and A.M. Reinhorn, 7/10/88, (PB89-122600, A04, MF-A01). NCEER-88-0026 "Earthquake Simulation Tests of a Low-Rise Metal Structure," by J.S. Hwang, K.C. Chang, G.C. Lee and

R.L. Ketter, 8/1/88, (PB89-102917, A04, MF-A01). NCEER-88-0027 "Systems Study of Urban Response and Reconstruction Due to Catastrophic Earthquakes," by F. Kozin and

H.K. Zhou, 9/22/88, (PB90-162348, A04, MF-A01). NCEER-88-0028 "Seismic Fragility Analysis of Plane Frame Structures," by H.H-M. Hwang and Y.K. Low, 7/31/88, (PB89-

131445, A06, MF-A01). NCEER-88-0029 "Response Analysis of Stochastic Structures," by A. Kardara, C. Bucher and M. Shinozuka, 9/22/88, (PB89-

174429, A04, MF-A01). NCEER-88-0030 "Nonnormal Accelerations Due to Yielding in a Primary Structure," by D.C.K. Chen and L.D. Lutes,

9/19/88, (PB89-131437, A04, MF-A01). NCEER-88-0031 "Design Approaches for Soil-Structure Interaction," by A.S. Veletsos, A.M. Prasad and Y. Tang, 12/30/88,

(PB89-174437, A03, MF-A01). This report is available only through NTIS (see address given above). NCEER-88-0032 "A Re-evaluation of Design Spectra for Seismic Damage Control," by C.J. Turkstra and A.G. Tallin, 11/7/88,

(PB89-145221, A05, MF-A01). NCEER-88-0033 "The Behavior and Design of Noncontact Lap Splices Subjected to Repeated Inelastic Tensile Loading," by

V.E. Sagan, P. Gergely and R.N. White, 12/8/88, (PB89-163737, A08, MF-A01). NCEER-88-0034 "Seismic Response of Pile Foundations," by S.M. Mamoon, P.K. Banerjee and S. Ahmad, 11/1/88, (PB89-

145239, A04, MF-A01). NCEER-88-0035 "Modeling of R/C Building Structures With Flexible Floor Diaphragms (IDARC2)," by A.M. Reinhorn, S.K.

Kunnath and N. Panahshahi, 9/7/88, (PB89-207153, A07, MF-A01). NCEER-88-0036 "Solution of the Dam-Reservoir Interaction Problem Using a Combination of FEM, BEM with Particular

Integrals, Modal Analysis, and Substructuring," by C-S. Tsai, G.C. Lee and R.L. Ketter, 12/31/88, (PB89-207146, A04, MF-A01).

NCEER-88-0037 "Optimal Placement of Actuators for Structural Control," by F.Y. Cheng and C.P. Pantelides, 8/15/88,

(PB89-162846, A05, MF-A01). NCEER-88-0038 "Teflon Bearings in Aseismic Base Isolation: Experimental Studies and Mathematical Modeling," by A.

Mokha, M.C. Constantinou and A.M. Reinhorn, 12/5/88, (PB89-218457, A10, MF-A01). This report is available only through NTIS (see address given above).

NCEER-88-0039 "Seismic Behavior of Flat Slab High-Rise Buildings in the New York City Area," by P. Weidlinger and M.

Ettouney, 10/15/88, (PB90-145681, A04, MF-A01). NCEER-88-0040 "Evaluation of the Earthquake Resistance of Existing Buildings in New York City," by P. Weidlinger and M.

Ettouney, 10/15/88, not available. NCEER-88-0041 "Small-Scale Modeling Techniques for Reinforced Concrete Structures Subjected to Seismic Loads," by W.

Kim, A. El-Attar and R.N. White, 11/22/88, (PB89-189625, A05, MF-A01). NCEER-88-0042 "Modeling Strong Ground Motion from Multiple Event Earthquakes," by G.W. Ellis and A.S. Cakmak,

10/15/88, (PB89-174445, A03, MF-A01).

Page 221: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

183

NCEER-88-0043 "Nonstationary Models of Seismic Ground Acceleration," by M. Grigoriu, S.E. Ruiz and E. Rosenblueth, 7/15/88, (PB89-189617, A04, MF-A01).

NCEER-88-0044 "SARCF User's Guide: Seismic Analysis of Reinforced Concrete Frames," by Y.S. Chung, C. Meyer and M.

Shinozuka, 11/9/88, (PB89-174452, A08, MF-A01). NCEER-88-0045 "First Expert Panel Meeting on Disaster Research and Planning," edited by J. Pantelic and J. Stoyle, 9/15/88,

(PB89-174460, A05, MF-A01). NCEER-88-0046 "Preliminary Studies of the Effect of Degrading Infill Walls on the Nonlinear Seismic Response of Steel

Frames," by C.Z. Chrysostomou, P. Gergely and J.F. Abel, 12/19/88, (PB89-208383, A05, MF-A01). NCEER-88-0047 "Reinforced Concrete Frame Component Testing Facility - Design, Construction, Instrumentation and

Operation," by S.P. Pessiki, C. Conley, T. Bond, P. Gergely and R.N. White, 12/16/88, (PB89-174478, A04, MF-A01).

NCEER-89-0001 "Effects of Protective Cushion and Soil Compliancy on the Response of Equipment Within a Seismically

Excited Building," by J.A. HoLung, 2/16/89, (PB89-207179, A04, MF-A01). NCEER-89-0002 "Statistical Evaluation of Response Modification Factors for Reinforced Concrete Structures," by H.H-M.

Hwang and J-W. Jaw, 2/17/89, (PB89-207187, A05, MF-A01). NCEER-89-0003 "Hysteretic Columns Under Random Excitation," by G-Q. Cai and Y.K. Lin, 1/9/89, (PB89-196513, A03,

MF-A01). NCEER-89-0004 "Experimental Study of `Elephant Foot Bulge' Instability of Thin-Walled Metal Tanks," by Z-H. Jia and R.L.

Ketter, 2/22/89, (PB89-207195, A03, MF-A01). NCEER-89-0005 "Experiment on Performance of Buried Pipelines Across San Andreas Fault," by J. Isenberg, E. Richardson

and T.D. O'Rourke, 3/10/89, (PB89-218440, A04, MF-A01). This report is available only through NTIS (see address given above).

NCEER-89-0006 "A Knowledge-Based Approach to Structural Design of Earthquake-Resistant Buildings," by M. Subramani,

P. Gergely, C.H. Conley, J.F. Abel and A.H. Zaghw, 1/15/89, (PB89-218465, A06, MF-A01). NCEER-89-0007 "Liquefaction Hazards and Their Effects on Buried Pipelines," by T.D. O'Rourke and P.A. Lane, 2/1/89,

(PB89-218481, A09, MF-A01). NCEER-89-0008 "Fundamentals of System Identification in Structural Dynamics," by H. Imai, C-B. Yun, O. Maruyama and

M. Shinozuka, 1/26/89, (PB89-207211, A04, MF-A01). NCEER-89-0009 "Effects of the 1985 Michoacan Earthquake on Water Systems and Other Buried Lifelines in Mexico," by

A.G. Ayala and M.J. O'Rourke, 3/8/89, (PB89-207229, A06, MF-A01). NCEER-89-R010 "NCEER Bibliography of Earthquake Education Materials," by K.E.K. Ross, Second Revision, 9/1/89,

(PB90-125352, A05, MF-A01). This report is replaced by NCEER-92-0018. NCEER-89-0011 "Inelastic Three-Dimensional Response Analysis of Reinforced Concrete Building Structures (IDARC-3D),

Part I - Modeling," by S.K. Kunnath and A.M. Reinhorn, 4/17/89, (PB90-114612, A07, MF-A01). This report is available only through NTIS (see address given above).

NCEER-89-0012 "Recommended Modifications to ATC-14," by C.D. Poland and J.O. Malley, 4/12/89, (PB90-108648, A15,

MF-A01). NCEER-89-0013 "Repair and Strengthening of Beam-to-Column Connections Subjected to Earthquake Loading," by M.

Corazao and A.J. Durrani, 2/28/89, (PB90-109885, A06, MF-A01). NCEER-89-0014 "Program EXKAL2 for Identification of Structural Dynamic Systems," by O. Maruyama, C-B. Yun, M.

Hoshiya and M. Shinozuka, 5/19/89, (PB90-109877, A09, MF-A01).

Page 222: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

184

NCEER-89-0015 "Response of Frames With Bolted Semi-Rigid Connections, Part I - Experimental Study and Analytical Predictions," by P.J. DiCorso, A.M. Reinhorn, J.R. Dickerson, J.B. Radziminski and W.L. Harper, 6/1/89, not available.

NCEER-89-0016 "ARMA Monte Carlo Simulation in Probabilistic Structural Analysis," by P.D. Spanos and M.P. Mignolet,

7/10/89, (PB90-109893, A03, MF-A01). NCEER-89-P017 "Preliminary Proceedings from the Conference on Disaster Preparedness - The Place of Earthquake

Education in Our Schools," Edited by K.E.K. Ross, 6/23/89, (PB90-108606, A03, MF-A01). NCEER-89-0017 "Proceedings from the Conference on Disaster Preparedness - The Place of Earthquake Education in Our

Schools," Edited by K.E.K. Ross, 12/31/89, (PB90-207895, A012, MF-A02). This report is available only through NTIS (see address given above).

NCEER-89-0018 "Multidimensional Models of Hysteretic Material Behavior for Vibration Analysis of Shape Memory Energy

Absorbing Devices, by E.J. Graesser and F.A. Cozzarelli, 6/7/89, (PB90-164146, A04, MF-A01). NCEER-89-0019 "Nonlinear Dynamic Analysis of Three-Dimensional Base Isolated Structures (3D-BASIS)," by S.

Nagarajaiah, A.M. Reinhorn and M.C. Constantinou, 8/3/89, (PB90-161936, A06, MF-A01). This report has been replaced by NCEER-93-0011.

NCEER-89-0020 "Structural Control Considering Time-Rate of Control Forces and Control Rate Constraints," by F.Y. Cheng

and C.P. Pantelides, 8/3/89, (PB90-120445, A04, MF-A01). NCEER-89-0021 "Subsurface Conditions of Memphis and Shelby County," by K.W. Ng, T-S. Chang and H-H.M. Hwang,

7/26/89, (PB90-120437, A03, MF-A01). NCEER-89-0022 "Seismic Wave Propagation Effects on Straight Jointed Buried Pipelines," by K. Elhmadi and M.J. O'Rourke,

8/24/89, (PB90-162322, A10, MF-A02). NCEER-89-0023 "Workshop on Serviceability Analysis of Water Delivery Systems," edited by M. Grigoriu, 3/6/89, (PB90-

127424, A03, MF-A01). NCEER-89-0024 "Shaking Table Study of a 1/5 Scale Steel Frame Composed of Tapered Members," by K.C. Chang, J.S.

Hwang and G.C. Lee, 9/18/89, (PB90-160169, A04, MF-A01). NCEER-89-0025 "DYNA1D: A Computer Program for Nonlinear Seismic Site Response Analysis - Technical

Documentation," by Jean H. Prevost, 9/14/89, (PB90-161944, A07, MF-A01). This report is available only through NTIS (see address given above).

NCEER-89-0026 "1:4 Scale Model Studies of Active Tendon Systems and Active Mass Dampers for Aseismic Protection," by

A.M. Reinhorn, T.T. Soong, R.C. Lin, Y.P. Yang, Y. Fukao, H. Abe and M. Nakai, 9/15/89, (PB90-173246, A10, MF-A02). This report is available only through NTIS (see address given above).

NCEER-89-0027 "Scattering of Waves by Inclusions in a Nonhomogeneous Elastic Half Space Solved by Boundary Element

Methods," by P.K. Hadley, A. Askar and A.S. Cakmak, 6/15/89, (PB90-145699, A07, MF-A01). NCEER-89-0028 "Statistical Evaluation of Deflection Amplification Factors for Reinforced Concrete Structures," by H.H.M.

Hwang, J-W. Jaw and A.L. Ch'ng, 8/31/89, (PB90-164633, A05, MF-A01). NCEER-89-0029 "Bedrock Accelerations in Memphis Area Due to Large New Madrid Earthquakes," by H.H.M. Hwang,

C.H.S. Chen and G. Yu, 11/7/89, (PB90-162330, A04, MF-A01). NCEER-89-0030 "Seismic Behavior and Response Sensitivity of Secondary Structural Systems," by Y.Q. Chen and T.T.

Soong, 10/23/89, (PB90-164658, A08, MF-A01). NCEER-89-0031 "Random Vibration and Reliability Analysis of Primary-Secondary Structural Systems," by Y. Ibrahim, M.

Grigoriu and T.T. Soong, 11/10/89, (PB90-161951, A04, MF-A01).

Page 223: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

185

NCEER-89-0032 "Proceedings from the Second U.S. - Japan Workshop on Liquefaction, Large Ground Deformation and Their Effects on Lifelines, September 26-29, 1989," Edited by T.D. O'Rourke and M. Hamada, 12/1/89, (PB90-209388, A22, MF-A03).

NCEER-89-0033 "Deterministic Model for Seismic Damage Evaluation of Reinforced Concrete Structures," by J.M. Bracci,

A.M. Reinhorn, J.B. Mander and S.K. Kunnath, 9/27/89, (PB91-108803, A06, MF-A01). NCEER-89-0034 "On the Relation Between Local and Global Damage Indices," by E. DiPasquale and A.S. Cakmak, 8/15/89,

(PB90-173865, A05, MF-A01). NCEER-89-0035 "Cyclic Undrained Behavior of Nonplastic and Low Plasticity Silts," by A.J. Walker and H.E. Stewart,

7/26/89, (PB90-183518, A10, MF-A01). NCEER-89-0036 "Liquefaction Potential of Surficial Deposits in the City of Buffalo, New York," by M. Budhu, R. Giese and

L. Baumgrass, 1/17/89, (PB90-208455, A04, MF-A01). NCEER-89-0037 "A Deterministic Assessment of Effects of Ground Motion Incoherence," by A.S. Veletsos and Y. Tang,

7/15/89, (PB90-164294, A03, MF-A01). NCEER-89-0038 "Workshop on Ground Motion Parameters for Seismic Hazard Mapping," July 17-18, 1989, edited by R.V.

Whitman, 12/1/89, (PB90-173923, A04, MF-A01). NCEER-89-0039 "Seismic Effects on Elevated Transit Lines of the New York City Transit Authority," by C.J. Costantino,

C.A. Miller and E. Heymsfield, 12/26/89, (PB90-207887, A06, MF-A01). NCEER-89-0040 "Centrifugal Modeling of Dynamic Soil-Structure Interaction," by K. Weissman, Supervised by J.H. Prevost,

5/10/89, (PB90-207879, A07, MF-A01). NCEER-89-0041 "Linearized Identification of Buildings With Cores for Seismic Vulnerability Assessment," by I-K. Ho and

A.E. Aktan, 11/1/89, (PB90-251943, A07, MF-A01). NCEER-90-0001 "Geotechnical and Lifeline Aspects of the October 17, 1989 Loma Prieta Earthquake in San Francisco," by

T.D. O'Rourke, H.E. Stewart, F.T. Blackburn and T.S. Dickerman, 1/90, (PB90-208596, A05, MF-A01). NCEER-90-0002 "Nonnormal Secondary Response Due to Yielding in a Primary Structure," by D.C.K. Chen and L.D. Lutes,

2/28/90, (PB90-251976, A07, MF-A01). NCEER-90-0003 "Earthquake Education Materials for Grades K-12," by K.E.K. Ross, 4/16/90, (PB91-251984, A05, MF-

A05). This report has been replaced by NCEER-92-0018. NCEER-90-0004 "Catalog of Strong Motion Stations in Eastern North America," by R.W. Busby, 4/3/90, (PB90-251984, A05,

MF-A01). NCEER-90-0005 "NCEER Strong-Motion Data Base: A User Manual for the GeoBase Release (Version 1.0 for the Sun3)," by

P. Friberg and K. Jacob, 3/31/90 (PB90-258062, A04, MF-A01). NCEER-90-0006 "Seismic Hazard Along a Crude Oil Pipeline in the Event of an 1811-1812 Type New Madrid Earthquake,"

by H.H.M. Hwang and C-H.S. Chen, 4/16/90, (PB90-258054, A04, MF-A01). NCEER-90-0007 "Site-Specific Response Spectra for Memphis Sheahan Pumping Station," by H.H.M. Hwang and C.S. Lee,

5/15/90, (PB91-108811, A05, MF-A01). NCEER-90-0008 "Pilot Study on Seismic Vulnerability of Crude Oil Transmission Systems," by T. Ariman, R. Dobry, M.

Grigoriu, F. Kozin, M. O'Rourke, T. O'Rourke and M. Shinozuka, 5/25/90, (PB91-108837, A06, MF-A01). NCEER-90-0009 "A Program to Generate Site Dependent Time Histories: EQGEN," by G.W. Ellis, M. Srinivasan and A.S.

Cakmak, 1/30/90, (PB91-108829, A04, MF-A01). NCEER-90-0010 "Active Isolation for Seismic Protection of Operating Rooms," by M.E. Talbott, Supervised by M.

Shinozuka, 6/8/9, (PB91-110205, A05, MF-A01).

Page 224: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

186

NCEER-90-0011 "Program LINEARID for Identification of Linear Structural Dynamic Systems," by C-B. Yun and M. Shinozuka, 6/25/90, (PB91-110312, A08, MF-A01).

NCEER-90-0012 "Two-Dimensional Two-Phase Elasto-Plastic Seismic Response of Earth Dams," by A.N. Yiagos, Supervised

by J.H. Prevost, 6/20/90, (PB91-110197, A13, MF-A02). NCEER-90-0013 "Secondary Systems in Base-Isolated Structures: Experimental Investigation, Stochastic Response and

Stochastic Sensitivity," by G.D. Manolis, G. Juhn, M.C. Constantinou and A.M. Reinhorn, 7/1/90, (PB91-110320, A08, MF-A01).

NCEER-90-0014 "Seismic Behavior of Lightly-Reinforced Concrete Column and Beam-Column Joint Details," by S.P.

Pessiki, C.H. Conley, P. Gergely and R.N. White, 8/22/90, (PB91-108795, A11, MF-A02). NCEER-90-0015 "Two Hybrid Control Systems for Building Structures Under Strong Earthquakes," by J.N. Yang and A.

Danielians, 6/29/90, (PB91-125393, A04, MF-A01). NCEER-90-0016 "Instantaneous Optimal Control with Acceleration and Velocity Feedback," by J.N. Yang and Z. Li, 6/29/90,

(PB91-125401, A03, MF-A01). NCEER-90-0017 "Reconnaissance Report on the Northern Iran Earthquake of June 21, 1990," by M. Mehrain, 10/4/90, (PB91-

125377, A03, MF-A01). NCEER-90-0018 "Evaluation of Liquefaction Potential in Memphis and Shelby County," by T.S. Chang, P.S. Tang, C.S. Lee

and H. Hwang, 8/10/90, (PB91-125427, A09, MF-A01). NCEER-90-0019 "Experimental and Analytical Study of a Combined Sliding Disc Bearing and Helical Steel Spring Isolation

System," by M.C. Constantinou, A.S. Mokha and A.M. Reinhorn, 10/4/90, (PB91-125385, A06, MF-A01). This report is available only through NTIS (see address given above).

NCEER-90-0020 "Experimental Study and Analytical Prediction of Earthquake Response of a Sliding Isolation System with a

Spherical Surface," by A.S. Mokha, M.C. Constantinou and A.M. Reinhorn, 10/11/90, (PB91-125419, A05, MF-A01).

NCEER-90-0021 "Dynamic Interaction Factors for Floating Pile Groups," by G. Gazetas, K. Fan, A. Kaynia and E. Kausel,

9/10/90, (PB91-170381, A05, MF-A01). NCEER-90-0022 "Evaluation of Seismic Damage Indices for Reinforced Concrete Structures," by S. Rodriguez-Gomez and

A.S. Cakmak, 9/30/90, PB91-171322, A06, MF-A01). NCEER-90-0023 "Study of Site Response at a Selected Memphis Site," by H. Desai, S. Ahmad, E.S. Gazetas and M.R. Oh,

10/11/90, (PB91-196857, A03, MF-A01). NCEER-90-0024 "A User's Guide to Strongmo: Version 1.0 of NCEER's Strong-Motion Data Access Tool for PCs and

Terminals," by P.A. Friberg and C.A.T. Susch, 11/15/90, (PB91-171272, A03, MF-A01). NCEER-90-0025 "A Three-Dimensional Analytical Study of Spatial Variability of Seismic Ground Motions," by L-L. Hong

and A.H.-S. Ang, 10/30/90, (PB91-170399, A09, MF-A01). NCEER-90-0026 "MUMOID User's Guide - A Program for the Identification of Modal Parameters," by S. Rodriguez-Gomez

and E. DiPasquale, 9/30/90, (PB91-171298, A04, MF-A01). NCEER-90-0027 "SARCF-II User's Guide - Seismic Analysis of Reinforced Concrete Frames," by S. Rodriguez-Gomez, Y.S.

Chung and C. Meyer, 9/30/90, (PB91-171280, A05, MF-A01). NCEER-90-0028 "Viscous Dampers: Testing, Modeling and Application in Vibration and Seismic Isolation," by N. Makris

and M.C. Constantinou, 12/20/90 (PB91-190561, A06, MF-A01). NCEER-90-0029 "Soil Effects on Earthquake Ground Motions in the Memphis Area," by H. Hwang, C.S. Lee, K.W. Ng and

T.S. Chang, 8/2/90, (PB91-190751, A05, MF-A01).

Page 225: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

187

NCEER-91-0001 "Proceedings from the Third Japan-U.S. Workshop on Earthquake Resistant Design of Lifeline Facilities and Countermeasures for Soil Liquefaction, December 17-19, 1990," edited by T.D. O'Rourke and M. Hamada, 2/1/91, (PB91-179259, A99, MF-A04).

NCEER-91-0002 "Physical Space Solutions of Non-Proportionally Damped Systems," by M. Tong, Z. Liang and G.C. Lee,

1/15/91, (PB91-179242, A04, MF-A01). NCEER-91-0003 "Seismic Response of Single Piles and Pile Groups," by K. Fan and G. Gazetas, 1/10/91, (PB92-174994,

A04, MF-A01). NCEER-91-0004 "Damping of Structures: Part 1 - Theory of Complex Damping," by Z. Liang and G. Lee, 10/10/91, (PB92-

197235, A12, MF-A03). NCEER-91-0005 "3D-BASIS - Nonlinear Dynamic Analysis of Three Dimensional Base Isolated Structures: Part II," by S.

Nagarajaiah, A.M. Reinhorn and M.C. Constantinou, 2/28/91, (PB91-190553, A07, MF-A01). This report has been replaced by NCEER-93-0011.

NCEER-91-0006 "A Multidimensional Hysteretic Model for Plasticity Deforming Metals in Energy Absorbing Devices," by

E.J. Graesser and F.A. Cozzarelli, 4/9/91, (PB92-108364, A04, MF-A01). NCEER-91-0007 "A Framework for Customizable Knowledge-Based Expert Systems with an Application to a KBES for

Evaluating the Seismic Resistance of Existing Buildings," by E.G. Ibarra-Anaya and S.J. Fenves, 4/9/91, (PB91-210930, A08, MF-A01).

NCEER-91-0008 "Nonlinear Analysis of Steel Frames with Semi-Rigid Connections Using the Capacity Spectrum Method,"

by G.G. Deierlein, S-H. Hsieh, Y-J. Shen and J.F. Abel, 7/2/91, (PB92-113828, A05, MF-A01). NCEER-91-0009 "Earthquake Education Materials for Grades K-12," by K.E.K. Ross, 4/30/91, (PB91-212142, A06, MF-

A01). This report has been replaced by NCEER-92-0018. NCEER-91-0010 "Phase Wave Velocities and Displacement Phase Differences in a Harmonically Oscillating Pile," by N.

Makris and G. Gazetas, 7/8/91, (PB92-108356, A04, MF-A01). NCEER-91-0011 "Dynamic Characteristics of a Full-Size Five-Story Steel Structure and a 2/5 Scale Model," by K.C. Chang,

G.C. Yao, G.C. Lee, D.S. Hao and Y.C. Yeh," 7/2/91, (PB93-116648, A06, MF-A02). NCEER-91-0012 "Seismic Response of a 2/5 Scale Steel Structure with Added Viscoelastic Dampers," by K.C. Chang, T.T.

Soong, S-T. Oh and M.L. Lai, 5/17/91, (PB92-110816, A05, MF-A01). NCEER-91-0013 "Earthquake Response of Retaining Walls; Full-Scale Testing and Computational Modeling," by S.

Alampalli and A-W.M. Elgamal, 6/20/91, not available. NCEER-91-0014 "3D-BASIS-M: Nonlinear Dynamic Analysis of Multiple Building Base Isolated Structures," by P.C.

Tsopelas, S. Nagarajaiah, M.C. Constantinou and A.M. Reinhorn, 5/28/91, (PB92-113885, A09, MF-A02). NCEER-91-0015 "Evaluation of SEAOC Design Requirements for Sliding Isolated Structures," by D. Theodossiou and M.C.

Constantinou, 6/10/91, (PB92-114602, A11, MF-A03). NCEER-91-0016 "Closed-Loop Modal Testing of a 27-Story Reinforced Concrete Flat Plate-Core Building," by H.R.

Somaprasad, T. Toksoy, H. Yoshiyuki and A.E. Aktan, 7/15/91, (PB92-129980, A07, MF-A02). NCEER-91-0017 "Shake Table Test of a 1/6 Scale Two-Story Lightly Reinforced Concrete Building," by A.G. El-Attar, R.N.

White and P. Gergely, 2/28/91, (PB92-222447, A06, MF-A02). NCEER-91-0018 "Shake Table Test of a 1/8 Scale Three-Story Lightly Reinforced Concrete Building," by A.G. El-Attar, R.N.

White and P. Gergely, 2/28/91, (PB93-116630, A08, MF-A02). NCEER-91-0019 "Transfer Functions for Rigid Rectangular Foundations," by A.S. Veletsos, A.M. Prasad and W.H. Wu,

7/31/91, not available.

Page 226: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

188

NCEER-91-0020 "Hybrid Control of Seismic-Excited Nonlinear and Inelastic Structural Systems," by J.N. Yang, Z. Li and A. Danielians, 8/1/91, (PB92-143171, A06, MF-A02).

NCEER-91-0021 "The NCEER-91 Earthquake Catalog: Improved Intensity-Based Magnitudes and Recurrence Relations for

U.S. Earthquakes East of New Madrid," by L. Seeber and J.G. Armbruster, 8/28/91, (PB92-176742, A06, MF-A02).

NCEER-91-0022 "Proceedings from the Implementation of Earthquake Planning and Education in Schools: The Need for

Change - The Roles of the Changemakers," by K.E.K. Ross and F. Winslow, 7/23/91, (PB92-129998, A12, MF-A03).

NCEER-91-0023 "A Study of Reliability-Based Criteria for Seismic Design of Reinforced Concrete Frame Buildings," by

H.H.M. Hwang and H-M. Hsu, 8/10/91, (PB92-140235, A09, MF-A02). NCEER-91-0024 "Experimental Verification of a Number of Structural System Identification Algorithms," by R.G. Ghanem,

H. Gavin and M. Shinozuka, 9/18/91, (PB92-176577, A18, MF-A04). NCEER-91-0025 "Probabilistic Evaluation of Liquefaction Potential," by H.H.M. Hwang and C.S. Lee," 11/25/91, (PB92-

143429, A05, MF-A01). NCEER-91-0026 "Instantaneous Optimal Control for Linear, Nonlinear and Hysteretic Structures - Stable Controllers," by J.N.

Yang and Z. Li, 11/15/91, (PB92-163807, A04, MF-A01). NCEER-91-0027 "Experimental and Theoretical Study of a Sliding Isolation System for Bridges," by M.C. Constantinou, A.

Kartoum, A.M. Reinhorn and P. Bradford, 11/15/91, (PB92-176973, A10, MF-A03). NCEER-92-0001 "Case Studies of Liquefaction and Lifeline Performance During Past Earthquakes, Volume 1: Japanese Case

Studies," Edited by M. Hamada and T. O'Rourke, 2/17/92, (PB92-197243, A18, MF-A04). NCEER-92-0002 "Case Studies of Liquefaction and Lifeline Performance During Past Earthquakes, Volume 2: United States

Case Studies," Edited by T. O'Rourke and M. Hamada, 2/17/92, (PB92-197250, A20, MF-A04). NCEER-92-0003 "Issues in Earthquake Education," Edited by K. Ross, 2/3/92, (PB92-222389, A07, MF-A02). NCEER-92-0004 "Proceedings from the First U.S. - Japan Workshop on Earthquake Protective Systems for Bridges," Edited

by I.G. Buckle, 2/4/92, (PB94-142239, A99, MF-A06). NCEER-92-0005 "Seismic Ground Motion from a Haskell-Type Source in a Multiple-Layered Half-Space," A.P. Theoharis, G.

Deodatis and M. Shinozuka, 1/2/92, not available. NCEER-92-0006 "Proceedings from the Site Effects Workshop," Edited by R. Whitman, 2/29/92, (PB92-197201, A04, MF-

A01). NCEER-92-0007 "Engineering Evaluation of Permanent Ground Deformations Due to Seismically-Induced Liquefaction," by

M.H. Baziar, R. Dobry and A-W.M. Elgamal, 3/24/92, (PB92-222421, A13, MF-A03). NCEER-92-0008 "A Procedure for the Seismic Evaluation of Buildings in the Central and Eastern United States," by C.D.

Poland and J.O. Malley, 4/2/92, (PB92-222439, A20, MF-A04). NCEER-92-0009 "Experimental and Analytical Study of a Hybrid Isolation System Using Friction Controllable Sliding

Bearings," by M.Q. Feng, S. Fujii and M. Shinozuka, 5/15/92, (PB93-150282, A06, MF-A02). NCEER-92-0010 "Seismic Resistance of Slab-Column Connections in Existing Non-Ductile Flat-Plate Buildings," by A.J.

Durrani and Y. Du, 5/18/92, (PB93-116812, A06, MF-A02). NCEER-92-0011 "The Hysteretic and Dynamic Behavior of Brick Masonry Walls Upgraded by Ferrocement Coatings Under

Cyclic Loading and Strong Simulated Ground Motion," by H. Lee and S.P. Prawel, 5/11/92, not available. NCEER-92-0012 "Study of Wire Rope Systems for Seismic Protection of Equipment in Buildings," by G.F. Demetriades,

M.C. Constantinou and A.M. Reinhorn, 5/20/92, (PB93-116655, A08, MF-A02).

Page 227: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

189

NCEER-92-0013 "Shape Memory Structural Dampers: Material Properties, Design and Seismic Testing," by P.R. Witting and F.A. Cozzarelli, 5/26/92, (PB93-116663, A05, MF-A01).

NCEER-92-0014 "Longitudinal Permanent Ground Deformation Effects on Buried Continuous Pipelines," by M.J. O'Rourke,

and C. Nordberg, 6/15/92, (PB93-116671, A08, MF-A02). NCEER-92-0015 "A Simulation Method for Stationary Gaussian Random Functions Based on the Sampling Theorem," by M.

Grigoriu and S. Balopoulou, 6/11/92, (PB93-127496, A05, MF-A01). NCEER-92-0016 "Gravity-Load-Designed Reinforced Concrete Buildings: Seismic Evaluation of Existing Construction and

Detailing Strategies for Improved Seismic Resistance," by G.W. Hoffmann, S.K. Kunnath, A.M. Reinhorn and J.B. Mander, 7/15/92, (PB94-142007, A08, MF-A02).

NCEER-92-0017 "Observations on Water System and Pipeline Performance in the Limón Area of Costa Rica Due to the April

22, 1991 Earthquake," by M. O'Rourke and D. Ballantyne, 6/30/92, (PB93-126811, A06, MF-A02). NCEER-92-0018 "Fourth Edition of Earthquake Education Materials for Grades K-12," Edited by K.E.K. Ross, 8/10/92,

(PB93-114023, A07, MF-A02). NCEER-92-0019 "Proceedings from the Fourth Japan-U.S. Workshop on Earthquake Resistant Design of Lifeline Facilities

and Countermeasures for Soil Liquefaction," Edited by M. Hamada and T.D. O'Rourke, 8/12/92, (PB93-163939, A99, MF-E11).

NCEER-92-0020 "Active Bracing System: A Full Scale Implementation of Active Control," by A.M. Reinhorn, T.T. Soong,

R.C. Lin, M.A. Riley, Y.P. Wang, S. Aizawa and M. Higashino, 8/14/92, (PB93-127512, A06, MF-A02). NCEER-92-0021 "Empirical Analysis of Horizontal Ground Displacement Generated by Liquefaction-Induced Lateral

Spreads," by S.F. Bartlett and T.L. Youd, 8/17/92, (PB93-188241, A06, MF-A02). NCEER-92-0022 "IDARC Version 3.0: Inelastic Damage Analysis of Reinforced Concrete Structures," by S.K. Kunnath, A.M.

Reinhorn and R.F. Lobo, 8/31/92, (PB93-227502, A07, MF-A02). NCEER-92-0023 "A Semi-Empirical Analysis of Strong-Motion Peaks in Terms of Seismic Source, Propagation Path and

Local Site Conditions, by M. Kamiyama, M.J. O'Rourke and R. Flores-Berrones, 9/9/92, (PB93-150266, A08, MF-A02).

NCEER-92-0024 "Seismic Behavior of Reinforced Concrete Frame Structures with Nonductile Details, Part I: Summary of

Experimental Findings of Full Scale Beam-Column Joint Tests," by A. Beres, R.N. White and P. Gergely, 9/30/92, (PB93-227783, A05, MF-A01).

NCEER-92-0025 "Experimental Results of Repaired and Retrofitted Beam-Column Joint Tests in Lightly Reinforced Concrete

Frame Buildings," by A. Beres, S. El-Borgi, R.N. White and P. Gergely, 10/29/92, (PB93-227791, A05, MF-A01).

NCEER-92-0026 "A Generalization of Optimal Control Theory: Linear and Nonlinear Structures," by J.N. Yang, Z. Li and S.

Vongchavalitkul, 11/2/92, (PB93-188621, A05, MF-A01). NCEER-92-0027 "Seismic Resistance of Reinforced Concrete Frame Structures Designed Only for Gravity Loads: Part I -

Design and Properties of a One-Third Scale Model Structure," by J.M. Bracci, A.M. Reinhorn and J.B. Mander, 12/1/92, (PB94-104502, A08, MF-A02).

NCEER-92-0028 "Seismic Resistance of Reinforced Concrete Frame Structures Designed Only for Gravity Loads: Part II -

Experimental Performance of Subassemblages," by L.E. Aycardi, J.B. Mander and A.M. Reinhorn, 12/1/92, (PB94-104510, A08, MF-A02).

NCEER-92-0029 "Seismic Resistance of Reinforced Concrete Frame Structures Designed Only for Gravity Loads: Part III -

Experimental Performance and Analytical Study of a Structural Model," by J.M. Bracci, A.M. Reinhorn and J.B. Mander, 12/1/92, (PB93-227528, A09, MF-A01).

Page 228: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

190

NCEER-92-0030 "Evaluation of Seismic Retrofit of Reinforced Concrete Frame Structures: Part I - Experimental Performance of Retrofitted Subassemblages," by D. Choudhuri, J.B. Mander and A.M. Reinhorn, 12/8/92, (PB93-198307, A07, MF-A02).

NCEER-92-0031 "Evaluation of Seismic Retrofit of Reinforced Concrete Frame Structures: Part II - Experimental

Performance and Analytical Study of a Retrofitted Structural Model," by J.M. Bracci, A.M. Reinhorn and J.B. Mander, 12/8/92, (PB93-198315, A09, MF-A03).

NCEER-92-0032 "Experimental and Analytical Investigation of Seismic Response of Structures with Supplemental Fluid

Viscous Dampers," by M.C. Constantinou and M.D. Symans, 12/21/92, (PB93-191435, A10, MF-A03). This report is available only through NTIS (see address given above).

NCEER-92-0033 "Reconnaissance Report on the Cairo, Egypt Earthquake of October 12, 1992," by M. Khater, 12/23/92,

(PB93-188621, A03, MF-A01). NCEER-92-0034 "Low-Level Dynamic Characteristics of Four Tall Flat-Plate Buildings in New York City," by H. Gavin, S.

Yuan, J. Grossman, E. Pekelis and K. Jacob, 12/28/92, (PB93-188217, A07, MF-A02). NCEER-93-0001 "An Experimental Study on the Seismic Performance of Brick-Infilled Steel Frames With and Without

Retrofit," by J.B. Mander, B. Nair, K. Wojtkowski and J. Ma, 1/29/93, (PB93-227510, A07, MF-A02). NCEER-93-0002 "Social Accounting for Disaster Preparedness and Recovery Planning," by S. Cole, E. Pantoja and V. Razak,

2/22/93, (PB94-142114, A12, MF-A03). NCEER-93-0003 "Assessment of 1991 NEHRP Provisions for Nonstructural Components and Recommended Revisions," by

T.T. Soong, G. Chen, Z. Wu, R-H. Zhang and M. Grigoriu, 3/1/93, (PB93-188639, A06, MF-A02). NCEER-93-0004 "Evaluation of Static and Response Spectrum Analysis Procedures of SEAOC/UBC for Seismic Isolated

Structures," by C.W. Winters and M.C. Constantinou, 3/23/93, (PB93-198299, A10, MF-A03). NCEER-93-0005 "Earthquakes in the Northeast - Are We Ignoring the Hazard? A Workshop on Earthquake Science and

Safety for Educators," edited by K.E.K. Ross, 4/2/93, (PB94-103066, A09, MF-A02). NCEER-93-0006 "Inelastic Response of Reinforced Concrete Structures with Viscoelastic Braces," by R.F. Lobo, J.M. Bracci,

K.L. Shen, A.M. Reinhorn and T.T. Soong, 4/5/93, (PB93-227486, A05, MF-A02). NCEER-93-0007 "Seismic Testing of Installation Methods for Computers and Data Processing Equipment," by K. Kosar, T.T.

Soong, K.L. Shen, J.A. HoLung and Y.K. Lin, 4/12/93, (PB93-198299, A07, MF-A02). NCEER-93-0008 "Retrofit of Reinforced Concrete Frames Using Added Dampers," by A. Reinhorn, M. Constantinou and C.

Li, not available. NCEER-93-0009 "Seismic Behavior and Design Guidelines for Steel Frame Structures with Added Viscoelastic Dampers," by

K.C. Chang, M.L. Lai, T.T. Soong, D.S. Hao and Y.C. Yeh, 5/1/93, (PB94-141959, A07, MF-A02). NCEER-93-0010 "Seismic Performance of Shear-Critical Reinforced Concrete Bridge Piers," by J.B. Mander, S.M. Waheed,

M.T.A. Chaudhary and S.S. Chen, 5/12/93, (PB93-227494, A08, MF-A02). NCEER-93-0011 "3D-BASIS-TABS: Computer Program for Nonlinear Dynamic Analysis of Three Dimensional Base Isolated

Structures," by S. Nagarajaiah, C. Li, A.M. Reinhorn and M.C. Constantinou, 8/2/93, (PB94-141819, A09, MF-A02).

NCEER-93-0012 "Effects of Hydrocarbon Spills from an Oil Pipeline Break on Ground Water," by O.J. Helweg and H.H.M.

Hwang, 8/3/93, (PB94-141942, A06, MF-A02). NCEER-93-0013 "Simplified Procedures for Seismic Design of Nonstructural Components and Assessment of Current Code

Provisions," by M.P. Singh, L.E. Suarez, E.E. Matheu and G.O. Maldonado, 8/4/93, (PB94-141827, A09, MF-A02).

NCEER-93-0014 "An Energy Approach to Seismic Analysis and Design of Secondary Systems," by G. Chen and T.T. Soong,

8/6/93, (PB94-142767, A11, MF-A03).

Page 229: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

191

NCEER-93-0015 "Proceedings from School Sites: Becoming Prepared for Earthquakes - Commemorating the Third

Anniversary of the Loma Prieta Earthquake," Edited by F.E. Winslow and K.E.K. Ross, 8/16/93, (PB94-154275, A16, MF-A02).

NCEER-93-0016 "Reconnaissance Report of Damage to Historic Monuments in Cairo, Egypt Following the October 12, 1992

Dahshur Earthquake," by D. Sykora, D. Look, G. Croci, E. Karaesmen and E. Karaesmen, 8/19/93, (PB94-142221, A08, MF-A02).

NCEER-93-0017 "The Island of Guam Earthquake of August 8, 1993," by S.W. Swan and S.K. Harris, 9/30/93, (PB94-

141843, A04, MF-A01). NCEER-93-0018 "Engineering Aspects of the October 12, 1992 Egyptian Earthquake," by A.W. Elgamal, M. Amer, K.

Adalier and A. Abul-Fadl, 10/7/93, (PB94-141983, A05, MF-A01). NCEER-93-0019 "Development of an Earthquake Motion Simulator and its Application in Dynamic Centrifuge Testing," by I.

Krstelj, Supervised by J.H. Prevost, 10/23/93, (PB94-181773, A-10, MF-A03). NCEER-93-0020 "NCEER-Taisei Corporation Research Program on Sliding Seismic Isolation Systems for Bridges:

Experimental and Analytical Study of a Friction Pendulum System (FPS)," by M.C. Constantinou, P. Tsopelas, Y-S. Kim and S. Okamoto, 11/1/93, (PB94-142775, A08, MF-A02).

NCEER-93-0021 "Finite Element Modeling of Elastomeric Seismic Isolation Bearings," by L.J. Billings, Supervised by R.

Shepherd, 11/8/93, not available. NCEER-93-0022 "Seismic Vulnerability of Equipment in Critical Facilities: Life-Safety and Operational Consequences," by

K. Porter, G.S. Johnson, M.M. Zadeh, C. Scawthorn and S. Eder, 11/24/93, (PB94-181765, A16, MF-A03). NCEER-93-0023 "Hokkaido Nansei-oki, Japan Earthquake of July 12, 1993, by P.I. Yanev and C.R. Scawthorn, 12/23/93,

(PB94-181500, A07, MF-A01). NCEER-94-0001 "An Evaluation of Seismic Serviceability of Water Supply Networks with Application to the San Francisco

Auxiliary Water Supply System," by I. Markov, Supervised by M. Grigoriu and T. O'Rourke, 1/21/94, (PB94-204013, A07, MF-A02).

NCEER-94-0002 "NCEER-Taisei Corporation Research Program on Sliding Seismic Isolation Systems for Bridges:

Experimental and Analytical Study of Systems Consisting of Sliding Bearings, Rubber Restoring Force Devices and Fluid Dampers," Volumes I and II, by P. Tsopelas, S. Okamoto, M.C. Constantinou, D. Ozaki and S. Fujii, 2/4/94, (PB94-181740, A09, MF-A02 and PB94-181757, A12, MF-A03).

NCEER-94-0003 "A Markov Model for Local and Global Damage Indices in Seismic Analysis," by S. Rahman and M.

Grigoriu, 2/18/94, (PB94-206000, A12, MF-A03). NCEER-94-0004 "Proceedings from the NCEER Workshop on Seismic Response of Masonry Infills," edited by D.P. Abrams,

3/1/94, (PB94-180783, A07, MF-A02). NCEER-94-0005 "The Northridge, California Earthquake of January 17, 1994: General Reconnaissance Report," edited by

J.D. Goltz, 3/11/94, (PB94-193943, A10, MF-A03). NCEER-94-0006 "Seismic Energy Based Fatigue Damage Analysis of Bridge Columns: Part I - Evaluation of Seismic

Capacity," by G.A. Chang and J.B. Mander, 3/14/94, (PB94-219185, A11, MF-A03). NCEER-94-0007 "Seismic Isolation of Multi-Story Frame Structures Using Spherical Sliding Isolation Systems," by T.M. Al-

Hussaini, V.A. Zayas and M.C. Constantinou, 3/17/94, (PB94-193745, A09, MF-A02). NCEER-94-0008 "The Northridge, California Earthquake of January 17, 1994: Performance of Highway Bridges," edited by

I.G. Buckle, 3/24/94, (PB94-193851, A06, MF-A02). NCEER-94-0009 "Proceedings of the Third U.S.-Japan Workshop on Earthquake Protective Systems for Bridges," edited by

I.G. Buckle and I. Friedland, 3/31/94, (PB94-195815, A99, MF-A06).

Page 230: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

192

NCEER-94-0010 "3D-BASIS-ME: Computer Program for Nonlinear Dynamic Analysis of Seismically Isolated Single and Multiple Structures and Liquid Storage Tanks," by P.C. Tsopelas, M.C. Constantinou and A.M. Reinhorn, 4/12/94, (PB94-204922, A09, MF-A02).

NCEER-94-0011 "The Northridge, California Earthquake of January 17, 1994: Performance of Gas Transmission Pipelines,"

by T.D. O'Rourke and M.C. Palmer, 5/16/94, (PB94-204989, A05, MF-A01). NCEER-94-0012 "Feasibility Study of Replacement Procedures and Earthquake Performance Related to Gas Transmission

Pipelines," by T.D. O'Rourke and M.C. Palmer, 5/25/94, (PB94-206638, A09, MF-A02). NCEER-94-0013 "Seismic Energy Based Fatigue Damage Analysis of Bridge Columns: Part II - Evaluation of Seismic

Demand," by G.A. Chang and J.B. Mander, 6/1/94, (PB95-18106, A08, MF-A02). NCEER-94-0014 "NCEER-Taisei Corporation Research Program on Sliding Seismic Isolation Systems for Bridges:

Experimental and Analytical Study of a System Consisting of Sliding Bearings and Fluid Restoring Force/Damping Devices," by P. Tsopelas and M.C. Constantinou, 6/13/94, (PB94-219144, A10, MF-A03).

NCEER-94-0015 "Generation of Hazard-Consistent Fragility Curves for Seismic Loss Estimation Studies," by H. Hwang and

J-R. Huo, 6/14/94, (PB95-181996, A09, MF-A02). NCEER-94-0016 "Seismic Study of Building Frames with Added Energy-Absorbing Devices," by W.S. Pong, C.S. Tsai and

G.C. Lee, 6/20/94, (PB94-219136, A10, A03). NCEER-94-0017 "Sliding Mode Control for Seismic-Excited Linear and Nonlinear Civil Engineering Structures," by J. Yang,

J. Wu, A. Agrawal and Z. Li, 6/21/94, (PB95-138483, A06, MF-A02). NCEER-94-0018 "3D-BASIS-TABS Version 2.0: Computer Program for Nonlinear Dynamic Analysis of Three Dimensional

Base Isolated Structures," by A.M. Reinhorn, S. Nagarajaiah, M.C. Constantinou, P. Tsopelas and R. Li, 6/22/94, (PB95-182176, A08, MF-A02).

NCEER-94-0019 "Proceedings of the International Workshop on Civil Infrastructure Systems: Application of Intelligent

Systems and Advanced Materials on Bridge Systems," Edited by G.C. Lee and K.C. Chang, 7/18/94, (PB95-252474, A20, MF-A04).

NCEER-94-0020 "Study of Seismic Isolation Systems for Computer Floors," by V. Lambrou and M.C. Constantinou, 7/19/94,

(PB95-138533, A10, MF-A03). NCEER-94-0021 "Proceedings of the U.S.-Italian Workshop on Guidelines for Seismic Evaluation and Rehabilitation of

Unreinforced Masonry Buildings," Edited by D.P. Abrams and G.M. Calvi, 7/20/94, (PB95-138749, A13, MF-A03).

NCEER-94-0022 "NCEER-Taisei Corporation Research Program on Sliding Seismic Isolation Systems for Bridges:

Experimental and Analytical Study of a System Consisting of Lubricated PTFE Sliding Bearings and Mild Steel Dampers," by P. Tsopelas and M.C. Constantinou, 7/22/94, (PB95-182184, A08, MF-A02).

NCEER-94-0023 “Development of Reliability-Based Design Criteria for Buildings Under Seismic Load,” by Y.K. Wen, H.

Hwang and M. Shinozuka, 8/1/94, (PB95-211934, A08, MF-A02). NCEER-94-0024 “Experimental Verification of Acceleration Feedback Control Strategies for an Active Tendon System,” by

S.J. Dyke, B.F. Spencer, Jr., P. Quast, M.K. Sain, D.C. Kaspari, Jr. and T.T. Soong, 8/29/94, (PB95-212320, A05, MF-A01).

NCEER-94-0025 “Seismic Retrofitting Manual for Highway Bridges,” Edited by I.G. Buckle and I.F. Friedland, published by

the Federal Highway Administration (PB95-212676, A15, MF-A03). NCEER-94-0026 “Proceedings from the Fifth U.S.-Japan Workshop on Earthquake Resistant Design of Lifeline Facilities and

Countermeasures Against Soil Liquefaction,” Edited by T.D. O’Rourke and M. Hamada, 11/7/94, (PB95-220802, A99, MF-E08).

Page 231: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

193

NCEER-95-0001 “Experimental and Analytical Investigation of Seismic Retrofit of Structures with Supplemental Damping: Part 1 - Fluid Viscous Damping Devices,” by A.M. Reinhorn, C. Li and M.C. Constantinou, 1/3/95, (PB95-266599, A09, MF-A02).

NCEER-95-0002 “Experimental and Analytical Study of Low-Cycle Fatigue Behavior of Semi-Rigid Top-And-Seat Angle

Connections,” by G. Pekcan, J.B. Mander and S.S. Chen, 1/5/95, (PB95-220042, A07, MF-A02). NCEER-95-0003 “NCEER-ATC Joint Study on Fragility of Buildings,” by T. Anagnos, C. Rojahn and A.S. Kiremidjian,

1/20/95, (PB95-220026, A06, MF-A02). NCEER-95-0004 “Nonlinear Control Algorithms for Peak Response Reduction,” by Z. Wu, T.T. Soong, V. Gattulli and R.C.

Lin, 2/16/95, (PB95-220349, A05, MF-A01). NCEER-95-0005 “Pipeline Replacement Feasibility Study: A Methodology for Minimizing Seismic and Corrosion Risks to

Underground Natural Gas Pipelines,” by R.T. Eguchi, H.A. Seligson and D.G. Honegger, 3/2/95, (PB95-252326, A06, MF-A02).

NCEER-95-0006 “Evaluation of Seismic Performance of an 11-Story Frame Building During the 1994 Northridge

Earthquake,” by F. Naeim, R. DiSulio, K. Benuska, A. Reinhorn and C. Li, not available. NCEER-95-0007 “Prioritization of Bridges for Seismic Retrofitting,” by N. Basöz and A.S. Kiremidjian, 4/24/95, (PB95-

252300, A08, MF-A02). NCEER-95-0008 “Method for Developing Motion Damage Relationships for Reinforced Concrete Frames,” by A. Singhal and

A.S. Kiremidjian, 5/11/95, (PB95-266607, A06, MF-A02). NCEER-95-0009 “Experimental and Analytical Investigation of Seismic Retrofit of Structures with Supplemental Damping:

Part II - Friction Devices,” by C. Li and A.M. Reinhorn, 7/6/95, (PB96-128087, A11, MF-A03). NCEER-95-0010 “Experimental Performance and Analytical Study of a Non-Ductile Reinforced Concrete Frame Structure

Retrofitted with Elastomeric Spring Dampers,” by G. Pekcan, J.B. Mander and S.S. Chen, 7/14/95, (PB96-137161, A08, MF-A02).

NCEER-95-0011 “Development and Experimental Study of Semi-Active Fluid Damping Devices for Seismic Protection of

Structures,” by M.D. Symans and M.C. Constantinou, 8/3/95, (PB96-136940, A23, MF-A04). NCEER-95-0012 “Real-Time Structural Parameter Modification (RSPM): Development of Innervated Structures,” by Z.

Liang, M. Tong and G.C. Lee, 4/11/95, (PB96-137153, A06, MF-A01). NCEER-95-0013 “Experimental and Analytical Investigation of Seismic Retrofit of Structures with Supplemental Damping:

Part III - Viscous Damping Walls,” by A.M. Reinhorn and C. Li, 10/1/95, (PB96-176409, A11, MF-A03). NCEER-95-0014 “Seismic Fragility Analysis of Equipment and Structures in a Memphis Electric Substation,” by J-R. Huo and

H.H.M. Hwang, 8/10/95, (PB96-128087, A09, MF-A02). NCEER-95-0015 “The Hanshin-Awaji Earthquake of January 17, 1995: Performance of Lifelines,” Edited by M. Shinozuka,

11/3/95, (PB96-176383, A15, MF-A03). NCEER-95-0016 “Highway Culvert Performance During Earthquakes,” by T.L. Youd and C.J. Beckman, available as

NCEER-96-0015. NCEER-95-0017 “The Hanshin-Awaji Earthquake of January 17, 1995: Performance of Highway Bridges,” Edited by I.G.

Buckle, 12/1/95, not available. NCEER-95-0018 “Modeling of Masonry Infill Panels for Structural Analysis,” by A.M. Reinhorn, A. Madan, R.E. Valles, Y.

Reichmann and J.B. Mander, 12/8/95, (PB97-110886, MF-A01, A06). NCEER-95-0019 “Optimal Polynomial Control for Linear and Nonlinear Structures,” by A.K. Agrawal and J.N. Yang,

12/11/95, (PB96-168737, A07, MF-A02).

Page 232: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

194

NCEER-95-0020 “Retrofit of Non-Ductile Reinforced Concrete Frames Using Friction Dampers,” by R.S. Rao, P. Gergely and R.N. White, 12/22/95, (PB97-133508, A10, MF-A02).

NCEER-95-0021 “Parametric Results for Seismic Response of Pile-Supported Bridge Bents,” by G. Mylonakis, A. Nikolaou and G. Gazetas, 12/22/95, (PB97-100242, A12, MF-A03).

NCEER-95-0022 “Kinematic Bending Moments in Seismically Stressed Piles,” by A. Nikolaou, G. Mylonakis and G. Gazetas, 12/23/95, (PB97-113914, MF-A03, A13).

NCEER-96-0001 “Dynamic Response of Unreinforced Masonry Buildings with Flexible Diaphragms,” by A.C. Costley and D.P. Abrams,” 10/10/96, (PB97-133573, MF-A03, A15).

NCEER-96-0002 “State of the Art Review: Foundations and Retaining Structures,” by I. Po Lam, not available.

NCEER-96-0003 “Ductility of Rectangular Reinforced Concrete Bridge Columns with Moderate Confinement,” by N. Wehbe, M. Saiidi, D. Sanders and B. Douglas, 11/7/96, (PB97-133557, A06, MF-A02).

NCEER-96-0004 “Proceedings of the Long-Span Bridge Seismic Research Workshop,” edited by I.G. Buckle and I.M. Friedland, not available.

NCEER-96-0005 “Establish Representative Pier Types for Comprehensive Study: Eastern United States,” by J. Kulicki and Z. Prucz, 5/28/96, (PB98-119217, A07, MF-A02).

NCEER-96-0006 “Establish Representative Pier Types for Comprehensive Study: Western United States,” by R. Imbsen, R.A. Schamber and T.A. Osterkamp, 5/28/96, (PB98-118607, A07, MF-A02).

NCEER-96-0007 “Nonlinear Control Techniques for Dynamical Systems with Uncertain Parameters,” by R.G. Ghanem and M.I. Bujakov, 5/27/96, (PB97-100259, A17, MF-A03).

NCEER-96-0008 “Seismic Evaluation of a 30-Year Old Non-Ductile Highway Bridge Pier and Its Retrofit,” by J.B. Mander, B. Mahmoodzadegan, S. Bhadra and S.S. Chen, 5/31/96, (PB97-110902, MF-A03, A10).

NCEER-96-0009 “Seismic Performance of a Model Reinforced Concrete Bridge Pier Before and After Retrofit,” by J.B. Mander, J.H. Kim and C.A. Ligozio, 5/31/96, (PB97-110910, MF-A02, A10).

NCEER-96-0010 “IDARC2D Version 4.0: A Computer Program for the Inelastic Damage Analysis of Buildings,” by R.E. Valles, A.M. Reinhorn, S.K. Kunnath, C. Li and A. Madan, 6/3/96, (PB97-100234, A17, MF-A03).

NCEER-96-0011 “Estimation of the Economic Impact of Multiple Lifeline Disruption: Memphis Light, Gas and Water Division Case Study,” by S.E. Chang, H.A. Seligson and R.T. Eguchi, 8/16/96, (PB97-133490, A11, MF-A03).

NCEER-96-0012 “Proceedings from the Sixth Japan-U.S. Workshop on Earthquake Resistant Design of Lifeline Facilities and Countermeasures Against Soil Liquefaction, Edited by M. Hamada and T. O’Rourke, 9/11/96, (PB97-133581, A99, MF-A06).

NCEER-96-0013 “Chemical Hazards, Mitigation and Preparedness in Areas of High Seismic Risk: A Methodology for Estimating the Risk of Post-Earthquake Hazardous Materials Release,” by H.A. Seligson, R.T. Eguchi, K.J. Tierney and K. Richmond, 11/7/96, (PB97-133565, MF-A02, A08).

NCEER-96-0014 “Response of Steel Bridge Bearings to Reversed Cyclic Loading,” by J.B. Mander, D-K. Kim, S.S. Chen and G.J. Premus, 11/13/96, (PB97-140735, A12, MF-A03).

NCEER-96-0015 “Highway Culvert Performance During Past Earthquakes,” by T.L. Youd and C.J. Beckman, 11/25/96, (PB97-133532, A06, MF-A01).

NCEER-97-0001 “Evaluation, Prevention and Mitigation of Pounding Effects in Building Structures,” by R.E. Valles and A.M. Reinhorn, 2/20/97, (PB97-159552, A14, MF-A03).

NCEER-97-0002 “Seismic Design Criteria for Bridges and Other Highway Structures,” by C. Rojahn, R. Mayes, D.G. Anderson, J. Clark, J.H. Hom, R.V. Nutt and M.J. O’Rourke, 4/30/97, (PB97-194658, A06, MF-A03).

Page 233: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

195

NCEER-97-0003 “Proceedings of the U.S.-Italian Workshop on Seismic Evaluation and Retrofit,” Edited by D.P. Abrams and G.M. Calvi, 3/19/97, (PB97-194666, A13, MF-A03).

NCEER-97-0004 "Investigation of Seismic Response of Buildings with Linear and Nonlinear Fluid Viscous Dampers," by A.A. Seleemah and M.C. Constantinou, 5/21/97, (PB98-109002, A15, MF-A03).

NCEER-97-0005 "Proceedings of the Workshop on Earthquake Engineering Frontiers in Transportation Facilities," edited by G.C. Lee and I.M. Friedland, 8/29/97, (PB98-128911, A25, MR-A04).

NCEER-97-0006 "Cumulative Seismic Damage of Reinforced Concrete Bridge Piers," by S.K. Kunnath, A. El-Bahy, A. Taylor and W. Stone, 9/2/97, (PB98-108814, A11, MF-A03).

NCEER-97-0007 "Structural Details to Accommodate Seismic Movements of Highway Bridges and Retaining Walls," by R.A. Imbsen, R.A. Schamber, E. Thorkildsen, A. Kartoum, B.T. Martin, T.N. Rosser and J.M. Kulicki, 9/3/97, (PB98-108996, A09, MF-A02).

NCEER-97-0008 "A Method for Earthquake Motion-Damage Relationships with Application to Reinforced Concrete Frames," by A. Singhal and A.S. Kiremidjian, 9/10/97, (PB98-108988, A13, MF-A03).

NCEER-97-0009 "Seismic Analysis and Design of Bridge Abutments Considering Sliding and Rotation," by K. Fishman and R. Richards, Jr., 9/15/97, (PB98-108897, A06, MF-A02).

NCEER-97-0010 "Proceedings of the FHWA/NCEER Workshop on the National Representation of Seismic Ground Motion for New and Existing Highway Facilities," edited by I.M. Friedland, M.S. Power and R.L. Mayes, 9/22/97, (PB98-128903, A21, MF-A04).

NCEER-97-0011 "Seismic Analysis for Design or Retrofit of Gravity Bridge Abutments," by K.L. Fishman, R. Richards, Jr. and R.C. Divito, 10/2/97, (PB98-128937, A08, MF-A02).

NCEER-97-0012 "Evaluation of Simplified Methods of Analysis for Yielding Structures," by P. Tsopelas, M.C. Constantinou, C.A. Kircher and A.S. Whittaker, 10/31/97, (PB98-128929, A10, MF-A03).

NCEER-97-0013 "Seismic Design of Bridge Columns Based on Control and Repairability of Damage," by C-T. Cheng and J.B. Mander, 12/8/97, (PB98-144249, A11, MF-A03).

NCEER-97-0014 "Seismic Resistance of Bridge Piers Based on Damage Avoidance Design," by J.B. Mander and C-T. Cheng, 12/10/97, (PB98-144223, A09, MF-A02).

NCEER-97-0015 “Seismic Response of Nominally Symmetric Systems with Strength Uncertainty,” by S. Balopoulou and M. Grigoriu, 12/23/97, (PB98-153422, A11, MF-A03).

NCEER-97-0016 “Evaluation of Seismic Retrofit Methods for Reinforced Concrete Bridge Columns,” by T.J. Wipf, F.W. Klaiber and F.M. Russo, 12/28/97, (PB98-144215, A12, MF-A03).

NCEER-97-0017 “Seismic Fragility of Existing Conventional Reinforced Concrete Highway Bridges,” by C.L. Mullen and A.S. Cakmak, 12/30/97, (PB98-153406, A08, MF-A02).

NCEER-97-0018 “Loss Asssessment of Memphis Buildings,” edited by D.P. Abrams and M. Shinozuka, 12/31/97, (PB98-144231, A13, MF-A03).

NCEER-97-0019 “Seismic Evaluation of Frames with Infill Walls Using Quasi-static Experiments,” by K.M. Mosalam, R.N. White and P. Gergely, 12/31/97, (PB98-153455, A07, MF-A02).

NCEER-97-0020 “Seismic Evaluation of Frames with Infill Walls Using Pseudo-dynamic Experiments,” by K.M. Mosalam, R.N. White and P. Gergely, 12/31/97, (PB98-153430, A07, MF-A02).

NCEER-97-0021 “Computational Strategies for Frames with Infill Walls: Discrete and Smeared Crack Analyses and Seismic Fragility,” by K.M. Mosalam, R.N. White and P. Gergely, 12/31/97, (PB98-153414, A10, MF-A02).

Page 234: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

196

NCEER-97-0022 “Proceedings of the NCEER Workshop on Evaluation of Liquefaction Resistance of Soils,” edited by T.L. Youd and I.M. Idriss, 12/31/97, (PB98-155617, A15, MF-A03).

MCEER-98-0001 “Extraction of Nonlinear Hysteretic Properties of Seismically Isolated Bridges from Quick-Release Field Tests,” by Q. Chen, B.M. Douglas, E.M. Maragakis and I.G. Buckle, 5/26/98, (PB99-118838, A06, MF- A01).

MCEER-98-0002 “Methodologies for Evaluating the Importance of Highway Bridges,” by A. Thomas, S. Eshenaur and J. Kulicki, 5/29/98, (PB99-118846, A10, MF-A02).

MCEER-98-0003 “Capacity Design of Bridge Piers and the Analysis of Overstrength,” by J.B. Mander, A. Dutta and P. Goel, 6/1/98, (PB99-118853, A09, MF-A02).

MCEER-98-0004 “Evaluation of Bridge Damage Data from the Loma Prieta and Northridge, California Earthquakes,” by N. Basoz and A. Kiremidjian, 6/2/98, (PB99-118861, A15, MF-A03).

MCEER-98-0005 “Screening Guide for Rapid Assessment of Liquefaction Hazard at Highway Bridge Sites,” by T. L. Youd, 6/16/98, (PB99-118879, A06, not available on microfiche).

MCEER-98-0006 “Structural Steel and Steel/Concrete Interface Details for Bridges,” by P. Ritchie, N. Kauhl and J. Kulicki, 7/13/98, (PB99-118945, A06, MF-A01).

MCEER-98-0007 “Capacity Design and Fatigue Analysis of Confined Concrete Columns,” by A. Dutta and J.B. Mander, 7/14/98, (PB99-118960, A14, MF-A03).

MCEER-98-0008 “Proceedings of the Workshop on Performance Criteria for Telecommunication Services Under Earthquake Conditions,” edited by A.J. Schiff, 7/15/98, (PB99-118952, A08, MF-A02).

MCEER-98-0009 “Fatigue Analysis of Unconfined Concrete Columns,” by J.B. Mander, A. Dutta and J.H. Kim, 9/12/98, (PB99-123655, A10, MF-A02).

MCEER-98-0010 “Centrifuge Modeling of Cyclic Lateral Response of Pile-Cap Systems and Seat-Type Abutments in Dry Sands,” by A.D. Gadre and R. Dobry, 10/2/98, (PB99-123606, A13, MF-A03).

MCEER-98-0011 “IDARC-BRIDGE: A Computational Platform for Seismic Damage Assessment of Bridge Structures,” by A.M. Reinhorn, V. Simeonov, G. Mylonakis and Y. Reichman, 10/2/98, (PB99-162919, A15, MF-A03).

MCEER-98-0012 “Experimental Investigation of the Dynamic Response of Two Bridges Before and After Retrofitting with Elastomeric Bearings,” by D.A. Wendichansky, S.S. Chen and J.B. Mander, 10/2/98, (PB99-162927, A15, MF-A03).

MCEER-98-0013 “Design Procedures for Hinge Restrainers and Hinge Sear Width for Multiple-Frame Bridges,” by R. Des Roches and G.L. Fenves, 11/3/98, (PB99-140477, A13, MF-A03).

MCEER-98-0014 “Response Modification Factors for Seismically Isolated Bridges,” by M.C. Constantinou and J.K. Quarshie, 11/3/98, (PB99-140485, A14, MF-A03).

MCEER-98-0015 “Proceedings of the U.S.-Italy Workshop on Seismic Protective Systems for Bridges,” edited by I.M. Friedland and M.C. Constantinou, 11/3/98, (PB2000-101711, A22, MF-A04).

MCEER-98-0016 “Appropriate Seismic Reliability for Critical Equipment Systems: Recommendations Based on Regional Analysis of Financial and Life Loss,” by K. Porter, C. Scawthorn, C. Taylor and N. Blais, 11/10/98, (PB99-157265, A08, MF-A02).

MCEER-98-0017 “Proceedings of the U.S. Japan Joint Seminar on Civil Infrastructure Systems Research,” edited by M. Shinozuka and A. Rose, 11/12/98, (PB99-156713, A16, MF-A03).

MCEER-98-0018 “Modeling of Pile Footings and Drilled Shafts for Seismic Design,” by I. PoLam, M. Kapuskar and D. Chaudhuri, 12/21/98, (PB99-157257, A09, MF-A02).

Page 235: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

197

MCEER-99-0001 "Seismic Evaluation of a Masonry Infilled Reinforced Concrete Frame by Pseudodynamic Testing," by S.G. Buonopane and R.N. White, 2/16/99, (PB99-162851, A09, MF-A02).

MCEER-99-0002 "Response History Analysis of Structures with Seismic Isolation and Energy Dissipation Systems:

Verification Examples for Program SAP2000," by J. Scheller and M.C. Constantinou, 2/22/99, (PB99-162869, A08, MF-A02).

MCEER-99-0003 "Experimental Study on the Seismic Design and Retrofit of Bridge Columns Including Axial Load Effects,"

by A. Dutta, T. Kokorina and J.B. Mander, 2/22/99, (PB99-162877, A09, MF-A02). MCEER-99-0004 "Experimental Study of Bridge Elastomeric and Other Isolation and Energy Dissipation Systems with

Emphasis on Uplift Prevention and High Velocity Near-source Seismic Excitation," by A. Kasalanati and M. C. Constantinou, 2/26/99, (PB99-162885, A12, MF-A03).

MCEER-99-0005 "Truss Modeling of Reinforced Concrete Shear-flexure Behavior," by J.H. Kim and J.B. Mander, 3/8/99,

(PB99-163693, A12, MF-A03). MCEER-99-0006 "Experimental Investigation and Computational Modeling of Seismic Response of a 1:4 Scale Model Steel

Structure with a Load Balancing Supplemental Damping System," by G. Pekcan, J.B. Mander and S.S. Chen, 4/2/99, (PB99-162893, A11, MF-A03).

MCEER-99-0007 "Effect of Vertical Ground Motions on the Structural Response of Highway Bridges," by M.R. Button, C.J.

Cronin and R.L. Mayes, 4/10/99, (PB2000-101411, A10, MF-A03). MCEER-99-0008 "Seismic Reliability Assessment of Critical Facilities: A Handbook, Supporting Documentation, and Model

Code Provisions," by G.S. Johnson, R.E. Sheppard, M.D. Quilici, S.J. Eder and C.R. Scawthorn, 4/12/99, (PB2000-101701, A18, MF-A04).

MCEER-99-0009 "Impact Assessment of Selected MCEER Highway Project Research on the Seismic Design of Highway

Structures," by C. Rojahn, R. Mayes, D.G. Anderson, J.H. Clark, D'Appolonia Engineering, S. Gloyd and R.V. Nutt, 4/14/99, (PB99-162901, A10, MF-A02).

MCEER-99-0010 "Site Factors and Site Categories in Seismic Codes," by R. Dobry, R. Ramos and M.S. Power, 7/19/99,

(PB2000-101705, A08, MF-A02). MCEER-99-0011 "Restrainer Design Procedures for Multi-Span Simply-Supported Bridges," by M.J. Randall, M. Saiidi, E.

Maragakis and T. Isakovic, 7/20/99, (PB2000-101702, A10, MF-A02). MCEER-99-0012 "Property Modification Factors for Seismic Isolation Bearings," by M.C. Constantinou, P. Tsopelas, A.

Kasalanati and E. Wolff, 7/20/99, (PB2000-103387, A11, MF-A03). MCEER-99-0013 "Critical Seismic Issues for Existing Steel Bridges," by P. Ritchie, N. Kauhl and J. Kulicki, 7/20/99,

(PB2000-101697, A09, MF-A02). MCEER-99-0014 "Nonstructural Damage Database," by A. Kao, T.T. Soong and A. Vender, 7/24/99, (PB2000-101407, A06,

MF-A01). MCEER-99-0015 "Guide to Remedial Measures for Liquefaction Mitigation at Existing Highway Bridge Sites," by H.G.

Cooke and J. K. Mitchell, 7/26/99, (PB2000-101703, A11, MF-A03). MCEER-99-0016 "Proceedings of the MCEER Workshop on Ground Motion Methodologies for the Eastern United States,"

edited by N. Abrahamson and A. Becker, 8/11/99, (PB2000-103385, A07, MF-A02). MCEER-99-0017 "Quindío, Colombia Earthquake of January 25, 1999: Reconnaissance Report," by A.P. Asfura and P.J.

Flores, 10/4/99, (PB2000-106893, A06, MF-A01). MCEER-99-0018 "Hysteretic Models for Cyclic Behavior of Deteriorating Inelastic Structures," by M.V. Sivaselvan and A.M.

Reinhorn, 11/5/99, (PB2000-103386, A08, MF-A02).

Page 236: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

198

MCEER-99-0019 "Proceedings of the 7th U.S.- Japan Workshop on Earthquake Resistant Design of Lifeline Facilities and Countermeasures Against Soil Liquefaction," edited by T.D. O'Rourke, J.P. Bardet and M. Hamada, 11/19/99, (PB2000-103354, A99, MF-A06).

MCEER-99-0020 "Development of Measurement Capability for Micro-Vibration Evaluations with Application to Chip Fabrication Facilities," by G.C. Lee, Z. Liang, J.W. Song, J.D. Shen and W.C. Liu, 12/1/99, (PB2000-105993, A08, MF-A02).

MCEER-99-0021 "Design and Retrofit Methodology for Building Structures with Supplemental Energy Dissipating Systems," by G. Pekcan, J.B. Mander and S.S. Chen, 12/31/99, (PB2000-105994, A11, MF-A03).

MCEER-00-0001 "The Marmara, Turkey Earthquake of August 17, 1999: Reconnaissance Report," edited by C. Scawthorn; with major contributions by M. Bruneau, R. Eguchi, T. Holzer, G. Johnson, J. Mander, J. Mitchell, W. Mitchell, A. Papageorgiou, C. Scaethorn, and G. Webb, 3/23/00, (PB2000-106200, A11, MF-A03).

MCEER-00-0002 "Proceedings of the MCEER Workshop for Seismic Hazard Mitigation of Health Care Facilities," edited by G.C. Lee, M. Ettouney, M. Grigoriu, J. Hauer and J. Nigg, 3/29/00, (PB2000-106892, A08, MF-A02).

MCEER-00-0003 "The Chi-Chi, Taiwan Earthquake of September 21, 1999: Reconnaissance Report," edited by G.C. Lee and C.H. Loh, with major contributions by G.C. Lee, M. Bruneau, I.G. Buckle, S.E. Chang, P.J. Flores, T.D.O'Rourke, M. Shinozuka, T.T. Soong, C-H. Loh, K-C. Chang, Z-J. Chen, J-S. Hwang, M-L. Lin, G-Y. Liu,K-C. Tsai, G.C. Yao and C-L. Yen, 4/30/00, (PB2001-100980, A10, MF-A02).

MCEER-00-0004 "Seismic Retrofit of End-Sway Frames of Steel Deck-Truss Bridges with a Supplemental Tendon System: Experimental and Analytical Investigation," by G. Pekcan, J.B. Mander and S.S. Chen, 7/1/00, (PB2001-100982, A10, MF-A02).

MCEER-00-0005 "Sliding Fragility of Unrestrained Equipment in Critical Facilities," by W.H. Chong and T.T. Soong, 7/5/00, (PB2001-100983, A08, MF-A02).

MCEER-00-0006 "Seismic Response of Reinforced Concrete Bridge Pier Walls in the Weak Direction," by N. Abo-Shadi, M. Saiidi and D. Sanders, 7/17/00, (PB2001-100981, A17, MF-A03).

MCEER-00-0007 "Low-Cycle Fatigue Behavior of Longitudinal Reinforcement in Reinforced Concrete Bridge Columns," by J. Brown and S.K. Kunnath, 7/23/00, (PB2001-104392, A08, MF-A02).

MCEER-00-0008 "Soil Structure Interaction of Bridges for Seismic Analysis," I. PoLam and H. Law, 9/25/00, (PB2001-105397, A08, MF-A02).

MCEER-00-0009 "Proceedings of the First MCEER Workshop on Mitigation of Earthquake Disaster by Advanced Technologies (MEDAT-1), edited by M. Shinozuka, D.J. Inman and T.D. O'Rourke, 11/10/00, (PB2001-105399, A14, MF-A03).

MCEER-00-0010 "Development and Evaluation of Simplified Procedures for Analysis and Design of Buildings with Passive Energy Dissipation Systems, Revision 01," by O.M. Ramirez, M.C. Constantinou, C.A. Kircher, A.S. Whittaker, M.W. Johnson, J.D. Gomez and C. Chrysostomou, 11/16/01, (PB2001-105523, A23, MF-A04).

MCEER-00-0011 "Dynamic Soil-Foundation-Structure Interaction Analyses of Large Caissons," by C-Y. Chang, C-M. Mok, Z-L. Wang, R. Settgast, F. Waggoner, M.A. Ketchum, H.M. Gonnermann and C-C. Chin, 12/30/00,(PB2001-104373, A07, MF-A02).

MCEER-00-0012 "Experimental Evaluation of Seismic Performance of Bridge Restrainers," by A.G. Vlassis, E.M. Maragakis and M. Saiid Saiidi, 12/30/00, (PB2001-104354, A09, MF-A02).

MCEER-00-0013 "Effect of Spatial Variation of Ground Motion on Highway Structures," by M. Shinozuka, V. Saxena and G. Deodatis, 12/31/00, (PB2001-108755, A13, MF-A03).

MCEER-00-0014 "A Risk-Based Methodology for Assessing the Seismic Performance of Highway Systems," by S.D. Werner, C.E. Taylor, J.E. Moore, II, J.S. Walton and S. Cho, 12/31/00, (PB2001-108756, A14, MF-A03).

Page 237: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

199

MCEER-01-0001 “Experimental Investigation of P-Delta Effects to Collapse During Earthquakes,” by D. Vian and M. Bruneau, 6/25/01, (PB2002-100534, A17, MF-A03).

MCEER-01-0002 “Proceedings of the Second MCEER Workshop on Mitigation of Earthquake Disaster by Advanced Technologies (MEDAT-2),” edited by M. Bruneau and D.J. Inman, 7/23/01, (PB2002-100434, A16, MF-A03).

MCEER-01-0003 “Sensitivity Analysis of Dynamic Systems Subjected to Seismic Loads,” by C. Roth and M. Grigoriu, 9/18/01, (PB2003-100884, A12, MF-A03).

MCEER-01-0004 “Overcoming Obstacles to Implementing Earthquake Hazard Mitigation Policies: Stage 1 Report,” by D.J. Alesch and W.J. Petak, 12/17/01, (PB2002-107949, A07, MF-A02).

MCEER-01-0005 “Updating Real-Time Earthquake Loss Estimates: Methods, Problems and Insights,” by C.E. Taylor, S.E. Chang and R.T. Eguchi, 12/17/01, (PB2002-107948, A05, MF-A01).

MCEER-01-0006 “Experimental Investigation and Retrofit of Steel Pile Foundations and Pile Bents Under Cyclic Lateral Loadings,” by A. Shama, J. Mander, B. Blabac and S. Chen, 12/31/01, (PB2002-107950, A13, MF-A03).

MCEER-02-0001 “Assessment of Performance of Bolu Viaduct in the 1999 Duzce Earthquake in Turkey” by P.C. Roussis, M.C. Constantinou, M. Erdik, E. Durukal and M. Dicleli, 5/8/02, (PB2003-100883, A08, MF-A02).

MCEER-02-0002 “Seismic Behavior of Rail Counterweight Systems of Elevators in Buildings,” by M.P. Singh, Rildova and L.E. Suarez, 5/27/02. (PB2003-100882, A11, MF-A03).

MCEER-02-0003 “Development of Analysis and Design Procedures for Spread Footings,” by G. Mylonakis, G. Gazetas, S. Nikolaou and A. Chauncey, 10/02/02, (PB2004-101636, A13, MF-A03, CD-A13).

MCEER-02-0004 “Bare-Earth Algorithms for Use with SAR and LIDAR Digital Elevation Models,” by C.K. Huyck, R.T. Eguchi and B. Houshmand, 10/16/02, (PB2004-101637, A07, CD-A07).

MCEER-02-0005 “Review of Energy Dissipation of Compression Members in Concentrically Braced Frames,” by K.Lee and M. Bruneau, 10/18/02, (PB2004-101638, A10, CD-A10).

MCEER-03-0001 “Experimental Investigation of Light-Gauge Steel Plate Shear Walls for the Seismic Retrofit of Buildings” by J. Berman and M. Bruneau, 5/2/03, (PB2004-101622, A10, MF-A03, CD-A10).

MCEER-03-0002 “Statistical Analysis of Fragility Curves,” by M. Shinozuka, M.Q. Feng, H. Kim, T. Uzawa and T. Ueda, 6/16/03, (PB2004-101849, A09, CD-A09).

MCEER-03-0003 “Proceedings of the Eighth U.S.-Japan Workshop on Earthquake Resistant Design f Lifeline Facilities and Countermeasures Against Liquefaction,” edited by M. Hamada, J.P. Bardet and T.D. O’Rourke, 6/30/03, (PB2004-104386, A99, CD-A99).

MCEER-03-0004 “Proceedings of the PRC-US Workshop on Seismic Analysis and Design of Special Bridges,” edited by L.C. Fan and G.C. Lee, 7/15/03, (PB2004-104387, A14, CD-A14).

MCEER-03-0005 “Urban Disaster Recovery: A Framework and Simulation Model,” by S.B. Miles and S.E. Chang, 7/25/03, (PB2004-104388, A07, CD-A07).

MCEER-03-0006 “Behavior of Underground Piping Joints Due to Static and Dynamic Loading,” by R.D. Meis, M. Maragakis and R. Siddharthan, 11/17/03, (PB2005-102194, A13, MF-A03, CD-A00).

MCEER-04-0001 “Experimental Study of Seismic Isolation Systems with Emphasis on Secondary System Response and Verification of Accuracy of Dynamic Response History Analysis Methods,” by E. Wolff and M. Constantinou, 1/16/04 (PB2005-102195, A99, MF-E08, CD-A00).

MCEER-04-0002 “Tension, Compression and Cyclic Testing of Engineered Cementitious Composite Materials,” by K. Kesner and S.L. Billington, 3/1/04, (PB2005-102196, A08, CD-A08).

Page 238: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

200

MCEER-04-0003 “Cyclic Testing of Braces Laterally Restrained by Steel Studs to Enhance Performance During Earthquakes,” by O.C. Celik, J.W. Berman and M. Bruneau, 3/16/04, (PB2005-102197, A13, MF-A03, CD-A00).

MCEER-04-0004 “Methodologies for Post Earthquake Building Damage Detection Using SAR and Optical Remote Sensing: Application to the August 17, 1999 Marmara, Turkey Earthquake,” by C.K. Huyck, B.J. Adams, S. Cho, R.T. Eguchi, B. Mansouri and B. Houshmand, 6/15/04, (PB2005-104888, A10, CD-A00).

MCEER-04-0005 “Nonlinear Structural Analysis Towards Collapse Simulation: A Dynamical Systems Approach,” by M.V. Sivaselvan and A.M. Reinhorn, 6/16/04, (PB2005-104889, A11, MF-A03, CD-A00).

MCEER-04-0006 “Proceedings of the Second PRC-US Workshop on Seismic Analysis and Design of Special Bridges,” edited by G.C. Lee and L.C. Fan, 6/25/04, (PB2005-104890, A16, CD-A00).

MCEER-04-0007 “Seismic Vulnerability Evaluation of Axially Loaded Steel Built-up Laced Members,” by K. Lee and M. Bruneau, 6/30/04, (PB2005-104891, A16, CD-A00).

MCEER-04-0008 “Evaluation of Accuracy of Simplified Methods of Analysis and Design of Buildings with Damping Systems for Near-Fault and for Soft-Soil Seismic Motions,” by E.A. Pavlou and M.C. Constantinou, 8/16/04, (PB2005-104892, A08, MF-A02, CD-A00).

MCEER-04-0009 “Assessment of Geotechnical Issues in Acute Care Facilities in California,” by M. Lew, T.D. O’Rourke, R. Dobry and M. Koch, 9/15/04, (PB2005-104893, A08, CD-A00).

MCEER-04-0010 “Scissor-Jack-Damper Energy Dissipation System,” by A.N. Sigaher-Boyle and M.C. Constantinou, 12/1/04 (PB2005-108221).

MCEER-04-0011 “Seismic Retrofit of Bridge Steel Truss Piers Using a Controlled Rocking Approach,” by M. Pollino and M. Bruneau, 12/20/04 (PB2006-105795).

MCEER-05-0001 “Experimental and Analytical Studies of Structures Seismically Isolated with an Uplift-Restraint Isolation System,” by P.C. Roussis and M.C. Constantinou, 1/10/05 (PB2005-108222).

MCEER-05-0002 “A Versatile Experimentation Model for Study of Structures Near Collapse Applied to Seismic Evaluation of Irregular Structures,” by D. Kusumastuti, A.M. Reinhorn and A. Rutenberg, 3/31/05 (PB2006-101523).

MCEER-05-0003 “Proceedings of the Third PRC-US Workshop on Seismic Analysis and Design of Special Bridges,” edited by L.C. Fan and G.C. Lee, 4/20/05, (PB2006-105796).

MCEER-05-0004 “Approaches for the Seismic Retrofit of Braced Steel Bridge Piers and Proof-of-Concept Testing of an Eccentrically Braced Frame with Tubular Link,” by J.W. Berman and M. Bruneau, 4/21/05 (PB2006-101524).

MCEER-05-0005 “Simulation of Strong Ground Motions for Seismic Fragility Evaluation of Nonstructural Components in Hospitals,” by A. Wanitkorkul and A. Filiatrault, 5/26/05 (PB2006-500027).

MCEER-05-0006 “Seismic Safety in California Hospitals: Assessing an Attempt to Accelerate the Replacement or Seismic Retrofit of Older Hospital Facilities,” by D.J. Alesch, L.A. Arendt and W.J. Petak, 6/6/05 (PB2006-105794).

MCEER-05-0007 “Development of Seismic Strengthening and Retrofit Strategies for Critical Facilities Using Engineered Cementitious Composite Materials,” by K. Kesner and S.L. Billington, 8/29/05 (PB2006-111701).

MCEER-05-0008 “Experimental and Analytical Studies of Base Isolation Systems for Seismic Protection of Power Transformers,” by N. Murota, M.Q. Feng and G-Y. Liu, 9/30/05 (PB2006-111702).

MCEER-05-0009 “3D-BASIS-ME-MB: Computer Program for Nonlinear Dynamic Analysis of Seismically Isolated Structures,” by P.C. Tsopelas, P.C. Roussis, M.C. Constantinou, R. Buchanan and A.M. Reinhorn, 10/3/05 (PB2006-111703).

MCEER-05-0010 “Steel Plate Shear Walls for Seismic Design and Retrofit of Building Structures,” by D. Vian and M. Bruneau, 12/15/05 (PB2006-111704).

Page 239: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

201

MCEER-05-0011 “The Performance-Based Design Paradigm,” by M.J. Astrella and A. Whittaker, 12/15/05 (PB2006-111705).

MCEER-06-0001 “Seismic Fragility of Suspended Ceiling Systems,” H. Badillo-Almaraz, A.S. Whittaker, A.M. Reinhorn and G.P. Cimellaro, 2/4/06 (PB2006-111706).

MCEER-06-0002 “Multi-Dimensional Fragility of Structures,” by G.P. Cimellaro, A.M. Reinhorn and M. Bruneau, 3/1/06 (PB2007-106974, A09, MF-A02, CD A00).

MCEER-06-0003 “Built-Up Shear Links as Energy Dissipators for Seismic Protection of Bridges,” by P. Dusicka, A.M. Itani and I.G. Buckle, 3/15/06 (PB2006-111708).

MCEER-06-0004 “Analytical Investigation of the Structural Fuse Concept,” by R.E. Vargas and M. Bruneau, 3/16/06 (PB2006-111709).

MCEER-06-0005 “Experimental Investigation of the Structural Fuse Concept,” by R.E. Vargas and M. Bruneau, 3/17/06 (PB2006-111710).

MCEER-06-0006 “Further Development of Tubular Eccentrically Braced Frame Links for the Seismic Retrofit of Braced Steel Truss Bridge Piers,” by J.W. Berman and M. Bruneau, 3/27/06 (PB2007-105147).

MCEER-06-0007 “REDARS Validation Report,” by S. Cho, C.K. Huyck, S. Ghosh and R.T. Eguchi, 8/8/06 (PB2007-106983).

MCEER-06-0008 “Review of Current NDE Technologies for Post-Earthquake Assessment of Retrofitted Bridge Columns,” by J.W. Song, Z. Liang and G.C. Lee, 8/21/06 (PB2007-106984).

MCEER-06-0009 “Liquefaction Remediation in Silty Soils Using Dynamic Compaction and Stone Columns,” by S. Thevanayagam, G.R. Martin, R. Nashed, T. Shenthan, T. Kanagalingam and N. Ecemis, 8/28/06 (PB2007-106985).

MCEER-06-0010 “Conceptual Design and Experimental Investigation of Polymer Matrix Composite Infill Panels for Seismic Retrofitting,” by W. Jung, M. Chiewanichakorn and A.J. Aref, 9/21/06 (PB2007-106986).

MCEER-06-0011 “A Study of the Coupled Horizontal-Vertical Behavior of Elastomeric and Lead-Rubber Seismic Isolation Bearings,” by G.P. Warn and A.S. Whittaker, 9/22/06 (PB2007-108679).

MCEER-06-0012 “Proceedings of the Fourth PRC-US Workshop on Seismic Analysis and Design of Special Bridges: Advancing Bridge Technologies in Research, Design, Construction and Preservation,” Edited by L.C. Fan, G.C. Lee and L. Ziang, 10/12/06 (PB2007-109042).

MCEER-06-0013 “Cyclic Response and Low Cycle Fatigue Characteristics of Plate Steels,” by P. Dusicka, A.M. Itani and I.G. Buckle, 11/1/06 06 (PB2007-106987).

MCEER-06-0014 “Proceedings of the Second US-Taiwan Bridge Engineering Workshop,” edited by W.P. Yen, J. Shen, J-Y. Chen and M. Wang, 11/15/06 (PB2008-500041).

MCEER-06-0015 “User Manual and Technical Documentation for the REDARSTM Import Wizard,” by S. Cho, S. Ghosh, C.K. Huyck and S.D. Werner, 11/30/06 (PB2007-114766).

MCEER-06-0016 “Hazard Mitigation Strategy and Monitoring Technologies for Urban and Infrastructure Public Buildings: Proceedings of the China-US Workshops,” edited by X.Y. Zhou, A.L. Zhang, G.C. Lee and M. Tong, 12/12/06 (PB2008-500018).

MCEER-07-0001 “Static and Kinetic Coefficients of Friction for Rigid Blocks,” by C. Kafali, S. Fathali, M. Grigoriu and A.S. Whittaker, 3/20/07 (PB2007-114767).

MCEER-07-0002 “Hazard Mitigation Investment Decision Making: Organizational Response to Legislative Mandate,” by L.A. Arendt, D.J. Alesch and W.J. Petak, 4/9/07 (PB2007-114768).

MCEER-07-0003 “Seismic Behavior of Bidirectional-Resistant Ductile End Diaphragms with Unbonded Braces in Straight or Skewed Steel Bridges,” by O. Celik and M. Bruneau, 4/11/07 (PB2008-105141).

Page 240: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

202

MCEER-07-0004 “Modeling Pile Behavior in Large Pile Groups Under Lateral Loading,” by A.M. Dodds and G.R. Martin, 4/16/07(PB2008-105142).

MCEER-07-0005 “Experimental Investigation of Blast Performance of Seismically Resistant Concrete-Filled Steel Tube

Bridge Piers,” by S. Fujikura, M. Bruneau and D. Lopez-Garcia, 4/20/07 (PB2008-105143). MCEER-07-0006 “Seismic Analysis of Conventional and Isolated Liquefied Natural Gas Tanks Using Mechanical Analogs,”

by I.P. Christovasilis and A.S. Whittaker, 5/1/07, not available. MCEER-07-0007 “Experimental Seismic Performance Evaluation of Isolation/Restraint Systems for Mechanical Equipment –

Part 1: Heavy Equipment Study,” by S. Fathali and A. Filiatrault, 6/6/07 (PB2008-105144). MCEER-07-0008 “Seismic Vulnerability of Timber Bridges and Timber Substructures,” by A.A. Sharma, J.B. Mander, I.M.

Friedland and D.R. Allicock, 6/7/07 (PB2008-105145). MCEER-07-0009 “Experimental and Analytical Study of the XY-Friction Pendulum (XY-FP) Bearing for Bridge

Applications,” by C.C. Marin-Artieda, A.S. Whittaker and M.C. Constantinou, 6/7/07 (PB2008-105191). MCEER-07-0010 “Proceedings of the PRC-US Earthquake Engineering Forum for Young Researchers,” Edited by G.C. Lee

and X.Z. Qi, 6/8/07 (PB2008-500058). MCEER-07-0011 “Design Recommendations for Perforated Steel Plate Shear Walls,” by R. Purba and M. Bruneau, 6/18/07,

(PB2008-105192). MCEER-07-0012 “Performance of Seismic Isolation Hardware Under Service and Seismic Loading,” by M.C. Constantinou,

A.S. Whittaker, Y. Kalpakidis, D.M. Fenz and G.P. Warn, 8/27/07, (PB2008-105193). MCEER-07-0013 “Experimental Evaluation of the Seismic Performance of Hospital Piping Subassemblies,” by E.R. Goodwin,

E. Maragakis and A.M. Itani, 9/4/07, (PB2008-105194). MCEER-07-0014 “A Simulation Model of Urban Disaster Recovery and Resilience: Implementation for the 1994 Northridge

Earthquake,” by S. Miles and S.E. Chang, 9/7/07, (PB2008-106426). MCEER-07-0015 “Statistical and Mechanistic Fragility Analysis of Concrete Bridges,” by M. Shinozuka, S. Banerjee and S-H.

Kim, 9/10/07, (PB2008-106427). MCEER-07-0016 “Three-Dimensional Modeling of Inelastic Buckling in Frame Structures,” by M. Schachter and AM.

Reinhorn, 9/13/07, (PB2008-108125). MCEER-07-0017 “Modeling of Seismic Wave Scattering on Pile Groups and Caissons,” by I. Po Lam, H. Law and C.T. Yang,

9/17/07 (PB2008-108150). MCEER-07-0018 “Bridge Foundations: Modeling Large Pile Groups and Caissons for Seismic Design,” by I. Po Lam, H. Law

and G.R. Martin (Coordinating Author), 12/1/07 (PB2008-111190). MCEER-07-0019 “Principles and Performance of Roller Seismic Isolation Bearings for Highway Bridges,” by G.C. Lee, Y.C.

Ou, Z. Liang, T.C. Niu and J. Song, 12/10/07 (PB2009-110466). MCEER-07-0020 “Centrifuge Modeling of Permeability and Pinning Reinforcement Effects on Pile Response to Lateral

Spreading,” by L.L Gonzalez-Lagos, T. Abdoun and R. Dobry, 12/10/07 (PB2008-111191). MCEER-07-0021 “Damage to the Highway System from the Pisco, Perú Earthquake of August 15, 2007,” by J.S. O’Connor,

L. Mesa and M. Nykamp, 12/10/07, (PB2008-108126). MCEER-07-0022 “Experimental Seismic Performance Evaluation of Isolation/Restraint Systems for Mechanical Equipment –

Part 2: Light Equipment Study,” by S. Fathali and A. Filiatrault, 12/13/07 (PB2008-111192). MCEER-07-0023 “Fragility Considerations in Highway Bridge Design,” by M. Shinozuka, S. Banerjee and S.H. Kim, 12/14/07

(PB2008-111193).

Page 241: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

203

MCEER-07-0024 “Performance Estimates for Seismically Isolated Bridges,” by G.P. Warn and A.S. Whittaker, 12/30/07 (PB2008-112230).

MCEER-08-0001 “Seismic Performance of Steel Girder Bridge Superstructures with Conventional Cross Frames,” by L.P. Carden, A.M. Itani and I.G. Buckle, 1/7/08, (PB2008-112231).

MCEER-08-0002 “Seismic Performance of Steel Girder Bridge Superstructures with Ductile End Cross Frames with Seismic Isolators,” by L.P. Carden, A.M. Itani and I.G. Buckle, 1/7/08 (PB2008-112232).

MCEER-08-0003 “Analytical and Experimental Investigation of a Controlled Rocking Approach for Seismic Protection of Bridge Steel Truss Piers,” by M. Pollino and M. Bruneau, 1/21/08 (PB2008-112233).

MCEER-08-0004 “Linking Lifeline Infrastructure Performance and Community Disaster Resilience: Models and Multi-Stakeholder Processes,” by S.E. Chang, C. Pasion, K. Tatebe and R. Ahmad, 3/3/08 (PB2008-112234).

MCEER-08-0005 “Modal Analysis of Generally Damped Linear Structures Subjected to Seismic Excitations,” by J. Song, Y-L. Chu, Z. Liang and G.C. Lee, 3/4/08 (PB2009-102311).

MCEER-08-0006 “System Performance Under Multi-Hazard Environments,” by C. Kafali and M. Grigoriu, 3/4/08 (PB2008-112235).

MCEER-08-0007 “Mechanical Behavior of Multi-Spherical Sliding Bearings,” by D.M. Fenz and M.C. Constantinou, 3/6/08 (PB2008-112236).

MCEER-08-0008 “Post-Earthquake Restoration of the Los Angeles Water Supply System,” by T.H.P. Tabucchi and R.A. Davidson, 3/7/08 (PB2008-112237).

MCEER-08-0009 “Fragility Analysis of Water Supply Systems,” by A. Jacobson and M. Grigoriu, 3/10/08 (PB2009-105545).

MCEER-08-0010 “Experimental Investigation of Full-Scale Two-Story Steel Plate Shear Walls with Reduced Beam Section Connections,” by B. Qu, M. Bruneau, C-H. Lin and K-C. Tsai, 3/17/08 (PB2009-106368).

MCEER-08-0011 “Seismic Evaluation and Rehabilitation of Critical Components of Electrical Power Systems,” S. Ersoy, B. Feizi, A. Ashrafi and M. Ala Saadeghvaziri, 3/17/08 (PB2009-105546).

MCEER-08-0012 “Seismic Behavior and Design of Boundary Frame Members of Steel Plate Shear Walls,” by B. Qu and M. Bruneau, 4/26/08 . (PB2009-106744).

MCEER-08-0013 “Development and Appraisal of a Numerical Cyclic Loading Protocol for Quantifying Building System Performance,” by A. Filiatrault, A. Wanitkorkul and M. Constantinou, 4/27/08 (PB2009-107906).

MCEER-08-0014 “Structural and Nonstructural Earthquake Design: The Challenge of Integrating Specialty Areas in Designing Complex, Critical Facilities,” by W.J. Petak and D.J. Alesch, 4/30/08 (PB2009-107907).

MCEER-08-0015 “Seismic Performance Evaluation of Water Systems,” by Y. Wang and T.D. O’Rourke, 5/5/08 (PB2009-107908).

MCEER-08-0016 “Seismic Response Modeling of Water Supply Systems,” by P. Shi and T.D. O’Rourke, 5/5/08 (PB2009-107910).

MCEER-08-0017 “Numerical and Experimental Studies of Self-Centering Post-Tensioned Steel Frames,” by D. Wang and A. Filiatrault, 5/12/08 (PB2009-110479).

MCEER-08-0018 “Development, Implementation and Verification of Dynamic Analysis Models for Multi-Spherical Sliding Bearings,” by D.M. Fenz and M.C. Constantinou, 8/15/08 (PB2009-107911).

MCEER-08-0019 “Performance Assessment of Conventional and Base Isolated Nuclear Power Plants for Earthquake Blast Loadings,” by Y.N. Huang, A.S. Whittaker and N. Luco, 10/28/08 (PB2009-107912).

Page 242: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

204

MCEER-08-0020 “Remote Sensing for Resilient Multi-Hazard Disaster Response – Volume I: Introduction to Damage Assessment Methodologies,” by B.J. Adams and R.T. Eguchi, 11/17/08 (PB2010-102695).

MCEER-08-0021 “Remote Sensing for Resilient Multi-Hazard Disaster Response – Volume II: Counting the Number of

Collapsed Buildings Using an Object-Oriented Analysis: Case Study of the 2003 Bam Earthquake,” by L. Gusella, C.K. Huyck and B.J. Adams, 11/17/08 (PB2010-100925).

MCEER-08-0022 “Remote Sensing for Resilient Multi-Hazard Disaster Response – Volume III: Multi-Sensor Image Fusion

Techniques for Robust Neighborhood-Scale Urban Damage Assessment,” by B.J. Adams and A. McMillan, 11/17/08 (PB2010-100926).

MCEER-08-0023 “Remote Sensing for Resilient Multi-Hazard Disaster Response – Volume IV: A Study of Multi-Temporal

and Multi-Resolution SAR Imagery for Post-Katrina Flood Monitoring in New Orleans,” by A. McMillan, J.G. Morley, B.J. Adams and S. Chesworth, 11/17/08 (PB2010-100927).

MCEER-08-0024 “Remote Sensing for Resilient Multi-Hazard Disaster Response – Volume V: Integration of Remote Sensing

Imagery and VIEWSTM Field Data for Post-Hurricane Charley Building Damage Assessment,” by J.A. Womble, K. Mehta and B.J. Adams, 11/17/08 (PB2009-115532).

MCEER-08-0025 “Building Inventory Compilation for Disaster Management: Application of Remote Sensing and Statistical

Modeling,” by P. Sarabandi, A.S. Kiremidjian, R.T. Eguchi and B. J. Adams, 11/20/08 (PB2009-110484). MCEER-08-0026 “New Experimental Capabilities and Loading Protocols for Seismic Qualification and Fragility Assessment

of Nonstructural Systems,” by R. Retamales, G. Mosqueda, A. Filiatrault and A. Reinhorn, 11/24/08 (PB2009-110485).

MCEER-08-0027 “Effects of Heating and Load History on the Behavior of Lead-Rubber Bearings,” by I.V. Kalpakidis and

M.C. Constantinou, 12/1/08 (PB2009-115533). MCEER-08-0028 “Experimental and Analytical Investigation of Blast Performance of Seismically Resistant Bridge Piers,” by

S.Fujikura and M. Bruneau, 12/8/08 (PB2009-115534). MCEER-08-0029 “Evolutionary Methodology for Aseismic Decision Support,” by Y. Hu and G. Dargush, 12/15/08. MCEER-08-0030 “Development of a Steel Plate Shear Wall Bridge Pier System Conceived from a Multi-Hazard Perspective,”

by D. Keller and M. Bruneau, 12/19/08 (PB2010-102696). MCEER-09-0001 “Modal Analysis of Arbitrarily Damped Three-Dimensional Linear Structures Subjected to Seismic

Excitations,” by Y.L. Chu, J. Song and G.C. Lee, 1/31/09 (PB2010-100922). MCEER-09-0002 “Air-Blast Effects on Structural Shapes,” by G. Ballantyne, A.S. Whittaker, A.J. Aref and G.F. Dargush,

2/2/09 (PB2010-102697). MCEER-09-0003 “Water Supply Performance During Earthquakes and Extreme Events,” by A.L. Bonneau and T.D.

O’Rourke, 2/16/09 (PB2010-100923). MCEER-09-0004 “Generalized Linear (Mixed) Models of Post-Earthquake Ignitions,” by R.A. Davidson, 7/20/09 (PB2010-

102698). MCEER-09-0005 “Seismic Testing of a Full-Scale Two-Story Light-Frame Wood Building: NEESWood Benchmark Test,” by

I.P. Christovasilis, A. Filiatrault and A. Wanitkorkul, 7/22/09 (PB2012-102401). MCEER-09-0006 “IDARC2D Version 7.0: A Program for the Inelastic Damage Analysis of Structures,” by A.M. Reinhorn, H.

Roh, M. Sivaselvan, S.K. Kunnath, R.E. Valles, A. Madan, C. Li, R. Lobo and Y.J. Park, 7/28/09 (PB2010-103199).

MCEER-09-0007 “Enhancements to Hospital Resiliency: Improving Emergency Planning for and Response to Hurricanes,” by

D.B. Hess and L.A. Arendt, 7/30/09 (PB2010-100924).

Page 243: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

205

MCEER-09-0008 “Assessment of Base-Isolated Nuclear Structures for Design and Beyond-Design Basis Earthquake Shaking,” by Y.N. Huang, A.S. Whittaker, R.P. Kennedy and R.L. Mayes, 8/20/09 (PB2010-102699).

MCEER-09-0009 “Quantification of Disaster Resilience of Health Care Facilities,” by G.P. Cimellaro, C. Fumo, A.M Reinhorn

and M. Bruneau, 9/14/09 (PB2010-105384). MCEER-09-0010 “Performance-Based Assessment and Design of Squat Reinforced Concrete Shear Walls,” by C.K. Gulec and

A.S. Whittaker, 9/15/09 (PB2010-102700). MCEER-09-0011 “Proceedings of the Fourth US-Taiwan Bridge Engineering Workshop,” edited by W.P. Yen, J.J. Shen, T.M.

Lee and R.B. Zheng, 10/27/09 (PB2010-500009). MCEER-09-0012 “Proceedings of the Special International Workshop on Seismic Connection Details for Segmental Bridge

Construction,” edited by W. Phillip Yen and George C. Lee, 12/21/09 (PB2012-102402). MCEER-10-0001 “Direct Displacement Procedure for Performance-Based Seismic Design of Multistory Woodframe

Structures,” by W. Pang and D. Rosowsky, 4/26/10 (PB2012-102403). MCEER-10-0002 “Simplified Direct Displacement Design of Six-Story NEESWood Capstone Building and Pre-Test Seismic

Performance Assessment,” by W. Pang, D. Rosowsky, J. van de Lindt and S. Pei, 5/28/10 (PB2012-102404). MCEER-10-0003 “Integration of Seismic Protection Systems in Performance-Based Seismic Design of Woodframed

Structures,” by J.K. Shinde and M.D. Symans, 6/18/10 (PB2012-102405). MCEER-10-0004 “Modeling and Seismic Evaluation of Nonstructural Components: Testing Frame for Experimental

Evaluation of Suspended Ceiling Systems,” by A.M. Reinhorn, K.P. Ryu and G. Maddaloni, 6/30/10 (PB2012-102406).

MCEER-10-0005 “Analytical Development and Experimental Validation of a Structural-Fuse Bridge Pier Concept,” by S. El-

Bahey and M. Bruneau, 10/1/10 (PB2012-102407). MCEER-10-0006 “A Framework for Defining and Measuring Resilience at the Community Scale: The PEOPLES Resilience

Framework,” by C.S. Renschler, A.E. Frazier, L.A. Arendt, G.P. Cimellaro, A.M. Reinhorn and M. Bruneau, 10/8/10 (PB2012-102408).

MCEER-10-0007 “Impact of Horizontal Boundary Elements Design on Seismic Behavior of Steel Plate Shear Walls,” by R.

Purba and M. Bruneau, 11/14/10 (PB2012-102409). MCEER-10-0008 “Seismic Testing of a Full-Scale Mid-Rise Building: The NEESWood Capstone Test,” by S. Pei, J.W. van de

Lindt, S.E. Pryor, H. Shimizu, H. Isoda and D.R. Rammer, 12/1/10 (PB2012-102410). MCEER-10-0009 “Modeling the Effects of Detonations of High Explosives to Inform Blast-Resistant Design,” by P. Sherkar,

A.S. Whittaker and A.J. Aref, 12/1/10 (PB2012-102411). MCEER-10-0010 “L’Aquila Earthquake of April 6, 2009 in Italy: Rebuilding a Resilient City to Withstand Multiple Hazards,”

by G.P. Cimellaro, I.P. Christovasilis, A.M. Reinhorn, A. De Stefano and T. Kirova, 12/29/10. MCEER-11-0001 “Numerical and Experimental Investigation of the Seismic Response of Light-Frame Wood Structures,” by

I.P. Christovasilis and A. Filiatrault, 8/8/11 (PB2012-102412). MCEER-11-0002 “Seismic Design and Analysis of a Precast Segmental Concrete Bridge Model,” by M. Anagnostopoulou, A.

Filiatrault and A. Aref, 9/15/11. MCEER-11-0003 ‘Proceedings of the Workshop on Improving Earthquake Response of Substation Equipment,” Edited by

A.M. Reinhorn, 9/19/11 (PB2012-102413). MCEER-11-0004 “LRFD-Based Analysis and Design Procedures for Bridge Bearings and Seismic Isolators,” by M.C.

Constantinou, I. Kalpakidis, A. Filiatrault and R.A. Ecker Lay, 9/26/11.

Page 244: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

206

MCEER-11-0005 “Experimental Seismic Evaluation, Model Parameterization, and Effects of Cold-Formed Steel-Framed Gypsum Partition Walls on the Seismic Performance of an Essential Facility,” by R. Davies, R. Retamales, G. Mosqueda and A. Filiatrault, 10/12/11.

MCEER-11-0006 “Modeling and Seismic Performance Evaluation of High Voltage Transformers and Bushings,” by A.M. Reinhorn, K. Oikonomou, H. Roh, A. Schiff and L. Kempner, Jr., 10/3/11.

MCEER-11-0007 “Extreme Load Combinations: A Survey of State Bridge Engineers,” by G.C. Lee, Z. Liang, J.J. Shen and J.S. O’Connor, 10/14/11.

MCEER-12-0001 “Simplified Analysis Procedures in Support of Performance Based Seismic Design,” by Y.N. Huang and A.S. Whittaker.

MCEER-12-0002 “Seismic Protection of Electrical Transformer Bushing Systems by Stiffening Techniques,” by M. Koliou, A. Filiatrault, A.M. Reinhorn and N. Oliveto, 6/1/12.

MCEER-12-0003 “Post-Earthquake Bridge Inspection Guidelines,” by J.S. O’Connor and S. Alampalli, 6/8/12.

MCEER-12-0004 “Integrated Design Methodology for Isolated Floor Systems in Single-Degree-of-Freedom Structural Fuse Systems,” by S. Cui, M. Bruneau and M.C. Constantinou, 6/13/12.

MCEER-12-0005 “Characterizing the Rotational Components of Earthquake Ground Motion,” by D. Basu, A.S. Whittaker and M.C. Constantinou, 6/15/12.

MCEER-12-0006 “Bayesian Fragility for Nonstructural Systems,” by C.H. Lee and M.D. Grigoriu, 9/12/12.

MCEER-12-0007 “A Numerical Model for Capturing the In-Plane Seismic Response of Interior Metal Stud Partition Walls,” by R.L. Wood and T.C. Hutchinson, 9/12/12.

MCEER-12-0008 “Assessment of Floor Accelerations in Yielding Buildings,” by J.D. Wieser, G. Pekcan, A.E. Zaghi, A.M. Itani and E. Maragakis, 10/5/12.

MCEER-13-0001 “Experimental Seismic Study of Pressurized Fire Sprinkler Piping Systems,” by Y. Tian, A. Filiatrault and G. Mosqueda, 4/8/13.

MCEER-13-0002 “Enhancing Resource Coordination for Multi-Modal Evacuation Planning,” by D.B. Hess, B.W. Conley and C.M. Farrell, 2/8/13.

MCEER-13-0003 “Seismic Response of Base Isolated Buildings Considering Pounding to Moat Walls,” by A. Masroor and G. Mosqueda, 2/26/13.

MCEER-13-0004 “Seismic Response Control of Structures Using a Novel Adaptive Passive Negative Stiffness Device,” by D.T.R. Pasala, A.A. Sarlis, S. Nagarajaiah, A.M. Reinhorn, M.C. Constantinou and D.P. Taylor, 6/10/13.

MCEER-13-0005 “Negative Stiffness Device for Seismic Protection of Structures,” by A.A. Sarlis, D.T.R. Pasala, M.C. Constantinou, A.M. Reinhorn, S. Nagarajaiah and D.P. Taylor, 6/12/13.

MCEER-13-0006 “Emilia Earthquake of May 20, 2012 in Northern Italy: Rebuilding a Resilient Community to Withstand Multiple Hazards,” by G.P. Cimellaro, M. Chiriatti, A.M. Reinhorn and L. Tirca, June 30, 2013.

MCEER-13-0007 “Precast Concrete Segmental Components and Systems for Accelerated Bridge Construction in Seismic Regions,” by A.J. Aref, G.C. Lee, Y.C. Ou and P. Sideris, with contributions from K.C. Chang, S. Chen, A. Filiatrault and Y. Zhou, June 13, 2013.

MCEER-13-0008 “A Study of U.S. Bridge Failures (1980-2012),” by G.C. Lee, S.B. Mohan, C. Huang and B.N. Fard, June 15, 2013.

MCEER-13-0009 “Development of a Database Framework for Modeling Damaged Bridges,” by G.C. Lee, J.C. Qi and C. Huang, June 16, 2013.

Page 245: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

207

MCEER-13-0010 “Model of Triple Friction Pendulum Bearing for General Geometric and Frictional Parameters and for Uplift Conditions,” by A.A. Sarlis and M.C. Constantinou, July 1, 2013.

MCEER-13-0011 “Shake Table Testing of Triple Friction Pendulum Isolators under Extreme Conditions,” by A.A. Sarlis, M.C. Constantinou and A.M. Reinhorn, July 2, 2013.

MCEER-13-0012 “Theoretical Framework for the Development of MH-LRFD,” by G.C. Lee (coordinating author), H.A Capers, Jr., C. Huang, J.M. Kulicki, Z. Liang, T. Murphy, J.J.D. Shen, M. Shinozuka and P.W.H. Yen, July 31, 2013.

MCEER-13-0013 “Seismic Protection of Highway Bridges with Negative Stiffness Devices,” by N.K.A. Attary, M.D. Symans, S. Nagarajaiah, A.M. Reinhorn, M.C. Constantinou, A.A. Sarlis, D.T.R. Pasala, and D.P. Taylor, September3, 2014.

MCEER-14-0001 “Simplified Seismic Collapse Capacity-Based Evaluation and Design of Frame Buildings with and without Supplemental Damping Systems,” by M. Hamidia, A. Filiatrault, and A. Aref, May 19, 2014.

MCEER-14-0002 “Comprehensive Analytical Seismic Fragility of Fire Sprinkler Piping Systems,” by Siavash Soroushian, Emmanuel “Manos” Maragakis, Arash E. Zaghi, Alicia Echevarria, Yuan Tian and Andre Filiatrault, August 26, 2014.

MCEER-14-0003 “Hybrid Simulation of the Seismic Response of a Steel Moment Frame Building Structure through Collapse,” by M. Del Carpio Ramos, G. Mosqueda and D.G. Lignos, October 30, 2014.

MCEER-14-0004 “Blast and Seismic Resistant Concrete-Filled Double Skin Tubes and Modified Steel Jacketed Bridge Columns,” by P.P. Fouche and M. Bruneau, June 30, 2015.

MCEER-14-0005 “Seismic Performance of Steel Plate Shear Walls Considering Various Design Approaches,” by R. Purba and M. Bruneau, October 31, 2014.

MCEER-14-0006 “Air-Blast Effects on Civil Structures,” by Jinwon Shin, Andrew S. Whittaker, Amjad J. Aref and David Cormie, October 30, 2014.

MCEER-14-0007 “Seismic Performance Evaluation of Precast Girders with Field-Cast Ultra High Performance Concrete (UHPC) Connections,” by G.C. Lee, C. Huang, J. Song, and J. S. O’Connor, July 31, 2014.

MCEER-14-0008 “Post-Earthquake Fire Resistance of Ductile Concrete-Filled Double-Skin Tube Columns,” by Reza Imani, Gilberto Mosqueda and Michel Bruneau, December 1, 2014.

MCEER-14-0009 “Cyclic Inelastic Behavior of Concrete Filled Sandwich Panel Walls Subjected to In-Plane Flexure,” by Y. Alzeni and M. Bruneau, December 19, 2014.

MCEER-14-0010 “Analytical and Experimental Investigation of Self-Centering Steel Plate Shear Walls,” by D.M. Dowden and M. Bruneau, December 19, 2014.

MCEER-15-0001 “Seismic Analysis of Multi-story Unreinforced Masonry Buildings with Flexible Diaphragms,” by J. Aleman, G. Mosqueda and A.S. Whittaker, June 12, 2015.

MCEER-15-0002 “Site Response, Soil-Structure Interaction and Structure-Soil-Structure Interaction for Performance Assessment of Buildings and Nuclear Structures,” by C. Bolisetti and A.S. Whittaker, June 15, 2015.

MCEER-15-0003 “Stress Wave Attenuation in Solids for Mitigating Impulsive Loadings,” by R. Rafiee-Dehkharghani, A.J. Aref and G. Dargush, August 15, 2015.

MCEER-15-0004 “Computational, Analytical, and Experimental Modeling of Masonry Structures,” by K.M. Dolatshahi and A.J. Aref, November 16, 2015.

MCEER-15-0005 “Property Modification Factors for Seismic Isolators: Design Guidance for Buildings,” by W.J. McVitty and M.C. Constantinou, June 30, 2015.

Page 246: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

208

MCEER-15-0006 “Seismic Isolation of Nuclear Power Plants using Sliding Bearings,” by Manish Kumar, Andrew S. Whittaker and Michael C. Constantinou, December 27, 2015.

MCEER-15-0007 “Quintuple Friction Pendulum Isolator Behavior, Modeling and Validation,” by Donghun Lee and Michael C. Constantinou, December 28, 2015.

MCEER-15-0008 “Seismic Isolation of Nuclear Power Plants using Elastomeric Bearings,” by Manish Kumar, Andrew S. Whittaker and Michael C. Constantinou, December 29, 2015.

MCEER-16-0001 “Experimental, Numerical and Analytical Studies on the Seismic Response of Steel-Plate Concrete (SC) Composite Shear Walls,” by Siamak Epackachi and Andrew S. Whittaker, June 15, 2016.

MCEER-16-0002 “Seismic Demand in Columns of Steel Frames,” by Lisa Shrestha and Michel Bruneau, June 17, 2016.

MCEER-16-0003 “Development and Evaluation of Procedures for Analysis and Design of Buildings with Fluidic Self-Centering Systems” by Shoma Kitayama and Michael C. Constantinou, July 21, 2016.

MCEER-16-0004 “Real Time Control of Shake Tables for Nonlinear Hysteretic Systems,” by Ki Pung Ryu and Andrei M. Reinhorn, October 22, 2016.

MCEER-16-0006 “Seismic Isolation of High Voltage Electrical Power Transformers,” by Kostis Oikonomou, Michael C. Constantinou, Andrei M. Reinhorn and Leon Kemper, Jr., November 2, 2016.

MCEER-16-0007 “Open Space Damping System Theory and Experimental Validation,” by Erkan Polat and Michael C. Constantinou, December 13, 2016.

MCEER-16-0008 “Seismic Response of Low Aspect Ratio Reinforced Concrete Walls for Buildings and Safety-Related Nuclear Applications,” by Bismarck N. Luna and Andrew S. Whittaker.

MCEER-16-0009 “Buckling Restrained Braces Applications for Superstructure and Substructure Protection in Bridges,” by Xiaone Wei and Michel Bruneau, December 28, 2016.

MCEER-16-0010 “Procedures and Results of Assessment of Seismic Performance of Seismically Isolated Electrical Transformers with Due Consideration for Vertical Isolation and Vertical Ground Motion Effects,” by Shoma Kitayama, Michael C. Constantinou and Donghun Lee, December 31, 2016.

MCEER-17-0001 “Diagonal Tension Field Inclination Angle in Steel Plate Shear Walls,” by Yushan Fu, Fangbo Wang and Michel Bruneau, February 10, 2017.

MCEER-17-0002 “Behavior of Steel Plate Shear Walls Subjected to Long Duration Earthquakes,” by Ramla Qureshi and Michel Bruneau, September 1, 2017.

MCEER-17-0003 “Response of Steel-plate Concrete (SC) Wall Piers to Combined In-plane and Out-of-plane Seismic Loadings,” by Brian Terranova, Andrew S. Whittaker, Siamak Epackachi and Nebojsa Orbovic, July 17, 2017.

MCEER-17-0004 “Design of Reinforced Concrete Panels for Wind-borne Missile Impact,” by Brian Terranova, Andrew S. Whittaker and Len Schwer, July 18, 2017.

MCEER-17-0005 “A Simple Strategy for Dynamic Substructuring and its Application to Soil-Foundation-Structure Interaction,” by Aikaterini Stefanaki and Metttupalayam V. Sivaselvan, December 15, 2017.

MCEER-17-0006 “Dynamics of Cable Structures: Modeling and Applications,” by Nicholas D. Oliveto and Mettupalayam V. Sivaselvan, December 1, 2017.

MCEER-17-0007 “Development and Validation of a Combined Horizontal-Vertical Seismic Isolation System for High-Voltage-Power Transformers,” by Donghun Lee and Michael C. Constantinou, November 3, 2017.

Page 247: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

209

MCEER-18-0001 “Reduction of Seismic Acceleration Parameters for Temporary Bridge Design,” by Conor Stucki and Michel Bruneau, March 22, 2018.

MCEER-18-0002 “Seismic Response of Low Aspect Ratio Reinforced Concrete Walls,” by Bismarck N. Luna, Jonathan P. Rivera, Siamak Epackachi and Andrew S. Whittaker, April 21, 2018.

MCEER-18-0003 “Seismic Damage Assessment of Low Aspect Ratio Reinforced Concrete Shear Walls,” by Jonathan P. Rivera, Bismarck N. Luna and Andrew S. Whittaker, April 16, 2018.

MCEER-18-0004 “Seismic Performance Assessment of Seismically Isolated Buildings Designed by the Procedures of ASCE/ SEI 7,” by Shoma Kitayama and Michael C. Constantinou, April 14, 2018.

MCEER-19-0001 MCEER-19-0001 “Development and Validation of a Seismic Isolation System for Lightweight Residential Construction,” by Huseyin Cisalar and Michael C. Constantinou, March 24, 2019.

MCEER-20-0001 “A Multiscale Study of Reinforced Concrete Shear Walls Subjected to Elevated Temperatures,” by Alok Deshpande and Andrew S. Whittaker, June 26, 2020.

MCEER-20-0002 “Further Results on the Assessment of Performance of Seismically Isolated Electrical Transformers,” by Shoma Kitayama and Michael C. Constantinou, June 30, 2020.

Page 248: Further Results on the Assessment of Performance of ... · documented in numerous tables, may be used to decide on the benefits offered by a seismic isolation system depending on

ISSN 1520-295X

University at Buffalo, The State University of New York133A Ketter Hall | Buffalo, NY 14260

[email protected]; buffalo.edu/mceer

MCEER: Earthquake Engineering to Extreme Events